scadapack 32 controller
TRANSCRIPT
SCADAPack 32 Controller Hardware Manual
CONTROL MICROSYSTEMS SCADA products... for the distance
28 Steacie Drive Telephone: 613-591-1943 Kanata, Ontario Facsimile: 613-591-1022 K2K 2A9 Technical Support: 888-226-6876 Canada 888-2CONTROL
SCADAPack 32 Controller Hardware Manual ©1997-2001 Control Microsystems Inc. All rights reserved.
Printed in Canada.
Trademarks TeleSAFE, SmartWIRE, Micro16, SCADAPack 32, and TelePACE are registered trademarks of Control Microsystems Inc.
All other product names are copyright and registered trademarks or trade names of their respective owners.
Table of Contents
OVERVIEW......................................................................................................................... 6
INSTALLATION.................................................................................................................. 8 Field Wiring .................................................................................................................... 8
Controller Board Field Wiring Connectors................................................................ 8 Lower I/O Module Field Wiring Connectors ............................................................. 9
Jumpers ....................................................................................................................... 10 Power Supply............................................................................................................... 10
Controller Board Power Supply .............................................................................. 10 Lower I/O Module Power Supply............................................................................ 11 Recommended AC Power Supply Configuration ................................................... 12 Recommended DC Power Supply Configuration ................................................... 13 Alternate AC Power Supply Configuration ............................................................. 14 Using Model 5103 Uninterruptible Power Supplies................................................ 15 Recommended 5103 Power Supply Configuration ................................................ 15 Sample Power Supply Calculations ....................................................................... 16
Sample Power Calculation for SCADAPack 32 Controller ....................... 16 System Grounding.................................................................................................. 17
Analog Inputs ............................................................................................................... 18 Controller Board Internal Analog Inputs ................................................................. 18 Lower I/O Module Analog Inputs ............................................................................ 18 Analog Inputs Data Format..................................................................................... 19
Analog Outputs ............................................................................................................ 21 Current Outputs ...................................................................................................... 21 Voltage Outputs...................................................................................................... 21 Analog Outputs Data Format.................................................................................. 22
Digital Inputs ................................................................................................................ 23 Controller Board Digital /Counter Inputs................................................................. 23 Controller Board Interrupt Input.............................................................................. 23 Lower I/O Module Digital Inputs ............................................................................. 25
Digital Outputs ............................................................................................................. 26 Controller Board Status Output .............................................................................. 26 Lower I/O Module Digital Outputs .......................................................................... 26
SERIAL COMMUNICATION ............................................................................................ 29 RS-232 Serial Communications Ports ......................................................................... 29
COM1 RS-232 Serial Port ...................................................................................... 29 COM2 RS-232 Serial Port ...................................................................................... 30 COM3 RS-232 Serial Port ...................................................................................... 30 COM4 RS-232 Serial Port ...................................................................................... 31 RJ-45 Modular Connector for RS-232.................................................................... 32 DE-9P Connector for RS-232................................................................................. 33
RS-485 Serial Communication Port............................................................................. 35 RJ-45 Modular Connector for RS-485.................................................................... 35 RS-485 Bias Resistors ........................................................................................... 36
SCADAPack 32 Controller User and Reference Manual 3
RS-485 Termination Resistors ............................................................................... 36 RS-232 Wiring Examples............................................................................................. 37
DTE to DTE without Handshaking.......................................................................... 37 DTE to DTE with Handshaking............................................................................... 37 DTE to DCE with Handshaking .............................................................................. 38
RS-485 Wiring Examples............................................................................................. 39 Four wire mode....................................................................................................... 39 Two wire mode ....................................................................................................... 39
RS-232 Cables ............................................................................................................ 41 RJ-45 to DE-9S DTE .............................................................................................. 41 RJ-45 to DE-9P DCE.............................................................................................. 41 RS-485 Cable ......................................................................................................... 41
ETHERNET COMMUNICATION ...................................................................................... 43 LAN Port Settings ........................................................................................................ 43
TCP/IP Settings ...................................................................................................... 43 Modbus/TCP Settings............................................................................................. 43 RJ-45 Modular Connector for Ethernet .................................................................. 45
OPERATION..................................................................................................................... 46 Operating Modes ......................................................................................................... 46
Run Mode ............................................................................................................... 46 Service Mode.......................................................................................................... 46 Cold Boot Mode...................................................................................................... 47
LED Indicators ............................................................................................................. 47 Controller Board LEDs............................................................................................ 47 Lower I/O Module LEDs ......................................................................................... 48
LED Power Control ...................................................................................................... 49 Status LED and Output................................................................................................ 49
I/O Module Error Indication..................................................................................... 49 Configuration Switches ................................................................................................ 51
Analog Input Range Selection................................................................................ 51 Analog Output Range Selection ............................................................................. 51 Digital Input Filters.................................................................................................. 52 Line Frequency Selection....................................................................................... 52
MAINTENANCE ............................................................................................................... 54 Fuses ........................................................................................................................... 54 Lithium Battery ............................................................................................................. 54
TROUBLESHOOTING ..................................................................................................... 55 Analog Inputs ............................................................................................................... 55 Analog Outputs ............................................................................................................ 55 Digital Inputs ................................................................................................................ 56 Digital Outputs ............................................................................................................. 56
SPECIFICATIONS............................................................................................................ 57 General ........................................................................................................................ 57
SCADAPack 32 Controller User and Reference Manual 4
Controller Board........................................................................................................... 57 Communications .......................................................................................................... 58 Visual Indicators .......................................................................................................... 59 Power Supply............................................................................................................... 60
Controller Board ..................................................................................................... 60 Lower I/O Module ................................................................................................... 60
I/O Capacity ................................................................................................................. 60 Analog Inputs ............................................................................................................... 61 Analog Outputs ............................................................................................................ 62 Digital Inputs ................................................................................................................ 63
Controller Board ..................................................................................................... 63 Lower I/O Module ................................................................................................... 63
Digital Outputs ............................................................................................................. 65 Controller Board ..................................................................................................... 65 Lower I/O Module ................................................................................................... 65
CE Mark Self Declaration ............................................................................................ 66
SCADAPack 32 Controller User and Reference Manual 5
Overview The SCADAPack 32 controller is the latest in the SCADAPack series of controllers and is fully compatible with existing SCADAPack installations. The SCADAPack 32 consists of a controller board and a lower I/O module.
The controller board has an integrated power supply, three digital/counter inputs, an interrupt input, a status output, a 10-BaseT Ethernet port and three serial communication ports. Two of the serial communication ports are RS-232 and the third is configurable RS-232/485.
The lower I/O module has eight analog inputs, sixteen digital inputs, twelve digital outputs and one RS-232 serial communication port. The lower I/O module may be configured with two optional analog outputs.
The I/O capacity of SCADAPack 32 Controllers can be expanded by using 5000 Series I/O modules. A maximum of forty 5000 Series I/O modules may be used for a total expansion capacity of 256 digital inputs, 256 digital outputs, 128 analog inputs, 64 analog outputs (when no optional analog outputs have been installed) and 32 counter inputs.
The lower I/O module RS-232 serial communication port supports half-duplex communication and RTS/CTS hardware handshaking for connection to modems and radio modems. This RS-232 port operates at baud rates from 1200 baud to 115200 baud.
SCADAPack 32 memory has 8 Mbytes SDRAM, 4 Mbytes flash ROM, and 0.5 Mbytes CMOS SRAM. The CMOS SRAM is non-volatile (battery backed.). A real time clock
SCADAPack 32 Controller User and Reference Manual 6
calendar provides for time of day operations and alarms. A hardware watchdog timer protects against application program failures.
The SCADAPack 32 is able to enable and disable status LEDs on all modules connected to the 5000 Series I/O bus including the controller board and the lower I/O modules.
SCADAPack 32 Controller User and Reference Manual 7
Installation The installation of SCADAPack 32 controllers requires mounting the SCADAPack 32 controller on the 7.5mm by 35mm DIN rail and connecting the SCADAPack 32 controller to the system I/O Bus. Refer to the System Configuration Guide, at the beginning of this manual, for complete information on system layout, I/O Bus cable routing and SCADAPack 32 controller installation.
Field Wiring SCADAPack 32 controllers use screw termination style connectors for termination of field wiring. These connectors accommodate solid or stranded wires from 12 to 22 AWG.
The connectors fit over pins on the controller board and the lower I/O module. The connectors are removable allowing replacement of the SCADAPack 32 Controller without disturbing the field wiring. Leave enough slack in the field wiring for the connector to be removed.
CAUTION: Remove power before servicing unit.
To remove the termination connector:
• Pull the connector upward from the board. Apply even pressure to both ends of the connector.
To install the termination connector:
• Line up the pins on the module with the holes in the connector. Make sure all the pins line up properly.
• Push the connector onto the pins. Apply even pressure to both ends on the connector.
Controller Board Field Wiring Connectors The controller board has six connectors for field wiring. Refer to the following diagram for connector locations.
The power inputs and output are wired to a six-pole connector. Refer to the Controller Board Power Supply section for more information.
Digital/counter inputs, the interrupt input and the status output are wired to an eight-pole connector. Refer to the Controller Board Digital /Counter Inputs, Controller Board Interrupt Input and Controller Board Status Output sections for more information.
Each of the three serial communication ports are wired to a black 8 pin modular connectors. Refer to the Serial Communication Section for more information.
The Ethernet LAN Port is wired to a black 8 pin modular connector. Refer to the Ethernet Communication Section for more information.
SCADAPack 32 Controller User and Reference Manual 8
0 1 2 COMDIN/COUNTER
+ –STATUS
+ –INT
AC/DCPWR IN
+ –DC PWR
5V LEDS STATRUN FORCE INT CTR1 CTR2CTR0 LAN LINK TX RX CTS DCD TX RX CTS DCD TX RX CTS DCD
Power Supply and CPU Interupt and Counters COM1 COM4LAN COM2
SW1
P11
F2F1
J5
TXRX
RS485 RS232
J7J8
J9 J10
COM PortJ4
P1 P2
BT1
P6COM1
RS-232/485
P7COM2RS-232
P8COM4RS-232
P5LAN
LED POWER
P4P3
P11
P9J2
Lower I/O Module Field Wiring Connectors The lower I/O module has seven connectors for field wiring. Refer to the drawing below for connector locations.
The AC/DC power inputs, DC power output and analog outputs are wired to a nine-pole connector. Refer to the Lower I/O Module Power Supply section and the Analog Outputs section for more information.
The analog inputs are wired to a nine-pole connector. Refer to the Lower I/O Module Analog Inputs section for more information.
The digital inputs are wired to two nine-pole connectors. Refer to the Lower I/O Module Digital Inputs section for more information.
The digital outputs are wired to two ten pole connectors. Refer to the Lower I/O Module Digital Outputs section for more information.
The lower I/O module has one RS-232 serial communication port that is wired to a DE-9P plug connector. Refer to the Serial Communication section for more information.
SCADAPack 32 Controller User and Reference Manual 9
COM3Status LEDS
Analog InputConnector (P4)
Power and AnalogOutput Connector (P3)
Digital Inputs 0-7Connector andstatus LEDs (P5)
Digital Inputs 8-15Connector andstatus LEDs (P6)
Relay Contacts 4-11Connector (P8)
Relay Contacts 0-3Connector (P7)
Relay StatusLEDs
COM3 RS-232Connector (P11)
DIN Status LEDS
Chassis Groundlink. (J3)
Jumpers Most headers and jumpers on the controller board are reserved for manufacturing and test functions.
The RS-485 termination jumpers are described in the RS-485 Serial Communication Port section. See the RS-485 Termination Resistors section for additional information.
Power Supply The primary power supply is a 5V and 24V supply in the controller board. This supply is sufficient to power the controller board and the lower I/O module and a limited number of 5000 Series I/O modules. A second 24V supply is available in the lower I/O module on the SCADAPack 32 Controller.
NOTE: Voltage referred to as Vrms (or VAC on some products) indicates AC power. Voltage referred to as V indicates DC power.
Controller Board Power Supply The controller board power supply provides a 5V output to power the lower I/O module and 5000 Series modules through the IMC cables. This supply has a 1.3A output capacity. The 24V can be supplied from the controller board to the lower I/O module and to other 5000 Series I/O modules. Refer to the System Configuration Guide, at the beginning of this manual, for more information.
SCADAPack 32 Controller User and Reference Manual 10
The controller board power supply accepts AC or DC input power. Connect a power source to the input power in one of the following ways:
CAUTION: Power can be applied to either the AC/DC power input OR the DC power input. DO NOT apply power to both inputs. Damage to the power supply may result.
A 16Vrms source connects to the AC/DC PWR IN terminals. Recommended AC Power Supply Configuration shows this AC power source coming from a transformer.
A 13-24V source may be connected to the AC/DC PWR IN terminals instead of the 16Vrms source, although this is not common. The polarity of the source does not matter.
An 11-24V source connects to the DC PWR terminals. Recommended DC Power Supply Configuration shows this DC power source coming from a battery.
The AC/DC power input typically connects to a 16Vrms source or a 24V source. Under these conditions, 20 to 24V is available at the DC PWR terminals, suitable for powering 20mA loop transmitters.
The DC PWR input typically connects to 12V batteries or 12-24V DC power supplies. There is no battery charger with the SCADAPack 32 controller. Under these conditions, no connection should be made to the AC/DC power input.
Lower I/O Module Power Supply The lower I/O module power supply is used primarily to power the internal circuitry of the lower I/O module. When a 16Vrms or 24V source is connected to the AC/DC PWR IN input 20 to 24V is available at the DC PWR terminals. Refer to the System Configuration Guide, at the beginning of this manual, for more information.
The lower I/O module power supply accepts AC or DC input power. Connect a power source to the input power in one of the following ways:
CAUTION: Power can be applied to either the AC/DC power input OR the DC power input. DO NOT apply power to both inputs. Damage to the power supply may result.
An 11-24V source connects to the DC PWR terminals. Recommended AC Power Supply Configuration shows this DC power source coming from the controller board. Recommended DC Power Supply Configuration shows this DC power source coming from a battery.
A 16Vrms source connects to the AC/DC PWR IN terminals. Alternate AC Power Supply Configuration. shows this AC power source coming from a second transformer.
A 13-24V source may be connected to the AC/DC PWR IN terminals instead of the 16Vrms source, although this is not common. The polarity of the source does not matter.
The DC PWR input connects to 12V batteries or the DC PWR output of the controller. Under these conditions, no connection should be made to the AC/DC PWR IN input. There is no battery charger with the lower I/O module.
The AC/DC PWR IN input typically connects to a 16Vrms or 24V source. Under these conditions, 22 to 24V are available at the DC PWR terminals, suitable for powering 20mA loop transmitters.
SCADAPack 32 Controller User and Reference Manual 11
Recommended AC Power Supply Configuration This configuration uses a single Class 2 transformer to power the controller board and the lower I/O modules. 24V are available on the controller module connector P3. They are used to power the analog circuitry for the analog input circuits on the lower I/O module.
AC/DCPWR IN
DC PWR+ –
120Vrms
16Vrms
1 2 3 4 5 6
Class 2Transformer
P3
P3
Lower I/O Module
Controller Board
AC/DCPWR IN
DC PWR+ –
1 2 3 4 5 6
AOUT 0 1 COM7 8 9
SCADAPack 32 Controller User and Reference Manual 12
Recommended DC Power Supply Configuration This configuration uses a single power supply or battery to power the controller board and lower I/O module. Refer to the System Configuration Guide, at the beginning of this manual, for more information. The power supply is used to power the analog circuitry for the lower I/O module.
AC/DCPWR IN
DC PWR+ –
1 2 3 4 5 6P3
P5
Controller Board
AC/DCPWR IN
DC PWR+ –
1 2 3 4 5 6
AOUT 0 1 COM7 8 9
11-24V powersupply or battery.
Lower I/O Module
SCADAPack 32 Controller User and Reference Manual 13
Alternate AC Power Supply Configuration This configuration uses two single Class 2 transformers to power the controller board and the lower I/O module. This configuration is capable of higher DC power output levels than those shown in the Recommended AC Power Supply Configuration section..
AC/DCPWR IN
DC PWR+ –
120Vrms
16Vrms
1 2 3 4 5 6
Class 2Transformer
P5
P3
AC/DCPWR IN
DC PWR+ –
1 2 3 4 5 6
AOUT 0 1 COM7 8 9
120Vrms
16Vrms FUSE
+ 24 V for transmitters
1.0A slow blow
Controller Board
Lower I/O Module
SCADAPack 32 Controller User and Reference Manual 14
Using Model 5103 Uninterruptible Power Supplies When additional power is required by the system, 5000 Series 5103 power supplies can be used in combination with the SCADAPack 32 controllers. Refer to the System Configuration Guide, at the beginning of this manual, for more information.
The 5103 power supplies can be connected anywhere downstream (to the right) of the controller. They will supply power to the modules downstream of them.
The 5103 power supply may also be connected upstream (to the left) of any SCADAPack 32 Controller, but only if no power is applied to the power inputs of the controller board.
Recommended 5103 Power Supply Configuration This configuration uses a 5103 Power Supply module to power a SCADAPack 32. The 24VDC output from the 5103 powers the lower I/O modules. The 5103 power supply provides a 5V output to power the lower I/O module, the controller board and 5000 Series modules through the IMC cables.
Note that no connection is made to the AC/DC PWR IN or DC PWR terminals on the controller board.
AC/DCPWR IN
DC PWR+ –
1 2 3 4 5 6P5
P3
Controller Board
AC/DCPWR IN
DC PWR+ –
1 2 3 4 5 6
AOUT 0 1 COM7 8 9
Lower I/O Module
1 2 3 4 5 9 10P3
5103 Power Supply
120Vrms
24Vrms
Class 2Transformer
AC/DC+ -BATT
+ -24V
Optional 12 VoltGel Cel Battery
Install Jumper J5 when using 5103to power controller board.
SCADAPack 32 Controller User and Reference Manual 15
Sample Power Supply Calculations In the Recommended AC Power Supply Configuration section the controller board may be powering the lower I/O module, as well as other 5000 Series modules. Refer to the System Configuration Guide, at the beginning of this manual, for more information.
The following table shows current requirements of the controllers and I/O modules:
SCADAPack 32 Component
5V Current Requirement
24V Current Requirement
SCADAPack 32 Controller Board
500mA 0mA
SCADAPack 32 Lower I/O Module
20mA +40mA per relay 20mA + 20mA per analog input
SCADAPack 32 Optional Analog Output Module
10mA 15mA + 20mA/output
Sample Power Calculation for SCADAPack 32 Controller In this example there is a SCADAPack 32 controller board with a lower I/O module and analog outputs. Assume all 12 digital output relays will be on, and 24V must be available for both analog outputs and 4 of the analog inputs.
5V Current 24V Current
SCADAPack 32 Controller Board
500mA 0mA
Lower I/O Module 500mA 100mA
Analog Outputs 10mA 55mA
Total 1010mA 155mA
The SCADAPack 32 controller board has 1300mA available from the 5V supply. A minimum of 100mA is available from the 24V supply. Additional current is available from the 24V supply when the 5V is not loaded to its 1300mA maximum.
The total 24V supply current is calculated as follows:
24V current = 100 + ((1300 – Total Current @ 5V) x 0.25)
where: 100 = Minimum current @ 24V
1300 = Maximum current @ 5V
Total Current @ 5V =
Sum of 5V current required for system
0.25 = Derating factor
In this example, when 1010mA is required at 5V, 172.5mA is available on the 24V supply. This is less than the 155mA required by the 24V supply.
SCADAPack 32 Controller User and Reference Manual 16
System Grounding In most applications, it is desirable to ground the system by connecting the system power supply common, to the chassis or panel ground.
On the SCADAPack 32 controller board, the – side of both the 5V and the 24V supplies are connected to the enclosure. Pins 1 and 2 on P3 are connected internally to the enclosure.
On the lower I/O module, the – side of the 24V supply is connected to the enclosure by a printed circuit board trace labeled J3. This trace may be cut. See the Controller Board Field Wiring Connectors section for the location of this trace.
SCADAPack 32 Controller User and Reference Manual 17
Analog Inputs The controller boards have two internal analog inputs, used by application programs to monitor RAM voltage and controller board ambient temperature. The lower I/O module has eight single ended analog inputs.
Controller Board Internal Analog Inputs SCADAPack 32 Controllers have two internal analog inputs. The ambient temperature input measures the temperature at the controller circuit board. It is useful for measuring the operating environment of the controller. The temperature sensor returns a value in the range -40°C to 75°C or -40°F to 167°F. Temperatures outside this range cannot be measured.
The lithium battery input measures the voltage of the battery that maintains the non-volatile RAM in the controller. It is useful in determining if the battery needs replacement. The 3.6V lithium battery will return a value in mV. Readings of 3600 or 3700 are typical. A readings less than 3000 (3.0V) indicates that the lithium battery requires replacement.
Lower I/O Module Analog Inputs The lower I/O module in the SCADAPack 32 and SCADAPack 32 provides eight single ended analog inputs that are configured for either 20mA current or 5V operation. The 20mA version has 250Ω current sense resistors on the inputs. It is otherwise identical to the 5V version.
The lower I/O module uses a 12-bit, successive approximation, analog to digital (A/D) converter. The analog inputs are transient protected, and are optically isolated from the main logic power. All inputs share a common return (COM).
A 24V supply powers the isolated analog input circuits. The controller board power supply normally provides this voltage. Refer to the Power Supply section to see the recommended AC and DC power supply configurations. A wide range of voltages can be tolerated. Refer to the Specifications section for details.
A 16Vrms transformer can also power the analog input circuitry. Refer to the Lower I/O Module Power Supply section of the manual for alternate power supply wiring examples. Both 20mA and 5V analog input modules require this supply.
The 20mA version supports loop powered and self powered transmitters. Loop powered transmitters connect between the +24V and the analog input. The loop current continues to the COM through a 250Ω resistor built into the 20mA input circuit. Self powered transmitters connect to the analog input and to COM. The following diagram shows how to wire these transmitters.
SCADAPack 32 Controller User and Reference Manual 18
1 1 2 3 4 5 6 7
0 71 2 3 4 5 6 COM
+ 24V Supply
8 9
+
– +
–
Self poweredtransmittershown on Input
2 wire looppoweredtransmitter shown
3 4
+24V Supply–
P3 1 2 5 6 7 8 P4
Refer to the PowerSupply section of themanual for alternatepower supply wiringexamples.
AC/DCPWR IN
DC PWR+ –
AOUT 0 1 COM
The 20mA version analog inputs have a signal measurement range of 0-20mA or 4-20mA. The 5V version analog inputs have a measurement range of 0-5 V or 1-5V. The controller board Option Switch 1 selects the measurement range. All eight analog inputs are set to the same range. The Analog Input Range Selection section shows the Option switch settings for selecting the measurement range.
The 5V version is identical to the 20mA version except that the 250Ω input resistors are not installed. 5V signals connect from the analog input to COM. The following diagram shows how to wire 5V inputs.
1 1 2 3 4 5 6 7 8 9
+
–5V output transmittershown on Input 6
3 4
+24V Supply–
P3 1 2 5 6 7 8 P4
Refer to the PowerSupply section of themanual for alternatepower supply wiringexamples.
0 71 2 3 4 5 6 COMAC/DCPWR IN
DC PWR+ –
AOUT 0 1 COM
Analog Inputs Data Format The lower SCADAPack 32 I/O modules have a 12-bit, unipolar, analog to digital (A/D) converter. There are 4096 A/D counts in the input signal range.
The input resolution is:
4.88µA/count on 20mA version
1.22mV/count on the 5V version
The following table shows the A/D output value for several input signals.
SCADAPack 32 Controller User and Reference Manual 19
Current Voltage A/D Output
0mA 0V 0
4.88µA 1.22mV 8
4mA 1.00V 6552
10mA 2.5V 16384
15mA 3.75V 24576
19.995mA 4.999V 32760
SCADAPack 32 Controller User and Reference Manual 20
Analog Outputs The lower I/O module may include two channels of analog output if this option was requested at time of purchase. Refer to the Analog Output Range Selection section for information on configuring the analog outputs range.
Current Outputs The optional lower I/O module analog output module provides two 20mA analog outputs. These outputs are isolated from the system 5V power supply. They are not isolated from each other. The outputs share a common return with each other and the lower I/O module analog inputs.
The analog output resolution is 12 bits. Analog outputs are isolated from logic circuits, for protection against voltage transients and high common mode voltages.
An external 24V supply powers the isolated output circuits. This is usually the same power supply that powers current loop transmitters in the system. A power supply normally provides this power. A wide range of voltages are tolerated. Refer to the Specifications section for details. The following diagram shows recommended field wiring practices.
93 4
+24V Supply–
P3 1 2 5 6 7 8
Refer to the PowerSupply section of themanual for alternatepower supply wiringexamples.
AC/DCPWR IN
DC PWR+ –
AOUT 0 1 COM
LOAD
LOAD
Voltage Outputs To obtain voltage outputs, connect a load resistor as shown in the diagram above. Connect the voltage device across the load resistor. The table below list resistance values and output range settings for common voltage ranges. The resistance value listed is the parallel resistance of the device and the load resistor.
Voltage Range Resistance Output Range
0 to 5V 250Ω 0-20mA
0 to 10V 500Ω 0-20mA
SCADAPack 32 Controller User and Reference Manual 21
Analog Outputs Data Format The optional analog output module installed in the lower I/O module has a 12-bit, unipolar, digital to analog (D/A) converter. There are 4096 D/A counts in the output signal range. The 0-20mA output range resolution is 4.88µA/count. The table below shows the output current for several D/A values.
D/A Value Current
0 0mA
8 4.88µA
6552 4mA
16384 10mA
24576 15mA
32760 19.995mA
SCADAPack 32 Controller User and Reference Manual 22
Digital Inputs The controller board has four digital (discrete) inputs. The lower I/O module has sixteen digital inputs.
Controller Board Digital /Counter Inputs The controller board has three Digital / Counter inputs. These inputs are labeled DIN\Counter 0, 1 and 2 on the P4 terminal connector. These inputs operate as AC or DC digital inputs or as counter inputs.
• For DC inputs the maximum input voltage is 30V and the minimum voltage to turn the input ON is 10V.
• For AC inputs the maximum input voltage is 24Vrms and the minimum voltage to turn the input ON is 10Vrms.
• For counter inputs the maximum frequency is 5KHz with the filters off.
The DIN\Counter inputs can be used as both digital inputs and counters in an application program. Refer to the din520x and cntr520x I/O boards in the I/O Connection Reference section of the ISaGRAF User Manual for information on how to use these inputs in an application program.
Each of the three digital / counter (DIN/Counters) inputs on the SCADAPack 32 controller has a switch selectable filter, which limits the maximum input frequency. Filtering limits the maximum digital input or counter frequency to approximately 30Hz. Refer to the Digital Input Filters section for filter selection information.
• Use a filter for 50 or 60Hz digital inputs and for low speed counting applications that experience problems due to contact bounce.
• Do not use filtering for high speed counting applications.
An example of wiring each type of input is shown in the diagram below.
Connection Example:SW1 Filter 0 is ON to debounce contacts.SW1 Filter 1 is ON to filter AC.SW1 Filter 2 is OPEN for high speed counting.
3 4
0
+ 24V
–
DIN/Counter
21 5 6 7 8P4
COM21
16Vrms
+Pulse Output
–
SW1
2
123401
not used
Options
Filters
Controller Board Interrupt Input The controller board has one Interupt digital input. This input is labeled DINT on the P4 terminal connector. This input operates as a DC digital input or as a counter inputs.
SCADAPack 32 Controller User and Reference Manual 23
• For DC input the maximum input voltage is 28V and the minimum voltage to turn the input ON is 2.5V.
• For counter input the maximum frequency is 500Hz.
The INT input can be used as both a digital input and as a counter in an application program. Refer to the dinint and cntrint I/O boards in the I/O Connection Reference section of the ISaGRAF User Manual for information on how to use these inputs in an application program.
The diagram below shows how to wire this input.
3 4
+
+2.5-28V
–
INT
21 5 6 7 8P4
—
SCADAPack 32 Controller User and Reference Manual 24
Lower I/O Module Digital Inputs The lower I/O module, on the SCADAPack 32 includes sixteen digital inputs. These digital inputs are optically isolated from the logic power. To simplify field wiring, the inputs are organized into two groups of eight inputs. Each group shares a common return. These groups of eight inputs are isolated from each other. Inputs 0 to 7 are in one group. Inputs 8 to 15 are in the other group.
The lower I/O module digital inputs are available in four standard voltage ranges, for both AC and DC applications. A current limiting resistor, on each input, determines the voltage range. Light Emitting Diodes (LED) on the digital inputs show the status of each of the inputs.
1 2 3 4 5 6 7 8 9
9 10 11 12 138 148-15COM15
P5 1 2 3 4 5 6 7 8 9
1 2 3 4 50
24Vrms
60-7
COM7
P6
P5 1 2 3 4 5 6 7 8 9
1 2 3 4 50
+ 24V
60-7
COM7
COM
1 2 3 4 5 6 7 8 9
9 10 11 12 138 148-15COM15
P6
The lower I/O module accommodates AC or DC inputs, depending on the configuration ordered from the factory. The first diagram above shows typical AC input field wiring. The second diagram above shows typical DC input field wiring. Signal polarity must be observed when using DC inputs. Connect the positive signal to the input. Connect the negative signal to the common.
SCADAPack 32 Controller User and Reference Manual 25
Digital Outputs The controller boards have one digital (status) output. The lower I/O module has 12 digital (relay) outputs.
Controller Board Status Output The controller board status output indicates an alarm condition to an external device. The output is ON (capable of conducting current) during normal operation. The output is OFF (high impedance) during the following conditions:
• Power failure.
• Controller board RESET.
• Application program defined conditions.
The status output is an optically isolated transistor. The polarity of the output must be observed. The output current must be limited to 60mA during the ON condition. The output voltage must be limited to 30V during the OFF condition.
A typical application of this output is shown in the following diagram. The output energizes a relay. The normally closed contacts of this relay are used to activate an alarm. The relay in this application has a 24V coil with greater than 400Ω resistance.
Relay Coil Specifications:• 24V• > 400 ohms• < 60mA
3 4
STATUS + –
NCNO COM
+24 V
–
NC ALARM CONTACTS:closed during powerfailures and faultconditions.
21 5 6 7 8P4
Lower I/O Module Digital Outputs The lower I/O module has 12, dry contact, digital (mechanical relay) outputs. Ten outputs are Form A (normally open NO) and two outputs are Form C (both normally open NO and normally closed NC contacts). The table below shows the type of digital outputs for each lower I/O module digital output.
Digital Output Terminals Type Contact Description
0 P7 - 8,9,10 Form C NO and NC with common – isolated
1 P7 - 5,6,7 Form C NO and NC with common – isolated
SCADAPack 32 Controller User and Reference Manual 26
Digital Output Terminals Type Contact Description
2 P7 - 3, 4 Form A NO – isolated
3 P7 - 1, 2 Form A NO – isolated
4 P8 – 9 Form A NO – common return P8-10
5 P8 – 8 Form A NO – common return P8-10
6 P8 – 7 Form A NO – common return P8-10
7 P8 – 6 Form A NO – common return P8-10
8 P8 – 4 Form A NO – common return P8-5
9 P8 – 3 Form A NO – common return P8-5
10 P8 – 2 Form A NO – common return P8-5
11 P8 – 1 Form A NO – common return P8-5
The two Form C outputs and two of the Form A outputs are individually isolated allowing multiple power sources to be used within the same module. Loads can be connected to either output terminal and to either the high or the low side of the power source. The following wiring diagrams show how to wire these outputs.
10 9 8 7 6 5 4 3 2 1
0NO NC COM
LOAD
+24 V
–
HOT120VrmsNeutral
These are typical wiring examples.Only four outputs are shown.
FUSE
LOAD
DC Wiring Examples AC Wiring Examples
LOAD
FUSE
LOAD
Fuses shownare optional.
NOTE: Refer to specificationsfor current and voltagelimitations.
P7
1NO NC COM
2 3 DigitalOutputs
SCADAPack 32 Controller User and Reference Manual 27
10 9 8 7 6 5 4 3 2 1
94 5 6 7 108 4-7COM
LOAD
+24V
–
HOT120VrmsNeutral
These are typical wiring examples.Only four outputs are shown.
FUSE
LOAD
LOAD
DC Wiring Examples AC Wiring Examples
FUSE
LOAD
NOTE: Refer to specificationsfor current and voltagelimitations.
8-11COM
P8
Fuses shownare optional.
11DigitalOutputs
SCADAPack 32 Controller User and Reference Manual 28
Serial Communication The SCADAPack 32 controller is equipped with four serial communication ports. All four serial communication ports support RS-232 serial communication and one port supports both RS-232 and RS-485 serial communication. Three of the communication ports are located on the SCADAPack 32 controller board and one is located on the SCADAPack 32 Lower I/O module.
Serial ports on the SCADAPack 32 controller are designated COM1, COM2, COM3 and COM4. Refer to the drawing in the Controller Board Field Wiring Connectors section for the location of the serial ports.
RS-232 Serial Communications Ports All RS-232 wiring must use shielded cable. The shield should be connected to chassis ground at one point. The DE-9 connector shell is a good ground point. Failure to properly shield the cable may result in the installation not complying with FCC or DOC radio interference regulations.
COM1 RS-232 Serial Port Serial port COM1 may be configured as an RS-232 or RS-485 serial communication port.
• A jumper must installed on J9 to operate COM1 in RS-232 mode.
• A jumper must installed on J10 to operate COM1 in RS-485 mode.
Refer to the drawing in the Controller Board Field Wiring Connectors section for the location of COM1 and jumpers J9 and J10.
For information on using COM1 as a RS-485 serial port refer to the RS-485 Serial Communication Port section.
Connections to COM1 are made through a RJ-45 modular connector. The wiring and pin connections for this connector are described in the RJ-45 Modular Connector for RS-232 section.
The following table shows the serial and protocol communication parameters supported by COM1. These parameters are set from the ISaGRAF Workbench or from an application program running in the SCADAPack 32 controller. Default values are set when a Cold Boot or Service Boot is performed on the SCADAPack 32 controller.
Parameter Supported Values Baud Rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600 and 115200. Default: 9600
Duplex Full or Half Default: Full
Parity Odd, None or Even Default: None
Data Bits 7 or 8 Bits Default: 8 Bits
Stop Bits 1 or 2 Bits Default: 1 Bit
SCADAPack 32 Controller User and Reference Manual 29
Parameter Supported Values Receive Flow Control ModbusRTU or None
Default: ModbusRTU Transmit Flow Control Ignore CTS or None
Default: None Station 1 to 65534
Default: 1 Protocol None, Modbus RTU or Modbus ASCII
Default: Modbus RTU Addressing Mode Standard or Extended
Default: Standard
COM2 RS-232 Serial Port Connections to COM2 are made through a RJ-45 modular connector. The wiring and pin connections for this connector are described in the RJ-45 Modular Connector for RS-232 section.
Refer to the Controller Board Field Wiring Connectors section for the location of COM2 on the SCADAPack controller board.
The following table shows the serial and protocol communication parameters supported by COM2. These parameters are set from the ISaGRAF Workbench or from an application program running in the SCADAPack 32 controller. Default values are set when a Cold Boot or Service Boot is performed on the SCADAPack 32 controller.
Parameter Supported Values Baud Rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600 and 115200. Default: 9600
Duplex Full or Half Default: Full
Parity Odd, None or Even Default: None
Data Bits 7 or 8 Bits Default: 8 Bits
Stop Bits 1 or 2 Bits Default: 1 Bit
Receive Flow Control ModbusRTU or None Default: ModbusRTU
Transmit Flow Control Ignore CTS or None Default: None
Station 1 to 65534 Default: 1
Protocol None, Modbus RTU or Modbus ASCII Default: Modbus RTU
Addressing Mode Standard or Extended Default: Standard
COM3 RS-232 Serial Port Connections to COM3 are made through a DE-9P connector. The wiring and pin connections for this connector are described in the DE-9P Connector for RS-232 section.
SCADAPack 32 Controller User and Reference Manual 30
Refer to the Controller Board Field Wiring Connectors section for the location of COM3 on the SCADAPack controller board.
The following table shows the serial and protocol communication parameters supported by COM1. These parameters are set from the ISaGRAF Workbench or from an application program running in the SCADAPack 32 controller. Default values are set when a Cold Boot or Service Boot is performed on the SCADAPack 32 controller.
Parameter Supported Values Baud Rate 1200, 2400, 4800, 9600, 19200, 38400, 57600 and
115200. Default: 9600
Duplex Full or Half Default: Half
Parity Odd, None or Even Default: None
Data Bits 7 or 8 Bits Default: 8 Bits
Stop Bits 1 or 2 Bits Default: 1 Bit
Receive Flow Control ModbusRTU or None Default: ModbusRTU
Transmit Flow Control Ignore CTS or None Default: None
Station 1 to 65534 Default: 1
Protocol None, Modbus RTU or Modbus ASCII Default: Modbus RTU
Addressing Mode Standard or Extended Default: Standard
COM4 RS-232 Serial Port Connections to COM4 are made through a RJ-45 modular connector. The wiring and pin connections for this connector are described in the RJ-45 Modular Connector for RS-232 section.
Refer to the Controller Board Field Wiring Connectors section for the location of COM4 on the SCADAPack controller board.
The following table shows the serial and protocol communication parameters supported by COM4. These parameters are set from the ISaGRAF Workbench or from an application program running in the SCADAPack 32 controller. Default values are set when a Cold Boot or Service Boot is performed on the SCADAPack 32 controller.
Parameter Supported Values Baud Rate 300, 600, 1200, 2400, 4800, 9600, 19200, 38400,
57600 and 115200. Default: 9600
Duplex Full or Half Default: Full
Parity Odd, None or Even Default: None
Data Bits 7 or 8 Bits Default: 8 Bits
SCADAPack 32 Controller User and Reference Manual 31
Parameter Supported Values Stop Bits 1 or 2 Bits
Default: 1 Bit Receive Flow Control ModbusRTU or None
Default: ModbusRTU Transmit Flow Control Ignore CTS or None
Default: None Station 1 to 65534
Default: 1 Protocol None, Modbus RTU or Modbus ASCII
Default: Modbus RTU Addressing Mode Standard or Extended
Default: Standard
RJ-45 Modular Connector for RS-232 Serial communication ports COM1, COM2 and COM4 are located on the SCADAPack 32 controller board. These are RS-232 serial ports using a 8-pin female RJ-45 connectors configured as Data Terminal Equipment (DTE). The recommended specification for RS-232 cable length is a maximum of 50 feet or 15.2 meters. Shielded cable must be used and the shield should be connected to chassis ground at one end.
The following diagram shows the pin connections for the RS-232 (RJ-45) port connector for COM1, COM2 and COM4.
RJ-45 Modular Jack
1. + 5V2. DCD3. DTR4. GND5. RxD6. TxD7. CTS8. RTS
21 876543
Notes: • +5V is only available on Pin 1 when a jumper is installed on J4. Refer to the
Controller Board Field Wiring Connectors section for the location of J4.
• Serial port COM1 may be configured as RS-232 or RS-485. A jumper must installed on J10 to operate COM1 in RS-232 mode. Refer to the Controller Board Field Wiring Connectors section for the location of J10.
The following table provides a description of the function of each pin of the RJ-45 connector. In this table a MARK level is a voltage of +3V or greater and a SPACE level is a voltage of –3V or less.
Pin Function Description
1 5V (Output)
This pin can be connected to the 5V power supply by installing a jumper at J4 on the SCADAPack controller board.
2 DCD (Input)
The DCD led is on for a MARK level.
3 DTR (Output)
This pin is normally at a MARK level.
SCADAPack 32 Controller User and Reference Manual 32
Pin Function Description
(Output) This pin is at a SPACE level when DTR is de-asserted.
4 GND This pin is connected to the system ground.
5 RxD (Input)
The level is SPACE on standby and MARK for received data.
The LED is lit for a MARK level.
6 TxD (Output)
The level is SPACE on standby and MARK for transmitted data.
The LED is lit for a MARK level.
7 CTS (Input)
This level must be a MARK for the communication port to transmit data. When the attached device does not provide this signal, the controller keeps the line at a MARK.
When the attached device does provide this signal, it must set CTS to MARK to allow the controller to transmit data.
8 RTS (Output)
This pin is a MARK if full-duplex operation is selected for the port.
This pin is set to a MARK just before and during transmission of data if half-duplex operation is selected.
This pin is set to a SPACE when no data is being transmitted.
DE-9P Connector for RS-232 Serial communication port COM3 is located on the SCADAPack 32 Lower I/O module. COM3 is an RS-232 port with a 9-pin male D-sub-miniature (DE-9P) connector configured as Data Terminal Equipment (DTE). The recommended specification for RS-232 cable length is a maximum of 50 feet or 15.2 meters. Shielded cable must be used and the shield should be connected to chassis ground at one end.
The following diagram shows the pin connections for the RS-232 (DE-9P) port connector for COM3.
1. DCD2. RxD3. TxD4. DTR5. GND6. nc7. RTS8. CTS9. + 5V
7 86 9
1 2 3 4 5
The following table provides a description of the function of each pin of the DE-9P connector. In this table a MARK level is a voltage of +3V or greater and a SPACE level is a voltage of –3V or less.
Pin Function Type Description
1 DCD Input The DCD led is on for a MARK level.
2 RxD Input The level is SPACE on standby and MARK for received data.
The LED is lit for a MARK level.
SCADAPack 32 Controller User and Reference Manual 33
Pin Function Type Description
3 TxD Output The level is SPACE on standby and MARK for transmitted data.
The LED is lit for a MARK level.
4 DTR Output This pin is normally at a MARK level.
This pin is at a SPACE level when DTR is de-asserted.
5 GND This pin is connected to the system ground.
6 This pin is not connected.
7
RTS Output This pin is a MARK if full-duplex operation is selected for the port.
This pin is set to a MARK just before and during transmission of data if half-duplex operation is selected.
This pin is set to a SPACE when no data is being transmitted.
8
CTS Input This level must be a MARK for the communication port to transmit data. When the attached device does not provide this signal, the controller keeps the line at a MARK.
When the attached device does provide this signal, it must set CTS to MARK to allow the controller to transmit data.
9 5V Output This pin is connected to the 5V power supply. Exercise caution when using it. COM3 on the Lower I/O module has 5V present at all times. COM1, COM2 and COM4 have 5V present only when a jumper is installed at J4 on the SCADAPack 32 controller board.
SCADAPack 32 Controller User and Reference Manual 34
RS-485 Serial Communication Port Serial port COM1 on the SCADAPack 32 controller may be configured as an RS-485 serial communication port. A jumper must installed on J9 to operate COM1 in RS-232 mode. Refer to the Controller Board Field Wiring Connectors section for the location of J9.
When configured as a RS-485 port COM1 transmits and receives differential voltages to other RS-485 devices on a network. The RS-485 specification allows a maximum of 32 devices connected on a single RS-485 network. The recommended specification for RS-485 is the cable length should not exceed a maximum of 4000 feet or 1200 meters. Termination resistors are required when using long cable lengths and high baud rates. Refer to the RS-485 Termination Resistors section for information on termination resistors.
The signal grounds of the RS-485 devices in the network are not connected together but instead are referenced to their respective incoming electrical grounds. The grounds of the RS-485 devices on the network must be within several volts of each other.
The RS-485 port operates in two or four wire mode.
RJ-45 Modular Connector for RS-485 The following diagram shows the pin connections for the RS-485 (RJ-45) port connector for COM1.
RJ-45 Modular JackBlack
1. + 5V2. –Rx3. –Tx4. GND5. + Rx6. + Tx7. Do not
connect8. Do not
connect
21 876543
+5V is only available on Pin 1 when a jumper is installed on J4. Refer to the Controller Board Field Wiring Connectors section for the location of J4.
Serial port COM1 may be configured as RS-232 or RS-485. A jumper must installed on J9 to operate COM1 in RS-485 mode. Refer to the Controller Board Field Wiring Connectors section for the location of J9.
The differential receive and transmit signals are labeled +/–Rx and +/–Tx respectively. Some RS-485 devices refer to the – side of the signal as A and the + side of the signal as B.
The following table provides a description of the function of each pin of the RJ-45 connector. In this table a MARK level is a voltage of +3V or greater and a SPACE level is a voltage of –3V or less.
SCADAPack 32 Controller User and Reference Manual 35
Pin Function Description
1 5V (Output)
This pin can be connected to the 5V power supply by installing a jumper at J4 on the SCADAPack controller board.
2 -Rx (Input)
The DCD led is on for a MARK level.
3 -Tx (Output)
This pin is normally at a MARK level.
This pin is at a SPACE level when DTR is de-asserted.
4 GND This pin is connected to the system ground.
5 +Rx (Input)
The level is SPACE on standby and MARK for received data.
The LED is lit for a MARK level.
6 +Tx (Output)
The level is SPACE on standby and MARK for transmitted data.
The LED is lit for a MARK level.
7 N/C Do not connect this pin for RS-485 operation.
8 N/C Do not connect this pin for RS-485 operation.
RS-485 Bias Resistors The RS-485 receiver inputs on the SCADAPack 32 controller are biased to ensure that that received data is driven to a valid state (space) when there are no active drivers on the network. The value of these bias resistors is 4700 ohms from Ground to the –Rx input and 4700 ohms from +5V to the +Rx input.
RS-485 Termination Resistors Termination resistors are required in long networks operating at the highest baud rates. Shorter networks in high noise environments may also benefit from terminations. Networks as long 1000 ft. operating at 9600 baud will function without termination resistors. Terminations should be considered if the baud rate is higher and the network is longer.
When termination resistors are required, they are installed on the first and last station on the RS-485 wire pair. All other stations should not have termination resistors.
RS-485 networks are generally terminated with 120 ohm resistors on each end. The required 120 ohm resistor is built into the SCADAPack 32 controller. When these termination resistors are used, the biasing generally has to be increased in order to generate at least 0.2V across the +/–Rx input.
To connect the termination resistors:
• Install a jumper across J8 to terminate the Rx pair.
• Install a jumper across J7 to terminate the Tx pair.
To disconnect the termination resistors:
• Remove the jumper across J8 to terminate the Rx pair.
• Remove the jumper across J7 to terminate the Tx pair.
SCADAPack 32 Controller User and Reference Manual 36
RS-232 Wiring Examples
DTE to DTE without Handshaking There are several methods for wiring the RS-232 COM port to DTE (Data Terminal Equipment) and DCE (Data Communications Equipment) devices. The simplest connection requires only 3 wires: RxD, TxD and signal ground. The following diagram shows a common RS-232 COM port to DTE device.
RS-232 COM port (DTE) DTE
DCD
RxD
TxD
DTR
GND
RTS
CTS
+ 5V
DCD
RxD
TxD
DTR
GND
RTS
CTS
See devicespecifications
for pin numbers
DTE to DTE with Handshaking Some DTE devices may require hardware handshaking lines. The most common are the CTS and RTS lines. Less common are the DTR and DCD lines. These lines are not required by the controller. Refer to the specifications of the external device for exact requirements. The following diagram shows a common connection of an RS-232 COM port with a DTE device requiring handshaking lines.
RS-232 COM port (DTE) DTE
DCD
RxD
TxD
DTR
GND
RTS
CTS
+ 5V
DCD
RxD
TxD
DTR
GND
RTS
CTS
See devicespecifications
for pin numbers
SCADAPack 32 Controller User and Reference Manual 37
DTE to DCE with Handshaking DCE devices require different wiring. The handshaking lines must be connected in most cases. Note that many DCE devices are half duplex. Select half-duplex operation with these devices. The diagram below shows common connection of a SCADAPack with a DCE device requiring handshaking lines. RS-232 COM port (DTE) DCE
DCD
RxD
TxD
DTR
GND
RTS
CTS
+ 5V
DCD
RxD
TxD
DTR
GND
RTS
CTS
See devicespecifications
for pin numbers
SCADAPack 32 Controller User and Reference Manual 38
RS-485 Wiring Examples
Four wire mode Four wire operation uses one pair of wires for transmitting data and a second pair for receiving data. The transmitting pair is connected to +Tx and –Tx. The receiving pair is connected +Rx and –Rx. The following diagram shows the wiring details for a four wire connection.
+ TX
–TX
–RX
+ RX
+ TX
–TX
–RX
+ RX
+ TX
–TX
–RX
+ RX
+ TX
–TX
–RX
+ RX
MASTER
SLAVE
SLAVE
SLAVE
Last station in networkmay require terminations.
First station in networkmay require termination.
RS-485 network4000 feet (1200 m)maximum length
Two wire mode Two wire operation uses one pair of wires for transmitting and receiving data. +Tx must be connected to +Rx and –Tx must be connected to the –Rx. This pair of wires becomes
SCADAPack 32 Controller User and Reference Manual 39
the transmitting and receiving pair. The following diagram shows the wiring details for a two wire connection.
+ TX
–TX
–RX
+ RX
+ TX/RX
–TX/RX
+ TX
–TX
–RX
+ RX
+ TX
–TX
–RX
+ RX
5232
5232
5232
Other RS-485 Device
Last station in networkmay require terminations.
First station in networkmay require terminations.
RS-485 network4000 feet (1200 m)maximum length
SCADAPack 32 Controller User and Reference Manual 40
RS-232 Cables
RJ-45 to DE-9S DTE This cable is used to connect from an RJ-45 based RS-232 port on the SCADAPack 32 controller to DE-9P connector on a DTE such as a PC. A 10 ft. long cable is available from Control Microsystems as part number 297217.
RJ-45 8 Pins
SCADAPack 32 DTE Function
DE9S DTE Function
DE9S
Shield connects to shell
6 TxD RxD 2
5 RxD TxD 3
4 GND GND 5
1, 2, 3, 7 and 8 are not connected at this end.
GND GND No wires connected at this end.
RJ-45 to DE-9P DCE This cable is used to connect from an RJ-45 based RS-232 port on the SCADAPack 32 controller to DE-9S connector on a DCE such as a modem. A 15 inch long cable is available from Control Microsystems as part number 297218.
RJ45 SCADAPack 32 DTE Function
DE-9P DCE Function
DE-9P
Shield connects to shell
3 DTR DTR 4
6 TxD TxD 3
5 RxD RxD 2
2 DCD DCD 1
4 GND GND 5
7 CTS CTS 8
8 RTS RTS 7
1 +5V +5V 9
RS-485 Cable This cable is used to connect from an RJ-45 based RS-485 port on the SCADAPack 32 controller to other RS-485 devices. The cable has a RJ-45 connector on one end and stripped wires at the other end. A 10-foot long cable is available from Control Microsystems as part number 297234.
SCADAPack 32 Controller User and Reference Manual 41
RJ45 Function Wire color
Connect to Chassis Shield
3 –Tx Orange
6 +Tx Blue
5 +Rx Grey
2 –Rx Brown
4 GND Black
7 Do not connect. Yellow
8 Do not connect. Green
1 +5V Red
SCADAPack 32 Controller User and Reference Manual 42
Ethernet Communication The SCADAPack 32 controller has one 10BaseT Ethernet port. 10BaseT is a single communications channel running at 10MHz over unshielded, twisted - pair cabling. 10BaseT uses differential signaling.
LAN Port Settings Connections to the LAN port are made through a RJ-45 modular connector. The wiring and pin connections for this connector are described in the RJ-45 Modular Connector for Ethernet section.
Refer to the Controller Board Field Wiring Connectors section for the location of the LAN port on the SCADAPack controller board.
TCP/IP Settings The following table shows the TCP/IP parameters supported by the LAN port. These parameters are set from the ISaGRAF Workbench or from an application program running in the SCADAPack 32 controller. Default values are set when a Cold Boot is performed on the SCADAPack 32 controller.
Parameter Supported Values
IP Address In the format 255.255.255.255
Default: 0.0.0.0
Subnet Mask In the format 255.255.255.255
Default: 0.0.0.0
Gateway In the format 255.255.255.255
Default: 0.0.0.0
The IP Address is the address of the controller. The IP address is statically assigned. Contact your network administrator to obtain an IP address for the controller.
The Subnet Mask is determines the subnet on which the controller is located. The subnet mask is statically assigned. Contact your network administrator to obtain the subnet mask for the controller.
The Gateway determines how your controller communicates with devices outside its subnet. Enter the IP address of the gateway. The gateway is statically assigned. Contact your network administrator to obtain the gateway IP address.
Modbus/TCP Settings The following table shows the Modbus/TCP parameters supported by the LAN port. These parameters are set from the ISaGRAF Workbench or from an application program running in the SCADAPack 32 controller. Default values are set when a Cold Boot or Service Boot is performed on the SCADAPack 32 controller.
SCADAPack 32 Controller User and Reference Manual 43
Parameter Supported Values Master Idle Timeout Any value in seconds.
Default: 10 seconds Server Receive Timeout Any value in seconds.
Default: 10 seconds Maximum Server Connections
Valid values are 1 to 20. Default: 20
TCP Port Valid values are 1 to 65535 Default: 502
Modbus Addressing Type Valid values are Standard or Extended Default: Standard
Modbus Station Address Valid values are 1 to 65534. Default: 1
Store and Forward Messaging
Valid values are Enabled and disabled. Default: Disabled
The Master Idle Timeout parameter sets when connections to a slave controller are closed. Setting this value to zero disables the timeout; the connection will be closed only when your program closes it. Any other value sets the timeout in seconds. The connection will be closed if no messages are sent in that time. This allows the slave device to free unused connections.
The Server Receive Timeout parameter sets when connections from a remote device are closed. Setting this value to zero disables the timeout; the connection will be closed only when the remote device closes it. Any other value sets the timeout in seconds. The connection will be closed if no messages are received in that time. This allows the controller to free unused connections.
The Maximum Server Connections parameter sets the number of incoming (server) connections that the controller will allow. Incoming (server) connections are used when a remote device creates a connection to this controller. Outgoing connections are used when this controller creates a connection to a remote device (e.g. using a masterip function block). Setting this value to the maximum allows the server to use all connections for incoming connections. Setting the value below the maximum limits the number of incoming connections from remote devices. This reserves the remaining connections for use by the controller for outgoing connections.
The TCP Port parameter sets the port used by the Modbus/TCP protocol. In almost all cases this should be set to 502. This is the well-known port number for Modbus/TCP. Modbus/TCP devices use 502 by default, and on many devices the value cannot be changed. It is suggested that you change this value only if this port is used by another service on your network. Consult your network administrator to obtain a port if you are not using the default.
The Addressing parameter selects standard or extended Modbus addressing. Standard addressing allows 255 stations and is compatible with standard Modbus devices. Extended addressing allows 65534 stations, with stations 1 to 254 compatible with standard Modbus devices.
The Station parameter sets the station number of the controller. The valid range is 1 to 255 if standard addressing is used, and 1 to 65534 if extended addressing is used.
The Store and Forward Messaging parameter controls forwarding of messages on the Ethernet port. If this option is enabled, messages will be forwarded according to the settings in the store and forward routing table.
SCADAPack 32 Controller User and Reference Manual 44
RJ-45 Modular Connector for Ethernet The SCADAPack 32 can be connected directly to a wall jack or hub using standard RJ-45 Category 5 patch cables. The following diagram shows the pin connections for the RJ-45 modular connector.
RJ-45 Modular JackGrey
1. + Tx2. –Tx3. + Rx4. 5. 6. –Rx7. 8.
21 876543
10BaseT has a maximum run of 100m or 350 feet, but the actual limit is based on signal loss and the noise in the environment. This may limit the practical distance to less than 100m or 350 feet. The Ethernet cables should not be run in parallel with power or any cables that generate noise.
SCADAPack 32 Controller User and Reference Manual 45
Operation
Operating Modes SCADAPack 32 Controllers may start up in RUN, SERVICE or COLD BOOT mode. Start up in the RUN mode automatically executes the application programs in the controller memory. Start up in the SERVICE mode stops the programs to allow reprogramming and controller initialization. Start up in the COLD BOOT mode initializes the controller and erases all programs.
Run Mode The RUN mode is the normal operating mode of the SCADAPack 32 Controller. No action is required to select RUN mode. When power is applied to the controller board:
• The user defined serial communication parameters, for all COM ports are used.
• The user defined TCP/IP and Modbus/TCP parameters are used for the Ethernet port.
• If a ISaGRAF application program is loaded it is executed.
• If a ISaGRAF C++ application program is loaded and the program checksum is correct, it is executed.
• The controller lock settings and password are used.
Service Mode SERVICE mode is used during application programming and maintenance work. When the SCADAPack 32 controller starts in SERVICE mode:
• The default serial communication parameters are used. See the RS-232 Serial Communications Ports section of this manual for a description of the default parameters.
• The user defined TCP/IP parameters are used for the Ethernet port.
• The default Modbus/TCP parameters are used for the Ethernet port. See the Modbus/TCP Settings section of this manual for the default parameters.
• If a ISaGRAF application program is loaded it is stopped.
• If an ISaGRAF C++ application program is loaded it is stopped.
• All programs are retained in non-volatile memory.
• The controller lock settings and password are used.
SERVICE mode is selected by performing a SERVICE BOOT using the following procedure:
• Remove power from the SCADAPack 32 controller.
• Hold down the LED POWER button.
• Apply power to the controller.
SCADAPack 32 Controller User and Reference Manual 46
• Continue holding the LED POWER button until the STAT LED turns on.
• Release the LED POWER button.
Note: If the LED POWER button is released before the STAT LED turns on, the SCADAPack 32 controller will start in RUN mode.
Cold Boot Mode COLD BOOT mode is used after installing new controller firmware. When the SCADAPack 32 controller starts in COLD BOOT mode:
• The default serial communication parameters are used. See the RS-232 Serial Communications Ports section of this manual for a description of the default parameters.
• The default TCP/IP parameters are used for the Ethernet port. See the TCP/IP Settings section of this manual for the default parameters.
• The default Modbus/TCP parameters are used for the Ethernet port. See the Modbus/TCP Settings section of this manual for the default parameters.
• The ISaGRAF application program is erased.
• The ISaGRAF C++ application program is erased.
• The controller is unlocked.
COLD BOOT mode is selected by performing a COLD BOOT using the following procedure:
• Remove power from the SCADAPack 32 controller.
• Hold down the LED POWER button.
• Apply power to the SCADAPack 32 controller.
• Continue holding the LED POWER button for 25 seconds until the STAT LED begins to flash on and off continuously.
• Release the LED POWER button.
Note: If the LED POWER button is released before the STAT LED begins to flash, the SCADAPack 32 controller will start in SERVICE mode.
LED Indicators
Controller Board LEDs There are twenty three LEDs on the SCADAPack 32 controller board. These LEDs are used to indicate the operational status of the controller. All LEDs except the 5V LED can be disabled to conserve power. Refer to the LED Power Control section for details on LED power control.
SCADAPack 32 Controller User and Reference Manual 47
The following table describes the SCADAPack 32 controller board LEDs.
LED Function
5V On when 5V power is present in the SCADAPack 32 controller. The controller must have 5V power to operate. 5V power is supplied by the SCADAPack 32 internal power supply or from an external model 5103 power supply.
RUN On when an ISaGRAF application program is running in the SCADAPack 32 controller. This LED may be controlled by a C++ Tools application, in which case the application will control the LED status.
LEDS On when LED power is enabled.
STAT This LED is normally off. The LED will blink when an error exists. Refer to the Status LED and Output section for more information on this LED and the STATUS output.
FORCE On when and SCADAPack 32 I/O points are forced, or locked, in an ISaGRAF application.
INT/Counters 0 INT/Counters 1 INT/Counters 2
On when a signal is applied to the corresponding input.
INT On when a signal is applied to the INT input
LAN On when receive or transmit data on the Ethernet port.
LINK On when Ethernet port is connected to a network.
COM1 RX COM2 RX COM4 RX.
On when receiving data on the corresponding serial port.
COM1 TX COM2 TX COM4 TX.
On when transmitting data on the corresponding serial port.
COM1 CTS COM2 CTS COM4 CTS.
On when the CTS input is asserted on the corresponding serial port.
COM1 DCD COM2 DCD COM4 DCD.
On when the DCD input is asserted on the corresponding serial port.
Lower I/O Module LEDs The SCADAPack 32 has a total of thirty LEDs on the Lower I/O module. All LEDs, except the digital input LEDs, can be disabled to conserve power. Refer to the LED Power Control section for details on LED power control.
The table below describes the LEDs on the SCADAPack 32 Lower I/O module.
LED Function
COM3 RX On when receiving data COM3.
COM3 TX On when transmitting data on COM3.
SCADAPack 32 Controller User and Reference Manual 48
LED Function
DIN 0 to DIN 15 On when the corresponding digital input is on.
DOUT 0 to DOUT 11 On when the corresponding digital output is on.
LED Power Control Power to the LEDs on the SCADAPack 32 controller board, Lower I/O module and 5000 Series I/O modules connected to the SCADAPack 32 can be disabled to conserve power. This feature is particularly useful when the SCADAPack 32 is used in solar powered or unattended installations.
The LEDS LED on the controller board indicates the LED power state. This LED is on when power to the LEDs is enabled and off when power to the LEDs is disabled. See the Controller Board Field Wiring Connectors section for the location of the LEDS LED.
The LED POWER push-button toggles the LED power state. Press the LED POWER push-button to toggle LED power state from disable to enable, or from enable to disable.
The default setting of the LED power state is LED power enabled. The LED power returns to the default state 5 minutes after the LED POWER push-button is last pressed. The application program may change the default state and time to return to the default state using the setled function in an application program.
The LED POWER push-button does not affect some LEDs, such as digital inputs and counter inputs. These LEDs are on when a signal is applied to the corresponding input. these LEDs cannot be disabled to conserve power.
Status LED and Output The status LED and output indicate alarm conditions. The STAT LED blinks and the STATUS output opens when an alarm occurs. The STAT LED turns off and the STATUS output closes when all alarms clear.
Note: The STATUS output remains open continuously when an alarm condition is present. The STAT LED is on continuously during reset.
The STAT LED blinks a binary sequence indicating alarm codes. The sequences consist of long and short flashes, followed by an off delay of 1 second. The sequence then repeats. The sequence may be read as the Controller Status Code. A short flash indicates a binary zero. A long flash indicates a binary one. The least significant bit is output first. As few bits as possible are displayed, all leading zeros are ignored. The application program defines the values of the alarm codes.
The table below shows the meaning of the sequences.
Sequence Controller Status Code
Off 0 = Normal
1 Long 1 = I/O Module Error Indication
I/O Module Error Indication When the Status LED flashes the controller status code 1 (i.e. a long flash, once every second), there is a communication failure with one or more I/O module. To correct the problem, do one of the following:
SCADAPack 32 Controller User and Reference Manual 49
• Ensure that every module contained in the ISaGRAF I/O Connection Table is connected to the SCADAPack 32 controller. Check that the module address selected for each module agrees with the selection made in the I/O Connection Table.
• If a module is still suspect of having failed, confirm the failure by removing the module from the I/O Connection Table. Download the changes to the SCADAPack 32 controller. The Status LED should stop flashing.
• If a module is currently not connected to the SCADAPack 32 controller, delete it from the I/O Connection Table. Download the changes to the SCADAPack 32 controller. The Status LED should stop flashing.
If unused modules must be intentionally left in the I/O Connection Table, the I/O error indication may be disabled. To disable the I/O error indication:
• Select Controller from the Tools menu in the ISaGRAF Project Management window.
• Select I/O Error Indication from the Controller commands.
• Select the Disable I/O Error Indication radio button and click OK.
SCADAPack 32 Controller User and Reference Manual 50
Configuration Switches The SCADAPackl32 controller board SW1 is an eight position DIP switch. The first seven switches on SW1 are used to configure digital / counter input filtering and analog input and output ranges. SW1 is shown in the following diagram. Refer to Controller Board Field Wiring Connectors section for the location of SW1 on the SCADAPack 32 controller board.
SW1
2
123401
not used
Options
Filters
• SW1-1 Option 1 Lower I/O module analog input range selection.• SW1-2 Option 2 Optional 5303 analog output module range selection.• SW1-3 Option 3 Available for application programs.• SW1-4 Option 4 Available for application programs.• SW1-5 Filter 0 DIN/Counters input 0 filtering.• SW1-6 Filter 1 DIN/Counters input 1 filtering.• SW1-7 Filter 2 DIN/Counters input 2 filtering.• SW1-8 Not Used
Configuration switches can be changed with the power applied. Configuration changes take effect immediately.
To select configuration switch functions:
• Remove the module cover and locate the configuration switches. See Controller Board Field Wiring Connectors for SW1 location.
• Slide the switch actuator to the right side of the switch to enable the switch function.
• Slide the switch actuator to the left side of the switch to disable the switch function.
Analog Input Range Selection The SCADAPack 32 analog inputs on the Lower I/O module have a signal measurement range of 0-20mA or 4-20mA. SCADAPack 32 Controllers with voltage-measuring analog inputs have a measurement range of 0-5V or 1-5V.
The controller board Option Switch 1 selects the measurement range. All analog inputs are set to the same range. The diagram below shows the switch settings for selecting the analog input range.
Slide the actuatorto this side for
4-20mA or 1-5V
Slide the actuatorto this side for
0-20mA or 0-5V
How to Set the Range Switch:• Determine the desired range.• Slide the actuator to the side of
the switch shown in gray.
0-20mA or 0-5VInputsSW1
2
123401
not used
Options
Filters
SW1
2
123401
not used
Options
Filters
4-20mA or 1-5VInputs
Analog Output Range Selection The SCADAPack 32 analog outputs on the optional AOUT module outputs a 0-20mA signal or a 4-20mA signal. The controller board Option Switch 2 selects the signal range.
SCADAPack 32 Controller User and Reference Manual 51
All analog outputs are set to the same range. The diagram below shows the switch settings for selecting the analog output range.
Slide the actuatorthis side for
4-20mA
Slide the actuatorto this side for
0-20mA
How to Set the Range Switch:• Determine the desired range.• Slide the actuator to the side of
the switch shown in gray.
4-20mA Outputs0-20mA OutputsSW1
2
123401
not used
Options
Filters
SW1
2
123401
not used
Options
Filters
Digital Input Filters Each of the three digital / counter (DIN/Counters) inputs on the SCADAPack 32 controller board can be filtered. Filtering limits the maximum digital input or counter frequency to approximately 30Hz.
• Use a filter for 50 or 60Hz digital inputs and for low speed counting applications that experience problems due to contact bounce.
• Do not use filtering for high speed counting applications.
SCADAPack 32 controller board SW1, switches Filter 0, Filter 1 and Filter 2 switches control the input filter functions.
• Filter 0 for DIN/Counters input 0.
• Filter 1 for DIN/Counters input 1.
• Filter 2 for DIN/Counters input 2.
SW1
2
123401
not used
Options
Filters
• To enable a filter, slide the Filter 0, Filter 1or Filter 2 actuator to the right side of theswitch (closed).
• To disable a filter, slide the Filter 0, Filter 1or Filter 2 actuator to the left side of theswitch (closed).
Line Frequency Selection The lower I/O module may select 50 or 60 Hz line frequency for digital and analog input processing. The controller board Option Switch 3 selects the line frequency option. The diagram below shows the switch settings for selecting the line frequency.
SCADAPack 32 Controller User and Reference Manual 52
This side for50Hz.
This side for60 Hz.
How to Set the Frequency Switch:• Determine the desired range.• Slide the actuator to the side of
the switch shown in gray.
60 Hz OperationSW1
2
123401
not used
Options
Filters
SW1
2
123401
not used
Options
Filters
50 Hz Operation
SCADAPack 32 Controller User and Reference Manual 53
Maintenance The SCADAPack 32 controllers require little maintenance. The 5V power LED indicates the status of the 5V supply. If the LED is off, and the SCADAPack 32 controller is powered using the integrated power supply, on board fuse F1 or F2 may require replacing. If the LED is off, and the SCADAPack 32 controller is powered using a 5103 power supply fuse F1 (5V) or F2 (24V) on the 5103 may require replacing. If the program is lost during power outages, the lithium battery may require replacement.
The analog input and output circuitry is calibrated at the factory and does not require periodic calibration. Calibration may be necessary if the module has been repaired as a result of damage.
If the SCADAPack 32 Controller is not functioning correctly, contact Control Microsystems Technical Support for information on returning the SCADAPack 32 Controller for repair.
WARNING: Do not connect or disconnect any field wiring, including the wiring to the RS-232 ports, unless the power is off or the area is know to be non-hazardous.
Fuses Two 1.0 Amp slow-blow fuses protects the power supply. The fuse is mounted under the cover. Fuse F1 protects the SCADAPack 32 controller when powered from the AC/DC Power Input. Fuse F2 protects the controller when powered from the DC Power Input. Refer to Controller Board Field Wiring Connectors section for their location.
CAUTION: Remove power before servicing unit.
Always replace a defective fuse with a fuse of the same rating. Under no circumstances should a fuse be bypassed or replaced with a fuse of a higher rating.
The fuse is a Littelfuse Nano-SMF. Littelfuse part number LF R452 001. Control Microsystems part number 200072.
In all cases investigate and correct the cause of the fuse failure before replacement. Common causes of fuse failure are short circuits and excessive input voltages.
Lithium Battery A small lithium battery powers the CMOS memory and real-time clock when input power is removed. The voltage of a functioning battery should be greater than 3.0V. An application program can monitor this voltage. Refer to the programming manual for details.
The battery should not require replacement under normal conditions. The shelf life of the battery is 10 years. The battery is rated to maintain the real-time clock and RAM data for two years with the power off. Accidental shorting or extreme temperatures may damage the battery.
The battery is plugged into the circuit board and secured with a tie-wrap. If necessary it can be replaced with an identical battery available from Control Microsystems. It is not necessary to replace the tie-wrap.
SCADAPack 32 Controller User and Reference Manual 54
Troubleshooting
Analog Inputs Problem Action
20mA inputs always read 0. Check transmitter power.
Reading is at or near 0 for all input signals.
Check if the input transient suppressers are damaged.
20mA readings are not accurate.
Check for a damaged 250Ω current sense resistor.
Reading is constant. Check that the analog input is not forced.
Reading seems out of calibration for small inputs but improves as input increases.
Check the input range switch setting.
Analog Outputs Problem Action
Outputs are always 0mA Check the 24V power.
Check that the analog option is installed.
The full-scale output is less than 20mA.
Check the 24V power.
Check that the load resistance is within specification.
Output is constant and should be changing.
Check that the analog outputs are not forced.
The output is 4mA when a value of 0 is output. 0mA was expected.
The 4-20mA output range is selected. Select the 0-20mA range.
The output is 0mA when a value of 0 is output. 4mA was expected.
The 0-20mA output range is selected. Select the 4-20mA range.
The output seems to be uncalibrated at small output values. The error improves as larger values are output.
Check the setting of the output range switch. The wrong output range is probably selected.
SCADAPack 32 Controller User and Reference Manual 55
Digital Inputs Problem Action
Input LED does not come on when input signal is applied.
Check the input signal at the termination block. It should be at least 50% of the digital input range.
If this is a DC input, check the polarity of the signal.
Input LED comes on but appears dim.
Confirm correct digital input type, AC o DC. This problem is typically the result of applying a DC voltage to an AC type input.
Input is on when no signal is applied. The LED is off.
Check that the digital inputs are not forced on.
Input is off when a signal is applied. The LED is on.
Check that the digital inputs are not forced off.
Digital Outputs Problem Action
Output LED does not come on when output is turned on.
Check the LED POWER from the SCADAPack 32 controller.
Output LED is off, but the output is closed.
Output LED is on, but the output is open.
Relay contacts can be normally closed and/or normally open.
Output LED comes on but the output does not close.
Check if the relay is stuck. If so, return the board for repair.
Output LED comes on and output is closed, but the field device is not activated.
Check the field wiring.
Check the external device.
Output LED and relay are on when they should be off.
Check that the output is not forced on.
Output LED and relay are off when they should be on.
Check that the output is not forced off.
SCADAPack 32 Controller User and Reference Manual 56
Specifications
General I/O Terminations 6,8,9 and 10 pole, removable terminal blocks.
12 to 22 AWG
15A contacts
Dimensions
8.40 inch (213mm) wide
6.13 inch (155mm) high
2.80 inch (72mm) deep
Packaging corrosion resistant zinc plated steel with black enamel paint
Environment 5% RH to 95% RH, non-condensing
–40oC to 70oC
–40oF to 158oF
Controller Board Processor Hitachi SH-3 32-bit CMOS microcontroller
120 MHz. clock
Memory 4Mbytes Flash
8Mbytes SDRAM
512kBytes CMOS RAM
Non-volatile RAM
CMOS RAM with lithium battery retains contents for 2 years with no power
Clock calendar ±1 minute/month at 25°C
+1/–3 minutes/month 0 to 50°C
SCADAPack 32 Controller User and Reference Manual 57
Communications Communication Ports, SCADAPack 32 controller board
2 RS-232 serial ports (COM2, COM4)
Data Terminal Equipment (DTE)
8 pin modular jack
Communication Ports, SCADAPack 32 controller board
One serial port configurable RS-232 or RS-485 (COM1)
RS-232:
Data Terminal Equipment (DTE)
8 pin modular jack
RS-485:
2 wire half duplex
4 wire full or half duplex
optional termination resistors
Communication Ports, Lower I/O module
one RS-232 serial port (COM3)
Data Terminal Equipment (DTE)
DE-9P male connector
Baud Rates (COM1, COM2, COM4)
300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.
Baud Rates (COM3)
1200, 2400, 4800, 9600, 19200, 38400, 57600 and 115200.
Parity none, even, or odd
Word Length 7 or 8 bits
Stop Bits 1 or 2 bits
Duplex (COM1, COM2, COM 4)
full or half with RTS/CTS control
Duplex (COM3) half with RTS/CTS control
Cable Length RS-232 –maximum 50 ft (15.2 m)
RS-485 –maximum 4000 ft (1200 m)
Ethernet Termination
RJ-45 modular connector
10BaseT (twisted pair)
10M bits per second.
Protocol TeleBUS (compatible with Modbus RTU and Modbus ASCII)
Protocol Modes slave, master, master/slave, store and forward
SCADAPack 32 Controller User and Reference Manual 58
Visual Indicators COM1,COM2, COM4
received data (RxD) LED
transmitted data (TxD) LED
clear to send (CTS) LED
data carrier detect (DCD) LED
Ethernet LAN Ethernet network receive or transmit data LAN LED
Ethernet port connected to a network LINK LED
I/O module LED power status LED
Status LED (shows functional status)
5V power LED (LED power not applicable)
Run LED
Forced I/O LED
Counter Inputs 0, 1, 2 and 3 LEDs
Digital Inputs Lower I/O Module
16 red LEDs
field powered (LED power not applicable)
Digital Outputs 12 red LEDs on the lower I/O module
Push-button LED power toggle
SCADAPack 32 Controller User and Reference Manual 59
Power Supply
Controller Board Power Input AC/DC PWR IN
16Vrms ±20%
13 to 24V nominal
DC power Input DC PWR
28V maximum
10.7V typical turn on
9V typical turn off
5 Volt Power Output
5V at 1.3A capacity
5V at 500 mA required by SCADAPack 32 controller
DC power Output 16Vrms applied
20-24V with 1.0Vp-p maximum ripple.
300mA available at 5V/0.5A, de-rate linearly to 100mA available at 5V/1.3A
Efficiency 85%, 12V on DC PWR input
Lower I/O Module Power Input AC/DC PWR IN
16Vrms ±20%
14 to 28V
DC power Input DC PWR
11 to 28V at 20mA (loop power extra at 20mA maximum per loop)
DC power Output 16Vrms applied
20-24V with 1.0Vp-p maximum ripple.
400mA available
5V power required
500mA (all relays ON)
20mA (all relays OFF)
I/O Capacity 5000 Series I/O Expansion Capacity
256 digital inputs
256 digital outputs
128 analog inputs
64 analog outputs
32 counter inputs
maximum 40 I/O modules
SCADAPack 32 Controller User and Reference Manual 60
Analog Inputs Input Points 8 on SCADAPack 32 lower I/O module
Resolution 12 bits
Input Resistance
100kΩ for 5V inputs
250Ω for 20mA inputs
Converter type successive approximation
Accuracy ±0.1% of full scale at 25oC (77ºF)
±0.2% over temperature range
Type single ended
Normal mode rejection
60dB at 50 / 60 Hz.
Over-scale Input Capacity (without damage)
Continuous: 60% over scale sustained input signal. 0.25A maximum current and 8.2V maximum voltage.
Transient: 2.5kV surge withstand capability as per ANSI/IEEE C37.90.1-1989
Isolation Lower I/O Module
70Vrms / 100V from the logic power and chassis when jumper J3 on the lower I/O module has been cut and an isolated power supply is used to the lower I/O module.
Reading Update Time
100ms
Response Time 20ms typical for 10% to 90% signal change
SCADAPack 32 Controller User and Reference Manual 61
Analog Outputs Output Points 2 (when optional 5303 analog outputs installed)
Output Signal Range
0-20mA
Maximum Load Resistance
1000Ω with 24V DC loop power
400Ω with 12V DC loop power
250Ω with 9V DC loop power
Output Type single ended regulation on positive side with common negative return
Isolation 70Vrms / 100V from the logic power and chassis when jumper J3 on the lower I/O module has been cut and an isolated power supply is used to the lower I/O module.
D/A Resolution 12 bits
Absolute Accuracy
±0.05% at 25oC (77oF) with 250Ω load
±0.2% over temperature range, 0-1000Ω load
Noise and Ripple
0.04% maximum
Transient Protection
600W transient suppresser on each output
Response Time 250ms typical for 10% to 90% signal change
Power Requirements
5V at 10mA
9 to 28V at 15mA (55mA with all outputs at 20mA)
SCADAPack 32 Controller User and Reference Manual 62
Digital Inputs
Controller Board Input Points 4 Digital Input/Counter, opto coupler isolation
Digital Input, Counter
24Vrms/30V maximum input
10Vrms/10V minimum ON input
2V maximum OFF input
Typical threshold voltage is 4 to 6V
Typical input hysteresis 1.0V
Typical input current 2.5mA at 10V
7mA at 24V
Counter Input Frequency (Counter 0, 1, 2)
5 kHz maximum with filter OFF
30 Hz maximum with filter ON
Counter Input Frequency (Counter 3)
500 Hz maximum
Lower I/O Module Input Points 16
Over-voltage Tolerance 150% sustained over-voltage without damage
Input Current 6.5mA typical at 24V on the 24V range
3.5mA typical at 115V on the 115V range
Input Logic-HI Level OFF to ON transition threshold is typically 7.5V on 24V range
OFF to ON transition threshold is typically 50% of full scale signal range on 48V, 115V and 220V ranges.
AC Input Voltage 12V and 24V 115V
Off – To – On 8.8Vrms+/-0.5Vrms
65Vrms+/- 5Vrms
On – To – Off 6.0Vrms+/-0.5Vrms
45Vrms+/- 5Vrms
DC Input Voltage 12V and 24V 115V
Off – To – On
7.5Vdc+/- 0.5Vdc
57Vdc +/- 5Vdc
On – To – Off
7.5Vdc+/- 0.5Vdc
57Vdc +/- 5Vdc
AC Response Time @50 Hz @60 Hz
Off – To – On
6 – 18mS
5 – 15mS
On – To – Off
6 – 18mS
5 - 15mS
SCADAPack 32 Controller User and Reference Manual 63
DC Response Time @50 Hz @60 Hz
Off – To – On
6 – 8mS
5 – 7mS
On – To – Off
16 – 18mS
13 - 15mS
Isolation 1500Vrms in groups of 8 inputs
SCADAPack 32 Controller User and Reference Manual 64
Digital Outputs
Controller Board Status Output Opto coupler open collector transistor
30V, 60mA
opens on fault
Lower I/O Module Outputs 12 on lower I/O module
Lower I/O Module
sealed mechanical relay
Form C (normally open and normally closed) on Outputs 0 and 1.
Form A (normally open) contacts on Outputs 2 and 3.
Form A (normally open) contacts with common return on Outputs 4 through 7.
Form A (normally open) contacts with common return on Outputs 8 through 11.
Contact Ratings 0.4A at 125 Vrms, 2A at 30V resistive loads
1.0A at 30V, 0.2A at 125Vrms inductive load with pf=0.4, L/R=7ms
250Vrms, 220V maximum operating voltage
Operating Frequency
36,000 operations/hour mechanically, 1,800 electrically at rated load
Service Life 1,500,000 operations at 1A/30V resistive load
150,000 operations at 0.25A/125Vrms resistive load
Operate Time 10ms maximum
Release Time 10ms maximum
Bounce Time 3ms typical
Contact Isolation
1000Vrms
Logic Isolation 1500Vrms
SCADAPack 32 Controller User and Reference Manual 65
SCADAPack 32 Controller User and Reference Manual 66
CE Mark Self Declaration Control Microsystems attests that the SCADAPack 32 Programmable Controller, comply under Module “A”, self declaration route, with the European Harmonized Standards:
EN55081-2: 1993 Electromagnetic Compatibility Generic Emission Standard Part 2: Industrial Environment
EN 61000-6-2; 1999 Electromagnetic Compatibility Generic Standards Immunity For Industrial Environments
and are eligible to bear the CE mark:
The Machine Directive and Low Voltage Directives are not applicable to these products.