DAY DESIGN PTY LTD A.B.N. 73 107 291 494 C O N S U L T I N G A C O U S T I C A L E N G I N E E R S A IRCRAFT , R OAD T RAFFIC AND T RAIN N OISE C ONTROL A RCHITECTURAL A COUSTICS I NDUSTRIAL N OISE AND V IBRATION C ONTROL E NVIRONMENTAL N OISE I MPACT I NVESTIGATION AND C ONTROL O CCUPATIONAL N OISE I NVESTIGATIONS Q UIET P RODUCT D EVELOPMENT Suite 17, 808 Forest Road Peakhurst Sydney NSW 2210 Phone: (02) 9584 2639 Fax: (02) 9584 2619 Email: [email protected] www.daydesign.com.au AIRBORNE SOUND TRANSMISSION LOSS M PANEL 75 mm M PANEL REPORT NUMBER: 4854 PREPARED FOR: M Panel Pty Ltd 3/15 Works Place Milperra NSW 2214 Attention: Mr Don Yu Telephone: (02) 9792 5300 DATE ISSUED: 25 June 2012 Report Status Prepared by: Alex Li Approved by: Stephen Gauld Final Document R\4854-r1, 10 pages plus attachments Sigma Panel(M Panel) www.soovee.cn

Upload: farhan

Post on 18-Mar-2016

223 views

Category:

Documents


3 download

DESCRIPTION

 

TRANSCRIPT

Page 1: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

A.B.N. 73 107 291 494

C O N S U L T I N G A C O U S T I C A L E N G I N E E R S

• A I R C R A F T , R O A D T R A F F I C A N D T R A I N N O I S E C O N T R O L

• A R C H I T E C T U R A L A C O U S T I C S • I N D U S T R I A L N O I S E A N D V I B R A T I O N C O N T R O L

• E N V I R O N M E N T A L N O I S E I M P A C T I N V E S T I G A T I O N A N D C O N T R O L

• O C C U P A T I O N A L N O I S E I N V E S T I G A T I O N S • Q U I E T P R O D U C T D E V E L O P M E N T

Suite 17, 808 Forest Road Peakhurst Sydney NSW 2210

Phone: (02) 9584 2639 Fax: (02) 9584 2619 Email: [email protected]

www.daydesign.com.au

AIRBORNE SOUND TRANSMISSION LOSS

M PANEL

75 mm M PANEL

REPORT NUMBER:

4854

PREPARED FOR:

M Panel Pty Ltd 3/15 Works Place Milperra NSW 2214 Attention: Mr Don Yu Telephone: (02) 9792 5300

DATE ISSUED: 25 June 2012

Report Status Prepared by: Alex Li Approved by: Stephen Gauld

Final

Document R\4854-r1, 10 pages plus attachments

Sigma Panel(M Panel)

www.soovee.cn

Page 2: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 2

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

TABLE OF CONTENTS

1.0 INTRODUCTION ....................................................................................................3

2.0 INSTRUMENTATION ............................................................................................3

3.0 ACOUSTIC TEST LABORATORY .....................................................................4

4.0 MEASUREMENT PROCEDURE ..........................................................................5

4.1 Reverberation Time (T60) .......................................................................................................5

4.2 Equivalent Absorption Area (A).............................................................................................6

4.3 Sound Reduction Index (R) ....................................................................................................6

4.4 Weighted Sound Reduction Index (Rw) & Correction Factor (Ctr) .........................................6

5.0 TEST SPECIMEN DESCRIPTION AND RESULTS ........................................8

Sigma Panel(M Panel)

www.soovee.cn

Page 3: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 3

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

1.0 INTRODUCTION

Day Design was commissioned by M Panel Pty Ltd to measure the airborne sound transmission loss of their 75 mm thick M Panel, in the twin reverberation rooms at the National Acoustic Laboratories generally in accordance with Australian Standard AS 1191-2002: “Acoustics – Method for Laboratory Measurement of Airborne Sound Insulation of Building Elements”.

The standard test aperture was reduced in height to 3 m as the test specimen panels were only available in 3 m lengths. An acoustic bulkhead of considerably much higher noise attenuation was constructed to maintain the acoustic integrity of the test setup.

The test specimen was rated in accordance with AS/NZS ISO 717.1:2004 “Acoustics – Rating of Sound Insulation in buildings and of building elements”.

2.0 INSTRUMENTATION

Measurements and analysis were made with instrumentation as follows in Table 2.1:

Table 2.1 Instrumentation

Description Serial No.

Brüel and Kjær “PULSE” Data Acquisition Unit type 3560C

Brüel and Kjær Cathode Follower type 2669

Brüel and Kjær Cathode Follower type 2660

Brüel and Kjær Microphone type 4144

Brüel and Kjær Microphone type 4179

Brüel and Kjær Microphone Power Supply type 2807

Brüel and Kjær Measuring Amplifier type 2636

Brüel and Kjær Sound Level Calibrator type 4231

Yamaha Professional Sound Sources type S500 (2x units)

Murray 100 Watt Amplifier type MA534

Vaisala Digital Barometer type PTB201AD

Testo Temperature/Humidity Logger, type 177-H1

2336733

1888716

1097420

439142

1052016

1263220

1193776

2095415

1068 & 1069

15

R3330001

00886924

All acoustic instrument systems have been laboratory calibrated using instrumentation traceable to Australian National Standards and certified within the last two years thus conforming to Australian Standards. The acoustic measurement system was also calibrated at 1,000 Hz prior to and after the noise level measurements. Calibration drift was found to be less than 0.5 dB during the measurements.

Sigma Panel(M Panel)

www.soovee.cn

Page 4: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 4

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

3.0 ACOUSTIC TEST LABORATORY

Location: National Acoustic Laboratories

126 Greville Street, Chatswood, NSW.

Room Construction: The twin Reverberation Rooms were used for the acoustical measurements with the test specimen installed in the aperture. The rooms are of concrete and masonry construction, each having an internal volume of approximately 200 cubic metres. The floors are pentagonally shaped and the ceilings are inclined so that no two surfaces are parallel. The rooms are vibration and sound isolated from the enclosing building, being floated on steel springs and rubber dampers below the concrete floor.

Large panels of 19 mm thick plywood, heavily coated with an epoxy resin are suspended inside the test room in random orientation to aid in the diffusion of the sound field.

Room Surface Area: 231 m2

Bulkhead Construction:

The bulkhead consisted of:

- 2 rows of 90 mm timber studs separated by 15 mm

- 2 layers of 13 mm standard plasterboard (density 8.4 kg/m2) and 2 layers of 13 mm Knauf QuadShield (density 11.7 kg/m2) fixed to the source room side studs

- 2 layers of 13 mm Knauf Permarock (density 15 kg/m2) and 2 layers of 13 mm sound-rated plasterboard (density 12.3 kg/m2) fixed to the receive room side studs

- 75 mm thick R1.5 glasswool insulation fitted between each row of studs

- 2 layers of 17 mm thick plywood directly fixed to the underside of the bulkhead

- The bulkhead is estimated to have a weighted sound insulation rating of Rw 75 and Rw + Ctr 66

Test Wall: The test wall consisted of:

- Single leaf of 75 mm thick M Panel

- M Panel is of composite material consisting 63 mm polystyrene magnesium-sulfate mix core sandwiched between two sheets of 6 mm magnesium oxide board (overall surface density 48 kg/m2)

Date of Construction:

Friday 8th June, 2012

Date of Test: Tuesday 12th June, 2012

Sigma Panel(M Panel)

www.soovee.cn

Page 5: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 5

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

4.0 MEASUREMENT PROCEDURE

Before testing commenced, the reverberation room temperature, relative humidity and barometric air pressure were noted. The measurement microphones were acoustically calibrated and the acoustical noise floor of the room checked.

All reverberation rooms have small space variations of the sound field distribution and time variations in sound field decay (of reverberation time) during the measurement period. The gathering of meaningful results therefore requires multiple measurements to determine the extent of these variations. The testing procedure uses 48 sets of data to determine the spread of results around the estimate of the mean, each set containing 18 measurements of one-third octave reverberation times.

The two reverberation rooms are identified as the Reverberation Room and the Diffuse Field Room; the Reverberation Room being the room where noise is generated, and the Diffuse Field Room is the room on the other side of the test specimen measuring the transmitted noise levels.

The suite of data is divided into two sets of 24 measurements. The first set consists of sound pressure level measurements in the Reverberation Room and Diffuse Field Room measured simultaneously as noise is generated in the Reverberation Room and is transmitted into the Diffuse Field Room. Sound pressure levels are measured at 12 different locations in each of the two rooms to obtain a spatial average of the sound pressure levels in the rooms. Measurements of sound transmission loss were carried out in accordance to AS 1191-2002: “Acoustics – Method for Laboratory Measurements of Airborne Sound Insulation of Building Elements”.

The second set of measurements are of the reverberation times in the Diffuse Field Room, which determines the absorption characteristics of the Diffuse Field Room. The measurements consist of a spatial average of six different combinations of two loudspeakers and three microphone positions, and four measurements taken at each combination for a time average to obtain an estimate of the reverberation time precision.

This space-time measurement data was computer processed on a pre-configured Excel spreadsheet to obtain a final average and standard deviation for the test specimen results. The calculations provide sound absorption coefficients and precision level of the measurements to a 95% confidence level.

4.1 Reverberation Time (T60)

The reverberation time, T60, is the time it takes for a noise source to decay by 60 dB. A “live” room, such as a reverberation room, which consist of only hard surfaces will typically have a long reverberation time. A “dead” room, such as an anechoic chamber, which consist of highly absorptive surfaces, will have a much shorter reverberation time.

Measurement of the reverberation time in the Receiving Room allows us to adjust the measured sound reduction to account for the sound energy absorption by the room.

Sigma Panel(M Panel)

www.soovee.cn

Page 6: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 6

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

4.2 Equivalent Absorption Area (A)

The equivalent absorption area, A, of the receiving room is obtained from the measured reverberation time, T, at each one-third octave centre frequency by use of the following equation:

A =

where V = volume of receiving room (m3)

T = space-averaged reverberation time of receiving room (seconds)

4.3 Sound Reduction Index (R)

The Sound Reduction Index, R, is the ratio of the incident sound power to the transmitted sound power through a building element. It is expressed as:

R = 2

1

W

W

where 1W = sound power incident on the element under test (watts)

2W = sound power transmitted through and radiated by the element under test

(watts)

However, as sound powers cannot be measured directly, the Sound Reduction Index has been redefined in AS 1191-2002 in terms of sound pressure levels. The Sound Reduction Index is derived from the following equation:

R = ( )ASLL pp log1021 +−

where 1pL = average sound pressure level in the source room (dB)

2pL = average sound pressure level in the receiving room (dB)

S = area of building element specimen under test (m2)

A = equivalent absorption area in receiving room (m2)

4.4 Weighted Sound Reduction Index (Rw) & Correction Factor (Ctr)

The weighted sound reduction index (Rw) as described in Australian Standard AS/NZS ISO 717.1:2004 provides an acoustic rating for the sound insulation of walls and partitions subject to airborne sounds having a spectrum similar to that of the human voice, which is typically of a mid-to-high frequency character.

T

V16.0

Sigma Panel(M Panel)

www.soovee.cn

Page 7: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 7

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

Sound insulation varies with frequency and is dependant on the type of material and construction. However, the Rw provides a convenient method of rating sound insulation using a single number. The higher the Rw rating the better the sound insulation provided by the partition.

The Rw rating is determined by comparing the measured sound reduction indices against a set of reference values between one-third-octave band centre frequency range of 100 Hz to 3150 Hz, as specified in AS/NSZ ISO 717.1:2004.

The reference data is then amplitude shifted in 1 dB increments across the spectrum until the sum of the unfavourable deviations is as large as possible without exceeding 32 dB. (The unfavourable deviation is the difference between the measured data and the reference data where the measured data is less than the reference data).

The spectrum adaptation terms C and Ctr are applied to the sound reduction index to account for the different spectra of noise sources that the specimen can be exposed to. The adaptation term C is used for sources such as children playing and highway road traffic noise, which have a wide energy distribution in their noise spectra. The adaptation term Ctr is used for noise sources such as aircraft noise (at long distance), slow railway traffic, and disco music, which has a high concentration of energy in the low frequency range of the measurement spectrum.

Sigma Panel(M Panel)

www.soovee.cn

Page 8: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 8

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

5.0 TEST SPECIMEN DESCRIPTION AND RESULTS

A wall system consisting of a single leaf of 75 mm M Panel was constructed in the reduced aperture between the two reverberation rooms at the National Acoustic Laboratories as shown in Figure 1 below. Due to the limited size of the test panels, an acoustic bulkhead of considerably higher transmission loss was constructed in the 10 m2 aperture between the reverberation rooms to reduce the effective test area to 8.7 m2 to accommodate the test panels. Any gaps between the panels and around the aperture perimeter were sealed using a hard-setting adhesive.

Figure 1. M Panel wall with acoustic bulkhead

Figure 2. Close-up of M Panel wall and acoustic bulkhead

Sigma Panel(M Panel)

www.soovee.cn

Page 9: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 9

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

Sound reduction indices (rounded to the nearest one-tenth decibel) are tabulated for each one-third-octave band tested, and presented in Table 1.

Table 1 Measured Sound Reduction Index

1/3 Octave Band Centre Frequency (Hz) Sound Reduction Index (dB)

1/3 Octave 1/1 Octave

100 25

125 22 23

160 25

200 25

250 27 26

315 28

400 26

500 25 27

630 31

800 34

1000 36 36

1250 38

1600 41

2000 41 42

2500 45

3150 47

4000 50 49

5000 53

Rw (C;Ctr) 34 (-1;-3)

The 75 mm M Panel wall achieved a weighted sound reduction index of Rw (C;Ctr) = 34 (-1;-3).

Sigma Panel(M Panel)

www.soovee.cn

Page 10: Sigmapanel(m panel) single layer

DAY DESIGN PTY LTD

75 mm M PANEL Report 4854 Page 10

Document: 4854-r1

M PANEL PTY LTD

25 Jun 12

Test measurements and calculations were conducted by the undersigned.

Alex Li, BE (Mech) Hons

Consulting Acoustical Engineer

for and on behalf of Day Design Pty Ltd.

AAAC MEMBERSHIP

Day Design Pty Ltd is a member company of the Association of Australian Acoustical Consultants, and the work herein reported has been performed in accordance with the terms of membership.

Attachments:

• Test Certificate 4854 – 75 mm M Panel Wall

Sigma Panel(M Panel)

www.soovee.cn

Page 11: Sigmapanel(m panel) single layer

Client: Test Specimen:

M Panel

Australian Standards: Measured generally in accordance to AS 1191-2002Rated to AS/NZS ISO 717.1:2004

Test Specimen Dimensions:3.00 m (H) x 2.89 m (W)

Test Location:Twin Reverberation RoomsNational Acoustic Laboratories126 Greville Street, Chatswood NSW

Instrumentation:Brüel and Kjær Pulse Analyser type 3560CBrüel and Kjær Cathode Follower type 2669Brüel and Kjær Cathode Follower type 2660Brüel and Kjær Microphone type 4144Brüel and Kjær Microphone type 4179Brüel and Kjær Sound Level Calibrator type 4231Brüel and Kjær Microphone Power Supply type 2807Yamaha Professional Sound Sources type S500 (2x units)Murray 100 Watt Amplifier type MA534Testo Temperature/Humidity Logger, type 177-H1

5000 53

Rw (C;Ctr) 34 ( -1 ; -3 )

3150 474000 50 49

2000 41 42 2500 45

1250 381600 41

800 341000 36 36

500 25 27630 31

315 28400 26

200 25250 27 26

125 22 23160 25

Frequency - HzSound Reduction Index - dB1/3 Octave 1/1 Octave

100 25

(Surface density 48 kg/m2)

M PANEL WALL SYSTEMSOUND TRANSMISSION LOSS

TEST CERTIFICATE

D A Y D A Y D A Y D A Y

D E S I G N D E S I G N D E S I G N D E S I G N Test 4854

D E S I G ND E S I G ND E S I G ND E S I G N

75 mm M Panel3/15 Works PlaceMilperra NSW 2214

..................................................................

Date of Test: Test Engineer: Alex Li, BE(Mech) Hons

Project Number: For and on behalf of Day Design Pty Ltd

Tuesday, 12 June 2012

4854

0

5

10

15

20

25

30

35

40

45

50

55

60

100 125 160 200 250 315 400 500 630 800 1000 1250 1600 2000 2500 3150 4000 5000

So

un

d R

edu

ctio

n In

dex

(d

B)

Frequency (Hz)

1/3 Octave Transmission Loss Rw-34 Curve

Sigma Panel(M Panel)