  • 7/30/2019 Report 130910 Edited

    1/26

    POWER SYSTEM

    PROTECTIONCOORDINATION

    REPORT FOR

    1 x 8MVA,66/11

    kV Transformer

    station and 11kV

    Distribution

    Client:

    M/s REID and TAYLOR, Nanjangud, Mysore

    Project:

    1 x 8MVA, 66/11 kV Transformer station and 11kV

    Distribution System

    EPC Contractor

    SIEMENS LTD, Chennai, India

    Compiled and Study made by

    Interface Electronics Pvt Ltd,

    5, Nana Street, T.Nagar, Chennai, India

    9884370326

  • 7/30/2019 Report 130910 Edited

    2/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    2

    Contents

    1 Introduction 3

    2 Network- and Single Line Diagrams 4

    3 In feed Data 4

    4 Single Line Diagram 5

    5 Device details 6

    6 Short circuit Current Details 7

    7 Detailed calculations for Transformer Protection 10

    8 Setting Details for Relay and Control Panel 11

    9 11 kV HT Switchgear Panel 18

    10 Time Current Character Curves 24

  • 7/30/2019 Report 130910 Edited

    3/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    3

    Introduction

    Interface Electronics pvt ltd was requested to prepare a protection co-ordination report for 1 X 8 MVA ,66/11 kV

    Transformer Station and 11 kV Distribution for the Project of Reid and Taylor at Nanjangud,Mysore .This Project is

    executed by M/s Siemens Ltd, CHENNAI.

    This report includes calculation results of the study 66/11switchgear.

    The system data for calculation are based on the provided data by M/s Siemens ltd, Chennai.

    The most important tool for documentation of over current protection co-ordination is Paladin Design Base 3.

    Typical grading paths have been chosen in a single line and in a current/time diagram the selectivity of the

    characteristic curves of the devices are shown.

    2 Power System Data

    The following single line diagrams, data collection and papers were used as data input and data base for this network

    calculation study.

    2.1 Network- and Single Line Diagrams

    Following diagrams /documents were made available to us : for making the study

    2.2 General Power System Data

    Nominal Voltage = 66 KV

    Nominal Frequency = 50 Hz

    Method of neutral point connection= Solidly earthed

    Nominal Voltage = 11 KV

    Nominal Frequency = 50 Hz

    Method of neutral point connection= Resistance earthed

    Nominal Voltage = 0.433 KV

    Nominal Frequency = 50 Hz

    Method of neutral point connection= Solidly earthed

  • 7/30/2019 Report 130910 Edited

    4/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    4

    2.3 Infeed Data

    Short-circuit power 3-phase @ Karakul SS 66 kV 1877 MVA

    Short-circuit power 3-phase @ Dhavanur SS 66 kV 664.7MVA

    Method of neutral point connection= Solidly Earthed

    Line tap is taken @ 4 km from Kadoka SS on the line between Kadakola and Dhavanur SS

    3.0 Protection Coordination

    Based on the short circuit calculations protection coordination study was carried out for this Project

    Short circuit currents calculated for each of the bus bar is tabulated.

    Selectivity of relays have been worked out only for 66 kV Relay and control Panel and for the Incomer of 11 kV

    Switchgear panel only .The settings for Outgoing feeders and the DG incoming Feeders have been retained with the

    existing settings.

    4.0 Conclusion

    Setting sketches for the over current devices have been performed for the 66/11 kV network The selectivity of the

    protection settings for characteristic feeders was verified with the protection grading diagrams prepared with

    software Paladin Design base 3 Generally, attention was given to provide the largest possible safety clearance

    between the individual protective devices..

  • 7/30/2019 Report 130910 Edited

    5/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    5

    Single Line Diagram

    GRID

    KPCL

    50

    51

    Relay_HVside

    Power Transformer

    5051

    Relay LVside

    11kV Switch Gea

    GENG1

    5051

    12

    DG1 Panel 14

    5051

    15

    Cable:DG1_11kVSWGR

    5051

    18

    GENG2

    5051

    21

    DG2 Panel

    5051

    23

    Cable:DG2_11k

    VSWGR

    5051

    26

    50

    51

    28

    Existing Transformer 1

    50

    51

    31

    Existing Transformer 2

    Kadakola SS

    Transmission Line

    Reid&taylor SS

    Cable:ss_11kVswgr

    43

  • 7/30/2019 Report 130910 Edited

    6/26

    Protection Coordination Report for 1

    6

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    6

    tribution System

    6

  • 7/30/2019 Report 130910 Edited

    7/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    7

    Short Circuit Report

  • 7/30/2019 Report 130910 Edited

    8/26

    Protection Coordination Report for 1

    8

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    8

    tribution System

    8

  • 7/30/2019 Report 130910 Edited

    9/26

    Protection Coordination Report for 1

    9

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    9

    tribution System

    9

  • 7/30/2019 Report 130910 Edited

    10/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    1 0

  • 7/30/2019 Report 130910 Edited

    11/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    1 1

    Setting Details for Relay and

    Control Panel

  • 7/30/2019 Report 130910 Edited

    12/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    1 2

  • 7/30/2019 Report 130910 Edited

    13/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    1 3

  • 7/30/2019 Report 130910 Edited

    14/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    1 4

  • 7/30/2019 Report 130910 Edited

    15/26

    Protection Coordination Report for 1

    1 5

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    1 5

    tribution System

    1 5

  • 7/30/2019 Report 130910 Edited

    16/26

    Protection Coordination Report for 1

    1 6

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    1 6

    tribution System

    1 6

  • 7/30/2019 Report 130910 Edited

    17/26

    Protection Coordination Report for 1

    1 7

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    1 7

    tribution System

    1 7

  • 7/30/2019 Report 130910 Edited

    18/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    1 8

    Setting DetailsFor

    11kV Switch Gear Panel

  • 7/30/2019 Report 130910 Edited

    19/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    1 9

  • 7/30/2019 Report 130910 Edited

    20/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    2 0

  • 7/30/2019 Report 130910 Edited

    21/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    2 1

  • 7/30/2019 Report 130910 Edited

    22/26

    Protection Coordination Report for 1

    2 2

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    2 2

    tribution System

    2 2

  • 7/30/2019 Report 130910 Edited

    23/26

    Protection Coordination Report for 1

    2 3

    8MVA, 66/11 kV Transformer Station and 11kV Dis

    2 3

    tribution System

    2 3

  • 7/30/2019 Report 130910 Edited

    24/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    2 4

    Time Current Characteristic

    Curves

  • 7/30/2019 Report 130910 Edited

    25/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    Compiled by Interface Electronics Pvt Ltd for Siemens Ltd, Chennai

    2 511000 Volt Phase Time-Current Characteristic Curves

    1 - Path 66 kV side relay-Transformer-11kV side relay

    09-13-2010

    08:15:20

    E:\Local Disk\siemens\ReidTaylor\reidtaylor.PDC

    .01

    .1

    1

    10

    100

    1000

    10000

    TimeinSeconds

    .5 1 10 100 1000 10000Current in Amperes X 10

    Relay_HVside

    47280SCA@

    11000V

    (Relay_HVside)

    8 MVA Trafo

    Inrush

    relay LVside

    4091SCA@

    11000V

    (RelayLVsid

    e)

  • 7/30/2019 Report 130910 Edited

    26/26

    Protection Coordination Report for 1x 8MVA, 66/11 kV Transformer Station and 11kV Distribution System

    2 611000 Volt Ground Time-Current Characteristic Curves

    1 - Path 66 kV side relay-Transformer-11kV side relay

    09-13-2010

    08:13:46

    E:\Local Disk\siemens\ReidTaylor\reidtaylor PDC

    .01

    .1

    1

    10

    100

    1000

    10000

    TimeinSeconds

    .5 1 10 100 1000 10000Current in Amperes X 10

    Relay_LV side

    100SCA@

    11000V

    (RelayLVsid

    e)

    Relay_HVside :7S

    33366SCA@

    11000V

    (Relay_HVside)