sinkrotakt manual 5

Upload: vlado-radojsolic

Post on 16-Oct-2015

100 views

Category:

Documents


11 download

DESCRIPTION

User manual for SINKROTAKT 5

TRANSCRIPT

  • We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. ABB Switzerland Ltd

    Issued Esmaeil Habashi 00.05.03 Operating instructions No of pagesChecked Werner Zimmerli 00.07.25 SYNCHROTACT 5 39Released Werner Zimmerli 00.07.25

    Document No Art Part Language Revision Page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 1Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -

    SYNCHROTACT 5Operating instructions

    SYN 5100

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 2Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    Content1 GENERAL INFORMATIONS ....................................................................................... 3

    2 FUNCTIONAL PRINCIPLE .......................................................................................... 5

    3 HARDWARE CONSTRUCTION .................................................................................. 9

    4 PARAMETERS .......................................................................................................... 13

    5 ENGINEERING INSTRUCTIONS............................................................................... 17

    6 INSTALLATION AND DISPOSAL ............................................................................. 19

    7 OPERATING INSTRUCTIONS .................................................................................. 21

    8 COMMISSIONING...................................................................................................... 23

    9 MAINTENANCE AND FAULTS ................................................................................. 29

    10 TECHNICAL DATA.................................................................................................... 31

    11 SCHEMATIC .............................................................................................................. 35

    12 RECORD AND QUESTIONNAIRE ............................................................................ 37

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 3Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    1 General informations

    1.1 IntroductionThis User Manual is aimed at persons who have a basic knowledge of working withelectronic equipment, who understand electrical symbols in schematic diagrams, butwho know little or nothing about working with SYNCHROTACT 5 equipment.The User Manual provides the information required in order to install, commission andoperate the SYNCHROTACT 5 device of type SYN 5100.

    1.2 Marking of text sectionsGeneral warningThis symbol placed before the text indicates situations or conditions which can cause arisk of death or serious injury. The text describes the procedure for preventing theserisks.

    Dangerous voltagesThis symbol indicates that, when handling the equipment, dangerous voltages occurwhich can cause death or serious injury.The sections of text marked with "Caution" contain information on situations which canlead to material damage or equipment failure if the instructions are disregarded.

    The sections of text marked with "Note" provide additional information. This must betaken into consideration in order to prevent malfunctions.

    1.3 Purpose and use of the SYN 5100The digital synchronizer can be used for the following applications: As a paralleling monitoring device (synchrocheck) for monitoring automatic or manu-

    al paralleling sequences including dead bus.

    1.4 Manufacturers addressABB Switzerland LtdSynchronizing devices and voltage regulatorsCH-5300 Turgi/Switzerland

    Phone: +41 58 589 24 86Fax: +41 58 589 23 33Email: [email protected]: www.abb.com/synchrotact

    24 h - hot line for urgent service inquiries: +41 844 845 845

    Caution

    Note

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 4Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 5Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    2 Functional principle

    2.1 Brief descriptionThe digital synchronizing device SYNCHROTACT 5 is used as Synchrocheck formonitoring of automatic or manual paralleling of generators with lines as well as for theparalleling of already synchronized lines. The device is designed for system frequenciesof either 50/60 Hz or 16 2/3 Hz.

    The setting values are entered via the keys provided on the front side of the device.

    2.2 Paralleling functionsThe paralleling process can basically be divided into four function blocks:1. Measuring2. Voltage and frequency matching3. Monitoring of paralleling conditions4. Paralleling command generation

    The functions measuring and monitoring of the paralleling conditions are both integratedin the application of the Synchrocheck.

    U1

    U2

    UUmax

    s

    smax

    max

    U

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 6Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    2.2.1 MeasuringThe following measured variables are generated from the two single-phase measuringvoltages:Voltage U1, U2U1 is the reference voltage e.g. lineU2 sit the adjustable voltage e.g. generator.Frequency f1, f2f1 is the reference frequencyf2 is the adjustable frequency.Voltage difference UU = IU1I IU2IU > 0 Adjustable voltage is lowerU < 0 Adjustable voltage is higherSlip s

    %100*21 fnff

    s

    =

    s > 0 Adjustable frequency is less (e.g. generator is sub-synchronous)s < 0 Adjustable frequency is greater (e.g. generator is oversynchronous)Phase-angle difference

    21 = > 0 Adjustable frequency is lagging < 0 Adjustable frequency is leadingVoltage measurementThe two input voltages U1 and U2 are passed through high-impedance input resistorsand differential amplifiers. The signal for the amplitude value is formed from this byconversion and filtering . For zero-passage detection, the signal is filtered and passedthrough a comparator. The signals prepared in this way are passed to the processor viathe A/D converter.

    S00023

    U2

    U1

    SYNCHROTACT 5

    A

    D

    CPU

    Amplitude

    Amplitude

    crossingZero-

    crossingZero-

    SYN 5100

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 7Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    2.2.2 Monitoring of paralleling conditionsThe monitoring of the paralleling conditions can be divided into these parallel-functioningblocks: voltage-carrying lines no-voltage lines

    Paralleling of two voltage-carrying linesThe monitoring of the paralleling conditions enables a paralleling command (CHKRELEASE) if the following conditions are fulfilled simultaneously: the phase-angle difference is within the tolerance band the slip is within the tolerance band the voltage difference is within the tolerance band

    Paralleling of no-voltage lines (dead bus)A special case for the monitoring is the paralleling of no-voltage lines. A parallelingcommand release is only issued if the external release signal is active.

    The monitoring issues the paralleling command if the following conditions are fulfilledsimultaneously: the releasing signal for dead bus (digital input) is issued the zero voltage(s) does not exceed the set threshold U0max

    2.3 Sequences of the synchronization processThe software is initialised after switching on the auxiliary voltage and immediatelyafterwards the synchronizing process is started. The device begins issuing theparalleling command release as soon as, and as long as the paralleling conditions arefulfilled.

    The synchronizing process can be interrupted by disconnecting the auxiliary voltage.Since the device has only a monitoring function as a Synchrocheck, the synchronizingprocess can remain in operation.

    2.4 Self-monitoring of the synchronizerExtensive monitoring includes the following functions:

    2.4.1 Hardware monitoringAuxiliary voltage: The internally stabilised (reference) voltages are monitored. In theevent of inadmissible deviations, the device is immediately blocked.

    Paralleling command circuit: Contact monitoring is provided by means of forciblyguided contacts (normally closed = NC) on the command releasing relay. The deviceshould be controlled in such a way that the switching on the auxiliary voltage as well asthe command issuing circuit is only possible by closed NC contacts.

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 8Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    2.4.2 Software monitoringThe program sequence is interrupted and reset by the internal watchdog, if an erroroccurs. After reset, it is again started automatically. This starting procedure is carried outthree times, afterwards the device is totally blocked.

    2.5 Stored dataThe parameter values are permanently stored in a non-volatile memory, and are notaffected by ageing or failure of the auxiliary voltage. The parameter settings can only bechanged by means of write commands.

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 9Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    3 Hardware construction

    3.1 Type code for devices

    2: internal codeCommunication

    B: Ethernet & ModbusC: Ethernet & ProfibusD: Ethernet & Lon-Bus

    0: none1: Ethernet2: Modbus3. Profibus4: Lon-Bus

    Number of parameter sets1: 1 Parameter set7: 7 Parameter sets

    Auxiliary voltage / System frequency1: 24...48 VDC; 50/60 Hz2: 100...125 VAC/ VDC; 50/60 Hz3: 220...250 VDC; 50/60 Hz

    Synchronization mode

    02: Dual channel device

    Construction size1: Small size2: Middle size3: Large size

    SYNCHROTACTSYN = SYNCHROTACT5: fifth generation

    OptionsType

    SYN 5302 - XXXX

    S00010

    00: Synchrocheck01: Single channel device

    2 35: 100...125 VAC/VDC; 16 / Hz2 36: 220...250 VDC; 16 / Hz

    4: 24...48 VDC; 16 / Hz2 3

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 10Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    3.2 Front panelOn the front panel of the SYN 5100 there is a status display (LEDs). The built-in controlunit consisting of six keys and the display is located on the front side of the device.

    Status displays (LED)Designation FunctionU < Umaxs < smax < maxU1/U2 = 0(colour: yellow)

    Indicate if U, and s are within the tolerance bandor at least one measuring voltage is lacking.

    Control unitThe parameter settings can be viewed or modified by means of the control panel.

    The keypad consists of 6 keys with the following functions:Pre-selection key for display or change of the correspondingparameter and Enter key for saving a new setting value.

    Moving up the pre-selected parameter value

    An LED-display is used to display parameter values.

    The electrical connections are fixed with screwable connectors and spring clamps on thetop and bottom of the front side.

    cS c

    cUcUn

    cU0

    c

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 11Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    3.3 Rear of unitAt the rear side there is the snap-profile for mounting a horizontal top-hat rail.

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 12Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 13Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    4 Parameters

    4.1 Parameter tableParametersNo. Parameter name Symbol Range/resolution Unit Default setting1. Slip limit smax 0.1 to 2.0 % 0.52. Angle limit max 5 to 40/5 DEG 153. Maximum

    voltage differenceUmax 5 to 40/5 % 5

    4. Maximum zero voltage U0max 0 to 50/5 % 505. Nominal voltage Un 50 to 130/5 VAC 110

    4.2 Parameter settingsNominal voltage UnThe nominal voltage is set in volts. The nominal voltage is plant-dependent. It is typically58 (100/ 3 ); 64 (110/ 3 ); 100; 110 VAC, but can also have a different value.

    Slip limit smaxThe setting value is based on different criteria, depending on the application:a) normal synchronizationb) paralleling of synchronous linesc) paralleling of asynchronous linesa) Normal synchronizationThe slip limit values set in practice are far from placing a serious load on the machine,even in large machines. Usual setting values in synchrocheck operation for monitoringof a manual paralleling: 0.1 to 0.3 %. For monitoring of automatic paralleling: larger thanthe limiting value of the automatic device. Default setting: 0.5 %The following are a number of points which can influence the setting value: Smaller slip limits should be chosen for large and modern generators. Gas turbines are more sensitive than hydrogenerators. Lower values should be selected if fine synchronization has priority and higher

    values if fast synchronization is to take place. Lower slip values are usually selected where settings are made for synchrocheck

    operation to monitor manual synchronizing.

    b) Paralleling of synchronous linesIf only synchronous sources are paralleled, the slip limits do not need to be set

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 14Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    c) Paralleling of asynchronous lines:If two lines do not form a ring connection, the slip limits are restricted by the currentlimit permitted after paralleling. If the flow of power in a particular direction is to beavoided, the corresponding slip limit must be set to zero .

    Angle limit maxThe permissible angle limit is based on different criteria, depending on the application:a) paralleling of asynchronous sources.b) paralleling of synchronous sources.a) Paralleling of asynchronous sources:If 3,6*fn*smax*t+3 > 10 DEG (t = closing time of the circuit breaker), the value should berounded up to whole degrees. Setting values above 15 DEG are not usual. If thecalculation produces such a result, it should be checked whether the maximum slip canbe reduced. For monitoring of automatic paralleling: larger than the limiting value of theautomatic device.

    b) Paralleling of synchronous sources:The coupling reactance xK in ring mains lines and the balancing current IK flowingthrough these cause a phase shift between the two voltages U1 and U2.

    Line 1 (H.V. line)

    Line 2 (L.V. line)S00014

    ORDER

    U2

    LS

    SYNCHROTACT 5

    X T

    +P

    I TU1

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 15Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    The maximum phase shift max permitted for paralleling is calculated from the greatestphase shift which occurs plus a reserve. max is limited by the current iT = f(U1, U2, xT)flowing after paralleling.

    Maximum voltage difference UmaxMaximum permitted amplitude difference between the two voltages. usual values for generators: 1 to 5 % usual values for synchronous lines 3 to 10 %For monitoring of automatic paralleling: larger than the limiting value of the automaticdevice.Recommended setting: default setting

    Maximum zero voltage U0maxMaximum voltage at which the SYNCHROTACT 5 still recognises the measuringvoltages as zero voltage. A different value should only be set if necessary.

    Line 1 (H.V. line)

    Line 2 (L.V. line) S00015

    ORDER

    U2

    LS

    SYNCHROTACT 5

    X K

    X T

    +P I K

    I TU1

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 16Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 17Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    5 Engineering instructions

    5.1 General advice

    5.1.1 Cable connectionsCables or wires with cross sections of 0.4 mm2 to 2.5 mm2 can be connected to all theconnection terminals. It is recommended that 1 mm2 should be used for control circuitsand power supply connections; at least 1,5 mm2 should be used for measuring circuits.Connection of more than one cable to a terminal is not permitted.

    The casing must be connected with the earth potential via the connection provided forthis purpose.

    In order to prevent polarity errors, marked cables should be used for all voltagetransformers (measuring circuits).

    5.1.2 Recommended measures for long distancesFor distances >50 m, the following measures are recommended: The cables for the actual value measurement should have a cross section 2.5 mm2

    and should be twisted or shielded. The control circuits should be operated with a nominal voltage of 125 VDC in order

    to prevent inductive interference. All cables must be laid separately from high-voltage and high-current cables.

    5.2 Sequences of the synchronizing processSwitching on the paralleling point: measuring voltage, auxiliary voltage and commandcircuit are all switched-on on the device.

    The normally closed contact of the paralleling command release relay is provided toavoid the switching on, if the command release issuing contact (normally open) is in aclosed status as a result of pre-occurred error (see also the schematic diagram).

    Caution

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 18Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 19Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    6 Installation and disposalSYNCHROTACT 5 devices operate with in some cases dangerous voltages (>50 V),e.g. measuring inputs up to 170 VAC and relay outputs up to 250 VAC/VDC.Manipulations carried out on these parts can cause death or injury to the personsinvolved or damage to surrounding objects. If handled correctly and in the properenvironment, as described in these instructions, there is no risk.

    All relevant regulations must be observed during installation. It is essential that thesesafety regulations are read before starting any work on the SYNCHROTACT 5equipment.

    The safe operation of the device requires appropriate transport and proper storage,erection and installation.

    The equipment should be unpacked with the usual degree of care, without the use offorce and using suitable tools.

    The device should be checked visually for any damage caused during transport. Anycomplaints of defects caused by improper transport should be addressed immediately tothe receiving station or the last carrier.

    Only interior rooms which are dry and dust-free and which contain no gases, acid fumesor similar are suitable as sites for installation.

    6.1 Diagram of dimensions

    128

    S00024

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 20Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    6.2 FixingSnap on the device on a top-hat rail. Check for the correct fitting.

    6.3 Earthing and wiringThe casing must be connected with the earth potential via the connection provided forthis purpose.

    The use of shielded cables is not necessary. If shielded cables are nonetheless used forprotection against high-frequency interference, it is recommended that the shielding beconnected to the earth potential at both ends over as wide an area as possible. If it isnot possible to earth the cables at both ends, one of the following procedures can betaken: Earthing of the shielding via a capacitor. The shielding is earthed directly at one end

    and via a capacitor at the other end. Use of a double shielded cable: one of the two shields is earthed at one end, the

    other at the other end.

    6.4 DisposalThe inappropriate disposal of electrical equipment can lead to an environmental hazard.It is therefore important that electrical equipment be disposed of by qualified personnel.

    The metallic casing, cover and front frame do not present any environmental risk andcan be recycled.

    The circuit boards must be removed and should be disposed by a licensed disposalcompany. Environmentally harmful elements such as capacitors must be separated fromthe circuit boards.

    The SYNCHROTACT 5 devices are environmentally friendly designed. The circuitboards are easy to remove.

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 21Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    7 Operating instructions

    7.1 Operation for commissioning and maintenance purposes

    7.1.1 CommandsThe following commands can be carried out using the keypad.

    Commands Keys

    Change parameter values :Keep down the corresponding pre-selection key:

    Change the value by pressing:

    Confirm (save) the value withcorresponding pre-selection key within30 s; display blinks during this time

    7.1.2 DisplayAfter switching on the auxiliary voltage, all the elements light up for short time. The pointat the bottom right blinks. As soon as, one of the pre-selction key is pressed, itscorresponding setting value is displayed. The display is cleared 1 minute after the lastkey press.

    7.2 Operational control

    7.2.1 Starting and stopping the synchronizing processThe software is initialised after switching on the auxiliary voltage and immediatelyafterwards the synchronizing process is started. The device begins issuing theparalleling command releases as soon as, and as long as the paralleling conditions arefulfilled.

    The synchronizing process can be interrupted by disconnecting the auxiliary voltage.Since the device has only a monitoring function as a Synchrocheck, the synchronizingprocess can remain in operation.

    7.2.2 Use of the built-in control panelThe service controls are not normally required with commissioned devices. However, ifone wishes to use these, in order to read out setting values, this can be done bypressing the keys as shown in the table in section 7.1.1. The commands dont changethe functionality of the SYNCHROTACT 5, as long as, the save command is not issuedwithin 30 s after modification of the setting value.

    cS c cUn cU cU0

    c

    cS c cUn cU cU0

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 22Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 23Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    8 Commissioning

    8.1 Warnings and instructionsSYNCHROTACT 5 devices operate with in some cases dangerous voltages (>50 V),e.g. voltage transformer inputs up to 170 VAC and relay outputs up to 250 VAC/VDC.Manipulations carried out on these parts can cause death or injury to the personsinvolved or damage to surrounding objects. If handled correctly and in the properenvironment, as described in these instructions, there is no risk.

    All relevant regulations must be observed during commissioning. It is essential thatthese safety regulations are read before starting any work on the SYNCHROTACT 5equipment.

    After the device has been switched off, it must be ensured, by measuring, that nomeasuring voltages or control voltages >50 V are present at the terminals beforeanything is done to the device itself, e.g. unplugging the connector to replace the device.In order to prevent open voltage circuits being accidentally closed by third parties, thecircuits in question should be marked at the disconnection point (e.g. with a warningsign).If work is being carried out in the environment of the SYNCHROTACT 5, e.g. on therelay controls, electronics power supply, synchronizing instruments, all voltages greaterthan 50 V which are connected to the system must be switched off.

    Before switching on, always check whether all connectors are plugged in.

    The device may only be opened by qualified personnel. It is essential that ESDregulations are complied with.

    8.2 Work carried out with the machine at a standstill

    8.2.1 Wiring checkThe casing must be connected with the earth potential via the connection provided forthis purpose. All electrical connections must be checked against the system schematic(connection point and cross section).

    8.2.2 First power-upInterrupt paralleling circuit(s): Bring the machine circuit breaker or circuit breaker to Testposition, draw out the carriage or pull command relay.

    Switch on auxiliary voltage. All the elements light up on the LED-display. The the pointat the bottom right blinks.

    Caution

    Caution

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 24Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    8.2.3 Pre-setting of parametersInstructions on the correct use of the service control panel can be found in section 7Operating instructions. Advice on the parameter settings can be found in section 4.2Parameter settings.

    Some parameter settings can already be determined and set while the machine is at astandstill: Un, smax, max, Umax, U0max.

    Each single parameter setting after its modification must be confirmed within 30 s. If thisrule is not complied with, the old value remains in the memory.

    8.2.4 Comparison of measuring points and switching pointsIf there are several paralleling points, it is essential to check whether the parallelingcommand and the measuring circuits (both) go to the same circuit breaker.

    8.2.5 Test of the phase sequence and tuning of the measuring voltagesThe following tasks are the most important ones during the entire commissioning.They don't concern the synchronization device itself, but their right connectionsat the measuring voltages. In case of ignorance, damages may be caused to theplant!

    It is a prerequisite for the following work and for the correct functioning of thesynchronization that the nominal voltage Un is set.

    When disconnecting high voltage cables, it is essential that the correspondingregulations on working on high voltage installations are complied with.

    Bring the circuit breaker to operating position so that it can be operated manually.

    Note

    Caution

    Caution

    Caution

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 25Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    Closing the CB: Isolate one voltage source: open either isolator on generator side or star point

    isolator or isolator on busbar side The other voltage source must be connected Close circuit breaker

    The three LEDs U < Umax, s < smax, < max must light up now, in particular thelast one. Otherwise, either the measuring cables are incorrectly connected (in terms ofpolarity) or there is a phase shift.Incorrect polarity cannot be detected by the synchronizer. Paralleling with incorrectpolarity can lead to serious damage.

    The synchronizing instruments (double voltmeter, double frequency meter andsynchroscope) if present, must be checked. The synchronoscope must stand at twelveoclock!

    If this is not the case, the measuring circuits must be checked.

    If the synchronoscope stands at six oclock, one voltage has been incorrectlyconnected. In other positions, either measuring is being carried out on incorrect phasesor a phase shift caused by the connection group of a step-up transformer has not beencompensated.

    The circuit breaker should be opened again (or brought into test position) and theparalleling circuit interrupted.

    If it is not possible to test the phase sequence as described above, it is still essential totest the measuring circuits. For example, the phase positions can be tested using highvoltage measuring sensors.

    Note

    Isolator

    Starpoint-isolator

    CB

    S00013

    U1

    G

    SYNCHROTACT 5

    U2U = 0 = 0

    U1 = U2

    Caution

    Caution

    Caution

    Caution

    Caution

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 26Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    8.3 Work carried out while the machine is running

    8.3.1 Function testsChecking the parallelingAt the end of commissioning, blind synchronization should be carried out several times(circuit breaker in Test position). The differential voltage and the paralleling commandshould thereby be recorded using a transient recorder. At the same time, thesynchronizing process should be observed using the synchronizing instruments in theplant.

    Bring circuit breaker to operating position, adjust voltage and frequency and carry outlive synchronization. Record the synchronizing process.

    Example of a correct parallelingdU = Voltage difference u1 u2S1 = Manual paralleling commandS2 = Paralleling command release

    by SYN 5100

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 27Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    Angle error(switches too early)Possible causes: -measuring incorrect (phase

    error) Manual paralleling switch

    closed to early or automaticsynchronizing device wronglyset

    Angle error(switches too late)Possible causes: - measuring incorrect (phase

    error) Manual paralleling switch

    closed to late or automaticsynchronizing device wronglyset

    Slip too big/angle errorPossible causes: smax set too high

    Voltage differencePossible causes: Umax set too high Measuring error

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 28Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    8.3.2 Keeping recordsIf parameter settings are carried out, these should be entered in the settings record atthe end of this operating manual.

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 29Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    9 Maintenance and faults

    9.1 MaintenanceSYNCHROTACT 5 does not require any maintenance. In order to detect faults in goodtime before use, test synchronizing is recommended (external test circuit). However, themachine must be available for this purpose.

    9.2 Faults

    9.2.1 GeneralSYNCHROTACT 5 devices operate with in some cases dangerous voltages (>50 V),e.g. voltage transformer inputs up to 170 VAC and relay outputs up to 250 VAC/VDC.Manipulations carried out on these parts can cause death or injury to the personsinvolved or damage to surrounding objects. If handled correctly and in the properenvironment, as described in these instructions, there is no risk.

    All relevant regulations must be observed during fault-rectification. It is essential thatthese safety regulations are read before starting any work on the SYNCHROTACT 5equipment.

    If work is being carried out in the environment of the SYNCHROTACT 5, e.g. on therelay controls, electronics power supply, synchronizing instruments, all voltages greaterthan 50 V which are connected to the system must be switched off. In order to preventopen voltage circuits being accidentally closed by third parties, the circuits in questionshould be marked at the disconnection point (e.g. with a warning sign).Before switching on again, all connectors must always be plugged in.

    9.2.2 TroubleshootingFirst of all it is important to ensure that the cabling of the synchronizing device is ok,prior to sending the device (in vain) for repair.In order to interpret a fault more accurately, it is important to make a distinction as towhich phase the synchronizer is currently in:1. System testing2. Commissioning3. Operation

    System testing Is the wiring correct? Does the test method correspond to reality?

    CommissioningFaults which occur during commissioning often have their cause in incorrect handling,incorrect settings, inadmissible external conditions or connection errors at the interfacebetween plant and synchronizing system.

    Caution

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 30Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    The simplest way to check the synchronization is using the synchronoscope.

    If it seems that the SYNCHROTACT should really have acted by now, you should checkwhich conditions could not be fulfilled. This can be seen simply from the LEDsU < Umax, s < smax and < max. All three conditions must always be fulfilled(LEDs lit), in order for a command release to be issued.Some governors do not operate in a very stable manner. The set tolerance band for theslip can often not be achieved for a long time, or not at all. In this case the problem maybe remedied by increasing the smax settings. However, you should not go beyond theusual values of 0.1 to 0.3 % without making sure that the machine can withstand this(see section 4.2).Following commissioning (operation)In this case, setting errors can usually be ruled out. It should be considered whether anychanges were made to the plant prior to the failed synchronization which could affect thesynchronizing process.

    Otherwise, poor contacts, dropped connections, malfunctioning relays or tripped fusesmay be the cause.

    9.2.3 Fault rectification

    Replacing a SYNCHROTACT 5If a device is replaced, the circuit breaker must be set to test position or its commandcircuit must be interrupted to ensure that it can no longer be actuated.

    1. Switch off SYNCHROTACT 5 and isolate all voltages which are still present from theSYNCHROTACT 5

    It must be ensured, by measuring, that no measuring voltages or control voltages >50 Vare present at the terminals before anything is done to the device itself .

    2. Connectors: loosen screws and unplug connectors

    3. Press the device down, then tilt up and remove.

    The replacement unit is installed in the reverse order. The commissioning and functioncheck of the replacement unit is carried out as described in the section onCommissioning. As soon as the settings are known, these can be used (refer to settingsrecord).Sending the device in for repairIf it has been definitely established that the synchronizer is defective, it must be sent infor repair. In order to guarantee that repairs proceed smoothly, it is essential that thequestionnaire at the end of the document is filled in and sent to the responsible ABBdepartment together with a copy of the settings record and the device.

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 31Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    10 Technical data

    10.1 InputsAuxiliary voltageNominal voltage ranges 50 to 130 VAC

    100 to 125 VDCPermissible voltage range 0,75 to 1,25*UnMaximum power consumption 2 W/4 VA

    Measuring inputs U1, U2Nominal voltage range 50 to 130 VACVoltage range 0 to 130 % UnNominal frequency 162/3 or 50/60 HzFrequency range 10 to 100 HzMaximum current consumption per channel

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 32Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    10.4 Environmental values

    10.4.1 IsolationDielectric test IEC 255-5 2 kVImpulse voltage test IEC 255-5 5 kV

    10.4.2 Climatic stabilityTemperature ranges:Transport/storage -40 to +85 CFunctionable -25 to +70 COperation (compliance with technical data) -10 to +55 CTests:Cold IEC 60068-2-1 -25 CDry heat IEC 60068-2-2 +70 C; 16 hDamp heat, steady state IEC 60068-2-3 Ca 4 daysDamp heat, cyclic IEC 60068-2-30 55 C/2 cyclesChange of temperature IEC 60068-2-14 Nb; 1C/min.

    10.4.3 Mechanical stabilityVibrationVibration responseEndurance

    IEC 60255-21-1 10 to 150 Hz; Kl. 21 g2 g

    Shocks and bumpsShock responseWithstandBump

    IEC 60255-21-2 class 210 g30 g20 g

    EarthquakeSingle-axis sine sweep seismic test IEC 60255-21-3

    IEEE STD 344-1987Method A5g in each axis

    10.4.4 Interference immunity/transmission (EMC)Emission, terminal disturbance EN 55011/

    CISPR 110,15 to 0,5 MHz: 79 dB0,5 to 30 MHz: 73 dB

    Emission, radiation disturbance EN 55011/CISPR 11

    30 to 230 MHz: 30 dB230 to 1000MHz:37dB

    Electrostatic discharges IEC 61000-4-2 Contact: 6 kVAir: 8 kV

    Electromagnetic fields IEC 61000-4-6

    IEC 61000-4-3

    0,15 to 80 MHz10 V; 80 % AM80 to 1000 MHz10 V/m; 80 % AMand PM (900 MHz)

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 33Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    Fast transients/Bursts IEC 61000-4-4 2 kV / 4 kVSurge voltage IEC 61000-4-5 0,5 / 1 / 2 / 4 kVVoltage dips IEC 61000-4-11 AC:

    30 %: 10 ms60 %: 100 ms>95 %: 5000 ms

    1 MHz burst disturbancecommon modedifferential mode

    IEC 60255-22-12,5 kV1 kV

    10.5 Relevant standardsCE conformityEMC directive:Generic standard

    Low voltage directive:Safety of information technologyequipment

    89/336/EWGEN 50081-2EN 50082-273/23/EWGEN 60950

    EmissionImmunity

    Product standardsMeasuring relays and protectionequipmentProduct standard for measuring re-lays and protection equipmentHydro Qubc standard for electro-nic equipment and relays

    IEC 60255-6

    EN 50263

    SN-62.1008d

    10.6 Construction dataProtection type according to IEC 60529

    IP 40

    WeightSYN 5100 0.3 kg

    Installation altitude

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 34Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 35Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    11 Schematic

    MEASURING U1

    PARALLELING ORDERRELEASE

    MEASURING U2

    SYNCHROTACT 5SYN 5100

    V/V

    f/

    f

    -X1:1-X1:2-X1:3-X1:4

    -X1:6-X1:7-X1:8-X1:9

    -X2:1-X2:2-X2:3-X2:4

    L1L2L3

    L1L2L3

    CB

    ACSYSTEM 1

    ACSYSTEM 2

    EXCITATION

    GOVERNOR S51000

    -X1:14

    -X1:15-X1:13

    0 5 24V

    -X1:11-X1:12

    RELEASEDB0V

    AUX. VOLTAGE

    CONTROL INPUT

    UCTRL:+24VDC/48VDC

    f-

    f+

    U+

    U-

    +

    +

    +

    -

    MANUAL PARALLELLINGSWITCH

    -X2:5-X2:6

    -X1:5

    OUT 1

    OUT 2

    OUT 3

    -X1:10

    50 to 130VAC100 to 125VDC

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 36Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 37Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    12 Record and questionnaire

    12.1 Settings record for SYNCHROTACT 5

    Name and address of customer: ________________________________________

    ________________________________________

    ________________________________________

    Plant: ________________________________________

    Order no.: ________________________________________

    Plant schematic no.: ________________________________________

    Device identification:

    Type plate:

    Delivery date: ________________________________________

    Software number: ________________________________________

    Remarks:

    Place and date of commissioning:Name: Company:

    Important: Please send a copy of the record to the following address:

    ABB Switzerland LtdDept. ATPECH-5300 TurgiTelefax: +41 58 589 23 33

    Parameter settingsSynchrocheck Abbreviation Value Unit

    1 Synchrocheckparameters

    1.1 Slip limit smax %1.2 Angle limit max DEG1.3 Max. voltage difference Umax %1.4 Max. zero voltage U0max %1.5 Nominal voltage Un VAC

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 38Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    12.2 SYNCHROTACT 5 QuestionnaireIs the unit under guarantee?Yes

    NoFault detection? (YY/MM/DD):______________________________________

    Plant

    Customers address

    Tech. Contact Pers.

    Telephone No.

    Fax. No.

    ___________________

    ___________________

    ___________________

    ___________________

    ___________________

    Commissioning date? (YY/MM/DD):_____________________________________

    Type plate:Ident. number Manufacturing no. Type_______________________________________________________________________________

    ____________________________________________________________________________Configuration:Supply/control voltage.VDC/........VDCNominal measuring voltage..VACAmbient temperature..C

    Replacement unit used? Yes No

    Description of type of fault:

    Request

    Test only

    Repair and test

    Status of Display and LED`s when faultoccurred

    Display:............................................................................................................

    ......................................................

    ......................................................

    LED U

  • Operating Instructions SYN 5100

    Document No Art Part Language Revision page

    abb ABB Switzerland Ltd 3BHS109760 E01 en B 39Template: CHIND Techn doc stand, A4 P de, R1.DOT; Filename: 109760eb.doc; Print: 05.03.2002 00:00; Save: 04.03.2002 23:32; CHIND No. 3BHS109763 ZAB D14 Rev. -; I-Q

    ModificationsRev.Ind.

    Page (P)Section (S)

    Descriptions(or revision status)

    DateDept./Exec.

    A All sections Completely revised 00.07.06;ICA/WZ

    B S 2.5 New 02.01.07;ATP/WZ

    B S 3 and S 4 Completely revised:- Division into two main sections (S 3 and S 4)- Adaptation of the type code- Section on parameter settings moved from the

    section on commissioning to section 4

    02.01.07;ATP/WZ

    B S 8.3.1 Addition of the key to the signals and values of thetransient recorder

    02.01.07;ATP/WZ

    B S 10 Additions to technical data:- Current consumption of the measuring inputs

    02.01.07;ATP/WZ

    B Insertion of this table 02.01.07;ATP/WZ