Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] 2.3 Other Publications. 2.3.1 ANSI ASME Publications. National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P... 1 of 39 1/6/2015 1:35 PM

Upload: others

Post on 10-Aug-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ]

2.3 Other Publications.2.3.1 ANSI ASME Publications.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

1 of 39 1/6/2015 1:35 PM

Page 2: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, Society of Mechanical Engineers, Three Park Avenue, New York,NY 10036.ANSI/ 10016-5990.

Boiler and Pressure Vessel Code (BPVC), Section IX, Welding and Brazing Qualifications , 2013 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

2 of 39 1/6/2015 1:35 PM

Page 3: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

ASME B1.20.1, Pipe Threads, General Purpose , 2006

2013 .

ANSI B16

ASME B16 .1,

Cast

Gray Iron Pipe Flanges and Flanged Fittings ,

2005

2010 .

ANSI

ASME B16.3, Malleable Iron Threaded Fittings Classes 150 and 300 ,

2006

2011 .

ANSI B16

ASME B16 .4, Gray Iron Threaded Fittings Classes 125 and 250 ,

2006

2011 .

ANSI

ASME B16.5, Pipe Flanges and Flanged Fittings ,

2006

2013 .

ANSI

ASME B16.9, Factory-Made Wrought Steel Buttwelding Fittings ,

2007

2012 .

ANSI

ASME B16.11, Forged Fittings, Socket-Welding and Threaded ,

2009

2011 .

ANSI

ASME B16.18, Cast Copper Alloy Solder Joint Pressure Fittings ,

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

3 of 39 1/6/2015 1:35 PM

Page 4: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

2001

2012 .

ANSI

ASME B16.22, Wrought Copper and Copper Alloy Solder Joint Pressure Fittings ,

2001

2013 .

ANSI

ASME B16.25, Buttwelding Ends ,

1997

2012 .

ANSI

ASME B36.10M, Welded and Seamless Wrought Steel Pipe , 2004.

ANSI

ASME B36.19M, Stainless Steel Pipe ,

2002

2004 .

ANSI C2, National Electrical Safety Code , 2007.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

4 of 39 1/6/2015 1:35 PM

Page 5: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

2.3. 2 ASME Publications.American Society of Mechanical Engineers, Three Park Avenue, New York, NY 10016-5990.

Boiler and Pressure Vessel Code (BPVC), Section IX, Welding and Brazing Qualifications , 2010.

2.3.3 32.3.2 ASTM Publications.ASTM International, 100 Barr Harbor Drive, Box C700, West Conshohocken, PA 19428-2959.

ASTM A 53/ A 53M , Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless, 2007 2012 .

ASTM A 135/A 135M , Standard Specification for Electric-Resistance-Welded Steel Pipe, 2009.

ASTM A 182/A 182 M , Standard Specification for Forged or Rolled Alloy-Steel Pipe Flanges, Forged Fittings, and Valves and Parts forHigh-Temperature Service, 2009 2014 .

ASTM A 234/A 234M , Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High TemperatureService, 2007 2013 .

ASTM A 312/A 312M , Standard Specification for Seamless Welded and Heavily Cold Worked Austenitic Stainless Steel Pipes, 2009 2014 .

ASTM A 536, Standard Specification for Ductile Iron Castings, 2009.

ASTM A 795/A 795M , Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for FireProtection Use, 2008 2013 .

ASTM B 75/B 75M , Standard Specification for Seamless Copper Tube, 2002 2011 .

ASTM B 88, Standard Specification for Seamless Copper Water Tube, 2009.

ASTM B 251, Standard Specification for General Requirements for Wrought Seamless Copper and Copper-Alloy Tube, 2002 2010 .

ASTM D 323, Standard Test Method for Vapor Pressure of Petroleum Products (Reid Method), 2008.

2.3. 4 42.3.3 AWS Publications.American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672 .

AWS A 5.8M/ A5.8, Specification for Filler Metals for Brazing and Braze Welding, 2004 2010 .

AWS B2.1, Specification for Welding Procedures and Performance Qualification, 2009.

AWS B2.2/B 2.2M , Standard for Brazing Procedure and Performance Qualification, 1991 3 rd edition .

2.3. 5 52.3.4 IEEE Publications.Institute of Electrical and Electronics Engineers, Three Park Avenue, 17th Floor, New York, NY 10016-5997.

IEEE /ASTM- SI - 10 , American National Standard Practice for Use of the International System of Units (SI): The Modern Metric System ,2002 For Metric Practice , 2012 .

2.3. 6 62.3.5 Other Publications.Merriam-Webster’s Collegiate Dictionary, 11th edition, Merriam-Webster, Inc., Springfield, MA, 2003.

Statement of Problem and Substantiation for Public Input

Updated edition dates to current editions, change in address for American Welding Society, and elimination of ANSI due to development by ASME and

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

5 of 39 1/6/2015 1:35 PM

Page 6: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

IEEE.

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 37-NFPA 15-2014 [Chapter C]

Submitter Information Verification

Submitter Full Name: Aaron AdamczykOrganization: [ Not Specified ]Street Address:City:State:Zip:Submittal Date: Sat Jun 07 21:45:01 EDT 2014

Committee Statement

Resolution: FR-1-NFPA 15-2014Statement: References updated per manual of style.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

6 of 39 1/6/2015 1:35 PM

Page 7: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 32-NFPA 15-2014 [ Section No. 2.3.3 ]

2.3.3 ASTM Publications.ASTM International, 100 Barr Harbor Drive, Box C700, West Conshohocken, PA 19428-2959.

ASTM A 53/A53M , Standard Specification for Pipe, Steel, Black and Hot-Dipped, Zinc-Coated, Welded and Seamless, 2007 2012 .

ASTM A 135/A135M , Standard Specification for Electric-Resistance-Welded Steel Pipe, 2009.

ASTM A 182/A182M , Standard Specification for Forged or Rolled Alloy-Steel Pipe Flanges, Forged Fittings, and Valves and Parts forHigh-Temperature Service, 2009 2014A .

ASTM A 234/A234M , Standard Specification for Piping Fittings of Wrought Carbon Steel and Alloy Steel for Moderate and High TemperatureService, 2007 2013e1 .

ASTM A 312/A312M , Standard Specification for Seamless Welded and Heavily Cold Worked Austenitic Stainless Steel Pipes, 2009 2014 .

ASTM A 536, Standard Specification for Ductile Iron Castings, -84( 2009) .

ASTM A 795/A795M , Standard Specification for Black and Hot-Dipped Zinc-Coated (Galvanized) Welded and Seamless Steel Pipe for FireProtection Use, 2008 2013 .

ASTM B 75, Standard Specification for Seamless Copper Tube, 2002 2011 .

ASTM B 88, Standard Specification for Seamless Copper Water Tube, 2009.

ASTM B 251, Standard Specification for General Requirements for Wrought Seamless Copper and Copper-Alloy Tube, 2002 2010 .

ASTM D 323, Standard Test Method for Vapor Pressure of Petroleum Products (Reid Method), 2008 08(2014) .

Statement of Problem and Substantiation for Public Input

Update to current year dates.

Submitter Information Verification

Submitter Full Name: Steve MawnOrganization: ASTM InternationalStreet Address:City:State:Zip:Submittal Date: Wed Jul 02 15:29:01 EDT 2014

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

7 of 39 1/6/2015 1:35 PM

Page 8: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Committee Statement

Resolution: FR-1-NFPA 15-2014Statement: References updated per manual of style.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

8 of 39 1/6/2015 1:35 PM

Page 9: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 25-NFPA 15-2014 [ Section No. 3.3.2 ]

3.3.2* Combustible Liquid.Any liquid that has a closed-cup flash point at or above 100°F (37.8°C), as determined by the appropriate test procedures and apparatus.

4.5 Flammable and combustible liquids.

4.5.1 The test procedures and apparatus to assess whether a liquid is a flammable or combustible liquid are set forth in Section 4.4 of NFPA30. Combustible liquids are

4.5.2 The Reid vapor pressure shall not exceed an absolute pressure of 40 psi (276 kPa) at 100°F (37.8°C), as determined by ASTM D323,Standard Test Method for Vapor Pressure of Petroleum Products (Reid Method).

4.5.3 Flammable and combustible liquids shall be classified according to Section 4.3 of NFPA 30. [ 30, 2012]

Statement of Problem and Substantiation for Public Input

Definitions cannot contain requirements based on other codes, standards or regulations and the requirements must be in the body of the standard, per the NFPA Manual of Style.

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 26-NFPA 15-2014 [Section No. 3.3.11]

Submitter Information Verification

Submitter Full Name: Marcelo HirschlerOrganization: GBH InternationalStreet Address:City:State:Zip:Submittal Date: Fri Jun 27 17:45:02 EDT 2014

Committee Statement

Resolution: This needs to be addressed with NFPA 30 as this definition is extracted and some of the proposed terms are not enforceable.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

9 of 39 1/6/2015 1:35 PM

Page 10: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 28-NFPA 15-2014 [ Section No. 3.3.10 ]

3.3.10 * Fire Area.For the purpose of this standard, an area that is physically separated from other areas by space, barriers, walls, or other means in order tocontain fire within that area .

Statement of Problem and Substantiation for Public Input

Fire Areas in NFPA 15 are not necessarily meant to contain a fire, but are merely the maximum constraints of a single water spray system. Section 7.1.10.2, specifically (2) and (5), shows that it is not the intent of this standard to limit a fire to a single fire area.

7.1.10.2* The number of systems expected to operate simultaneously shall be determined by evaluating the following factors:(1)Possible flow of burning liquids between areas before or during operation of the water spray systems(2)Possible flow of hot gases between fire areas that could actuate adjoining systems, thereby increasing demand(3)Flammable gas detection set to automatically actuate systems(4)Manual operation of multiple systems(5)Other factors that would result in operation of systems outside of the primary fire area

Submitter Information Verification

Submitter Full Name: Roland AspOrganization: National Fire Sprinkler AssociationStreet Address:City:State:Zip:Submittal Date: Tue Jul 01 14:49:27 EDT 2014

Committee Statement

Resolution: FR-3-NFPA 15-2014Statement: Fire Areas in NFPA 15 are not necessarily meant to contain a fire, but are merely the maximum constraints of a single water spray system.

Section 7.1.10.2, specifically (2) and (5), shows that it is not the intent of this standard to limit a fire to a single fire area.

7.1.10.2*

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

10 of 39 1/6/2015 1:35 PM

Page 11: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

The number of systems expected to operate simultaneously shall be determined by evaluating the following factors:

(1)Possible flow of burning liquids between areas before or during operation of the water spray systems

(2)Possible flow of hot gases between fire areas that could actuate adjoining systems, thereby increasing demand

(3)Flammable gas detection set to automatically actuate systems

(4)Manual operation of multiple systems

(5)Other factors that would result in operation of systems outside of the primary fire area

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

11 of 39 1/6/2015 1:35 PM

Page 12: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 26-NFPA 15-2014 [ Section No. 3.3.11 ]

3.3.11* Flammable Liquid.Any liquid that has a closed-cup flash point below 100°F (37.8°C), as determined by the appropriate test procedures and apparatus.

4.5 Flammable and combustible liquids.

4.5.1 The test procedures and apparatus to assess whether a liquid is a flammable or combustible liquid are set forth in Section 4.4 of NFPA30

, and a

.

4.5.2 The Reid vapor pressure

that does

of flammable or combustible liquids shall not exceed an absolute pressure of 40 psi (276 kPa) at 100°F (37.8°C), as determined by ASTM

D 323

D323 , Standard Test Method for Vapor Pressure of Petroleum Products (Reid Method) .

4.5.3 Flammable and combustible liquids are shall be classified according to Section 4.3 of NFPA 30. [ 30, 2012]

Statement of Problem and Substantiation for Public Input

Definitions cannot contain requirements based on other codes, standards or regulations and the requirements must be in the body of the standard, per the NFPA Manual of Style.

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 25-NFPA 15-2014 [Section No. 3.3.2]

Submitter Information Verification

Submitter Full Name: Marcelo HirschlerOrganization: GBH InternationalStreet Address:City:State:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

12 of 39 1/6/2015 1:35 PM

Page 13: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Zip:Submittal Date: Fri Jun 27 17:55:34 EDT 2014

Committee Statement

Resolution: This needs to be addressed with NFPA 30 as this definition is extracted and some of the proposed terms are not enforceable.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

13 of 39 1/6/2015 1:35 PM

Page 14: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 22-NFPA 15-2014 [ New Section after 3.3.16 ]

3.3.17 Qualified.A competent and capable person or company that has met the requirements and training for a given field acceptable to the AHJ.

Statement of Problem and Substantiation for Public Input

This suggested revision adds the definition of "qualified" to the standard, and is related to Public Input #21 that adds the term "qualified person" to section 4.3. These two Public Inputs suggest revision to the standard to follow the format of other NFPA standards. This definition was extracted from NFPA 96, section 3.3.41. This definition was chosen over the definition of "qualified person" in NFPA 80 because it is simplified, requires acceptance of the AHJ and does not utilize a laundry list more suited for an annex provision. We also suggest petitioning the NFPA Standards Council to consider using one definition for all standards using the term "qualified" or "qualified person" as an Official Definition.

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 21-NFPA 15-2014 [Section No. 4.3]

Submitter Information Verification

Submitter Full Name: Jim MuirOrganization: Building Safety Division, Clark County, WashingtonAffilliation: NFPA's Building Code Development Committee (BCDC)Street Address:City:State:Zip:Submittal Date: Tue May 20 13:39:09 EDT 2014

Committee Statement

Resolution: FR-5-NFPA 15-2014Statement: This suggested revision adds the definition of "qualified" to the standard, and is related to Public Input #21 that adds the term "qualified

person" to section 4.3. These two Public Inputs suggest revision to the standard to follow the format of other NFPA standards. This definitionwas extracted from NFPA 96, section 3.3.41. This definition was chosen over the definition of "qualified person" in NFPA 80 because it issimplified, requires acceptance of the AHJ and does not utilize a laundry list more suited for an annex provision. We also suggest petitioning

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

14 of 39 1/6/2015 1:35 PM

Page 15: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

the NFPA Standards Council to consider using one definition for all standards using the term "qualified" or "qualified person" as an OfficialDefinition.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

15 of 39 1/6/2015 1:35 PM

Page 16: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 9-NFPA 15-2014 [ Section No. 4.2.1 ]

4.2.1 A study shall A hazard risk analysis shall be made of the physical and chemical properties of the materials for which the water spray protectionis being considered and a fire risk analysis to determine the advisability of its use.

Statement of Problem and Substantiation for Public Input

The word “study” is too vague and provides little direction. Hazard risk analysis and fire risk analysis are both defined NFPA terms and are specific and applicable to this standard.

Submitter Information Verification

Submitter Full Name: Kelly NicolelloOrganization: Western Regional Fire Code DevStreet Address:City:State:Zip:Submittal Date: Tue Apr 01 18:48:04 EDT 2014

Committee Statement

Resolution: FR-6-NFPA 15-2014Statement: The word “study” is too vague and provides little direction. Hazard analysis is considered to be a term applicable to the analysis of the

design of a water spray system. The use of code reference or other materials qualifies as a hazard analysis.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

16 of 39 1/6/2015 1:35 PM

Page 17: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 21-NFPA 15-2014 [ Section No. 4.3 ]

4.3 * Workmanship.Water spray system design, layout, and installation shall be entrusted to fully experienced and responsible parties only performed by qualifiedpersons .

Statement of Problem and Substantiation for Public Input

The existing text is not clear. This suggested revision would clarify the intent of the provision and utilize text already used in other NFPA documents. This revision eliminates unenforceable terms such as "entrusted" and "fully experienced." This Public Input is related to another Public Input that would add the definition of "qualified persons" from NFPA 96.

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 22-NFPA 15-2014 [New Section after 3.3.16]

Submitter Information Verification

Submitter Full Name: Jim MuirOrganization: Building Safety Division, Clark County, WashingtonAffilliation: NFPA's Building Code Development Committee (BCDC)Street Address:City:State:Zip:Submittal Date: Tue May 20 13:29:49 EDT 2014

Committee Statement

Resolution: FR-4-NFPA 15-2014Statement: The existing text is not clear. This suggested revision would clarify the intent of the provision and utilize text already used in other NFPA

documents. This revision eliminates unenforceable terms such as "entrusted" and "fully experienced." This Public Input is related to anotherPublic Input that would add the definition of "qualified".

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

17 of 39 1/6/2015 1:35 PM

Page 18: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 10-NFPA 15-2014 [ Section No. 4.4.4 ]

4.4.4 * Where the protected hazard involves the possible release of flammable or combustible liquids, the drainage system shall be designed to safelyhandle burning liquids, be dedicated to this one purpose and not interconnected to the facility normal drainage system . .

Statement of Problem and Substantiation for Public Input

Combustible and flammable liquids are not to be allowed into common drain systems without proper water fuel separation or containment sump for environmental and fire protection safety. The way the section is currently written the drainage system only needs to withstand burning liquids.

Submitter Information Verification

Submitter Full Name: Kelly NicolelloOrganization: Western Regional Fire Code DevStreet Address:City:State:Zip:Submittal Date: Tue Apr 01 18:49:57 EDT 2014

Committee Statement

Resolution: This additional guidance is not necessary as the term "design" will take this into consideration. A dedicated drainage system may not benecessary.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

18 of 39 1/6/2015 1:35 PM

Page 19: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 17-NFPA 15-2014 [ Section No. 4.4.6 ]

A. 4.4 .6 Open trenches and ditches shall should be routed so as not to expose fire fighters, critical equipment and piping, other important structures, orproperty of others.

Statement of Problem and Substantiation for Public Input

How is an AHJ to measure avoidance of exposure of fire fighters? This provision in the standard is not measurable. And the term “exposure” is not clearly defined. This is appropriate as guidance in the annex, rather than a requirement in the body of the standard. An alternative to this suggestion is to revise the provision to direct flow away from specific areas, which would be measureable.

Submitter Information Verification

Submitter Full Name: Jim MuirOrganization: Building Safety Division, Clark County, WashingtonAffilliation: NFPA's Building Code Development Committee, (BCDC)Street Address:City:State:Zip:Submittal Date: Tue May 20 13:09:04 EDT 2014

Committee Statement

Resolution: FR-7-NFPA 15-2014Statement: How is an AHJ to measure avoidance of exposure of fire fighters? This provision in the standard is not measurable. And the term “exposure”

is not clearly defined. This is appropriate as guidance in the annex, rather than a requirement in the body of the standard. An alternative tothis suggestion is to revise the provision to direct flow away from specific areas, which would be measureable.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

19 of 39 1/6/2015 1:35 PM

Page 20: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 11-NFPA 15-2014 [ Section No. 4.4.10 ]

4.4.10 The water and liquids drained from protected areas shall be collected and , separated and treated as required by local regulations.

Statement of Problem and Substantiation for Public Input

Adding the word “separated” adds clarity to the requirement.

Submitter Information Verification

Submitter Full Name: Kelly NicolelloOrganization: Western Regional Fire Code DevStreet Address:City:State:Zip:Submittal Date: Tue Apr 01 18:51:04 EDT 2014

Committee Statement

Resolution: Separation may not be required or achievable in all situations.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

20 of 39 1/6/2015 1:35 PM

Page 21: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 18-NFPA 15-2014 [ New Section after 5.1.2.3 ]

5.1.2.4Component parts for which a listing is unavailable may be utilized if their required performance individually and within assembly is analyzed andverified by a fire protection engineer or other qualified design professional acceptable to the authority having jurisdiction, provided the unlistedcomponent is also found to be acceptable to the authority having jurisdiction.

Statement of Problem and Substantiation for Public Input

It appears the standard prohibits unlisted components. This will allow the use of certain unlisted components that would be acceptable otherwise.

Submitter Information Verification

Submitter Full Name: Jim MuirOrganization: Building Safety Division, Clark County, WashingtonAffilliation: NFPA's Building Code Development Committee (BCDC)Street Address:City:State:Zip:Submittal Date: Tue May 20 13:17:36 EDT 2014

Committee Statement

Resolution: This is covered by section 1.5 equivalency and section 5.1.2.1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

21 of 39 1/6/2015 1:35 PM

Page 22: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 13-NFPA 15-2014 [ Section No. 5.10.4 ]

5.10.4 Connections shall be equipped with approved plugs or caps.

Statement of Problem and Substantiation for Public Input

Remove section it is repetitive with section 5.10.2.

Submitter Information Verification

Submitter Full Name: Doug HohbeinOrganization: Northcentral Fire Code DevelopStreet Address:City:State:Zip:Submittal Date: Tue Apr 22 16:33:47 EDT 2014

Committee Statement

Resolution: FR-8-NFPA 15-2014Statement: Remove section it is repetitive with section 5.10.2.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

22 of 39 1/6/2015 1:35 PM

Page 23: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 19-NFPA 15-2014 [ Section No. 6.2.1.4 ]

6.2.1.4 Where acceptable to the authority having jurisdiction approved , sprinklers shall be permitted to be used in water spray systems and installed inpositions other than anticipated by their listing to achieve specific results where special situations require.

Statement of Problem and Substantiation for Public Input

This Public Input intends to simplify the provision and follow the NFPA Manual of Style. The definition of “approved” means “Acceptable to the authority having jurisdiction.” Section 2.3.2.6 of the NFPA Manual of Style states that “Existing official definitions contained in the Regulations Governing Committee Projects shall be used where applicable.

Submitter Information Verification

Submitter Full Name: Jim MuirOrganization: Building Safety Division, Clark County, WashingtonAffilliation: NFPA's Building Code Development Committee (BCDC)Street Address:City:State:Zip:Submittal Date: Tue May 20 13:20:30 EDT 2014

Committee Statement

Resolution: FR-9-NFPA 15-2014Statement: This Public Input intends to simplify the provision and follow the NFPA Manual of Style. The definition of “approved” means “Acceptable to

the authority having jurisdiction.” Section 2.3.2.6 of the NFPA Manual of Style states that “Existing official definitions contained in theRegulations Governing Committee Projects shall be used where applicable.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

23 of 39 1/6/2015 1:35 PM

Page 24: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 23-NFPA 15-2014 [ Section No. 6.3.3.7 ]

6.3.3.7 Drain connections shall be sized as shown in Table 6.3.3.7.Table 6.3.3.7 Drain Size

Riser or Main Size(in.)

Size of Drain Connection (in.)

Up to 2 3 ⁄ 4 or larger

2 1 ⁄ 2 , 3, 3 1 ⁄ 2

1 1 ⁄

3/ 4 or larger4 and larger

2 only

3/4 or larger

Note: For SI units, 1 in. = 25.4 mm.

Statement of Problem and Substantiation for Public Input

The minimum requirments for drain sizes are given in tabel 6.3.3.7. Due to the fact that these systems normally will not be operated or tested under freezing conditions, there is no need to drain the piping within a couple of minutes. Therefore it is my opinion that a drain of 3/4" will be sufficient at all times. Even when there is an incident and the system will be activated at temperatures far below freezing point, a 3/4" drain will be sufficient to drain the piping in a relativly short time.

Submitter Information Verification

Submitter Full Name: Hans LuijmesOrganization: Dept. Industrial Safety of the Regional Firebrigade Rotterdam-RijnmondAffilliation: Veiligheidsregio Rotterdam-RijnmondStreet Address:City:State:Zip:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

24 of 39 1/6/2015 1:35 PM

Page 25: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Submittal Date: Tue Jun 03 01:53:55 EDT 2014

Committee Statement

Resolution: Larger drains are necessary for draining after a system trips and for compiling main drain test results.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

25 of 39 1/6/2015 1:35 PM

Page 26: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 27-NFPA 15-2014 [ Section No. 7.3.3.1 ]

7.3.3.1 Subsection 7.3.3 shall apply to the control of pool fires resulting from a flammable or combustible liquid spill.

Statement of Problem and Substantiation for Public Input

Already covered in 7.3.3

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 12-NFPA 15-2014 [Section No. 7.3.3.2] another part of 7.3.3

Submitter Information Verification

Submitter Full Name: Peter WillseOrganization: XL Global Asset Protection SerStreet Address:City:State:Zip:Submittal Date: Mon Jun 30 09:19:46 EDT 2014

Committee Statement

Resolution: FR-10-NFPA 15-2014Statement: Already covered in 7.3.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

26 of 39 1/6/2015 1:35 PM

Page 27: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 12-NFPA 15-2014 [ Section No. 7.3.3.2 ]

7.3.3.2

The water spray system shall be designed to apply a net rate of not less than 0.30 gpm/ft 2 [12.2 (L/min)/m 2 ] of protected area.

Statement of Problem and Substantiation for Public Input

Alrerady stated in 7.3.3

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 27-NFPA 15-2014 [Section No. 7.3.3.1]

Submitter Information Verification

Submitter Full Name: Peter WillseOrganization: XL Global Asset Protection SerStreet Address:City:State:Zip:Submittal Date: Sat Apr 12 12:55:45 EDT 2014

Committee Statement

Resolution: FR-11-NFPA 15-2014Statement: Alrerady stated in 7.3.3

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

27 of 39 1/6/2015 1:35 PM

Page 28: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 15-NFPA 15-2014 [ New Section after 7.4.3.4 ]

TITLE OF NEW CONTENTType your content here ...

7.4.3.4.1 Nozzles shall be directed toward the wetted surface of the column (see Figure 7.4.3.1)

7.4.3.4.2* Nozzles shall be spaced not less than 10 ft. on center with each alternate nozzle located on the opposite side of the column.

A.7.4.3.4.2 Nozzles need to be located on opposites sides of the column with every other nozzle on the opposite side. This will result in anarrangement such that the nozzles on one side alone will be 20 ft. apart, but all nozzles will be 10 ft. apart.

7.4.3.4.3 Nozzles shall extend the full length of the column, or until a fire rated barrier is reached.

Statement of Problem and Substantiation for Public Input

NFPA 15, as currently written, provides little or no guidance on how the nozzles should be positioned or located when used to protect a steel column. This addition will provide that guidance.

Submitter Information Verification

Submitter Full Name: Jeffery SuttonOrganization: Global Risk ConsultantsStreet Address:City:State:Zip:Submittal Date: Tue May 06 12:05:47 EDT 2014

Committee Statement

Resolution: A task group is being formed to review this issue and develop a public comment. The proposed requirements are too restrictive.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

28 of 39 1/6/2015 1:35 PM

Page 29: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 34-NFPA 15-2014 [ Sections 7.4.4.6, 7.4.4.7 ]

Sections 7.4.4.6, 7.4.4.77.4.4.6

Nozzles shall be positioned such that the water spray does not envelop energized bushings or lightning arresters surge protectiondevices(SPD) by direct impingement.7.4.4.7

Direct impingement of water spray on energized bushings and/or lightning arresters surge protection devices(SPD) shall be permitted onlywhen authorized by the manufacturer or manufacturer’s literature and the owner.

Statement of Problem and Substantiation for Public Input

Proposal is submitted to clarify the new accepted term of "Surge Protection Device(SPD)". This phrase is consistent with other NFPA documents, as well as UL standards.

Submitter Information Verification

Submitter Full Name: Mark MorganOrganization: East Coast Lightning EquipmentAffilliation: NFPA 780 References Task GroupStreet Address:City:State:Zip:Submittal Date: Sat Jul 05 08:18:45 EDT 2014

Committee Statement

Resolution: FR-12-NFPA 15-2014Statement: Proposal is submitted to clarify the new accepted term of "Surge Protection Device(SPD)". This phrase is consistent with other NFPA

documents, as well as UL standards.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

29 of 39 1/6/2015 1:35 PM

Page 30: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 20-NFPA 15-2014 [ Section No. 8.2.1.2 ]

8.2.1.2 Deviation from approved plans shall require written permission by the design professional of the revised plans and approval by the authorityhaving jurisdiction.

Statement of Problem and Substantiation for Public Input

The design professional is responsible for the overall plan. It is important that the design professional agree with changes being made to the plan. A good example is the design change that occurred to the skywalk in Kansas City that collapsed, with devastating effects. In that case, a change was made to the plan that the design professional was unaware. Written permission from the design professional is needed for verification.

Submitter Information Verification

Submitter Full Name: Jim MuirOrganization: Building Safety Division, Clark County, WashingtonAffilliation: NFPA's Building Code Development Committee (BCDC)Street Address:City:State:Zip:Submittal Date: Tue May 20 13:23:34 EDT 2014

Committee Statement

Resolution: There may not be a design professional on every project and the existing language requires the approval of an AHJ.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

30 of 39 1/6/2015 1:35 PM

Page 31: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 16-NFPA 15-2014 [ New Section after 8.4 ]

8.4.1 Water supply information shall be current within 12 months of the plan submittal.

Statement of Problem and Substantiation for Public Input

Although NFPA 15 currently requires detailed water supply information to be provided on the plans, there is no requirement regarding how current this information needs to be. Water supply information current within 1 year is a common practice and also required by NFPA 13, 23.2.1.1.

Submitter Information Verification

Submitter Full Name: Jeffery SuttonOrganization: Global Risk ConsultantsStreet Address:City:State:Zip:Submittal Date: Tue May 06 12:59:49 EDT 2014

Committee Statement

Resolution: FR-13-NFPA 15-2014Statement: Although NFPA 15 currently requires detailed water supply information to be provided on the plans, there is no requirement regarding how

current this information needs to be. Water supply information current within 1 year is a common practice and also required by NFPA 13,23.2.1.1.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

31 of 39 1/6/2015 1:35 PM

Page 32: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 35-NFPA 15-2014 [ Section No. 8.5.3.10 ]

8.5.3.10 Pipe friction loss shall be calculated in accordance with the Hazen-Williams formula, using C values as shown in Table 8.5.3.10, and using theactual internal pipe diameter in the formula.Table 8.5.3.10 Hazen-Williams C Value for Pipe and Tube

Pipe or TubeHazen-Williams

C Value

Unlined cast or ductile iron 100Galvanized steel (all) 120Black Steel (all) 120Plastic (listed) — underground 150Cement lined cast or ductile iron 140Copper tube or stainless steel 150

Statement of Problem and Substantiation for Public Input

Water filled black steel pipe is permitted by NFPA 15 (see section 5.3.6.3 - "Water-filled steel piping shall be permitted to be black steel."). As black steel piping is allowed, the Hazen-C Value for water filled black steel should be included in Table 8.5.3.10 of NFPA 15. This c value (120) was taken from NFPA 13, table 23.4.4.7.1.

Submitter Information Verification

Submitter Full Name: Roland AspOrganization: National Fire Sprinkler AssociationStreet Address:City:State:Zip:Submittal Date: Mon Jul 07 11:40:08 EDT 2014

Committee Statement

Resolution: FR-14-NFPA 15-2014

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

32 of 39 1/6/2015 1:35 PM

Page 33: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Statement: Table 8.5.3.10 was revised to align with NFPA 13.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

33 of 39 1/6/2015 1:35 PM

Page 34: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 7-NFPA 15-2013 [ New Section after 10.2.5 ]

10.2.6 Flushing operations shall occur through a strainer, screen, filter or other method to visually ensure piping isclear of debris. Openings in the strainer, screen, filter, or other method shall not be more that 1/8 inches indiameter.

Statement of Problem and Substantiation for Public Input

Provides prescriptive details with pipe flushing process.

Submitter Information Verification

Submitter Full Name: Kelly NicolelloOrganization: Western Regional Fire Code DevStreet Address:City:State:Zip:Submittal Date: Tue Sep 24 19:34:15 EDT 2013

Committee Statement

Resolution: Flushing of underground does not require the capturing of debris in the pipe.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

34 of 39 1/6/2015 1:35 PM

Page 35: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 36-NFPA 15-2014 [ Chapter 11 ]

Chapter 11 System Inspection, Testing and Maintenance11.1 General.11.1.1

A water spray system installed in accordance with this standard shall be properly inspected, tested, and maintained in accordance with NFPA25, Standard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems, and NFPA 72, National Fire Alarm andSignaling Code, to provide at least the same level of performance and protection as designed.11.1.2

The owner shall be responsible for conducting system inspection, testing, and maintenance and maintaining the system in operating condition.

Statement of Problem and Substantiation for Public Input

NFPA 25 also addresses inspections and testing of fire protection systems.

Submitter Information Verification

Submitter Full Name: Roland AspOrganization: National Fire Sprinkler AssociationStreet Address:City:State:Zip:Submittal Date: Mon Jul 07 11:57:39 EDT 2014

Committee Statement

Resolution: FR-15-NFPA 15-2014Statement: NFPA 25 also addresses inspections and testing of fire protection systems.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

35 of 39 1/6/2015 1:35 PM

Page 36: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 37-NFPA 15-2014 [ Chapter C ]

Annex C Informational ReferencesC.1 Referenced Publications.The documents or portions thereof listed in this annex are referenced within the informational sections of this standard and are not part of therequirements of this document unless also listed in Chapter 2 for other reasons.C.1.1 NFPA Publications.

National Fire Protection Association, 1 Batterymarch Park, Quincy, MA 02169-7471.

NFPA 13, Standard for the Installation of Sprinkler Systems, 2010 edition 2016 .

NFPA 14, Standard for the Installation of Standpipe and Hose Systems, 2010 edition 2016 .

NFPA 24, Standard for the Installation of Private Fire Service Mains and Their Appurtenances, 2010 edition 2016 .

NFPA 30, Flammable and Combustible Liquids Code, 2012 edition 2015 .

NFPA 68, Standard on Explosion Protection by Deflagration Venting, 2007 edition 2013 .

NFPA 69, Standard on Explosion Prevention Systems, 2008 edition 2014 .

NFPA 750, Standard on Water Mist Fire Protection Systems, 2010 edition 2015 .

NFPA 1964, Standard for Spray Nozzles, 2008 edition 2013 .

Fire Protection Guide to Hazardous Materials, 2001 edition 2008 .

C.1.2 Other Publications.C.1.2.1 ANSI ASME Publications.

American National Standards Institute, Inc., 25 West 43rd Street, 4th Floor, New York, NY 10036.

ANSI/ASME B1.20.1, Pipe Threads, General Purpose , 1983.

C.1.2.2 ASME Publications.American Society of Mechanical Engineers, ASME International , Three Park Avenue, New York, NY 10016-5990.

ASME B.1.20.1, Pipe Threads, General Purpose (inch) , 1983 2013 .

Transactions of the ASME, January 1944, 1–53. “Requirements for relief of pressure in vessels exposed to fire,” “Venting of tanks exposed tofire,” and “Heat input to vessels.”

C.1.2. 3 2 ASTM Publications.ASTM International, 100 Barr Harbor Drive, PO. Box C700, West Conshohocken, PA 19428-2959.

ASTM A 135/A 135M , Standard Specification for Electric-Resistance-Welded Steel Pipe, 1993 2009, reapproved 2014 .

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

36 of 39 1/6/2015 1:35 PM

Page 37: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

C.1.2. 4 3 CSB Publications.U.S. Chemical Safety and Hazard Investigation Board, 2175 K Street NW, Washington, DC 20037.

CSB Report No. 2004-10-I-IL, Vinyl Chloride and Monomer Explosion, March 2007.

C.1.2. 5 4 NIST Publications.National Institute of Standards and Technology, 100 Bureau Drive, Stop 1070, Gaithersburg, MD 20899-1070.

Mawhinney, J. R. “Engineering Criteria for Water Mist Fire Suppression Systems.” Presented at Water Mist Fire Suppression Workshop, March1–2, 1993.

C.1.2. 6 5 National Technical Information Service Publications.National Technical Information Service, 5285 Port Royal 5301 Shawnee Road, Springfield Alexanderia , VA 22161 22312 .

U.S. Department of Defense Standard DOD 6055.9-STD, Ammunition and Explosives Safety Standards.

C.1.2. 7 6 Other Publications.Rubber Reserve Company Memorandum 123, “Protection of Vessels Exposed to Fire.”C.2 Informational References.

The following documents or portions thereof are listed here as informational resources only. They are not a part of the requirements of thisdocument.

Requirements for Relief of Overpressure in Vessels Exposed to Fire, J. J. Duggan, C. H. Gilmour, P. F. Fisher.

Rubber Reserve Company Memorandum 89, November 19, 1944, “Heat Input to Vessels.”

Sprinkler Hydraulics and What It’s All About, Harold S. Wass, Jr., Society of Fire Protection Engineers, April 2000.

C.3 References for Extracts in Informational Sections.NFPA 30, Flammable and Combustible Liquids Code, 2012 edition 2015 .

Statement of Problem and Substantiation for Public Input

Referenced current editions.

Related Public Inputs for This Document

Related Input RelationshipPublic Input No. 24-NFPA 15-2014 [Section No. 2.3] Referenced current editions.

Submitter Information Verification

Submitter Full Name: Aaron AdamczykOrganization: [ Not Specified ]Street Address:City:

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

37 of 39 1/6/2015 1:35 PM

Page 38: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

State:Zip:Submittal Date: Mon Jul 07 21:22:02 EDT 2014

Committee Statement

Resolution: FR-2-NFPA 15-2014Statement: Referenced current editions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...

38 of 39 1/6/2015 1:35 PM

Page 39: Public Input No. 24-NFPA 15-2014 [ Section No. 2.3 ] · 2016-02-29 · American Welding Society, 550 8669 N.W . LeJeune Road, 36 Street, #130 , Miami, FL 33126 33166-6672. AWS A 5.8M

Public Input No. 33-NFPA 15-2014 [ Section No. C.1.2.3 ]

C.1.2.3 ASTM Publications.ASTM International, 100 Barr Harbor Drive, PO. Box C700, West Conshohocken, PA 19428-2959.

ASTM A 135/A35M , Standard Specification for Electric-Resistance-Welded Steel Pipe, 1993 09(2014) .

Statement of Problem and Substantiation for Public Input

Update to latest year date.

Submitter Information Verification

Submitter Full Name: Steve MawnOrganization: ASTM InternationalStreet Address:City:State:Zip:Submittal Date: Wed Jul 02 15:34:21 EDT 2014

Committee Statement

Resolution: FR-2-NFPA 15-2014Statement: Referenced current editions.

National Fire Protection Association Report http://submittals.nfpa.org/TerraViewWeb/ContentFetcher?commentParams=(CommentType="P...