    Primary Test Manager (PTM)

    The Next Generation inPower Transformer Diagnostics and Assessment

  • 8/4/2019 PTM Brochure ENU

    2/8

    2

    Power transformers are critical andcapital-intensive assets. They need to be

    kept in operation as long as possible -

    and should never fail. If a transformer

    failure does occur, it may cause huge

    economic losses and can even result

    in injury or death. Thus testing and

    diagnosis of the condition of power

    transformers is essential.

    OMICRON offers state-of-the-art power

    transformer test equipment for testing

    according to national and international

    standards, such as IEEE 62 (C57.152) or

    IEC 60076-1 and -3.

    OMICRONs industry experts offer

    support with diagnostic measurementson power transformers and help with

    the interpretation of the results in

    order to reliably assess a transformers

    condition. The application-oriented

    training help to understand theory

    and practice.

    The New Standard

  • 8/4/2019 PTM Brochure ENU

    3/8

    3

    Analyzing the transformer condition

    The new Primary Test Manager software makes the CPC 100together with the CP TD1 the perfect instrument for analyzingthe condition of transformer and other assets like bushingsand LTCs.

    With laboratory accuracy and excellent noise suppression, theCPC 100 plus CP TD1 provide reliable results regardless of thelevel of electrical interference in the area. During all tests thehighest safety standard is guaranteed by the safety switch,the strobe light, the transformer switch box CP SB1 and othersafety features.

    Setting standards

    The test can be performed as recommended in relatedstandards such as IEEE 62 (C57.152) or IEC 60076-1 and -3.The CPC 100 plus CP TD1 meet and exceed all measurementand accuracy requirements.

    Portable, lightweight and easy to handle

    In spite of its overall rugged design, the heaviest CPC 100component only weighs 29 kg (64 lbs). Therefore it is easy totransport and can be handled by one person. A custom-builttrolley allows for practical handling on site and off site alongwith easy and quick breakdown into portable components.

    Eight standard primary test measurements

    Using the multifunctional primary test system CPC 100together with the unique capacitance and power factor /dissipation factor (tan delta) measuring instrument CP TD1you can perform a wide range of tests in only one system.

    This multifunctionality saves money, time and training costs

    for the staff. The following tests can be performed:

    1. Transformer power factor / dissipation factor (tandelta) and capacitance

    2. Bushing power factor / dissipation factor (tan delta)and capacitance

    3. Exciting current

    4. TTR - transformer turns ratio

    5. Surge arrester

    6. Insulating fluids

    7. Leakage reactance

    8. DC winding resistance

    ower Transformer Diagnostics

    The application of innovative measurement techniques andthe use of high-precision components in the CP TD1 bringslaboratory precision with a rugged design into the fieldof insulation condition testing. The CPC 100 plus CP TD1also offer new test methods such as testing with variablefrequency.

  • 8/4/2019 PTM Brochure ENU

    4/8

    4

    Transient current during switching process

    Taps

    DynamicLTCdiagnostics

    Ripple of a Load Tap Changer (LTC)s

    A

    Aged LTC

    Good LTC

    Slope

    Phase A Phase B Phase C

    Ripple

    The CPC 100 can be operated stand alone or through a PCwith the Primary Test Manager. Test templates for all standardtests are available. This allows performing the test mostcomfortably, saves time, delivers a clear result and offers an

    automatic reporting.

    Variable frequency power factor / Dissipation factor(tan delta) frequency sweeps (15 Hz to 400 Hz) forpower factor fills in missing details not obtainablefrom a single power factor measurement, discerningwhether moisture contamination is in the cellulose orif the oil is contaminated or otherwise compromised.It also offers the ability to effectively discriminatebetween a deteriorated power factor / dissipation factor

    (tan delta) test result that warrants more frequentmonitoring and one that requires immediateremediation.

    1

    3 Frequency Response of Stray Losses (FRSL) shortedparallel strands, which cannot be detected using excitingcurrent testing at system frequency, can be foundby performing the leakage reactance test at higherfrequencies.

    Fast and in-depth

    The Advanced Diagnostics features provide a moreilluminating and much faster condition assessment oftransformers, bushings and LTCs than ever before.

    Condenser-type bushing (220 kV RIP)

    PowerFactor/DissipationFactor(tandelta)

    Additional diagnostics because of

    frequency sweep from 15 to 400 Hz

    Aged Bushing

    Medium Aged Bushing

    New Bushing

    Variablefrequency

    60 Hz

    2 Dynamic LTC diagnostics (OLTC test) the transientswitch is recorded Slope and Ripple and isgraphically displayed to find faults on the OLTC, TapSelector or DETC.

    Short-circuit impedance / leakage reactance

    R(f)-ThreePh

    aseEquivalent

    Frequencyrespon

    seofstraylosses

    Increased losses are visible at higher frequencies due toshorted parallel strands (delta between phases)

    Additional diagnostics because of

    frequency sweep from 15 to 400 Hz

    Phase A Phase B Phase C

    Fast and safe

    While using the transformer switch box CP SB1, the trans-former must only be connected once for TTR, DC WindingResistance and the dynamic OLTC test. This makes it a mostefficient accessory for the CPC 100 which dramaticallyreduces the necessary test time and improves safety.

    The automatic tap changer control feature simplifies the testprocedure and reduces test errors. Additional safety featuresare provided by the built-in safety standards of the CPC 100which can be combined with the 3-position remote safety

    switch and the strobe light accessories.

    Advanced Diagnostics and Safety Features

  • 8/4/2019 PTM Brochure ENU

    5/8

  • 8/4/2019 PTM Brochure ENU

    6/8

    6

    Technical Data

    CPC 100

    Generator / Output

    Current outputs

    Range Amplitude tmax

    1 Vmax

    2 Powermax

    2 f

    800 A AC3 0 ... 800 A 25 s 6.0 V 4800 VA 15 ... 400 Hz

    0 ... 400 A 8 min 6.4 V 2560 VA 15 ... 400 Hz

    0 ... 200 A > 2 h 6.5 V 1300 VA 15 ... 400 Hz

    6 A AC10 0 ... 6 A > 2 h 55 V 330 VA 15 ... 400 Hz

    3 A AC10 0 ... 3 A > 2 h 110 V 330 VA 15 ... 400 Hz

    400 A DC 0 ... 400 A 2 min 6.5 V 2600 VA DC

    0 ... 300 A 3 min 6.5 V 2600 VA DC

    0 ... 200 A > 2 h 6.5 V 2600 VA DC

    6 A DC4,10 0 ... 6 A > 2 h 60 V 360 VA DC

    2000 A AC3 with an optional Current Booster

    Voltage outputs

    Range Amplitude5 tmax

    Imax

    Powermax

    5 f

    2 kV AC3 0 ... 2 kV 1 min 1.25 A 2.5 kVA 15 ... 400 Hz

    0 ... 2 kV > 2 h 0.5 A 1.0 kVA 15 ... 400 Hz

    1 kV AC3 0 ... 1 kV 1 min 2.5 A 2.5 kVA 15 ... 400 Hz

    0 ... 1 kV > 2 h 1.0 A 1.0 kVA 15 ... 400 Hz

    500 V AC3 0 ... 0.5 kV 1 min 5.0 A 2.5 kVA 15 ... 400 Hz

    0 ... 0.5 kV > 2 h 2.0 A 1.0 kVA 15 ... 400 Hz

    130 V AC10 0 ... 130 V > 2 h 3.0 A 390 VA 15 ... 400 Hz

    Internal measurement of outputs (Accuracy6)

    Amplitude Phase

    Output Range Reading Full Scale Full Scale

    800 A AC - error < 0.10 % error < 0.10 % error < 0.10

    400 A DC - error < 0.20 % error < 0.05 % -

    2 kV AC 2000 V error < 0.05 % error < 0.05 % error < 0.10

    1000 V error < 0.05 % error < 0.05 % error < 0.15

    500 V error < 0.05 % error < 0.05 % error < 0.20

    5 A error < 0.20 % error < 0.05 % error < 0.10

    500 mA error < 0.05 % error < 0.05 % error < 0.10

    Inputs

    Measuring inputs (Accuracy6)

    Amplitude Phase

    Input Imped. Range Reading Full Scale Full Scale

    I AC/DC4,7 < 0.1 10 A AC error < 0.05 % error < 0.05 % error < 0.10

    1 A AC error < 0.05 % error < 0.05 % error < 0.15

    10 A DC error < 0.03 % error < 0.08 % -

    1 A DC error < 0.03 % error < 0.08 % -

    V1 AC8 500 k 300 V error < 0.05 % error < 0.05 % error < 0.10

    30 V error < 0.05 % error < 0.05 % error < 0.10

    3 V error < 0.10 % error < 0.05 % error < 0.10

    300 mV error < 0.15 % error < 0.05 % error < 0.10

    V2 AC8 10 M 3 V error < 0.03 % error < 0.08 % error < 0.10

    300 mV error < 0.08 % error < 0.08 % error < 0.10

    30 mV error < 0.10 % error < 0.25 % error < 0.15

    V DC4,7 500 k 10 V error < 0.03 % error < 0.08 % -

    1 V error < 0.03 % error < 0.08 % -

    100 mV error < 0.05 % error < 0.10 % -

    10 mV error < 0.05 % error < 0.15 % -

    meter (DC)

    Mode Connection Range Current Accuracy (full scale)

    0.5 ... 12.5 m 4-wire 400 A DC 400 A error < 0.45 %

    10 ... 1 4-wire 6 A DC 6 A error < 0.35 %

    100 ... 10 4-wire 6 A DC 1 A error < 0.25 %

    0.2 ... 20 k 2-wire V DC in 100 kResponse time 1 msBinary input for dry contacts or voltages up to 300 V DC7

    Guaranteed values valid over one year within 23C 5C (73F 10F), in the frequencyrange of 45 to 65 Hz or DC. Accuracy values indicate that the error is smaller than +/-(Value read * Reading error + Full Scale of the range * Full Scale Error).

    1 With mains voltage 230 V with 2 x 6 m high current cable at 23C 5C (73F 10F)ambient temperature.

    2 Signals below 50 Hz or above 60 Hz with reduced values possible.3 Output can be synchronized with mains.4 The input / output is protected with lightning arrestors between the pins and against

    protective earth. In case of energies above a few hundred Joule the lightning arrestorsapply a permanent short circuit to the input / output.

    5 Signals below 50 Hz or above 200 Hz with reduced values possible.6 98 % of all units have an accuracy better than specified as Typical.7 Input is galvanically separated from all other inputs.8 V1 and V2 are galvanically coupled but separated from all other inputs.9 There are power restrictions for mains voltages below 190 V AC.10

    Fuse protected.11 Error of reading < than value.

  • 8/4/2019 PTM Brochure ENU

    7/8

    7

    CP TC12 - 12kV Oil Test Cell

    Cell Type Three-terminal, guarded

    Cell Gap Spacing 0.43 in / 11 mm

    Sample Volume (min - max) 41 to 68 f l.oz. / 1.2 to 2 liters

    Cell Capacitance 65 pF, nominal (in air)

    Maximum Test Voltage 12 kV rms

    Voltage Operating Range 2.5 to 12 kV for a stress of200 to 1100 V/mm7.9 to 43.3 V/in

    Dimensions (W x H x D) 8.7 x 9.3 x 8.7 in / 220 x 235 x 220 mm

    Weight approx. 20 lbs / 9 kg

    Article Number VEHZ0601

    CP SB1 Switch Box

    Max. Voltage 300 V AC

    Max. Current 6 A DC

    Dimensions (W x H x D) 14 x 9 x 4.5 inch / 360 x 235 x 110 mm

    Weight approx. 13 lbs / 6 kg

    Article Number VEHZ0692

    CP TD1 (with CPC 100)

    High voltage output

    V I tmax

    at f

    0 ... 12 kV AC 300 mA > 2 min 15-400 Hz

    100 mA > 60 min 15-400 Hz

    Internal measurement of voltage output / current inputs

    Range Resolution Accuracy

    12000 V AC 1 V error < 0.3 % reading + 1V

    5 A AC 5 digits error < 0.5 % reading

    8 mA AC 5 digits error < 0.3 % reading + 100 nA

    Capacitance Cp (equivalent parallel circuit)

    Range Resolution Accuracy Conditions

    1 pF 3 F error < 0.05 % reading + 0.1 pF > 2 min < 8 mA

    error < 0.2 % reading > 60 min > 8 mA

    Power factor PF / Dissipation factor DF

    Range Resolution Accuracy Conditions

    0 10 %(capacitive)

    5 digits error < 0.1 % reading+ 0.005 %

    15 ... 70 Hz< 8 mA

    0 100(0 ... 10000 %)

    5 digi ts error < 0.5 % reading+ 0.02 %

    -

    Inductance

    Range Resolution Accuracy

    1 H ... 1000 KH (CP TD1 + CPC 100) 6 digits 0.3 % reading

    50 H ... 1 H (CPC 100) 6 digits 0.3 % reading

    Watts / Power (P, Q, S)

    Range Resolution Accuracy

    0 ... 3600 W / VA / var 5 digits 0.5 % reading + 1 mW

    Impedance

    Range Resolution Accuracy

    1,000 ... 1,200 M 6 digits 0.5 %

  • 8/4/2019 PTM Brochure ENU

    8/8

    AmericasOMICRON electronics Corp. USA12 Greenway Plaza, Suite 1510Houston, TX 77046, USAPhone: +1 713 830-4660

    +1 800-OMICRONFax: +1 713 [email protected]

    OMICRONL217, February 2011Subject to change without notice

    Asia-PacificOMICRON electronics Asia LimitedSuite 2006, 20/F, Tower 2The Gateway, Harbour CityKowloon, Hong Kong S.A.R.Phone: +852 2634 0377Fax: +852 2634 [email protected]

    Europe, Middle East, AfricaOMICRON electronics GmbHOberes Ried 16833 Klaus, AustriaPhone: +43 5523 507-0Fax: +43 5523 [email protected]

    www.omicron.at www.omicronusa.com

    The following publications provide further information on the solutions described in thisbrochure (catalog):

    For a complete list of available literature please visit our website.

    OMICRON is an international company serving the electricalpower industry with innovative testing and diagnostic solutions.The application of OMICRON products allows users to assessthe condition of the primary and secondary equipment on theirsystems with complete confidence. Services offered in the area ofconsulting, commissioning, testing, diagnosis, and training makethe product range complete.

    Customers in more than 130 countries rely on the companysability to supply leading edge technology of excellent quality.

    Broad application knowledge and extraordinary customer supportprovided by offices in North America, Europe, South and East Asia,Australia, and the Middle East, together with a worldwide networkof distributors and representatives, make the company a marketleader in its sector.

    Transformer DiagnosisCPC 100 + CP TD1

    Switch Box CP SB1 Switch Box CP TC12

    CP SB1 Switch BoxAccessorytoCPC100

    MUX

    Ctrl

    CPSB1 CPC100

    Scope ofdelivery

    CP SB1 switch box 1 pcs

    C on ne ct io n ca bl e (1 5 m / 5 0 ft ) 1 0 pc s

    Kelvin clamps 8 pcs

    Tap changer connectors 6 pcs

    Grounding cable 1 pcs

    R S2 32 co mm un ic at io n ca bl e 1 p cs

    OMICRON duffel bag 1 pcs

    S tu rd y tr an sp or t c a se w it h wh ee ls 1 p cs

    Technicaldata

    Max. Voltage 300VAC

    Max. Current 6 A D CMeasurementOptionsonTransformers

    ConvertionratioWindingresistanceTapchangeroperation

    AmbientTemperature -10to55C /15to130F

    Weight 3.5kg/7.7lbs

    Dimensions( W x H x D ) 3 5 7 x 2 3 5 x 1 1 1 mm14.1x 9.3x 4.4in

    Article Number VEHZ 0692

    CPSB1SwitchBox withCPC100faster- safer- morereliable

    Fullyautomated 3-phase transformertesting

    Measurementsofratio,windingresistanceand thetapchangerbecamecomfortablewiththeCP SB1.Asan accessorytotheCPC100, testingofpowertransformersover alltapsandphasesisfullyautomated.Time consumingrewiringin-betweenmeasurementscanbe avoided.

    Benefits

    > Savestimebycomfortablyabolishingtheneed forrewiring

    > Increasessafetybyreducingthe risk ofaccidents

    > Minimizesthelikelihoodofmeasurement errors performstheratioandwindingresistancetests automatically

    Features

    > MultiplexestheCPC100outputs toallphasesof apowertransformerandviceversa

    > Quicklydischargesthetransformerbetweenmeasurements> Operatesthetapchanger,so measurementscanbeperformedwithout theneed foruserinteraction

    CPC100 plusCPSB1

    Comfortable,fullyautomated3-phasepowertransformertesting.

    t r n ic t c h n l y

    TechnicalData

    CellType Three-terminal,guarded

    CellGap Spacing 11mm /0.43in

    Meas. Electrode ( x H) 149x 104mm /5.9x 4.1in

    Sample Volume 1.2- 2liters/41- 68fl.oz.

    CellCapacitance 65pF,nominal(in air)

    MaximumTestVo ltage 12kVrms

    Voltage Operating Range 2.5- 12kVforast ressof200-1100V/mm/7.9-43.3V/in

    HVConnectors 6mm sockets

    Meas. Connectors 4mm sockets

    InnerDimensions ( x H ) 172x 180.8mm /6.8x 7.1in

    OuterDimensions

    (Wx H x D)220x 235.5x 220mm8.7x 9.3x 8.7in

    Weight ( ap pr ox .) 9 .2 k g / 2 0 lb s

    OrderNumber VEHZ0601

    CP TC12 - 12 kV Oil Test Cell

    AccessorytoCPC100

    TheCPTC12is usedinconjunctionwiththeCPC100andCPTD1to measuretangent delta/powerfactorandpermittivityofinsulationliquids,e.g.transformeroil.Thethree-electrodedesignwithguardallowsprecisemeasurement,especiallyofsmalllosses.

    Thecircularelectrodesareconstructedfrom rigidstainlesssteelandrequirea sampleof1.2to 2liters/41to68 fl.oz.

    Electricalconnectiontothe Test Cellismadeusing thestandardcablesprovidedwiththeCPTD1.