Seismic Design Requirements City of Medford Municipal Code Chapter 9 Presented by the Building Safety Department

Upload: lamdan

Post on 01-Feb-2018

237 views

Category:

Documents


2 download

TRANSCRIPT

Page 1: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

City of Medford Municipal CodeChapter 9

Presented by the

Building Safety Department

Page 2: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design RequirementsTHESE PROVISIONS PRESCRIBE THE DESIGN REQUIREMENTS OF EXISTING BUILDINGS UNDERGOING:

CHANGE OF OCCUPANCYADDITIONSALTERATIONS

SECTION 9.600

Page 3: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

FOR CHANGE OF OCCUPANCY AND STRUCTURAL ADDITIONS THE DESIGN STANDARD SHALL BE THE CURRENT EDITION OF OREGON STRUCTURAL SPECIALTY CODE.FOR OTHER WORK COVERED UNDER THESE PROVISIONS THE DESIGN STANDARD SHALL BE FEMA 178, NEHRP HANDBOOK FOR THE SEISMIC EVALUATION OF EXISTING BUILDINGS.

SECTION 9.610

Page 4: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

THE USE OR CHARACTER OF A QUALIFIED HISTORIC BUILDING OR PROPERTY, OR PORTION THERE OF, SHALL BE PERMITTED TO CONTINUE IN USE REGARDLESS OF ANY PERIOD OF TIME IT MAY HAVE BEEN UNOCCUPIED OR IN OTHER USE;PROVIDED THE BUILDING OR PROPERTY OTHERWISE CONFORMS TO ALL APPLICABLE REQUIREMENTS OF THIS CHAPTER.

SECTION 9.615

Page 5: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

THE TABLE BELOW IS USED TO CLASSIFY THE RELATIVE HAZARD OF ALL BUILDING OCCUPANCIES;

RELATIVE HAZARD OCC. CLASSIFICATION5 (HIGHEST) A, E,I-1.1, 1-3, H-1, H-3, H-6,

H-7 4 R-1, SR, 1-2, 1-3.13 B, I-1.2, I-1.3, M2 F, S, H-4, H-51 (LOWEST) R-3, U

SECTION 9.620

Page 6: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

AN OCCUPANCY CHANGE OF THE SAME OR A LOWER RELATIVE HAZARD CLASSIFICATION NUMBER WILL NOT REQUIRE SIESMIC IMPROVEMENTS,UNLESS THE CHANGE RESULTS IN AN OCCUPANT LOAD INCREASE OF MORE THAN 20%

SECTION 9.620

Page 7: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

AN OCCUPANCY CHANGE TO A HIGHER RELATIVE HAZARD CLASSIFICATION NUMBER WILL NOT REQUIRE SEISMIC IMPROVEMENTS,WHEN THE NET FLOOR AREA OF THE CHANGED PORTION OCCUPIES LESS THAN 15% OF THE NET FLOOR AREA OF THE BUILDING AND WHERE THE CHANGE DOES NOT RESULT IN AN INCREASE IN OCCUPANT LOAD AS DEFINED BY THE OREGON STRUCTURAL SPECIALTY CODE OF MORE THAN 100 PERSONS.

SECTION 9.620

Page 8: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

ALL OTHER CHANGES TO A HIGHER RELATIVE HAZARD OCUPANCY WILL REQUIRE SEISMIC IMPROVEMENTS USING THE CURRENT EDITION OF THE OREGON STRUCTURAL SPECIALTY CODE.

SECTION 9.620

Page 9: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

ALL STRUCTURES, WHICH ARE BEING CONVERTED TO ESSENTIAL FACILITIES, AS DEFINED IN THE OREGON STRUCTURAL SPECIALTY CODE, SHALL COMPLY WITH CURRENT SEISMIC REQUIREMENTS, REGARDLESS OF OTHER REQUIREMENTS IN THIS SECTION.

SECTION 9.620

Page 10: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design RequirementsAN ADDITION THAT IS NOT STRUCTURALLY INDEPENDENT FROM AN EXISTING BUILDING SHALL BE DESIGNED AND CONSTRUCTED SUCH THAT THE ENTIRE BUILDING CONFORMS TO THE SEISMIC FORCE RESISTANCE REQUIREMENTS FOR NEW BUILDINGS UNLESS THE FOLLOWING THREE CONDITIONS ARE MET:

SECTION 9.625

Page 11: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

THE ADDITION SHALL COMPLY WITH THE REQUIREMENTS FOR NEW BUILDINGS, ANDTHE ADDITION SHALL NOT INCREASE THE SEISMIC FORCES IN ANY STRUCTURAL ELEMENT OF THE BUILDING BY MORE THAN 5 PERCENT UNLESS THE CAPACITY OF THE ELEMENT SUBJECT TO THE INCREASED FORCES IS EQUAL TO OR GREATER THAN THAT REQUIRED FOR NEW BUILDINGS, AND

SECTION 9.625

Page 12: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

THE ADDITION SHALL NOT DECREASE THE SEISMIC RESISTANCE OF ANY STRUCTURAL ELEMENT OF THEEXISTING BUILDING UNLESS THE REDUCED SEISMIC RESISTANCE OF THE ELEMENT IS EQUAL TO OR GREATER THAN THAT REQUIRED FOR NEW BUILDINGS.

SECTION 9.625

Page 13: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

IF A BUILDING IS DAMAGED BY FIRE, ALL DAMAGED LATERAL LOAD RESISTING COMPONENTS OF A BUILDING’S STRUCTURAL SYSTEM MUST BE DESIGNED AND REBUILT TO CURRENT PROVISIONS OF THE OREGON STRUCTURAL SPECIALTY CODE.

SECTION 9.630

Page 14: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design RequirementsTHESE COMPONENTS MUST ALSO BE CONNECTED TO THE BALANCE OF THE UNDAMAGED LATERAL LOAD RESISTING SYSTEM IN CONFORMANCE WITH CURRENT CODE PROVISIONS. UNDAMAGED COMPONENTS NEED NOT BE UPGRADED TO CURRENT LATERAL LOAD PROVISIONS OF THE CURRENT CODE, UNLESS REQUIRED BY OTHER PROVISIONS OF THE OREGON STRUCTURAL SPECIALTY CODE.

SECTION 9.630

Page 15: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design RequirementsWHEN AND ALTERATION, FOR WHICH A BUILDING PERMIT IS REQUIRED, HAS A VALUE OF MORE THAN $100,000 A FEMA 178 EVALUATION IS REQUIRED. A LETTER OF INTENT TO HAVE A FEMA 178 EVALUATION PERFORMED MAY BE SUBMITTED ALONG WITH THE PERMIT APPLICATION. THE EVALUATION MUST BE COMPLETED BEFORE ANY FUTURE PERMITS WILL BE ISSUED. THE FOLLOWING SHALL BE EXEMPTED FROM THIS REQUIREMENT:

SECTION 9.635

Page 16: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

BUILDINGS CONSTRUCTED OR RENOVATED TO SEISMIC ZONE 2, 2B OR 3 UNDER A PERMIT ISSUED AFTER JANUARY 1, 1974.ONE-AND-TWO FAMILY DWELLINGS.SINGLE STORY, LIGHT METAL BUILDINGS LESS THAN 5,000 SQUARE FEET IN AREA.LIGHT WOOD BUILDINGS LESS THAN 5,000 SQUARE FEET IN AREA.A PREVIOUSLY PREPARED SEISMIC STUDY MAY BE SUBMITTED FOR CONSIDERATION BY THE DEPARTMENT AS EQUIVALENT TO A FEMA 178 EVALUATION.

SECTION 9.635

Page 17: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS AND REPAIRS IN UNREINFORCED MASONRYBUILDINGS, AS FOLLOWS:WHEN THE ROOF COVERING IS REPAIRED OR REPLACED, THE BUILDING STRUCTURAL ROOF SYSTEM, ANCHORAGE, AND PARAPET SHALL BE REPAIRED AND REHABILITATED PER APPENDIX C OF THE DESIGN STANDARDS-FEMA 178, OR

SECTION 9.640

Page 18: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

WHEN THE COST OF ALTERATION WORK WHICH REQUIRES A BUILDING PERMIT IN A 2 YEAR PERIOD EXCEEDS A $15 PER SQUARE FOOT FOR THE TOTAL NET FLOOR AREA IN THE BUILDING, THEN THE BUILDING SHALL BE IMPROVED SEISMICALLY PER SECTION 9.610.

SECTION 9.640

Page 19: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

COSTS FOR SITE IMPROVEMENTS AND MANDATORY FM41 AGREEMENTS, MANDATED ADA IMPROVEMENTS, MANDATED LANDSCAPING AND MANDATED OR VOLUNTARY SEISMIC IMPROVEMENTS WILL NOT BE INCLUDED IN THE $15 PER SQUARE FOOT AMOUNT.

SECTION 9.640

Page 20: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

THE BUILDING SAFETY DIRECTOR MAY APPROVE A MULTI-YEAR PHASED PROGRAM OF SEISMIC IMPROVEMENTS WHEN THE IMPROVEMENTS ARE PRE-DESIGNED AND AN IMPROVEMENT/IMPLEMENTATION PLAN IS APPROVED BY THE BUILDING SAFETY DIRECTOR. THE MAXIMUM TOTAL TIME ALLOWED FOR COMPLETION OF PHASED IMPROVEMENTS SHALL BE TEN YEARS.

SECTION 9.645

Page 21: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

BUILDING PERMIT APPLICATIONS TO IMPROVE THE SEISMIC CAPABILITY OF A BUILDING SHALL NOT TRIGGER:ACCESSIBILITY IMPROVEMENTS SO LONG AS THE SEISMIC IMPROVEMENT DOES NOT LESSEN ACCESSIBILITY.FIRE LIFE SAFETY IMPROVEMENTS SO LONG AS THE SEISMIC IMPROVEMENT DOES NOT LESSON THE BUILDING’S FIRE RESISTANCE OR EXITING CAPABILITY.

SECTION 9.650

Page 22: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

LANDSCAPE IMPROVEMENTS REQUIRED BY THE LAND DEVELOPMENT CODE CHAPTER 10.STREET TREE IMPROVEMENTS REQUIRED BY THE LAND DEVELOPMENTS CODE.CONFORMANCE WITH THESE INTERIM REGULATIONS MAY NOT EXEMPT BUILDINGS FROM FUTURE SEISMIC REQULATIONS.

SECTION 9.650

Page 23: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

BUILDING PERMIT, PLAN REVIEW AND FIRE LIFE SAFETY REVIEW FEES ARE WAIVED WHEN SUCH FEES TOTAL LESS THEN $2,500, AND REDUCED BY 50% WHEN SUCH FEES WOULD TOTAL $2,500 OR MORE.

SECTION 9.655

Page 24: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Seismic Design Requirements

BECAUSE UNANTICIPATED CIRCUMSTANCES MAY ARISE IN THE ENFORCEMENT OF THESE REQUIREMENTS FOR EXISTING BUILDINGS, CONSIDERATION AS TO THE REASONABLE APPLICATION OF THIS CHAPTER MAY BE ADDRESSED THROUGH THE UNITED APPEAL BOARD. SEE SECTION 2.475 THROUGH 2.481.

SECTION 9.655

Page 25: Seismic Design Requirements - ci. · PDF fileSeismic Design Requirements SEISMIC HAZARDS SHALL BE MITIGATED IN CONJUCTION WITH BUILDING ALTERATIONS ... URM BLDG. Unreinforced Masonry

Yes

NoYes

NoYes

No

YesYes

NoYes

No

NoYes

No

REHABILITATE, CONFORM TO

Yes

ATTACH WALLS TO ROOF structureand BRACE PARAPETS as needed

per FEMA 178, appendix c

to become overloaded?(Strength and / or stiffness)

Upgrade building toUBC.1994

Upgrade building toUBC.1994

FEMA 178EVALUATION

FEMA 178, appendix C

Does work cause existing element

New elements conformto UBC.1994

APPLICATION FOR WORKON EXISTING BUILDING

ADDITION with LOAD > 5% on BLDG?

CHANGE OF OCCUPANCY(To higher hazard) OR 20%increase of occupant load?

PERMIT VALUE> $100,000?

URM BLDG.Unreinforced Masonry Bldg?

PERMIT VALUE>$15/Sq Ft?

ROOF REPAIR 50%or more of roof covering?

Any new structural elements requiringstructural design or are fire-damagedstructural elements being replaced?

Any work done to existingstructural elements?

GUIDELINES FOR STRUCTURAL WORK IN EXISTING BUILDINGS

No YesElement must be

improved toUBC.1994

Element can be modified

code for new workwithout conforming to

NO STRUCTURAL REQUIREMENTS