solution #7 - single door delayed egress single delayed egress … · alarm warning will also be...

1
NOTES: (1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 18-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED. (2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ON THIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE. (3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES. (4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION. (5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE. (6) DOOR POSITION SWITCHES SHOWN WITH THE DOOR CLOSED Solution #7 - Single Door Delayed Egress Delayed Egress Door Single Delayed Egress EMLock w/ Remote Annunciator Panel & Remote Bypass - - - Page 1 of ϭ - © Security Door Controls AC Mains (3) COND / 14 AWG FACTORY INSTALLED JUMPER (REMOVE ONLY IF FIRE ALARM INTERFACE IS CONNECTED) VOLTAGE SELECTION SWITCHES (SET FOR 24VDC) TO 120VAC PRIMARY VOLTAGE CONNECTION Battery Input Terminals DC Voltage Output Terminals 24 12 + - + - C 602RF (8) COND 1511S ExitCheck® w/ EA100 Exit Annunciator 602RF Power Supply (8) COND* *Single Lock Application (5) COND PROJECT NAME: DIST.: DWG. NO.: DRAWN BY: DATE: LOCATION.: CONTACT: SO NO.: REV TITLE: - 801 Avenida Acaso Camarillo, CA 93012 t 805.494.0622 ~ f 805.494.8861 www.sdcsecurity.com NOTE: ALL WIRING MUST BE REVIEWED AND APPROVED BY THE PROJECT ENGINEER ASSIGNED TO THE LOCATION FOR ITS CORRECTNESS AND SUITABILITY FOR THE APPLICATION IN WHICH THE EQUIPMENT IS INSTALLED AND OPERATED. ALL WIRING MUST CONFORM TO NATIONAL, STATE, AND LOCAL CODES FOR CLASS 2 FIRE PROTECTION AND CONTROL DEVICES. C NC - + - + NC NO NO C C NC NO C NO C NO C NO C NO C NC NO C NC [ BAS ] [ DPS ] [RESET] [RM TRIG] [REX] [RED RLY] [GRN RLY] [ LOCK ] [ FP ] [ PWR ] J6 J7 J2 [IBO] [EXT SPKR] UP DN COM UP DN COM UP DN COM UP DN COM A1 A3 A2 + - PWR RED YEL GRN RTN RED YEL GRN RTN RED YEL GRN RTN 1 2 3 4 RED YEL GRN RTN BLK RED GRN BLU ORG WHT GRN - SECURE YEL - ALARM RED - UNLOCKED OFF - BYPASS AUDIBLE SHUNT ACCESS ON OFF BLK – LED COM (-) GRN LED (+) RED LED (+) YEL YEL WHT WHT GRN - SECURE YEL - ALARM RED - UNLOCKED OFF - BYPASS Keep Closed To Unlock Close To Override Unlock Patient Protection System (Optional - By Others) To Patient Protection System (3) COND 1511S ExitCheck® Delayed Egress EMLock® EA100 TCC Control Panel 101-PAM PUSH UNTIL ALARM SOUNDS. DOOR CAN BE OPENED IN 15 SECONDS. Mechanical Latching Exit Device 101-PAM Annunciator Panel (Access/Bypass) TCC Series Desktop Console (Access/Bypass/Reset) REMOTE CONTROL DESK OPTIONS Method of Operation Door normally closed and secured with Delayed Egress unit and latching mechanical exit bar. Authorized Access – Access from outside not allowed. Authorized Egress – Desk personnel may allow authorized egress by pressing appropriate button on desk console or pressing Access button on 101-PAM wall plate. Unauthorized Egress – When an unauthorized egress is attempted, the Delayed Egress unit goes into alarm and announces warnings. Alarm warning will also be provided by siren in 101-PAM. The person attempting to exit is delayed for 15 seconds (or 30 seconds by AHJ) by the Delayed Egress unit. At end of 15 second period, the Delayed egress Emlock releases allowing person to exit by pressing exit bar push pad. The Delayed egress unit will continue to alarm until manually Reset. Fire/Emergency - Power supply to be connected the Fire/Emergency system to turn Off power supply and Unlock the Delayed Egress Emlock. Free egress allowed by pushing on exit bar pad.

Upload: others

Post on 15-May-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

NOTES:

(1) ALL LOW VOLTAGE SIGNAL WIRING SHALL BE 18-GAUGE MINIMUM. THE MINIMUM INDUCTIVE LOAD (LOCK) POWER WIRE GAUGE SHALL BE DETERMINED PER THE SDC WIRE GAUGE CHART. ALL WIRING (SINGLE OR MULTI-CONDUCTOR) SHALL BE COLOR CODED WITHOUT SPLICES. A MINIMUM OF TWO SPARE CONDUCTORS IS RECOMMENDED.

(2) SPECIFY VOLTAGE WHEN ORDERING PRODUCTS. VOLTAGE IS NOT SPECIFIED ONTHIS WIRE DIAGRAM, BE SURE ALL PRODUCTS ARE VOLTAGE COMPATIBLE.

(3) ALL WIRING MUST CONFORM TO NATIONAL, STATE AND LOCAL CODES.

(4) ALWAYS CONSULT WITH THE AUTHORITY HAVING JURISDICTION (AHJ) BEFORE INSTALLATION.

(5) WHERE REQUIRED BY CODE, CONNECT FAILSAFE SYSTEMS TO THE LOCAL FIRE LIFE SAFETY SYSTEM FOR EMERGENCY RELEASE.

(6) DOOR POSITION SWITCHES SHOWN WITH THE DOOR CLOSED

Solution #7 - Single Door Delayed Egress

Delayed Egress Door

Single Delayed Egress EMLock w/ Remote Annunciator Panel & Remote Bypass

- -- Page 1 of

-

© Security Door Controls

ACMains

(3) COND / 14 AWG

FACTORY INSTALLED JUMPER(REMOVE ONLY IF FIRE ALARM

INTERFACE IS CONNECTED)

VOLTAGE SELECTIONSWITCHES(SET FOR 24VDC)

TO 120VAC PRIMARYVOLTAGE CONNECTION

Battery InputTerminals

DC Voltage Output

Terminals

24 12

+ - + - C

602RF

(8) COND

1511SExitCheck® w/

EA100 Exit Annunciator

602RFPowerSupply

(8) COND**Single Lock Application

(5) COND

PROJECT NAME:

DIST.: DWG. NO.:DRAWN BY: DATE:LOCATION.: CONTACT:

SO NO.: REVTITLE:-801 Avenida Acaso

Camarillo, CA 93012t 805.494.0622 ~ f 805.494.8861www.sdcsecurity.com

NOTE: ALL WIRING MUST BE REVIEWED AND APPROVED BY THE PROJECT ENGINEER ASSIGNED TO THE LOCATION FOR ITS CORRECTNESS AND SUITABILITY FOR THE APPLICATION IN WHICH THE EQUIPMENT IS INSTALLED AND OPERATED. ALL WIRING MUST CONFORM TO NATIONAL, STATE, AND LOCAL CODES FOR CLASS 2 FIRE PROTECTION AND CONTROL DEVICES.

C NC- + - + NC NONO C C NC NO CNO C NO C NO C NO C NC NO C NC

[ BAS ][ DPS ][RESET][RM TRIG] [REX][RED RLY][GRN RLY][ LOCK ][ FP ][ PWR ]J6

J7

J2

[IBO][EXT SPKR]

UP

DNCOM

UP

DNCOM

UP

DNCOM

UP

DNCOM

A1

A3A2

+-PWR

RED

YELGRN

RTNRED

YELGRN

RTNRED

YELGRN

RTN

1234

RED

YELGRN

RTN

BLK

RED

GRN

BLUO

RG

WH

T

GRN - SECUREYEL - ALARM RED - UNLOCKED OFF - BYPASS

AUDIBLESHUNT

ACCESS

ONOFF

BLK – LED COM (-)GRN LED (+)RED LED (+)

YEL

YELWHT

WHT

GRN - SECUREYEL - ALARM RED - UNLOCKED OFF - BYPASS

Keep Closed

To Unlock

CloseTo

OverrideUnlock

PatientProtection

System(Optional - By Others)

To Patient Protection

System(3) COND

1511S ExitCheck® Delayed Egress EMLock®

EA100

TCC Control Panel

101-PAM

PUSH UNTIL ALARMSOUNDS. DOOR CAN BEOPENED IN 15 SECONDS.

MechanicalLatching Exit Device

101-PAMAnnunciator

Panel(Access/Bypass)

TCC SeriesDesktopConsole

(Access/Bypass/Reset)

REMOTE CONTROL DESK OPTIONS

Method of OperationDoor normally closed and secured with Delayed Egress unit and latching mechanical exit bar.Authorized Access – Access from outside not allowed.Authorized Egress – Desk personnel may allow authorized egress by pressing appropriate button on desk console or pressing Access button on 101-PAM wall plate.Unauthorized Egress – When an unauthorized egress is attempted, the Delayed Egress unit goes into alarm and announces warnings. Alarm warning will also be provided by siren in 101-PAM. The person attempting to exit is delayed for 15 seconds (or 30 seconds by AHJ) by the Delayed Egress unit. At end of 15 second period, the Delayed egress Emlock releases allowing person to exit by pressing exit bar push pad. The Delayed egress unit will continue to alarm until manually Reset.Fire/Emergency - Power supply to be connected the Fire/Emergency system to turn Off power supply and Unlock the Delayed Egress Emlock. Free egress allowed by pushing on exit bar pad.