rebuilding cooling efficiencyener.co/wp-content/uploads/2016/07/rce.pdf · 2018. 7. 23. · in...
TRANSCRIPT
![Page 1: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/1.jpg)
Rebuilding Cooling
Efficiency A quantitative view
of the benefits of Ener.co®
![Page 2: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/2.jpg)
Rebuilding Cooling
Efficiency Our mission.
Existing buildings consume more than 60% of
the nation’s electricity. They deserve to receive
as much attention from the clean technology
community as new buildings do. Unfortunately,
they don’t. Our mission is to bring cutting edge
clean tech solutions to the existing buildings’
marketplace. We reduce energy consumption,
curtail capital expenses, trim maintenance costs,
and curb environmental impact while improving
building comfort and indoor air quality. And by
doing all of that, we enhance property values.
Air-cooled heat exchangers lie at the heart of
the energy efficiency of the air conditioning
system of any building. Ener.co’s flagship
product is Enercoat™, a graphene nano-
polymer coating that provides complete
protection from corrosion while simultaneously
enhancing the thermal conductivity of any air-
cooled heat exchanger.
Figure 1: Higher EER and lower peak demand
Volatile weather and environmental conditions
as well as airborne dirt and debris threaten
outdoor cooling equipment. The exposed
surface of an untreated heat exchanger coil
begins to corrode from day one. Just 10 years of
corrosion can impair thermal performance in a
coil by 30% to 50%. The American Society of
Heating, Refrigeration and Air-conditioning
Engineers (ASHRAE) estimates a 3 - 5% loss in
efficiency per year. Figures 1 and 2 below
illustrate significant improvements in efficiency
and cooling capacity– an over 10% reduction of
peak demand and electrical consumption and an
even greater increase in output and efficiency.
0
5
10
Efficiency Peak Demand
EER
, kW
2
0
50
100
150
Cooling Capacity Electrical Consumption
MB
H, k
Wh
Before
After
Figure 2: Restored capacity and reduced consumption
![Page 3: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/3.jpg)
Proven results.
When applied as part of our
restoration service, our coating
treatment is proven to bolster
energy efficiency ratios of air-
cooled systems from upwards of 20%, yielding a
simple payback in one to three years.
Performance has been tested globally by third
party engineers according to the IPMVP® Option
B – ECM isolation protocol. Applying the
Ener.co® coating on condenser coils of air-
cooled systems can effectively restore a unit’s
efficiency close to original performance. Further
loss in efficiency from heat transfer surface
deterioration can be averted, reducing energy
bills and the cost of repairing and replacing
equipment.
Who can benefit from Ener.co®?
Our coatings are suitable for use on all air-
cooled heat exchangers. Original equipment
manufacturers (OEMs) can spray-treat or dip
before product delivery. End users can have new
equipment in-factory treated. Existing HVAC
equipment can be treated as part of restoration
and maintenance projects.
Independent testing and
verification.
Our superior performance is test-verified for
thermal conductivity and diffusivity per ASTM
1461 as carried out by Dynalene Labs. Multiple
high-level efficiency demonstrations have
included data centers, hospitals, factories and
pharmaceutical facilities. Our products have
delivered on 3,000+ hours of the accelerated
corrosion test ASTM B117 conducted by
Intertek. Our products have been evaluated by
the EPA and state regulatory agencies for
component compliance and are low-VOC.
This document serves to reveal the findings
gathered from years of field monitoring that
establish the effectiveness of Ener.co® on air-
cooled heat exchangers. Peak-power demand
and electricity consumption reduction along
with restored cooling capacity and EER are
discussed in detail.
Figure 3: Condenser coil before Ener.co® treatment Figure 4: Condenser coil after Ener.co® treatment
3
![Page 4: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/4.jpg)
Curtail Your
Demand When it counts.
A building’s peak electrical demand
(kW) occurs during the hot summer
months when the outdoor
temperature and humidity climb
causing air-conditioning to run in high gear. Utilities
charge customers a premium for electrical power
during these peak periods, and so it is in the best
interest of energy managers and facility operators
to keep the building’s power demand profile to a
minimum.
Cooling systems can add up to 40% of a facility’s
maximum electrical demand. Our treatment process
has been proven to reduce the electrical demand of
air-cooled AC systems by up to
17% – a large share of a site’s load profile. Figure 5
below summarizes the findings for air-cooled AC
units that compare peak power draw before and
after the treatment process. The coil condition is
based on the average of three metrics based on a
scale from 1 to 5: the level of corrosion, amount of
debris, and fin alignment. Bubble area represents
the capacity of the unit ranging from 7.5 to 80 tons.
Typically, poorer conditions offer larger
opportunities for demand reduction.
0%
5%
10%
15%
20%
2 2.5 3 3.5 4 4.5
Pea
k kW
Red
uct
ion
Coil Condition
4
Figure 5: Peak power demand reduction vs. coil condition
![Page 5: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/5.jpg)
Healthier coils mean healthier compressors and fans.
Component break-down of fan and compressor energy use for an air-cooled chiller is presented in Figure 6 below. Of the total peak kilowatt reduction of 10%, 87% of the drop in power was compressor power, and the other 13% was fan power. Figure 6 below summarizes the findings. Following our treatment, an increase in the heat rejection capacity of the condenser coil results in a lower operating
head pressure of the compressors, and therefore a reduction of their power draw. Further, realignment of the aluminum fins increases the aerodynamic efficiency of the coil allowing the condenser fans to pass the same amount of air at a lower power draw.
And lower power draw equates to less compressor
and fan use, and therefore less wear and tear on
the equipment. Owners could expect savings in life
extension of not only the coil itself, but also the
compressors and fans.
Figures 6 (top), 7 (left), and 8 (right): Electrical sub-metering summary – reduction by component
14.7 16.3 14.3
5.76.0
5.7
0
5
10
15
20
25
Catalog Before After
kW
Controls
Fan
Compressor
10
12.5
15
17.5
55°F 60°F 65°F 70°F 75°F
kW
Outside Air Temp.
Compressor Power
5
5.5
6
6.5
55°F 60°F 65°F 70°F 75°F 80°F
kW
Outside Air Temp.
Fan Power
Before
After
5
![Page 6: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/6.jpg)
Reclaim Your CapacityA ton today, gone tomorrow.
Our treatment technology offers a proven solution
to revive cooling systems and recover lost
capacity. Figure 9 below logs the cooling capacity
of a five-ton, 20-year-old AC unit during the weeks
both preceding and following treatment. Sensible
capacity reflects the energy drop in the air
temperature. Latent capacity removes moisture
from the air.
The unit in Figure 9 was unable to meet the
cooling load and left the conditioned space warm
and humid. After the treatment, the unit regained
its original capacity and maintained a cool and dry
building space.
Remove moisture and improve
thermal comfort.
Latent cooling capacity has been
demonstrated to improve vastly
after treatment. A healthier heat
exchanger coil results in a cooler, drier, and
more comfortable space per the ASHRAE 55
human thermal comfort index. Indoor air quality
is vastly improved. An increased heat rejection
capacity of the condenser coil promotes a lower
evaporator coil temperature due to extra
subcooling of refrigerant. The air entering this
coil from the conditioned space is more prone
to reaching its dew point temperature, and the
result is the removal of its moisture (latent
heat).
Figure 9: Increased sensible and latent cooling capacity for a 20-year-old five ton unit (two week comparison)
°F
20°F
40°F
60°F
80°F
100°F
0
2.5
5
7.5
Ton
s
Sensible Latent Outside Air Temp.
AfterBefore
6
![Page 7: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/7.jpg)
The moisture removal chart shown in Figure 10
below shows a large increase in moisture removal
measured in gallons per hour after the treatment
based on the enthalpy of the airstream entering the
cooling coil. Further evidence can be seen Figure 11
that shows the psychrometric properties of air
leaving the evaporator coil before and after the
treatment. The ability of the evaporator to remove
moisture from the passing airstream can be
measured by the tendency of air to approach the
100% relative humidity saturation line.
Figure 10 (left) and Figure 11 (right): Improvement of latent heat removal and psychrometric properties of air leaving the evaporator coil
0
2
4
6
8
22 24 26 28
Gal
lon
s o
f W
ater
Rem
ove
d p
er
Ho
ur
Enthalpy of Air Entering the Evaporator Coil, Btu/lbm
0.004
0.006
0.008
0.010
0.012
40°F 45°F 50°F 55°F 60°F 65°F 70°F
Hu
mid
ity
Rat
io (
lbw
/lb
da)
Dry Bulb Temperature
Before
After
7
![Page 8: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/8.jpg)
Optimize Your System Lower kWh and more Btus.
Formulated to cut energy use, slash operating costs,
and curtail environmental impact, Ener.co’s
products offer a premium energy efficiency
investment for owners who seek superior
performance for their building’s cooling systems.
Engineered to ensure quality performance, the
coating treatment has been proven to nearly double
the energy efficiency ratio of air-cooled cooling
equipment per AHRI testing protocols.
Our monitoring studies reveal that the
enhancement of thermal conductivity of the
air-cooled heat exchanger permits AC units to
operate at a lower part-load ratio more often
than before
the treatment.
Figure 12 below
provides a data overlay
of one week each before and
after the treatment with comparable weather
conditions. Despite warmer outdoor
temperatures, the unit was able to ramp-down
the required cooling staging. The results are
smaller peaks of demand (kW), less total
energy consumed (kWh), and a more
comfortable building environment.
Figure 12: Comparison of energy consumption one week before and after treatment
0
10
20
30
40
50
60
70
80
90
0
5
10
15
20
25
°FkWh
Before kWh After kWh Before Outside Temp. After Outside Temp.
1st stage
2nd stage
3rd stage
8
8
4th stage
![Page 9: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/9.jpg)
Advanced technology, uncompromised performance.
Our coatings deliver unrivaled performance under
all climate conditions and in all environments.
Reduced energy consumption and boosted cooling
capacity result in nothing less than a cooling system
enhanced to perform at peak levels of energy
efficiency. AC unit performance shown in Figure 13
shows the vastly improved
cooling performance – EERs rise
up to 20% after the treatment.
Higher-EER systems require less
energy to meet the same cooling load.
Figure 13 (left) and Figure 14 (right): Improvement of EER and reduction of power draw
Performance that Persists
5
6
7
8
9
10
70°F 75°F 80°F 85°F
EER
Outside Air Temp.
15
16
17
18
19
70°F 75°F 80°F 85°F
kW
Outside Air Temp.
before
after
9
![Page 10: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/10.jpg)
The Ener.co® Advantage. Traditional intelligence suggests that
corrosion prevention coatings come
at the cost of decreased thermal
conductivity of the heat exchanger
surface. This is not the case with our coatings; they
all enhance thermal conductivity and halt corrosion
for years to come in the harshest of outdoor
environments. Our coatings eliminate corrosion at
aluminum fins, copper tubes, and the critical fin-to-
tube bond, a bond notoriously known for being the
weakest link in the heat-flux pathway through the
coil assembly. This fin-tube bond is restored to its
optimal condition to secure cooling performance
and indoor thermal comfort.
In summer 2010, a then four-year-old 60-ton
rooftop air-cooled chiller was monitored for energy
use to examine the immediate effectiveness of our
treatment. Before measurements were taken, the
facility performed their own routine cleaning of the
coil assembly. The unit was later treated in the fall
of 2010. The results after the first year of
monitoring evaluation demonstrate that the
treatment immediately reduces the kW load of a
well-maintained unit. The results are seen in Figures
6, 7, and 8 on page 5. Compressor power reduction,
Figure 7, is reshown here as Figure 15. Chiller 1
benefited from a 10% immediate reduction in
power draw (2.3 kW), the lion’s share of savings,
87%, being compressor power reduction (2.0 kW).
Long-term benefits – 2017 update
Six years later in 2017, continuous monitoring
shows that the level of performance reached
immediately after the treatment has been
maintained, and that the reduction in compressor
power endured the five year period. Figure 16
below shows Figure 15 with the addition of 2017
data.
10
10
12.5
15
17.5
55°F 60°F 65°F 70°F 75°F
kW
Outside Air Temp.
Compressor Power - Immediate Reduction
Figures 15 and 16: Permanent reduction in compressor power draw before treatment, after treatment, and 5 years after treatment
10
12.5
15
17.5
55°F 60°F 65°F 70°F 75°F
kW
Outside Air Temp.
Compressor Power - Permanent Reduction
Before - 2010
After - 2011
2017
![Page 11: Rebuilding Cooling Efficiencyener.co/wp-content/uploads/2016/07/RCE.pdf · 2018. 7. 23. · In summer 2010, a then four-year-old 60-ton rooftop air-cooled chiller was monitored for](https://reader036.vdocuments.us/reader036/viewer/2022071420/61197fc4fb93a82f49367107/html5/thumbnails/11.jpg)
Reduced Energy Cost$2,196,853
Savings$482,236
Projected Cumulative Savings10 Years
Case Study
Iconic Printing Factory – Flushing, NY
In the fall of 2016, Ener.co performed its comprehensive
energy saving retrofit measure on the condenser coils
part of a mission-critical printing factory equipped with
3,475 tons of air-cooled RTUs in Flushing, NY. The New
York State Energy and Research Development Authority
(NYSERDA) was responsible for determining the energy
savings under M&V IPMVP® Option B Protocol.
Treatment resulted in verified energy savings of 18%,
improved airflow, enhanced heat transfer, and a
permanent reduction power consumption.
Real-time monitoring shows that the project reached its
first-year savings projection and is on track to save the
facility an additional $482,236 over the next ten years.
Key metrics include:
First year energy use reduction: 343,474 kWh (18%)
Average annual savings: $48,224
Peak power reduction: 117 kW
Project incentive awarded through NYSERDA’s
Industrial and Process Efficiency program
In addition to reducing their energy bills, the customer
reduced their maintenance costs while avoiding a $7
million replacement cost for a new set of RTUs.
Energy cost without treatment $2,679,089
$-
$100,000
$200,000
$300,000
20
16
20
17
20
18
20
19
20
20
20
21
20
22
20
23
20
24
20
25
An
nu
al
Co
olin
g C
ost
Lifetime Energy Cost Comparison
With treatment without treatment