residential ventilation solutions - nuaire · residential ventilation solutions system c / d...

39
FOR THE COMPLETE VENTILATION SOLUTION WORLDWIDE Residential Ventilation Solutions SYSTEM C / D PRODUCTS

Upload: nguyentruc

Post on 17-May-2018

214 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

FOR THE COMPLETE VENTILATION SOLUTION WORLDWIDE

Residential Ventilation SolutionsSYSTEM C / D PRODUCTS

Page 2: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

NUAIRE’S PEDIGREE

www.nuairegroup.com | [email protected]

Nuaire is a world leader

in the development and

manufacture of fans and

ventilation systems.

With roots stretching

back to the 1920’s and a

tradition of excellence in

ventilation since 1963,

the Nuaire name has

been at the forefront of

the industry worldwide

for more than 40 years.

Page 3: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

3For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

Unit with and without Wireless Control

DIMENSIONS

With its roots in fans and mechanical ventilation products, Nuaire has progressively expanded itsrange and extended its capability to encompass technologies at all levels of ventilation solutions.It is the only company able to offer the complete ventilation solution for the built environment.

The company is renowned worldwide for its expertise, commitment to innovation and the outstandingquality of its products and customer service. People are at the heart of Nuaire, and the company has over450 staff at its UK headquarters and has technical sales engineers throughout Britain, as well as dedicatedpartners across the globe, including an offices in Dubai, Oman, Qatar, Kuwait, Bahrain and Finland. Its committed staff include leading experts who are constantly setting new standards for the industry bydeveloping new, innovative products in the company’s research and development department – thelargest and most advanced in the UK.

This passion for excellence ensures a large, loyal and growing customer base in the UK and overseas andhas been recognised by numerous awards.

QUALITY

Nuaire embodies the ‘gold standard’ of quality, which has earned British engineering and manufacturingits reputation for excellence around the world. Indeed, Nuaire was the first fan manufacturer in the worldto achieve the quality standard ISO 9001, and its commitment to quality remains embedded in allaspects of its operations.

Business is growing by 15% annually and the company is on course to double in size within four to fiveyears, mainly through the development of innovative new products, which set the standards for energyefficiency and reduced carbon emissions.

Page 4: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

www.nuairegroup.com | [email protected]

NUAIRE DELIVERS

DELIVERING TO YOUAn expert team of partners, covering countries and regions around the

world, provide a dedicated point of contact for overseas customers,

providing a customer care delivery package, which sets a new standard for

the ventilation industry.

All of Nuaire’s component suppliers are committed to ensuring our

schedules are met so that we can meet your requirements.

• Key components such as high temperature motors and car park impulse

jet fans are kept in stock in our factory in the UK, which means that you

receive the best possible delivery dates

• All goods are expertly secured by a team of professional packers ensuring

your equipment is received in pristine condition ready for installation

• Partners with all major shipping lines and airlines ensuring the quickest

most cost efficient deliveries

• All deliveries co-ordinated to meet your specific requirements and

construction programme

• Specialist team fully conversant with all documentation requirements

ensuring you have a smooth trouble free process from official order right

through to delivery at your site

• Full members of the UK’s Institute of Export

Nuaire is is renowned for its attention to

detail and has over 30 years experience in

delivering Nuaire equipment from the UK

to worldwide destinations.

Nuaire has a dedicated customer service

team working to ensure the highest

standards demanded by the export market

are met, ensuring that your goods arrive on

time and in pristine condition.

NUAIRE IS PASSIONATE ABOUT CUSTOMER SERVICE & ESTABLISHING LONG TERM PARTNERSHIPS.

Page 5: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

5For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

FAN SELECTOR/PRODUCT GUIDE

The software provides detailed datasheets comprising efficiency, performance, sound,wiring and specification. The software allows all of the data to be imported in Microsoft orDXF format for AutoCAD.

To download Fan Selector simply visit www.nuairegroup.com/fanselector and follow theinstructions.

An email reminder will be sent to you each time Fan Selector has been updated, enablingyou to download the latest copy.Alternatively, you can request a copy of Fan Selector on CD-RO M from the above website.

A practical and extremely helpful tool to assist with the

selection of products to meet your specification.

Page 6: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

All buildings have their own unique

requirements for ventilation. With the

new government guidelines on energy

efficiency it is more difficult to maintain

a comfortable, healthy environment

whilst providing an energy efficient

solution.

CONSTANT PRESSURE FOR

MULTI-ROOM VENTILATION

A central extract system provides a

continuous trickle of air to ensure the room

is kept fresh. When the room becomes

occupied the system will increase the

ventilation to the desired design duty.

MECHANICAL EXTRACT FOR OFFICES

& COMMUNAL AREAS

Extract fans are the most simplest form of

ventilation for office and communal

environment. Whether duct, wall, window or

ceiling mounted these fans will extract

moisture from wet rooms and offices to

provide continuous fresh air.

STAIRWELL PRESSURISATION & SMOKE

EXTRACT FOR MULTI-FLOOR

REQUIREMENTS

Nuaire have manufactured smoke and car

park ventilation for over 30 years and a

design service is available to complement

the complete range of smoke pressurisation

and extract fans (duct or roof mounted) for

300/400ºC for 1 & 2 hours, certified to

EN12101-3 2002.

CAR PARK EXTRACT

The comprehensive range of AXUS smoke

fans together with the Impulse car park

extract fan meets the ever increasing need

to provide smoke extract for car parks.

Systems designed for life

www.nuairegroup.com | [email protected]

WHATEVER YOUR BUILDING - Nuaire has a product that fits.

IMPULSE High temperature car parkextract system• Powerful yet quiet with inbuilt silencers• Unobtrusive low depth design

(320 or 400mm)• No ductwork reduces costs by up

to 30%• Reduce running costs by 40% with this

energy efficient system• For added security unit fixing brackets

are ‘2 stage’• Flexible system is fully reversible• For added safety Impulse is certified to

EN12101-3 (300ºC for 2 hours)

AXUS SMOKE High temperature axialextract fans (up to 85m3/s)• Flexible solution can be used for a wide

range of smoke applications• Choice of matched ancillaries• For added safety AXUS smoke fans are

certified EN12101-3 (400ºC for 2 hours& 300ºC for 2 hours)

• Flexible options for either smoke or nonsmoke reservoir applications

AXUS Duct mounted axial extract fans(up to 95m3/s)• Flexible solution can be used for a wide

range of applications• For ease of application a ‘stock range’ is

available contact Nuaire• Choice of matched ancillaries

SQUIF RANGE Run and standby unitsideal for ‘motor out of airstream’applications• Ideal for high resistance applications• Single and twin fan options• Twin fan option for 24/7 ventilation• Suitable for high temperature

applications• Options for internal and external

mounting• Ambient and high temperature models• Wide range of ancillaries available

AIRE-VOLVE TWIN FANS, NUAIRE’S LATESTINNOVATION • Patented in-line fan assembly providing optimum

performance, lowest noise, and lowest overall productenvelope size.

• Low profile new Twin Fan up to 1.9m3/s. Low SFP and noise.

MRXBOX95 WALL & LOFT COOL AIR & HEAT RECOVERY• Optimum performance – low specific fan power and highefficiency results in SAP Q

• Meets Building Regulations• Improves indoor air quality and prevents condensation• Extremely low noise levels ensuring occupant satisfaction• Independent controls for quick and easy commissioning• Easy and flexible installation options

Installation features: External Constant Pressure

Quiet Scroll Twin Fan

CAR PARK EXTRACT OPTIONS

Page 7: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

7For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

XBOXER TAILOR MADE AHUS

23 sizes covering airflow range up to 20m3/s.

STAIRWELL PRESSURISATION FOR ESCAPE

ROUTE PROTECTION

AXT High temperature ‘run & standby’ axial fan

(up to 73m3/s)• Ideal system for stairwell pressurisation• Added strength & stability as units are welded and

manufactured from heavy gauge galvanised steel• Optional access doors make observation, &

maintenance very quick & easy• Systems designed for life• Certified to EN12101-3

ES-OPUSDC Energy efficient range of inline, surface &recessed fans (Up to 115l/s)• Exceptionally quiet fans (typical dBA of 29)• Energy efficient Ecosmart ‘plug & go’ control option• Quick & easy to install and commission• Wide range of complementary ancillaries, sensors

and controls• Twin fan options available• Hard wearing, robust and flame retardant casing

ECOSMART SQURBOEnergy efficient make up air supply & extractunits (up to 0.5m3/s)• Exceptionally quiet fans ideal for above ceiling

applications• Ecosmart ‘plug & go’ controls are quick to install

and commission• Quick & easy to commission with easily adjustable

fan and heater duty• Wide range of complementary sensors and controls

suitable for most applications• Reduce installation time with ‘one box’ containing

filter, fan, heater & controls

XTRACTORHigh efficiency centrifugal fan (up to 6.2m3/s)• Quiet fan ideal for ‘noise sensitive’ areas• Powerful extract fan for multi-room system• For quick & easy installation and commissioning

include the Ecosmart energy efficient ‘plug & go’controls

• Requires very low maintenance• Flexible solution, with a wide range of 27 fans to

suit most applications

TERMINATOR Horizontal discharge roof extract fan• Flexible solution with choice of axial, centrifugal or

mixed flow impellers• On-site flexibility allows unit to be mounted

vertically or horizontally• Low profile weather cowl provides unobtrusive roof

top option• Reduce energy costs by selecting Ecosmart efficient

controls

XBOXER THERMAL WHEEL.Range of energy efficient units for internal orexternal applications (up to 10m3/s)• High efficiency wheel (up to 85%)• Optional energy efficient Ecosmart control option• Quiet solution with double skin construction• LPHW or no heater battery available• No control option• Wide range of ancillaries such as advanced

condensate pump, weather roof and motoriseddampers

Installation features:Impulse and Axushigh temperature fan

Installation features: ES-Opus Twin Fan

MECHANICAL EXTRACT FOR OFFICES AND COMMUNAL AREAS

Page 8: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

Nuaire’s MVHR units are complemented by a comprehensive range

of optional ancillaries and ducting.

WE OFFER THE COMPLETE SOLUTION

8 www.nuairegroup.com | [email protected]

MRXBOX95B-350WC & 350

MRXBOX95B-450WC & 450

MRXBOX95B-LP1

Supply air to lounge via Air Valve .

Extract air from kitchen via Air Valve in ceiling.

Supply air to bedrooms via Air Valve in ceiling.

MVHR-DRAIN condensate drain,running to SVP.

MVHR ceiling void mounted unit.

Extract air from bathroom via Air Valve in ceiling.

Exhaust air from kitchen/bathroom to outside via air brick(Part no. PVC505NS).

Supply and extract ducts from external air bricks to the unit needs to be insulated.

Top of ceiling void.

Intake air from outside via air brick(Part no. PVC505NS).

Air supply to lounge via Air Valve (Part no. VS125) in ceilings.

Extract air from kitchen/bathroom via Air Valve (Part no. VS125) in ceilings.

Exhaust air from kitchen/bathroom to outside via louvre grille(Part no. PVC504).

Intake air from outsidevia louvre grille(Part no. PVC504).

All duct between MVHR unit and atmosphere to be insulated*.

*Insulated supply duct.

Top of ceiling void.

Air supply to bedrooms via Air Valve (Part no. VS125) in ceilings.

MVHR wall mounted unit.

MVHR-DRAIN Condensate drain, uninsulated drain pipe with 10o fall running to SVP.

*Insulated extract duct.

Exhaust air from kitchen/bathroom to outside via air brick(Part no. PVC501).

Intake air from outsidevia air brick(Part no. PVC501).

All duct between MVHR unit and atmosphere to be insulated*.

*Insulated supply duct.

Air supply to lounge via Air Valve (Part no. VS125) in ceilings.

Extract air from kitchen/bathroom via Air Valve (Part no. VS125) in ceilings.

Air supply to bedrooms via Air Valve (Part no. VS125) in ceilings.

Top of ceiling void.

MVHR-DRAIN Condensate drain, uninsulated drain pipe with 10o fall running to SVP.

*Insulated extract duct.

MVHR wall mounted unit.

Unit shown in typical installation using

Nuaire circular duct and ancillaries.

(Note: Flat duct can also be used as

shown in the illustration below).

See page 26 for full range of duct and

ancillaries.

Unit shown in typical installation using

Nuaire circular duct and ancillaries.

(Note: Flat duct can also be used as

shown in the illustration below).

See page 26 for full range of duct and

ancillaries.

Unit shown in typical installation using

Nuaire circular duct and ancillaries.

(Note: Flat duct can also be used as

shown in the illustration below).

See page 26 for full range of duct and

ancillaries.

Page 9: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

INTENSE WIRED SWITCHOur universal 4 button switch, to connect any low voltage bus interface(KNX, MODBUS) and execute orders on the bus line.

Note: The wireless switch will typically operate up to a distance of 30m inside a building, however, this is dependent on the layout andconstruction of the building. This distance will be reduced depending on obstructions e.g. walls.

SIMPLE 3 SPEED SWITCHFor simple control and commissioning we offer a 3 speed switch for

the MVHR units.

ADDITIONAL SENSORS

PIR Passive Infra-Red. Humidistat.

WIRELESS AND WIRED CONTROLS

9For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

TOUCH SCREEN CONTROLLER

Stylish and simple full control of ventilation and commissioning with an LCD screen.

Page 10: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

COMPLETE ADVISORY AND DESIGN SERVICE

10 www.nuairegroup.com | [email protected]

We understand the many

challenges and regulations

that modern building

ventilation must meet,

and our full service is

designed to make your life

easier from start to finish.

DESIGN & SUPPLY SERVICEA Design & Supply service is available for

residential applications utilising 3D CAD

software to illustrate ducting systems and

components. This allows Nuaire to provide

the complete service of design drawings,

fan selection, ducting schedule for each

dwelling and deliver these products as a

bespoke package to assist project

management and material control on site.

Pre-delivery advice calls and text

messaging in advance further assist clients

in preparation for planned deliveries.

• A wide range of products with the

best scores on SAP

• Free SAP advice on products and

fabric choices

• Expert advice on product selection

and REVIT drawing service to

replicate system performance

• Advice on the latest building

regulations and legislation on

ventilation

• Over 65 office and field based staff to

support you

• BPEC training free of charge to insure

your installers get it right first time

TYPICAL EXAMPLE OF A NUAIRE DESIGN FOR A TYPICAL MVHR INSTALLATION

Page 11: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

11For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

REVIT SYSTEMThe system we use ensures that all calculations required are taken into

consideration when designing your project/ home. The key elements are

all taken into account: noise, air flow and resistance.

EMAIL DRAWINGS SERVICE & 3D SYSTEM LAYOUTYou can email your drawings to our design team and we will give back

to you a simple, clean system layout in 3D showing only the ventilation

design with all other services taken out. You can then drop this into your

programme as a separate layer.

The system we use generates the quote so you can be assured of an

accurate parts list.

PARTS LISTThe information we provide makes it easier to visualise how our products

are actually installed in the building. We eliminate any concerns about

ordering the correct ancillaries with our computer generated parts list.

This gives you every product and ancillary needed to complete the job and

includes a service list from tile vent through to grilles.

THE BEST SOLUTION FOR DESIGNERS

ISOMETRIC VIEW OF CONNECTION DETAILS AND PARTS LIST FOR A TYPICAL MVHR INSTALLATION

Page 12: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

A COMPACT HIGH DUTY MVHR UNIT WITH

LOW SPECIFIC FAN POWER (SFP)

Designed to meet the requirements of larger properties,

providing a versatile, cost effective, energy efficient

ventilation solution.

This whole house mechanical ventilation heat recovery

system combines supply and extract in one unit.

Tempered air is delivered into “living areas” whilst

extracting warm moisture laden air from “wet” areas

creating a comfortable living environment, with enhanced

energy efficient characteristics.

Low watt EC fans combined with high efficiency impellers

provides extremely quiet running and long life motors.

EC fans will also reduce power consumption,

operating, and the life cycle costs.

BENEFITS• EN308 compliant

• Tested to SAP APPENDIX Q - utilising EN13141-7 testing method

• Compact, lightweight - and easy to install

• Fan controls - designed for quick and easy commissioning

• Full design and supply - solution package

• Easy accessible filters from front cover – no tools required

• Heat recovery efficiency - in excess of 85%

• 350WC unit - has Wireless Control

• Constant quiet running fans – ensuring occupant acceptability

• 100% Summer bypass

• Summer boost facility

• Integral humidity sensor - (set point adjustment)

• Integral frost protection - (-5 degrees C as standard)

• Improves indoor air quality - creating healthier environment

• Prevents condensation - by keeping moisture levels low

• Significant energy savings - with very low running costs, due to EC

fan motors

• No trickle vents – reducing draught issues and noise levels from outside

• Facility to provide - additional fresh clean air

• 1 year warranty

www.nuairegroup.com | [email protected]

MRXBOX95B-350WC AND 350WALL MOUNTED SUPPLY AND EXTRACT HEAT RECOVERY SOLUTION FOR LARGER PROPERTIES

Page 13: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

13For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

MRXBOX95B-350WC AND 350

Sound Power Levels dB re 1pW63 125 250 500 1K 2K 4K 8K LwA

Extract Full speed Open inlet 50 51 58 55 50 48 41 37 5690% Open Inlet 50 50 57 54 48 46 39 35 5580% Open Inlet 49 50 56 52 46 44 37 33 5365% Open Inlet 48 48 53 49 40 38 31 27 4945% Open Inlet 46 45 50 44 33 31 24 20 4530% Open Inlet 43 42 44 36 22 20 13 9 38

Intake Full Speed Open Inlet 51 50 59 52 46 42 33 24 5490% Open Inlet 51 49 58 51 44 40 31 22 5380% Open Inlet 50 49 57 49 42 38 29 20 5165% Open Inlet 49 47 54 46 36 32 23 14 4845% Open Inlet 47 44 51 41 29 25 16 7 4430% Open Inlet 44 41 45 33 18 14 16 16 37

Discharge Full Speed Open Outlet 58 64 66 64 58 57 50 44 6590% Open Outlet 58 63 65 63 56 55 48 42 6480% Open Outlet 57 63 64 61 54 53 46 40 6265% Open Outlet 56 61 61 58 48 47 40 34 5845% Open Outlet 54 58 58 53 41 40 33 27 5330% Open Outlet 51 55 52 45 30 29 22 16 46

Supply Full Speed Open Outlet 57 62 68 62 58 57 50 46 6590% Open Outlet 57 61 67 61 56 55 48 44 6380% Open Outlet 56 61 66 59 54 53 46 42 6265% Open Outlet 55 59 63 56 48 47 40 36 5845% Open Outlet 53 56 60 51 41 40 33 29 5430% Open Outlet 50 53 54 43 30 29 22 18 47

Breakout SoundPressure Level

dBA@ 3m LwA

Breakout Full Speed Breakout 51 57 59 50 43 42 34 25 32 53

90% Breakout 51 56 58 49 41 40 32 23 31 5280% Breakout 50 56 57 47 39 38 30 21 30 5165% Breakout 49 54 54 44 33 32 24 15 27 4845% Breakout 47 51 51 39 26 25 17 8 23 4430% Breakout 44 48 45 31 15 14 16 16 17 38

0 100 200 300 400 500

500

450

400

350

300

250

200

150

100

50

0

Air volume flow rate (m3/hr)

Fan

Stat

ic P

ress

ure

100%

90%

80%

65%

45%

30%

PERFORMANCE

SOUND & BREAKOUT LEVELS

PRODUCT SPECIFICATION

Duty 350m3/hr (97l/s) @ 150pa

Efficiency Up to 90% @ required duty

Standards European EN308 Annex 5G Compliant, 2% leakage and UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers.

Speed Supply and extract fans can be individuallyadjusted and have 3 speeds - low, medium, high with timed boost.

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 704mm

Depth 571mm

Height 707mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standardwith the facility of optional higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 32mm dia. tray/drain Connection either side of HX block - TBC

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost. Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze Please contact Nuaire for any otheroptions. (TBC)

Integral Optional item that is adjustable from humidistat 60%-95% RH (TBC)

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire for details

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 x 200mm dia. outside and configuration 180mm inside dia.

Maintenance Ease of replacement for filters, motors,access, spares heat exchabgers and controls& replacementparts

Warranty 2 years

PRODUCT SPECIFICATION

Duty 350m3/hr @ 100pa.

Efficiency Up to 90% @ required duty

Standards European EN308 Annex 5G Compliant, 2% leakage and UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers

Speed Supply and extract fans can be individually adjusted and have 3 speeds - low, medium, high with timed boost

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 710mm

Depth 585mm

Height 710mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standardwith the facility of optiona higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 32mm dia. tray/drain Connection either side of HX block

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit.

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze. Please contact Nuaire for options

Integral Optional item that is adjustable from humidistat 60%-95% RH

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 x 200mm dia. outside and configuration 180mm inside dia.

Maintenance Ease of replacement for filters, motors,access, spares heat exchangers and controls& replacementparts

Warranty 1 year

Unit with and without Wireless Control

DIMENSIONS

Wireless control

585mm

710mm

710m

m

790m

m

Wit

h W

irel

ess

cont

rol

WIRELESS CONTROLThe Wireless control is standard on the

MRXBOX95B-350WC unit but is available as

an optional item for the standard unit.

The Wireless Control has 3 speeds and a timed

momentary switch for high speed boost.

Note: The switch will operate up to a distance

of 200 metres line of sight, this distance will

be reduced depending on obstructions e.g.

walls.

Page 14: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

www.nuairegroup.com | [email protected]

MRXBOX95B-450WC AND 450WALL MOUNTED SUPPLY AND EXTRACT HEAT RECOVERY SOLUTION FOR LARGER PROPERTIES

A COMPACT HIGH DUTY MVHR UNIT WITH

LOW SPECIFIC FAN POWER (SFP)

Designed to meet the requirements of larger properties,

providing a versatile, cost effective, energy efficient

ventilation solution.

This whole house mechanical ventilation heat recovery

system combines supply and extract in one unit.

Tempered air is delivered into “living areas” whilst

extracting warm moisture laden air from “wet” areas

creating a comfortable living environment, with enhanced

energy efficient characteristics.

Low watt EC fans combined with high efficiency impellers

provides extremely quiet running and long life motors.

EC fans will also reduce power consumption,

operating, and the life cycle costs.

BENEFITS• EN308 compliant

• Tested to SAP APPENDIX Q - utilising EN13141-7 testing method

• Compact, lightweight - and easy to install

• Fan controls - designed for quick and easy commissioning

• Full design and supply - solution package

• Easy accessible filters from front cover – no tools required

• Heat recovery efficiency - in excess of 85%

• 450WC unit - has Wireless Control

• Constant quiet running fans – ensuring occupant acceptability

• 100% Summer bypass

• Summer boost facility

• Integral humidity sensor - (set point adjustment)

• Integral frost protection - (-5 degrees C as standard)

• Improves indoor air quality - creating healthier environment

• Prevents condensation - by keeping moisture levels low

• Significant energy savings - with very low running costs, due to EC

fan motors

• No trickle vents – reducing draught issues and noise levels from outside

• Facility to provide - additional fresh clean air

• 1 year warranty

Page 15: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

15For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

MRXBOX95B-450WC AND 450

0 100 200 300 400 500 600 700

800

700

600

500

400

300

200

100

0

Air volume flow rate (m3/hr)

Fan

Stat

ic P

ress

ure

100%

90%

80%

65%

45%

30%

PERFORMANCE

SOUND & BREAKOUT LEVELSSound Power Levels dB re 1pW63 125 250 500 1K 2K 4K 8K LwA

Extract Full speed Open inlet 58 56 57 63 57 51 46 45 6390% Open Inlet 58 55 56 62 55 49 44 43 6180% Open Inlet 57 55 55 60 53 47 42 41 5965% Open Inlet 56 53 52 57 47 41 36 35 5545% Open Inlet 54 50 49 52 40 34 29 28 5030% Open Inlet 51 47 43 44 29 23 18 17 43

Intake Full Speed Open Inlet 56 54 59 67 55 48 37 34 6490% Open Inlet 56 53 58 66 53 46 35 32 6380% Open Inlet 55 53 57 64 51 44 33 30 6165% Open Inlet 54 51 54 61 45 38 27 24 5845% Open Inlet 52 48 51 56 38 31 20 17 5330% Open Inlet 49 45 45 48 27 20 16 16 45

Discharge Full Speed Open Outlet 67 63 65 75 68 63 56 53 7490% Open Outlet 67 62 64 74 66 61 54 51 7380% Open Outlet 66 62 63 72 64 59 52 49 7165% Open Outlet 65 60 60 69 58 53 46 43 6745% Open Outlet 63 57 57 64 51 46 39 36 6230% Open Outlet 60 54 51 56 40 35 28 25 54

Supply Full Speed Open Outlet 59 62 65 71 65 63 57 53 7190% Open Outlet 59 61 64 70 63 61 55 51 7080% Open Outlet 58 61 63 68 61 59 53 49 6865% Open Outlet 57 59 60 65 55 53 47 43 6445% Open Outlet 55 56 57 60 48 46 40 36 5930% Open Outlet 52 53 51 52 37 35 29 25 51

Breakout SoundPressure Level

dBA@ 3m LwA

Breakout Full Speed Breakout 61 61 60 63 53 48 40 35 40 61

90% Breakout 61 60 59 62 51 46 38 33 39 6080% Breakout 60 60 58 60 49 44 36 31 37 5865% Breakout 59 58 55 57 43 38 30 25 34 5545% Breakout 57 55 52 52 36 31 23 18 29 5030% Breakout 54 52 46 44 25 20 16 16 22 43

PRODUCT SPECIFICATION

Duty 350m3/hr (97l/s) @ 150pa

Efficiency Up to 90% @ required duty

Standards European EN308 Annex 5G Compliant, 2% leakage and UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers.

Speed Supply and extract fans can be individuallyadjusted and have 3 speeds - low, medium, high with timed boost.

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 704mm

Depth 571mm

Height 707mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standardwith the facility of optional higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 32mm dia. tray/drain Connection either side of HX block - TBC

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost. Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze Please contact Nuaire for any otheroptions. (TBC)

Integral Optional item that is adjustable from humidistat 60%-95% RH (TBC)

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire for details

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 x 200mm dia. outside and configuration 180mm inside dia.

Maintenance Ease of replacement for filters, motors,access, spares heat exchabgers and controls& replacementparts

Warranty 2 years

PRODUCT SPECIFICATION

Duty 450m3/hr @ 190pa.

Efficiency Up to 90% @ required duty

Standards European EN308 Annex 5G Compliant, 2% leakage and UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers

Speed Supply and extract fans can be individually adjusted and have 3 speeds - low, medium, high with timed boost

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 710mm

Depth 585mm

Height 710mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standardwith the facility of optional higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 32mm dia. tray/drain Connection either side of HX block

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost. Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze. Please contact Nuaire for options.

Integral Optional item that is adjustable from humidistat 60%-95% RH

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire.

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 x 200mm dia. outside and configuration 180mm inside dia.

Maintenance Ease of replacement for filters, motors,access, spares heat exchangers and controls& replacementparts

Warranty 1 year

Unit with and without Wireless Control

DIMENSIONS

Wireless control

585mm

710mm

710m

m

790m

m

Wit

h W

irel

ess

cont

rol

WIRELESS CONTROLThe Wireless control is standard on the

MRXBOX95B-450WC unit but is available as

an optional item for the standard unit.

The Wireless Control has 3 speeds and a timed

momentary switch for high speed boost.

Note: The switch will operate up to a distance

of 200 metres line of sight, this distance will

be reduced depending on obstructions e.g.

walls.

Page 16: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

www.nuairegroup.com | [email protected]

MRXBOX95AB-WM1CUPBOARD/WALL MOUNTED SUPPLY AND EXTRACT HEAT RECOVERY SOLUTION FOR

SMALL TO MEDIUM SIZE HOUSES AND APARTMENTS

A COMPACT HIGH DUTY MVHR UNIT WITH

LOW SPECIFIC FAN POWER (SFP)

Designed to meet the requirements of medium sized

houses and apartments, to provide optimised

balanced (supply and extract) mechanical ventilation

with heat recovery.

MRXBOX95AB-WM1 uses the latest generation of low

voltage DC fans and motors, counter flow heat exchanger

and easy accessible controls. The heat exchanger block

can recover up to 95% of the normally wasted heat

The two independent fans has full speed control for

background and boost ventilation rates as well

as a run-on timer facility.

BENEFITS• SAP Appendix Q recognised - Part F&L, England & Wales. Scottish

technical handbook (BRE398 referenced). Technical booklet K1998

• High efficiency - heat exchanger is up to 95% efficient

• Easy installation - compact, lightweight and simple to install

Full installation service available

• Optimum performance - Low Specific Fan power and high efficiency

results in SAP Q

• No need for trickle vents - a cost saving and tenant acceptability

• Improves indoor air quality - prevents condensation by keeping moisture

levels low - creating a healthier environment

• Integral frost protection - protects the unit during extreme cold spells

• Low & easy maintenance - easy accessible filters from front cover

– no tools required. Filter replacement typically every 12 – 18 months

• Extremely low noise levels - quiet running unit ensuring

occupant acceptability

• Pre-commissioning filter protection - filters are covered in a removable

protective film to prevent clogged up filters prior to occupant handover

• Summer bypass - provides cooling during warmer months

• 1 year warranty

Page 17: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

17For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

MRXBOX95AB-WM1

Maximumpower consumption Sound Power Levels dB re 1pW dBA

Curve (Watts) 63 125 250 500 1K 2K 4K 8K @3m1 71 Open inlet 45 41 48 47 41 39 24 24 30

Open outlet 48 51 57 59 54 47 39 33 41Breakout 51 50 53 51 43 38 30 26 33

2 39 Open Inlet 44 39 46 44 36 34 20 19 26Open outlet 44 48 52 53 48 41 29 25 36Breakout 50 48 51 48 38 33 25 21 30

3 21 Open inlet 42 38 43 37 31 26 20 17 21Open outlet 42 46 49 49 42 35 23 19 31Breakout 48 46 47 44 32 27 19 15 26

4 10 Open inlet 40 35 39 32 23 18 12 9 16Open outlet 40 43 44 43 33 20 14 13 24Breakout 46 43 43 38 23 18 10 6 21

5 5 Open inlet 35 29 30 20 5 - - - <10Open outlet 36 38 37 33 18 11 - - 15Breakout 42 38 36 28 8 3 - - 13

Air volume flow rate (m3/hr)

Fan

Stat

ic P

ress

ure

(Pa)

100

250

350

0 36 72 108 144 180 216 0

200

300

150

1

2

4

3

5

50

PERFORMANCE

SOUND & BREAKOUT LEVELS

PRODUCT SPECIFICATION

Duty 187m3/hr @ 150pa

Efficiency Up to 95% @ required duty

Standards UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers.

Speed Supply and extract fans can be individuallyadjusted and have 3 speeds - low, medium, high with timed boost.

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 601mm

Depth 288mm

Height 468mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standard with the facility of optional higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 21.5mm dia. tray/drain Flowpast connection

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost. Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze. Please contact Nuaire for any other options

Integral Optional item that is adjustable from humidistat 60%-95% RH

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire for details

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 x 125mm outside dia. configuration

Maintenance Ease of replacement for filters, motors,access, spares heat exchangers and controls& replacementparts

Warranty 1 year

288mm

601mm

468m

m

ExtractFan Supply

Fan

Run on Trickle Boost Trickle Boost

Extract air from house

Intake air from outside

to outside

Supply air to house

DIMENSIONS AIRFLOW THROUGH UNIT

The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking intoaccount any heat recovery saving and based on SAP Appendix Q testing.

Page 18: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

www.nuairegroup.com | [email protected]

MRXBOX95AB-WM2CUPBOARD/WALL MOUNTED SUPPLY AND EXTRACT HEAT RECOVERY SOLUTION FOR

SMALL TO MEDIUM SIZE HOUSES AND APARTMENTS

BENEFITS• SAP Appendix Q recognised - Part F&L, England & Wales. Scottish

technical handbook (BRE398 referenced). Technical booklet K1998

• Optimum performance - Low Specific Fan power and high efficiency

results in SAP Q

• Compact - the unit fits easily into cupboards not taking up valuable

storage space

• Extremely low noise levels - quiet running unit ensuring

occupant acceptability

• No need for trickle vents - a cost saving and tenant acceptability

• Descreet run monitor - records units operational time

• Improves indoor air quality - prevents condensation by keeping moisture

levels low - creating a healthier environment

• Integral frost protection - protects the unit during extreme cold spells

• Low & easy maintenance - easy accessible filters from front cover

– no tools required. Filter replacement typically every 12 – 18 months

• Pre-commissioning filter protection - filters are covered in a removable

protective film to prevent clogged up filters prior to occupant handover

• Summer bypass - provides cooling during warmer months

• 1 year warranty

A COMPACT HIGH DUTY MVHR UNIT WITH

LOW SPECIFIC FAN POWER (SFP)

Designed to meet the requirements of medium sized

houses and apartments, providing optimised balanced

(supply & extract) mechanical ventilation

with heat recovery.

Tempered air is delivered into ‘living’ areas whilst

extracting moisture laden air from ‘wet’ areas creating

comfortable well ventilated homes.

The unit has the facility to commission the supply &

extract fans independently on both minimum and

maximum speeds. The heat exchanger block can recover

up to 90% of normally wasted heat.

Page 19: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

19For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

MRXBOX95AB-WM2

Air volume flow rate (m3/hr)

Fan

Stat

ic P

ress

ure

(Pa)

200

400

0 72 144 216 288 360 432 0

100

300

500

50

150

250

350

450

550

3

2

5

4

1

PERFORMANCE

353mm

603mm

503m

m

PRODUCT SPECIFICATION

Duty 350m3/hr @ 150pa

Efficiency Up to 90% @ required duty

Standards UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers

Speed Supply and extract fans can be individuallyadjusted and have 3 speeds - low, medium, high with timed boost

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 603mm

Depth 353mm

Height 503mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standard with the facility of optional higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 21.5mm dia. tray/drain Flowpast connection

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost. Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze. Please contact Nuaire for any other options

Integral Optional item that is adjustable from humidistat 60%-95% RH

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire for details

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 x 125mm outside dia.

Maintenance Ease of replacement for filters, motors,access, spares heat exchabgers and controls& replacementparts

Warranty 1 year

Maximumpower consumption Sound Power Levels dB re 1pW dBA

Curve (Watts) 63 125 250 500 1K 2K 4K 8K @3m

1 150 Open inlet 57 57 61 56 50 47 36 34 40Open outlet 55 65 71 67 64 60 51 43 52Breakout 61 61 56 53 47 44 35 33 37

2 75 Open inlet 51 51 55 48 40 35 25 20 32Open outlet 53 59 61 58 55 52 39 32 43Breakout 56 55 51 44 38 35 23 17 29

3 36 Open inlet 48 48 48 42 33 28 18 <16 26Open outlet 52 56 55 53 49 45 32 25 37Breakout 52 54 47 39 33 30 <16 <16 26

4 14 Open inlet 44 44 39 34 27 21 <16 <16 18Open outlet 51 52 49 48 43 37 25 18 31Breakout 49 52 44 34 29 25 <16 <16 22

5 8 Open Inlet 40 39 25 22 18 <16 <16 <16 <16Open outlet 50 48 41 41 36 24 17 <16 24Breakout 46 50 39 27 22 19 <16 <16 18

ELECTRICAL, SOUND & BREAKOUT LEVELS

Extract air from house

Intake air from outside

to outside

Supply air to house

DIMENSIONS AIRFLOW THROUGH UNIT

The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking intoaccount any heat recovery saving based on SAP Appendix Q testing.

Page 20: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

www.nuairegroup.com | [email protected]

MRXBOX95B-LP1VERY LOW DEPTH CEILING VOID HEAT RECOVERY SOLUTION FOR APARTMENTS

A COMPACT HIGH DUTY MVHR UNIT WITH

LOW SPECIFIC FAN POWER (SFP)

Designed to meet the requirements of apartments where

storage space is at a premium the unit provides ultra-

efficient ventilation for up to four wet rooms.

With specific fan power down to 0.58 w/l/s the

MRXBOX95B-LP1 provides the lowest SFP’s of any

void-mounted MVHR system available.

Using the latest technology of low watt EC fans

combined with high efficiency impellers provides

extremely quiet running and long life motors.

EC fans will also reduce power consumption,

operating, and the life cycle costs.

BENEFITS• SAP Appendix Q recognised - Part F&L, England & Wales. Scottish

technical handbook (BRE398 referenced). Technical booklet K1998

• Optimum performance - Low Specific Fan power and high efficiency

results in SAP Q

• Extremely low noise levels - quiet running unit ensuring

occupant acceptability

• No need for trickle vents - a cost saving and tenant acceptability

• Overcomes valuable cupboard space restrictions - mounted within

ceiling void

• Descreet run monitor - records units operational time

• Improves indoor air quality - high efficiency filters help to create a

healthier environment

• Integral frost protection - protects the unit during extreme cold spells

• Simple fan controls - independent controls for supply & extract for

quick and easy commissioning

• Low & easy maintenance - easy accessible filters from front cover

– no tools required. Filter replacement typically every 12 – 18 months

• Provides extra storage/cupboard space - occupancy acceptability

• Summer bypass - provides cooling during warmer months

• 1 year warranty

Page 21: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

21For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

MRXBOX95B-LP1

0 36 72 108 144 180 216 252 288

Fan

Stat

ic P

ress

ure

(Pa)

300

350

400

450

500

550

0

50

100

150

200

250

Air volume flow rate (m3/hr)

1

2

3

4

5

PERFORMANCE

850mm

200m

m

700mm

PRODUCT SPECIFICATION

Duty 216m3/hr @ 150pa

Efficiency Up to 90% @ required duty

Standards UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers

Speed Supply and extract fans can be individuallyadjusted and have 3 speeds - low, medium, high with timed boost

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 850mm

Depth 700mm

Height 200mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standard with the facility of optional higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 21.5mm dia. tray/drain Flowpast connection

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost. Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze. Please contact Nuaire for any other options

Integral Optional item that is adjustable from humidistat 60%-95% RH

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire for details

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 spigots for 204 x 60mm configuration rectangular ducting

Maintenance Ease of replacement for filters, motors,access, spares heat exchabgers and controls& replacementparts

Warranty 1 year

Maximumpower consumption Sound Power Levels dB re 1pW dBA

Curve (Watts) 63 125 250 500 1K 2K 4K 8K @3m

1 100 Open inlet 50 56 55 55 46 42 32 23Open outlet 57 67 68 69 67 65 56 48Breakout 64 64 63 62 52 47 38 30 43

2 85 Open inlet 50 52 55 51 43 39 27 17Open outlet 56 63 65 65 63 59 51 42Breakout 62 62 61 57 48 43 32 20 40

3 65 Open inlet 45 47 48 44 35 30 20 9Open outlet 52 57 58 58 56 53 42 32Breakout 57 56 54 49 41 33 23 - 33

4 45 Open inlet 39 42 37 34 26 19 12 -� Open outlet 46 50 49 49 46 44 30 21Breakout 50 49 44 39 29 19 14 -� 23

5 26 Open Inlet 36 36 26 24 17 14 - -

Open outlet 39 43 37 38 35 28 17 10

Breakout 42 40 33 27 14 - - - 12

ELECTRICAL, SOUND & BREAKOUT LEVELS

The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking intoaccount any heat recovery saving based on SAP Appendix Q testing.Please note step curves shown are for information purposes only and are not individual units. The units actual dutyrange is infinitely variable.

DIMENSIONS AIRFLOW THROUGH UNIT

Fresh air from outsideExhaust air

to outside

Extract air from houseSupply air

to house

Page 22: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

22 www.nuairegroup.com | [email protected]

MRXBOX95AB-WH1WALL MOUNTED SUPPLY AND EXTRACT HEAT RECOVERY SOLUTION FOR

LARGE HOUSES AND APARTMENTS WITH VENTILATION FOR UP TO 7 WET ROOMS

A COMPACT HIGH DUTY MVHR UNIT.

SYSTEM WORKS TO PRE-HEAT OR COOL

INCOMING AIR SUPPLY

This high duty system has ultra-low Specific Fan

Power (SFP) and will recover up to 95% of heat

which would normally be wasted.

The MRXBOX95AB-WH1 incorporates the latest

generation of low voltage DC fans to provide ultra-

quiet running and long life motors. The DC fans will

also reduce power consumption, operating costs

and life cycle costs.

This system has the facility to commission the

supply and extract fans independently.

BENEFITS• SAP Appendix Q recognised - Part F&L - England & Wales. Scottish

technical handbook (BRE398 referenced). Technical booklet K1998

• Optimum performance - low specific fan power and high efficiency

results in SAP Q

• Suitable for larger applications - designed to meet the duty for

medium to large properties including 3 storey

• Compact - the unit fits easily into cupboards not taking up valuable

storage space

• Extremely low noise levels - quiet running unit ensuring

occupant acceptability

• Improves indoor air quality - high efficiency filters

• Low & easy maintenance - easy accessible filters from front cover

– no tools required. Filter replacement typically every 12 - 18 months

• Descreet run monitor - records units operational time

• Integral frost protection - protects the unit during extreme cold spells

• Summer bypass - provides cooling during warmer months

• Pre-commissioning filter protection - filters are covered in a removable

protective film to prevent clogged up filters prior to occupant handover

• Simple fan controls - independent controls for supply & extract

for quick and easy commissioning

• 1 year warranty

Page 23: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

23For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

MRXBOX95AB-WH1

DIMENSIONS AIRFLOW THROUGH UNIT

PERFORMANCE

431mm

654mm

619m

m

PRODUCT SPECIFICATION

Duty 290m3/hr @ 150pa

Efficiency Up to 90% @ required duty

Standards European EN308 Annex 5G Compliant, 2% leakage and UK SAP APPENDIX Q utilising EN13141-7 testing method

Fan/motor EC motors with high efficiency backward assembly curved centrifugal impellers.

Speed Supply and extract fans can be individuallyadjusted and have 3 speeds - low, medium, high with timed boost.

Bypass 100% bypass - intelligent, automatic as standard i.e. identifies the difference between external and internal air temperatures and shall direct the air accordingly. Factory set at 20oC – please contact Nuaire for other options

Width 654mm

Depth 431mm

Height 619mm

Access Front access for filter, HX block, fan / motor asssemblies, control module and condensate tray/drain

Handing Left and right handed

Filters G3 as standard with the facility of optional higher grades e.g. F7 panel

Filter Filter dirty indication required either by maintenance timer e.g. every 3-6 months

Condensate Condensate tray to 21.5mm dia. tray/drain Fastpast connection

Control 3 speed, timed momentary boost, frost system protection/speed offset, filter dirty, failure

indication, wireless receiver

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Remote Wireless control is an optional item andControl has 3 speeds and a timed momentary

switch for high speed boost. Wireless Wireless facility is available as an option controls and is easily fitted as to a standard unit

Fan controls 3 speed, hard wired control supplied as initial set-up & standardcommissioning

Frost Standard - supply air volume is reduced in protection frost condition(-5oC) to ensure that the

filter and Heat recovery block does not freeze. Please contact Nuaire for any other options

Integral Optional item that is adjustable from humidistat 60%-95% RH

Additional Facility for heaters to be fitted before or heaters after the unit depending on your projects

requirements. Please contact Nuaire for details

Condensate Centrally located from the the front of position the unit - Left and right handing to be

considered

Spigot Multiple 4 x 150mm outside dia. configuration

Maintenance Ease of replacement for filters, motors,access, spares heat exchangers and controls& replacementparts

Warranty 1 year

Maximumpower consumption Sound Power Levels dB re 1pW dBA

Curve (Watts) 63 125 250 500 1K 2K 4K 8K @3m

1 150 Open inlet 48 51 58 49 47 39 25 <16 31Open outlet 56 63 67 67 62 60 50 41 47Breakout 56 61 59 53 43 40 25 <16 33

2 114 Open inlet 48 50 57 48 45 37 23 <16 30Open outlet 56 62 66 66 60 58 48 39 45Breakout 56 60 58 52 41 38 23 <16 32

3 75 Open inlet 47 50 56 46 43 35 21 <16 29Open outlet 55 62 65 64 58 56 46 37 44 Breakout 55 60 57 50 39 36 21 <16 31

4 36 Open inlet 46 48 53 43 37 29 <16 - 25

Open outlet 54 60 62 61 52 50 40 31 40Breakout 54 58 54 47 33 30 <16 <16 28

5 14 Open Inlet 44 45 50 38 30 22 <16 <16 22Open outlet 52 57 59 56 45 43 33 24 35Breakout 52 55 51 42 26 23 <16 <16 24

6 8 Open inlet 41 42 44 30 19 <16 <16 <16 <16

Open outlet 49 54 53 48 34 32 22 <16 27

Breakout 49 52 45 34 <16 <16 <16 <16 19

ELECTRICAL, SOUND & BREAKOUT LEVELS

The maximum power consumption shown above (Watts) is consumed on units running continuously, not taking intoaccount any heat recovery saving based on SAP Appendix Q testing.

Air volume flow rate (m3/hr)

Fan

Stat

ic P

ress

ure

(Pa)

200

400

0 90 180 270 360 450 0

100

300

500

6

3

2

5

4

1

Extract air from house

Intake air from outside

Exhaust air from houseto outside

Supply air to house

Page 24: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

24 www.nuairegroup.com | [email protected]

A MULTI-POINT EXTRACT UNIT

WITH LOW DEPTH AND HIGH PERFORMANCE

The MEVDC is a centralised extract system which can

ventilate your entire property without the need to install

individual extract fans. The low-profile MEVDC offers

flexible installation, as the unit has a unique locating

bracket which enables fixing in any orientation.

The low-watt DC motors provide high performance

with low SFPs and low noise.

At only 190mm deep, the low profile MEVDC is

designed to save space whilst still providing

high performance ventilation.

BENEFITS• SAP Appendix Q recognised - Part F&L, England & Wales. Scottish

technical handbook (BRE398 referenced). Technical booklet K1998

• Low depth, high performance - only 190mm deep, and up to 98l/s

• Most efficient - latest DC motors provide high performance with

low SFP within their respective class

• Quietest solution - advanced motor and impeller technology with

acoustic lined lid (fully lined case option available) provide one of the

quietest options

• Quick installation - a unique locating bracket enables the units to be

fixed in horizontal or vertical plane, quickly and efficiently at either 1st fix or

2nd fix stage

• Easy commissioning - Ecosmart ‘dial a duty’ option allows for infinitely

variable speed selection allowing for exact design selection

• Easy maintenance - Easy to access for optional filters for quick and

easy maintenance

• Added strength - ABS moulded lid and case provides longer life

and a more robust unit

• 1 year warranty

MEVDC A QUIET, ENERGY EFFICIENT, LOW DEPTH CENTRAL MULTI-POINT EXTRACT SYSTEM

WHICH OFFERS FLEXIBLE INSTALLATION OPTIONS

Page 25: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

MEVDC

25For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

PERFORMANCE

350mm490mm

190mm

Power consumption Sound Power Levels dB re 1pW dBA Curve (Watts) (Amps) 63 125 250 500 1K 2K 4K 8K @3m

1 11 0.14 39 39 44 36 31 22 21 18 19

2 21 0.19 40 42 46 41 37 28 24 18 27

3 35 0.25 43 43 50 46 41 31 28 27 31

4 52 0.37 45 44 54 52 44 35 31 27 34

ELECTRICAL, SOUND & BREAKOUT LEVELS

Note: above sound level figures are for lined lid unit. Unit has a soft start feature as standard therefore the startingcurrent is the same as the full load current.Step curves are for information purposes only and are not individual units. The electrical and sound information in thetable is nominal. Note: dBA figures are calculated based on hemi-spherical propagation.

0 72 144 216 288 360 432

Fan

Stat

ic P

ress

ure

(Pa)

100

200

300

400

500

600

Air volume flow rate (m3/hr)

3

0

2

1

4

Note: Above are variable speeds,not set speeds.

DIMENSIONS AIRFLOW THROUGH UNIT

The case is constructed in grey /blue ABS plastic. The full length

access cover is located on the underside of the unit. This cover is

acoustically lined with flame retardant acoustic foam (full lining

also available).

The mounting bracket, on the opposite side, is retained by four

quarter turn fasteners.

THE MEVDC UNIT

PRODUCT SPECIFICATION

Duty 300m3/hr @ 100pa

Efficiency Up to 90% @ required duty

Standards Manufactured by a BSI Registered Firm with ISO 9000 certification.

Fan/motor DC motors, high efficiency with sealed assembly for life bearings

Speed Fully speed adjustable from 0-100%

Width 350mm

Depth 490mm

Height 180mm

Access Removable front access panel to all components.

Filters G3 as standard with the facility of optional higher grades e.g. G4

Filter Filter to be cleaned maintenance every 3-6 months

Sensors Carbon dioxide (CO2), combined Carbon available dioxide and temperature sensors, passive

infra red movement detector (PIR), humidistat, thermostat, remote failure indication, hour run monitor, etc.

Integral Optional item that is adjustable from humidistat 60%-95% RH

Spigot 2 x 125mm dia, 4 x 100mm dia. configuration 110 x 54mm dia option available

Maintenance Ease of replacement for filters, motors,access, spares heat exchangers and controls& replacementparts

Warranty 1 year

Page 26: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

ALSO FROM NUAIRE -

New

ALL YOUR REQUIREMENTS FROM

A SINGLE SUPPLIER

Compliant with building regulations the light weight

material not only enables a one person lift, but also

removes the time and cost of insulating PVC pipe line.

Unlike other thermal ducting systems that fit around a

PVC pipe Nuaire Thermal is an all in one

complete insulated ducting system, providing

a cost effective and quick installation.

BENEFITS• Simple, unique solution - for neat ducting

• Building Regulations - fully compliant

• Fixing clamps - forms an airtight seal and removes the

need for sealant or tape

• Eliminates the risk of condensation - forming in the ducting

• Easy installation - only one person necessary

• Promotes best practice installation

THERMAL DUCTING - AN ALL IN ONE INSULATED DUCTING SYSTEM FOR UNHEATED SPACES

26 www.nuairegroup.com | [email protected]

Page 27: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

27For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

The most common method of insulation duct used through un-heated spaces is bubble wrapped ductwork (figure 1)

which has limited resistance. Single wrap using this method does not comply with building regulations. An alternative

method which is currently used is to wrap the ductwork in 25mm of rockwool (figure 2) which can be very labour

intensive and can be prone to human error, often leaving areas of the ductwork uncovered. Nuaire’s thermal insulation

(figure 3) significantly improves thermal efficiency and is the simplest cost effective solution to meet current building

regulations.

Figure 1: Bubble wrap. Figure 2: Rockwool. Figure 3: Nuaire thermal ducting.

NUAIRE THERMAL EXCEEDS BUILDING REGULATION REQUIREMENTS

Bubble wrap = 0.033 W/m.k 3.6mm thick

Thermal resistances (m2.k)/W)

Rockwool = 0.04 W/m.k 25mm thick

Non-compliant

Domestic Compliance Guide Requirements

Nuaire thermal ducting = 0.03 W/m.k 20mm thick

0.7

0.6

0.5

0.4

0.3

0.2

0.1

0

1

2

3

COMPLIANCE CHART

HOW NUAIRE THERMAL COMPLIESTHE SIMPLE SOLUTION TO MEET BUILDING REGULATIONS

Page 28: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

28 www.nuairegroup.com | [email protected]

RECTANGULAR 204 X 60mm INSULATED DUCTING AND ANCILLARIES

INSULATED T PIECEBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-TP 204mm x 60mm Insulated T Piece 6 0.9 2.3 5.9 11.2 18.3

INSULATED 90º HORIZONTAL BEND Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-90H 204mm x 60mm Insulated 90º Horizontal Bend 6 0.6 1.6 4.1 7.9 12.8

INSULATED 45º HORIZONTAL BEND Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-45H 204mm x 60mm Insulated 45º Horizontal Bend 6 0 0.3 1.2 2.6 4.5

INSULATED 90º VERTICAL BEND Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-90V 204mm X 60mm Insulated 90º Vertical Bend 6 0.7 1.9 5.2 10.1 16.6

INSULATED PLENUM Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-PL 204mm x 60mm Insulated Plenum 6 0.5 1.3 3.4 6.4 10.4

INSULATED DUCT 1M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-1M 204mm x 60mm Insulated Duct 1M length 6 0.2 0.4 0.8 1.4 2.2

INSULATED RECTANGULAR DUCT CLAMP WITH FIXING LUGSBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-CONL 204mm x 60mm Insulated Duct Clamps 6 - - - - -

with Fixing Lugs

INSULATED RECTANGULAR DUCT CLAMP Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-204-CON 204mm x 60mm Insulated Duct Clamps 6 - - - - -

without Fixing Lugs

Page 29: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

ROUND 125mm DIA. INSULATED DUCTING AND ANCILLARIES

29For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

Use rigid duct for the majority of

your installation.

Avoid using flexible ducting, if you must,

remember the regulations, pull taut to 90% of its

length, support the install and don’t install where

it can be crushed.

Minimise bends and ensure your duct routes take

the path of least resistance.

Use a non-hardening acrylic sealant and

aluminium duct tape to connect your ductwork

and use ducting with guide veins to avoid gaps

and air leakage.

Use insulated ducting for unheated spaces or

heated spaces that are carrying cold air.

Install Nuaire’s CONTRAP and install the

ductwork correctly to prevent backflow of

moisture going to the fan unit.

Follow the design provided by Nuaire.

NUAIRE’S TOP TIPS

INSULATED T PIECEBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-125-TP 125mm Dia. Insulated T Piece 6 0.5 1 2.2 3.9 6.1

INSULATED 90º BEND Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-125-90H 125mm Dia. Insulated 90º Bend 6 0.5 1.4 4 7.9 13

INSULATED 45º BEND Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-125-45H 125mm Dia. Insulated 45º Bend 6 0.2 0.5 1.4 2.7 4.5

INSULATED DUCT 1M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-125-1M 125mm Dia. Insulated Duct 1M length 6 0.1 0.2 0.4 0.65 0.9

INSULATED ROUND DUCT CLAMP WITH FIXING LUGSBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-125-CONL 125mm Dia. Insulated Duct Clamps 6 - - - - -

with Fixing Lugs

INSULATED ROUND DUCT CLAMPBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sNTD-125-CON 125mm Dia. Insulated Duct Clamps 6 - - - - -

without Fixing Lugs

Page 30: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

DUCTING AND ANCILLARIESALL YOUR REQUIREMENTS FROM A SINGLE SUPPLIER

30 www.nuairegroup.com | [email protected]

ALL YOUR REQUIREMENTS FROM

A SINGLE SUPPLIER

Nuaire provides a comprehensive range of

installation ancillaries for all ducted

applications to ensure the most cost effective

solutioncan be achieved.

BENEFITS• Circular PVC duct - Provides optimum system efficiency.

Lightweight with simple push fit connections for ease of installation

• Slim PVC duct - Ideal for apartments, ceiling voids, loft and other

confined spaces

• Flat PVC duct systems - In confined areas where is space is minimum

without reducing whole system performance

• Attenuation - Reduce duct noise as per 'Domestic Compliance Guide 2010'

and noise requirements in 'Part F Building Regulations 2010'.

Attenuator ducting also reduces cross talk through the ventilation systems,

between rooms

• Wide selection of internal/external grilles - Designed to maximise

system airflow performance and occupant comfort.

• Fire protection - Available for all duct systems to meet regulations

ALSO FROM NUAIRE -

New range of thermal ducting, an

all-in-one insulated ducting system. See page 26.

Page 31: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

PVC FLAT DUCTING

31For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

FLAT CHANNEL 1m LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC510WH 204mm x 60mm Flat Channel 1m Length 5 0.2 0.4 0.8 1.4 2.2PVC4010WH 121mm x 60mm Flat Channel 1m Length 10 0.5 1.0 2.1 3.5 5.3PVC010WH 110mm x 54mm Flat Channel 1m Length 10 0.7 1.5 3.4 5.8 9.0

FLAT CHANNEL 1.5M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC515WH 204mm x 60mm Flat Channel 1.5m Length 5 0.3 0.6 1.3 2.2 3.3PVC4015WH 121mm x 60mm Flat Channel 1.5m Length 10 0.7 1.5 3.1 5.3 7.9PVC015WH 110mm x 54mm Flat Channel 1.5m Length 10 1.2 2.4 5.3 9.0 13.7

FLAT CHANNEL 2M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sD3-2000 204mm x 60mm Flat Channel 2m Length 5 0.4 0.8 1.7 2.9 4.4D1-2000 110mm x 54mm Flat Channel 2m Length 10 1.5 3.1 6.7 11.7 17.9

SLIM DUCT CONNECTORSBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC520WH 204mm x 60mm Slim Duct Connector 10 0 0 0 0 0PVC420WH 121mm x 60mm Slim Duct Connector 10 0 0 0 0 0PVC020WH 110mm x 54mm Slim Duct Connector 20 0 0 0 0 0

CHANNEL CLIPSBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC122-5WH 204mm x 60mm Channel Clip 10 0 0 0 0 0PVC422WH 121mm x 60mm Channel Clip 10 0 0 0 0 0PVC122WH 110mm x 54mm Channel Clip 10 0 0 0 0 0

90º HORIZONTAL BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC550WH 204mm X 60mm Horizontal 90º Bend 10 0.6 1.6 4.1 7.9 12.8PVC450WH 121mm X 60mm Horizontal 90º Bend 10 1.9 4.8 12.3 23.3 37.8PVC050WH 110mm X 54mm Horizontal 90º Bend 20 2.6 7.2 19.3 37.2 61

90º VERTICAL BENDS Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC560WH 204mm X 60mm Vertical 90º Bend 10 0.7 1.9 5.2 10.1 16.6PVC460WH 121mm X 60mm Vertical 90º Bend 10 2.1 5.7 14.8 28.1 45.7PVC060WH 110mm X 54mm Vertical 90º Bend 20 4.3 11.6 30.7 58.7 95.8

45º HORIZONTAL BEND Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC555WH 204mm X 60mm Horizontal 45º Bend 10 0 0.3 1.2 2.6 4.5

45º VERTICAL BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC575WH 204mm X 60mm Vertical 45º Bend 10 0 0.3 1.2 2.6 4.6

ADAPTORS Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC570WH 204mm X 60mm 125 Dia Round to Rect. Adaptor 10 0 0.3 1.1 2.5 4.3PVC470WH 121mm X 60mm 100 Dia Round to Rect. Adaptor 10 0.6 1.3 3.1 5.5 8.6PVC070WH 110mm X 54mm 100 Dia Round to Rect. Adaptor 20 1.1 2.8 7.2 13.6 22.2

FLAT CHANNEL END CAP Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC518WH 204mm x 60mm Flat Channel End Cap 1 0 0 0 0 0PVC018WH 110mm x 54mm Flat Channel End Cap 1 0 0 0 0 0

Page 32: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

PVC ROUND DUCTING

32 www.nuairegroup.com | [email protected]

RIGID ROUND PIPE 2M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC1200-4WH 100mm x 2m 100mm dia Rigid Pipe 2m Length 3 0.1 0.3 1 1.9 3.1PVC1200-5WH 125mm x 2m 125mm dia Rigid Pipe 2m Length 3 0 0.1 0.4 0.8 1.3PVC1200-6WH 150mm x 2m 150mm dia Rigid Pipe 2m Length 2 0 0 0.2 0.5 0.8

PIPE CONNECTORBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC493WH 100mm 100mm dia Pipe Connector 10 0 0 0 0 0PVC593WH 125mm 125mm dia Pipe Connector 10 0 0 0 0 0PVC693WH 150mm 150mm dia Pipe Connector 10 0 0 0 0 0

90º BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/s PVC490WH 100mm 90° Bend 100mm PVC 10 0.9 2.7 7.4 14.4 23.7PVC590WH 125mm 90° Bend 125mm PVC 10 0.5 1.4 4 7.9 13.6PVC690WH 150mm 90° Bend 150mm PVC 10 0.5 1.3 3.1 5.9 9.5

45º BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC491WH 100mm 45° Bend 100mm PVC 10 0.3 0.9 2.7 5.4 8.9PVC591WH 125mm 45° Bend 125mm PVC 10 0.2 0.5 1.4 2.7 4.5

INLINE BACKDRAUGHT SHUTTERBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC494WH 100mm Back Draught Shutter 100mm dia 10 12.2 19.6 32 45 58.6PVC594WH 125mm Back Draught Shutter 125mm dia 10 9.4 14.8 23.3 31.5 39PVC694WH 150mm Back Draught Shutter 150mm dia 10 7.1 11.2 17.4 23.4 29

PIPE HANGERBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC496WH 100mm Pipe Hanger 100mm 10 0 0 0 0 0PVC596WH 125mm Pipe Hanger 125mm 10 0 0 0 0 0PVC696WH 150mm Pipe Hanger 150mm 10 0 0 0 0 0

TEE PIECE (MALE FITTING)Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC492M 100mm Tee Piece 100 x 100 x 100 (Male fit) 4 0.7 1.6 4.0 7.4 11.8PVC592M 125mm Tee Piece 125 x 125 x 125 (Male fit) 1 0.5 1.0 2.2 3.9 6.1

REDUCING PIECEBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC119WH 125 ID-100 OD Circular Reducing Piece 10 0.6 1.5 3.6 6.6 10.6PVC121WH 150 ID-125/100 OD Circular Reducing Piece 10 0.4 1.4 4.2 8.4 14

ROUND HOSE CONNECTORBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC380WH 100mm Round Hose Connector 10 0 0 0 0 0

REDUCERBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sRED125X100 125mm x 100mm Reducer 125 x 100 (Male Fitting) 1 0.6 1.2 2.8 5 7.9RED150X100 150mm x 100mm Reducer 150 x 100 (Male Fitting) 1 0.5 1.3 3.1 5.9 9.5

TEE PIECE (FEMALE FITTING)Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sTP150X150X100 150mm x 100mm Tee Piece 150 x 150 x 100 (Female fit) 1 0.1 0.4 1 1.9 3

FLAT CHANNEL WALL PLATEBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC114-4WH 100mm Wall Plate 10 0 0 0 0 0PVC114-5WH 125mm Wall Plate 10 0 0 0 0 0

Page 33: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

PVC ROUND INSULATED DUCTING

33For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

INSULATED RIGID ROUND PIPE 1M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC100IRP-1 100 dia 1m 100mm dia Insualted Pipe 1m 3 0.3 0.5 0.9 1.3 1.7PVC125IRP-1 125 dia 1m 125mm dia Insualted Pipe 1m 3 0.1 0.2 0.4 0.65 0.9PVC150IRP-1 150 dia 1m 150mm dia Insulated Pipe 1m 2 0.05 0.1 0.2 0.35 0.55

INSULATED RIGID ROUND PIPE 2M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC100IRP-2 100 dia 2m 100mm dia Insulated Pipe 2m 3 0.6 1 1.8 2.6 3.4PVC125IRP-2 125 dia 2m 125mm dia Insulated Pipe 2m 3 0.2 0.4 0.8 1.3 1.8PVC150IRP-2 150 dia 2m 150mm dia Insulated Pipe 2m 2 0.1 0.2 0.4 0.7 1.1

INSULATED 90º BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC100IB90 100 dia 100mm dia Insulated 90º Elbow Bend 1 1.8 4.4 10.7 19.7 31.4PVC125IB90 125 dia 125mm dia Insulated 90º Elbow Bend 1 0.5 1.4 4 7.9 13PVC150IB90 150 dia 150mm dia Insulated 90º Elbow Bend 1 0.2 0.7 2 4 6.6

INSULATED 45º BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC100IB45 100 dia 100mm dia insulated 45º Elbow Bend 1 0.7 1.7 4.1 7.6 12.2PVC125IB45 125 dia 125mm dia insulated 45º Elbow Bend 1 0.2 0.5 1.4 2.7 4.5

INSULATED TEE PIECE Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC100ITP 100 dia 100mm dia Insulated Tee Piece 1 0.7 1.6 4.0 7.4 11.8PVC125ITP 125 dia 125mm dia Insulated Tee Piece 1 0.5 1.0 2.2 3.9 6.1PVC150ITP 150 dia 150mm dia Insulated Tee Piece 1 0.4 0.6 1.3 2.1 3.0

INSULATED FLAT CHANNELBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC5629WH 204mm x 60mm Insulated flat channel 2m 5 0.4 0.8 1.7 2.9 4.4PVC5628WH 204mm x 60mm Insulated flat channel 1.5m 5 0.3 0.6 1.3 2.2 3.3PVC5604WH 204mm x 60mm Insulated flat channel 1m 5 0.2 0.4 0.8 1.4 2.2

INSULATED 45O HORIZONTAL BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC5616WH 204mm X 60mm Insulated 45º Horizontal bend 10 0 0.3 1.2 2.6 4.5PVC5605WH 204mm X 60mm Insulated 90º Horizontal bend 10 0.6 1.6 4.1 7.9 12.8

INSULATED HORIZONTAL T-PIECEBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC5630WH 204mm X 60mm Insulated Tee piece 10 0.9 2.3 5.9 11.2 18.3

INSULATED 90O VERTICAL BENDBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC5612WH 204mm X 60mm Insulated 90º vertical bend 10 0.7 1.9 5.2 10.1 16.6

INSULATED CONNECTOR Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC5608WH 204mm x 60mm 204mm x 60mm 10 0 0 0 0 0

Insulated Connector

PVC FLAT INSULATED DUCTING

Page 34: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

PVC FLEXIBLE DUCTING

34 www.nuairegroup.com | [email protected]

FLEXIBLE RECTANGULAR DUCTING 3M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC333WH 114mm x 57mm Rectangular Flexible Duct PVC (3m length)1 1 2.7 7.2 13.9 22.7PVC433WH 121mm x 60mm Rectangular Flexible Duct PVC (3m length)1 0.4 0.8 1.7 2.8 4.3PVC533WH 211mm x 64mm Rectangular Flexible Duct PVC (3m length)1 0.2 0.6 1.5 2.6 4.1

FLEXIBLE ALUMINIUM DUCTING 5M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sFLD100 5m length 100dia Flexible Ducting Aluminium 100mm 1 0.2 6 1.7 3.4 5.6FLD125 5m length 125dia Flexible Ducting Aluminium 125mm 1 0.4 0.7 1.4 2.5 3.8FLD150 5m length 150dia Flexible Ducting Aluminium 150mm 1 0.2 0.3 0.6 1 1.5FLD200 5m length 200dia Flexible Ducting Aluminium 200mm 1 0.2 0.3 0.6 0.9 1.1

FLEXIBLE INSULATED DUCTING 5M LENGTH Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sFLDI100 5m length 100dia Insulated Flexible Ducting 100mm 1 0.2 0.6 1.7 3.4 5.6FLDI125 5m length 125dia Insulated Flexible Ducting 125mm 1 0.4 0.7 1.4 2.5 3.8FLDI150 5m length 150dia Insulated Flexible Ducting 150mm 1 0.2 0.3 0.6 1 1.5FLDI200 5m length 200dia Insulated Flexible Ducting 200mm 1 0.2 0.3 0.6 0.9 1.1

SEMI-RIGID ACOUSTIC DUCTING 3M LENGTHBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sSRDI100 3m length 100 dia Semi-rigid Acoustic ducting 100mm 1 0.3 0.6 1.5 2.5 4.4SRDI125 3m length 125 dia Semi-rigid Acoustic ducting 125mm 1 0.1 0.1 0.3 0.7 1.5SRDI150 3m length 150 dia Semi-rigid Acoustic ducting 150mm 1 0 0 0.1 0.3 1.3SRDI200 3m length 200 dia Semi-rigid Acoustic ducting 200mm 1 0 0 0 0 0.2

FLEXIBLE DUCTING 3M LENGTH Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC363WH 3m length 100dia Flexible Ducting 100mm 1 0.2 0.6 1.7 3.4 5.7

Page 35: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

GRILLES AND TERMINALS

35For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

Nuaire external grilles supplied White (RAL9010) as standard.

For alternative colours please replace the WH at the end of the product code with

BR for Brown (RAL 8017) l COT for Beige-Cotswold (RAL 1001) l TC for Red-Terracotta (RAL 8012) l All sizes are internal dimensions.

WHITE STEEL EXTRACT / SUPPLY VALVESBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sVS100 100 dia spigot Extract/Supply valve (white only) 1 7 14 34 85 130VS125 125 dia spigot Extract/Supply valve (white only) 1 6 10 19 35 55The above resistances are based on 10mm opening setting

FILTERED INLET GRILLEBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/s100IG 125mm x Filtered Inlet Grilles 1 5.8 14.5 37.1 70.2 113.8

125mm OD (white only) 100mm dia

LOUVRED GRILLE - WITH FLYSCREENBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC104WH 100mm dia spigot Louvred grille with flyscreen 20 3.4 7.9 18.9 34.6 54.8PVC504WH 125mm dia spigot Louvred grille with flyscreen 10 0.8 1.7 3.8 6.6 10.2PVC604WH 150mm dia spigot Louvred grille with flyscreen 10 0.7 1.3 2.8 4.9 7.4PVC105WH 110mm X 54mm Louvred grille with flyscreen 20 6.6 15.8 38.4 70.8 112.9

LOW RESISTANCE LOUVRED GRILLE - NO FLYSCREENBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC104LR 100mm dia spigot Low resistance louvred grille 20 0.6 1.6 3.9 7.3 11.8

AIR BRICKBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC501WH 201mm x 57mm Air brick - with shutter 20 6.4 10.1 17.3 26.1 36.5PVC505NS 201mm x 57mm Air brick - no shutter 20 2.2 5.5 13.9 26.0 41.8

DOUBLE AIR BRICKBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC905WH 204mm X 60mm Double airbrick 10 0.4 0.9 2.1 3.8 5.9

UNIVERSAL COWL Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC4411 100-150 dia Universal 100-160mm Cowl 1 0.5 0.9 1.7 2.6 3.7

fan spigot

GRAVITY SHUTTER WALL OUTLETBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC100WH 100mm dia spigot Wall outlet with gravity flaps 20 4.8 6.9 9.8 11.7 12.8PVC101WH 110mm X 54mm Wall outlet with gravity flaps 20 6.2 8.6 11.6 13.6 14.6PVC506WH 125mm dia spigot Wall outlet with gravity flaps 10 3.6 5.5 8.1 10.1 11.5

COWLED WALL OUTLET WITH DAMPERBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC102WH 100mm dia spigot Cowled wall outlet & damper 20 2.6 4.4 8.1 12.9 18.8PVC103WH 110mm X 54mm Cowled wall outlet & damper 20 1.8 3.8 9.0 16.5 26.4PVC502WH 125mm dia spigot Cowled wall outlet & damper 10 3.6 5.5 8.0 10.1 11.6

ROOF COWLBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/s4RC 100 dia spigot Roof Cowl 100mm 1 2.3 6 15.7 29.9 48.7

Page 36: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

GRILLES AND TERMINALS

36 www.nuairegroup.com | [email protected]

Nuaire external grilles supplied White (RAL9010) as standard.

For alternative colours please replace the WH at the end of the product code with

BR for Brown (RAL 8017) l COT for Beige-Cotswold (RAL 1001) l TC for Red-Terracotta (RAL 8012) l

WALL MOUNTING AIRBRICKBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCWALL/5 100mm dia Wall Mounting Airbrick

fan spigot with Reducer 1 10.9 17.7 30.5 45.6 62.9155mm Length of 110mm x 54 Duct and Rectangular to 100mm dia. Adaptor

WALL MOUNTING WEATHER LOUVRE Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCWALL/6 100dia fan spigot Low Resistance Wall Mounting

Weather Louvre and Telescopic 1 0.6 1.6 4 7.4 12Wall Duct 300-550mm

HIGH RISE Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC2447T 100mm dia High Rise 100mm Round Cowl 2447T 1 6.5 17.2 44.9 85.7 139.5

fan spigot

WALL COWLBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/s4WC 100 dia spigot Wall Cowl 100mm 1 2.2 6.2 16.4 31.6 51.5

WALL MOUNTING SHUTTERSBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCWALL/1 100mm dia Wall Mounting Gravity Operated 1 3.4 5.3 8.1 10.9 13.6

fan spigot Anti-backdraught Shutters andWall Duct 300-550mm

WALL MOUNTING LOUVREBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCWALL/2 100mm dia Wall Mounting Weather 1 3.7 9.6 24.9 47.4 77

fan spigot Louvre Complete with Fly Screenand Telescopic Wall Duct 300-550mm

WALL MOUNTING RECTANGULAR COWLED OUTLETBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCWALL/3 100mm dia Wall Mounting Rectangular 1 3.5 7.3 15.8 27.2 41.7

fan spigot Cowled Outlet Complete with Anti-backdraught Damper and Telescopic Wall Duct 300-550mm

WALL MOUNTING CIRCULAR COWLED OUTLET Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCWALL/4 100mm dia Wall Mounting Circular Cowled 1 2.3 6 15.4 29.2 47.2

fan spigot Outlet with Telescopic Wall Duct 300-550mm

Page 37: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

DUCTING ANCILLARIES

37For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

SLIMDUCT SILENCERBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sMEV-SIL10 204mm x 60mm Slimduct Silencer 1000mm 1 0.7 1.3 2.4 3.4 4.6MEV-SIL15 204mm x 60mm Slimduct Silencer 1500mm 1 0.2 0.8 2.3 4.6 7.7MEV-SIL21 204mm x 60mm Slimduct Silencer 2100mm 1 0.7 1.6 3.6 6.6 10.4For noise insertion details please contact Nuaire.

SLIMDUCT SILENCERBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCSIL-500 204mm x 60mm 204mm x 60mm 1 0.2 0.6 1.9 3.8 6.5

Slimduct Silencer 500mmPVCSIL-1000 204mm x 60mm 204mm x 60mm 1 0.2 0.8 2.3 4.6 7.7

Slimduct Silencer 1000mmPVCSIL-1500 204mm x 60mm 204mm x 60mm 1 0.7 1.6 3.6 6.6 10.4

Slimduct Silencer 1500mm

CONDENSATION TRAPBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sCONTRAP100 100mm Condensation trap 100mm dia 10 0.3 1.0 3.0 6.1 10.3CONTRAP125 125mm Condensation trap 125mm dia 1 0.3 1.0 3.0 6.1 10.3

INLINE CONDENSATE DRAINBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sMVHR-DRAIN 22mm Inline Condensate Drain 1 0 0 0 0 0

DYNO TIESBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sDT33 150-200 OD Dyno Ties Up To 200mm dia 1 0 0 0 0 0

DUCT ACCESSORIESBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCDSEAL N/A Duct Sealant 1 0 0 0 0 0PVC50TP45 N/A Aluminium Duct Tape 45m 1 0 0 0 0 0

CIRCULAR FIRE DAMPERBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sCFD-100 100mm Circular Fire Damper 100mm dia 1 5.6 8.7 15.6 24.8 36.2CFD-125 125mm Circular Fire Damper 125mm dia 1 0 0.5 2.6 5.8 10.2CFD-150 150mm Circular Fire Damper 150mm dia 1 0 0 0 1 1.9

CIRCULAR FIRE DAMPER AIR VALVE Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sVFD-100 100mm Circular Fire Damper 1 1 5.7 24.6 53.6 92.7

Air Valve 100mm diaVFD-125 125mm Circular Fire Damper 1 0 2.6 11.3 24.7 42.8

Air Valve 125mm diaVFD-150 150mm Circular Fire Damper 1 0 1.7 6.6 13.9 23.7

Air Valve 150mm dia

100 125

Page 38: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

DUCTING ANCILLARIES

38 www.nuairegroup.com | [email protected]

Wrap

Collar

FIRE WRAP Box Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVC087-110X50 110mm x 54mm Fire Wrap 1 0 0 0 0 0PVC587-204X60 204mm x 60mm Fire Wrap 1 0 0 0 0 0

PVC588 125mm Intumescent Fire Break 1 0 0 0 0 0

FW110X54 110mm x 54mm Fire Wrap 1 0 0 0 0 0FW204X60 204mm x 60mm Fire Wrap 1 0 0 0 0 0FWS110X54 110mm x 54mm Fire Collar 1 0 0 0 0 0FWS204X60 204mm x 60mm Fire collar 1 0 0 0 0 0

DUCT ACCESSORIESBox Resistance in PA

Part Number Duct Size Description Quantity @8l/s @13l/s @21l/s @29l/s @37l/sPVCFSEAL N/A Intumescent Duct Sealant 1 0 0 0 0 0

Page 39: Residential Ventilation Solutions - Nuaire · Residential Ventilation Solutions SYSTEM C / D PRODUCTS. ... • Ideal system for stairwell pressurisation • Added strength & stability

39For full details install Fan Selector from CD or visit www.nuairegroup.com/fanselector

NOTES