ST 800 SmartLine Pressure Transmitter Honeywell Quick Installation Card Know your Transmitter The transmitter can measure the differential, absolute and gauge pressures which can be communicated in Fieldbus, HART Version 7, and Digitally Enhanced protocols in process engineering. It has meter body and electronic housing assemblies which can easily assembled in your process. The following figure shows the flange type connection of the transmitter. Figure: Flange Type connection of Transmitter

Upload: vinay-tarsem-lal

Post on 17-Jul-2016

19 views

Category:

Documents


3 download

DESCRIPTION

Quick installation card for ST800 Honeywell pressure transmitter.

TRANSCRIPT

Page 1: Quick Installation Card ST800 HoneyWell

ST 800 SmartLine Pressure Transmitter Honeywell

Quick Installation Card

Know your Transmitter The transmitter can measure the differential, absolute and gauge pressures which can be communicated in Fieldbus,

HART Version 7, and Digitally Enhanced protocols in process engineering. It has meter body and electronic housing

assemblies which can easily assembled in your process. The following figure shows the flange type connection of the

transmitter.

Figure: Flange Type connection of Transmitter

Page 2: Quick Installation Card ST800 HoneyWell

ST 800 SmartLine Pressure Transmitter Honeywell

Figure: The exploded transmitter parts

Features Single, Dual, or Triple Calibration

Analog output in 4-20 mA range

Human machine interface using three buttons and 2 lines digital or graphical display

Approvals from FM, CSA, ATEX, IECEx, SAEx, INMETRO, NEPSI, GOST, MARINE and MID

Angle/flat carbon steel/304 stainless steel, Marine 304 stainless steel, 316 Stainless Steel Mounting Brackets

Display supports English, German, French, Italian, Spanish, Turkish, Chinese and Russian languages

Page 3: Quick Installation Card ST800 HoneyWell

ST 800 SmartLine Pressure Transmitter Honeywell Connections

The transmitter can be mounted on flange, Flush or Remote diaphragm seal arrangements. The electronic connections

have two wires which are connected to the terminals and an internal ground connection in the terminal block.

Installation Prerequisites

Evaluate the following parameters:

• Environmental Conditions: o Ambient Temperature o Relative Humidity

• Potential Noise Sources:

o Radio Frequency Interference (RFI) o Electromagnetic Interference (EMI)

• Vibration Sources o Pumps o Motorized System Devices (e.g., pumps) o Valve Cavitation

• Process Parameters o Temperature o Maximum Pressure Rating

Safety

The display shows the following critical errors:

Electronic Module DAC Failure

Meter Body NVM Corrupt

Config Data Corrupt

Electronic Module Diag Failure

Meter Body Critical Failure

Sensor Comm Timeout

Page 4: Quick Installation Card ST800 HoneyWell

ST 800 SmartLine Pressure Transmitter Honeywell Non Critical errors or warnings:

No DAC Compensation

No Factory Calibration

PV Out of Range

Fixed Current Mode

Sensor Over Temperature

Meter Body Excess Correct

Local Display

Low Supply Voltage

AO Out of Range

Loop Current Noise

Troubleshooting Fault Conditions and Recommended Corrective Actions

Condition Analysis Recommended Corrective Action

Meterbody fault. A critical failure has been detected in the Meterbody

Use a HART, DE, or FF communicator to read the detailed status information

from the transmitter. Refer to the appropriate communicator

manual to get more information about the possible

causes of the failure.

Cycle power to the Transmitter. If the problem continues to occur, replace

the Meterbody.

Electronics Module Fault. A critical failure has been

detected on the HART, DE, or FF Electronics Module.

Use a HART, DE, or FF communicator to read the detailed status information

from the transmitter. Refer to the appropriate communicator manual for more information

about the possible failure causes.

Cycle power to the transmitter.

If the problem continues to occur replace the Electronics

Module.

Meterbody Comm fault. .

This could be the result of a failure on either of these modules or the cable that

connects them.

Check the ribbon cable that connects the Meterbody to

the Electronics Module. Make sure that the cable is securely plugged into the Electronics Module. Make sure that all pins are plugged into the

connector (i.e., make sure that the connector is not

offset in a way that leaves some pins unconnected).

Communications between the Meterbody and the

Electronics Module has failed

Use a HART, DE, or FF communicator to read the detailed status information

from the transmitter. Refer to the appropriate communicator

manual to get more information about the possible

causes of the failure.

Cycle power to the transmitter.

If the problem continues to occur replace the Electronics Module. If this does not fix the

problem, replace the Meterbody.