solair guidelines en

Upload: mihailo-filipovic-jelic

Post on 07-Aug-2018

227 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/20/2019 SOLAIR Guidelines En

    1/100

     

    Requirements on the design

    and configuration of small and medium sized

    solar air‐conditioning applications

    Guidelines

  • 8/20/2019 SOLAIR Guidelines En

    2/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    2

  • 8/20/2019 SOLAIR Guidelines En

    3/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    3

    Guidelines

    This publication has been produced in the framework of the

    SOLAIR project which is supported by the Intelligent Energy –

    Europe programme of the European Commission.SOLAIR aims mainly at capacity building, promotion and

    influencing the process of decision making for the

    implementation of small and medium‐sized solar air‐

    conditioning (SAC) systems in order to increase the

    confidence on the technology and to encourage its

    implementation.

    April 15, 2009

    www.solair‐project.eu

  • 8/20/2019 SOLAIR Guidelines En

    4/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    4

    This report was prepared as deliverable D10 in the SOLAIR project on base of material and

    information provided by all partners in the project.

    Edited by Edo Wiemken, Fraunhofer ISE. Chapter one – Building cooling and air‐conditioning –

    was prepared by Sašo Medved, University of Ljubljana, Slovenia. Chapter seven – Planning tools –

    was prepared by Maria João Carvalho, INETI, Portugal.

    SOLAIR is co‐ordinated by

    •  target GmbH, Germany

    Partners in the SOLAIR consortium:

    •  AEE – Institute for Sustainable Technologies, Austria•  Fraunhofer Institute for Solar Energy Systems ISE, Germany•  Instituto Nacional de Engenharia, Technologia e Innovação INETI, Portugal•  Politecnico di Milano, Italy

    •  University of Ljubljana, Slovenia•  AIGUASOL, Spain•  TECSOL, France•  Federation of European Heating and Air‐conditioning Associations RHEVA, The Netherlands•  Centre for Renewable Energy Sources CRES, Greece•  Ente Vasco de la Energia EVE, Spain•  Provincia di Lecce, Italy•  Ambiente Italia, Italy

    0

    SOLAIR is supported by

    The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinionof the European Communities. The European Commission is not responsible for any use that may be made of the

    information contained therein

  • 8/20/2019 SOLAIR Guidelines En

    5/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    5

    Table of content

    Introduction.................................................................................................................................7

    1 Building cooling and air‐conditioning..............................................................................9

    1.1 Indoor thermal comfort ....................................................................................................9

    1.2 Cooling demand of buildings ..........................................................................................13

    1.3 Energy conservation principles .......................................................................................18

    1.4 Fundamentals of solar cooling ........................................................................................22

    1.5 Impact of climate changes on thermal indoor comfort

    and energy demand for cooling......................................................................................23

    2 Technologies applicable for solar thermally driven cooling ...........................................1

    2.1 Chilled water systems .....................................................................................................29

    2.2 Open cycle processes......................................................................................................37

    2.3 Solar thermal collectors ..................................................................................................40

    3 General requirements on solar air‐conditioning and cooling systems.........................46

    3.1 Primary energy saving.....................................................................................................46

    3.2 Requirements on basic system layout ............................................................................50

    3.3 Heat rejection system .....................................................................................................52

    3.4 Solar collector system.....................................................................................................54

    4 Selection of the appropriate technology.......................................................................60

    4.1 All air systems .................................................................................................................62

    4.2 Full air system + chilled water distribution.....................................................................66

    4.3 Supply air system + chilled water distribution................................................................684.4 All water system..............................................................................................................69

    5 Small systems: schemes for typical applications ..........................................................71

    6 Recommendations on monitoring and quality assurance ............................................77

    7 Planning tools .................................................................................................................84

    7.1 Design approaches..........................................................................................................84

    7.2 Rules of Thumb ...............................................................................................................85

    7.3 Simple pre‐design tools...................................................................................................87

    7.3.1 SHC‐Softwaretool (NEGST Project) .................................................................................87

    7.3.2 SACE Solar cooling evaluation light tool .........................................................................89

    7.3.3 SolAC – Solar Assisted Air Conditioning Software...........................................................90

    7.3.4 ODIRSOL – Solar Assisted cooling Software....................................................................92

    7.3.5 Expected new pre‐design tools.......................................................................................93

    7.4 Detailed simulation tools ................................................................................................94

    7.4.1 System orientated...........................................................................................................94

    7.4.2 Building orientated .........................................................................................................95

    7.4.3 Further simulation tool description ................................................................................96

  • 8/20/2019 SOLAIR Guidelines En

    6/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    6

  • 8/20/2019 SOLAIR Guidelines En

    7/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    7

    Introduction

    The demand for building cooling and air‐conditioning is still rapidly increasing. To give an

    impression: the sales rate in 2008 for small size electrically driven room air conditioners (< 5 kW

    chilling capacity) was approx. 82 million units worldwide, of which 8.6 million were sold in Europe.

    It is not surprising that in some areas the peak load in the public electricity grid is evoked during

    hot summer seasons already by electrically driven air‐conditioning. In Germany, a country with

    definitely not the highest demand for cooling and air‐conditioning, the overall electricity demand

    for building air‐conditioning in 2006 was estimated to approx. 5% of the total electricity

    consumption (14% for the total of air‐conditioning and refrigeration); in other South European

    countries this share might be far higher.

    Building air‐conditioning is today based mainly on electrically driven mechanic vapour

    compression technologies. Although for new developed, predominantly large capacity scale

    developments it is reported about high efficiencies in the compression cycle, for the standard of

    air‐conditioning in existing buildings it can be assumed that on an average less than 3 kWh ‘cold’

    are produced with the electricity input of 1 kWhel. Subsequently this implies that approximately

    1 kWh primary energy is used for the provision of 1 kWh useful ‘cold’.

    At the same time of peak cooling demand, high amounts of solar radiation are available at many

    sites and could be used for thermally driven processes, e.g., cooling and air ‐conditioning. The

    processes are in general well known and not new. Thermally driven cooling was applied within the

    last decades in niche‐markets preferably in the large capacity range, using waste heat or heat

    from combined heat and power production. However, the combination of this technology with

    solar heat is new and some more complexity arises with this combination. Solar cooling and air‐

    conditioning is demonstrated in a few hundred installations so far.

    Solar thermally assisted cooling and air‐conditioning can contribute to an environmentally friendly

    building supply system for the following reasons:

    •  considerable savings in primary energy consumption and reduction of CO2  emissions arepossible

    •  load relieving of the public electricity grid in terms of both, peak power and energy, thuscontributing to grid stabilisation

    •  combined use of solar heat for heating, cooling and domestic hot water preparation, thus anall‐season high utilisation of the solar thermal system

    •  no use of working materials with high global warming potential•  less noise emissions and less vibrations than vapour compression technologies.

    Thus, support for the market development of this technology is useful; these guidelines, edited in

    the frame of the SOLAIR1 project, is one of the supporting activities.

    1 SOLAIR ‐ Increasing the market implementation of solar air  ‐conditioning systems for small and medium applications inresidential and commercial buildings (SOLAIR). Supported in the Intelligent Energy Europe Programme of the European

    Commission. EIE/06/034/S12.446612. Duration: until 12/2009.www.solair ‐ project.eu 

  • 8/20/2019 SOLAIR Guidelines En

    8/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    8

    Interaction in the design and layout of a solar thermally driven cooling and air  ‐conditioning system, to be considered in

    the planning phase.

    The proper design of a solar cooling and air‐conditioning system and the choice of the

    components interact to a high degree with the site conditions (climatic conditions) and with thedemand for cooling (load conditions). The intention of this guideline is to support the

    understanding of the interactions and to provide in parallel a picture on the state of the art of

    solar cooling and air‐conditioning.

    As one of the most cost‐effective measures in the planning of an air‐conditioning system is the

    reduction of cooling loads already in the building planning and design phase, chapter one deals

    with general aspects on building cooling and air‐conditioning and prepares the reader for the

    subsequent chapters, focusing on the technical aspects of solar thermally driven technologies.

    However, some aspects of solar cooling and air‐conditioning may have found not the adequate

    attendance in these guidelines, such as e.g. more details on system control or on detailed site

    oriented installation information. The reason for this lack is the still ongoing process in the

    development and preparation of such information.The thematic structure of the content underlines the target group of technical orientated

    planners in the building services and utilities management area, but the guidelines are hopefully

    useful to anyone, interested on this subject.

    Finally, a more comprehensive description of solar cooling and air‐conditioning can be found in

    the handbook for planners ‘Solar Assisted Air‐Conditioning in Buildings’2, elaborated in the Task

    25 on Solar Cooling within the Solar Heating and Cooling Programme (SHC) of the International

    Energy Agency (IEA). In the current Task 38 ‘Solar Air‐Conditioning and Refrigeration’, a new

    edition of this handbook will be launched and available in 2010. In the context with the existing

    handbook, these guidelines may be seen in both ways: as a straightforward introduction into solar

    cooling and air‐conditioning on the one hand, and as a market and practically oriented

    complement to the handbook on the other hand.

    2 Hans ‐Martin Henning (Editor): Solar Assisted Air ‐Conditioning of Buildings – A Handbook for Planners. Second revised

    edition 2007. ISBN 978‐3‐211‐73095‐9, Springer Wien New York.

  • 8/20/2019 SOLAIR Guidelines En

    9/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    9

    1 Building cooling and air‐conditioning

    The main goal of every building planner is to assure the most pleasant and healthy living

    environment to people that live in the building. However the challenge here is to attain the

    optimal indoor comfort with minimal energy consumption and minimal environmental impact.

    From the engineering point of view the quality of indoor environment is defined by four groups of

    requirements: thermal comfort, indoor air quality, lighting comfort and noise protection.

    Concerning energy consumption the most important issue is fulfilling of thermal comfort

    requirements.

    Figure 1.1 Indoor environment quality could be assured by fulfilling of four groups of requirements

    1.1 Indoor thermal comfort

    Human is a warm‐blooded being with constant internal temperature (37 ± 0.8°C), which isindependent of surrounding temperature and muscle activity. The body produces heat in internal

    organs with combustion (oxidation) of nutritive substances. This process is called metabolism or

    basal metabolism. Metabolism is regulated by our body regarding to momentarily activity. Similar

    as with heat machines, the human body has to give off the excess heat to the environment by

    means of different heat transfer mechanisms. If such heat transfer from our body to surroundings

    does not cause any unpleasant sensation the requirements of thermal comfort are fulfilled.

    Thermal confort

    Lighting confort

    Indoor air qualityIAQ

    Noise protection

    IEQ

  • 8/20/2019 SOLAIR Guidelines En

    10/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    10

    Figure 1.2 Human body emits sensible and latent heat into environment using different heat transfer processes. If this

     process does not cause unpleasant sensation the thermal comfort is provided.The body emits the heat in the form of sensible and latent heat. Sensible heat is emitted with convection and radiation

    of the body to the surrounding air and surfaces, conduction of heat on the places where we stand and with exhaling the

    warm air. Latent heat is given off to surroundings with diffusion of vapour trough the skin, evaporation of water on the

    skin surface and humidifying the exhaled air.

    air temperature (oC)

       h  e  a   t   f   l  u  x   (   W   )

     

    Figure 1.3 Heat transfer mechanisms and heat flux emitted by human body to surroundings depends on air temperature

    and humidity ‐  at low temperatures radiation and convection are the most important mechanisms, meanwhile at air

    temperatures above 30°C latent heat transfer is dominant, emitted amounts of water vapour as function of air

    temperature are presented as well.

    1.1.1 Parameters of indoor thermal comfort

    The importance of individual heat transfer mechanisms is varying with regard to the state of

    indoor environment which is evaluated with several parameters: air temperature, mean radiant

    temperature of surrounding surfaces, air velocity and air humidity. Because the amount of heat

    that the body gives off depends on the difficulty of the work and on the clothes we are wearing,

    the activity level, which is given in “met” (metabolism) and clothing which is given in “clo” (cloth)

    are two very important additional parameters that affect thermal comfort. 1 Met corresponds

    with 58 W released by 1 m2 of human surface area or approximately 100 W in total. During heavy

    work metabolic rate can reach up to 10 Met and this corresponds to emitted heat flux of 270 W.

  • 8/20/2019 SOLAIR Guidelines En

    11/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    11

    Clo is proportional to thermal resistant of cloths. Characteristic values are 0 clo for a nude body, 1

    clo for a business suit and 3 clo for winter clothes.

    Indoor air temperature Ti   is the most evident indicator of proper thermal comfort. In principle,

    the temperature should be higher on lower activity level and lighter clothing. For building cooling

    it is important that our body is capable to adapt to the seasonal conditions. Thus the appropriateindoor temperatures are between 20 and 22

    oC in the winter and 26 to 27

    oC in the summer time

    when ambient temperature is above 30°C.

    Mean radiant temperature Tr is mean temperature of the surfaces that surround the living space.

    It has a strong influence on radiative heat transfer between human body and surroundings. The

    difference between the indoor air temperature Ti and mean radiant temperature Tr should not be

    greater than 2K. During the summer, the indoor surfaces or internal window blinds exposed to the

    solar radiation can warm up to 50 and more °C, which can be disturbing. Bright coloured or

    reflective external window blinds are a good solution for decreasing the mean radiant

    temperature.

    The air velocity  in the room affects the convective heat losses and evaporation of water, which

    we are excreting trough the skin and sweat glands. During the heating season our body feel as

    unpleasant velocities above 0.15 m/s, meanwhile in the summer time we have no comfort

    problems with higher velocities up to 0.6 or even 0.8 m/s. For example, we can increase the air

    flow around our bodies with a ceiling fan and it results as feeling the environment around us

    being cooler.

    Air humidity affects the latent heat transfer from the bodies to the surrounding air. Therefore in

    case of higher temperatures the humidity level has to be lower. Air humidity in the buildings is

    varying because of air conditioning and different sources of water vapour in living spaces (human,

    plants, cooking, etc.). The air humidity can be given as moisture content of air x, which is definedwith the ratio of water vapour mass (in g or kg) added to the mass of one kilogram of dry air

    (typical values are between 5 to 20 g/kg) or as relative humidity  which is defined as ration

    between actual water vapour pressure and water vapour pressure in saturated air at the same

    temperature. Values are quoted in percents in range between 0% in dry air and 100% in air

    saturated with water vapour. At the air temperature Ti between 20 ‐ 26°C air humidity should

    be 70 to 35%, or the moisture content x should not exceed 11.5 g/kg. In practice the air humidity

    could be reduced by cooling the air beyond its dew point with cooling devices in the rooms or

    with central air conditioning units. In both cases dehumidification increase the electricity

    consumption, unless thermally driven cooling engines are used instead of compressor driven

    cooling systems.

    1.1.2 Integrated indicators of thermal comfort

    Joint influence of the thermal comfort parameters could be evaluated with the predicted main

    vote PMV indicator. PMV is an agreed relative assessment scale of thermal comfort in indoor

    environment. The values of PMV are in the range between ‐3 (cold), ‐2 (moderately cold), ‐1

    (pleasantly cold), 0 (neutral), +1 (pleasantly warm), +2 (warm) and +3 (hot environment). The

    value PMV equal to 0 therefore means neutral environment, positive values mean warmer

    environment, negative values mean colder environment. The PMV value is established by a

    mathematical expression or based on measurements of thermal comfort parameters and

    considering the activity and clothing of the occupancies. The predicted mean vote can be related

    to percentage of dissatisfied people (PPD), which tells us the percent of dissatisfied people in

    observed room.

  • 8/20/2019 SOLAIR Guidelines En

    12/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    12

    Figure 1.4 Instrument for determination of predicted mean vote of indoor environment (PMV); sensor for temperature,

    velocity and humidity measurements, knobs for Met and Clo input.

    Figure 1.5 Instrument Correlation between PMV and PPD values. According to the graph at PMV +2 80% of people will

    be dissatisfied with their thermal environment. Source: [EN ISO 7730, 2005]

    The demands concerning the indoor thermal environment are defined in many international and

    national standards and regulations. Thus EN 15251 standard defines three levels of comfort

    expectations: class A (high expectations), class B(normal expectations) and class C (moderate

    expectations). For class A the PMV must be ± 0.2 (corresponds with PPD < 6%), for class B ± 0.5(PPD < 10%) and for class C ± 0.7 (PPD < 15%). EN ISO 7730 defines thermal comfort as acceptable

    if 80% or more inhabitants feel comfortable in such indoor environment.

    As cooling of buildings is closely related to indoor air temperatures and humidity some other

    comfort indicators could be used as well. Humid operative temperature is the temperature of the

    environment with 100% relative humidity in which a human body emits the same total amount of

    heat as in real environment. The heat stress index is the ratio of the total evaporative heat losses

    of human body required for thermal comfort and maximum evaporative heat losses possible in

    the same environment multiplied by factor 100. The decimal value of heat stress index is called

    skin wettedness.

  • 8/20/2019 SOLAIR Guidelines En

    13/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    13

    1.2 Cooling demand of buildings

    1.2.1 Conventional or mechanical cooling

    Most of the buildings today are cooled with mechanical cooling or air conditioning systems. In

    both cases a cooling machine is needed. Usually, this is a heat pump which pumps the heat out of

    the cooler building to the warmer surrounding of the building. In cases of smaller systems(compact cooling units) the air is directly cooled in the evaporator of the cooling unit placed in the

    room. When dealing with larger buildings central air or water cooling systems are commonly

    used. In case of air cooling systems the air in the air‐conditioning device is cooled with chilled

    water before delivered into the building. In water cooling systems water with temperature

    between 5° to 7°C is pumped through chilled water pipe distribution systems to the end heat

    exchangers (e.g. fan‐coils) installed in each indoor space.

    Figure 1.6 Fan‐coil units with coil heat exchanger and fans are end heat exchangers in central water cooling systems.

    During operation the cooling machine consumes electricity. Because it is working as a heat pump,

    the amount of heat transferred out of the building is significantly larger than the amount of used

    electric energy. The ratio between the heat extract out of the building Qc and the electric energy

    demand W is named coefficient of performance (COPel). Modern cooling units have COPel 

    between 3 and 5 depending on the cooling power and the type of compressor. In spite of highCOPel, these cooling devices still use electricity which is in many countries produced with high

    emissions of greenhouse gasses. An increased consumption of electricity is characteristic for all

    “modern” societies. In Europe the consumption of electricity has increased by a factor 12 within

    the last 50 years. Today the yearly increase of electricity consumption is twice as high as the

    increase of fossil fuel consumption. Building cooling systems also have a high factor of

    simultaneity, which consequently leads to electricity network overload. In Slovenia for example

    the peak electricity demand has changed from 19 PM in the winter time to 15 PM in the summer

    time in last three years indicating increased electricity demand for cooling of the buildings.

  • 8/20/2019 SOLAIR Guidelines En

    14/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    14

    Figure 1.7  Air handling unit of central air conditioning system; air is cooled with chilled water provided by cooling

    engine.

    Figure 1.8 Cooling machines operates as a heat pump, therefore heat transferred from buildings to the environment islarger than consumption of electricity. The ratio is called coefficient of performance or COPel . Modern cooling units have

    COPel  between 3 and 5.

    Building heat

    COPelelectricity coefficient of

    performance

    Q   kWhc    hCOP el    W    kWh

    e

    =

     

    Compressor

    Environment

    Qc W

    Qod 

  • 8/20/2019 SOLAIR Guidelines En

    15/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    15

    1.2.2 Cooling loads and energy demand for cooling of the buildings

    Cooling loads and energy demand can be calculated using different approaches. In engineering

    practice VDI 2078 and ASHRAE calculation procedures are often used. Regardless to the method

    the first step in buildings cooling analyses is the determination of heat gains. Heat gains  are

    divided into sensible and latent heat gains. Sensible heat gains are originated by:

    •  solar radiation and heat transfer through windows•  unsteady heat transfer through opaque building envelopment•  internal heat gains (human, lighting, appliances,..)•  heat transfer by air exchange between surrounding and building because of infiltration and

    ventilation

    Heat gains through windows and transparent walls can be characterized by several optical

    parameters:

    •  transmittivity of solar radiation t•  total energy transmittivity g•  shading factor of shading devices Sf

    Transmissivity of solar radiation is the ratio between transmitted and incoming solar radiation.

    Since part of solar radiation is absorbed in glazing, radiation and convection heat flux from the

    inner glass layer into the interior represent additional heat gains. The sum of heat gains can be

    expressed by g‐value as the ratio between sum of solar radiation and heat flux gains and incoming

    solar radiation on window surface. The g‐value is the most adequate window characteristic for

    cooling load determination. Cooling loads through transparent building envelopment could be

    significantly reduced by selection of effective shading devices.

    Gi

    Gτ =

     

    skGi q qgG

    + +=

     

    G'S

    G=  

    Figure 1.9 Transmissivity of glazing is the ratio between transmitted (Gi) and incoming solar radiation (G) (left); total

    energy transmissivity g of glazing is the ratio between sum of transmitted solar radiation and heat flux transferred from

    inner glass surface by radiation and convection (Gi + qk+qs) and incoming solar radiation G. (middle); shading factor Sf

    of shadings is the ratio between transmitted solar radiation G’ and incoming solar radiation G (right)

  • 8/20/2019 SOLAIR Guidelines En

    16/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    16

    Heat gains through opaque building envelopment depends on absorbed solar radiation (wall

    orientation and wall surface colour), thermal conductivity of wall materials and heat accumulation

    of the wall. Heat gains can be calculated by hour‐to‐hour analyses of steady heat transfer

    replacing air temperature differences with reference temperature difference as it is proposed in

    VDI 2078. Since contemporary building envelope elements have low a heat transfer coefficient,

    heat gains through opaque elements are in most cases small.Internal heat gains are often major reason for overheating. The human body itself emits a heat

    flux between 100 W and 250 W in condition of heavy activity. Large number of appliances

    characterized for commercial buildings contribute to large internal heat gains as well. Good

    daylighting design and use of high efficient compact and LED lamps can significantly reduce the

    internal cooling loads.

    Contemporary buildings are sufficiently tight to prevent significant infiltration of ambient air into

    the building. Nevertheless they must be ventilated to ensure good indoor air quality. Mechanical

    ventilation must be regulated according to demand to ensure lower cooling load with supply air.

    Latent heat gains are in general generated in buildings because of different water vapour sources,

    nevertheless in humid regions supply external air must be dehumidified before supplied to the

    buildings. For example, a human body emits up to 50 g of water vapour per hour, plants up to 20g per day.

    Cooling load  indicates heat flux (removed rate of energy) needed for fulfilling requirements of

    thermal comfort especially regarding to indoor air temperature and humidity. Time dependant

    heat gains and cooling loads differ by amplitude and time shift because of heat accumulation in

    building constructions. Cooling loads are calculated for a climate dependant hot summer design

    day and the daily maximum value is taken as design cooling load of the building. More advanced

    methods are based on hour‐by‐hour analyses using a computer tool, among others TRNSYS is very

    well known. In such tools, a Test Reference Year as meteorological data source is used for specific

    locations. The software Meteonorm (CD published by James & James, UK) includes TRY for more

    than 5000 location world wide. Such tools are most useful for the calculation of energy demand

    for cooling  which taks into account hour‐

    by‐

    hour cooling load, COPel  of cooling machine andoverall cooling system efficiency.

    Detailed descriptions of planning tools are presented in Chapter 7. 

    Important note:

    The Energy Performance of Buildings Directive (EPBD) requests that the energy demand for

    cooling must be included into buildings energy performance indicators. As a consequence, in

    some national regulations the rated power of cooling machines is limited. In Slovenia, for

    example the permitted power of the cooling machine is 24 W per m3 of building volume.  

  • 8/20/2019 SOLAIR Guidelines En

    17/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    17

    1.2.3. Study cases

    As an example of computer simulation approaches, annual specific cooling loads and energy

    (electricity) demand for four business buildings are presented below. All buildings are built at

    locations with continental climate.

    Cooling

    load

    (W/m3)

    Cooling

    load

    (W/m2)

    Useful

    energy

    demand

    (heat)

    (kWh/m2)

    End energy

    demand

    (electricity)

    (kWh/m2)

    Office

    building 1

    7.7 21 8 3.4

    Office

    building 2

    31 84 51 18.7

    Office

    building 3

    14 38 29 10.6

    Shopping

    centre

    21.6 76 58 19.2

    Tabel 1.1 Specific cooling loads and energy demand of four business buildings

    Remark: useful energy is related to quantity of heat extracted from indoor air, end energy

    demand is related to electricity demand of mechanical cooling.

  • 8/20/2019 SOLAIR Guidelines En

    18/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    18

    1.3 Energy conservation principles

    The energy demand for cooling of buildings can be reduced by implementation of five principles

    presented on Figure 1.10: solar radiation controlling, reduction of heat gains thought opaque

    building envelope, intensive night ventilation, reduction of internal gains and implementation offree cooling techniques.

    Figure 1.10 Principles of energy conservation for buildings cooling. Source [McQuiston et al., 2005]

    Shading devices must be external, high reflective for solar radiation and mounted in such a way

    that enables convective cooling as well as daylighting of the interior. Figure 1.11 shows the

    temperature profile in an office without shadings and mechanical cooling and in the neighbouring

    office with external shadings; shading devices are installed in such a way that convective cooling is

    enabled on both sides of shadings and they are movable to improve shading factor Sf   all day long

    and enable optimal daylighting in offices.

    18

    23

    28

    33

    38

    43

    48

    3984 4152 4320 4488 4656 4824 4992 5160

    Dan v letu

       T  e  m  p  e  r  a   t  u  r  a  p  r  o  s   t  o  r  a  v   t  r  e   t   j  e  m   n

      a   d  s   t  r  o  p   j  u   (  o   C   )

    Brez senčil in haljenja

    Zunanja lamelna senčila, nehlajen prostor 

    Without shadings

    With shadings

    Hour starting 1st of January

       R  o  o  m

       t  e  m  p  e  r  a   t  u  r  e   (   °   C   )

     

    Figure 1.11 Only external, high reflective and movable shading devices controls successfully solar radiation heat gains;temperature in an office without shadings and cooling (gray line), and temperatures in office equipped with external

    shadings as presented on photo (orange line).

  • 8/20/2019 SOLAIR Guidelines En

    19/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    19

    Shading devices could be multi purpose. For example PV modules can be used as external shading

    device. Following example shows such a case. PV modules are mounted on the part of glass roof

    of atrium in office building. The result is the reduction of the peak cooling load from 150 kW to 75

    kW, meanwhile the heating load remains practically unchanged. In this particular case PV

    shadings have little influence on daylighting as well.

    -100

    -50

    0

    50

    100

    150

    200

    Jan. Feb. Mar. Apr. Maj Jun. Jul. Aug. Sept. Okt. Nov. Dec.

        [   k   W   ]

    heating load

    cooling load

    -100

    -50

    0

    50

    100

    150

    200

    Jan. Feb. Mar. Apr. Maj Jun. Jul. Aug. Sept. Okt. Nov. Dec.

        [   k   W

       ]

    heating load

    cooling load

     

    Figure 1.12 PV modules as external shading devices on the glass roof of an atrium in office buildings reduce peak cooling

    load by 50% meanwhile heating demand and daylighting remain practically unchanged (left heating and cooling loadswithout PV modules, right after PV modules were installed)

    Heat gains through the opaque envelope could be reduced with light surface colours and quality

    thermal insulation in combination with a high building construction thermal mass. As a

    consequence, a significant decrease of temperature amplitude swing at the inner side of the

    construction and a time lag of several hours can be attained. Modern architecture often requires

    dark surface colours of walls and roofs. Selective paints can be used in this case to reduce both,

    surface temperature and resulting cooling loads. Such colours have equal reflectivity of light as

    ordinary colours, but enlarged near IR reflectivity. This causes a reduction of dark surface

    temperature during solar noon by 20°C. Even more effective are green roofs and walls.

    Evapotranspiration by grass and plants reduce cooling loads for 5 to 10 times regarding to darkroofs.

  • 8/20/2019 SOLAIR Guidelines En

    20/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    20

    Figure 1.13  Additional selective white paint layer (left) pained below green coating (right) reduces peak wall surface

    temperature up to 15 K

    Night ventilation can significantly reduce cooling loads but only in case if intensive night

    ventilation with at least 4 to 5 exchanges of building volume per hour is provided. On the other

    hand ventilation systems can be supplemented by free cooling techniques like evaporative

    cooling. Evaporative cooling is most effective in hot and dry areas. It can significantly contribute

    to cooling power reduction and therefore to the peak electricity demand for mechanical cooling.

    COPel of such systems are 50 or more.

    8

    10

    12

    14

    16

    18

    20

    22

    24

    26

    28

    30

    32

    34

    0 300 600 900 1200 1500 1800 2100

    number of hours per year (h)

      s  u  p  p

       l  y  a   i  r   t  e  m  e  p  r  a   t  u  r  e   (   °   C   )

    T ambient

    T afterevaporativecooling

     

    Figure 1.14 Evaporative cooling is most effective at high ambient temperature at solar noon; duration of ambient air

    and supply air temperatures after evaporative cooling (left); evaporative cooling can significantly contribute to cooling

     power reduction and peak electricity demand additional for mechanical cooling. Source: [Vidrih, Medved, 2006]

  • 8/20/2019 SOLAIR Guidelines En

    21/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    21

    15

    17

    19

    21

    23

    25

    27

    29

    31

    0 12 24 36 48 60 72 84 96Time (h)

       T  e  m  p  e  r  a   t  u  r  e   (   °   C   )

    Ta (LHTES inlet temperature)

    To (measured)

    To (numerical model)

     

    Figure 1.15 Latent heat storage integrated into ventilation system are cooled down during the night and provide lower

    supply air temperatures during the next summer day; such system can be combined with other free cooling systems to

     provide all day free cooling operation. Source: [Arkar, Medved, 2007]

    Ground heat exchangers can be coupled to mechanical ventilation systems for pre‐cooling of

    ventilation air during the daytime in summer days. They are used in smaller buildings, and they

    have to be planned very carefully, to ensure a high COPel. Mechanical ventilation system can be

    upgraded with a cold storage as well. Especially effective are the latent storages which are cooled

    during the night, and at day time they are used to cool the supply air. These systems are moreexpensive, and are still in a phase of development.

    Despite the fact that free cooling techniques are effective and can reduce energy demand for

    cooling greatly they alone cannot guarantee that indoor comfort will be fulfilled all the time. In

    such cases other energy efficient cooling technology must be implemented  – the solar cooling. 

    night y

  • 8/20/2019 SOLAIR Guidelines En

    22/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    22

    1.4 Fundamentals of solar cooling

    1.4.1 Principles of desiccant‐evaporative solar cooling

    Air is a mixture of different gasses and water vapour. The change of air state can be a

    consequence of sensible heat transfer during the heating or cooling and the transfer of latentheat because of humidification or dehumidification. For that reason the state of the air should be

    expressed by the internal energy called enthalpy (h) instead of the air temperature. We can

    demonstrate the changes of air states in an T‐x diagram. During the humidification of air,

    dispersed drops of water in the air, transforms into molecules of water vapour with assistance of

    internal energy of air. Consequently the air cools down. This kind of natural cooling is very

    efficient, although it has an side effect of increasing the air’s moisture content and it’s relative

    humidity, which can exceed the appropriate levels, defined by thermal comfort.

    2

    1

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    0 2 4 6 8 10 12 14 16 18 20 22 24

    x (g/kg)

       T   (   °   C   )

    φ=0,1

    φ=0,2

    φ=0,3

    φ=1

    Figure 1.16 The process of evaporative cooling goes on at constant enthalpy. Air temperature drops, but at the same

    time moisture content of air (x) and relative humidity ( φ ) increase.

    9

    10

    0

    10

    20

    30

    40

    50

    60

    70

    80

    90

    0 2 4 6 8 10 12 14 16 18 20 22 24

    x (g/kg)

       T   (   °   C   )

    φ=0,1

    φ=0,2

    φ=0,3

    φ=1

    Figure 1.17 The process of sorption drying (10 ‐> 9) also goes on at constant enthalpy. Air temperature increases as

    moisture content (x) and relative humidity ( φ ) decrease.

  • 8/20/2019 SOLAIR Guidelines En

    23/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    23

    In conventional cooling systems air is dehumidified by cooling below the dew point, resulting in

    condensation of water vapour. The second option for drying the air is using special materials

    which have the ability of sorption removal of water vapour molecules out of the air. These

    materials are for example silica gel or lithium chloride. The first one is a solid, the second one is a

    liquid; however, lithium chloride is also applied in impregnated structures, thus appearing as solid

    form sorption unit. A side effect of this process is an increase in the air temperature andhumidification of the material, which absorbs the water vapour from the air. When heating the

    sorption material above the temperature of 60 to 70°C the water vapour is released from it and

    the process can be repeated. In solar driven desiccant‐evaporative solar cooling systems, this

    regeneration heat is provided by a solar thermal collector system.

    In market available applications, the processes are combined with a heat recovery unit to the

    desiccant‐evaporative solar cooling  cycle, described in detail in Chapter 2.

    1.4.2 Principle of sorption solar cooling

    Conventional cooling system use a compressor to compress refrigerant vapour. Sorption cooling

    processes run in a similar way. However instead of mechanical compressor which uses electricity,only fluid pumps are applied to pump binary mixture of two substances – the refrigerant and a

    substance that absorbs the refrigerant and is called absorbent, in case of an absorption process is

    applied. In practice a mixture of water (refrigerant) and lithium bromide (absorbent) on the one

    hand, or ammonia (refrigerant) and water (absorbent) on the other hand is used. Circulation

    pump electricity consumption is negligible compared to a compressor in a conventional cooling

    system. Additional energy needed for the operation of sorption cooling systems must be provided

    in form of heat, which can be produced by high efficient solar thermal system.

    Alternatively, an adsorption process may be applied, based on the physical process of adsorption

    of the refrigerant at a solid state sorption material, such as silica gel or types of zeolithes.

    Since the result ab‐   or adsorption processes is coolant water with temperature of 7 to 10°C all

    kinds of cooling system can be used. Details of sorption solar cooling can be found in Chapter 2.

    1.5 Impact of climate changes on thermal indoor comfort

    and energy demand for cooling

    Predicted climate changes due to anthropogenic emissions will cause an increase in mean

    atmosphere temperatures and atmospheric IR radiation. For that reason the climate changes will

    have a strong influence on thermal comfort in the buildings in the summer period and therefore

    on the energy demand for cooling as well. Based on simulations of a low‐energy dwelling and an

    office building without cooling shown on Figure 1.18 and considering a corrected test reference

    years (TRY) one can find out that the number of overheated hours will strongly increase. In case of

    mechanical cooling and if the most severe scenario (D, Ta + 3°C, +6 W/m2) is taken into account

    the energy demand for cooling will increase by 10 times (depending on the location and

    application). It can be expected, that the cooling demand will increase for 3 to 5 kWh/m2  of

    buildings living space. The conditions will be similar as in the year 2003. As temperatures will be

    also higher in the night time, the free cooling systems will be less efficient.

  • 8/20/2019 SOLAIR Guidelines En

    24/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    24

    Figure 1.18 Low energy and commercial building used in climate change impact simulations.

    0

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    1800

    2000

    2200

    TRY A B C D Year 2003

    CTRY

       N  u  m   b  e  r

      o   f   h  o  u  r  s   [   h   /  a   ]

     

    0

    200

    400

    600

    800

    1000

    1200

    1400

    1600

    1800

    2000

    2200

    2400

    2600

    TRY A B C D Year 2003

    CTRY

       N  u  m   b  e  r  o

       f   h  o  u  r  s   [   h   /  a   ]

     

    Figure 1.19 Increased overheating hours (Ti > 26°C) in un‐cooled one family (left) and office (right) building; Scenario A

    (+1°C), Scenario B (+1°C, +3 W/m2

     ), Scenario C (+3°C), Scenario D (+3°C, +6 W/m2

     ) Source: [Vidrih, Medved, 2006]

    0,0

    0,51,0

    1,5

    2,0

    2,5

    3,0

    3,5

    4,0

    4,5

    5,0

    5,5

    6,0

    TRY A B C D Year 2003

    CTRY

       C  o  o   l   i  n  g   d  e  m  a  n   d   [   k   W   h   /  m   2  a   ]

     

    0

    2

    4

    6

    8

    10

    12

    14

    16

    18

    20

    22

    24

    TRY A B C D Year 2003

    CTRY

       C  o  o   l   i  n  g   d  e  m  a  n   d   [   k   W   h   /  m   2  a   ]

     

    Figure 1.20 Increased specific cooling demand in cooled one family (left) and office (right) building in kWh per m2 of floor

    area per year

    Taking all these facts into account, we can expect that more and more buildings will be cooled

    in the future, especially every new built building. This gives solar cooling a great possibility to

    enforce itself in the market.  

  • 8/20/2019 SOLAIR Guidelines En

    25/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    25

    References

    [EN ISO 7730, 2005]

    Ergonomics of the thermal environment – Analytical determination and interpretation of thermal comfort using

    calculation of the PMV and PPD indices and local thermal criteria.

    [EN 15251, 2007]

    Indoor environmental input parameters for design and assessment of energy performance of buildings addressing

    indoor air quality, thermal environment, lighting and acoustics.

    [McQuiston et al., 2005]

    F. McQuiston, J. Parker, J. Spitler: “Heating, Ventilating, and Air Conditioning, Analysis and Design”; Jonn Wiley&Sons,

    Inc, 2005

    [Vidrih, Medved, 2006]

    B. Vidrih, S. Medved: “The Connection Between the Climate Change Model and a Buildings Thermal Response Model: A

    Case of Slovenia”, Journal of Mechanical Engineering, vol. 52, no. 9/06, Ljubljana, 2006

    [Arkar, Medved, 2007]

    C. Arkar, S. Medved; ”Free cooling of a building using PCM heat storage integrated into the ventilation system”, SolarEnergy, vol. 81, no 9, Elsevier Press, 2007

  • 8/20/2019 SOLAIR Guidelines En

    26/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    26

    2 Technologies applicable for solar thermally driven cooling

    The focus in SOLAIR is on solar cooling and air‐conditioning systems in the small and medium size

    capacity range. The classification into ‘small’ and ‘medium’ aligns with available chiller products;small applications are in this sense systems with a nominal chilling capacity below 20 kW, and

    medium size systems may range up to approx. 100 kW.

    Systems in the small capacity range are usually consist of thermally driven chilled water systems,

    whereas medium sized systems may be open cycle desiccant evaporative (DEC) cooling systems as

    well. While in the first type of system technology the distribution medium is chilled water in a

    closed loop to remove the loads from the building, in the latter one supply air is directly handled

    in humidity and temperature respectively in an open process. Figure 2.1 visualises the two general

    types of applications. Of course, applications using both types of technology at the same time are

    possible. In chilled water systems, the central cold water distribution grid may serve decentralised

    cooling units such as fan coils (mostly with dehumidification), chilled ceilings, walls or floors; but

    the chilled water may be used for supply air cooling in a central air handling unit as well. The re‐quired chilled water temperature depends on this type of usage and is important for the system

    design and configuration, but the end‐use devices are not in the focus of SOLAIR and thus are not

    presented more in detail.

    Cooled /Conditionedarea

    Chilled ceiling

    Supply air

    Fan coil

    ~18°C

    16°C - 18°C(< 12°C)

    6°C - 9°C

    Chilled watertemperature

    Heat> 60°C

    ThermallydrivenChiller

     

    Supply air

    Heat> 50°C

    Return air

    Desiccant evaporativecooling (DEC)

    Conditionedarea

     

    Figure 2.1 General types of thermally driven cooling and air  ‐conditioning technologies. In the figure above, chilled water

    is produced in a closed loop for different decentral applications or for supply air cooling. In the figure below, supply air is

    directly cooled and dehumidified in an open cycle process. Source: Fraunhofer ISE. The technologies are outlined more indetail below. Heat is required in both technologies, to allow a coninuous system operation. In the applications surveyed

    in SOLAIR, the heat is at least to a significant part produced by a solar thermal collector system.

  • 8/20/2019 SOLAIR Guidelines En

    27/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    27

    Figure 2.2 illustrates that any thermally driven cooling process operates at three different tem‐

    perature levels: with driving heat Qheat  supplied to the process at a temperature level of T H , heat

    is removed from the cold side thereby producing the useful ‘cold’ Qcold    at temperature T C . Both

    amounts of heat are to be rejected (Qreject ) at a medium temperature level T M. The driving heat

    Qheat  may be provided by an appropriate designed solar thermal collector system, either alone or

    in combination with auxiliary heat sources.While in open cycle processes the heat rejection is with the air flow in the system integrated into

    the process, closed chilled water processes require for an external heat rejection system, e.g., a

    cooling tower. The type of the heat rejection system is currently turning more into the field of

    vision, as this component usually is responsible for a considerable fraction of the remaining

    energy consumption of solar cooling systems.

    A basic number to quantify the thermal process quality in thermally driven chilled water systems

    is the coefficient of performance COP, defined as

    heat 

    cold 

    Q

    QCOP  = ,

    thus indicating the amount of required heat per unit ‘produced cold’ (more accurately: per unit

    removed heat). The COP and the chilling capacity depends strongly on the temperature levels of

    T H, T C  and T M. In open cycle desiccant cooling systems, the performance is more difficult to assess,

    since it depends more strongly on the system operation. It is useful, to define here the

    performance for the desiccant operation mode only, since in this operation mode heat is required

    (section 2.2). The performance is then calculated from the enthalpy difference between ambient

    and supply air, related to the required heat input. Experiences from DEC plants have shown that

    performance values comparatively to single‐effect chillers may be achieved.

    Focussing on chilled water systems, a maximum process performance COP ideal   for each

    temperature level can be derived from thermodynamic laws:

    C M 

    M H 

    C ideal 

    T T 

    T T 

    T COP 

    −−

    ⋅= .

    This dependency is discussed more in detail in e.g. [Henning, 2006]. As shown in figure 2.3, the

    ideal performance of a reversible process is far above the performance, obtained in market

    available thermally driven chillers. The COP in realised products ranges from 0.5 to 0.8 in single‐

    effect chillers (absorption or adsorption), and may range to 1.4 in double‐effect chillers.

    Qcold

    Qreject

    Qheat

    TC

    TM

    TH

     

    Figure 2.2 Basic scheme of a thermally driven cooling process.

  • 8/20/2019 SOLAIR Guidelines En

    28/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    28

    0.00

    0.20

    0.40

    0.60

    0.80

    1.00

    1.20

    1.40

    1.60

    1.80

    45 60 75 90 105 120 135 150

    Hot water inlet [°C[

       C   O   P

    ideal

    double-effect

    absorption

    single-effect

    absorption

    adsorption

    chilled water temperature: 9°C

    cooling water temperature: 28°C

     

    Figure 2.3 Exemplary curves of the coefficient of performance COP for different sorption chiller technologies and the

    limit curve for an ideal process. The curves are shown as function of the driving temperature and for a constant chilledand cooling water temperature level. Source: [Henning, Wiemken, 2006]

    The difference between real and ideal performance of the thermally driven chillers can be

    expressed with a process quality number   PQ:

    PQ = COP real  / COP ideal .

    Typical vaules of PQ  , extracted from market available products, are 0.3. The process quality

    number allows to assess the advantages of an improved process quality with respect to the

    required driving temperature. This is shown in figure 2.4. The figure presents the driving

    temperature as a function of the ‘temperature lift’ ∆T , which is defined as the difference between

    heat rejection temperature T M and chilled water temperature T C : ∆T = (T M  ‐ T  C  ). As an example,

    the temperature lift is low in case of high chilled water temperature and wet heat rejection (low

    cooling water temperatures) and high in case of low required chilled water temperatures and dry

    cooling. Driving temperatures for two different COP values are included. For each COP‐curve, the

    driving temperature depends furthermore on the process quality; therefore, two different quality

    numbers are assumed. The operation areas of different collector technologies are indicated as

    well. As an example, a single‐effect chiller with COP of 0.7, working at ∆T  = 35 K, may be driven

    still with vacuum tube collectors, if the process requires driving temperatures of approx. 100 °C

    (process quality number of 0.4). In case of a lower process quality, the required driving

    temperature is higher and tracked concentrating collectors are necessary.

  • 8/20/2019 SOLAIR Guidelines En

    29/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    29

    0

    50

    100

    150

    200

    250

    300

    350

    400

    10 15 20 25 30 35 40 45 50 55

    useful temperature lift T = TM – TC  [K]

      r  e  q  u   i  r  e   d   d  r   i  v   i  n  g   t  e  m

      p .   T   H   [   °   C   ]

    1,1 / 0,4

    1,1 / 0,3

    0,7 / 0,4

    0,7 / 0,3

    Flat-plate collector 

    Vacuum-tube

    collector 

    1-axis tracked

    concentrating collector 

    COP / PQ

    Chilledceilings

    Fan-coils;wet cooling

    Fan-coils;dry cooling

    High temperature lift:ice storage, dry cooling

    Application examples:

    0

    50

    100

    150

    200

    250

    300

    350

    400

    10 15 20 25 30 35 40 45 50 55

    useful temperature lift T = TM – TC  [K]

      r  e  q  u   i  r  e   d   d  r   i  v   i  n  g   t  e  m

      p .   T   H   [   °   C   ]

    1,1 / 0,4

    1,1 / 0,3

    0,7 / 0,4

    0,7 / 0,3

    Flat-plate collector 

    Vacuum-tube

    collector 

    1-axis tracked

    concentrating collector 

    COP / PQ

    Chilledceilings

    Fan-coils;wet cooling

    Fan-coils;dry cooling

    High temperature lift:ice storage, dry cooling

    Application examples:

     

    Figure 2.4 Heat source temperature required for different COP/  PQ  combinations, plotted as a function of the

    temperature lift. Typical operation ranges of solar collector technologies are included as well as different system

    application examples (grey marked areas). Source: [Hennng, 2006].

    2.1 Chilled water systems

    Absorption chillers

    The dominating technology of thermally driven chillers is based on absorption. The basic physical

    process consists of at least two chemical components, one of them serving as refrigerant and the

    other as the sorbent. The main components of an absorption chiller are shown in figure 2.5. The

    process is well documented, e.g., in [ASHRAE, 1988]; thus, details will be not presented here.

    The majority of absorption chillers use water as refrigerant and liquid lithium‐bromide as sorbent.

    Typical chilling capacities are in the range of several hundred kW. Mainly, they are supplied with

    waste heat, district heat or heat from co‐generation. The required heat source temperature is

    usually above 85°C and typical COP values are between 0.6 and 0.8. Until a few years ago, the

    smallest machine available was a Japanese product with a chilling capacity of 35 kW.Recently, the situation has improved due to a number of chiller products in the small and medium

    capacity range, which have entered the market. In general, they are designed to be operated with

    low driving temperatures and thus applicable for stationary solar thermal collectors. The lowest

    chiller capacity available is now 4.5 kW. Some examples of small and medium size absorption

    chillers are given in figure 2.6. In addition to the traditional working fluids H2O/LiBr, also H2O/LiCl

    and NH3/H2O are applied. The application of the latter working fluid with Ammonia as refrigerant

    ist relatively new for building cooling, as this technology was dominantly used for industrial

    refrigeration purposes below 0°C in large capacities. An advantage of this chiller type is especially

    given in applications, where a high temperature lift (T M – T  C ) is necessary. This is for example the

    case in areas with water shortage, when dry cooling at high ambient temperatures has to be

    applied.

  • 8/20/2019 SOLAIR Guidelines En

    30/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    30

    chilled water cooling water 

    cooling water hot water 

    (driving heat)

    GENERATOR

     ABSORBER

    CONDENSER

    EVAPORATOR

     

    chilled water cooling water 

    cooling water hot water 

    (driving heat)

    GENERATOR

     ABSORBER

    CONDENSER

    EVAPORATOR

     

    Figure 2.5 Scheme of a thermally driven single‐effect absorption chiller. Compared to a conventional electrically driven

    compression chiller, the mechanical compression unit is replaced by a ‘thermal compression’ unit with absorber andgenerator. The cooling effect is based on the evaporation of the refrigerant (e.g., water) in the evaporator at low

     pressure. Due to the properties of the phase change, high amounts of energy can be transferred. The vaporised

    refrigerant is absorbed in the absorber, thereby diluting the refrigerant/sorbent solution. Cooling is necessary, to run the

    absorption process efficient. The solution is continuousely pumped into the generator, where the regeneration of the

    solution is achieved by applying driving heat (e.g., hot water). The refrigerant leaving the generator by this process

    condenses through the application of cooling water in the condenser and circulates by means of an expansion valve

    again into the evaporator.

    Figure 2.6a Examples of small absorption chillers using water as refrigerant and Lithium‐Bromide as sorption fluid. Left:

    air ‐cooled chiller with a capacity of 4.5 kW of the Spanish manufacturer Rotartica. Middle: 10 kW Chiller with high part ‐

    load efficiency and overall high COP of the German manufacturer Sonnenklima, shown without housing. Right: Chiller

    with 15 kW capacity, manufactured by the German company EAW; this machine is also available in capacities of 30 kW,

    54 kW, 80 kW and above. Sources: Rotartica, Sonnenklima, EAW.

  • 8/20/2019 SOLAIR Guidelines En

    31/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    31

    Figure 2.6b Further examples of absorption chillers. Left: Absorption chiller with the working fluid H2O/LiBr and a

    capacity of 35 kW from Yazaki, Japan. This chiller is often found in solar cooling systems, since it was for several years

    the smallest in Europe available absorption chiller, applicable with solar heat. Currently, a smaller version with 17.5 kWchiller capacity from this manufacturer has entered the European market. Source: Gasklima. Right: This chiller uses

    water as refrigerant and Lithium‐Chloride as sorption material. The crystallisation phase of the sorption material is also

    used, effecting in an internal energy storage. The capacity is approx. 10 kW; the machine is developed by ClimateWell,

    Sweden, and can operate as heat pump as well. Source: ClimateWell.

    Figure 2.6c Examples of absorption chillers with the working fluid ammonia‐water. In principle, these types of chillers

    are foreseen to provide chilled water at temperatures < 0°C for commercial and industrial cooling, but may be applied

     for higher chilled water temperature levels under appropriate operating conditions as well. Left: Absorption chiller with

    12 kW rated chilling capacity, developed by Pink, Austria; shown without housing. Right: Absorption chiller from Ago,Germany. This chiller is available with 50 kW capacity and with higher capacities. Sources: Pink/SolarNext.

    Figure 2.7 displays current available hot water driven aborption chillers, sorted by chilling

    capactiy. The presentation makes no claim to be exhaustive.

    Double‐effect machines with two generators require for higher driving temperatures > 140°C, but

    show higher COP values of > 1.0. The smallest available chiller of this type shows a capacity of

    approx. 170 kW. With respect to the high driving temperatures, this technology demands in

    combination with solar thermal heat for concentrating collector systems. This is an option for

    climates with high fractions of direct irradiation.

  • 8/20/2019 SOLAIR Guidelines En

    32/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    32

    0 20 50 100 150 200 250 300 350 400 450

    Chilling capacity range [kW]

    York, Carrier, Trane ..

    Broad

    EAW

    ClimateWell

    Rotartica

    Sonnenklima

    Pink*

    Ago*

    Yazakiwater/LiBr

    ammonia/water*

    water/LiCl

    water/LiBr

    ammonia/water*

    water/LiCl

    Robur*

    Thermax

    * typical for applicationswith Tcold ≤ 0°C

     Figure 2.7 Typical capacity range of hot water driven absorption chillers. The listed products are market available, either

    by small series production or fabrication on demand. No claim to be complete.

    Adsorption chillers

    Beside processes using a liquid sorbent, also machines using solid sorption materials are available.

    This material adsorbs the refrigerant, while it releases the refrigerant under heat input. A quasi‐

    continuous operation requires for at least two compartments with sorption material. Figure 2.8

    shows the components of an adsorption chilller. Market available systems use water as

    refrigerant and silica gel as sorbent, but R&D on systems using zeolithes as sorption material is

    ongoing.

    To date, only few manufacturers from Japan, China and from Germany produce adsorptionchillers; a German company is with a small unit of 5.5 kW capacity on the market since 2007 and

    has increased the rated capacity in improved versions to 7.5 kW and 15 kW (models of 2008).

    Typical COP values of adsorption chillers are 0.5‐0.6. Advantageouos are the low driving

    temperatures, beginning from 60°C, the absence of a solution pump and a comparatively

    noiseless operation. Figure 2.9 shows examples of adsorption chillers, whereas figure 2.10

    displays current available adorption chillers, sorted by chilling capactiy. The presentation makes

    no claim to be exhaustive.

    An overview on closed cycle water chillers is also presented in [Mugnier et al., 2008].

  • 8/20/2019 SOLAIR Guidelines En

    33/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    33

    cooling water 

    cooling water 

    chilled water 

    hot water 

    (driving heat)

    CONDENSER

    EVAPORATOR

    12

     

    Figure 2.8 Scheme of an adsorption chiller. They consist basically of two sorbent compartments 1 and 2, and the

    evaporator and condenser. While the sorbent in the first compartment is desorbing (removal of adsorbed water) using

    hot water from the external heat source, e.g. the solar collector, the sorbent in the second compartment adsorbs the

    refrigerant vapour entering from the evaporator; this compartment has to be cooled in order to increase the process

    efficiency. The refrigerant, condensed in the cooled condenser and transferred into the evaporator, is vaporised under

    low pressure in the evaporator. Here, the useful cooling is produced. Periodically, the sorbent compartment are switched

    over in their functions from adsorption to desorption. This is usually done through a switch control of external located

    valves.

    Figure 2.9Examples of adsorption chillers. Left: Chiller with 70 kW capactiy of the Japanese manufacturer Nishiyodo,

    installed for laboratory cooling at the University Hospital in Freiburg, Germany. Adsorpition chillers of similar medium

    capacity are available from the Japanese manufacturer Mayekawa as well. Middle: Small ‐size adsorption chilllers with

    7.5 kW and 15 kW chilling capacity from SorTech company, Germany. Source: SorTech. Right: Small  ‐size adsorption

    chiller in the capacity range 7 to 10 kW of the manufacturer Invensor, Germany. Source: Invensor.

  • 8/20/2019 SOLAIR Guidelines En

    34/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    34

    0 20 50 100 150 200 250 300 350 400 450

    Invensor (DE)

    SorTech (DE)

    Mayekawa (JP)

    Nishyodo (JP)

    water/silicagel

    water/zeolite

    { SJTU (CN) }

    Chilling capacity range [kW]

    { } no detailed informationon market status

     

    Figure 2.10 Typical capacity range of adsorption chiller brands. The listed products are market available, either by smallseries production or fabrication on demand. No claim to be complete.

    Heat rejection

    Figure 2.2 in section 2 indicates that the amount of heat extracted from the building (‘useful cold’)

    plus the driving heat of the transformation process has both to be charged to the environment at

    (medium) ambient temperature level. This operation is done by means of a heat rejection system.

    Figure 2.11 illustrates as an example the difference in the demand of heat rejection between a

    conventional compression chiller system and an ab‐  or adsorption chiller system. It is evident that

    heat rejection in thermally driven systems plays a central role in the system development.

    Compression

    Qc = 3 x W

    QM = Qc + W

    WCompression

    1 kWc

    0,33 kWe

    1,33 kW

    Sorption

    Qc = 0,7 x QH

    QM = Qc + QH

    QH

    1 kWc

    1,4 kWt

    2,4 kW

    Sorption

     

    Figure 2.11 Example on the demand for heat rejection in a conventional electrically driven compression chiller system

    (left) and in a (single‐effect) thermally driven chiller system (right). In the comparison, the chilling capacity is 1 kW in

    both systems. Typical efficiency numbers have been used. Source: Tecsol.

  • 8/20/2019 SOLAIR Guidelines En

    35/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    35

    In principle, different possibilities and heat rejection technologies may be applicable:

    1.  wet cooling, either of open type or of closed type, using the evaporative cooling effect

    2.  dry cooling without evaporation

    3.  hybrid cooling, allowing for both options: wet and dry cooling

    4.  geothermal heat rejection by use of ground tubes

    5.  heat rejection by use of ground water, sea water, river or spring water6.  application of low temperature level cooling water by thus rejecting the medium temperature

    level heat

    If applicable in any case, the options 5. and 6. should be preferred, as these applications are

    connected with the lowest electricity consumption of the different heat rejection possibilities.

    Unfortunately, application fields of low temperature level heat (~ 30°C) is rarely identified, and

    sea water cooling is for financial reasons limited to applications direct at costal sites and for large

    applications. Additionally, the permittance to increase the sea water temperature level by this

    means is difficult to obtain.

    Heat rejection using ground tubes is a comparatively new approach and may be of interest,

    especially when the ground tubes are used for heat pump operation as well during winter, thuscontributing to an annual balanced charging and dischcharging of the ground. However, the

    investment cost for ground tubes are currently still high. An example of such an application in

    combination with a small adsorption chiller (with heat pump operation) is shown in the SOLAIR

    Best practice examples [SOLAIR: Best Practice Catalogue, 2008].

    The most applied heat rejection technology in combination with thermally driven chillers today is

    still wet cooling by means of open cooling towers. Figure 2.12 illustrates the principle of such a

    heat rejection system: the cooling water is sprayed on top of the cooling tower towards the filling

    material, which increases the effective exchange area between air and cooling water. The main

    cooling effect is obtained through evaporation of a small percentage of the cooling water

    (typically < 5%); this loss has to be compensated by fresh water supply. The cooled water then

    returns to the cooling circuit of the chiller. A fan removes the saturated air in order to keep theprocess running. The process is very efficient in appropriate climates and in principle, the

    limitation temperature of the returned cooling water is not far from the wet‐bulb temperature of

    the air (3°C to 5°C above the wet‐bulb temperature). A commercial product is shown in

    figure 5.13.

    Fan

    Drip-catcher 

    Cooling waterdistribution

    Filling material

     Air inlet

    Sump

     

    Figure 2.12 Typical scheme of an open wet cooling tower. Source: GWA.

  • 8/20/2019 SOLAIR Guidelines En

    36/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    36

    Figure 2.13 Example of a large wet cooling tower installation.

    In dry climates, the fan speed of a wet cooling tower can be often decreased in order not to fall

    below the minimum cooling water temperature of the chiller (e.g., 25°C often defined for

    absorption chillers), whereas in a very humid climate also the wet‐bulb temperature often is high.

    Figure 2.14 displays as an example for more extreme climates monthly averages of the wet‐bulb

    temperature at Dubai. During summer, the monthly values are approx. 25°C, indicating that

    during daytime the obtained return cooling water temperature often may exceed 30°C. Also the

    ambient temperature levels are very high and during day, up to 40°C ambient temperature is

    detected, which indicates the limit of dry cooling (limitation temperature: a few °C above ambient

    temperature).

    In the application with adsorption chiller technology, closed wet cooling towers have to be

    applied instead of open wet cooling towers. The reason is the connection of the heat rejectioncircuit with the driving circuit for some seconds during the heat recovery phase, which is activated

    between the functional interchange of adsorption and desorption partitions of the chiller. The

    hydraulic pressure conditions do not usually allow for an open cooling water loop. In the closed

    cooling towers, the tower is equipped with a cooling water heat exchanger, which is sprayed by

    an external water loop for indirect evaporative cooling. A disadvantage of this technique are

    lower efficiencies and higher costs.

    In some countries, regulations exist on the application of wet cooling towers with respect to

    hygienic aspects. In order to avoid unfavourable growth of bacteria, a water treatment of the

    cooling water may be necessary. For this reason and for reasons of improving the optical

    acceptance of heat rejection systems especially in small scale applications, dry cooling is still of

    interest, although the cooling temperature level as well as the electricity consumption is ingeneral higher (higher power consumption of the fans due to pure sensible cooling). Dry heat

    rejection in solar thermally driven cooling systems has been applied in a number of

    demonstration systems for testing this opportunity. Furthermore, a supplier of small capacity

    adsorption chillers offers a dry cooler with spray function in case of high ambient temperatures,

    adapted to the chiller.

  • 8/20/2019 SOLAIR Guidelines En

    37/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    37

    0

    10

    20

    30

    40

    50

    60

    70

    Jan Feb Mar Apr May Jun Jul Aug Sept Oct Nov Dec

       A  m   b   i  e  n   t  a   i  r  a  n   d  w  e   t   b  u   l   b   T  e  m  p  e  r  a   t  u  r  e   [   °   C   ] ,

      r  e   l .   h  u  m   i   d   i   t  y   [   %   ]

    0

    50

    100

    150

    200

    250

       G   l  o   b  a   l   h  o  r   i  z  o  n   t  a   l  r  a   d   i  a   t   i  o  n  s  u  m

    Ta [°C] Twb [°C] RH [%] G_Gh [kWh/m2]

     Figure 2.14 Monthly climate data for Dubai site. During summer, very high wet ‐bulb temperautes may be expected

    during daytime, thus limiting the efficiency of wet cooling towers. At the same time, also the ambient temperature as

    indicator for dry cooling limits is very high as well.

    2.2 Open cycle processes

    While thermally driven chillers produce chilled water, which can be supplied to any type of air‐

    conditioning equipment, open cooling cycles produce directly conditioned air. Any type of

    thermally driven open cooling cycle is based on a combination of evaporative cooling with air

    dehumidification by a desiccant, i.e., a hygroscopic material. Again, either liquid or solid materials

    can be employed for this purpose. The standard cycle which is mostly applied today uses rotating

    desiccant wheels, equipped either with silica gel or lithium‐chloride as sorption material. All

    required components, such as desiccant wheels, heat recovery units, humidifiers, fans and water‐

    air heat exchangers are standard components and have been used in air‐conditioning and air‐

    drying applications for buildings or factories since many years. However, the appropriate

    combination of the components to form a desiccant evaporative cooling system (DEC), which is

    the most common solar driven open cycle system, requires some special experience and

    attention.

    The standard cycle using a desiccant wheel is shown in figure 2.15. The application of this cycle is

    limited to temperate climates, since the possible dehumidification is not high enough to enable

    evaporative cooling of the supply air at conditions with far higher values of the humidity of

    ambient air. For climates like those in the Mediterranean countries therefore other configurations

    of desiccant processes have to be used.

    Systems employing liquid sorption materials which have several advantages like higher air

    dehumidifiation at the same driving temperature and the possibility of high energy storage by

    means of concentrated hygrocopic solutions are note yet market available but they are close to

    market introduction; several demonstration projects are carried out in order to test the applica‐

    bility of this technology for solar assisted air conditioning. A possible general scheme of a liquid

    desiccant cooling system is shown in figure 2.16.

  • 8/20/2019 SOLAIR Guidelines En

    38/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    38

    humidifier cooling

    loads

    supply air

    backupheater

    return air

    dehumidifier

    wheel

    heat recovery

    wheel

    1 2 3 4 56

    789101112

     

    Figure 2.15 Scheme of a solar thermally driven solid Desiccant Evaporative Cooling system (DEC), using rotating sorption

    and heat recovery wheels (source: Fraunhofer ISE). Below: sketch of the DEC unit (source: Munters). The successive

     processes in the air stream are as follows:

    12 sorptive dehumidification of supply air; the process is almost adiabatic and the air is

    heated by the adsorption heat released in the matrix of the sorption wheel

    23 pre‐cooling of the supply air in counter‐flow to the return air from the building

    34 evaporative cooling of the supply air to the desired supply air humidity by means of a

    humidifier

    45 the heating coil is used only in the heating season for pre‐heating of air

    56 small temperature increase, caused by the fan

    67 supply air temperature and humidity are increased by means of internal loads

    78 return air from the building is cooled using evaporative cooling close to the saturation

    line

    89 the return air is pre‐heated in counter‐flow to the supply air by means of a high

    efficient air‐to‐air heat exchanger, e.g. a heat recovery wheel

    910 regeneration heat is provided for instance by means of a solar thermal collector

    system

    1011 the water bound in the pores of the desiccant material of the dehumidifer wheel is

    desorbed by means of the hot air

    1112 exhaust air is removed to the environment by means of the return air fan.

  • 8/20/2019 SOLAIR Guidelines En

    39/100

    Requirements on the design and configuration of small and medium sized solar air‐conditioning applications  Guidelines  

    39

    diluted solution

    concentratedsolution

    regeneration air 

      QH

    driving heat

    ⇒  QM rejected heat

    Regenerator 

    Absorber 

    supply air 

    solution storage

    LiCl/water

     

    Figure 2.16 General scheme of a liquid desiccant cooling system (top). The supply air is dehumidified in a specialconfigured spray zone of the absorber, where a concentrated salt solution is diluted by the humidity of the supply air.

    The process efficiency is increased through heat rejection of the sorption heat, eg., by means of indirect evaporative

    cooling of the return air and heat recovery. A subsequent evaporative cooling of the supply air may be applied, if

    necessary (heat recovery and evaporative cooling is not shown in the figure). In a regenerator, heat e.g. from a solar

    collector is applied, to concentrate the solution again. The concentrated and diluted solution may be stored in high

    energy storages, thus allowing a decoupling in time between cooling and regeneration to a certain extent. Bottom: a

    liquid desiccant cooling demonstration system is installed at the Solar Info Center in Freibug, Germany, for air  ‐

    conditioning of 310 m² office area. The air volume flow rate is 1500 m³/h. The system was developed and installed by

    the German company Menerga. The ventilation system is at the left side of the figure, the solution storages are located

    right hand side in the foreground. The storage in the background is part of the solar thermal driving heat source,

    consisting of 17 m² flat ‐ plate collectors. Sources: Fraunhofer ISE.

    In general, desiccant evaporative cooling is an interesting option if centralized ventilation systems

    are used. At sites with high latent and sensible cooling loads, the air ‐conditioning process can be

    splitted into dehumidification by means of a thermally driven open cycle desiccant process, and

    an additional chilled water system to maintain the sensible loads by means of e.g. chilled ceilings

    with high chilled water temperatures, in order to increase the efficiency of the chilled water

    production.

    More details on open cycle processes are given in [Henning, 2004/2008] and in [Beccali, 2008].

  • 8/20/2019 SOLAIR Guidelines En

    40/100

    Guidelines Requirements on the design and configuration of small and medium sized solar air‐conditioning applications

    40

    2.3 Solar thermal collectors

    A broad variety of solar thermal collectors is available and many of them are applicable in solar

    cooling and air‐conditioning systems. However, the appropriate type of the collector depends on

    the selected cooling technology and on the site conditions, i.e., on the radiation availability.General types of stationary collectors are shown in figure 2.17, and construction principles of

    improved flat‐plate collectors and evacuated tube collectors are given in figure 2.17a‐c.

    The use of cost‐effictive solar air collectors in flat plate construction is limited to desiccant cooling

    systems, since this technology requires the lowest driving temperatures (starting from approx.

    50°C) and allows under special conditions the operation without thermal storage. To operate

    thermally driven chillers with solar he