script thermal comfort 2013

Upload: liviu-adrian-popescu

Post on 03-Apr-2018

225 views

Category:

Documents


1 download

TRANSCRIPT

  • 7/28/2019 Script Thermal Comfort 2013

    1/37

    Laboratory: measurement techniques THERMAL COMFORT

    1 A.Thewes/A.Degens

    THERMAL COMFORT

    Laboratory: measurement techniques

  • 7/28/2019 Script Thermal Comfort 2013

    2/37

    Laboratory: measurement techniques THERMAL COMFORT

    2 A.Thewes/A.Degens

    1. What is thermal comfort?

    Although the human can acclimate on different external conditions, there is a range, therange of comfort, within the human feels most comfortable. Thermal comfort is defined

    as the feeling, that express satisfaction with the environment.

    Figure 1: Thermal comfort in dependent on physiological, intermediate and physical factors

    The first requirement on an acceptable thermal indoor climate is that the person is in

    thermal equilibrium (That means, the person does not know, if a higher or lower

    temperature is more comfortable). The ASHRAE-Standard 55 define the thermal

    comfort as: Thermal comfort is that condition of mind, which expresses satisfaction

    with the thermal environment..

    PRIMARY FACTORS

    ADDITIONAL FACTORS

    SECONDARY FACTORS

    Insulative

    clothing

    Activity level

    Air temperature

    Mean radiant

    temperature

    Relative humidity

    Air movement

  • 7/28/2019 Script Thermal Comfort 2013

    3/37

    Laboratory: measurement techniques THERMAL COMFORT

    3 A.Thewes/A.Degens

    The warmth sense will affected by e.g. type of activity, clothing or room temperature.

    Generally there are 21 different parameters. All factors can be combined in many

    different ways to create a comfortable thermal climate for a person. However there aremany factors which depend heavily on the individual in room, such as age, sex and

    constitution (Figure 1). Therefore it is impossible to specify a thermal environment that

    will satisfy everybody.

    The standard DIN EN ISO 7730 standardizes an analytical method based on the PMV-

    PPD index included the six main parameters (activity, clothing, air temperature, radiant

    temperature, air velocity and relative humidity), which are summarized to one value

    (PMV predicted mean vote). This heat balance model was developed by Fanger in

    1972. This allows estimation based on the following Seven-Point-Scale:

    +3 (hot), +2 (warm), +1 (slightly warm), 0 (neutral), -1 (slightly cool),-2 (cool),-3 (cold)

    The PMV-value is an index, which predicts the average value for the climate

    estimation by a large group. A PMV-value of zero means thermal neutrality and

    well-being. The thermal balance is reached, when in the body generated heat is equal

    to the released heat. The PMV can be used to verify, if the available thermal

    environment correspond to the comfort criteria.

    According to Fanger, the PMV is calculated with the equations (1) (4):

  • 7/28/2019 Script Thermal Comfort 2013

    4/37

    Laboratory: measurement techniques THERMAL COMFORT

    4 A.Thewes/A.Degens

    Where:

    M metabolic rate [W/m2

    ] tabular value (Figure 26 Annex a)W mechanical performance [W/m2] mostly 0 W/m2

    Icl clothing insulation [m2*K/W] tabular value (Figure 27-Annex b)

    fcl clothing area factor

    ta air temperature [C] measured value

    tr mean radiant temperature [C] measured value

    var relative air velocity [m/s] measured value

    pa partial pressure of water vapor [Pa] measured value as rel. humidity [%]

    hc convective heat transfer coefficient [W/(m2*K)]

    tcl surface temperature of persons clothing [C]

    The equations fcl and tcl could be solved iterative.

    Independent of these equations, the PMV-value can be estimated using tables (Annex

    c) of standard EN ISO 7730. For this, there are different combinations of activity,

    clothing, operative temperature and relative air velocity.

    Some estimations deviate around the value of thermal neutrality. Therefore, it is useful

    to predict the number of people, who feel the environment as too warm or too cold.

    Hence the quality of thermal environment can specify as predicted percentage ofdissatisfied (PPD-Index predicted percentage of dissatisfied). This percentage

    depends on the predicted mean vote (PMV).

    However, Fanger doesnt ask the people for their satisfaction with the thermal

    environment, but he decided that persons, who indicated a PMV-value of -3, -2, +2 or

    +3, are dissatisfied. The PPD-index of Fanger is a quantitative prediction of the number

    of dissatisfied people in regard to the thermal environment and is only based on

    assumptions. Furthermore, he defined, if the human is in thermal balance (PMV = 0),

    5% of all occupants can always be expected to be dissatisfied (Figure 2). Therefore it isimpossible to specify a thermal environment that will satisfy everybody.

  • 7/28/2019 Script Thermal Comfort 2013

    5/37

    Laboratory: measurement techniques THERMAL COMFORT

    5 A.Thewes/A.Degens

    The PPD-index can be calculated using following equation. It is necessary to know the

    PMV-value:

    PPD = 100 95 * exp(-0,03353 * PMV4 0,2179*PMV2)

    Figure 2: Correlation between PMV and PPD according to Fanger

    The PMV model of Fanger was expanded by studies of Mayer. Mayer asked the

    persons not only about the thermal sensation, he asked about the thermal satisfaction

    (thermal comfort) too. In the process he noted, that a vote of -1 (slightly cool) on the

    PMV scale classified already discomfort. Then he modified the correlation between

    PMV and PPD so that there is a better accord with his measurements. So the optimum

    is at a PMV value of +0,4 and a minimal percentage of dissatisfied of 16%. (Figure 3)

  • 7/28/2019 Script Thermal Comfort 2013

    6/37

    Laboratory: measurement techniques THERMAL COMFORT

    6 A.Thewes/A.Degens

    Figure 3: Correlation between PMV and PPD according to Mayer

    Thermal dissatisfaction could have other reasons too. For example unwanted cooling or

    heating of one particular part of the body. Therefore such a discomfort is known as

    local discomfort.

    One possible cause is a local convective cooling of the body (draught).If the room air

    temperature is higher than the temperature of the moved air, which flow only from one

    side against the human body, there are a great percentage of dissatisfied persons. Thispercentage of dissatisfied persons (DR = draught rating) can be calculated using

    following equation:

    Where:

    DR = percentage dissatisfied persons by draught [%]

    ta,I = local air temperature [C]

    va,l = local average air velocity [m/s], < 0,5 m/s

    Tu = local turbulence intensity [%], 10% - 60%, if the exact value is not available,

    generally can be calculated with 40%.

    if va,l > 0,05 m/s then va,l = 0,05 m/s

    if DR > 100% then DR = 100%

  • 7/28/2019 Script Thermal Comfort 2013

    7/37

    Laboratory: measurement techniques THERMAL COMFORT

    7 A.Thewes/A.Degens

    The turbulence intensity is a value of the uniformity or non-uniformity of air-flow. To

    calculate the turbulence intensity Tu is it necessary to have information about the

    standard deviation sv of the air velocity.

    Where:

    sv = standard deviation of instantaneous value of the air velocity

    = mean air velocity

    A second cause of local discomfort is vertical temperature differences between thehead and ankle level. The following graph shows the percentage of dissatisfied persons

    (PD = percentage of dissatisfied) as a result of vertical temperature differences.

    The graph (Figure 4) shows, that a uniform temperature with a maximum difference of 1

    degree Celsius, between head and ankle level, is most comfortable.

    Figure 4: Local discomfort as a result of vertical temperature differences

    Alternative the percentage of dissatisfied can be calculated:

    Where: PD = percentage of dissatisfied [%]

    = air temperature differences between head and ankle level [C]

  • 7/28/2019 Script Thermal Comfort 2013

    8/37

    Laboratory: measurement techniques THERMAL COMFORT

    8 A.Thewes/A.Degens

    Also local discomfort and a percentage of dissatisfied (PD = percentage of

    dissatisfied) can be estimated as a result of an asymmetric radiation environment

    or rathertoo high or too low floor temperatures.

    Figure 5: Local thermal discomfort as a result of a warm or cold floor

    Figure 5 demonstrates that the human feels most comfortable at a floor temperature of

    25C. The diagram is based on studies with persons who working in standing and

    sitting positions.

    The already mentioned discomfort as a result of asymmetric radiant temperature is

    mainly caused by warm ceilings and cold floors. In Figure 6 is shown the percentage of

    dissatisfied persons due to asymmetric radiation.

  • 7/28/2019 Script Thermal Comfort 2013

    9/37

    Laboratory: measurement techniques THERMAL COMFORT

    9 A.Thewes/A.Degens

    Figure 6: Local thermal discomfort as a result of asymmetric radiant temperature

    Where:

    PD = percentage of dissatisfied [%]

    = asymmetric radiant temperature [C]1 = warm ceilings

    2 = cool walls

    3 = cool ceilings

    4 = warm walls

    For old listed buildings the phenomena of local discomfort is very important. For

    example, they can often not be sufficiently thermally insulated although the rooms are

    used as offices or residences.

    In a long-term evaluation can be differentiated between three categories of general

    comfort. The favored conditions of a room can be chosen from the following table on

    the basis of the categories A, B and C. Category A comes up to high expectations and

    on the other hand category C moderate expectations. Each category allows a maximum

    percentage of dissatisfied persons (Figure 7). As well the maximum percentages of

    dissatisfied due to local discomfort are defined. It should be noted, that all criteria of a

    category should be met.

  • 7/28/2019 Script Thermal Comfort 2013

    10/37

    Laboratory: measurement techniques THERMAL COMFORT

    10 A.Thewes/A.Degens

    Figure 7: Three categories of ambient conditions

    In every room there is an optimal operative temperature corresponding to PMV = 0. The

    operative temperature is a uniform temperature of a hypothetical black room in which

    the human body would lose the same amount of heat by radiation and convection as it

    would in some actual environment. It results from the mean air temperature and

    radiation temperature and depends on the clothing and the activity of persons in the

    room.

    In the following figure is only shown the graph of category A. The operative

    temperatures are the same for all categories, only the acceptable range varies.

    Figure 8: The optimal operative temperature as a function of activity and clothing. The shaded areas

    inform about the comfort range around the optimal inside temperature

    X = clothing insulation [clo]

    Y = metabolic rate [met]

    Y = activity in W/m

  • 7/28/2019 Script Thermal Comfort 2013

    11/37

    Laboratory: measurement techniques THERMAL COMFORT

    11 A.Thewes/A.Degens

    The diagram is valid for a relative humidity of 50%. As well an air velocity lower than 0,1

    m/s in the room is assumed.

    One met is a metabolic unit and describes the energy consumption of people. So, 1

    met is equal to 58 W/mskin surface, and the average skin surface of adult human is 1,7m

    (Annex a Figure 26).

    Example:

    The starting point for the estimation of the optimal operative temperature of a room is to

    know which expectations regarding thermal comfort there are. If we consider there are

    high expectations, category A values applies (Figure 8). If the persons work in sitting

    positions (office work = 1,2met) and wear mean clothes (1 clo), the result is an optimal

    operative temperature of 21C 1C.

    For different room types, there are defined thermal criteria. The estimation of optimaloperative temperature is dependent on standard activity levels and clothing insulation.

    During the summer the closing insulation is 0,5 clo and 1,0 clo (Figure 27-30, Annex b)

    during the winter. Therefore in the following table, there are differences between the

    criteria of summer and winter.

  • 7/28/2019 Script Thermal Comfort 2013

    12/37

    Laboratory: measurement techniques THERMAL COMFORT

    12 A.Thewes/A.Degens

    Figure 9: Thermal criteria for different room in different building types

    All the above models are based on rooms with air conditioning plants. In a study of the

    ASHRAE society, several office buildings with natural window ventilation or air

    conditioning were analyzed. In the buildings with air conditioning there was a good

    correlation between the rating by the occupants and the PMV-model, whereas in

    buildings with natural ventilation were more deviations between ratings and model.

    Brager und de Dear found that the occupants of natural ventilated buildings are more

    tolerant regarding to the room temperature. They found a 80% acceptability within a 4K

    temperature spread for mechanical ventilated buildings and within 7K for natural

    ventilated.

    While the standard DIN EN ISO 7730 evaluates the range of comfortable temperature

    dependent on ambient conditions, the ASHRAE standard define a correlation between

    operative temperature and monthly mean ambient temperature (Figure 10).

    This approach of ASHRAE standard is only to apply by ambient temperatures between

    10C and 33,5C.

    A second requirement is a light sitting activity (1 to 1,3met).

  • 7/28/2019 Script Thermal Comfort 2013

    13/37

    Laboratory: measurement techniques THERMAL COMFORT

    13 A.Thewes/A.Degens

    Figure 10: comfortable operative temperature of natural ventilated rooms ASHRAE Standard 55

    2. Installing the measurement techniques and analysis

    The measuring system includes a globe-thermometer, a humidity-/temperature sensor

    and a thermo-anemometer. The height of the sensors should be approximate the same

    height than the head of a sitting person (approx. 1,10m).

    Figure 11: Measurement techniques

    It is possible with this measuring setup to measure all the physical parameters needed

    for assessing and evaluating thermal comfort. The data acquired from the series

    measuring the radiant temperature (globe-thermometer), room temperature, room air

  • 7/28/2019 Script Thermal Comfort 2013

    14/37

    Laboratory: measurement techniques THERMAL COMFORT

    14 A.Thewes/A.Degens

    flow and humidity, and the necessary input parameters (e.g. clothing insulation,

    activity level and mechanical power) are used together to calculate the PMV (predicted

    mean vote) and the PPD (predicted percentage of dissatisfied) values as per EN ISO7730 using the AMR WinControl software.

    The operative temperature is the sensed room Temperature

    and can be calculate as the arithmetic mean of air- and radiant

    temperature. To determine the radiant temperature it is

    necessary to measure the globe temperature. To measure the

    globe temperature is used a matt black copper bulb with a

    standard diameter of approximate 15cm to absorb the radiant

    heat of surrounding objects. Inside is a Pt100-sensor (Resistor

    based sensor).

    The air space inside of the black bulb makes sure that the

    absorbed heat influences are mixed inside the bulb and so

    create a uniform temperature which is measured by the precise

    sensor.

    Figure 12: Globe-Thermometer

    The operative temperature is to = a*ta + (1-a)*tr

    Where ta = air temperaturetr = radiant temperature

    a = 0,5 if air velocity v < 0,2 m/s

    a = 0,6 ifv = 0,2 0,6 m/s

    a = 0,7 ifv = 0,6 1,0 m/s

    If the globe-temperature tg, the air temperature ta and the air velocity va are measured, it

    is possible to calculate approximately the radiant temperature using following equation:

    [( )

    ( )]

    The air velocity can be measured using a mechanical anemometer (e.g. rotating vanes)

    or using a thermo-anemometer (e.g. hot wire anemometer). For this measurement

    system we use a thermo-anemometer (Figure 13)

  • 7/28/2019 Script Thermal Comfort 2013

    15/37

    Laboratory: measurement techniques THERMAL COMFORT

    15 A.Thewes/A.Degens

    Figure 13: thermo-anemometer

    The anemometer consists of a probe tube with heated miniature thermistor, cooled

    down by the air flow. The change in resistance is a measure for the air velocity. As this

    measurement strongly depends on the ambient temperature a further precision NTC

    resistance is used to measure and automatically compensate the ambient temperature.

    The measuring range of air velocity is 0,01 to 1 m/s.

    For an interpretation as per standard EN ISO 7730, must be assigned all measured

    values of room temperature, radiant temperature, humidity and air velocity by selection

    of measuring channels (Figure 14) in the Software AMR Win Control.

  • 7/28/2019 Script Thermal Comfort 2013

    16/37

    Laboratory: measurement techniques THERMAL COMFORT

    16 A.Thewes/A.Degens

    Figure 14: PMV assistant of Software WinControl

    During the measurement of air velocity it is important to make sure, that not the current

    value but the average value of each cycle will be saved. As per DIN 1946 Part 2 is

    requested, that the duration of each cycle is minimum 100s.

    For the mean radiant temperature there are three different possibilities, to measure,to estimate, or to link. The two last ones allow a simplified calculation, if for example

    the ambient influences are negligible or assumed as constant. For an exact calculation

    the method to measure is to choose. This method allows the measurement of the

    radiant temperature using appropriate equipment or to create complex analytic

    relationships with user defined equations in an output channel. This could be for

    example the above mentioned equation to calculate the radiant temperature with the

    measured values of air temperature, globe temperature and air velocity as necessary

    inputs.

    Finally according to ISO 7730 information about metabolic rate, mechanical

    performance and clothing insulation values are necessary:

  • 7/28/2019 Script Thermal Comfort 2013

    17/37

    Laboratory: measurement techniques THERMAL COMFORT

    17 A.Thewes/A.Degens

    Figure 15: PMV assistant of Software WinControl

    Possible outputs are the PMV index or the PPD value:

    Figure 16: PMV assistant of Software WinControl

    The results can be displayed as table or diagram (Figure 17 and 18):

  • 7/28/2019 Script Thermal Comfort 2013

    18/37

  • 7/28/2019 Script Thermal Comfort 2013

    19/37

    Laboratory: measurement techniques THERMAL COMFORT

    19 A.Thewes/A.Degens

    Figure 18: Output of PMV and PPD using Software WinControl as line diagram

  • 7/28/2019 Script Thermal Comfort 2013

    20/37

  • 7/28/2019 Script Thermal Comfort 2013

    21/37

  • 7/28/2019 Script Thermal Comfort 2013

    22/37

  • 7/28/2019 Script Thermal Comfort 2013

    23/37

    Laboratory: measurement techniques THERMAL COMFORT

    23 A.Thewes/A.Degens

    The necessary fresh air demand, to comply the CO2-limits, depends on quality of fresh

    air and type of activity.

    Figure 21: supply air flow depending on activity

  • 7/28/2019 Script Thermal Comfort 2013

    24/37

    Laboratory: measurement techniques THERMAL COMFORT

    24 A.Thewes/A.Degens

    Max von Pettenkofer (1858) defined that the human is the main source of air pollution.

    Therefore the necessary air exchange rate is based on the number of persons in theroom.

    New researches have shown that there are many other sources of pollution in a

    building.

    For the assessment of indoor air quality, it would be desirable to measure all pollutants

    and odours. Because this is very complex, Fanger (1990) introduced two new units:

    1 Olf

    1 Dezipol = 1 Olf / (10l*s)

    10 Dezipol = 1 Pol

    Figure 22: Definition of olf and dezipol.

    One Olf is the sensory pollution strength from a standard person, defined as anaverage adult with a hygienic standard equivalent of 0,7 baths per day and whose skin

    has a total area of 1,7 sqm. Each other source of pollution in a room (furniture, carpet,

    building materials,) is to convert in a sensory pollution strength from a number of

    standard persons (Figure 23).

    The average strength of a pollution source in buildings is:

    0,2 olf/m2 in buildings with low pollution

    0,6 olf/m

    2

    if there are approx. 40% smokers in the building

  • 7/28/2019 Script Thermal Comfort 2013

    25/37

    Laboratory: measurement techniques THERMAL COMFORT

    25 A.Thewes/A.Degens

    Figure 23: Sources of pollution illustrated in olf

    Because there arent applicable measuring instruments, the odour strength is evaluated

    by trained test persons.

    One Dezipol is defined as the unit for perceived air quality caused by a standard

    person (1 Olf) in a room, which is ventilated by 10l/s pure air. OnePol defined a room,

    which is ventilated by only 1l/s pure air. That means very bad air quality.

    Example:

    A room is ventilated by an air conditioning plant which supplies air flow rate of 10 l/s.The ambient air is polluted by 1 dezipol. In addition, 1 olf by the ventilation system is to

    note. Therefore the supply air is polluted by 2 dezipol. The occupants and the room

    produce 1 olf each. Finally, the perceived indoor air quality is 4 dezipol.

    Figure 24: Perceived air quality

  • 7/28/2019 Script Thermal Comfort 2013

    26/37

    Laboratory: measurement techniques THERMAL COMFORT

    26 A.Thewes/A.Degens

    The following two graphs show the dependence on the percentage of dissatisfied as a

    result of the air quality. Where the left graph shows the dependence on unit pol,

    illustrate the right graph the dependence on air exchange rate. Both graphs describethe reciprocal value of the other.

    It is evident, that the percentage of dissatisfied decrease with increasing air exchange

    rate and constant odour strength. The nonlinear behavior is explainable by the number

    of grumbler, which are always dissatisfied even if the best air quality is in the rooms.

    Figure 25: percentage of dissatisfied in dependence on the air quality or the air exchange rate.

    The left graph represents the solutions of the following equation:

    Where:

    PD = percentage of dissatisfied [%]

    C = air quality [dezipol]

  • 7/28/2019 Script Thermal Comfort 2013

    27/37

    Laboratory: measurement techniques THERMAL COMFORT

    27 A.Thewes/A.Degens

    The required supply air flow rate to evaluate a defined air quality in dezipol can be

    calculated using following equation:

    Where:

    V = required supply air flow rate [l/s]

    Ci = requested air quality [dezipol]

    CZU = quality of supply air [dezipol]

    V = effectiveness of ventilation

    G = total strength of pollution [olf]

    Exercise:

    A seminar room with a surface of 100 m2 shall be ventilated, that a perceived room air

    quality of 1,4 dezipol is existing (=20% dissatisfied). The room is occupied by 50

    persons. The strength of pollution per person is 1 olf, because they are working in a

    sitting position. The strength of pollution due to materials in room is 0,3 olf/m2.

    The quality of supply air is assumed to 0,2 dezipol. The effectiveness of ventilationshould be V = 1.

    Calculate the required supply air flow rate!

  • 7/28/2019 Script Thermal Comfort 2013

    28/37

    Laboratory: measurement techniques THERMAL COMFORT

    28 A.Thewes/A.Degens

    5. Summary

    Finally, an overview shows the most important values of thermal comfort, inclusivesome limit and reference values:

    PMV (= predicted mean vote) = 0 means thermal neutrality

    PPD (predicted percentage of dissatisfied) = 5% if thermal neutrality

    Local thermal discomfort:

    o Due to drafts < 0,2 m/s

    o Due to vertical temperature differences = T < 2C

    o Warm/cold floors = optimal floor temperature 25C

    o Asymmetric radiation temperature = warm ceilings and cold walls

    should be avoided!

    Clothing insulation value - office work = 1,0 clo = 0,155 mK/W (winter)

    = 0,5 clo = 0,08 mK/W (summer)

    Metabolic rate sedentary work = 1,2 met = 70 W/m

    (reference to 1,7m skin surface)

    Relative humidity = 45% is ideal value

    30 70 % comfortable

    according to DIN EN 7730

    Operative temperature, DIN EN 7730 = during winter 20C 24C

    = during summer 23C 26C

    Adm. Air velocity according to DIN 1946 = 20 22C 0,13 m/s

    Strength of pollution source = 1 olf (standard person)

    = 6 olf (smoker)

    optimal CO2-concentration in rooms = 800 1200 ppm

  • 7/28/2019 Script Thermal Comfort 2013

    29/37

    Laboratory: measurement techniques THERMAL COMFORT

    29 A.Thewes/A.Degens

    6. Standards

    DIN EN ISO 7730; 2005-11: Ergonomics of the thermal environment analyticaldetermination and interpretation of thermal comfort using calculation of the PMV and PPD

    indices and local thermal comfort criteria

    ASHRAE Standard 55: Thermal Environmental Conditions for Human Occupancy

    DIN EN ISO 9920; 2005-02: Ergonomics of thermal environment Estimation of thermal

    insulation and water vapor resistance of a clothing ensemble

    DIN ISO EN 8996: 2005-01: Ergonomics of thermal environment Determination of

    metabolic rate

    DIN EN 15251: 2007-08: Indoor environmental input parameter for design and assessment

    of energy performance of buildings addressing indoor air quality; thermal environment;

    lighting and acoustics

    DIN EN ISO 10551: 2002-01: Ergonomics of the thermal environment Assessment of

    the influence of the thermal environment using subjective judgment scales

    DIN 1946-2: Ventilation and air conditioning in workrooms and public areas (since May

    2005 replaced by DIN EN 13779: 2005 with reference to DIN EN ISO 7730)

  • 7/28/2019 Script Thermal Comfort 2013

    30/37

    Laboratory: measurement techniques THERMAL COMFORT

    30 A.Thewes/A.Degens

    7. Exercise: Questionnaire

    a.) Determine the thermal insulation of your clothes! (Annexe b)

    b.) How would you rate the indoor climate of the seminar room?

    very neithernor very

    1.) warm cold

    2.) dry air humid air

    3.) fresh air exhausted air

    4.) uncomfortable comfortable

    temperature temperature

    5.) bright dark

    6.) air draft no air movement

    7.) total indoor climate comfortable

    uncomfortable

  • 7/28/2019 Script Thermal Comfort 2013

    31/37

  • 7/28/2019 Script Thermal Comfort 2013

    32/37

    Laboratory: measurement techniques THERMAL COMFORT

    32 A.Thewes/A.Degens

    b. Table for estimation of clothing insulation values

    Figure 27: Thermal insulation values of typical clothing combinations DIN EN ISO 9920; 2005-02

  • 7/28/2019 Script Thermal Comfort 2013

    33/37

    Laboratory: measurement techniques THERMAL COMFORT

    33 A.Thewes/A.Degens

    Figure 28: Thermal insulation factors of typical clothing and the necessary changing of the

    optimum operative temperature DIN EN ISO 9920; 2005-02

  • 7/28/2019 Script Thermal Comfort 2013

    34/37

    Laboratory: measurement techniques THERMAL COMFORT

    34 A.Thewes/A.Degens

    Figure 29: Thermal insulation factors of typical clothing and the necessary changing of the

    optimum operative temperature DIN EN ISO 9920; 2005-02

    Figure 30: Thermal insulation of chairs DIN EN ISO 9920; 2005-02

  • 7/28/2019 Script Thermal Comfort 2013

    35/37

    Laboratory: measurement techniques THERMAL COMFORT

    35 A.Thewes/A.Degens

    c. Table to calculate the PMV-Index

    The PMV-values of the following table are valid for a relative humidity of 50%.Further you may only work with this table, if the difference between the air

    temperature and the operative temperature is lower than 5K. In this case, the

    uncertainty of the tabular values is better than 0,1 PMV.

  • 7/28/2019 Script Thermal Comfort 2013

    36/37

  • 7/28/2019 Script Thermal Comfort 2013

    37/37

    Laboratory: measurement techniques THERMAL COMFORT

    d. HX diagram (Mollier)

    Figure 32: hx Diagram