smart heating production - carrier.com

8
SMART HEATING PRODUCTION AIR CONDITIONING & HEATING SOLUTIONS High temperature heat-pump with PUREtec TM HFO refrigerant 200 kW to 2500 kW 61XWHZE D E S I G N I N G I N N O V A T I V E S O L U T I O N S Up to 85°C

Upload: others

Post on 17-Oct-2021

2 views

Category:

Documents


0 download

TRANSCRIPT

S M A R T H E A T I N G P R O D U C T I O N

A I R C O N D I T I O N I N G & H E AT I N G S O L U T I O N S

High temperature heat-pump with PUREtecTM HFO refrigerant

200 kW to 2500 kW

61XWHZE

D E S I G N I N G I N N O V A T I V E S O L U T I O N S

Up to85°C

75% of the people in Europe live in a city setting. People in cities use three times as much energy as people who live in the country. This has tremendous implications for the environment today and in the future if we do nothing. More and more, developers, consultants, cities, politics will need to imagine intelligent, sustainable cities with smart heating and cooling solutions.

Using renewable energy from both natural and wasted heat sources are great opportunities for more sustainable cooling and heating solutions.

Value natural heat source

Smart cities can value natural heat sources as an advanced and cost effective alternative to fossil fuels. It is available free of charge and offers independence from oil and gas:

Groundwater

Lake water

Sea water

Geothermal Probes

Value wasted heat source

Recent European surveys have demonstrated that there is enough waste heat produced in the European Union to heat the entire building stock. All this waste energy too frequently released into the air or into water bodies. Why not recover it? Smart cities shall value:

Waste heat from data centers

Waste heat from grey waters

Waste heat from industrial process

Waste heat from boilers (wood, gas...)

Waste heat from chillers

Heat recovery potential for smarter cities

Developing smarter cities to anticipate the increase of urbanisation

Smart urbanisation

COUNTRYCITY

ENERGY

ENERGY

with smartheating and

cooling solutions

25%

75%

X 3

X 1

2

The Carrier AquaForce 61XWHZE heat pumps can value both natural and wasted heat sources to offer sustainable energy solutions for multiple heating applications.

By using renewable energy sources for air, water and ground, AquaForce 61XWHZE heat pumps offer smart cities a more sustainable energy supply solution.

Delivering hot water up to 85°C, the 61XWHZE heat pumps can supplement traditional boilers in applications such as:

Commercial building heating

District heating Industrial process heating

AquaForce®, multiple heating applications

SEA WATER

LAKE WATER

INDUSTRIES

GEOTHERMAL PROBES

AND GROUND WATER

20°C85°C

HEAT RECOVERY

DISTRICT HEATING

OFFICES

DATA CENTER

15°C 55°C

INDUSTRIAL PROCESS

AND GREY WATERHOUSING

ADMINISTRATION

AquaForce, at the heart of smart city, providing both natural and wasted heat sources to multiple applications.

3

85°C hot water productionThe combination of Carrier technology and HFO refrigerantenables to offer high temperature PUREtec heat pumps capable of delivering hot water up to 85°C. Selecting the 61XWHZE, you can now supplement traditional boilers in applications such as district heating or industrial processes.The 61XWHZE units can also simultaneously produce chilled and hot water to supplement boilers and replace chillers.

High reliability and certified performancesEvery Carrier 61XWHZE heat pump is factory assembled on a dedicated production line, leak-tested and run-testedin a ISO 140001 and ISO 9001 certified factory. Furthermore Carrier 61XWHZE heat pumps performances have been checked in UTC laboratory during the development phase and are Eurovent certified by an independent laboratory.

Eligible to financial incentivesMany government environmental programs provide financial incentives for heat pumps to support renewable heat production in the industry, the district heating sector and at multi-family buildings: Fonds Chaleur, Certificats d’Economie d’Energie (CEE) in France, Non-Domestic Renewable Heat Incentive (RHI) in the UK.

Low total cost of ownership61XWHZE manufacture is based on large scale component production, standardized production line with leak test and running test of every machine to guarantee an absolute

reliability and peace of mind for our customers. During operation the bearing life time of the compressors is 100 000 hours without expensive mechanical revision and oil renewal. In regards with preventive maintenance, the cost of the replacement of components is limited as well. Only oil filter, motor expansion valves and liquid line core dryer are periodically concerned.

Low environmental footprint61XWHZE heat-pumps are using ultra-low GWP HFO R-1234ze refrigerant in a tight circuit, thus reducing environmental impact of more than 99% compared with previous-generation HFC refrigerants. Furthermore, these units are highly efficient as they reach a COP of 3.0 or more.This results in both direct and indirect CO2 emissions that contribute to global warming.

Carrier 61XWHZE multiple other advantagesCarrier 61XWHZE heat-pumps have many other advantages to meet every single customer needs and project constraints. It includes:

Compact design (from 1000 mm wide) to save space into technical rooms. Multiple water connection arrangements for flexible installation in existing technical rooms. High entering water temperature on condenser side (up to 60°C) to connect multiple units in series counterflow arrangement.

Up to85°C

Full reliability

Financialincentives

&Low total

cost of ownership

€Heating

& CoolingLow

environmental footprint

AquaForce®, smart heating production

4

Water-sourced heat pumps with PUREtec refrigerant

61XWHZE

TOUCH PILOT™ CONTROL

User-friendly touch screen

All main parameters displayed on one screen

Direct access to the unit’s technical drawings and main service documents

Easy remote monitoring via the internet

Easy and secure access to unit parameters

SCREW COMPRESSOR Carrier 06T screw model

High efficiency motor

100 000 hours bearing lifetime in operation

Variable slide valve for capacity control

AQUAFORCE HEAT PUMPS Compact sizes (from 1000 mm wide) for handling and installation flexibility

Easy access to critical components for great serviceability

SHELL AND TUBE HEAT EXCHANGERS

Flooded technology for enhanced heat transfer and easy cleaning of the tubes on the water side

Polyurethane foam thermal insulation as standard

Water drain and purge

Up to 1000 kPa operating pressure on water-side

PRESSURIZED ELECTRICAL BOX Integrated fan blowing (outside to inside)

Interface to receive inlet duct for fresh air

Hermetic closure (new box, new doors)

Fan operation detection prior unit startup

PUREtec REFRIGERANT Long-term refrigerant solution

Selection of HFO R-1234ze

GWP<1

ODP = 0

Technical Insight

5

AquaForce®,

a tried and trusted solution

6

CORIANCE, Blanc Mesnil • FranceDistrict heating network

CUSTOMER’S REQUIREMENTHeating capacity of 4.5 MW with a heat pump system connected to a geothermal heat source, located at 2 km depth. Condenser leaving water temperature of up to 85°C.Evaporator entering water temperature of 55°C.

CARRIER’S SOLUTION 2 AquaForce 61XWHZE heat pumps in cascade counterflow system with smart monitoring.

Carrier was ready to provide an innovative solution due to its leadership in HFO implementation. Beyond the high coefficient of performance (COP >4), the 61XWHZE heat pump offers an environmentally responsible solution with a very low GWP and non-toxic refrigerant (HFO R1234ze). Its compact dimensions allow for a simplified installation in existing buildings.

CADZIPLO, Plan-les-Ouates • SwitzerlandEurope’s first screw water-to-water heat pumps using HFO for a district heating application

CUSTOMER’S REQUIREMENTCompliance with stringent Swiss refrigerant regulations. Combination of reduced low GWP and high efficiency with a heating capacity of 2.5 MW.Re-use of data center energy as district heating source thanks to the large operation envelope of the AquaForce heat pumps.

CARRIER’S SOLUTION 2 AquaForce heat pumps with PUREtec HFO refrigerant.

Carrier’s experience and its leadership of HFO implementation have made the difference.

YGEO, Rosny sous bois, Noisy le sec, Montreuil • FranceDistrict heating network

CUSTOMER’S REQUIREMENTHeating capacity of 12 MW with a heat pump system connected to a geothermal heat source, located at 1.8 km depth. Condenser leaving water temperature of up to 80°C. Evaporator entering water temperature of 52°C.

CARRIER’S SOLUTION 6 AquaForce 61XWHZE heat pumps in cascade counterflow system with smart monitoring.

The 61XWHZE range offers full modularity due to the cascade system and smart monitoring management. The combination of full reliability and low maintenance ensure a high level of availability. Smart Carrier algorithms have been designed to optimize cascade system efficiency.

Bjölsen Energy, Oslo • NorwayDistrict heating network for student housing

CUSTOMER’S REQUIREMENTEnvironmentally responsible solutions able to deliver up to 71°C at brine temperature of 1°C.

CARRIER’S SOLUTION 2 AquaForce 61XWHZE heat pumps with PUREtec HFO refrigerant, recovering heat from geothermal source and from a nearby supermarket.

Carrier ensures the full reliability of the plant and experts close at hand. The smart algorithms of the control allows for a perfect management and monitoring of the heat pumps with the bio boiler in place.

7

©ENGIE RESEAUX

DISCOVER THE CADZIPLO PROJECT ON YOUTUBE.COM/C/UTCCLIMATECONTROLSSECURITY

Counterflow hydraulic configuration to maximize system efficiency

Exchangers with one pass more for large DT > 20 K on evaporator and condenser sides

Evaporator with one pass less to reduce significantly water pressure drops and pumping energy costs

Welded or flange water connections

Low noise option using evaporator acoustic insulation

Star/delta start to reduce the unit inrush current (models 3, 5 and 10 only)

Pump power/control circuit (models 3 to 10 only)

Master/slave operation

7 inch Touch Pilot user interface

J-Bus, Lon, Bacnet over IP communication gateways

Carrier smart monitoring solutions for remote energy servicing

MAIN OPTIONS

61XWHZEModel

L / - / H*

Size

3 5 7 10 14 15 17

HEATING CAPACITY* kW 300 484 727 967 1453 1468 1570

LENGTH m 2.7 3.1 3.3 4.7 4.7 4.8 4.8

WIDTH m 0.9 1.1 1.1 1.1 1.2 1.4 1.4

HEIGHT m 1.6 1.8 2.0 2.0 2.1 2.3 2.3In accordance with standard EN14511-3:2013. Heating performances of model H based on condenser hot water temperature 70°C/75°C and evaporator water temperature 20°C/15°C.*Each model is available in three versions to optimize system efficiency and offer multiple combinations: “L” for low heat source temperatures, ”-” for medium heat source temperatures and “H” for high heat source temperatures.

Technical

characteristics

The AquaForce 61XWHZE range covers heating capacities from 200 kW to 2500 kW and up to 12 MW or more in cascade systems when used with Carrier’s plant room management solution.

In a series counterflow arrangement with multiple 61XWHZE heat pumps, heating system efficiency is maximized. The work done (lift) by each compressor is reduced, which significantly improves the efficiency of the heat pumps at full and part load conditions. Such series counterflow arrangement can improve system efficiency by as much as 40% and Carrier’s plant room controls solution ensures efficient and precise control of multiple units to ensure that individual units act as one to meet the applications requirement.

www.carrier.comAquaForce with PUREtec - 61XWHZE - English - October 2018. © Carrier 2018. All rights reserved. Carrier reserves the right to change certain information and specifications contained in this document at any time and without prior notice.Since standards, specifications and designs are subject to occasional change, please ask for confirmation of the information given in this publication.

SYSTEM ONE1x heat pump unit

40°C 70°C

Series counterflow arrangement can improve COP by up to 40%

ENERGY EFFICIENCY OF 61XWHZE HEAT-PUMPS IN SINGLE UNIT CONFIGURATION

SYSTEM TWO2x heat pumps unitsin series counterflow

COP up to+ 40%

40°C 53°C 70°C

12°C 12°C 22°C 35°C35°C

The COP of 61XWHZE heat-pump will vary depending on the temperature difference between the heat source (evaporator side) and the heat sink (condenser side). The work done (lift) by each compressor is reduced when this temperature difference is low thus significantly improving the efficiency of the heat-pump.

Hot water temperature on condenser side (°C)

Outlet water temperature on evaporator side °C)

61XWHZE COP

ECO DESIGNREADY