rxm miniature relays
TRANSCRIPT
Data Bulletin
2014
Zelio™ Plug-In RelaysRXM miniature relays
3
Zelio™ Plug-In RelaysRXM miniature relays
Introduction
Introduction of the product range The RXM miniature relay range includes:1 12 A relays with 2 C/O contacts, 10 A relays with 3 C/O contacts, 6 A relays with
4 C/O contacts and 3 A “low level” relays with 4 C/O contacts. All these relays have the same dimensions.
2 Sockets with mixed or separate contact terminals.3 Protection modules (diode, RC circuit or varistor).4 Metal hold-down clip for all sockets.5 Plastic hold-down ejector clip for all sockets.6 2-pole bus jumper that can be used on sockets with separate contact terminals
in order to simplify wiring when creating a jumper between the coil terminals.7 Clip-in ID tags for all the sockets except RXZE2M114.
Relay description1 Spring return push-to-test button for checking contact operation (green: DC coil,
red: AC coil).2 Mechanical “relay status” indicator.3 Optional removable lock-down door enables continuous engagement of the
contacts for test or maintenance purposes. During normal operation, this lock-down door must always be in the closed position.
4 Bipolar LED indicating the relay status.5 Removable ID tag for relay identification.6 Four notches for DIN rail mounting adapter or panel mounting adapter with
mounting lugs.7 Eight, eleven or fourteen quick-connect pins.8 Finger grips for easy removal of the relay from a socket.9 Mounting adapter for direct mounting of the relay on a panel.10 Mounting adapter for direct mounting of the relay on a DIN rail.
Socket description Sockets with mixed contact terminals (1)
1 Connection by screw clamp terminals or box lug connector.2 Fourteen female contacts for the relay pins.3 Location for protection modules.4 Locking components for plastic and metal hold-down clips.5 Locating slot for mounting on DIN rail.6 Two or four mounting holes for panel mounting.
Sockets with separate contact terminals (2)1 Connection by screw connector.2 Connection by push-in spring clamp terminals. No tool is required to insert the
cable.3 Eight, eleven or fourteen female contacts for the relay pins.4 Location for protection modules.5 Locking components for plastic and metal hold-down clips. 6 Locating slot for mounting on DIN rail.7 Two mounting holes for panel mounting.8 Location for bus jumpers (see “Mounting on Sockets” section on
www.schneider-electric.com).9 Location for clip-in ID tag.
(1) The inputs are mixed with the relay coil terminals, with the outputs being located on the opposite side of the socket.
(2) The inputs and outputs are separated from the relay coil terminals.
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
9 9 10
2
6 9
17
3
45
6 8
Outputs
Inputs
Relay coil terminals6
1
2
3
4
5
Outputs
Inputs
Relay coil terminals
5
6
12
7
3
4
56
8
7
6
2
1
5
3
4
or
4
Zelio™ Plug-In RelaysRXM miniature relays
Specifications
General specificationsConforming to standards IEC/EN 61810-1, UL 508, CSA C22-2 n° 14Product certifications cULus File E164862 CCN NLDX, NLDX7; cURus File E164862 CCN NLDX2, NLDX8; CSA; CE; Lloyds
Register; GOST; RoHS compliantAmbient air temperature around the device
Storage °C (F) - 40… + 85 (-40... +185)Operation °C (F) - 40… + 55 (-40... +131)
Vibration resistanceconforming to IEC/EN 60068-2-6
In operation 3 gn (35...150 Hz), +/- 1 mm (10...35 Hz) with and without retention clipNot operating 5 gn (35...150 Hz), +/- 1 mm (10...35 Hz) with and without retention clip
Degree of protection Conforming to IEC/EN 60529
IP 40
Shock resistanceconforming to IEC/EN 60068-2-27
In operation 10 gn (11 ms) with retention clipNot operating 30 gn (11 ms) with retention clip
Protection category RT IMounting position Any
Insulation specificationsRated insulation voltage (Ui) V 250 (IEC), 300 (UL, CSA)Rated impulse withstand voltage (Uimp) kV 4 (1.2/50 ms) for RXM 2ppppp and RXM 3ppppp; 2.5 (1.2/50 ms) for RXM 4pppppDielectric strength(rms voltage)
Between coil/contact Vac 2000Between poles Vac 2000Between contacts Vac 1300
Contact specificationsRelay type RXM 2ABppp RXM 3ABppp RXM 4ABppp RXM 4GBppp
Number and type of contacts 2 C/O 3 C/O 4 C/O 4 C/O low levelContact materials Ag alloy with Au flash Ag with Au flash -
bifurcatedConventional thermal current (Ith)
For ambient temperature y 55 °C
A 12 10 6 3
Rated operational current in utilization categories AC-1 and DC-1
Conforming to IEC
N.O. 12 10 6 2N.C. 6 5 3 1
Switching current Minimum mA 10 3Switching voltage Maximum V 250 Vac / 28 Vdc (IEC); 300 Vac / 30 Vdc (UL)
Minimum V 17 Vdc 5 VdcNominal load (conforming to IEC, resistive, 100K cycles)
A 12 at 250 Vac (100K cycles) 10 at 250 Vac (100K cycles) 6 at 250 Vac (100K cycles) 3 at 250 Vac (100K cycles)(1)
A 12 at 28 Vdc (100K cycles) 10 at 28 Vdc (100K cycles) 6 at 28 Vdc (100K cycles) 3 at 28 Vdc (100K cycles)(1)
Rated operational current (conforming to UL)
Resistive A 12 at 277 Vac (100K cycles) 10 at 277 Vac (100K cycles) 6 at 277 Vac (200K cycles) 3 at 277 Vac (100K cycles)(1)A 12 at 120 Vac (200K cycles) 10 at 120 Vac (200K cycles) 8 at 120 Vac (200K cycles) 3 at 120 Vdc (100K cycles)(1)A 12 at 30 Vdc (100K cycles) 10 at 30 Vdc (100K cycles) 8 at 30 Vdc (200K cycles) 3 at 30 Vdc (100K cycles)(1)
Motor hp 1/2 at 120 Vac (6K cycles) 1/3 at 120 Vac (6K cycles) 1/3 at 120 Vac (6K cycles) 1/16 at 120 Vac (6K cycles)(1)hp 1 at 277 Vac (6K cycles) 1 at 277 Vac (6K cycles) 1/2 at 277 Vac (6K cycles) 2.8 A FLA at 120 Vac
Pilot Duty B300 B300 B300 5 A make, 0.5 A break, 3A continuous at 120 Vac(1)
Switching capacity Maximum AC VA 3000 2500 1500 750DC W 336 280 168 84
Minimum mW 170 15Maximum operating rateIn operating cycles per hour
No-load 18 000Under load 1200
Utilization coefficient 20 %Mechanical durability Cycles 10 000 000(1) When mounted horizontally
Electrical durability of contactsResistive load (AC)
Reduction coefficient for inductive load (AC) (depending on power factor cos j)
Maximum switching capacity on resistive load (DC)
A RXM 2ABppp B RXM 3ABppp C RXM 4ABppp D RXM 4GBppp Durability (inductive load) = durability (resistive load) x reduction coefficient.
105
106
107
2 30 1
A BDC
Dur
abili
ty (N
umbe
r of o
pera
ting
cycl
es)
Switching capacity (kVA)
0,3
0,5
0,61 0,4 0,2
0,4
0,60,81
Red
uctio
n co
effic
ient
(A)
0,1
1
200 2500 5028 100 150
10
3
6
CDBA
Cur
rent
c
Voltage (Vdc)
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
5
Zelio™ Plug-In RelaysRXM miniature relays
Specifications (continued)
Coil specificationsAverage consumption AC VA 0.9–1.2
DC W 0.8–1.1Drop-out voltage threshold AC u 0.15 Uc
DC u 0.1 UcOperating time(response time)
Between coil energization and making of the On-delay contact
AC ms 20 (max.)DC ms 20 (max.)
Between coil de-energization and making of the Off-delay contact
AC ms 20 (max.)DC ms 20 (max.)
Control circuit voltage Uc V 12 24 48 110 120 125 220 230 240Relay control voltage codes JD BD ED FD – GD MD – –
DC supply Average resistance at 20 °C ± 10% W 160 650 2560 13 440 – 17 360 48 400 – –Operating voltage limits Min. Vac 9.6 19.2 38.4 88 – 100 176 – –
Max. Vac 13.2 26.4 52.8 121 – 138 242 – –Relay control voltage codes – B7 E7 F7 – – P7 U7
AC supply Average resistance at 20 °C ± 15% W – 177 708 – 3630 – – 16 270 17 720Operating voltage limits Min. Vdc – 19.2 38.4 – 96 – – 184 192
Max. Vdc – 26.4 52.8 – 132 – – 253 264
Socket specificationsSocket type RXZE2S108M RXZE2S111M RXZE2S114M RXZE2S114S RXZE2M114M RXZE2M114Relay types used RXM2ppppp RXM3ppppp RXM4ppppp RXM2ppppp
RXM4pppppRXM2ppppp (1)RXM4ppppp
RXM2ppppp (1)RXM4ppppp
Contact terminal arrangement Separate MixedWire connection method Box lug connectors Spring clamp
terminalsBox lug connectors Screw clamp
terminalsProduct certifications cURus File E172326 CCN SWIV2, SWIV8; CSA; CE; GOST; Lloyds; RoHS compliantConforming to standards IEC 61984, UL 508, CSA 22.2 No. 14
Electrical specificationsConventional thermal current (Ith) A 12 10 12 (2-Pole),
6 (4-Pole)10
Maximum operating voltage Vac 250 (IEC)
Insulation specificationsBetween adjacent output contacts Vrms 2500Between input and output contacts Vrms 2500Between contacts and DIN rail Vrms 2500
General specificationsAmbient air temperaturearound the device
Operation °C (°F) - 40…+ 40 (- 40…+ 104)Storage °C (°F) - 40…+ 85 (- 40…+ 185)
Degree of protection Conforming to IEC/EN 60529
IP 20
Connection Solid wire without cable end
1 conductor 0.5…2.5 mm2 - AWG 20…AWG 14 0.5…1.5 mm2 AWG 20…AWG 16
0.5…2.5 mm2 AWG 20…AWG 14
0.5… 1.5 mm2 AWG 20…AWG 16
2 conductors 0.5…1.5 mm2 - AWG 20…AWG 16Flexible wire with cable end
1 conductor 0.25…2.5 mm2 - AWG 22…AWG 14 0.5…1.5 mm2 AWG 20…AWG 16
0.25…2.5 mm2 AWG 22…AWG 14
0.25…1 mm2
AWG 22…AWG 172 conductors 0.25…1 mm2 - AWG 22…AWG 17 0.5…1.5 mm2
AWG 20…AWG 160.25…1 mm2 - AWG 22…AWG 17
Maximum tightening torque / Screw size Nm 1 / M3 screwMounting On 35 mm DIN rail / on panelMounting on DIN rail By plastic clip By metal
compression spring
By plastic clip
Terminal referencing IEC, NEMABus jumper (Ith: 5 A) Yes NoCompatibility with the plastic hold-down ejector clip
Yes
Compatibility with the metal hold-down clip YesProtection module compatibility All RXM040W, RXM041pp, RXM021pp
Clip-in ID tag compatibility Yes (see page 6 for more information) NoWire connection method Screw connector Spring clamp
terminalsScrew connector Screw clamp
terminals
(1) When mounting relay RXM2ppppp on socket RXZE2Mpppp, the thermal current must not exceed 10A.
(1) (2)
mmin.
mmin.
9 ~ 110.35 ~ 0.43
2.5
0.09
8
F
F
1 2
1 2 3 4
F
F F
F
F
F
6
Zelio™ Plug-In RelaysRXM miniature relays
References
Miniature relays with lockable test button only (sold in lots of 10) Control circuit voltage
Number and type of contacts - Thermal current (Ith)2 C/O - 12 A 3 C/O - 10 A 4 C/O - 6 AUnit reference
Weight Unit reference
Weight Unit reference
Weight
V kg (lb) kg (lb) kg (lb)12 Vdc RXM2AB1JD 0.037 (0.082) RXM3AB1JD 0.037 (0.082) RXM4AB1JD 0.037 (0.082)24 Vdc RXM2AB1BD 0.037 (0.082) RXM3AB1BD 0.037 (0.082) RXM4AB1BD 0.037 (0.082)48 Vdc RXM2AB1ED 0.037 (0.082) RXM3AB1ED 0.037 (0.082) RXM4AB1ED 0.037 (0.082)110 Vdc RXM2AB1FD 0.037 (0.082) RXM3AB1FD 0.037 (0.082) RXM4AB1FD 0.037 (0.082)220 Vdc – – – – RXM4AB1MD 0.037 (0.082)
24 Vac RXM2AB1B7 0.037 (0.082) RXM3AB1B7 0.037 (0.082) RXM4AB1B7 0.037 (0.082)48 Vac RXM2AB1E7 0.037 (0.082) RXM3AB1E7 0.037 (0.082) RXM4AB1E7 0.037 (0.082)120 Vac RXM2AB1F7 0.037 (0.082) RXM3AB1F7 0.037 (0.082) RXM4AB1F7 0.037 (0.082)230 Vac RXM2AB1P7 0.037 (0.082) RXM3AB1P7 0.037 (0.082) RXM4AB1P7 0.037 (0.082)240 Vac – – – – RXM4AB1U7 0.037 (0.082)
Miniature relays with LED and lockable test button (sold in lots of 10) 12 Vdc RXM2AB2JD 0.037 (0.082) RXM3AB2JD 0.037 (0.082) RXM4AB2JD 0.037 (0.082)24 Vdc RXM2AB2BD 0.037 (0.082) RXM3AB2BD 0.037 (0.082) RXM4AB2BD 0.037 (0.082)48 Vdc RXM2AB2ED 0.037 (0.082) RXM3AB2ED 0.037 (0.082) RXM4AB2ED 0.037 (0.082)110 Vdc RXM2AB2FD 0.037 (0.082) RXM3AB2FD 0.037 (0.082) RXM4AB2FD 0.037 (0.082)125 Vdc – – – – RXM4AB2GD 0.037 (0.082)
24 Vac RXM2AB2B7 0.037 (0.082) RXM3AB2B7 0.037 (0.082) RXM4AB2B7 0.037 (0.082)48 Vac RXM2AB2E7 0.037 (0.082) RXM3AB2E7 0.037 (0.082) RXM4AB2E7 0.037 (0.082)120 Vac RXM2AB2F7 0.037 (0.082) RXM3AB2F7 0.037 (0.082) RXM4AB2F7 0.037 (0.082)230 Vac RXM2AB2P7 0.037 (0.082) RXM3AB2P7 0.037 (0.082) RXM4AB2P7 0.037 (0.082)
Miniature relays with LED only (sold in lots of 10) 12 Vdc RXM2AB3JD 0.037 (0.082) – – RXM4AB3JD 0.037 (0.082)24 Vdc RXM2AB3BD 0.037 (0.082) – – RXM4AB3BD 0.037 (0.082)110 Vdc RXM2AB3FD 0.037 (0.082) – – RXM4AB3FD 0.037 (0.082)125 Vdc – – – – RXM4AB3GD 0.037 (0.082)
24 Vac RXM2AB3B7 0.037 (0.082) – – RXM4AB3B7 0.037 (0.082)48 Vac RXM2AB3E7 0.037 (0.082) – – RXM4AB3E7 0.037 (0.082)120 Vac RXM2AB3F7 0.037 (0.082) – – RXM4AB3F7 0.037 (0.082)230 Vac RXM2AB3P7 0.037 (0.082) – – RXM4AB3P7 0.037 (0.082)
RXM4AB1BD
RXM4AB1F7
RXM4AB2BD
RXM4AB2F7
RXM2AB3F7
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
7
Zelio™ Plug-In RelaysRXM miniature relays
References (continued)
Miniature relays with low level contacts, lockable test button only (sold in lots of 10) Control circuit voltage
Number and type of contacts Thermal current (Ith)4 C/O - 3 AUnit reference
Weight
V kg (lb)12 Vdc RXM4GB1JD 0.037 (0.082)24 Vdc RXM4GB1BD 0.037 (0.082)48 Vdc RXM4GB1ED 0.037 (0.082)110 Vdc RXM4GB1FD 0.037 (0.082)
24 Vac RXM4GB1B7 0.037 (0.082)48 Vac RXM4GB1E7 0.037 (0.082)120 Vac RXM4GB1F7 0.037 (0.082)230 Vac RXM4GB1P7 0.037 (0.082)
Miniature relays with low level contacts, with LED and lockable test button (sold in lots of 10) 12 Vdc RXM4GB2JD 0.037 (0.082)24 Vdc RXM4GB2BD 0.037 (0.082)48 Vdc RXM4GB2ED 0.037 (0.082)110 Vdc RXM4GB2FD 0.037 (0.082)
24 Vac RXM4GB2B7 0.037 (0.082)48 Vac RXM4GB2E7 0.037 (0.082)120 Vac RXM4GB2F7 0.037 (0.082)230 Vac RXM4GB2P7 0.037 (0.082)240 Vac RXM4GB2U7 0.037 (0.082)
Miniature relays with low level contacts, with LED only (sold in lots of 10) 12 Vdc RXM4GB3JD 0.037 (0.082)24 Vdc RXM4GB3BD 0.037 (0.082)48 Vdc RXM4GB3ED 0.037 (0.082)110 Vdc RXM4GB3FD 0.037 (0.082)
24 Vac RXM4GB3B7 0.037 (0.082)48 Vac RXM4GB3E7 0.037 (0.082)120 Vac RXM4GB3F7 0.037 (0.082)230 Vac RXM4GB3P7 0.037 (0.082)
RXM4GB1BD
RXM4GB2BD
RXM4GB3F7
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
8
Zelio™ Plug-In RelaysRXM miniature relays
References (continued)
SocketsContact terminal arrangement
Connection Relay type Sold in lots of
Unit reference
Weightkg (lb)
Mixed Screw clamp terminals RXM2pppp (3)RXM4pppp
10 RXZE2M114 (1) 0.048 (0.106)
Screw connector RXM2pppp (3)RXM4pppp
10 RXZE2M114M (1) 0.056 (0.124)
Separate Spring clamp terminals RXM2pppp (3)RXM4pppp
10 RXZE2S114S (2) 0.070 (0.154)
Box lug connector RXM2pppp 10 RXZE2S108M (2) 0.058 (0.128)RXM3pppp 10 RXZE2S111M (1) 0.066 (0.146)RXM4pppp 10 RXZE2S114M (1) 0.070 (0.154)
Protection modulesDescription Voltage For
use withSold in lots of
Unit reference
Weight
V kg (lb)Diode 6...250 Vdc All sockets 20 RXM040W 0.003 (0.007)
RC circuit 24...60 Vac All sockets 20 RXM041BN7 0.010 (0.022)110...240 Vac All sockets 20 RXM041FU7 0.010 (0.022)
Varistor 6...24 Vac / Vdc All sockets 20 RXM021RB 0.003 (0.007)24...60 Vac / Vdc All sockets 20 RXM021BN 0.003 (0.007)110...240 Vac / Vdc All sockets 20 RXM021FP 0.003 (0.007)
Timing relaysDescription For
use withUnit reference
2 or 4 timed C/O contacts Sockets RXZEppppp REXL2pp (4) REXL4pp (4)
AccessoriesDescription For
use withSold in lots of
Unit reference
Weightkg (lb)
Metal hold-down clip All sockets 10 RXZ400 0.001 (0.002)Plastic hold-down ejector clip All sockets 10 RXZR335 0.005 (0.011)Bus jumper 2-pole (Ith: 5 A) All sockets with separate contacts 10 RXZS2 0.005 (0.011)
Mounting adapter for DIN rails (5)
All relays 10 RXZE2DA 0.004 (0.009)
Mounting adapter with mounting lugs for panel
All relays 10 RXZE2FA 0.002 (0.004)
Clip-in ID tags All relays (sheet of 108 legends) 10 RXZL520 0.080 (0.176)All sockets except RXZE2M114 and RXZE2S114S 10 RXZL420 0.001 (0.002)RXZE2S114S socket 10 RSZL300 0.001 (0.002)
(1) Thermal current Ith: 10A(2) Thermal current Ith: 12A(3) When mounting relay RXM2ppppp on socket RXZE2Mpppp, the thermal current must not exceed 10A. (4) Please consult the "Zelio Time timing relays" catalog.(5) Test button becomes inaccessible if used with DIN rail mounting adapter or panel mounting adapter and terminals face the user.
RXZ400
RXM041pp7
RXZE2M114M + Relay RXM4AB1F7
REXL4pp
9
Zelio™ Plug-In RelaysRXM miniature relays
Dimensions
DimensionsMiniature relaysRXMpppppp RXM2 RXM3 RXM4
Common view Pin side view
SocketsRXZE2M114 RXZE2M114M
Common side view RXZE2S108M RXZE2S111M RXZE2S114M
(1) Relays(2) Protection module(3) Metal hold-down clip(4) 2 elongated holes Ø 3.5 x 6.5(5) 2 bus jumpers
(1)
(2)(3)
25.51.00
347
A214
A113
246
448
145
12
1
11
9
21
10
31
11
41
12
22
2
32
3
42
4
(4)19
0.75
401.58
301.18
90.3523
0.91
210.8330
1.18692.72
70.28
39.5
1.56
61 2.40
3.5
0.14
79 3.11
(4)
mmin.
3.50.14
170.67
431.69
23.50.93
501.97 27
1.0667
2.64
40 1.58
80 3.15
448
347
246
145
424
323
222
121
A1
13
A2
1441
12
31
11
21
10
11
9
(3)
(1)
(2)
mmin.
70.28
3.50.14
190.75
612.40
291.14
230.91 70
2.767
0.28
3.5
0.14
79 3.11
(3) (2)
(1)
(5)
mmin.
23.50.9327
1.06
38 1.50
4112
119
448
145
A113
A214
424
121
3.50.14
319
346
A1
13
A2
14
323
218
245
222
117
144
121
23.50.9327
1.06
38 1.50
3.50.14
23.50.9327
1.06
38 1.50
3.50.14
4112
3111
2110
119
448
347
246
145
42
4
32
3
22
2
12
1
A1
13
A2
14
401.58
210.83
27 1.06
90.35
60.24
2.50.10
2.50.10
21
6.3
0.25
6.3
0.25
4.2
0.17
4.2
0.17
13.20.52
2.50.10
2.50.10
4.40.17
21
13.20.52
6.60.26
6.60.26
2.50.10
2.50.1013.2
0.52
4.40.17
4.40.17
4.40.17
mmin.
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
10
mmin.
311.22
94 3.70
281.10
(4)
(1)
(2)
(3)
98 3.86
522.05
702.76
803.15
Dimensions (continued)Sockets (continued)RXZE2S114S Socket only RXZE2S114S Socket with RXM relay and retention clip
(1) Relay(2) Protection module(3) Metal retention clip(4) I.D. tag
RXZE2S114S Socket with RXM relay and ejector clip
(1) Relay(2) Protection module(3) Ejector clip(4) I.D. tag
Zelio™ Plug-In RelaysRXM miniature relays
Dimensions (continued)
mmin.
311.22
94 3.70
281.10
(4)
(1)
(2)
(3)
98 3.86
522.05
702.76
762.99
35.51.40mm
in.29.51.16
23.50.93
311.2222
0.877.5
0.30
94 3.70 90 3.
54
15 0.59
28 1.10
48 1.89
1.2
0.05
Plastic ejector clip RXZR335 Metal retention clip RXZ400 ID tag RSZL300
572.24
27 1.06
8.0
0.3
14.50.6
7.20.3
22 0.87
421.65
0.80.03
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
11
Zelio™ Plug-In RelaysRXM miniature relays
Dimensions (continued)
Dimensions (continued)Plastic hold-down clip and clip-in ID tagsRXZR335 RXZL420 Mounting on all sockets (1)
(1) Clip-in ID tags for all sockets except RXZE2M114
Bus jumper Metal hold-down clipRXZS2 Mounting on sockets with separate contacts
(view from below)RXZ400
Example of bus jumper mounting on sockets
(1) 2 bus jumpers (polarity A2)(2) 2 bus jumpers (polarity A1)
Mounting adapter for rails (1) Mounting adapter for panelRXZE2DA RXZE2FA
(1) Test button becomes inaccessible
572.24
27 1.06
12
14,2
26,5
81
94,5
(1)
2,2 7,
3
25
22
2,3(1)(1)
(2)(2)
22 0.87
421.65
0.80.03
38
6 424
348
23
51
48 49
3,5
43 38
4
24
3,5
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
12
Wiring diagramsMiniature relaysRXM2ppppp RXM3ppppp RXM4ppppp
Symbols shown in black correspond to IEC markings; blue correspond to NEMA markings.
Sockets RXZE2M114 RXZE2M114M RXZE2S108M
347
14A2 A1
13
246
844 14
5
1
119
2110
3111
4112
2312223242
4
448
347
246
145
12312223242
4
14A2 A1
13
14 13
1021
9
9
5
1
111131
1241
1241 11
9
844 14
5
A1
13
A2
A1A214
424
121
INPUT
Symbols shown in black correspond to IEC markings; blue correspond to NEMA markings.RXZE2S111M RXZE2S114M RXZE2S114S
A1
13
A2
A1A214
319
346
3
218
245
2
117
144
32 22 121
INPUT
A1
13
A2
A1A214
4112
3111
2110
119
448
347
246
145
424
323
222
121
INPUT
Symbols shown in black correspond to IEC markings; blue correspond to NEMA markings.Protection modules RXM040W RXM041ppp RXM021ppp
– A2
+ A1
– A2
+ A1
– A2
+ A1
A2
A1
414442
111412
1
125
149
11
4
428
4412
4113
A1
14
A2
A2
A1
313432
212422
111412
1
12
4
147
11
2
22
5
248
21
3
32
6
349
3113
A1
14
A2
A2
A1
414442
212422
313432
111412
1
125
149
11
4
428
4412
41
2
226
2410
21
3
327
3411
3113
A1
14
A2
Zelio™ Plug-In RelaysRXM miniature relays
Wiring diagrams
4112
424
448
3111
323
347
2110
222
246
119
14 13
12
A2 A1
A2 A1
14 13
1
145
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
13
Wiring instructions for RXZE2S114S socketRecommended wire strip length Recommended removal tool: flat blade,
parallel tipOpenings for wiring and removal tool
(1) Wiring opening(2) Removal tool opening
Wiring insertion Wiring removal
Recommended wiring for RXZE2S114S socketFlexible wiring with cable end
1 wire 0.5 to 1.5 mm2 – 20 to 16 AWG
2 wires 0.5 to 1.5 mm2 – 20 to 16 AWG
Solid wiring without cable end
1 wire 0.5 to 1.5 mm2 – 20 to 16 AWG
2 wires 0.5 to 1.5 mm2 – 20 to 16 AWGNote: Allow only one wire per terminal opening
(1) (2)
mmin.
mmin.
9 ~ 110.35 ~ 0.43
2.5
0.09
8
F
F
1 2
1 2 3 4
F
F F
F
F
F
(1) (2)
mmin.
mmin.
9 ~ 110.35 ~ 0.43
2.5
0.09
8
F
F
1 2
1 2 3 4
F
F F
F
F
F
(1) (2)
mmin.
mmin.
9 ~ 110.35 ~ 0.43
2.5
0.09
8
F
F
1 2
1 2 3 4
F
F F
F
F
F
(1) (2)
mmin.
mmin.
9 ~ 110.35 ~ 0.43
2.5
0.09
8
F
F
1 2
1 2 3 4
F
F F
F
F
F
(1) (2)
mmin.
mmin.
9 ~ 110.35 ~ 0.43
2.5
0.09
8
F
F
1 2
1 2 3 4
F
F F
F
F
F
1 Wiring (cable) terminal opening2 Removal tool opening
12
35.51.40mm
in.29.51.16
23.50.93
311.2222
0.877.5
0.30
94 3.70 90 3.
54
15 0.59
28 1.10
48 1.89
1.2
0.05
Zelio™ Plug-In RelaysRXM miniature relays
Wiring instructions for RXZE2S114S socket
Introduction:page 2
Specifications page 4
References:page 6
Dimensions:page 9
Wiring:page 12
The information and dimensions in this catalog are provided for the convenience of our customers. While this information is believed to be accurate, Schneider Electric reserves the right to make updates and changes without prior notification and assumes no liability for any errors or omissions.
Zelio, Schneider Electric and logo, and “Make the most of your energy” are trademarks or registered trademarks of Schneider Electric or its affiliates in the United States and other countries. Other trademarks used herein are the property of their respective owners.
Design: Schneider ElectricPhotos: Schneider Electric
© 2013–2014 Schneider Electric. All rights reserved. 5/20148501DB1301
www.schneider-electric.comSchneider Electric USA, Inc.8001 Knightdale Blvd. Knightdale, NC 27545
USA Customer Care CenterTel: 888-778-2733
Schneider Electric Canada5985 McLaughlin Rd.Missassauga, Ontario, Canada L5R 1B8
Canada Customer Care CenterTel: 800-565-6699