safety webinar #3 - gb 2008 (2).ppt [read-only]

16
Grounding Services Presenter: Michael J. Johnston NECA Executive Director, Standards and Safety Objectives: Review general requirements for grounding electrical services and service equipment Review requirements specific to services supplied by grounded utility systems (sources) Review requirements specific to services supplied by ungrounded utility systems (sources) Review requirements for grounded conductors, main bonding jumpers, and equipment bonding jumpers Review essential conductors and connections for grounding electrical services.

Upload: others

Post on 01-Mar-2022

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Grounding Services

Presenter: Michael J. JohnstonNECA Executive Director,

Standards and Safety

Objectives:

• Review general requirements for grounding electrical services and service equipment

• Review requirements specific to services supplied by grounded utility systems (sources)

• Review requirements specific to services supplied by ungrounded utility systems (sources)

• Review requirements for grounded conductors, main bonding jumpers, and equipment bonding jumpers

• Review essential conductors and connections for grounding electrical services.

Page 2: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

General Grounding Provisions

• Electrical systems are grounded (connected to ground) in a fashion that limits voltages imposed by lightning, line surges, and contact with higher voltage lines.

• Grounding electrical systems stabilizes to voltage to ground during normal operation. [250.4(A)(1)]

• Grounding equipment limits the voltage potential to ground by keeping the grounded conductor and conductive parts of equipment at or as close to earth potential as possible. [250.4(A)(2)]

Definition of Service

• The conductors and equipment for delivering electric energy from the serving utility to the wiring system of the premises served.

• The definition of service includes the statement that electric energy to a service can be supplied only by the serving utility.

• If electric energy is supplied by other than the serving utility, the supplied conductors and equipment are considered feeders, not a service.

Page 3: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Services Supplied by Grounded Source

• Grounded conductor is required to be brought to the service equipment.

• The grounded conductor must be routed with the ungrounded phase conductors.

• The grounded conductor must be connected to the service equipment enclosure.

• The grounded conductor must be connected to the earth by a grounding electrode conductor.

• The grounded conductor must be sized not smaller that required by 250.24(C).

Page 4: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Services Supplied by Ungrounded Source

• The utility system or source is ungrounded.

• No grounded conductor is required to be brought to the service equipment.

• The service equipment is required to be grounded.

• A grounding electrode conductor connects the equipment enclosures to a grounding electrode system meeting the requirements of Article 250,Part III.

Page 5: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Grounding Electrode System Required

• All grounding electrodes specified in 250.52(A) that are present at each building or structure service shall be bonded together and used as the grounding electrode system for the service.

– Metal water pipe– Structural metal frame electrodes– Concrete-encased electrodes– Ground rings– Other electrodes such as rods, pipes, or plates

Page 6: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Conductors at Grounded Services

• Four conductors must be present for proper grounding at electrical services supplied by grounded utility sources.

– Grounded conductor– Main bonding jumper– Grounding electrode conductor– Equipment grounding conductor

• Each of these conductors will be covered separately.

Grounded Conductor Requirements

• Required to be run to the service equipment enclosure.

• Required to be bonded to the service equipment enclosure.

• Required to meet the minimum sizing requirements in 250.24(C).

• Overcurrent devices generally not permitted in the grounded conductor.

• Must be identified in accordance with 200.6.

Page 7: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Grounded (Neutral) Conductor Functions

• Carries the maximum unbalanced current on the neutral of the systems served.

• In ground-fault conditions, the grounded (neutral) conductor at each service functions as an effective ground-fault current path.

• It must be run to each service disconnecting means for this reason [250.24(C)]

Main Bonding Jumper

• The main bonding jumper connects the grounded service conductor to the equipment grounding conductor (enclosure) at the service equipment.

• Main bonding jumper can be a wire, bus, screw, or other suitable conductor. [250.28(A)]

• Main bonding jumpers in listed equipment can be used without calculating size.

• Wire-type main bonding jumpers shall be sized according to the provisions in 250.28(D) which indicates use of Table 250.66 or the 12.5% rule for larger services.

Page 8: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Suitable for Use as Service Equipment

• Equipment is required to be suitable for use as service equipment. [230.66]

• Service equipment includes grounding and bonding provisions for use as service.

• Main bonding jumper is part of listed equipment and can be used without calculation of size.

Grounding Electrode Conductor

• The grounding electrode conductor connections at the service shall meet the provisions in 250.24(A)(1) through (A)(5).

• Connect at an accessible location at any point from the load end of the service drop or lateral to an including the grounded conductor terminal bus at the service disconnect. [250.24(A)(1)]

• Where the service transformer is outside the building, an additional grounding connection shall be made at the transformer or elsewhere outside the building. [250.24(A)(2)]

Page 9: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Load-Side Grounding Connections

• The grounded conductor generally shall not be connected to normally non-current-carrying metal parts of equipment, to the equipment grounding conductor, or be connected to ground (earth) on the load side of the service disconnecting means. [250.24(A)(5)]

• Note that the grounded conductor is permitted to be used for grounded on the supply side of the service disconnect as indicated in 250.142(A).

• Separation generally required beyond that point to control normal current present in the grounded conductor (often a neutral).

Equipment grounding Conductor

• The last conductor that will be present in the service equipment is the equipment grounding conductor, which could be the service equipment enclosure.

• All four conductors have to be installed and connected properly within the service equipment enclosure.

Page 10: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Service Bonding Requirements

• Service bonding rules are provided in 250.92.

• The following conductive parts of equipment are required to be bonded together:

– Service raceways– Cable trays– Cable bus framework– Auxiliary gutters– Service cable armor or sheath

• Note: The bonding on the supply side of the service must be robust (strengthened method) due no overcurrent protection ahead of the service.

Service Bonding Requirements

• Service bonding rules are provided in 250.92 (cont).

• The following conductive parts of equipment are required to be bonded together:

– Service equipment enclosures– Meter sockets or metering equipment enclosures– Raceways that join metering equipment to the service

equipment enclosures

• Note: Some service equipment includes the meter and service disconnect in the same enclosure.

Page 11: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Bonding Methods

• Electrical continuity of conductive parts at service equipment shall be ensured by one of the following methods:

– Using the grounded conductor

– Threaded couplings or threaded bosses on enclosures

– Threadless couplings and connectors for metal raceways and metal-clad cables

– Other listed devices, such as bonding-type locknuts, bushings, or bushings with bonding jumpers

Bonding Methods (cont.)

• Bonding jumpers shall be installed around concentric or eccentric knockouts that are punched or otherwise impairing effective bonding connections between conductive parts.

• Note that standard locknuts are not permitted as to sole bonding means required by Section 250.92(B).

Page 12: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Grounded Conductor for Bonding

• Permitted on the supply side of the service disconnect in accordance with 250.142(A).

• Section 250.92(B)(1) indicates a method of bonding at the service equipment using the grounded conductor (usually a neutral conductor).

• The method of bonding is common between a separate meter socket enclosure and the service disconnecting means enclosure.

Supply-Side Equipment Bonding

• Metallic parts shall be bonded together using one of the methods in 250.92(B).

• Equipment bonding jumpers (wire-types) on the supply side of the service disconnecting means shall be sized not smaller than required by 250.102(C).

• Use Table 250.66 or 12.5% rule for larger services.

• Connections shall be in accordance with Section 250.8.

Page 13: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Other Service Bonding Connections

• Metal water piping systems must be bonded in accordance with 250.104(A).

• Other metal piping, including metal gas piping systems are required to be bonded in accordance with 250.104(B).

• Structural metal building frames must be bonded in accordance with 250.104(C).

Page 14: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Summary for Grounded Services

• Four conductors have to be installed and connected at the service equipment for proper grounding and bonding:

– Grounded conductor (usually a neutral)– Main bonding jumper– Grounding electrode conductor– Equipment grounding conductor

Ungrounded Services

• Rules for services supplied by ungrounded systems (utility sources) are provided in 250.24(E).

• Grounding electrode conductor is required to connect the equipment to a grounding electrode system meeting the requirements of Part III of Article 250.

• This connection shall be made at any accessible point from the load end of the service drop or lateral to the service disconnecting means.

Page 15: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Ungrounded Services (cont.)

• A minimum of three conductors must be present in the service disconnecting means enclosure as follows:

– Grounding electrode conductor– Supply-Side Equipment bonding jumper(s)– Equipment grounding conductor(s)

• Note: More bonding conductors may be required for water pipe bonding, other pipe bonding and bonding structural metal.

• Sizing requirements are the same as those for grounded services.

Summary for Grounded Services (cont.)

• Grounded services include a grounded conductor that must be:

– Routed to the service disconnect enclosure– Bonded to the service disconnect enclosure– Sized in accordance with 250.24(C)– Identified in accordance with 200.6

• Bonding at service equipment shall meet the requirements in 250.92(A) and (B).

• Other metallic parts to be bonded include metal water piping, other metal piping, and structural steel.

Summary for Ungrounded Services

• Ungrounded services do not include a grounded conductor.

• Must have a grounding electrode conductor connected to a grounding electrode system meeting the requirements in Part III of Article 250.

• Bonding at service equipment shall meet the requirements in 250.92(A) and (B).

• Other metallic parts to be bonded include metal water piping, other metal piping, and structural steel.

Page 16: Safety webinar #3 - GB 2008 (2).ppt [Read-Only]

Grounding Services

Presenter: Michael J. JohnstonNECA Executive Director,

Standards and Safety