�UT00655_�2-2006_EN
Presentation 2
Choicetable 4TechnicaldataThe intuitive switches 6The �8 mm intuitive switches 8 The annual switches 9 The multifunctional switch �0 The mechanical switches ��The �8 mm mechanical switches �2
PracticaladviceA few principles �3Programming examples �4
Dimensions �6
Summary
2
Time switches
UT00655_�2-2006_EN
PresentationEfficiency at your fingertips!
Residential lighting management
Time switches are used to accurately and automatically program the operation of heating, lighting, ventilation, access control, bells, roller blinds, etc.
Heating and ventilation management in buildings
Bell management in schools
Energy savingsThe installation only operates when necessary, and during low-rate periods.
Convenient useCustomization of operating periods, accurate start-up.
User safetySimulation of presence with the random operating mode proposed in IHP’+’ versions.
Access management in buildings
P93
362The intuitive switches
With 4 keys and a display, they operate on a weekly cycle: the same program is repeated week after week.
04�3
�2D
The annual switchesThey operate on an annual cycle: the same program is repeated year after year.
0592
39The multifunctional switchesThey operate with weekly or annual time programming distributed across 1, 2, 3 or 4 channels. 6 inputs to condition the functions.
PB
�00�
63
P94
9��The mechanical switches
They operate on an hourly, daily or weekly cycle: the same program is repeated hour after hour (IH 60 min), day after day (IH 24 h) or week after week (IH 7d).
0582
50N
H
3UT00655_�2-2006_EN
Time-savings with intuitive programmingb Only 4 keys.b Choice of language and guiding in the menus by key words to create, check, modify or partially or totally delete the program.b Time updating and changeover to winter/summer time:v automatic: selected when programming the changeover date (according to geographic area),v manually by the user,v without modification of programs.
P93
582
Unique programming legibilityLarge screen for display of:b Hour, minutes and day of the week.b Current operating mode.b Channel switching status («On», «Off»).b Control mode (automatic, override, random or holiday for the + version).b Operation on mains or battery.
P93
584
P93
589
Simplified installationb Mechanical compatibility with electrical distribution busbar.b Direct connection of loads up to �6 A under 250 V.b Fast connection; 2 screw-less terminals per pole for cables up to 2.5 mm² .b Installation leaflet always available in the device thanks to the built-in leaflet holder slot.b Swivel, sealable cover.
P93
580
Programming kit for PC
P93
58�
Memory key
Simplified useb Backlit display.b Saving and duplicating of programs with memory key.b Programming with a programming kit for PC.b Control of the time switch away from the panelboard via external inputs.
Advanced featuresof intuitive switches
4
Time switches
UT00655_�2-2006_EN
The time switches control opening and closing of one or more separate circuits according to a programming pre-set by the user:b by memorisation of On and Off switching operations for the IHP switchesb by positioning of jumpers or captive segments on a programming dial for the mechanical IH switches.An IHP or IH time switch is chosen according to the following criteria:
Choicetable
(1) Programming of dated days allows specific switching operations on certain days. (2) The IHP DCF is synchronised on the Frankfort transmitter via the ANT DCF antenna. (3) Supply voltage: �20 V CA.(4) 4 output channels and 6 condition inputs. (5) 45 time brackets in weekly time programming, �5 time brackets in annual time programming, 20 different pulses in pulse programming.(6) On/Off via an override input or a condition input.(7) For IHP +�c and IHP+ 2c.(8) For ITM 4c-6E.
Designation Numberofchannels
Cycleperiod(d: day)
Mnimumtimebetween2switchingoperations
Numberofswitchingoperations
Savingonmainscutoff
Width(modules of 9 mm)
Overridecontrols On / Off
Outputcontactchangeover switch(cos j =�)
Timechangeover(summer/winter)
Back-litdisplay,randomfunctionandpulseprogramming(9)
«Absenceforholidays»function
Screw-lessconnection
Mechanicalcompatibilitywithelectricaldistributioncombbusbars
Inputforexternalcontrol
Instructionmanualholderinfrontface
Memorykeyintegratedinfrontface
Cataloguenumber
Theintuitiveswitches
IHP �c � 24 h and/or 7 d � min. 56 6 years 5 On / Off �6 A Auto b b b CCT�5400 (10), CCT�5420 (11), CCT�5450 (12), CCT�5720 (13), CCT�5850 (14)
IHP + �c � 24 h and/or 7 d � s 84 6 years 5 On / Off �6 A Auto b b b b � input b b CCT�540� (10), CCT�542� (11), CCT�545� (12), CCT�572� (13), CCT�585� (14)
IHP 2c 2 24 h and/or 7 d � min. 56 6 years 5 On / Off �6 A Auto b b b CCT�5402 (10), CCT�5422 (11), CCT�5452 (12), CCT�5722 (13), CCT�5852 (14)
IHP + 2c 2 24 h and/or 7 d � s 84 6 years 5 On / Off �6 A Auto b b b b 2 inputs b b CCT�5403 (10), CCT�5423 (11), CCT�5453 (12), CCT�5723 (13), CCT�5853 (14)
IHP DCF �c (2) � 24 h and/or 7 d � s 42 4 years 5 On / Off �6 A Auto Random function b b �5857
IHP �c (UL) (3) � 24 h and/or 7 d � min. 28 3 years 5 On / Off �6 A Auto b �5830
IHP 2c (UL) (3) 2 24 h and/or 7 d � min. 42 5 years 5 On / Off �6 A Auto b �583�
The18mmintuitiveswitches
IHP �c �8 mm � 24 h and/or 7 d � min. 28 3 years 2 On / Off �6 A Auto �5854 (14), �5724 (13)
IHP + �c �8 mm � 24 h and/or 7 d � min. 42 3 years 2 On / Off �6 A Auto b b b �5837(14), �5725 (13)
Theannualswitches
IHP �c annual (1) � 7 d + dated d � min. ��6 4 years �0 On / Off �6 A Auto b �6355
IHP 2c annual (1) 2 7 d + dated d � min. ��6 4 years �0 On / Off �6 A Auto b �6356
Themultifunctionalswitch
ITM 4C-6E (4) 4 60 min., 24 h, 7 d, 7 d + dated d
� s (5) 5 years �0 On/Off (6) �0 A Auto Pulse function b b b �5270
Themechanicalswitches
IH 60 mn �c SRM � 60 min. � min. �5 s 24 On - 24 Off none 6 On �6 A Manual �5338
IH 24h �c SRM � 24 h 30 min. 24 On - 24 Off none 6 On �6 A Manual �6364
IH 24h �c ARM � 24 h 30 min. 24 On - 24 Off �50 h 6 On �6 A Manual �5365
IH 24h 2c ARM 2 24 h 30 min. 24 On - 24 Off �50 h 6 On �6 A Manual �5337
IH 7d �c ARM � 7 days 4h 2� On - 2� Off �50 h 6 On �6 A Manual �5367
IH 24 h + 7d �+�c ARM
�+� 24 h + 7 d 45 min. + �2 h
�6 On -�6 Off + 7 On -7 Off
�50 h 6 On �6 A Manual �5366
The18mmmechanicalswitches
IHH 7d �c ARM � 7 days 2 h 42 On - 42 Off �00 h 2 On / Off �6 A Manual �533�
IH 24h �c ARM � 24 h �5 min. 48 On - 48 Off �00 h 2 On / Off �6 A Manual �5336
IH 24h �c SRM � 24 h �5 min. 48 On - 48 Off none 2 On / Off �6 A Manual �5335
Accessories
Programming kit (7) CCT�5860
Memory key (7) CCT�586�
Memory cartridge (8) �5280
ANT DCF antenna �5858
5UT00655_�2-2006_EN
Designation Numberofchannels
Cycleperiod(d: day)
Mnimumtimebetween2switchingoperations
Numberofswitchingoperations
Savingonmainscutoff
Width(modules of 9 mm)
Overridecontrols On / Off
Outputcontactchangeover switch(cos j =�)
Timechangeover(summer/winter)
Back-litdisplay,randomfunctionandpulseprogramming(9)
«Absenceforholidays»function
Screw-lessconnection
Mechanicalcompatibilitywithelectricaldistributioncombbusbars
Inputforexternalcontrol
Instructionmanualholderinfrontface
Memorykeyintegratedinfrontface
Cataloguenumber
Theintuitiveswitches
IHP �c � 24 h and/or 7 d � min. 56 6 years 5 On / Off �6 A Auto b b b CCT�5400 (10), CCT�5420 (11), CCT�5450 (12), CCT�5720 (13), CCT�5850 (14)
IHP + �c � 24 h and/or 7 d � s 84 6 years 5 On / Off �6 A Auto b b b b � input b b CCT�540� (10), CCT�542� (11), CCT�545� (12), CCT�572� (13), CCT�585� (14)
IHP 2c 2 24 h and/or 7 d � min. 56 6 years 5 On / Off �6 A Auto b b b CCT�5402 (10), CCT�5422 (11), CCT�5452 (12), CCT�5722 (13), CCT�5852 (14)
IHP + 2c 2 24 h and/or 7 d � s 84 6 years 5 On / Off �6 A Auto b b b b 2 inputs b b CCT�5403 (10), CCT�5423 (11), CCT�5453 (12), CCT�5723 (13), CCT�5853 (14)
IHP DCF �c (2) � 24 h and/or 7 d � s 42 4 years 5 On / Off �6 A Auto Random function b b �5857
IHP �c (UL) (3) � 24 h and/or 7 d � min. 28 3 years 5 On / Off �6 A Auto b �5830
IHP 2c (UL) (3) 2 24 h and/or 7 d � min. 42 5 years 5 On / Off �6 A Auto b �583�
The18mmintuitiveswitches
IHP �c �8 mm � 24 h and/or 7 d � min. 28 3 years 2 On / Off �6 A Auto �5854 (14), �5724 (13)
IHP + �c �8 mm � 24 h and/or 7 d � min. 42 3 years 2 On / Off �6 A Auto b b b �5837(14), �5725 (13)
Theannualswitches
IHP �c annual (1) � 7 d + dated d � min. ��6 4 years �0 On / Off �6 A Auto b �6355
IHP 2c annual (1) 2 7 d + dated d � min. ��6 4 years �0 On / Off �6 A Auto b �6356
Themultifunctionalswitch
ITM 4C-6E (4) 4 60 min., 24 h, 7 d, 7 d + dated d
� s (5) 5 years �0 On/Off (6) �0 A Auto Pulse function b b b �5270
Themechanicalswitches
IH 60 mn �c SRM � 60 min. � min. �5 s 24 On - 24 Off none 6 On �6 A Manual �5338
IH 24h �c SRM � 24 h 30 min. 24 On - 24 Off none 6 On �6 A Manual �6364
IH 24h �c ARM � 24 h 30 min. 24 On - 24 Off �50 h 6 On �6 A Manual �5365
IH 24h 2c ARM 2 24 h 30 min. 24 On - 24 Off �50 h 6 On �6 A Manual �5337
IH 7d �c ARM � 7 days 4h 2� On - 2� Off �50 h 6 On �6 A Manual �5367
IH 24 h + 7d �+�c ARM
�+� 24 h + 7 d 45 min. + �2 h
�6 On -�6 Off + 7 On -7 Off
�50 h 6 On �6 A Manual �5366
The18mmmechanicalswitches
IHH 7d �c ARM � 7 days 2 h 42 On - 42 Off �00 h 2 On / Off �6 A Manual �533�
IH 24h �c ARM � 24 h �5 min. 48 On - 48 Off �00 h 2 On / Off �6 A Manual �5336
IH 24h �c SRM � 24 h �5 min. 48 On - 48 Off none 2 On / Off �6 A Manual �5335
Accessories
Programming kit (7) CCT�5860
Memory key (7) CCT�586�
Memory cartridge (8) �5280
ANT DCF antenna �5858
(9)Pulse programming allows switching operations of a duration less than one minute (adjustable from � to 59s); a pulse control always has priority. (10) English, russian, ukrainian, latvian, lituanien, estonian languages. (11) English, bulgarian, greek, slovene, serbian, croatian languages. (12) English, hungarian, polish, romanian, czech, slovak languages. (13) French, english, italian, spanish, german, portuguese languages. (14)French, english, swedish,dutch, finnish, norwegian/danish languages.
6
Time switches
UT00655_�2-2006_EN
TechnicaldataThe intuitive switches
Function
b These time switches automatically switch on and off loads according to the program entered by the user. b They operate on weekly cycle: the same program is repeated week after week.b They offer automatic summer/winter time change, and allow to adjust it according to where you are located.b The program can be overriden temporary or permanently by pressing 2 keys on the product.b The IHP �C and 2C, as the IHP+ also offer holidays program, by configuring the starting and ending dates of the absence.
Electricaldatab Voltage: 230 V AC ± �0 %. b Frequency: 50/60 Hz. b Consumption: 2 VA for IHP DCF �c, 4 VA for IHP�c/+�c, 7 VA for IHP 2c/+2c and 6 VA for IHP�c/2c (UL). b Saving of program and time by lithium battery: v lifetime: 6 years for IHP �c/2c, IHP+ �c/2c, �2 years for IHP DCF �c, IHP �c/2c (UL), v back-up time, cumulated mains cut off: 4 years for IHP DCF �c, 5 years for IHP �c/2c (UL), 6 years for IHP �c/2c and IHP+ �c/2c. b Time accuracy: v ± � s per day at 20°C, v � s on � million years thanks to the synchronisation on the DCF Frankfort transmitter signal for IHP DCF �c. b Contact rating: v �6 A under 250 V AC (cos j = �), v �0 A under 250 V AC (cos j = 0.6).
Mechanicaldatab Overall dimensions: 5 modules of 9 mm. b Degree of protection: IP20B. b Operating temperature: - �0°C to + 50°C. b Location for instruction manual on the front face for IHP �c/2c, IHP + �C/2c and IHP DCF �c. b The IHP �c/2c, IHP +�c/2c are compatible with electrical distribution comb busbars (mechanical compatibility).
Specificdatafor1and2channelIHP+b Manual functions: v temporary cancellation of programming for holidays, public holidays, etc. by configuration of the 2 dates - start and end of absence, v simulation of presence thanks to random operation during On periods. b Pulse functions: programming of pulses adjustable from � to 59 s (pulse takes priority over switching). b Back-lighting of the screen. b Memory key located on front face. b Supplementary inputs for external control with a switch or a push-button (� input for IHP+ �c and 2 inputs for IHP+ 2c). v characteristics of the input:- voltage: 230 V AC, +�0 %, -�5 %, - frequency: 50/60 Hz, - input current: max. �.2 mA,- consumption: max. 0.3 mW, - cable length: max. �00 m.b Accessory: v programming kit for PC consists of a programming device, a memory key, a CDROM and a 2 m USB cable. v memory key for saving and duplicating programs.
IHP �c
IHP 2c
IHP +�c
IHP +2c
P93
356
P93
362
P93
580
Programming kit for PC
P93
352
P93
358
P93
58�
Memory key
7UT00655_�2-2006_EN
SpecificdatafortheIHPDCFb Synchronisation on the Frankfort transmitter DCF 77 signal:v automatic on commissioning, then at � am, 2 am, 3 am and 4 am every day,v manual by pressing the IHP keys or after a «reset»,v displayed on the screen by the letters RC,v programming of pulses adjustable from � to 59 s (pulse takes priority over switching).b Manual functions:v temporary cancellation of programming for holidays, public holidays, etc. by configuration of the 2 dates - start and end of absence,v simulation of presence thanks to random operation during On periods.b Pulse functions: programming of pulses adjustable from � to 59 s (pulse takes priority over switching).
SpecificdatafortheANTDCFantennab Connection: �.5 mm², 5 IHP DCF maximum per antenna, maximum distance between the IHP DCF and the antenna: 200 m. b Installation: outside the electrical switchboard, outdoors, under shelter. b Operating temperature: - 20°C to + 70°C. b Degree of protection: IP54. b Overall dimensions: L x W x H: 70 x 57 x 92 mm.
Connectionb � screw connection per pole for cables up to 6 mm² for IHP �c/2c (UL) and IHP DCF �c. b 2 screw-less connection per pole for cables up to 2.5 mm² for IHP �c/2c and IHP+ �c/2c.
CataloguenumbersDesignation Cataloguenumber
IHP �c CCT�5400 (1), CCT�5420 (2), CCT�5450 (3), CCT�5720 (4), CCT�5850 (5)
IHP + �c CCT�540� (1), CCT�542� (2), CCT�545� (3), CCT�572� (4), CCT�585� (5)
IHP 2c CCT�5402 (1), CCT�5422 (2), CCT�5452 (3), CCT�5722 (4), CCT�5852 (5)
IHP + 2c CCT�5403 (1), CCT�5423 (2), CCT�5453 (3), CCT�5723 (4), CCT�5853 (5)
IHP DCF �c �5857
IHP �c (UL) �5830 (6)
IHP 2c (UL) �583� (6)
Accessories
ANT DCF �5858
Programming kit for PC
CCT�5860
Memory key CCT�586�
IHP DCF �c
ANT DCF
menuRes 21
ok
M
N
L
230-240V50-60Hz-10 T 50
1 2 3 4 5 6 7
3
0
6
22:30
15 RCAuto Prog
16(10) 250V
ANTDCF
Off
03Man9
12 15 18 21 24
menuRes 21
ok
M
N
L
230-240V50-60Hz-10 T 50
1 2 3 4 5 6 7
3
0
6
22:30
15 RCAuto Prog
16(10) 250V
ANTDCF
Off
03Man9
12 15 18 21 24
L
12 V
N
L
N
IHP DCF �c- connection of 5 IHP DCF maxi. per antenna
ANT DCF
0592
37N
HD
0592
36N
HD
�����
������
���
� � �� ����������
��������� � � � ����� �����������������������
� �
� � ��
��������������
����
�
�������
�����������
��������������
���
� � ��
��������������
����
��������������
�
� � ���
� � ���
�
�����
������
���� ����
� � �� ����������
��������� � � � ����� �����������������������
� �
��� � ��
��������������
����
�
�������
�����������
��
� � �
�������������������
���� ����
��� � ��
��������������
����
�������������������
� � ��
� � ���
� � ���
�
(1) English, russian, ukrainian, latvian, lituanien, estonian. (2) English, bulgarian, greek, slovene, serbian, croatian. (3) English, hungarian, polish, romanian, czech, slovak. (4) French, english, italian, spanish, german, portuguese. (5)French, english, swedish,dutch, finnish, norwegian/danish.(6) Supply voltage: �20 VAC ± �0%.
P93
864
P93
865
8
Time switches
UT00655_�2-2006_EN
Technicaldata The �8 mm intuitive switches
Functionb These time switches automatically switch on and off loads according to the program entered by the user. b They operate on weekly cycle: the same program is repeated week after week. b They offer automatic summer/winter time change, and allow to adjust it according to where you are located. b The program can be overriden temporary or permanently by pressing 2 keys on the product.
Electricaldatab Voltage: 230 V AC ± �0 %. b Frequency: 50/60 Hz. b Consumption: 2.5 VA for IHP �c �8 mm, 3 VA for IHP + �c �8 mm. b Saving of program and time by lithium battery: v lifetime: �0 years, v back-up time, cumulated mains cut off: 3 years. b Time accuracy: ± � s per day at 20°C. b Contact rating: v �6 A under 250 V AC (cos j = �), v 4 A under 250 V AC (cos j = 0.6).
Mechanicaldatab Overall dimensions: 2 modules of 9 mm. b Degree of protection: IP20B. b Operating temperature: - �0°C to + 50°C. b Mechanical compatibility with electrical distribution comb busbars (only for IHP + �c �8 mm).
Connectionb � screw connection per pole for cables up to 6 mm².
CataloguenumbersDesignation Cataloguenumber
IHP �c �8 mm �5854 (1), �5724 (2)
IHP + �c �8 mm �5837 (1), �5725 (2)
(1)French, english, swedish, dutch, finnish, norwegian/danish.(2) French, english, italian, spanish, german, portuguese.
menu
Res
ok
10:54
Prog
On
L N
IHP +�c �8 mm
PB
�00�
63
9UT00655_�2-2006_EN
Functionb These time switches automatically switch on and off loads according to the program entered by the user. b They operate on annual cycle: the same program is repeated year after year. b They offer automatic summer/winter time change and allow to adjust it according to where you are located. b The program can be overriden temporary or permanently by pressing keys on the product.
Electricaldatab Voltage: 230 V AC ± �0 %. b Frequency: 50/60 Hz. b Consumption: 3.5 VA. b Saving program and time by lithium battery: v lifetime: �0 years,v back-up time, cumulated mains cut off: 4 years. b Time accuracy: ± � s per day at 20°C. b Contact rating: v �6 A under 250 V AC (cos j = �), v �0 A under 250 V AC (cos j = 0.6).
Mechanicaldatab Overall dimensions: �0 modules of 9 mm. b Degree of protection: v front face: IP40, v terminals: IP20B. b Operating temperature: - �0°C to + 50°C.
Connectionb � screw connection per pole for cables up to 6 mm².
IHP �c annual IHP 2c annual
CataloguenumbersDesignation Cataloguenumber
IHP �c annual �6355
IHP 2c annual �6356
Accessory
Lithium battery �6357
IHP �c annual
Technicaldata The annual switches
IHP 2c annual
0539
4�04
�3�2
D
�0
Time switches
UT00655_�2-2006_EN
Functionb Weekly or annual time programming to be distributed over �, 2, 3 or 4 channels. 6 inputs to condition these functions. b A removable memory cartridge to duplicate on another ITM or to save the program created by the contractor.
Electricaldatab Voltage: 230 V AC ± �0 %. b Frequency: 50 Hz. b Consumption: 4.5 VA. b Saving program and time by lithium battery: v lifetime: �0 years, v back-up time: 5 years. b Time accuracy: ± � s per day at 20°C. b Contact rating: v �0 A under 250 V AC (cos j = �), v 6 A under 250 V AC (cos j = 0.6).
Mechanicaldatab Overall dimensions: �0 modules of 9 mm. b Degree of protection: v front face: IP40, v terminals: IP20B. b Operating temperature: - 5°C to + 50°C.
Connection
b � screw connection per pole for cables up to 6 mm².
CataloguenumbersDesignation Cataloguenumber
ITM 4C-6E �5270
Accessory
Memory cartridge �5280
ITM 4c - 6E
L N
L N L N L N L N
230V~50Hz 1...6=Entrées / Inputs 230V~
C1......C4Canaux / Channels �0A / 230V~
C 1 C 2 C 3 C 4
menu OK
+-
L N 1 2 3 4 5 6
(switch, pushbutton, light sensitive switch, thermostat, motion control switch, ...)
6 x 230 V AC inputs
Removable memory cartridge (optional)
4 x 230 V AC �0 A output channels
C1-C2C3-C4
ON
OFF
Load
(lamp, small motor, bell,
luminous sign, ...)
Preferably relay your load
with a contactor.
0592
39
Technicaldata The multifunctional switch
��UT00655_�2-2006_EN
IH 60 min �c SRM, IH 24h �c SRM/ARM, IH 7d �c ARM
IH 24h 2c ARM
IH 24d +7d �+�c ARM
IH 60 min. �c SRM
IH 24 h + 7d �+�c ARM
P94
906
P94
9��
Functionb These time switches automatically switch on and off loads according to the program entered by the user. b They operate on hourly, daily or weekly cycle: the same program is repeated hour after hour (IH 60 min), day after day (IH 24 h), week after week (IH 7d). b The program can be overriden on.
Electricaldatab Voltage: 230 V AC ± �0 %. b Frequency: 50/60 Hz (50 Hz for IH 60 min. �c SRM, IH 24h + 7d �+�c SRM). b Consumption: 2.5 VA (� VA for IH 60 min. �c SRM). b Time accuracy: ± � s per day at 20°C. b Contact rating: v �6 A under 250 VAC (cos j = �), v 4 A under 250 VAC (cos j = 0.6).
Mechanicaldatab Programming: v by jumpers (supplied):
IHtype Numberofjumperssupplied
IH 24h 2c ARM 4 red + 4 green + 2 white
IH 24h + 7d �+�c ARM 6 yellow (24 h)
�2 blue + 2 red (7 white)
IH 7d �c ARM 7 blue + 7 red v by captive segments for the other catalogue numbers.b Overall dimensions: 6 modules of 9 mm. b Degree of protection:v front face: IP40,v terminals: IP20B.b Operating temperature: - �0°C to + 50°C.b Accessories for IH 24h 2c ARM, IH 24h + 7d �+�c ARM, IH 7d �c ARM: the additional jumpers are used to program a larger number of sequences.
Connectionb Screw connection for cables up to 6 mm².
CataloguenumbersDesignation Cataloguenumber
IH 60 min �c SRM �5338
IH 24h �c SRM �6364
IH 24h �c ARM �5365
IH 24h 2c ARM �5337
IH 7d �c ARM �5367
IH 24h + 7d �+�c ARM �5366
Accessories
Additional jumpers (� bag containing: 5 red, 5 green, 5 white, 5 yellow) �534�
P94
907
IH 24 h �c SRM
Technicaldata The mechanical switches
�2
Time switches
UT00655_�2-2006_EN
Functionb These time switches automatically switch on and off loads according to the program entered by the user. b They operate daily or weekly cycle: the same program is repeated hour after hour, day after day (IH 24 h), week after week (IH 7d). b The program can be overriden on or off.
Electricaldatab Voltage: 230 V AC ± �0 %. b Frequency: 50/60 Hz. b Consumption: 2.5 VA. b Saving program and time: v lifetime: �0 years, v back-up time, cumulated mains cut off: �00 hours (except for IH 24 h �C SRM). b Time accuracy: ± � s per day at 20°C. b Contact rating: v �6 A under 250 V AC (cos j = �), v 4 A under 250 V AC (cos j = 0.6).
Mechanicaldatab Programming by captive segments b Overall dimensions: 2 modules of 9 mm. b Degree of protection: v front face: IP40, v terminals: IP20B. b Operating temperature: - �0°C to + 50°C.
Connectionb � screw connection per pole for cables up to 6 mm².
CataloguenumbersDesignation Cataloguenumber
IHH 7d �c ARM �533�
IH 24h �c SRM �5335
IH 24h �c ARM �5336
IHH 7d �c ARM
IH 24h �c ARM
0582
5�N
H05
8250
NH
Technicaldata The �8 mm mechanical switches
�3UT00655_�2-2006_EN
b For the IHP switches, this consists of memorising the days and times of the required switching operations.b For the IH - IHH switches, this is performed by positioning captive segments or jumpers on a switching dial.
Example b Controlling an air conditionner in a hairdressing salon:
Monday(1) Tuesday Wednesday Thursday(2) etc.
On n° � 08 h 30 08 h 30 08 h 30 switch on
Off n° � �2 h 00 �2 h 00 switch off
On n° 2 �3 h 30 �3 h 30 switch on
Off n° 2 20 h 00 20 h 00 20 h 00 switch off
(1)Closed on Mondays(2) Non-stop
Whenever identical switching operations are found at the same times, several days in the week, this function lets you program these operations once only. In this case a single switching operation is used. If this function is used wisely, the number of possible switching operations can be greatly increased.
Example
Monday Tuesday Wednesday Thursday Friday
On n°� �0 h 00 �0 h 00 switch on
Off n°� �8 h 00 �8 h 00 �8 h 00 switch off
Designation Numberofswitchingoperations
IHP �c 56
IHP + �c 84
IHP DCF �c 42
IHP 2c 56
IHP + 2c 84
IHP �c annual ��6
IHP 2c annual ��6
IHP �8 mm �c 28
IHP + �c �8 mm 42
ITM 4C-6E 45 time brackets in weekly time programming, �5 time brackets in annual time programming and 20 different pulses in pulse programming
IHP �c (UL) 28
IHP 2c (UL) 42
IH 7d �c ARM 42 On / 42 Off
IH 24h �c ARM 48 On - 48 Off
IH 24h �c SRM 48 On - 48 Off
IH 60 mn �c SRM 24 On - 24 Off
IH 24h �c SRM 24 On - 24 Off
IH 24h �c ARM 24 On - 24 Off
IH 24h 2c ARM 24 On - 24 Off
IH 7d �c ARM 2� On - 2� Off
IH 24 h + 7 d �+�c ARM �6 On - �6 Off + 7 On - 7 Off For IHP switches equipped with this function, a lithium battery is used for saving. The program, date and time are preserved. Switching operations are not performed.
PracticaladviceA few principles
Programming principle
Programming by copying or blocks
Number of switching operations
Saving on mains cut off
� switching operation � switching operation
�4
Time switches
UT00655_�2-2006_EN
PracticaladviceProgramming examples
Exampleb Controlling automatic watering:
On n° � 2 min. 30 s
Off n° � 5 min.
On n° 2 25 min.
Off n° 2 37 min. 30 s
Relevanttimeswitchesb IH 60 min �c SRM
Example b Controlling a door of a block of flats: v from 8 am to 7.30 pm: contact on «On», free access v from 7.30 pm to 8 am the next day: contact on «Off», access by confidential code every day of the week:
FromMondaytoSunday
On n° � 8 am
Off n° � 7.30 pm Relevanttimeswitchesb IH 24h �c SRM/ARMb IH 24h 2c ARMb IHP �c �8 mmb IHP + �c �8 mmb IHP DCF �cb IHP �c, IHP + �cb IHP 2c, IHP + 2cb ITM 4C-6E
Example b Controlling the lighting of a shop window:
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
On n° � 09 h 00 09 h 00 09 h 00
Off n° � �2 h 00 �2 h 00
On n° 2 �4 h 00 �4 h 00
Off n° 2 20 h 00 20 h 00 20 h 00
On n° 3 8 h 30 8 h 30
Off n° 3 �2 h 30 �2 h 30
On n° 4 �4 h 30 �4 h 30
Off n° 4 2� h 00 2� h 00
Relevanttimeswitchesb IH 7 d �c ARM b IHP �c, IHP + �c b IHP 2c, IHP + 2c b IHP �c �8 mm b IHP + �c �8 mm b IHP DCF �c b ITM 4C-6E
60 min. time programming. Lets you control starting and stopping of a group of loads according to a cycle that is repeated every 60 minutes.
24 h daily programming.Lets you control starting and stopping of one or two groups of loads according to a daily cycle that is repeated, in identical manner, every day of the week.
7 days weekly programming. Lets you control starting and stopping of one to 4 groups of loads according to a weekly cycle, that can be different each day, repeated each week.
�5UT00655_�2-2006_EN
Example b Automatic controlling of bells, lighting and distribution of food: bells sounding the resumption and finish of work (channel �), lighting of premises (channel 2), feeding fish in the aquarium (channel 3):
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Channel1:bell (20 s pulse order)
On 08 h 00 08 h 00 08 h 00 08 h 00 07 h 00 09 h 00
Duration 20 s 20 s 20 s 20 s 20 s 20 s
On �2 h 00 �2 h 00 �2 h 00 �2 h 00 �� h 00 �3 h 00
Duration 20 s 20 s 20 s 20 s 20 s 20 s
On �4 h 00 �4 h 00 �4 h 00 �4 h 00 �3 h 00
Duration 20 s 20 s 20 s 20 s 20 s
On �8 h 00 �8 h 00 �8 h 00 �8 h 00 �6 h 00
Duration 20 s 20 s 20 s 20 s 20 s
Channel2: lighting (latched order)
On 07 h 30 07 h 30 07 h 30 07 h 30 06 h 30 08 h 30
Off �8 h 30 �8 h 30 �8 h 30 �8 h 30 �7 h 00 �3 h 30
Channel3: aquarium (�5 s pulse order)
On �0 h 00 �0 h 00 �0 h 00 �0 h 00
Duration �5 s �5 s �5 s �5 s
Programming b Programming of a pulse takes up 2 memory spaces. b Combination of the two order types (pulse and latched) is possible on the same channel.
Relevanttimeswitchesb IHP + �c b IHP + �c �8 mm b IHP DCF �c b IHP + 2c b ITM 4C-6E
Example b Controlling lighting and heating in a school: v basic programming: program lighting (channel �) and heating (channel 2):
Monday Tuesday Wednesday Thursday Friday Saturday Sunday
Channel1:lighting
On 07 h 00 07 h 00 07 h 00 07 h 00 07 h 00
Off 20 h 00 20 h 00 �6 h 00 20 h 00 �6 h 00
Channel2:heating
On 06 h 00 06 h 00 06 h 00 06 h 00 06 h 00
Off �8 h 00 �8 h 00 �2 h 00 �8 h 00 �2 h 00
v dated programming: periods of non-operation, school holidays, etc.Just memorise an Off at the start and another Off at the end of each period of absence:
Holidays
Winter Spring Summer Autumn Endofyear
Channel1:lighting
Off Date 20 feb. �7-apr 07-july 23 oct. �8 dec.
Time �2 h 00 �7 h 00 �2 h 00 �7 h 00 �2 h 00
Off Date 08-march 03-may 9 sept. 2 nov. 4 jan.
Time 0� h 00 0� h 00 0� h 00 0� h 00 0� h 00
Channel2:heating
Off Date 20 feb. �7-apr 23 oct. �8 dec.
Time �2 h 00 �7 h 00 �7 h 00 �2 h 00
Off Date 08-march 03-may 2 nov. 4 jan.
Time 0� h 00 0� h 00 0� h 00 0� h 00
Relevanttimeswitchesb IHP �c annual b IHP 2c annual b ITM 4C-6E
Pulse programming.Lets you control by pulses (adjustable from 1 to 59 s) one to four groups of loads (pulse relays, bells, etc.).
Programming special days.Lets you create special programs for dated days.
�6
Time switches
UT00655_�2-2006_EN
Dimensions
�8�-070��94-0304
IHtimeswitches ANTDCFantenna
�83-070�
ITM4C-6E
5P (IHP �C/2C/+�C/+2C)*5P (IHP �C/2C/+�C/+2C)
IHPprogrammabletimeswitches
060-�0022P (�8 mm) 2P (�8 mm)5P �0P 5P, �0P
/ *
P93
586
P935832P (�8 mm) 2P (�8 mm)�2P �2P
IHtimeswitches(18mm)
P93
583
Schneider Electric Industries SAS89, boulevard Franklin RooseveltF-92506 Rueil-Malmaison CedexTel: +33 (0)1 41 29 85 00www.schneider-electric.com
As standards, specifications and designs change from time to time, please ask for confirmation of the information given in this publication.
Publishing: Schneider Electric Industries SASDesign:Printing:
This document has been printed on ecological paper
UT0
0655
_EN
© S
chne
ider
Ele
ctric
Indu
strie
s S
AS
All
right
s re
serv
ed
12-2006Art. xxxxx