REAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda Palm Desert, CA 92260 PREPARED EXCLUSIVELY FOR: Jack And John Doe INSPECTED ON: Wednesday, February 3, 2016 Bruce Carmichael, Inspector Advantage Inspection Professional, LLC 73118 Ajo Lane, Palm Desert, CA 92260 760-835-8772 www.advantagesocal.com. [email protected] Report # 110880348

Upload: others

Post on 22-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

REAL ESTATE INSPECTION REPORT

LOCATED AT:63632 Alameda

Palm Desert, CA 92260

PREPARED EXCLUSIVELY FOR:Jack And John Doe

INSPECTED ON:Wednesday, February 3, 2016

Bruce Carmichael, InspectorAdvantage Inspection Professional, LLC73118 Ajo Lane, Palm Desert, CA 92260

760-835-8772www.advantagesocal.com. [email protected]

Report # 110880348

� �

Page 2: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

Wednesday, February 3, 2016Jack And John Doe

63632 AlamedaPalm Desert, CA 92260

Dear Jack And John Doe,

We have enclosed the report for the property inspection we conducted for you on Wednesday, February 3, 2016 at:63632 Alameda

Palm Desert, CA 92260

Our report is designed to be clear, easy to understand, and helpful. Please take the time to review it carefully. If there is anything you would like us to explain, or if there is other information you would like, please feel free to call us. We would be happy to answer any questions you may have.

Throughout the report, you'll find special symbols at the front of certain comments. Below are the symbols and their meanings:

� = Needed Evaluation/Repairs: Conditions noted warrant further evaluation by a specialist in the appropriate trade(s).

� = Safety Concerns: Conditions noted that may pose a hazard to humans, the building or both.  These conditions warrant further evaluation by a specialist in the appropriate trade(s).

� = Recommended Repairs/Maintenance: Conditions noted in need of maintenance, repair, replacement or further evaluation. We recommend that all corrections be made by specialist in the appropriate trade(s).

� = Recommended Upgrades: Systems and/or components that may have not been available and or not required or have been improved since the building was constructed. Upgrades are not the responsibility of the seller and are reported as a courtesy to our clients. We recommend that all upgrades be made by specialists in the appropriate trade(s).

� = Did not test or evaluate this unit, component or area of property.

� = The term where used in this report was designed to draw your attention to a specific condition or component of a system.  While corrective action may not be warranted, we felt it was important that you be aware of its existence.

We thank you for the opportunity to be of service to you.

Sincerely,

Bruce Carmichael, Certified American Society of Home Inspectors and Certified California Real Estate Inspection Association InspectorAdvantage Inspection Professional, LLC 760-835-8772. www.advantagesocal.com

� ⚏

Page 3: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

Table of Contents♾☿Introduction............................................................…...............................................................................1

☿Inspection Info.......................................................…...............................................................................2

☿Emergency Disconnect Locations.........................…...............................................................................3

☿Exterior Areas........................................................…...............................................................................4

☿Exterior - Foundation............................................…...............................................................................6

☿Roof System..........................................................…...............................................................................8

☿Attic.......................................................................….............................................................................10

☿Garage..................................................................….............................................................................12

☿Electrical Systems.................................................….............................................................................14

☿Sub Panel..............................................................….............................................................................16

☿Plumbing Systems.................................................….............................................................................16

☿Water Heater.........................................................….............................................................................18

☿Heating System.....................................................….............................................................................21

☿Air Conditioning System........................................….............................................................................25

☿Heating /AC Distribution Systems.........................….............................................................................30

☿Fireplace................................................................….............................................................................31

☿Windows & Doors..................................................….............................................................................32

☿Interior Areas.........................................................….............................................................................33

☿Kitchen - Appliances..............................................….............................................................................34

☿Bathroom...............................................................….............................................................................38

☿Laundry..................................................................….............................................................................44

☿Outdoor Cooking...................................................….............................................................................45

☿Water Features/Fountains.....................................….............................................................................46

☿Pool/Spa & Equipment..........................................….............................................................................47

☿Beyond The Scope................................................….............................................................................56

Page 4: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

Introduction☿We have inspected the structural components and mechanical systems for signs of significant non- performance, excessive or unusual wear and general state of repair. The following report is an overview of the conditions

In the report, there may be specific references to areas and items that were inaccessible. We can make no representations regarding conditions that may be present but were concealed or inaccessible for review. With access and an opportunity for inspection, reportable conditions may be discovered. Inspection of the inaccessible areas will be performed upon arrangement and at additional cost after access is provided.

We do not review plans, permits, recall lists, and/or government or local municipality documents. Information regarding recalled appliances, fixtures and any other items in this property can be found on the Consumer Product Safety website. These items may be present but are not reviewed.

Our recommendations are not intended as criticisms of the building, but as professional opinions regarding conditions present. As a courtesy, the inspector may list items that they feel have priority in the Executive Summary portion of the report. Although the items listed in this section may be of higher priority in the opinion of the inspector, it is ultimately the client's responsibility to review the entire report. If the client has questions regarding any of the items listed, please contact the inspector for further consultation.

Lower priority conditions contained in the body of the report that are neglected may become higher priority conditions. Do not equate low cost with low priority. Cost should not be the primary motivation for performing repairs. All repair and upgrade recommendations are important and need attention.

This report is a "snapshot" of the property on the date and time of the inspection. The structure and all related components will continue to deteriorate/wear out with time and may not be in the same condition at the close of escrow.

All recommendations in this report should be addressed PRIOR TO THE END OF THE CLOSE OF ESCROW. This report is not intended for use by anyone other than the client named herein. No other persons should rely upon the information in this report. Client agrees to indemnify, defend and hold inspector harmless from any third party claims arising out of client's unauthorized distribution of the inspection report.

By accepting this inspection report, you acknowledge that you have reviewed and are in agreement with all of the terms contained in the inspection agreement provided by the inspector who prepared this report.

Page 1

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 5: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

Inspection Info☿BUILDING TYPESingle family with a pool

REPORTED AGE2000.

CURRENT WEATHERClear

WEATHER LAST 24HRSRain

SOILThe ground was dry

TEMPERATURE65-70 degrees

PRESENTBuyer(s)

INSPECTORBruce Carmichael, Certified ASHI & CREIA Inspector

SPACE BELOW GRADEConcrete Slab

UTILITIES STATUSAll utilities on

Page 2

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 6: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

Emergency Disconnect Locations☿WATER METERWater meter is located at the front of the subject property by the street.

MAIN WATER SHUT OFF VALVEWater shut off valve is located at right side of the subject property

MAIN ELECTRICAL METER & DISCONNECTElectrical Meter and Disconnect  is located at Main Panel exterior right side of the subject property

Page 3

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 7: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

GAS SHUT OFF AND METERMeter and Shut Off valve for gas is located at right side of the subject property

Exterior Areas ☿

! This inspection is not intended to address or include any geological conditions or site stability information. For information concerning these conditions, a geologist or soils engineer should be consulted. Any reference to grade is limited to only areas around the exterior of the exposed areas of the foundation or exterior walls. This inspection is visual in nature and does not attempt to determine drainage performance of the site of the condition of any underground piping, including municipal water and sewer service piping or septic systems. Decks and porches are often built to close to the ground, where no viewing or access is possible. These areas as well as others are too low to enter, or in some case not accessible, are excluded from the inspection and are not address in the report. We recommend that inquiry be made with the seller about knowledge or any prior foundation or structural issues or repairs

DRIVEWAYS TYPE/CONDITIONConcreteAppeared to be in good condition at time of inspection.

WALKWAYS TYPE/CONDITIONConcreteAppeared to be in good condition at time of inspection.

PATIOS TYPE/CONDITIONConcreteAppeared to be in good condition at time of inspection.

FENCES & GATESConcrete Block with Metal GatesVisible areas appear to be in good condition

GRADING-SURFACE DRAINAGE SITE & CONDITIONFlat site, Drainage of property appears to be adequate

Page 4

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 8: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

SPRINKLER SYSTEM NOTE

� Sprinkler systems and timers are not tested and not part of this inspection, inquire with seller or gardner about operation. Inspector will only inspect visible valves and pipes for leaks.

SPRINKLER SYSTEMS

� Sprinkler supply line is leaking, repair at front

LANDSCAPING

� Vegetation was planted too close to the house at the left side

� �

Page 5

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 9: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

EXTERIOR MISTER SYSTEMSManual system was turned on and found in good working condition.

� �

Exterior - Foundation☿

! Areas hidden from view by finished walls or stored items can not be judged and are not part of this inspection. Minor cracks are typical in manny foundations and most do not represent a structural problem. If major cracks are present along with bowing, we routinely recommend further evaluation be made by a qualified structual engineer. All exterior grades should allow for surface and roof water to flow away from the foundation. All concrete floor slabs experience some degree of cracking due to shrinkage in the drying process. In most instances floor coverings prevent recognition of cracks or settlement in all but the most severe cases. Where carpeting and floo coverings are installed, the material and condition of the flooring underneath cannot be determined. Some foundation issues may also be safety hazards, all recommendation should be addressed prior to the close of escrow.

EXTERIOR WALL STRUCTUREExterior walls are wood framed

EXTERIOR WALL MATERIALStucco

EXTERIOR WALLSAppeared to be in good condition at time of inspection

EXTERIOR EAVES, SOFFITS & FASCIAS MATERIALStucco

Page 6

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 10: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

EXTERIOR EAVES, SOFFITS & FASCIAS

� Cracks noted at exterior soffits

� �

� Damage noted at soffit. We recommend further review and repairs by a qualified specialist in the appropriate trade.

� �

Page 7

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 11: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

STUCCO WEEP SCREED

� Soil grade is blocking the stucco weep screed at bottom of stucco wall at left There should be a minimum 3 " maximum 6 " inches between the soil and the bottom of the weep screed. This will allow the wall to ventilate and drain properly.

SLAB ON GRADEConcrete slab noted. Slab is not visible due to carpet and/or floor covering - no readily visible problem are noted.

SLAB ON GRADE ANCHOR BOLTSAnchor Bolts Not visible, could not determine.

Roof System☿

! The foregoing is an opinion of the general quality and condition of the roof material. The underlayment of the roof may be blocked from view and could not be inspected. The inspector cannot and does not offer an opinion or warranty as to whether the roof leaks or may be subject to future leakage. This report is issued in consideration of the foregoing disclaimer. The only way to determine whether a roof is absolutely water tight is to observe it during a prolonged rainfall. Many times, this situation is not present during the inspection. Recommend asking the seller for further information on the roof and if they have had any leaks and or calling a State Qualified Roofing Contractor to obtain a roof certification before the close of escrow.

ROOF STYLESloped

ROOF TYPETile

ROOF ACCESSWalked on roof

Page 8

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 12: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

ROOF CONDITION

� Cracked tiles noted, We recommend the advice and services of a qualified Roofing Contractor

� �

� Loose tile noted. We recommend the advice and services of a qualified Roofing Contractor

FLASHINGSMetal

� Mastic seal is separated at flashings ,re sealing is needed. We recommend the advice and services of a qualified Roofing Contractor

� �

Page 9

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 13: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Clean debris from valley flashing to allow for proper drainage. We recommend the advice and services of a qualified Roofing Contractor

Attic☿ATTIC METHOD OF INSPECTIONEntered inside and inspected all of the accessible areas, Some areas were not accessible and not inspected.

ATTIC CEILING AND ROOF STRUCTUREEngineered Truss system

Visible portions of roof truss system appeared to be in good condition.

Page 10

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 14: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

ATTIC LEAK EVIDENCEThere is no current visible evidence of leakage into the attic area.

ATTIC ELECTRICALVisual attic electrical appeared to be in good condition.

ATTIC LIGHT(S)Attic light(s) appeared to be in good working condition

ATTIC INSULATIONFiberglass Batts.

Appeared to be in good condition.

ATTIC VAPOR RETARDERSNo vapor retarder installed.

Page 11

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 15: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

ATTIC VENTILATION

� Thermostatically controlled attic exhaust fan(s) noted in attic. Did not test.

ATTIC EXHAUST FAN DUCTINGThe bathroom exhaust fans are ducted through the roof.

Garage☿

! Notice: Determining the heat resistance rating of firewalls is beyond the scope of this inspection. Flammable materials should not be stored within closed garage areas.

TYPEAttached 2 car

ELECTRICAL SWITCHES FIXTURES & RECEPTACLESSwitche(s) and light fixture(s) appeared to be in good working condition at time of inspection

� J-box covers loose, further review and repair by qualified Electrical Contractor.

� �

Page 12

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 16: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

GROUND FAULT CIRCUIT INTERRUPTER (GFCI) Ground fault circuit Interrupter (GFCI) receptacle(s) were noted and tested by pushing the test button on the outlet  to see if outlet(s) went dead. Outlet appeared to test properly at time of inspection, recommend client test weekly to insure proper protection

ROOF/CEILINGSAppeared to be in good condition at time of inspection

FIRE SEPARATION WALLS/CEILINGS

� Openings/damaged noted to fire separation ceiling, repair any openings with approved materials to restore its fire rating, this is a safety hazard, correction is needed. We recommend further review and repairs by a qualified specialist in the appropriate trade.

DOOR TO LIVING SPACESolid core door installed, door closer operational, door self latches and weather-stripping is in good condition.

� A door stop has been installed on the self closing fire rated / solid door, these doors are designed to self close to prevent fires from entering the house and allow occupants to safely escape. We recommend that new owners remove or be aware that the door should never be left open except when entering or leaving the house.

WALLSNo damage noted to visible portions of walls

Page 13

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 17: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

FLOORSVisual examination of unobstructed areas of floor showed no damage at time of inspection

GARAGE EXTERIOR DOORSDoor appeared to be in good condition at time of inspection

GARAGE DOOR(S) Appeared to be in good working condition at time of inspection

� Minor cosmetic damage is noted

GARAGE OPENER(S) Automatic door opener(s)- operational

GARAGE DOOR(S) SAFETY BEAMSInfra-Red Sensors beams were tested and appeared to be in good working condition at time of inspection.

Electrical Systems☿

! An electrical system consist of the service, distribution, wiring and convenience outlets (switches, lights and receptacles). Our examination of the electrical system includes the exposed and accessible conductors, branch circuitry, panels, over current protection devices and a random sampling of convenience outlets. We look of adverse conditions such as improper installation, exposed wiring, running splices, reversed polarity and circuit protection devices. We do not evaluate fusing and/or calculate circuit loads. The hidden nature of the electrical system prevents inspection of every length of wire. Any electrical repairs should be done by a qualified company. The power to the entire house should be turned off prior to beginning any repairs, no matter how trivial the repairs may be. Operation of time clock motors is not verified. Inoperative light fixtures offen lack bulbs or have dead bulbs installed. Light bulbs are not changed during the inspection. We make every effort to test all accessible receptacles, swithes and fixtures, some may not have been accessible during the inspection and were not tested.

SERVICE UTILITY STATUSElectric was on

SERVICE Under ground service laterals are not visible and not inspected.

DISCONNECT TYPE & PANEL RATINGBreakers, Amperage rating 120/240 volt system, panel rated at 200 Amperes. Main breakers is 200 amps

MAIN PANEL Panel cover was removed and panel was inspected. Circuit and wire sizing correct so far as visible

Page 14

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 18: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Recommend trimming plants to allow for access to electrical panel.

MAIN ELECTRICAL PANEL GROUNDINGGrounding system is present

SERVICE WIRING CONDUCTORSCopper

BRANCH WIRING #1Copper, non-metallic sheathed cable (Romex)

MAIN ELECTRICAL BONDINGThe hot and cold water lines were bonded at the water heater

SMOKE DETECTORSNoted, but not tested, testing smoke detectors is beyond the scope of the inspection.

CARBON MONOXIDE DETECTORSCarbone Monoxide Detector(s) present, units are not tested and not part of this inspection. For minimum security, a CO Alarm should be centrally located outside of each separate sleeping area in the immediate vicinity of the bedrooms.  The Alarm should be located at least 6 inches (152mm) from all exterior walls and at least 3 feet (0.9 meters) from supply or return vents.

INTERIOR LIGHTING SWITCHES AND FIXTURESAll accessible switches and light fixtures appeared to be in good working condition

INTERIOR RECEPTACLESAll accessible receptacles appeared to be in good working condition

INTERIOR CEILING FANSFan(s) were in good working condition at time of inspection. Reverse feature is not tested

CLOSET FIXTURESCloset light(s) appeared to be in good working condition at time of inspection

Page 15

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 19: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

SECURITY SYSTEMS

� Security systems present but not tested, inquire with seller about alarm system and the company that monitors the system

EXTERIOR LIGHTING SWITCHES AND FIXTURESAll accessible switches and light fixtures appeared to be in good working condition.

EXTERIOR RECEPTACLESExterior receptacles are protected from garage GFCI receptacle.

EXTERIOR CEILING FANSFan(s) were in good working condition at time of inspection

EXTERIOR CONDUIT/WIRING

� Improper wiring noted at rear, Recommend further review and repair by qualified Electrical Contractor.

� �

Sub Panel☿SUB PANELSPanel cover was removed and panel was inspected. Circuit and wire sizing correct so far as visible. Grounding bar and neutral bars are properly separated at sub panel.

Plumbing Systems☿

! All under ground or hidden piping related to water supply, water drainage, venting, waste or sprinkler systems are excluded from this inspection. If we can not see is we can not report on it. Leakage or corrosion in underground piping cannot be detected by a visual inspection. It is impossible to determine if the house is connected to the city sewer system or septic. Contact the city for information. Water quality or hazardous material (lead) testing can be done by other companies. Recommend all plumbing repairs be done by a qualified company

Page 16

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 20: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

MAIN WATER SERVICE UTILITY STATUSWater was on

FUEL SYSTEM UTILITY STATUSGas was on

MAIN WATER PIPING TYPE/CONDITION CopperVisible section of piping appeared to be in good condition at time of inspection, no leaks were noted.

MAIN WATER SHUT OFF VALVEWater shut off valve present and tested, no leaks were present at or around valve area.

WATER PRESSUREWater pressure was within the recommended range of 40 to 80 psi.

WATER SUPPLY TYPE/CONDITIONVisible lines appear to be copperVisual sections of pipes appear to be in good condition at time of inspection

HOSE FAUCETSSample operated, appeared serviceable

WASTE LINES TYPE/CONDITIONPlastic ABSVisible sections of pipes appeared to be in good condition at time of inspection

WASTE LINES CLEAN OUTSClean out for waste line was present at exterior and interior of house

VENT PIPING TYPE/CONDITIONPlastic ABS

Page 17

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 21: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Plumbing vent(s) should terminate at least 6 to 12" above the roof surface, We recommend further review and repairs by a qualified specialist in the appropriate trade.

FUEL SYSTEMS TYPENatural GasSystem appeared to be in good condition at time of inspection

GAS PIPING TYPE/CONDITION Black PipeVisual sections of pipes appear to be in good condition at time of inspection

WATER SOFTENERSExterior

� Water softener was noted, but only inspected for leaks, inquire with seller/owner about operation and maintenance unit.

Water Heater☿

! The average life span of most water heaters is 12 to 15 years if they are properly maintained. Some may last longer and some may fail sooner.

Page 18

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 22: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

WATER HEATER BRANDA.O. Smith

WATER HEATER AGE2000.

WATER HEATER SIZE50 Gallons

WATER HEATER TYPENatural Gas

WATER HEATER VENTING SYSTEMFlue vent intact and venting properly.

WATER HEATER TANK

� Rumbling, Cracking and Popping heard at water heater.

WATER HEATER TANK DRAIN

� Remove handle or cap tank drain for safety to prevent accidental draining by a small child.

Page 19

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 23: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

WATER HEATER SUPPLY PIPINGSupply pipes were in good condition at time of inspection. A water shutoff valve is installed

WATER HEATER SEISMIC BRACINGSeismic Straps installed.

WATER HEATER COMBUSTION AIRA combustion air supply for the water heater was present.  Adequate ventilation for all fuel burning appliances is vital for their safe operation.

WATER HEATER ENERGY SUPPLYAn easy operate hand shut-off valve is installed on the gas line.  A flexible gas line is installed.

WATER HEATER TPR VALVEA temperature & pressure relief valve  and discharge line were installed for safety. These open only if water pressure builds up to unsafe levels inside the water heater, valves are never tested because once they are tripped they need to be replaced.

WATER HEATER CONTROLS

� The temperature control was set to the "high/very hot position". Excessively high water temperatures can be dangerous and inefficient.  We recommend the temperature setting be lowered to the manufacture' s recommended settings.

WATER HEATER BASEFunctional

WATER HEATER ELEVATIONUnit is properly elevated.

WATER HEATER CONDITION

� Unit is 16 years old, while still functioning, it is beyond its service life and should be replaced before it leaks and causes damage.

Page 20

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 24: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

Heating System☿

! The inspector is not equipped to inspect furnace heat exchangers for evidence of cracks or holes, as this can only be done by dismantling the unit. This is beyond the scope of this inspection. Some furnaces are designed in such a way that inspection is almost impossible. Safety devices are not tested by the inspector. NOTE: Asbestos materials have been commonly used in heating systems. Determining the presence of asbestos can ONLY be preformed by laboratory testing and is beyon the scope of the home inspection. Thermostats are not checked for calibration or timed functions. Adequacy, efficiency for the even distribution of air throughout a building cannot be addressed by a visual inspection. Electronic air cleaners, humidifiers and de humidifiers are beyond the scope of the inspection. Have these systems evaluated by a qualified company. Subjective judgment of system capacity is not part of the inspection. Normal service and maintenance is recommended every 6 months.

#1 / Attic Heating System

HEATING SYSTEM THERMOSTAT SETHeater was set to 67

HEATING SYSTEM BRANDYork

HEATING SYSTEM APPROXIMATE AGE2000.

HEATING SYSTEM BTU/HR40,000

HEATING SYSTEM SYSTEM TYPEForced Air Mid-Efficiency Gas Furnace

HEATING SYSTEM FUEL TYPENatural Gas

HEATING SYSTEM GAS CONNECTIONGas connection appears serviceable.

Page 21

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 25: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

HEATING SYSTEM PUMP/BLOWER FANAppears to be in good working condition at time of inspection

HEATING SYSTEM COMBUSTION AIRCombustion air supply adequate

HEATING SYSTEM VENTING SYSTEMThe combustion and exhaust venting appears to be in good condition

HEATING SYSTEM SUPPLY PLENUM/COILSupply plenum/coil was sealed, no leaks noted at time of inspection.

HEATING SYSTEM RETURN PLENUMReturn Plenum was in good condition.

HEATING FILTER LOCATION/CONDITION

� Filter(s) are located at interior hallway ceiling(s)

Filter appeared to be clean and serviceable at time of inspection.

HEATING SYSTEM THERMOSTAT CONTROLSThe thermostat was operational at time of inspection

Page 22

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 26: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

HEATING SYSTEM OPERATIONThermal image shows heater was operational at time of inspection. The heating unit was run through a complete cycle. The heater was operated by turning up the thermostat, and then turned back to its original setting.

#2 / Attic Heating System

HEATING SYSTEM THERMOSTAT SETHeater was set to 67

HEATING SYSTEM BRANDYork

HEATING SYSTEM APPROXIMATE AGE2000.

HEATING SYSTEM BTU/HR80,000

HEATING SYSTEM SYSTEM TYPEForced Air Mid-Efficiency Gas Furnace

HEATING SYSTEM FUEL TYPENatural Gas

Page 23

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 27: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

HEATING SYSTEM GAS CONNECTIONGas connection appears serviceable.

HEATING SYSTEM PUMP/BLOWER FANAppears to be in good working condition at time of inspection

HEATING SYSTEM COMBUSTION AIRCombustion air supply adequate

HEATING SYSTEM VENTING SYSTEMThe combustion and exhaust venting appears to be in good condition

HEATING SYSTEM SUPPLY PLENUM/COILSupply plenum/coil was sealed, no leaks noted at time of inspection.

HEATING SYSTEM RETURN PLENUMReturn Plenum was in good condition.

HEATING FILTER LOCATION/CONDITION

� Filter(s) are located at interior hallway ceiling(s)

� Heater filter(s) are dirty, new filter is needed, suggest cleaning/changing filter regularly

Page 24

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 28: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

HEATING SYSTEM THERMOSTAT CONTROLSThe thermostat was operational at time of inspection

HEATING SYSTEM OPERATIONThermal image shows heater was operational at time of inspection. The heating unit was run through a complete cycle. The heater was operated by turning up the thermostat, and then turned back to its original setting.

Air Conditioning System☿

! The average life span for an AC unit is 15 years, some may last longer and some may fail sooner. The inspector does not perform pressure test on coolant systems, therefore no representation is made regarding coolant charge of line integrity. Subjective judgment of system capacity is not part of the inspection. Normal service and maintenance is recommended every 6 months.

#1 / Exterior Right Side Air Conditioning System

A/C BRANDCarrier.

A/C AGE2015

Page 25

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 29: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

A/C TYPE AND METHODCentral Split System, Outdoor condenser with evaporator coil above heater unit indoors.

A/C COMPRESSOR SIZE3 tons

A/C COIL SIZE3 tons

A/C POWER SOURCE220 Volt, Electrical disconnect present

A/C MAX AMP RATING FOR FUSE/BREAKER30 amps

A/C BREAKER SIZE AT PANEL40 amp breaker at panel

AC FUSE/BREAKER RECOMMENDATIONS

� Air conditioners manufacture max fuse or circuit breaker per the National Electrical Code that should be installed for air conditioner is 30 amps. 40 amp breaker is too large for unit. Proper sized breaker or fused disconnect should be installed. We recommend further review and repairs by a qualified specialist in the appropriate trade.

� �

A/C CONDENSING UNIT FANFan was in good working condition at time of inspection

A/C REFRIGERANT LINESRefrigerant line insulation was in good condition at time of inspection, insulation should be replaced when it gets deteriorated.

A/C CONDENSATION LINECondensation  line installed.

Page 26

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 30: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

A/C SECONDARY CONDENSATION LINE

� Note that this exterior drain line installed at right side of house is the secondary line from the cooling coil that is located in the attic. If water is seen draining from this line you need to call a Licensed Heating/AC contractor to check the primary drain line. No water was seen draining from drain line at time of inspection

A/C CONDENSATE DRAIN PANPan is clean and free of debris.

� Pan and coil is sloped away from drain, Recommend further review and repairs as needed by a qualified state licensed mechanical contractor

A/C CONTROLSThe thermostat was operational at time of inspection

Page 27

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 31: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

A/C SYSTEM CONDITIONAmbient temp = 69 Supply temp = 50 Temperature split = 19. Unit was turned on and appeared to be in good working condition at time of inspection. Inspector is testing for a 15 to 22 degree drop in temperature.

� �

A/C NOTE

� New compressor was installed on original furnace and coil, We recommend the AC coil and compressor be evaluated by a qualified HVAC Contractor determine if systems are compatible.

#2 / Exterior Right Side Air Conditioning System

A/C BRANDYork

A/C AGE2000.

A/C TYPE AND METHODCentral Split System, Outdoor condenser with evaporator coil above heater unit indoors.

A/C COMPRESSOR SIZE4 tons

Page 28

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 32: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

A/C COIL SIZE4 tons

A/C POWER SOURCE220 Volt, Electrical disconnect present

A/C MAX AMP RATING FOR FUSE/BREAKER45 amps

A/C BREAKER SIZE AT PANEL40 amp breaker at panel

A/C CONDENSING UNIT FANFan was in good working condition at time of inspection

A/C REFRIGERANT LINESRefrigerant line insulation was in good condition at time of inspection, insulation should be replaced when it gets deteriorated.

A/C CONDENSATION LINECondensation  line installed.

A/C SECONDARY CONDENSATION LINE

� Note that this exterior drain line installed at right side of house is the secondary line from the cooling coil that is located in the attic. If water is seen draining from this line you need to call a Licensed Heating/AC contractor to check the primary drain line. No water was seen draining from drain line at time of inspection

A/C CONDENSATE DRAIN PANPan is clean and free of debris.

A/C CONTROLSThe thermostat was operational at time of inspection

Page 29

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 33: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

A/C SYSTEM CONDITIONAmbient temp = 72 Supply temp = {FillHere} Temperature split = {FillHere}. Unit was turned on and appeared to be in good working condition at time of inspection. Inspector is testing for a 15 to 22 degree drop in temperature.

� Ambient temp = 72 Supply temp = 70 Temperature split = 2. Unit is not producing a proper air temperature split of 15 to 22 degrees. We recommend the advice and services of a qualified HVAC Contractor

� �

A/C NOTE

� The AC unit is beyond its service life

Heating /AC Distribution Systems☿

! Cubic feet measurements (CFM's) of air flow are beyond the scope of the home inspection. Only a mechanical contractor can determine the exact condition of the air flow of the mechanical equipment.

HEATING DISTRIBUTION SYSTEMSFlexible Round

HEATING DISTRIBUTION SYSTEMS CONDITIONVisible ducts in attic were in good visible condition .

Page 30

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 34: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� All accessible duct registers were tested using a thermal infrared camera. This test only tells us if cool air is coming out from the registers, but not the actual CFM's of air flow or static pressure. Testing ducts for air flow, leaks or Cubic feet measurements (CFM's) of air flow is beyond the scope of the home inspection and requires specialize equipment. If you are concerned about this it is recommended that you hire a company to test the ducts for air leaks, air flow and proper static pressure.

Fireplace☿

! All fireplaces should be cleaned and inspected on a regular basis to make sure that no cracks have developed.

FIREPLACE TYPE OF UNITDecorative gas log fireplace

FIREPLACE GAS SHUT-OFFAn easy operate hand shut-off valve is installed on the gas line.

FIREPLACE GAS LINEFlexible gas line is installed on the gas line inside the firebox.

FIREPLACE DAMPER CONDITIONUnit has no damper

FIREPLACE FIREBOX CONDITIONAcceptable.

FIREPLACE FIRE SCREENThe recommended safety screen is installed.

FIREPLACE GLASS FIREPLACE DOORSGlass fireplace doors are installed.

FIREPLACE HEARTH EXTENSIONAdequate.

FIREPLACE FLUEChimney looks to be clean.  I was unable to view the entire flue assembly.

Page 31

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 35: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

FIREPLACE OPERATIONUnit was tested and in good working condition at time of inspection

Windows & Doors☿

! Due to wind, dry air, dust and dirt. You will see built up of sand, dust and dirt in your exterior doors and windows and tracks. Regular cleaning is needed for proper operation. Determining the condition of insulated glass windows and doors is not always possible due to temperature, weather and lighting conditions. Dirty windows may make it difficult to determine the exact condition of insulated windows. Check with the seller for further information

MAIN ENTRY DOORSAppeared to be in good working condition at time of inspection, deadbolt is operational.

EXTERIOR DOORS TYPEFrench, double pane and tempered.

EXTERIOR DOORSAppeared to be in good condition and functional at time of inspection.

WINDOWS TYPEAluminum, double paneAluminum single pane

WINDOWS CONDITIONAll accessible windows were opened and closed and found to be in good working condition at time of inspection.

Page 32

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 36: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Window glazing seals are moving at kitchen window. We recommend further review and repairs by a qualified specialist in the appropriate trade.

� �

WINDOW SCREENS

� Window screen(s) missing at several locations, repair.

INTERIOR DOORSAll interior doors appeared functional at time of inspection.

INTERIOR CLOSETSFunctional

Interior Areas☿

! The finished surfaces, hardware, windows and doors of the interior were found to be in generally acceptable condition. Any exceptions are noted in the report. Cosmetic flaws such as stained/worn carpet, marred surface finishes and worn paint that are apparent to the average person are not included in this inspection, although we may not occasionally report them as a courtesy to our clients. Cosmetic flaws such as minor cracks and nail pops occur in all houses. These are typical cosmetic in nature and are caused by settlement and / or shrinkage of building components. Furnishings are not typically moved in the inspection process by the inspector, which limits the inspection to free areas, defects may be blocked from view Blocked or concealed conditions are not the responsibility of the inspector. Determining the souce of odors or like conditions is not a part of this inspection. Floor covering damage or stains may be hidden by furniture. The conditions of floors underlying floor coverings is not inspected.

INTERIOR OCCUPIEDYes.

DOOR BELL CONDITIONDoorbell is functioning

WALL TYPE/CONDITIONDrywall,

Page 33

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 37: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Wall appears to have been repaired, inquire with seller about repair near front door

CEILING TYPE/CONDITIONDrywallVisual examination of unobstructed areas showed no damage at time of inspection

FLOOR TYPE/CONDITIONTileVisual examination of unobstructed areas of floor showed no damage at time of inspection

Kitchen - Appliances☿

! No opinion is offered as to the adequacy of dishwasher operation. Ovens, self or continuous cleaning operations, cooking functions, clocks, timing devices and thermostat accuracy are not tested during the inspection

LIGHTING SWITCHES AND FIXTURES CONDITIONLighting fixtures and switches appeared to be in good working condition

RECEPTACLE(S)Kitchen receptacles  are all ground fault circuit interrupter (GFCI) protected. GFCI protected receptacles appear to be  in good working condition and appear to be grounded at time of inspection, receptacles were tested by using the test button on outlet, turning them off and making sure all outlets in kitchen are protected

Page 34

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 38: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Faceplate loose on receptacle under stove

SINKS & FAUCETSPorcelainSink(s) appeared to be in good condition at time of inspectionDrain(s) appears serviceable, no leaks noted at time of inspectionFaucet(s) appear to be good working condition at time of inspectionHand sprayer was in good working condition at time of inspection

MAIN SINK GARBAGE DISPOSALSGarbage disposal was turned on and off and found in good in good working condition at time of inspection. Thermal image shows no cracks or leaks.

� �

Page 35

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 39: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

GARBAGE DISPOSAL WIRING

� Missing wire clamp at disposal connection, wire should be clamped for safety. We recommend further review and repairs by a qualified specialist in the appropriate trade.

� �

DISHWASHERSThe dishwasher(s) were/was cycled on the normal cycle to check for its operation and to identify any leakage.  Each cycle and feature of the unit was not tested and is Beyond the scope of this evaluation. There were no leaks found during the inspection.

� New owners should read the operating and loading instructions for this dishwasher

Page 36

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 40: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

DISHWASHER AIR GAPAir gap device is present on drain line at all dishwashers

RANGE/COOK TOP/OVEN TYPEElectric

RANGE/COOK TOP/OVENSThe unit was turned on to check to see if the elements heated up and then turned off.  Unit appeared to be in good working condition at time of inspection. The temperature settings and timer were not testedOven baking and broiling features were turned on to see if element heated up. The temperature settings and timer were not testedOven light was operational at time of inspection

STOVE EXHAUST FAN / VENTSExternalUnit appears to be in good working condition at time of inspection.

Light was working at time of inspection

MICROWAVEUnit was turned on and tested using a cup of water to see if it heated up. Unit appears to be in good working condition at time of inspection.

REFRIGERATORSElectric, Unit appears to be in good working condition at time of inspection, no leaks were seen at time of inspection. Unit was not moved at time of inspection.

REFRIGERATOR WATER HOOK-UPYes.

ICE MAKERSUnits appears to be in good working condition at time of inspection.

Page 37

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 41: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

CONDITION OF COUNTERSVisual examination of unobstructed areas of counter tops showed no damage at time of inspection

CONDITION OF CABINETSCabinets appeared to be in good working condition at time of inspection

CONDITION OF WALLSVisual examination of unobstructed areas of walls showed no damage at time of inspection

CONDITION OF CEILINGSVisual examination of unobstructed areas of ceilings showed no damage at time of inspection

CONDITION OF FLOORSVisual examination of unobstructed areas of flooring showed no damage at time of inspection

WATER FILTER SYSTEM

� Unit was not tested, inquire with seller about condition and service history.

Bathroom☿

! Our review of the interior includes inspection of walls, ceiling, floors, doors, windows, steps, and plumbing fixtures. These features are visually examined for proper function, excessive wear and general state of repair. Some of these components may not be visible/accessible because of furnishings and/or storage. In such cases these items are not inspected. Determining whether shower pans, tub/shower surrounds are water tight is beyond the scope of this inspection. It is very important to maintain all grouting and caulking in the bath areas.

Front Left / Bedroom Bathroom

LIGHT FIXTURESLight was in good working condition at time of inspection.

Page 38

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 42: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

RECEPTACLE(S)Bathroom receptacles are protected from garage GFCI receptacle. Inspector tested by tripping the receptacle and testing to see if receptacle was dead, recommend owner test outlets monthly to insure they are operating properly

CONDITION OF FAUCET(S)Faucet(s) components appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF SINK(S) AND DRAIN(S)Sink appeared to be in good condition at time of inspection, drain appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF COUNTERS

� Caulking / grouting needed at backsplash

CONDITION OF CABINETSAppeared to be in good condition at time of inspection

SHOWER PLUMBING FIXTURESShower fixtures and drain appeared to be in good working condition at time of inspection

TUB/SHOWER AREAS

� Caulking needed around trim plate(s) and tub spout to prevent moisture intrusion.

Page 39

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 43: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

SHOWER ENCLOSUREShower enclosure was in good condition at time of inspection, enclosure glass appears to be tempered.

CONDITION OF TOILETThe toilet flushed and filled properly at the time of inspection

BATHROOM FLOORVisual examination of unobstructed areas of floor showed no damage at time of inspection.

BATHROOM WALLS/CEILINGSWalls and ceiling appeared to be in good condition.

BATHROOM VENTILATIONFan appeared to be in good working condition at time of inspectionWindow appeared to be in good working condition at time of inspection

HEATING DEVICE(S)Heat register(s) were observed in bathroom

BATHROOM DOOR(S)Door closed and latched properly at time of inspection

Powder Room Bathroom

LIGHT FIXTURESLight was in good working condition at time of inspection.

RECEPTACLE(S)Ground Fault Circuit Interrupters appeared to be in good working condition at time of inspection. Inspector tested by tripping the receptacle at the master bathroom GFCI and testing to see if receptacle was dead.

CONDITION OF FAUCET(S)Faucet(s) components appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF SINK(S) AND DRAIN(S)Sink appeared to be in good condition at time of inspection, drain appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF COUNTERSVisual examination of unobstructed areas of counter tops showed no damage at time of inspection.

CONDITION OF TOILETThe toilet flushed and filled properly at the time of inspection

Page 40

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 44: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

BATHROOM FLOORVisual examination of unobstructed areas of floor showed no damage at time of inspection.

BATHROOM WALLS/CEILINGSWalls and ceiling appeared to be in good condition.

BATHROOM VENTILATIONFan appeared to be in good working condition at time of inspection

HEATING DEVICE(S)Heat register(s) were observed in bathroom

BATHROOM DOOR(S)Door closed and latched properly at time of inspection

Right Front / Bedroom Bathroom

LIGHT FIXTURESLight was in good working condition at time of inspection.

RECEPTACLE(S)Ground Fault Circuit Interrupters appeared to be in good working condition at time of inspection. Inspector tested by tripping the receptacle at the master bathroom GFCI and testing to see if receptacle was dead.

CONDITION OF FAUCET(S)Faucet(s) components appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF SINK(S) AND DRAIN(S)Sink appeared to be in good condition at time of inspection, drain appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF COUNTERSVisual examination of unobstructed areas of counter tops showed no damage at time of inspection.

CONDITION OF CABINETSAppeared to be in good condition at time of inspection

Page 41

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 45: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

SHOWER PLUMBING FIXTURES

� Leaking is noted at shower head connection

TUB/SHOWER AREASTub and shower areas appear serviceable, Regular caulking of the seams and joints is required to keep water penetration to a minimum

SHOWER ENCLOSUREShower enclosure was in good condition at time of inspection, enclosure glass appears to be tempered.

CONDITION OF TOILETThe toilet flushed and filled properly at the time of inspection

BATHROOM FLOORVisual examination of unobstructed areas of floor showed no damage at time of inspection.

BATHROOM WALLS/CEILINGSWalls and ceiling appeared to be in good condition.

BATHROOM VENTILATIONFan appeared to be in good working condition at time of inspectionWindow appeared to be in good working condition at time of inspection

HEATING DEVICE(S)Heat register(s) were observed in bathroom

BATHROOM DOOR(S)Door closed and latched properly at time of inspection

Master Bathroom

LIGHT FIXTURESLight was in good working condition at time of inspection.

Page 42

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 46: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

RECEPTACLE(S)Ground Fault Circuit Interrupters appeared to be in good working condition at time of inspection. Inspector tested by tripping the receptacle and testing to see if receptacle was dead, recommend owner test outlets monthly to insure they are operating properly

CONDITION OF FAUCET(S)Faucet(s) components appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF SINK(S) AND DRAIN(S)Sink appeared to be in good condition at time of inspection, drain appeared to be in good condition at time of inspection, no leaks were found.

CONDITION OF COUNTERSVisual examination of unobstructed areas of counter tops showed no damage at time of inspection.

CONDITION OF CABINETSAppeared to be in good condition at time of inspection

SHOWER PLUMBING FIXTURESShower fixtures and drain appeared to be in good working condition at time of inspection

TUB PLUMBING FIXTURESTub fixtures and drain appeared to be in good working condition at time of inspection

TUB/SHOWER AREASShower walls appeared to be in good condition at time of inspection. Regular caulking of the seams and joints is required to keep water penetration to a minimum

SHOWER ENCLOSUREShower enclosure was in good condition at time of inspection, enclosure glass appears to be tempered.

CONDITION OF TOILETThe toilet flushed and filled properly at the time of inspection

BATHROOM FLOORVisual examination of unobstructed areas of floor showed no damage at time of inspection.

BATHROOM WALLS/CEILINGSWalls and ceiling appeared to be in good condition.

BATHROOM VENTILATIONFan appeared to be in good working condition at time of inspection

HEATING DEVICE(S)Heat register(s) were observed in bathroom

Page 43

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 47: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

BATHROOM DOOR(S)Door closed and latched properly at time of inspection

Laundry☿

! Recommend water be shut off to washing machine if owner leaves residence for any extended period of time to prevent damage if case water hoses leak. Water hose should be replaced every 5 years.

LOCATIONInterior

LAUNDRY ROOM FIXTURES & RECEPTACLESLight fixture(s) were in good working condition at time of inspectionLaundry receptacle(s) are protected from garage GFCI receptacle.

EXHAUST FANExhaust fan is installed and appeared to be in good working condition at time of inspection

WATER HOOK-UPSWater supply was tested and was found to be in good working condition.

RECOMMENDATIONS

� It is recommended that you use braided steel flexible water supply lines for washer hook up.  The cheaper rubber lines are more  prone to rupturing and flooding of the home.

DRAIN LINEDrain line was tested and found to be in good working condition.

DRYER HOOK UP CONDITIONGas valve is provided and functional

Page 44

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 48: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

GAS SHUT-OFFAn easy operate hand shut-off valve is properly installed on the gas line, but valve was not tested. Testing valves is beyond the scope of the inspection

FLEXIBLE CONNECTORA flexible gas line is installed and functional.

DRYER VENTINGThe dryer vent is vented to the exterior

LAUNDRY SINKFaucet appeared to be in good condition at time of inspectionDrain was in good working condition, no leaks were present.

COUNTERS CONDITIONVisual examination of unobstructed areas of counter tops showed no damage at time of inspection

CABINETSCabinets appeared to be in good working condition at time of inspection

WALLSVisual examination of unobstructed areas of walls showed no damage at time of inspection

CEILINGSVisual examination of unobstructed areas of ceilings showed no damage at time of inspection

FLOORSVisual examination of unobstructed areas of flooring showed no damage at time of inspection

CLOTHES WASHERUnit was turned on and run through a short cycle, all cycles were not tested due to time constraints, unit appeared to be in good working condition at time of inspection

CLOTHES DRYERGas dryer. Unit was turned on and run through a short cycle, all cycles were not tested due to time constraints, unit appeared to be in good working condition at time of inspection.

Outdoor Cooking☿OUTDOOR COOKING EQUIPMENT ENERGY SOURCELP Gas

OUTDOOR COOKING EQUIPMENT CONDITION

� Unit was not tested, no propane

Page 45

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 49: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

OUTDOOR KITCHEN AREA SINKS TYPE AND CONDITION

� Sink not connected to any plumbing

OUTDOOR KITCHEN AREA REFRIGERATOR TYPE AND CONDITIONUnits appears to be in good working condition at time of inspection.

OUTDOOR KITCHEN AREA COUNTERS CONDITIONVisual examination of unobstructed areas of counter tops showed no damage at time of inspection

Water Features/Fountains☿CONDITION

� Could not locate switch to test

Page 46

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 50: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

Pool/Spa & Equipment☿POOL/SPA TYPEBelow Ground

POOL/HOT TUB SURFACE TYPEConcrete shell covered with an aggregate surface sometime called Pebble Tech.

POOL/HOT TUB SURFACE CONDITION

� Cracks noted to pool surface. We recommend the advice and services of a qualified Pool Contractor

Page 47

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 51: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Aggregate surface is not supposed to be installed above water line. Surface can deteriorate and crack like it already has. We recommend further review and repairs by a qualified specialist in the appropriate trade.

POOL/HOT TUB SURFACE DECORATIVE TILE & STONEGood overall condition at time of inspection.

� Staining is noted at tiles, cleaning is recommended.

� �

POOL DECKING/COPING TYPEConcrete

Page 48

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 52: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

POOL DECKING/COPING CONDITION

� Cracking is noted, recommend cracks be sealed.

� �

� Efflorescence seen on concrete indicates the presence of moisture.

POOL LIGHT CONDITIONPool light(s) were operational at time of inspection

Page 49

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 53: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

SPA LIGHT CONDITIONSpa light(s) were operational at time of inspection.

DRAIN COVER TYPE/CONDITIONMultiple anti vortex covers noted

SKIMMER & BASKET CONDITIONSkimmer area and basket was in serviceable condition at time of inspection.

FILL DEVICE CONDITIONUnit was tested and in good working condition at time of inspection

Page 50

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 54: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

PUMP CONDITION #1Pump was operational at time of inspection. No leaks found at time of inspection.

FILTER TYPECartridge

FILTER PRESSURE IN PSIPressure is low, filter is clean.

FILTER CONDITION

� Leaking noted at plumbing filter connection.

Page 51

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 55: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

CHLORINATOR: TYPEChlorine Generator present. Inspection of these units is limited to viewing of the display panel when pumps are operational - Buyer should inquire with seller or pool service company about equipment condition and operational procedures.

� Panel showed air temp to cold to generate, inquire with the pool service company about condition of the salt cell

VISIBLE PLUMBING LINE CONDITIONVisible plumbing lines were in good condition, no leaks were found

VALVE TYPEMotorized

VALVE CONDITIONAll valve(s) are in good working condition

POOL/SPA HEATER TYPENatural gas

POOL/SPA HEATER CONDITIONPool/spa heater was operational at time of inspection

Page 52

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 56: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

� Water was seen coming from under the pool heater, We recommend further review and repairs by a qualified specialist in the appropriate trade.

POOL/SPA HEATER GAS SUPPLYGas shut off valve present

� Gas line is rusted and in contact with dirt, pipe needs to be rapped. We recommend the advice and services of a qualified Plumbing Contractor

CONTROLSPool/spa controller(s) were in good working condition at time of inspection

Page 53

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 57: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

GROUND FAULT CIRCUIT INTERRUPTERS

� Recommend installation of listed outdoor cover for unattended cords on GFCI receptacle next to pool panel

� �

� GFCI receptacle for pool would not reset. Recommend further review and repair by qualified Electrical Contractor.

BONDINGBonding is noted at the pool heater and pool pump(s)

Page 54

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 58: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

POOL SUB PANEL(S)

� Missing breaker(s) for pool equipment at pool panel, breaker disconnect required at pool sub panel, Recommend further review and repair by qualified Electrical Contractor.

WATER FEATURE CONDITION

� Cleaning needed to sheer descent ports.

� �

SPA CONDITIONPump and motor operate properly and hydro jet action is good at all jets.

Page 55

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348

Page 59: REAL ESTATE INSPECTION REPORT - advantagesocal.comadvantagesocal.com/wp-content/uploads/2015/11/Sample-Inspection-Report.pdfREAL ESTATE INSPECTION REPORT LOCATED AT: 63632 Alameda

CHILD PROTECTION FENCING/BARRIERS

� None.  If children are present, it is recommended that a special child proof barrier fencing be installed around pool for safety along with exterior door alarms. We recommend further review and by a qualified specialist in the appropriate trade.

Beyond The Scope☿

! CONCEALED AREASIf areas of the home are inaccessible or concealed from the inspectors view, then an inspection of that area did not take place. Request that any information about any hidden problems be revealed to you about these inaccessible or hidden areas from the seller prior to the close of escrow. Return to the property prior to the close of escrow and perform a walk-through inspection of your own after the owner's belongings have been removed. If your inspection or information reveals hidden damage or concerns contact a qualified specialist or your inspector for a return visit.

! PERMITS/BUILDING CODE VIOLATIONSIf you are concerned about building permit information you should, request copy' s from seller/owner.

! GEOLOGICAL STABILITYSoil condition or stability is not determined during this home inspection. Should you decide to obtain a geological report of the site conditions you might contact a geological inspection firm through your real estate agent or a non profit association of geo technical engineers for referral.

! STRUCTURAL STABILITY OR ENGINEERING ANALYSISEngineering analysis of a buildings structure is performed only by a licensed structural engineer with the use of measurements, calculations, or other scientific evaluation. Engineering is beyond the scope of a typical home inspection. To receive an inspection and report on the structure by an engineer, ask your real estate agent or a nonprofit association of structural engineers for referral.

! SEWER BLOCKAGECheck with the seller for information about the history of the sewer or private septic waste disposal system. Having a drain service company video review and service the main drain line to be sure it is open and flowing before the close of escrow is recommended on all homes.

! ENVIROMENTAL CONCERNSEnvironmental issues include but are not limited to mold, radon, asbestos, lead paint, lead contamination, toxic waste, formaldehyde, electromagnetic radiation, buried fuel oil tanks, ground water contamination and soil contamination. We may make reference to one of more of these materials in this report when we recognize one of the common forms of these substances. If further study or analysis seems prudent, the advice and services of the appropriate specialists are advised

! AIR DUCT/REGISTER TESTINGAll accessible duct registers were tested using a thermal infrared camera. This test only tells us if cool air is coming out from the registers, but not the actual CFM's of air flow or static pressure. Testing ducts for air flow, leaks or Cubic feet measurements (CFM's) of air flow is beyond the scope of the home inspection and requires specialize equipment. If you are concerned about this it is recommended that you hire a company to test the ducts for air leaks, air flow and proper static pressure.

Page 56

The Doe Report63632 Alameda

Palm Desert, CA 92260 Wednesday, February 3, 2016

Copyright© 2006-2016, Advantage Inspection Professional, LLC, Bruce Carmichael, Inspector Report # 110880348