Specifications are subject to change without notice (10.12.2013) 1 Smart Dupline ® Product Description Ordering Key smart-house DIN housing 2 modules Dimmer Maximum load Energy measurement Power supply Type Selection Housing Mounting Max. load Output type Supply: 115 to 240 VAC 2 DIN DIN-rail 500W Power mosfet SH2D500WE230 Power dimmer up to 500W with Energy Reading Type SH2D500WE230 This 500W universal dimmer is designed for DIN-rail mounting with energy mea- surement. Single phase vari- ables: VLN, A, W. Energy measurement: total kWh consumed by the connected load. This universal dimmer is suitable for dimming resis- tive, inductive and capaci- tive loads and LED lamps (see LED lamps table). The maximum load of R, L, C type is 500W depending on the temperature: the reduc- tion is described according to the trend in the diagram “derating curve”. The dimmer automatically detects if the connected load is resistive, capacitive or inductive, but if a LED lamp is to be driven, the user has to select the right curve as described below. The dimmer is completely programmable via the smart-house tool. The technology used enables to electrically pro- tect the dimmer against short circuit, overload and over-temperature. Thanks to the internal bus, it can be easily connected to adjacent dimmers (see “wiring dia- gram”) without the need of cabling the Dupline ® BUS. Futhermore, the integrated sink allows you to mount the dimmers adjacently without any reduction of the load due to the increased tem- perature. Universal dimmer up to 500W for R, L, C load and LED lamps Automatic load detection for R, L, C loads Integrated heat sink for temperature dissipation 1 dimmable output Soft start/stop Protected against short circuit, overload and high temperature Minimum load 3 W Instantaneous variables readout: current, voltage, power Energy measurement: kWh Faulty lamp recognition S H 2 D 500W E 230 Output Specifications Maximum load 500 W for R, L, C load Note: this is the maximum power supplied to the load: if an inductive transformer is used, the efficiency of about 60% has to be considered before connecting the lamps. If a capacitive transformer is used, the efficiency is about 90%. Minimum load 3 W @ 230 V, 6 W @ 115V Protections Overload, short circuit, thermal Output type Power mosfet Rated operational voltage 115/240 VAC Operational voltage range 115/240 VAC ±10% Rated operational frequency 50/60 Hz Dimming speed Programmable Types of dimmable lamps Incandescent (R) Different types of outputs (L,C) LV halogen lamps with can not be mixed electronic ballast (C) LV halogen lamps with conventional transformer (L) HV halogen lamps (R) 115/230V dimmable LED lamp ESL (Electron Stimulated Luminescence) lamps Notes: if energy saving lamps are used, attention has to be paid to the maxi- mum inrush current at start- up: it must not be greater than 3.5A otherwise the overload protection will be activated.

Upload: others

Post on 05-Jul-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Smart Dupline Power dimmer up to 500W with Energy Reading … · 2017-04-14 · Power supply Overvoltage cat. II (IEC 60664-1, par. 4.3.3.2) Rated operational voltage 115/240 VAC

Specifications are subject to change without notice (10.12.2013) 1

Smart Dupline®

Product Description Ordering Keysmart-houseDIN housing2 modulesDimmerMaximum loadEnergy measurementPower supply

Type SelectionHousing Mounting Max. load Output type Supply: 115 to 240 VAC

2 DIN DIN-rail 500W Power mosfet SH2D500WE230

Power dimmer up to 500W with Energy Reading Type SH2D500WE230

This 500W universal dimmeris designed for DIN-railmounting with energy mea-surement. Single phase vari-ables: VLN, A, W. Energymeasurement: total kWhconsumed by the connectedload. This universal dimmeris suitable for dimming resis-tive, inductive and capaci-tive loads and LED lamps(see LED lamps table). Themaximum load of R, L, Ctype is 500W depending onthe temperature: the reduc-tion is described accordingto the trend in the diagram“derating curve”.The dimmer automaticallydetects if the connectedload is resistive, capacitiveor inductive, but if a LED

lamp is to be driven, theuser has to select the rightcurve as described below.The dimmer is completelyprogrammable via thesmart-house tool.The technology usedenables to electrically pro-tect the dimmer againstshort circuit, overload andover-temperature. Thanks tothe internal bus, it can beeasily connected to adjacentdimmers (see “wiring dia-gram”) without the need ofcabling the Dupline® BUS.Futhermore, the integratedsink allows you to mount thedimmers adjacently withoutany reduction of the loaddue to the increased tem-perature.

• Universal dimmer up to 500W for R, L, C load and LED lamps

• Automatic load detection for R, L, C loads• Integrated heat sink for temperature dissipation• 1 dimmable output• Soft start/stop• Protected against short circuit, overload and high temperature

• Minimum load 3 W• Instantaneous variables readout: current, voltage,power

• Energy measurement: kWh• Faulty lamp recognition

S H 2 D 500W E 230

Output Specifications Maximum load 500 W for R, L, C load Note: this is the maximumpower supplied to the load: ifan inductive transformer isused, the efficiency of about60% has to be consideredbefore connecting the lamps.If a capacitive transformer isused, the efficiency is about90%.Minimum load 3 W @ 230 V, 6 W @ 115VProtections Overload, short circuit, thermalOutput type Power mosfetRated operational voltage 115/240 VACOperational voltage range 115/240 VAC ±10%Rated operational frequency 50/60 Hz

Dimming speed ProgrammableTypes of dimmable lamps Incandescent (R)Different types of outputs (L,C) LV halogen lamps with can not be mixed electronic ballast (C) LV halogen lamps with conventional transformer (L) HV halogen lamps (R) 115/230V dimmable LED lamp ESL (Electron Stimulated Luminescence) lamps Notes: if energy savinglamps are used, attentionhas to be paid to the maxi-mum inrush current at start-up: it must not be greaterthan 3.5A otherwise theoverload protection will beactivated.

Page 2: Smart Dupline Power dimmer up to 500W with Energy Reading … · 2017-04-14 · Power supply Overvoltage cat. II (IEC 60664-1, par. 4.3.3.2) Rated operational voltage 115/240 VAC

2 Specifications are subject to change without notice (10.12.2013)

SH2D500WE230

Installation category Cat. IIDielectric strength Power supply to Dupline® 4 KV AC for 1 min.Dupline® to Output 6 KV impulse 1.2/50�µs

(IEC60664-1, TAB. A.1)Fail-safe mode In case of interruption of the

smart-house connection,the channel will be forcedinto a specific optional sta-tus as described below.

EnvironmentDegree of protection Front IP 50 Screw terminal IP 20

Pollution degree 2 (IEC 60664-1, par. 4.6.2)Operating temperature -20° to +50°C (-4° to 122°F)Storage temperature -50° to +85°C (-58° to 185°F)Humidity (non-condensing) 20 to 80% RHLED’s indicationSupply ON 1 greenDupline® status 1 yellowOutput status 1 redConnectionTerminal 4 Screw-typeCable cross-section max. 6 mm2, min. 0,5 mm2

Tightening torque 0.4 Nm / 1 Nm

General SpecificationsHousingDimensions 2 DIN moduleMaterial NorylWeight 150 gApprovals CRUUS, according to UL60950

UL notes: Max room temperature: 40°C A readily accessible discon- neting device shall be added in the building installation

CE Marking YesEMCImmunity EN 61000-6-2- Electrostatic discharge EN 61000-4-2- Radiated radiofrequency EN 61000-4-3- Burst immunity EN 61000-4-4- Surge EN 61000-4-5- Conducted radio frequency EN 61000-4-6- Power frequency magnetic fields EN 61000-4-8

- Voltage dips, variations,interruptions EN 61000-4-11

Emission EN 61000-6-3- Conducted and radiatedemissions CISPR 22 (EN55022), cl. B

- Conducted emissions CISPR 16-2-1 (EN55016-2-1)- Radiated emissions CISPR 16-2-3 (EN55016-2-3)

Power supply Overvoltage cat. II (IEC 60664-1, par. 4.3.3.2) Rated operational voltage 115/240 VACOperational voltage range 115/240 VAC ±10%Rated impulse voltage 2.5 kVRated operational power 1 W, 9 VAConnection 4 x 6 mm2

Power on delay Typ. 2 s

Supply Specifications Key Pad One push button on local dimmer

Input Specifications

Voltage 8.2 VMaximum Dupline® voltage 10 VMinimum Dupline® voltage 5.5 VMaximum Dupline® current 1 mA

Dupline® Output Specifications

Mode of OperationWorking mode If the SH2D500WE230 isconnected to the Dupline®bus and the bus is workingproperly, the dimmer is inSTANDARD mode and thegreen LED is ON. The dim-mer enters LOCAL mode ifthe push button is pressedor if the bus is faulty or notconnected. In LOCAL modethe dimmer doesn't acceptany command from the busand the green LED will beflashing. The dimmer can goback to STANDARD modeonly when the bus is ok andafter one of the following

events: 1) As soon as theDupline® bus returns 2) After a timeout of 1minute after a button press3) After a power cycle.

PushbuttonBus connectedThe push button can beused with a short or longpressure (>2 seconds): itspressure puts the dimmer inLOCAL mode.Short pressure: the light isswitched ON/OFF (togglefunction) with the set value.Factory settings is 100%, sothe first time this push but-

ton is pressed with a shortpressure, the light isswitched ON to 100%. If adifferent light scene is mem-orised in the module, thelight is switched ON at thatlevel.Long pressure: once thelight is ON, by keeping thekey pressed for more than 2seconds, the light will beincreased up to 100% andthen decreased down to5%. This will be repeateduntil the key is kept pressed.Every time the button ispressed, the ramp is invert-ed.

Bus not connected or faulty If the bus is not connectedor faulty, the push-buttonoverwrites the failsafe condi-tion with the previouslydescribed behaviour.

Coding/AddressingNo addressing is neededsince the module is providedwith a specific identificationnumber (SIN): the user hasonly to insert the SIN num-ber in the configuration toolwhen creating the systemconfiguration.

Page 3: Smart Dupline Power dimmer up to 500W with Energy Reading … · 2017-04-14 · Power supply Overvoltage cat. II (IEC 60664-1, par. 4.3.3.2) Rated operational voltage 115/240 VAC

Specifications are subject to change without notice (10.12.2013) 3

SH2D500WE230

Mode of Operation (cont.)Faulty lamps recognitionIf the measured current islower than 20mA, the relaymodule gives a message offaulty load (the connectedlamp might be broken). Thisinformation is sent toSH2WEB24 that makes itavailable to the user via theSHtool, Webserver, email,SMS, ...

Fail/safe conditionThe output status of thedimmers, when the Dupline®bus is not connected orfaulty, is programmed via theSH Tool and the user canchoose between the follow-ing options:1. Output always OFF2. Output always ON3. The output maintains the

status they had beforethe disconnection.

As default, output is factoryset to OFF.

Energy measurementThe electrical values mea-sured by theSH2D500WE230 are: cur-rent, voltage, power, energy.These readouts are sent tothe SH2WEB24 and loggedthere, the instant values andthe logged ones are accessi-

ble to the user by connect-ing to the webserver resi-dent in the SH2WEB24, viasms, emails or modbus.

Hardware short circuitprotectionAs described in the “LightingCircuit Design”, if morecapacitive transformers haveto be connected in parallelfor a total load higher than180W @20°, the hardwareshort circuit protection hasto be disabled.This protection has to bedisabled via the SH tool asdescribed below in “Pro-gramming”.If the hardware short circuitprotection is enabled, it isalways active when the out-put is both on and off. If theprotection is disabled, it isactive only when the load isoff, in this situation care hasto be taken to avoid shortcircuits when the output isactive, otherwise the dimmerwill be damaged.

Programming The dimmer SH2D500WE230is fully programmable via theSH tool and the pro-grammable parameters arethe following ones:

1)Ramp time. It is the timethe dimmer takes toswitch the light on from0% to 100% (and from100% to 0%). It can beset from a minimum of 2seconds to a maximum of27 seconds

2)Load type. This dimmercan drive

- RLC load (RLC curve): e.g.incandescent, halogenlamps

- LED lamps dimmable withtrailing edge curve (P1curve)

- LED lamps dimmable withleading edge curve (P2curve)

- LED lamps dimmable withleading edge curve and nosoft start (P3 curve)

Please see LED lamp dim-ming paragraph for moredetails.3)Fail safe state. The usercan program the three dif-ferent behaviour previous-ly described.

- Output always off- Output always on- The output maintains thestatus it had before thedisconnection.

4)Short circuit protection.The user can enable/dis-able the hardware short

circuit protection.5)Scenario changing

enabled. With this optionthe user can block thechanging of a dimmingscenario in a dimmingfunction (e.g. hotel, publicplaces, …).

6)Scenario saving enabled(unlock). With this optionthe user can block thesaving of a change in ascenario in a dimmingfunction.

7)Soft start ramp. Using theSH tool, the user candefine a different soft startramp for each scenario.The soft start can be pro-grammed from 1 to 31seconds.

8)Soft stop ramp. Using theSH tool, the user candefine a different soft stopramp for each scenario.The soft stop can be pro-grammed from 1 to 31seconds.

The dimmer SH2D500WE230can also be used, coupledwith any of the smart-houselux sensor, in dimming func-tions with constant light pro-gramming.

Error Overvoltage error High temperature error Frequency error Short circuit hardware protection

Error and Warning ReadoutWarning High current warning Short circuit software protection

Rated values Current 0 to 32,000 mAVoltage 103 to 260,0 VPower 0.1 to 6500,0 WEnergy 0.1 to 99999999.9 kWh with

roll over

Electrical Values Readout

Page 4: Smart Dupline Power dimmer up to 500W with Energy Reading … · 2017-04-14 · Power supply Overvoltage cat. II (IEC 60664-1, par. 4.3.3.2) Rated operational voltage 115/240 VAC

LEDs IndicationRed LED: Always ON: LoadON, no error - 1 short blink every 4 sec-onds: High current warning(> 2.5A). The dimmer goeson working but high temper-ature might occur. Thisdepends on the time theoutput stays on and on theroom temperature. - 2 short blinks every 4seconds: Overvoltage error.To reset it, switch the dim-mer OFF. If the error appearsagain, the load must bemodified. - 3 short blinks every 4

seconds: High temperatureerror: this error will be trig-gered if the internal tempera-ture raises above 90°C.Please wait until the insidetemperature goes below70°C. The reset of the error isautomatic once the tempera-ture is within operating range. - 4 short blinks every 4seconds: Wrong frequencyerror. If the frequency of thepower supply is correct, thiserror indicates a hardwarefailure. The reset of the erroris automatic once the fre-quency is ok.

- 5 short blinks every 4seconds: Short circuit soft-ware protection active. Remove the short circuit andpress the push button on thedimmer. If the error is still present,the above procedure shouldbe repeated.

Always blinking: Hardwareshort circuit protectionactive. To reset it, switch thedimmer OFF, remove theshort circuit and switch thedimmer ON again.

Green LED:ON: Supply ONOFF: Supply OFFBlinking: LOCAL mode.

Yellow LED: if the Dupline®Bus is working properly, it isalways ON.If there is a fault on the Busit will be flashing.It is OFF if the Bus is OFF ornot connected.

4 Specifications are subject to change without notice (10.12.2013)

SH2D500WE230

LED Lamp DimmingAs described in “Program-ming”, when using LEDlamps, the dimmer needs tobe programmed with curveP1 when the LED manufac-ture recommends trailingedge dimming (capacitive),P2/P3 when the LED manu-facturer recommends lead-ing edge dimming (induc-tive). The selection of P1,P2, P3 also implements adifferent response curve.This curve is the relationshipbetween lamp brightnessand the power supplied to it.LED lamps have a differentcurve compared to standardinductive loads.Please see table here for

manufacturer’s recommen-dation. If your LED lamp isnot listed, please refer to themanufacturer for advice ontheir preference for leadingor trailing edge dimming.If many LED lamps are con-nected in parallel, we sug-gest the following rule todefine the maximum numberof LED lamps, the maximumtotal LED lamp power ≤1/10th of dimmer’s maxi-mum rated power. The maxi-mum load depends on thecapacitive input impedenceof the LED lamps, so it canvary according to the LEDlamps type.If the red LED on the

SH2D500WE230 dimmerstarts blinking continuouslyas soon as the load isapplied, this suggests thatthe total load has becomemore capacitive than induc-tive (the total capacitance isdone by the sum of thecapacitance of each con-nected LED lamp) and cannot be driven anymore bythe P2 curve.The explanation of this is asfollows, as previouslydescribed most LED lampshave to be dimmed as aninductive load with leadingedge dimming (P2), but ifmore LED lamps are con-nected in parallel, the load

becomes more capacitive(total capacitance is the sumof capacitance for each con-nected).Since a capacitive load cannot be dimmed with leadingedge dimming (because ofthe currents peaks) the dim-ming curve must be set toP1. In this situation the dim-ming performance may bereduced.A compromise betweendimming performance andthe total load that can beconnected has to be decid-ed by the installer.

LED curve selectionwww.productselection.net/manuals/uk/led_curve_selection.pdf

Page 5: Smart Dupline Power dimmer up to 500W with Energy Reading … · 2017-04-14 · Power supply Overvoltage cat. II (IEC 60664-1, par. 4.3.3.2) Rated operational voltage 115/240 VAC

Specifications are subject to change without notice (10.12.2013) 5

SH2D500WE230

Lighting Circuit DesignSome general rules have tobe taken into considerationwhen designing lighting cir-cuits.

Ferromagnetic transformersWhen using halogen lightingwith ferromagnetic trans-formers, pay attention to theoutput of the transformers.To maximise efficiency, loadthese transformers with atleast 80% of their normalpower. Pay attention to theoutput of the transformerwhen determining the totalload of the dimmer. Thetransformer has to be suit-able for dimming.

Electronic transformersElectronic transformers pre-sent a capacitive load to thedimmer but if the cablebetween the transformerand the dimmer is significantthis will introduce an addi-tional inductive load, and thedimmer would see a combi-nation of the two types ofload (inductive and capaci-tive).It is recommended that anelectronic transformer isloaded to at least 75% of it’smaximum rated loading, thisreduces the possibility oflamp flicker when dimming,as is common with electron-ic transformers. Refer to themanufacturer’s specifica-tions for the electronic trans-

former being used.Pay attention to the outputof the transformer whendetermining the total load ofthe dimmer (average effi-ciently is around 90%). Thetransformer has to be suit-able for dimming.When a capacitive load isinitially connected there maybe a substantial surge ofcurrent through the primarywinding called the inrushcurrent.This inrush current may lastfor 2-3 seconds and canhave a peak of 10 times theRMS current stated by themanufacturer of the trans-former (this is also valid forCFL fittings).If many electronic transform-

ers are connected in parallel,the value of the total currentis given by the sum of thecurrent peaks generated byeach transformer.If the total inrush current ishigher than 3.5 A, the dim-mer’s hardware short circuitprotection will be activated.As a general rule if the shortcircuit protection is enabled,a total load of 30% of thenominal dimmer outputpower can be connected tothe dimmer (180W@20°C).If the short circuit protectionis disabled, a total load of90% of the nominal dimmeroutput power can be con-nected (540W@20°C).

Derating Curve

LOAD CURVE

0

100

200

300

400

500

600

700

-20 -10 0 10 20 30 40 50Environment temperature (°C)

Max

load

(Wat

t)

AC 230 VAC 115 V

Page 6: Smart Dupline Power dimmer up to 500W with Energy Reading … · 2017-04-14 · Power supply Overvoltage cat. II (IEC 60664-1, par. 4.3.3.2) Rated operational voltage 115/240 VAC

6 Specifications are subject to change without notice (10.12.2013)

SH2D500WE230

Wiring Diagrams

Dimensions

NLN

D-D+

3535

55

14,514,544,044,0

90,0

90,0

45,0

45,0

OUT

UWP-DIM

ON

55

90,0

90,0

14,5

14,5

44,0

44,0

3535

45,0

45,0

D+ D-

OUT

SH2D

500WON

OU T

DIM

500W

ON

OUT

ON SH2D

500W

smart-house

LOUT

N

OUT

DIM

500W

ON

OUTDIM

500W

ON

LNN

NLN

NLN

L

OUT

ON SH2D

500W

smart-house

OUT

ON SH2D

500W

-houssmart e

OUT

ON SH2D

500W

smart-house

LOUT LOUT LOUT

N

L2

OUT

DIM

500W

ON

OUT

DIM

500W

ON

OUT

DIM

500W

ON

NLN

NLN

NLN

L1

L3

OUT

ON SH2D

500W

smart-house

OUT

ON SH2D

500W

smart-house

OUT

ON SH2D

500W

smart-house

LOUT LOUT LOUT

Dupline® busDupline® bus