A well designed office space requires an advanced energy-efficient design and highly controllable lighting. This application illustrates how offices can take advantage of strategies such as daylighting, Manual On/Automatic Off to achieve energy savings up to 52% and achieve higher quality lighting. Providing control of emergency lighting, as well as, personal dimming levels gives employees more flexibility and control over their workspace.
The Room Controller QuicKit is shipped preconfigured to work out-of-the-box minimizing installation and setup time, while ensuring maximum energy savings. Using this design guide to specify your room with a Room Controller QuicKit catalog number will guarantee that after installation the lighting control system will work immediately as defined on this application guide.
Summary
Room Controller - Private Office w/Daylight Dimming and Receptacle Control
room Controller Sample room layout (10ʹ x 10ʹ)
SPRC-R-20-120(20A Receptacle Control)
Line Voltageto J-Box
OAWC-DT-120W(Wall Corner Occupancy Sensor)
DSRC-FMOIR(Multi-zone Daylight Sensor)
Normal PowerConnection
Emergency PowerConnection
Load 1
RC-SS1(Slider)
RC-3TLB-OS1-*(Pre-engraved Wallstation)
RC3DE(3 Relay + 3 Dimmer + 1 Emergency Relay)
OCC-RJ45(Connection to any Greengate sensor)
RC3DE
EM Load
Dimmer 2
Load 1
Dimmer 1
Load 2Dimmer 3
Half lights
Full lights
All Off
Room Controller QuicKitRCQK-OS3E-OS1-SS1-W1-D1-P-W
• Manual On/Automatic Off or Automatic On (50%)/Automatic Off
• Automatic multi-zone daylight dimming out-of-the-box
• Receptacle control based on occupancy
• Emergency UL 924 control (tracks with relay 1)
• Automatic Demand Response 10%-40% reduction based on input
• High-end trim/tuning to define target light levels
• Providing users with wall-based dimming controls to adjust the lighting levels to meet their needs
Control SequenCe
RC-3TLB-OS1 RC-SS1(Dimmer Raise/Lower)
Product Legend
Qty1: RC3DE3 Relay + 3 DimmeR + 1 emeRgenCy Relay
Qty1: RC-3tLB-OS1-WHalf ligHts, full ligHts, all off
qty:1 rC-SS1-W White Slider
qty1: dSrC-FmoirDayligHt sensoR
qty1: oaWC-dt-120WWall CoRneR vaCanCy sensoR
qty1: oCC-rJ45oCCupanCy sensoR RJ45 ConneCtoR
qty1: SprC-r-20-120ReCeptaCle ContRol
qty2: GGrJ45-10-GQuiCkConneCt Cable 10’
qty3: GGrJ45-25-GQuiCkConneCt Cable 25’
SingLE BOx PaCKaging With WiRing DEtaiL anD inStaLLatiOn
reCeSSed Fixture
For Guaranteed Compatibility reFer to preFerred Cooper liGhtinG Fixture inFormation beloW.
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half lights
Full lights
All Off
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half Lights
All Off
Full Lights
Raise
Lower
RC3DE
Entry Lighting
All Off
RC3D
General
Exam
Reading
All Off
cc
TV
1 2 3
4 5 67 8 9
PREV 0
1 3ALLON/OFF
2
MUTE
SLEEP OPTION
CHANNEL VOLUME
General
Whiteboard
Quiet Time •
A/V Mode
Raise
Lower
Half lights
Full lights
All Off
1. Preset - Load 1 On & 50% Dimmers
2. Preset - Load 1, 2, 3 On & 100% Dimmers
3. All Loads Off
inteGrated CapabilitieS Cooper liGhtinG Guaranteed Compatible FixtureS
UL924
Emergency
UL924
DemandResponse
Refer to these Cooper Lighting data sheets for lighting layouts and illuminance value information.
UL924
ReceptacleControl
UL924
DaylightingControl
UL924
Occupancy/VacancySensing
UL924
ManualControl
UL924
Integration
Metalux LED Room Controller Office Lighting Layouts
Metalux LFL Room Controller Office Lighting Layouts
Corelite LED Room Controller OfficeLighting Layouts
Corelite LFL Room Controller Office Lighting Layouts
www.coopercontrol.com
2
The RC3DE will automtically recognize any smart device connected with the quick connect cable (provided) and start working immediately upon power up with no programming required. The RC3DE defaults to Manual On/Automatic Off vacancy sensor mode for maximum energy savings. Office wallstations will provide On/Off/Preset/Raise/Lower control of the lighting loads and dimmers.
The daylight sensor will automatically provide multi-zone daylight dimming in the space. (Remote adjustments can be made later.)
*Refer to Room Controller website for more information on other integral no programming required benefits like Demand Response, Egress Control, BMS Output, Alert Mode, Emergency Lighting Control, and Slider Stations.
room Controller and Smart deviCeS uSe CliCk & Go teChnoloGy
QuickConnect coupler (GGRC-COUPLER)
Adjustable daylight sensor dome
Daylight sensor(DSRC-FMOIR)
(OCC-RJ45)
Dual TechnologyWall Corner Occupancy/Vacancy Sensor(OAWC-DT-120W)
Allows connection to any Greengate Occupancy/Vacancy Sensor
BLACK - Hot(120/277 VAC)
WHT/ORG or WHT/BLKNeutral
BLUE - Relay In(120/277 VAC)
Lighting Load (1)
Lighting Load (2)
Lighting Load (3)
YELLOW
RED
Violet - Dimmer 3
Requires 0-10V dimming ballasts
Quick connect cables are pre-terminated and included in the Room Controller QuicKit and measured to fit typical room layouts
Gray - Dimmer 3
Gray - Dimmer 2Violet - Dimmer 2
0-10V Dimming Zone Note: The 0-10V dimming zones within the Room Controller can be wired and controlled independent of the connected loads. This allows a each load to have a dedicated 0-10V dimming zone or a single load to have up to three 0-10V dimming zones.
Cooper Controls 203 Cooper Circle Peachtree City, GA 30269. USA
Tel: +1-800-553-3879 Fax: +1-800-954-7016 Email: [email protected]: www.coopercontrol.com
Room Controller - RC3DEThree Relay + Three Dimmers + 1 Emergency Relay Wiring Diagram
Drawing Name: RC3DE-OfficeSliderReceptacle.dwg
PURPLE
Drawing Date: 2/20/2013
*Immediately provides multi-zone daylight dimming upon powerup
*Defaults to vacancy sensor mode Manual On/Automatic Off (all loads) for maximum energy savings
Away from window
Near window
Undercabinet
SPRC-R-20-12020A Receptacle Control
Receptacle Control:20Amp 120 VAC receptacle control immediately works upon power up and connection to the Room Controller.Receptacle turns On by button press or occupancy and Off when space is vacant.
120V receptacle circuit
Emergency Note: Emergency load tracks with normal lighting YELLOW load for On/OFF. If dimming it will be adjusted with the dimming zone it is connected to. Upon loss of normal power to the RC3DE, the emergency load will be forced On and full bright to 100%.
In room ladderless testing is done by pressing the "All Off" button four times, within 3 seconds.
The RC3DE is UL 924 listed.
EMERGENCY NEUTRALEmergency Lighting Load(Tracks with normal lighting YELLOW load)
YELLOWEmergency Power OUT
BLUE - Emergency Power In(120/277 VAC)
Violet - Dimmer 1Gray - Dimmer 1
Button 2: Load (1), (2), (3) On & 100% dimmersAll Off
RC-2TLB-OS1-*Office Station
Full Lights
Half Lights
Button 1: Load (1) On & 50% dimmers
Button 3: Load (1), (2), (3) Off
Slider: Raise and Lowers dimming zones
RC-SS1-*Slider Station
Room Controller - Private Office w/Daylight Dimming and Receptacle Control
www.coopercontrol.com
3
mountinG the room Controller
WirinG diaGram
ConneCtionS
daylight Sensor Ceiling location1. Mount the daylight sensor one to two times the
window height from the window wall.2. Position the sensor so its arrow is pointed toward
the nearest window.3. Ensure the daylight sensor is not obstructed or
looking directly at electric light.4. For narrow spaces mount the daylight sensor near
the window facing into the space.
Sample placement diagram(for example purposes only)
room Controller 0-10v dimming ConnectionsDimmer 1: Near the WindowDimmer 2: Middle of RoomDimmer 3: Far from Window
The daylight sensor will automatically provide multi-zone dimming based on this wiring configuration
room Controller and Smart devices use Click & Go Connections1. Wallstations (up to four)2. Slider Station Connection (one)3. Occupancy Sensors (up to two)4. Daylight Sensor (one)5. Receptacle Control or BMS Output6. Switchpack (controlled with Load 1 for
alternate voltage)
60°
Area viewed bydaylight sensor
DaylightSensor
General On
Raise
Lower
Whiteboard
Quiet Time
AV Mode
General On
Off
Entry Wallstation
Room Controller(above entry door)Additional
Wallstation
Wall/Corner Mount Occupancy Sensor
Win
dow
Sample Placement Diagram(for example purposes only)
The Room Controller mounts above the ceiling in the space it is controlling, typically above the door to the room. The Room Controller include breakouts for direct conduit connection limiting the need for additional junction boxes. Mount the Room Controller using the keyhole slots at the top and secure to the wall using the holes at the bottom of the Room Controller.
Connect conduit to the line voltage breakout connections and connect the line and load wires. Connect low voltage cables either through the low voltage breakout openings or by connecting low voltage conduit to the breakouts on the low voltage side of the Room Controller.
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
Maximum coverage area mayvary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and roboticmethod were utilized to verify
coverage patterns.
24’ (7.3 mm)
Minor Motion, IR
Major Motion, IR
20’ (6 mm)
8’ (2.4 mm)
8’ (2.4 mm)
24’ (7.3 mm)
20’ (6 mm)
0
10 ft(3 mm)
12’ (3.7 mm)
12’ (3.7 mm)
6 ft(1.7 mm)
15 ft(4.6 mm)
24 ft(7.3 mm)
50 ft(15.3 mm)
Minor Motion, Ultrasonic
Major Motion, Ultrasonic
Maximum coverage area mayvary somewhat according to room
shape and the presence of obstacles.
The NEMA WD 7 Guide and roboticmethod were utilized to verify
coverage patterns.
24’ (7.3 mm)
Minor Motion, IR
Major Motion, IR
20’ (6 mm)
8’ (2.4 mm)
8’ (2.4 mm)
24’ (7.3 mm)
20’ (6 mm)
0
10 ft(3 mm)
12’ (3.7 mm)
12’ (3.7 mm)
6 ft(1.7 mm)
15 ft(4.6 mm)
24 ft(7.3 mm)
50 ft(15.3 mm)
Dimmer 3 Dimmer 2 Dimmer 1+ - -+ + -
0-10V Dimming
0-10V Violet (+)0-10V Gray (-)
4325 6
1
Half Lights
All Off
Line Voltageto J-Box
(Any GreengateOccupancy Sensor)
DSRC-FMOIR(Multi-zone
daylight sensor)
Wallstation(Entry)
Full Lights
Raise
Lower
Room Controller(Above Entry Door)
OCC-RJ45
Lower
Raise
Full Lights
Wallstation(Additional)
All Off
Half Lights
SPRC-R-20-120(20A Receptacle Control)
Line Voltageto receptacles
Normal Power(Line In & Load Out)
Emergency Power(Line In & Load Out)
RC3DE model only
0-10V Dimmer Wiring(Dimming Models Only)
(low voltage, class 2)RC3DE
Room Controller - Private Office w/Daylight Dimming & Receptacle Control
oCCupanCy SenSor CoveraGe diaGram (oaWC-dt-120W)
www.coopercontrol.com
4
orderinG
appliCationS
rC-3tlb-oS1 rC-5tSb-oS2 rC-6tSb-oS3 rC-2tlb-oS4 rC-6tSb-Cr1
room ControllerQuicKit
types of Space and ControlOS - Office Switching (RC3)
OS2 - Office 2 Zone Dimming (RC3D2)
OS3 - Office 3 Zone Dimming (RC3D)
OS3E - Office 3 Zone Dimming and
and Emergency Relay (RC3DE)
occupancy SensorC1 - Ceiling DT 2000 sq. ft.
C2 - Ceiling PIR 1500 sq. ft.
C3 - Ceiling DT 1000 sq. ft.
W1 - Wall Corner DT
W2 - Wall Corner PIR
W3 - Hallway PIR
daylightD1 - Multi-zone Daylight Sensor
DH - Multi-zone Daylight Sensor w/
Handheld Remote
optionsP - Plug Load
B - BMS/Egress
Station ColorW - White
G - Gray
V - Ivory
B - Blackoffice Stations (Choose up to 4)OS1 - Half Lights, Full Lights, All Off
(3 Large Buttons)
OS2 - Half Lights, Full Lights, Raise, Lower, All Off †
(5 Small Buttons)
OS3 - Half Lights, Full Lights, Under Cabinet, Raise, Lower, All Off †
(6 Small Buttons)
OS4 - All On, All Off (2 Large Buttons)
CR1 - General, Meeting, Whiteboard, Presentation, Raise, Lower
(6 Small Buttons - Scenes)
SS1 - Slider Station ††
RCQK - OS3E - OS1 - SS1 - W1 - D1 - P - W
office application button Functionality Conference room application button Functionality
programno.
button textControl
type
Function(unless a target level is indicated, the dimmer output will default to daylight
sensor control)
9 Half Lights PresetLoad 1 (yellow) ON, Load 2 (red) OFFAll Dimmers 50%Solatube Open (RC3DE only)
10 Full Lights PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ON All Dimmers 100%
11 Undercabinet Toggle Load 3 (purple) ON and OFF
6 Raise Raise Raise All Dimmers†
7 Lower Lower Lower All Dimmers†
16 All On PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ONAll Dimmers 100%
8 All Off PresetLoad 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFFSolatube Closed (RC3DE only)
Slider Slider Raise and Lower All Dimmers††
programno.
button textControl
type
Function(unless a target level is indicated, the dimmer output
will default to daylight sensor control)
12 General PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ONDimmer 1: 100%, Dimmer 2 80%, Dimmer 3 80%Solatube Open (RC3DE only)
13 Meeting PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ONDimmer 1: 80%, Dimmer 2 20%, Dimmer 3 100%Solatube Open (RC3DE only)
14 Whiteboard PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ONDimmer 1: 50%, Dimmer 2: 100%, Dimmer 3: 50%Solatube Closed (RC3DE only)
15 Presentation PresetLoad 1 (yellow) ON, Load 2 (red) ON, Load 3 (purple) ONDimmer 1: 30%, Dimmer 2: 0%, Dimmer 3: 25%Solatube Closed (RC3DE only)
6 Raise Raise Raise All Dimmers†
7 Lower Lower Lower All Dimmers†
16 All On PresetLoad 1 (yellow) ON, Load 2 (red) ON Load 3 (purple) ON All Dimmers 100%
8 All Off PresetLoad 1 (yellow) OFF, Load 2 (red) OFF, Load 3 (purple) OFF Solatube closed (RC3DE only)
Slider Slider Raise and Lower All Dimmers††
Half lights
Full lights
All Off
Half Lights
Full Lights
Undercabinet
Raise
Lower
All Off
All On
All Off
General
Meeting
Whiteboard
Presentation
Raise
Lower
Half Lights
Full Lights
Raise
Lower
All Off
Catalog #
Project
Comments
Prepared by
Type
Date
ACC130072
Room Controller - Private Office w/Daylight Dimming & Receptacle Control
Slider Station
pre-deFined WallStation model numberS
† These dimming wallstations can only be used with dimming Room Controllers (RC3D, RC3D2, RC3DE)
†† Slider stations can not be used if a wallstation with Raise/Lower buttons are used
*Catalog number automatically includes low voltage connection cable, wallplates and connectors based on room type and configuration.
*For site specific engraving, please see the Room Controller Wallstation custom engraving form on the Cooper Controls website