scope - donar.messe.de · scope t&m division introduction 5 scope protect division introduction...

32
SCOPE www.scopetnm.com SCOPE

Upload: others

Post on 13-Sep-2019

18 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

SCOPE

Page 2: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

A pioneer in offering solutions for the power sector

SCOPE started its operations in 1988 with the intent of designing portable electronic Test and Measuring instruments to ensure the optimum performance of major electrical equipment used in power generation, transmission & distribution. We have realized this vision and SCOPE is now one of the leading R&D driven companies in the power sector, making electronics work in switchyard environment up-to 1200 kV. We are now a trusted brand for field testing instruments & solutions in more than 40 countries across 5 continents.

We at SCOPE are committed to offer products, services and unique solutions of the highest quality at right price through the process of close interactions with customer, incorporating latest & smart technological developments, continuous learning and improvement within the company. To ensure this we have an independent and well-equipped R&D, “State of the Art” factory, elaborate calibration setup, an interactive sales force and a dedicated field support team. For quick response to customer requirements, we have strategically located set-ups across India. Our corporate office is headquartered in Mumbai, whereas our R&D and factory are located in Pune. Regional sales & service offices situated at Delhi, Chennai and Kolkata ensure that we are always close to our customers. We are reaching out to rest of the world through our partners in various countries.

Our approach of seeking synergetic solutions to our customer’s needs has enriched the quality of our ultimate goal - Customer Satisfaction. In fact, we owe our growth to the confidence with which our customers approach us for solutions. This has facilitated expansion of SCOPE into area of Protection and Services. We are now manufacturing Control & Relay Panels and are offering substation automation & smart grid solutions including RTUs and SCADA.

We present a brief introduction of our products and capabilities through this catalogue and hope that you will make challenging demands on us.

When you need Simple solutions for difficult measurements®, you can rely on the ingenuity of SCOPE.

2

SCOPE

Page 3: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

Business Verticals of SCOPE

SCOPE T&M: Test and Measurement Instruments Division

OO Design, Development, Manufacturing, Marketing & Maintenance of T&M Instruments

OX Test & Measurement Instruments for HV/EHV Substation Equipments

OX On-line Monitoring Systems for EHV Substation Equipments and Transmission lines

OX Supply of complete package of T&M, Tools, Tackles & Safety Equipment to projects through dedicated Project Business Group (PBG)

OX Calibration and Annual Maintenance Contract Services

OX Customised Industrial Aluminium Cases and Molded Cases

SCOPE Protect: Power System Protection & Automation Division OO It designs & executes state of art Protection & Substation Automation Solutions for up-to 765 kV.

OX Control & Relay Panels

OX Substation Automation Solutions, RTUs, SCADA

OX Power System Studies

OX Controlled Switching Device for point on wave control of Circuit Breakers

ISOSCELES: Power Sector Services DivisionOO It offers Testing & Commissioning services in India & Abroad.

OX Routine & Specialised Testing Services for existing substations

OX Complete Testing & Commissioning of new substations up-to 765 kV including Substation Automation

OX Specialised Commissioning Services for RTU based Automation and Controled Switching Devices

OX Contracts for comprehensive RLA / RLE Studies

OX Professional Training Services to Utilities

3

Page 4: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE T&M Division Introduction 5

SCOPE Protect Division Introduction 6

ISOSCELES Introduction 7

Circuit Breaker Dynamic Test System - HISAC Ultima 8

Circuit Breaker Operational Analyser - HISAC Swift 10

Loco Circuit Breaker Test System - CBSCOPE 11

Circuit Breaker Time Interval Meter - SCOT+ Series 12

CB Online Monitor - RTMon CB 13

Leakage Current Analyser for Surge Arrester (LA) - SA Series 14

SA Online Leakage Current Monitor - SAMon 15

Contact Resistance Meter - CRM Series 16

Winding Resistance Meter - TRM Series 18

Universal Time Interval Meter - SCOT MUT/MUT4 20

CT Polarity Tester - Dir CT 20

DC Earth fault Locator - DC Trace 21

Cable Fault Locator - CFL Test System 22

Battery Resistance Tester - BRT1 25

High Resistance, High Voltage Decade Resistance Box - DecR 26

SCOPE Cases 27

SCOPE CSG - Customer Support Group 28

Maintenance Manager Software - SCHELOG 29

Launching Soon... 30

Our Customers, Recognitions & Global Presence 31

INDEX

4

Page 5: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

SCOPE T&M division focuses on the manufacture and supply of portable test and measuring instruments to the power sector. This division was first division of company & was started on 13th January, 1988 after eight months of pre-operative product development period to become India’s first test and measuring instruments manufacturer which had made electronics work in extremely high electromagnetic induction prevailing in live EHV & UHV substations.

We have an independent R&D lab, where a team of highly qualified & experienced engineers are engaged in doing fundamental development in the field of test & measurement, acquiring knowledge and expertise on latest technology & trend on global basis and adapt them quickly to suite Indian environment and customer needs. We have capability to convert a concept into a product. The in-house hardware and software development capability gives us the total control over the product being sold.

SCOPE had done pioneering work in field of CB testing and had developed some unique products in close association with Indian utilities and CB manufacturers. SCOPE is the only Indian and one of very few of global manufacturers for some of the cutting edge technology products like DCRM for CBs and LCM for LAs. Similarly SCOPE is probably only company who had supplied on-line monitoring systems for CBs & LAs of 1200 kV. Many of our products had won the best product awards on global platforms like ELECRAMA.

In order to expand the products & services to customers from power sector & industry, SCOPE has forged partnership with companies from Australia, Brazil, Canada, China, USA etc.

Under SCOPE T&M, following groups & activities are performing:OO Manufactured Products Group: Design, development, manufacturing, marketing & maintenance of various

test & measuring instruments for HV/EHV substation equipment. OO Agency Business Group: Marketing & maintenance of various test & measuring instruments for HV/EHV

substation equipment & transmission lines. These are manufactured by our global partners.OO Project Business Group: Supply of complete package of T&M, tools & tackles, safety equipment, lab

instruments package etc. to EPC contractors for various projects.OO Cases Group: Manufacturing & marketing of customized industrial aluminum cases as well as marketing

of moulded cases.OO Customer Support Group: Dedicated to provide after sales support like repairs, calibration, up-gradation,

annual maintenance contracts & training for products supplied by SCOPE.

Understanding the future need of more & more on-line monitoring solutions for substation equipment and lines, SCOPE has already taken lead in this area. Details can be found further in this catalogue.

* For more information or enquiries mail to [email protected]

SCOPE T&M

Portable Test and Measuring Instruments Division

5

Page 6: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

To meet the growing demand for protection systems in energy sector, SCOPE has ventured into the protection business and is offering various solutions & services for power system protection & substation automation. SCOPE’s more than 25 years of experience in the power sector and associated domain knowledge had made it a formidable player in power system protection as well. Since the inception of this division, SCOPE has forged partnerships with major numerical relay manufacturers as well as RTU, SCADA manufacturers and is now offering end to end solutions in this area.

SCOPE has in-house engineering team, “State of the Art” manufacturing & testing set-up and large pool of field testing & commissioning engineers. In short span of time we have executed several contracts namely centralized bus-bar protection, transformer protection & feeder protection up to 400kV. SCOPE Protect has also executed contracts for 400 kV complete control and relay panels with substation automation systems in India. Additionally, we offer customised system solutions according to actual on-site conditions in order to satisfy customer's requirements.

Under the umbrella of SCOPE Protect, following solutions and services are offered:OO Consultancy and Engineering Services: Our experienced engineering team can understand the customer’s

requirements and design the systems according to their present trends. We will give consultancy services for designing better and efficient protection & automation systems by incorporating better technological advancements. We also provide consultancy for power system studies by providing the load flow studies or analysis.

OO Control & Relay Panel Assembly and System Integration Jobs: With our 6,000 square feet factory setup at Pune, we can handle multiple projects at a time with an expertise in assembling the panels, checking the schemes, quality inspection, factory testing and finally offering the factory inspections for total integrated systems.

OO Automation Solutions: We provide RTU based automation solutions in collaboration with Vizimax from Canada. This is extremely useful and cost effective solution for the conventional substations to convert it to fully automated substation making it compatible to smart grid. We are also system integrators for full-fledged SCADA system from Survalent Technology, Canada.

OO Controlled Switching Device: Our experience in understanding the circuit breaker has helped us a lot to bring this solution of point on wave control for closing or opening of CB in collaboration with Vizimax, Canada. Depending on the application, the CB is closed or opened on voltage zero or current zero thereby not only saving the abuse of CB, but more importantly the equipment protected by that CB. It has proven its efficacy and we had installed it on various types & makes of CB for various applications.

*For more information or enquiries mail to [email protected]

Power System Protection DivisionSCOPE Protect

6

Page 7: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

Power Sector Services Division

To augment the total solutions approach, we provide services to the power industry through our group company ISOSCELES Sales & Service Pvt. Ltd. ISOSCELES was started in 2005 and over the last 9 years, this division has earned an excellent reputation for itself by committing to give prompt response to critical testing requirements of power utilities, EPCs, OEMs and industrial customers spread all over India. It created the culture of completing the projects ahead of deadlines, which was unseen earlier in this sector which was plagued by “per day” method of quoting. We have recently expanded our services to countries outside India as well.

Our large pool of well-trained engineers conduct a wide range of activities efficiently and deliver reports that can be acted upon to increase the life and performance of assets used in power generation, transmission and distribution. Being a SCOPE group company it has inherited the ability of correct interpretation of results if various diagnostic tests.

ISOSCELES offers professional and time bound services that have resulted in significant direct and indirect savings in terms of equipment replacement and power outage costs. We have served the requirements of a large number of EPC contractors by completing testing & commissioning activities for new substations and obtaining Take Over Certificates (TOC) in a timely manner.

Services Offered

OO Testing and Commissioning of new substations up to 765 kV

OO Routine & Specialised testing services for existing substations

OO Earth quality analysis & Infra-red thermo vision scanning

OO Retrofitting of relays & relay panels and automation of substations

OO Specialised commissioning services for RTU based automation, SCADA integration & for Controlled Switching Devices

OO Annual Testing Contracts (ATCs), Comprehensive RLA / RLE studies

OO Comprehensive Maintenance Management and Database Management of test results for Substations through web based SCHELOG software.

OO Training to users on equipment testing & maintenance and power system protection

* For more information or enquiries mail to [email protected]

ISOSCELES

7

Page 8: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

HISAC Ultima Circuit Breaker Dynamic Test System

HISAC Ultima – new generation Circuit Breaker Dynamic Test Set from SCOPE …. The ultimate solution for testing Circuit Breakers of all types. HIASC Ultima is the most complete analyser for checking the dynamic performance of CBs in live EHV switchyards upto 765 kV.

HISAC Ultima can carry out Dynamic Contact Resistance Measurement on SIX breaks of THREE poles in one operation thereby significantly reducing stress on CB & testing downtime.

It offers flexibility to create pre-programmed Test Plans including all test settings for all types of circuit breakers available in a switchyard that can simply be recalled at the time of actual testing. This saves you from doing all settings in switchyards.

The Analysis software offers a range of utilities which enables effective Condition Monitoring of CB by comparing present test data with previous signatures and predicting future performance.

FeaturesOO Tests all types of circuit breakers - LV, HV & EHV for all critical performance parameters of all the poles /

breaks in a single shot.

OO Measures Main/PIR contact timings, bounce, non simultaneity of contacts and auxiliary contact timings.

OO Analyses contact travel characteristics for speed, insertion, contact gap, over-travel and rebound with suitable transducer and mounting fixture.

OO Records trip and close coil current characteristics.

OO Registers the signature of Dynamic Contact Resistance of main and arcing contacts, of all the 6 breaks simultaneously.

OO Displays settings, graphical and tabulated test results.

OO Prints test report in graphical format with test header and calculation footer, on external printer(not supplied).

OO Incorporates powerful and practical Windows™ based Test Manager Software to control & operate instrument; view, analyze and handle graphical test data on a laptop at high resolution.

OO Selects pre-programmed setup parameters and pass/fail limits through software.

OO Connects to CB with wear resistant test leads of sufficient length, having quick-fit connectors, suitable for EHV circuit breakers.

OO Moves easily within switchyard as the set can be mounted on a specially designed Trolley having large wheels & mains supply distribution board.

OO Travel – For evaluating travel characteristics of operating mechanisms, SCOPE offers rotary and linear resistive travel transducers with universal / specially designed fixtures to suit variety of CBs available.

8

Page 9: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

Specifications

Parameter HISAC UltimaTrigger Options O, C, C-O, O-C, O-C-O

Timing Channel 24 : 4 Main + 4 PIR per pole, 3 poles Simultaneously

Auxiliary Contact Timing Channel 8 : 4 dry + 4 wet Expandable up to 6 Dry + 6 Wet

Best Time Resolution 50µSCoil Current Channel 3 : Trip / Close coil currentTravel Channel 3 : Travel characteristicAnalog Channel for DCRM Input (Optional)

1 / 2 / 3 / 6 – as per DCRM modules selected

DCRM Resistance Range & Current (Optional)

1000 / 2000 / 4000 / 8000 µΩ Selectable,

Current 100A DCStatic Contact Resistance (CRM) Channel As per DCRM modules selected

CRM Resistance Range 1000 / 2000 / 4000 / 8000 µΩ SelectableConfigurable Analog Channel (Optional)

Up to 6: For inputs of station battery voltage, PIR value etc.

PIR value Measurement (Optional) 0-5000Ω with the resolution of 1ΩSampling Speed 1 / 2 / 5 / 10 / 20 kC SelectableDisplay Display of laptop Operation Interactive menu through laptopPC Connectivity EthernetPrinter External through laptopMemory Memory of laptop

Dimensions Analyser - 500 x 270 x 300 mm, DCRM Rack - 500 x 270 x 250 mm

Instrument WeightAnalyser - 12 kg

DCRM Rack-18 Kg(3 DCRM modules per Rack)

Power 230 V AC ± 15% , 50Hz ± 10%

OO DCRM module captures dynamic variation in contact resistance of main & arcing contacts during breaker operation.

OO Each DCRM module has in built independent isolated, rechargeable battery based 100A DC source.OO The result is plotted in graphical form on the software screen, which can be further analysed for finding

parameters such as contact gap, total insertion, arcing tip insertion, main and arcing contact resistance values etc.

OO Additional optional modules are available to measure PIR value and for monitoring Station DC (Coil voltage), Motor current or other static parameters through configurable Analog channels.

OO Type Tested as per IEC 60068, IEC 61326 & IEC 61010-1. CE marked.OO Supplied with suitable Test Leads & aluminium transport cases for instruments.OO Travel Transducer and fixture as per order based on make, type & rating of CB.

9

Page 10: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE offers HISAC Swift - Circuit Breaker Operational Analyser for checking the performance of the circuit breakers. The Analyser contains various intelligent measuring modules designed for measuring parameters such as contact timings of Main/PIR & Auxiliary contacts, Close/Trip Coil Current characteristics and Static Contact Resistance of R, Y & B poles simultaneously. The results can be directly viewed on the TFT touch screen display in graphical as well as numerical form. It is possible to print the graph on built-in thermal printer or download record to PC for further analysis on CPLOT software. This all in one instrument is best suited for gang operated CBs.

FeaturesOO Operations: C, O, C-O, O-C, O-C-O with configurable

delays and Static Contact Resistance.

OO Setup: Breaker information data entry and system settings are possible through the touch screen keyboard, which automatically invokes when this menu is selected.

OO Contact Timing: Channels for 3 Main and 3 PIR Contacts with 0.05mS resolution.

OO One internal channel to measure Close and Trip coil current.

OO Three multiplexed channels to measure Contact resistance with 0.1µΩ resolution and range up to 2Ω.

OO TFT color graphical display with touch screen. Displays the menu which is operated through touch screen. Graph is displayed after the operation with full resolution.

OO Printout: Through inbuilt, 56mm thermal printer is provided for printing test header, graph and calculation.

OO Memory: Provided with 2 MB inbuilt memory. Can store up to 75 records.

OO Windows based CPLOT software to download the record to PC through USB connectivity for further analysis & storage.

OO Type Tested as per IEC 60068, IEC 61326 & IEC 61010-1. CE marked.

Specifications

OO Breaker Control: Two solid state contacts rated at 50A, 300V AC/DC for breaker operation.

OO Sampling Speed: 20kC, 10kC, 5kC, 2kC & 1kC selectable.

OO Plot Length: 200mS at 20kC, 400mS at 10kC, 800mS at 5kC, 2000mS at 2kC and 4000mS at 1kC

OO Display : 320 x 240 pixel 5.7” color TFT LCD with LED back light, touch screen

OO Printer: 56 mm paper width, thermal printer

OO Environment: 0 to 50 deg C, 95% RH (non condensing).

OO Power: 96-246V AC, 50/60 Hz, 25VA (approx)

HISAC SwiftCircuit Breaker Operational Analyser

Channels Configuration Range Resolution Accuracy

Contact Status 6: 1 main + 1 PIR per pole, 3 poles Simultaneously

Measurement duration 1mS to 4S @ 1kC, 0.05mS

to 200mS @ 20kC

1mS @ 1kC 0.05mS @ 20kC

Value ±0.05% ± resolution

Auxiliary Contacts 2: Dry / Wet Selectable 15 to 300V DC (for Wet

Channels)1mS @ 1kC

0.05mS @ 20kC Value ± 0.05% ± resolution

Coil Current 1: Trip / Close coil current 1, 2, 5, 10, 25, 50A DC0.1% of

selected range Value ± 1% ± resolution

Contact Res. Channels

3: Multiplexed 3 Channels.10A Max.

200µΩ, 2000µΩ, 20mΩ, 200mΩ & 2Ω, auto ranging 0.1µΩ @200µΩ 1% of range

± resolution

10

Page 11: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

SCOPE introduces CBSCOPE – Loco Circuit Breaker Test System; the ultimate solution for testing Loco Circuit Breakers of all types. CBSCOPE is the most complete analyser for checking the dynamic performance of Loco VCBs; both Single bottle and Double bottle.

FeaturesOO CBSCOPE Measures timings, bounce, and simultaneity of contacts.OO Analyses contact travel characteristics for speed, contact gap, over-

travel and rebound.OO Records trip/ holding and close coil current characteristics.OO Displays settings, graphical and tabulated test results. OO Prints test report in graphical format with test header and calculation

footer, on external printer(not supplied).OO Incorporates powerful and practical Windows™ based Test Manager

Software to control & operate instrument; also to view, analyse and handle graphical test data on a laptop at high resolution.

OO Specially designed test commands for all Loco VCB testing. OO Analysis of test results provides inputs to assess and correct:

OX Settings for contact timings.

OX Closing and Opening speeds, over-travel, rebound and contact wipe.

OX Trip/Close release mechanism settings.

Specifications

OO Breaker Control: Two solid state contacts rated at 35A, 300V AC/DC for breaker operation (Close & Trip)

OO Trigger Options: Open Close, C-O, O-C, O-C-O, and delay between operations configurable

OO Sampling Speed: 20kC, 10kC, 5kC, 2kC, 1kC selectable

OO Travel Channels: For linear / rotary resistive transducers. 0-5V DC excitation source in-built

OO Communication Port : Ethernet port for communication between laptop and instrument

OO Power : 230V AC + 15%, 50Hz + 10%, 70VA Approx

OO Test Leads: Suitable to test Loco VCBs. Leads supplied are of suitable length, thickness, insulation quality & mechanical strength. They have colour coded terminators, quick-fit type rugged clamps & identification labels

OO Supplied with suitable Test Leads & aluminium transport case

Channels Configuration Range Resolution Accuracy

Contact Timing 3: 2 for double bottle VCB, 1 spare

Measurement duration1 mS to 40 Sec at 1 kC,

0.05 mS to 2 Sec at 20 kC

1 mS at 1 kC0.05 mS at 20 kC

Value ± 0.05%± resolution

Coil Current 2: Trip/ Holding & Close Coil current 1, 2, 5, 10, 25 A DC 0.1% of range at 1A

0.004% of rangeValue ± 0.5% ± resolution

Voltage (Travel) 2: Travel characteristics 0-5 V DC 1.2 mV at 25A Value ± 0.5%

± resolution

CBSCOPELoco Circuit Breaker Test System

11

Page 12: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOT+ SeriesCircuit Breaker Time Interval Meter

SCOPE introduces its next generation of iconic SCOT Series Circuit Breaker Time Interval Meters in all new super light avatars, based on cutting edge microcontroller & embedded technology.

User can choose from two models, SCOT M3K+ and SCOT MXP+ depending on type of testing to be done on circuit breakers.

FeaturesOO A radically new design makes SCOT the lightest available CB Time Interval Meter. OO High sampling frequency of up-to 10 KHz offers high timing resolution of 0.1 mS. OO Mains as well as rechargeable Li-ion battery operated. In built battery monitor and

cut off circuit for protection against battery deep discharge. OO In built real time clock, memory and printer*. Test time stamping on each record

enables time references for future use. OO PC Downloading & Analysis including ‘Trend Analysis’ is possible with “CData SCOT”

Software supplied with kit. OO Instrument debug options like contact status check, command check, memory check,

printer check*, PC downloading check are provided. OO Simple operation. Tests can be conducted even by technicians. OO Supplied with rugged test lead set, suitable for testing EHV CBs. OO Enclosed in ultra rugged IP67 class hard molded case. OO The instrument is supplied with CData software CD, Calibration Certificate, and Test

leads suitable for testing of EHV class circuit breakers.OO Type Tested as per IEC 60068, IEC 61326 & IEC 61010-1. CE marked

Note: * - These features are available only in SCOT MXP+.

Specifications

Parameter SCOT M3K+ SCOT MXP+

Contact Timing Channels 3 (Main contacts of 3 poles connected end to end, simultaneously)

12 ( Up-to 2 Main + 2 PIR contacts per pole, 3 poles simultaneously, i.e. 6 Main +

6 PIR contacts simultaneously)

Sampling Speed 10kC, 5kC, 2kC,1kC & 100C, Selectable

Timing Range 1Sec, 2Sec, 5Sec, 10Sec & 100Sec respectively for above Sampling Speeds

Resolution 0.1 mSec, 0.2 mSec, 0.5 mSec, 1 mSec & 10 mSec respectively for above Sampling Speeds

Accuracy Value ± 0.05% ± 1 digit

Breaker Control Two solid state contacts rated at 35A, 300V AC/DC for breaker operation

Trigger Options Close, Open, Close-Open

Display 4 Line X 20 character backlit LCD

Printer In-built, 58 mm thermal printer (Available only in SCOPT MXP+)

Keypad 5 keys

Memory 1 MB, 100 records, Internal

Inbuilt Battery Li-Ion, 11.1 V, 4 Ah

Battery Charger Input Supply - 100 to 300 VAC, 50/60 Hz ± 10% Output Voltage - 13.5 VDC, 1000 mA

Communication Port USB

Software CData SCOT - For PC Downloading & Analysis, Windows based

Environment 0 to 50°C, Upto 95% RH (Non condensing)

Dimensions 300 x 250 x 200 mm

Instrument Weight 5 kg

12

Page 13: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

RTMon CBCB Online Monitor

SCOPE introduces, for the first time in the country, the most powerful Real Time On-Line system for continuous monitoring of Circuit Breaker performance in HV / EHV substations.

RTMon consists of Field Unit which is inatalled near CB in IP enclosure, a PC in control room loaded with RTMon software and the communication link between the two.

No. of CBs in one subatation can be monitored by installing one field unit per CB, and they will communicate with central PC.

FeaturesOO The RTMon system is set up to monitor the signatures/ values of following parameters directly using

sensors:OX Close/ Trip Coil Current, Line/ Fault Current.OX Station DC Voltage.OX Close / Trip Auxiliary Contact Timings (field configurable

wet/ dry).OX Spring charging motor Current & Time.

OO RTMon continously monitors static parameters like SF6 gas pressure or density , pneumatic or hydraulic pressure, temperature etc.

OO The RTMon system calculates following parameters:OX Projected Main Contact Timings.OX Arcing Time and Fault Clearing Time.OX Cumulative Fault Current.

OO Provision for mechanism travel available. Can be used if suitable travel transducer with fixture is available.

Features of RTMon SoftwareOO Viewing, analysis and comparison of test data with

previous signatures or pre-set limits.

OO Dynamic calculations on graphical information for easy on-screen analysis.

OO Indication of any abnormality in real time helps planning of diagnostic testing.

OO In a substation having many RTMons, the software stores the signature data in a structured database to relate data to each CB / pole.

SpecificationsOO Trigger: Automatic, on coil current or auxiliary contact change over when the circuit breaker operates

OO Sampling Rate: 10 kHz

OO Auxiliary Contact: 6 Wet OR Dry contacts, field configurable, 15V to 300V DC input of wet contact

OO Coil Current: Records 'Trip 1' & 'Close' on 3 channels & 'Trip 2' on 3 channels. Total channels 6. Upto 25A.

OO Line/Fault Current: Records Trip/Close Line/Fault currents on 3 channels for 3 phase

OO Motor Current: Records Motor current upto 25A and spring charging time upto 60 Sec on 3 Channels

OO Station DC Voltage: Records variation in Station DC voltage during operation on 2 channels upto 250V DC

OO Spare Channels: 3 Analog input channels (0-5V input) each for SF6 gas and air or hydraulic pressure

OO Memory: Inbuilt, non volatile, 256 MB flash

OO Communication: RF, wired or fiber optic communication with remote PC

13

Page 14: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SA SeriesLeakage Current Analyser for Surge Arrester (LA)

SA 30i and SA 10i the Leakage Current Analyser and Leakage Current Meter from SCOPE are two state of the art on-line test system for Residual Life Assessment of metal oxide (Zno) Surge Arresters. The instrument measures and directly displays the values of resistive and total leakage current. it is capable to work accurately and safely in swithchyard upto 765kV.SA30i measures Third Harmonic Resistive leakage Current (THRC) with system harmonic compensation in accordance with IEC 60099-5 B2 (which is best recommended), whereas SA10i, a hand held Leakage Current Meter measures THRC without system harmonic compensation in accordance with IEC 60099-5 B1.

FeaturesOO Simple, lightweight, portable, feature-rich, affordable.OO Measures 3rd harmonic resistive current with system harmonic compensation*, and

the total leakage current.OO In-built temperature measurement facility enables calculation of temperature

compensated leakage currents.OO Results are displayed on LCD, printed on thermal printer and can be stored in the in-

built memory of the instrument. 1000 test records can be stored.OO Built-in standard calibration source for self-calibration check facility.OO USB communication port to transfer data to PC having Windows based data

management software.OO SA identity creation, Data management, Analysis and Trending through SAData software.OO Facility for testing of GIS LAs available optionally thorugh Field PT input.OO The instrument is supplied along with a low noise Clamp-on CT for measuring the leakage current, Field

Probe assembly for system harmonics compensation*, Test Leads suitable for testing of EHV class LAs*, Thermal paper roll*, SAData software installation CD and a Calibration Certificate.

* - Features available only in SA30i.

Specifications

Parameter SA 30i SA 10i

Total Leakage Current Range Up to 10mA

Resistive Leakage Current Range Up to 10mA

Field Probe Current Range Up to 1mA Not available

Resolution 1µA

Inputs External Clamp-on CT, Field Probe, External PT (110V AC) - Optional

External Clamp-on CT

Display 4 line x 20 character large backlit LCD 2 line x 16 character backlit LCD

Compensation Automatic for Noise, System Voltage, System Harmonic & Temperature

Automatic for Noise, System Voltage & Temperature

Temperature Sensor Inbuilt silicon thermometer Inbuilt silicon thermometer

Self-calibration Check Built-in source available No

PC Connectivity Yes

Memory 1000 results

Printer Inbuilt Thermal Printer Not available

Battery 11V / 2200mAh, Internal rechargeable Li-ion battery

7.4V / 1150mAh, Internal rechargeable Li-ion battery

Battery charging 100-270V AC, 50 / 60Hz ± 10%, 1 Phase 100-270V AC, 50 / 60Hz ± 10%, 1 Phase

Dimension 415 x 330 x 200mm 190 x 129 x 50mm

Instrument Weight 7.5 kg 1.5 kg

14

SA 30i

SA 10i

Page 15: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

SAMon from SCOPE is a powerful Online Leakage Current Monitoring system for continuous monitoring of metal oxide (Zno) Surge Arrester leakage current in live EHV / UHV substations.

It consists of portable Field Unit which is intalled near SA in IP enclosure, a PC at control room on which SAMon software is intalled and a Communication link between the two.

SAmon monitors Third Harmonic Resistive Leakage Current (THRC) which reflects the healthiness of SA, as per IEC 60099-5 B2.

Field Unit contuinously measures THRC at pre-set time interval and sends to central PC located in control room for monitoring all SAs in substation, multiple Field Units are used.

Features

OO State of the art, on-line test system for Residual Life Assessment of Surge Arrester (LA).

OO Measures 3rd harmonic resistive leakage current and total leakage current as per IEC 60099-5 B2.

OO Inbuilt system harmonic compensation.

OO Temperature compensation through inbuilt temperature sensor.

OO Specially designed low-noise permanent mounting type CT and field probe.

OO Authentic, time-stamped test results, data management through built-in real time clock, memory, PC connectivity & analysis software.

Features of SAMon softwareOO Create library of SA to be monitored with all relevant ID & rating data.

OO Set time interval between measurements. SAM Supplied with suitable Test Leads & aluminium transport case on unit will capture & transmit data accordingly.

OO Trend analysis of SA performance possible by using Analysis Software.

OO The SAMon analysis software is installed in the central PC. At decided interval PC sends request to the analyzing unit. The analyzing unit samples data from all the surge arresters calculates the parameters and send it to PC.

SpecificationsOO Total leakage current range – up to 10mA.

OO Resistive leakage current range – up to 10mA.

OO Field probe current range – up to 1mA.

OO Resolution – 1µA.

OO Accuracy – 5%

OO Power – 90 to 230 V AC or DC.

OO Communication: RF, wired or fiber optic communication with remote PC.

SAMonSA Online Leakage Current Monitor

15

Page 16: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

CRM SeriesContact Resistance Meter

SSCOPE offers its hugely popular CRM series Contact Resistance Meters, CRM 100B/100B+, CRM 200B/200B+ and CRM100C in all new super light avatars. The Plus (+) series is based on cutting edge ultra capacitor technology.

CRM directly measures micro-ohm values at 100 / 200 Amps DC under live EHV switchyard conditions quickly & accurately.

Features – CRM100B/100B+/200B/200B+/100COO Lightweight meters that directly measures & displays micro-ohm values.

OO Works reliably in live EHV switchyards up-to 765 kV.

OO Typically used for contact resistance of Circuit Breakers, Isolators, Bus Bar Joints, Earth Switch Joints etc.

OO 100A / 200A DC injection.

OO Uses Kelvin’s 4 wire measurement principle.

OO Direct readout of test current and micro-ohms on display.

OO Easy to connect and use.

OO Battery operated.

OO Simple operation. Tests can be conducted even by technicians.

Features only in CRM100B+ and 200B+OO Inbuilt memory.

OO Auto ranging.

OO PC Downloading & Analysis including ‘Trend Analysis’ possible with “CData CRM” Software.

OO In built real time clock, memory and printer. Test time stamping on each record enables time references for future use.

OO Report can be generated in software and can be exported to PDF or Microsoft Excel.

OO Enclosed in ultra rugged IP67 class hard molded case.

OO All models are supplied with rugged calibrated test lead set suitable for 4 wire measurement.

OO The instrument is supplied with CData CRM software CD, Calibration Certificate, Accessories and test leads suitable for testing of EHV class circuit breakers.

16

CRM 200B+

CRM 100B

Page 17: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

Features only in CRM100COO Powerful, truly continuous 100A DC source.

OO Selectable lower current ranges also available to test objects having higher resistance / lower current rating.

OO Optional features for CRM100C include:

OX Internal memory.OX PC connectivity and CData CRM software.

Specifications

Continuous Current Contact Resistance Meter – CRM100C

Parameter CRM100B CRM200B CRM100B+ CRM200B+

Test Current (DC) 100A 200A 100A plus 200A plus

Resistance Range 0 -199.9µΩ & 1999µΩ

0 - 199.9µΩ, 1999µΩ & 19.99mΩ

0-199.9µΩ, 1999µΩ, 19.99mΩ; Auto

ranging

0-199.99µΩ, 1999.9µΩ, 19.999mΩ; Auto

ranging

Resolution 0.1µΩ & 1 µΩ on above Ranges

0.1 µΩ, 1 µΩ& 10 µΩ on above

Ranges

0.1 µΩ, 1 µΩ& 10 µΩ on above

Ranges

0.01 µΩ, 0.1 µΩ& 1 µΩ on above Ranges

Accuracy Value ± 2% ± 1 Digit Value ± 1% ± 1 Digit Value ± 2% ± 1 Digit Value ± 1% ± 1 Digit

Display Two, 3½ digit, ½ inch LCD4 Line X 20 charac-ter LCD. 3 ½ digit

display

4 Line X 20 character LCD. 4 ½ digit display

Operation Modes Stand Alone Stand Alone & PC Control

Inbuilt Battery 6V, 4.5AH, 2 nos. 11.1V, 4 Ah

Memory Not available 1000 records

Printer Not available In-built, Thermal Printer

Battery Charger Directly on Mains input supply: 110 to 270VAC, 50/60 Hz, ± 10%

Input Supply:100 to 300 VAC, 50/60 Hz ± 10% Output Voltage: 13.5 VDC, 1000 mA

Environment 0 to 50°C, Upto 95% RH (Non condensing)

Instrument Weight 9 kg 9 kg 5kg 5kg

Parameter CRM100C

Test Current (DC) 100A, 50A, 20A, 10A - Selectable

Resistance Range 199.9µΩ, 1999µΩ, 19.99mΩ, 199.9mΩ, 1999mΩ - Selectable

Resolution 0.1µΩ

Accuracy Value ± 0.5% ± 5 digits

Display 4 line 20 character backlit LCD display

Instrument Weight 11 kg

Power 230 VAC ± 15%, 50 Hz ± 10%, 500 VA

Environment 0 to 50°C, Upto 95% RH (Non condensing)

17

CRM 100C

Page 18: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

TRM SeriesWinding Resistance Meter

TRM Series precision Winding Resistance Meters are designed for field testing as well as for factory testing of large rotating machines & transformers up to 500 MVA. Winding Resistance values of transformers and rotating machines are directly displayed. These are portable winding resistance meters designed to work in live EHV switchyards up-to 765 kV. A backlit LCD with a user-friendly menu sets up the instrument for the test. These meters are protected against the back-emf offered by large inductive windings.

FeaturesOO Uses Kelvin’s 4 wire method for resistance measurement.

OO Designed to measure DC winding resistance of highly inductive objects like transformers, generators, motor etc.

OO 30V / 50V* DC open circuit voltage.

OO Simultaneous measurement of 1 / 2 / 3* windings.

OO Quick stabilization of test results.

OO Direct readings of all channels on backlit LCD.

OO Automatic back-emf discharge with indication.

OO Simple setup and use.

OO Operation through keyboard and interactive menu.

OO Supplied with rugged aluminium carrying case for enhanced transport worthiness.

OO OLTC discontinuity indication .

*- Features available only in TRM25

Features only in TRM 25OO Displays, prints and stores test reports in the form of text header and tabulated test results.

OO Stand-alone & PC control mode.

OO Managed by powerful CTrans software to configure setup, conduct test, view & analyse results, generate test report.

OO Current range selection, enable / disable of channels, printing, downloading etc.

OO 25A / 10A / 5A / 1A / 0.1A / 0.01A DC current injection range. Resistance auto-ranging.

OO Inbuilt thermal printer for test results.

OO Temperature measurement channel and automatic temperature correction for winding resistance for copper & aluminum windings. Supplied with RTD temperature sensor.

OO OLTC dynamic test facility available optionally.

18

TRM 104

TRM 25

Page 19: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

OLTC FeatureTap changer failures account for more than 40 % of all failures on power transformers. OLTC failures are caused by degradation of OLTC contacts. SCOPE offers dynamic OLTC test facility with TRM 25 to identify weaknesses in OLTC assembly. The test is conducted in PC control mode at higher sampling speed of 10 KHz.

OO This test records variation in current flowing through the OLTC against time during tap change.

OO Gives % drop in current and transition time.

OO The drop in current during OLTC transition indicates change in transition resistance.

OO It is also possible to calculate transition time which shows healthiness of mechanism.

OO The test is very useful for assessing health of OLTC.

This optional feature extends the capability of the basic instrument making it complete test equipment for testing transformers.

Parameter TRM 14 TRM 104 TRM 25

Resistance Channels Two Two Three

Temperature Channel Not Available Yes

Current Ranges 1A, 0.1A, 0.01A 10A, 1A, 0.1A, 0.01A 25A, 10A, 5A, 1A, 0.1A, 0.01A

Maximum Resistance Range

2000Ω 2000Ω 2000Ω

Best Resolution 1µΩ 0.1µΩ 0.1µΩ

Accuracy Value ± 0.5% ± 2 digits

O/C Voltage 30V DC 50V DC

Protection Back EMF, Over Temperature, Accidental Disconnection of Lead

Discharge Automatic

OLTC Discontinuity indication

Yes

Temperature Correction No Yes

Display 4 Line 20 character backlit LCD for Resistance & Test Current

256 X 128 pixel, backlit graphic LCD for

Resistance & Test Current

Memory No 5000 results

Inbuilt Printer No Yes

PC Connectivity No Yes

Dimension 475 x 405 x 175 mm 475 x 405 x 230 mm 585 x 480 x 195 mm

Instrument Weight 10 kg 15 kg 20 kg

OLTC Dynamic Test No Yes (Optional)

Specifications

19

Page 20: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

Dir CT CT Polarity Tester

SCOPE proudly introduces Dir CT, a CT Polarity Tester specially designed to verify correctness of polarity of current transformers cores in live EHV switchyards. Polarity test is one of the most common yet crucial tests required to be done on current transformers by commissioning as well as maintenance engineers.

FeaturesOO Simple, Portable, Lightweight, Handheld device.

OO Easy and fast one push-button operation.

OO Gives analog indication (Forward & Reverse) of current transformer polarity.

OO Tests various types of CTs.

OO Works on easily available AA size alkaline batteries.

OO Gives reliable performance even after continuous usage.

OO Operating Voltage – 3 VDC, AA size alkaline batteries, 1.5 V – 2 Nos.

OO Display - Sensitive Analog Indicator. Forward & Reverse Polarity

OO Environment – 0 to 50°C, Up-to 95% RH (Non - Condensing) .

OO Dimensions – 205mm X 115mm X 50mm .

OO Weight - 400 gm.

OO Truly universal meter for variety of time interval measurement requirements such as Response time of Relays, Contactors, MCBs, MCCBs, other electro-mechanical switching devices, fusing time of Fuse elements etc.

OO Availability of 16 operation modes enable measurement of variety of time intervals.

OO Measurement from mS to hours.

OO Designed to work reliably on industrial shop-floors and in laboratories.

OO Unique feature of identifying errors in set up of test configuration.

OO Tamperproof test results through time stamp on the test data.

OO Optional PC connectivity and downloading software.

Specifications

Parameter SCOT MUT SCOT MUT4

Trigger Options START / STOP – Combination of Contact Opening / Closing & Voltage Application / Removal (AC/DC) with 16 Operation Modes

Time Range 1mS to 1999S 0.1mS to 9999S

Resolution 1mS 0.1mS

Accuracy Value ± 0.05% ± 1 digit

Display 4 line 20 character backlit LCD

Memory 50 results

SCOT UT SeriesUniversal Time Interval Meter

20

Page 21: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

DC TraceDC Earth Fault Locator

DC Trace, is most advanced and user friendly DC Earth (Ground) Fault Locator. This portable instrument consists of Signal Generator & Signal Receiver. It uses latest digital signal processing technology. It’s ability to detect earth faults in live DC system quickly & accurately in on-line condition greatly relieves the substation maintenance engineers from nightmare of earth leakages & its detection.

FeaturesOO On-Line fault detection, No shutdown required.

OO Signal Generator has adjustable output voltages (24V, 48V, 110V, 220V, 500V and 1000V) suitable for different applications.

OO Pinpoints high grounding resistance faults (up to 1MΩ).

OO Digital Signal Processing Technology for detecting grounding resistance and distributed capacitance.

OO Selectable output frequency (10Hz(default) , 50Hz, 60Hz, 325Hz) .

OO Frequency Spectrum Analysis to test the existing interferences available in the circuit and selection of correct test frequency.

OO Signal Receiver with adjustable sensitivity at different locations of circuit helps to locate the current leakage quickly.

OO Direction (positive or reverse) indication for leakage current helps quick tracing of the faulty grounding path.

OO Following multiple analysis & indications of ground fault makes pinpointing easy:

OX Direction of current flow

OX Phase angle difference

OX Comparison of signal strength

OO Can detect complex, multipoint faults.

OO Type Tested as per IEC 60068.

Specifications

Parameter Details Parameter Details

Fault Location Technique

Direction of current flow, Phase angle

difference, Comparison of signal strength

Battery Charging Input 230V / 110V AC, 50 / 60Hz

Output Voltage 24V,48V,110V, 220V, 500V, 1000V Memory 128MB

Output Frequency 10Hz, 50Hz, 60Hz, 325Hz Display - Signal Generator 128 × 64 pixel colour LCD

Fault Location Sensitivity Up to 1MΩ Display - Signal Receiver 240×320 pixel 3.5” colour TFT touch screen

Current Detection Sensitivity ≥0.1mA Working Environment 0˚C to 50˚C, <95% RH (Non-condensing)

Current Detection Clamp 60mm (jaw opening),

Ø 65 x 30mm and Ø12 x 8mm, dual range

Dimensions 360 X 260 X 135mm

Battery Life ≥4 hours Weight 7.0 kg (Approx.)

21

Page 22: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

CFL SeriesCable Fault Locator

SCOPE offers CFL Series, new generation Cable Fault Locator Test System, an ultimate solution for locating all types of underground cable faults in minimum time, thus saving long outages and consequential revenue loss & inconvenience. SCOPE offers full range of products required for fault location of LT/HT telecom and power cables. It includes various models of Surge Generators (Thumpers), Pre-Locators, Pin-Pointers, SIM Filters and Audio Generators. Based on application requirements correct models can chosen and product configuration can be optimized. Brief table giving availability of models is given hereunder.

Cable Fault Surge Generator: CFL SG SeriesSCOPE offers CFL SG Series Surge Generators ranging from 16 kV to 32 kV and 500 Joules to 2000 Joules.

Features OO Compact, rugged design.OO Key Lock Switch to prohibit unauthorized operation.OO Variac Zero & Output Plug Interlock for HV circuit.OO HV Switch Interlock.OO Over Heat Protection at 70 deg C.

Specifications

Product Model

Surge Generator (Thumper) CFL SG 1605/1610/3210/3220

Pre Locator CFL PL2, CFL PL3, CFL PL4

Pin Pointer CFL PP3

Audio Generator CFL AG2

SIM Filter CFL SIMF

Cable Identification System CFL CIS

Parameter CFL SG 1605 CFL SG 1610 CFL SG 3210 CFL SG 3220

Output Ranges 0-4/0-8/0-16 kV 0-8/0-16/0-32 kV

Output Energy 500J 1000J 1000J 2000J

Impulse Period Sequence Single Impulse/ 4 Sec /8 Sec Single Impulse 2 Sec/4 Sec /8 Sec.

Fault Distance Measurement Mode ICM (Internal Current Coupler) / SIM Filter

Output Voltage Indication Moving Coil Meter with 3 Ranges

Protections Key Lock Switch , Variac Zero Interlock, HV Switch Interlock , Output Plug Inter-lock, Over Heat Protection with LED Indicator

Input Supply 230V AC +/-10%, 50/60Hz

Environment 0 to 50 deg C, 95% RH (Non-condensing)

Housing Elegant, rugged aluminium housing. CFL SG will be directly mounted inside trol-ley, if optional trolley is purchased.

Dimensions 484(L) X 360(W) X 580(H) mm

540(L)X 430(W)X 750(H) mm

Main Unit: 540 (L)X 430 (W)X 750 (H) mm Additional Capacitor Bank: 540 (L)X

300 (W)X 400 (H) mm

Weight 55 Kg. 60 Kg. 95 Kg. 95 Kg. + 40 Kg.

22

Page 23: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

Cable Fault Pre Locators: CFL PL 2, CFL PL3 & CFL PL4CFL PL Series, new generation Cable Fault Pre-Locators from SCOPE are the ultimate solution for locating underground cable faults in minimum time. Three models, CFL PL2, CFL PL3 & CFL PL4 uses advanced technology

FeaturesOO Measuring range up to 16 km for PL2 / PL3. 64km for PL4.

OO Large LCD & User friendly operation. Colour LCD with touch screen in PL4.

OO Adjustable Balance of instrument resistance to suit the cable under test.

OO Adjustable Gain for optimal waveform resolution.

OO Large range of Propagation Velocity covers all type of cables including pilot and telecom cable

OO Facility to store & compare waveforms.

OO Memory to store up to 50 waveforms. 100 waveforms in PL4.

OO Housed in rugged, IP class moulded case.

Specifications

Cable Fault Pin Pointer: CFL PP3The most versatile Cable Fault Pin Pointer yet, SCOPE’s CFL PP3 is suitable for pin-pointing as well as route tracing of any type of power cable.

FeaturesOO Used for pinpointing as well as route tracing.

OO Magnetic & acoustic inputs making pinpointing very convenient.

OO Digital filters eliminate external influences.

OO Effective shielding against environmental noises.

OO Highly sensitive magnetic signal pick up.

OO Improved acoustic signal pick up.

OO Large LCD display with back-lit.

OO Internal Li-ion chargeable battery.

OO Specially made light weight case ensuring minimum strain to operator.

Parameter CFL PL2 CFL PL3 CFL PL4

Measuring Modes TDR & ICM TDR, ICM & SIM

Transmitting Pulse Amplitude 30V

Transmitting Pulse Width 40ns-3.56µs

Sampling Rate 100MHz (10nS)

ResolutionTDR Mode and SIM Mode: <±1m up to range <4km, <± 4m for range>4km

ICM Mode: <± 4m up to range <4 km and <± 16m for ranges >4km

Measuring Range 0-16 km 0-64km

Propagation Velocity 90-300m/µs.

Display 320x240 LCD 640x480, Touch screen and Color LCD

Communication RS232 USB

Internal Memory 50 results 100 results

Charger Voltage Input: 110-265V AC, Output: 8.4V ± 10% DC

23

Page 24: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

Specifications OO Filter Frequency: 200Hz, 300Hz, 500Hz

OO Time Delay Resolution: 0.2ms

OO Amplification: >120 dB, adjustable

OO Accuracy: High Resistance Fault: 0.1m, Low Resistance Fault: 2m, Route Tracing: 0.2m

OO Headphone Output: 3.5mm

OO Power Supply: 7.4 V Lithium-ion rechargeable battery

OO Charger: Input: 230 VAC±10% , Output: 8.4 VDC

OO Environment: 0 to 50 deg C, 95% RH (Non-condensing)

OO Dimension: 230mmx140mmx170mm

OO Weight: 1.5Kg

Cable Fault Audio Generator: CFL AG2Audio Frequency Generator has been designed to be used for cable route tracing, pin-pointing of low resistance welded faults, joint location and cable identification.

FeaturesOO Automatic impedance matching.

OO High audio power output.

OO Quartz stabilized frequency.

OO Clean and distortion free signal output.

OO Output in seven ranges, selectable manually or automatically.

OO User friendly operation with minimum controls and Analog Ammeter display.

OO Overload protection.

OO Over current protection and indication.

SpecificationsOO Max. Output Power: 20W

OO Max. Output Current: 2.8A ± 20%

OO Frequency: 1kHz Sine Wave.

OO Output Voltage: In 7 steps 4-7V/15-25V/30-40V/60-70V/90-100V/150-170V/200-230V

OO Operating Modes: Continuous and Intermittent

OO Input Supply: AC 230V±10%, 50Hz ±10%

OO Protection: Over Current

OO Environment: 0 to 50 deg C, 95% RH (Non-condensing)

OO Dimension & weight: 275mm x 255mm x 130mm, 5Kg

Cable Fault SIM Filter: CFL SIMF SIM Filter is an active filter having its own in-built DC Power Source of 1800 VDC for stabilizing the arc after breaking of the fault by Surge Generator. The SIM Filter, CFL SIMF works in conjunction with SCOPE’s Cable Fault Pre Locator CFL PL Series & appropriate Cable Fault Surge Generator, CFL SG Series, up-to 32KV.

SpecificationsOO Output Voltage: 1800 VDC, Negative Polarity

OO Arc Stabilization Time: ≥20 ms

OO HV Input: Max. 35 kV DC Negative Polarity

OO Input Power Supply: AC 230V±10%, 50±1Hz

OO Environment: 0 to 50 deg C, 95% RH (Non-condensing)

OO Dimension: 450mm x 370mm x 500mm

OO Weight: 25kg

24

Page 25: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

BRT 1Battery Resistance Tester

Battery bank installations are important & essential part of various power, communication, information technology & industrial set-ups. In order to ensure healthy performance of such installations, the batteries used need to be properly monitored. SCOPE’s BRT 1 is the comprehensive battery operated, portable, hand held Battery Resistance Tester suitable for all Lead Acid & Nickel Cadmium cells having cell voltage of 1.2V / 2V / 6V / 12V.

FeaturesOO Smart, rugged and portable hand held device with colour touch screen display

OO Suitable for batteries up to 6000 Ah.

OO Tests all types of batteries having cell voltage of 1.2V / 2V / 6V / 12V.

Option of self-defined voltage is also available.

OO On line measurement - No disconnection of cell.

OO Simultaneously tests cell terminal voltage, internal resistance and relative percentage capacity of the cell.

OO Built-in reference value or self-defined value for comparison of test results with standard values.

OO Low frequency testing effectively avoids interference from capacitive resistance of battery itself.

OO Stable and accurate results in presence of high interference.

OO Fast operation & quick stabilization. Auto saving of results.

OO Large memory to store results of up-to 3000 cells.

OO Auto-calibration of unit before testing.

OO Over voltage protection & audio alarm.

OO Analysis of results through PC Data Management Software including Histogram.

Note: SCOPE also offers Battery Conductance Tester, BCT 1 for conductance measurement of battery cells from 100 to 19990 Siemens.

Specifications

Parameter Range Resolution Accuracy

Resistance

0µΩ - 250µΩ 1 µΩ 5% ± 6 digit

250µΩ - 500µΩ 0.01mΩ 3% ± 6 digit

500µΩ - 100mΩ 0.1mΩ 1% ± 6 digit

Voltage 0 to 16V 1mV ± 0.2% of reading ± 6 digit

Measuring Cells Per String Up to 254

Display Colour TFT touch screen LCD, 320 x 240 pixel, 3.5”

Memory 3000 test results

Power Supply Li-ion battery

Working Time > 5 hours continuous

Environment 0°C to 50°C, up-to 95% RH (Non-condensing)

Dimension (L x W x H) 210 mm x 110 mm x 60 mm

Weight 2 kg (including accessories)

25

Page 26: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

DecR High Resistance, High Voltage Decade Resistance Box

A Decade resistance box is a enclosure containing number of precision resistors connected to panel terminals or contacts so that a desired resistance value can be obtained by withdrawing plugs or by setting multi-contact switches.

SCOPE offers High Resistance, High Voltage Decade Resistance Box - DecR designed using the high quality specially selected resistors. These range of high ohm resistance decades are ideal for variety of applications, having a voltage rating up to 5kV. It covers the resistance range from 1 kilo ohm to 1 tera ohm.

Features

OO Accurate and high precision resistors.

OO Compact, convenient to use.

OO Very low contact resistance.

OO Used in various applications such as:

OX Measurement of unknown resistances by the "bridge" method.

OX Calibration and integrity check of multimeters, LCR meters and calibrators.

OX In different electrical and electronic workshops and laboratories.

OX In developmental work it might be necessary to test which resistance will have the best effect given certain circuit characteristics.

OX Educational establishments.

OO Range: 1 kilo ohm to 1 tera ohm.

OO Max Voltage: 5kV.

OO Accuracy: ± 0.1%.

OO Portable, housed in rugged molded case.

Specifications

Resistance Per Step

Total Decade

Resistance

Maximum Volage(V)

VoltageCoefficient(ppm/V)

TempCoefficient(ppm/°C)

Accuracy(%) Power (Watt)

1kΩ 10kΩ 500 0 ±50 ±0.1 1

10kΩ 100kΩ 500 0 ±50 ±0.1 1

100kΩ 1MΩ 500 0 ±50 ±0.1 1

1MΩ 10MΩ 500 0 ±50 ±0.1 1.5

10MΩ 100MΩ 4,000 1 ±100 ±1 1.5

100MΩ 1GΩ 4,000 1 ±100 ±1 1.5

1GΩ 10GΩ 4,000 1 ±100 ±1 3.5

10GΩ 100GΩ 5000 1 ±100 ±1 3.5

100GΩ 1TΩ 5000 1 ±2,000 ±2 1.3

26

Page 27: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

SCOPE CasesIndustrial Cases Division

SCOPE introduced for the first time in the country, a range of professional industrial cases of international quality in aluminum composites way back in year 2000. These cases are made of sandwich board made of aluminum & plywood / MDF sheet. Aluminum sheet is at outside and is offered in different finishes. SCOPE developed its own sections and fittings to suit various inside arrangements. Initially for two years these cases were used only for our own electronic test & measurement instruments. We then started selling them as a product after having good knowledge and expertise.

Being manufacturers for more than 14 years, we have good set up consisting of necessary facilities and set processes to produce quality products consistently. Good quality material, unique features, design support, flexibility in sizes, value addition / customization as per customer needs are the main features of our growing business every year. Our products are renowned for their durability, style, excellent finishing, lightweight and resistance against scratches and corrosion.

OO SCOPE Industrial Aluminum cases are basically customized and are used as Transportation Cases, Demo Kits, Display kits, Laptop Case, Enclosures, Carrying case for expensive instruments, Toolkits etc.

OO Special sections allow us to provide partitions, different mounting arrangements etc.

OO Foam cushioning, hardware mounting chassis etc. is done as per the requirement.

OO SCOPE also supplies Trolleys as per requirement. These are made in M.S. Square tubes duly powder coated with wheels.

OO Supplying to multinational companies, medical instrumentation companies, National testing labs, Calibration labs, T&M and Home Security instrument manufacturers, Automation products companies, Electrical fittings manufacturers, Switchgear companies etc.

OO Now SCOPE also introduces Molded cases which are dust proof, shock proof and water proof, IP 65 compliant. These are available in various sizes.

* For more information or enquiries mail to [email protected]

27

Page 28: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

We at SCOPE take pride in ensuring that instruments supplied by us are always in good working condition and within valid calibration limits. Providing prompt & on-site after sales service support is our constant endeavor. In order to enrich the goal of customer satisfaction we have a range of services that go beyond "conformance to specifications” like technical support on usage, precautions, trouble-shooting, how to......, is it possible to…..., etc.

Under the CSG, we are providing following services:• Repairs & Servicing of instruments• Periodical Calibration with traceability to NPL• Comprehensive Annual Maintenance Contracts (AMC)• Product up- gradation

• Training on operation & maintenance of instruments, test results interpretationWe are providing above support on-site as well as at our Service Centers located at Pune, Delhi, Chennai & Kolkata. We have team of highly skilled & trained engineers located at these places who are highly customer focused.

We are still providing services for instruments as old as 20 years. In order to enhance the usable life of instruments we also offer the up-gradation of old products at nominal costs. It helps improve performance, reliability & serviceability. It also guards products from unavailability of some of the components that become obsolete in fast changing electronics field. Under AMC scheme our engineers periodically visit the site, check all components for deviation in performance, do calibration once in year and also give training / retraining to customers. If there are any design modifications incorporated to improve the reliability & performance of products, these modifications are also incorporated in old instruments as part of AMC.

We also conduct comprehensive workshops & training programs for Utility engineers covering usage, do’s and don’ts of instruments, precautions to be taken during usage in live switchyards, correct test procedures, maintenance & upkeep of kits and most importantly correct interpretation of test results to assess the condition of test object. It helps customers use the product to its fullest potential.

*For more information or enquiries mail to [email protected]

Customer Support Group

SCOPE CSG

28

Page 29: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

SCHELOGMaintenance Manager Software

OO A system by which maintenance of equipment is scheduled and monitored.

OO Easy & user friendly graphical user interface.OO Startup graphics in the form of single line diagrams for

substations.OO Separate tabs for Auxiliary and Protection equipment in the

startup GUI.OO Schedules tests automatically as per test frequency for every year and logs the data, logged data is

available in terms of reports and analysis.OO Web based, thereby facilitating remote access & data sharing.

Purpose

OO Schedule test activities for the various devices (Function as well as Support devices).OO Monitor test activities, collect and analyze test results.OO Take timely action thereby minimizing the possibility of a

system failure.

Features

OO EUT (Equipment Under Test) InformationOX EUT Type & Location info OX Component Hierarchy & History

OO Test Schedule - shows all pending tests at various stagesOX Substation Information OX EUT location & type OX Test Definition, Details and Parameters OX Test Instrument with Instrument Owner & Owner HierarchyOX Instrument details including category, Type, Serial No., Make and Calibration details OX User List & Approval Level OX Test procedure for each test as attachments OX Facility to reschedule tests, Skip tests, Disapprove and Approve tests with condition

OO AlarmsOX Allows a user to Schedule tests and raise alarm for tests. Scheduled - to be set by Administrator OX Alarms are raised until either the test is conducted or it is rescheduled OX Alarms are raised for calibration of the support equipments (e.g. test instruments)OX Alarms are also raised in case a device fails to clear tests

OO Forms and ReportsOX Collection of the test data are in user-friendly form, designed as per the company normsOX Reports are available for viewing collected data, uniformity in reports throughout the organization OX Design new report formats with the Provision to add pre-commissioning values OX Consolidated Schedule Reports OX Major Maintenance Reports

OX Failure Reports OX Trend Analysis & Component Performance

OO Analysis OX SCHELOG assists in analyzing collected data OX Maintains a history of all devices, test schedules and EUT locationsOX Compares test results of different types of EUT against specific test parameter

OO RolesOX Role Management - required access of the software to different role users only by the administrator OX Roles can be defined depending on the hierarchy in the company OX All roles (and thereby users) are not able to avail of all features of SCHELOG

29

Page 30: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

Transformer Turns Ratio Meter, TTRM 300Lightweight, rugged, high accuracy TTRM with convenient user interface having capability to work in live switchyards up-to 765 kV.

OO Accurate (24 bit ADC resolution) measurement of turns ratio of single as well as three phase transformers. Measurement of voltage ratio, excitation current and phase deviation.

OO Vector group detection & detection of polarity of windings.

OO Inbuilt tap changer control and tap position detection facility.

OO One time connection to three phase transformer with dedicated test lead set.

OO Excitations voltages of 10V, 40V and 100V.

OO 5.7” TFT display with touch screen & in built thermal printer.

OO Results data storage through USB port.

OO Protection against emergency stop, induced voltage & short circuit.

OO Ethernet connectivity to PC for downloading and analysis of results in windows based software.

OO Housed in rugged IP 67 class molded case.

Battery Loading Unit, BLU SeriesPortable, multi-range, all in one unit for controlled discharge of battery banks of various capacities. Choice of various models is available as per the discharge requirements.

OO Both control & discharge unit are part of single instrument with LCD display.

OO Discharge voltage range from 12 V to 380 V and current range up-to 300A.

OO Larger units have wheels for convenient onsite testing.

OO Real-time monitoring & display of voltage for each cell with the help of portable Data Acquisition Case (DAC) having wireless communication with main instrument.

OO BLU accepts 4 conditions for auto shut-down of discharge process thus enabling secured and time-saving operation.

OO Parallel connection of two discharging units for mass discharge is possible.

OO Auto sorting for log-out batteries during discharging.

OO Safe circuit design to avoid damage of battery while testing.

OO Powerful Software for real time data monitoring, analysis and printing of report.

OO Thermal cut-off and automatic overload protection.

Meter Testing System, MTS SeriesQuick check solution for verifying the accuracy of single & three phase (3W or 4W) metering units & kWh meters in on-line, on-site condition.

OO Checks power consumption, CT ratio, phase deviation, circuit breakage inspection, power abnormality analysis, power theft, wiring check etc.

OO Combination of electricity meter tester and power quality analyser.

OO Smart, portable and easy to use with vivid touch-screen (TFT) display.

OO Online monitor for real-time data testing and comparison.

OO Test result playback on screen and transferable to PC for report printing.

Launching Soon...

30

Page 31: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

www.scopetnm.com

Our Customer SegmentsOO Power Sector

OX Generation

OX Transmission

OX Distribution

OO OEM

OO Railways

OO Metal, Oil & Gas, Fertilizers, Cement Industries

OO Test Laboratories

OO Testing & Commissioning Companies

Best Product Award :CB Operational Analyser

Best Product Award LA Leakage Current Analyser

SCOPE is Partner Company in 1200kV National Test Station Project of POWERGRID at Bina, INDIA

ISO 9001:2008TUV NORD, Germany

Our Recognitions

Our Global Presence

31

Page 32: SCOPE - donar.messe.de · SCOPE T&M Division Introduction 5 SCOPE Protect Division Introduction 6 ISOSCELES Introduction 7 Circuit Breaker Dynamic Test System - HISAC Ultima 8

SCOPE

SCOPE