83-78-00-01 1/99 7800 Series Burner Control TOTAL BURNER CONTROL 7800 SERIES 7800 SERIES The latest in Flame Safeguard state-of-the-art technology is the7800SERlES Burner Control. The Honeywell 17800 SERIES combines safety, comprehensive diagnostics, communication and networking capabilities into one com- pact and affordable microcomputer burner control. It can do just about anything and everything you would like it to do. The 7800 SERIES works on a wide range of industrial applications: burners, boilers, furnaces, ovens, kilns, process heaters and more. The 7800 SERIES replaces more than 400 Honeywell and competitive control types. It offers you intelligent control anyway you want it: with or without communications, with or without an expanded an- nunciator, with or without a keyboard display module. Whatever features you want from a burner control, just ask. With the 7800 SERIES, the answer is...yes, it can. COMMUNICATIONS INTERFACE The 7800 SERIES can interface with compatible lBM® equivalent personal computers at an onsite or remote location through a communications interface.

Upload: marcos-russo

Post on 24-Oct-2014

236 views

Category:

Documents


6 download

TRANSCRIPT

Page 1: Programador 7800 Series RM Completa

83-78-00-011 / 9 9

7800 SeriesBurner Control

TOTAL BURNERCONTROL

7800 SERIES

7800 SERIESThe latest in Flame Safeguard state-of-the-art technologyis the7800SERlES Burner Control. The Honeywell 17800SERIES combines safety, comprehensive diagnostics,communication and networking capabilities into one com-pact and affordable microcomputer burner control. It cando just about anything and everything you would like it todo.

The 7800 SERIES works on a wide range of industrialapplications: burners, boilers, furnaces, ovens, kilns,process heaters and more. The 7800 SERIES replacesmore than 400 Honeywell and competitive control types.It offers you intelligent control anyway you want it: with orwithout communications, with or without an expanded an-nunciator, with or without a keyboard display module.Whatever features you want from a burner control, justask. With the 7800 SERIES, the answer is...yes, it can.

COMMUNICATIONS INTERFACEThe 7800 SERIES can interface with compatible lBM®equivalent personal computers at an onsite or remotelocation through a communications interface.

Page 2: Programador 7800 Series RM Completa

Flame Safeguard Systems

Product Selection Matrix for CE Sequence Primary/ProgrammerRelay Modules:

For 230 Vac nominal applications—

Fuel Burner Type Relay Module Type

Single Atmospheric EC7810

Single Atmospheric with fan EC7820

Combination or single On/Off Controlled Power Burner EC7830

Combination or single Full Modulation Power Burner EC7850

For 120 Vac nominal applications-

Fuel Burner Type Relay Module Type

Combination or single On/Off Controlled Power Burner RM7830

Combination or single Full Modulation Power Burner RM7850

Use the following pages to select the following required Use the following pages to select the following optional devices:devices: Keyboard Display module, up to 1 mounted to relay module, remoteRelay Module, 1 per burner as desiredSubbase, 1 per relay module Communications, network and controlbus modules to servicePurge Timer Card, 1 per relay module selected relaysFlame Amplifier, 1 per relay module Miscellaneous, as required to complete installation

Page 3: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC7810 PROGRAMMER RELAY MODULES:

M15515

SELECT A SUBBASE

SELECT A PURGECARD

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7810A1027EC7810A1035

DESCRIPTIONONE IGNITION ATTEMPTFIVE IGNITION ATTEMPTS

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7800E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEDATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 4: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC7820 PROGRAMMER RELAY MODULES:

M15516

SELECT A SUBBASE

SELECT A PURGECARD

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7820A1026EC7820A1034

DESCRIPTIONONE IGNITION ATTEMPTFIVE IGNITION ATTEMPTS

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7800E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEDATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 5: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC/RM7830 PROGRAMMER RELAY MODULES:

M15517

SELECT A SUBBASE

SELECT A PURGECARD

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7830A1033EC7830A1041EC7830A1066

120VAC 50/60 HZRM7830A1003RM7830A1011RM7830A1029

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

DESCRIPTIONPOST-PURGE 2 SECONDSPOST-PURGE 30 SECONDSPOST-PURGE 15 SECONDS

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEDATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 6: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC/RM7850 PROGRAMMER RELAY MODULES:

M15519

SELECT A SUBBASE

SELECT A PURGECARD

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7850A1064EC7850A1072EC7850A1080EC7850A1122

120VAC 50/60 HZ

RM7850A1001RM7850A1027RM7850A1019

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT2 SECOND FFRT1 SECOND FFRT2 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

DESCRIPTIONDYNAMIC AIR DAMPER CHECKPOST-PURGE 2 SECONDSPOST-PURGE 30 SECONDSPOST-PURGE 15 SECONDS

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEDATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 7: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC/RM7823 FLAME SWITCH RELAY MODULES:

M15520

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7823A1004

120VAC 50/60 HZRM7823A1016

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

Page 8: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR RM7824A 24VDC PRIMARY CONTROL RELAY MODULES:

M15521

SELECT A SUBBASE

SELECT A FLAME

AMPLIFIER

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULERM7824A1006 24VDC

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.R7824C1002R7848A1008R7848B1006

DESCRIPTION3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT

CHECKINGDYNAMIC SELF-CHECKNONEAMPLICHECK™

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEDATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHC7024E, FC7015C7015

1.)

2.)

3.)

4.)

Page 9: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC/RM7885 SEMI-AUTOMATIC PRIMARY RELAY MODULES:

M15522

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7885A1011

120VAC 50/60 HZRM7885A1015

DESCRIPTION

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEDATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

Page 10: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR RM7888A SPECIAL FUNCTION PRIMARY CONTROL RELAY MODULES:

M15523

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

120VAC 50/60 HZRM7888A1019

DESCRIPTION

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

Page 11: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC/RM7890 PRIMARY CONTROL RELAY MODULES:

M15524

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7890A1011

EC7890B1010

120VAC 50/60 HZRM7890A1015RM7890A1031RM7890B1014RM7890C1005RM7890D1004

DESCRIPTION

30 SECOND PFEPWITH SHUTTER DRIVESTANDING PILOT APPLICATIONS WITH FLAME RODS ONLYINFRARED HEATER ONLY 15 OR 30 PREF

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

Page 12: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR EC/RM7895 FULL FUNCTION PRIMARY RELAY MODULES:

M15525

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

220-240 VAC 50/60 HZEC7895A1010

EC7895C1000

120VAC 50/60 HZRM7895A1014RM7895A1048RM7895B1013

RM7895C1012RM7895C1020RM7895D1011RM7895E1002RM7895F1001

DESCRIPTION

EARLY SPARK TERMINATIONDYNAMIC AIRFLOW SWITCH CHECK

EARLY SPARK TERMINATIONDYNAMIC AIRFLOW SWITCH CHECKINFRARED HEATER APPLICATIONS, 15/30 SECOND PFEPDYNAMIC AIRFLOW SWITCH CHECK, INFRAREDHEATER APPLICATIONS, 15/30 SECOND PFEP

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITH RESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

INTERRUPTED PILOT

INTERMITTENT PILOT

SELECT A PURGECARD

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 13: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR RM7838A SEMI-AUTOMATIC INDUSTRIAL PRIMARY RELAY MODULE:

M15527

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

DESCRIPTIONINTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARD

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

SELECT A PURGECARD

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

120 VAC 50/60 HZRM7838A1014

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 14: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR RM7838B SEMI-AUTOMATIC INDUSTRIAL PROGRAMMER RELAY MODULE:

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

DESCRIPTIONSEMI-AUTOMATIC PROGRAMMER WITH S7800A1001 KEYBOARD DISPLAY STANDARD

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

M15528

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A PURGECARD

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

120 VAC 50/60 HZRM7838B1013

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 15: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR UL/CSA RM78XXG, M PROGRAMMER RELAY MODULE:

M15529

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A PURGECARD

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

120VAC 50 HZRM7800G1000

RM7840G1006RM7800M1003

RM7840M1009

120VAC 60 HZRM7800G1018

RM7840G1014RM7800M1011

RM7840M1017

DESCRIPTIONMODULATING BURNER CONTROL, S7800A1001 KEYBOARD DISPLAYMODULE STANDARDMODULATING BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULEON-OFF BURNER CONTROL, S7800A1001 KEYBOARD DISPLAY MODULESTANDARDON-OFF BURNER CONTROL, WITHOUT KEYBOARD DISPLAY MODULE

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 16: Programador 7800 Series RM Completa

7800 SERIES BURNER CONTROL

65-0198—2

PRODUCT SELECTION MATRIX FOR FM/IRI RM78XXE, L PROGRAMMER RELAY MODULE:

M15530

SELECT A SUBBASE

SELECTOPTIONAL

COMPONENTS

KEYBOARDDISPLAYMODULE

COMMUNICATIONS

MISCELLANEOUS

SELECT A RELAY

MODULE

O.S. NO.Q7800A1005Q7800B1003Q7800B1011

DESCRIPTIONPANEL MOUNTBURNER/WALL MOUNTBURNER/WALL MOUNT WITH 3 KNOCKOUTS

O.S. NO.R7847A1025R7847A1033R7847A1074R7847A1082R7847B1023R7847B1031R7847B1064R7847B1072R7847C1005R7848A1008R7848B1006R7849A1015R7849A1023R7849B1013R7849B1021R7861A1026R7861A1034R7886A1001

DESCRIPTION0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT3.0 SECOND FFRT0.8 SECOND FFRT3.0 SECOND FFRT

CHECKINGNONENONENONENONEAMPLICHECK™AMPLICHECK™NONENONEDYNAMIC SELF-CHECKNONEAMPLICHECK™NONENONEAMPLICHECK™AMPLICHECK™DYNAMIC SELF-CHECKDYNAMIC SELF-CHECKDYNAMIC SELF-CHECK

O.S. NO.S7800A1001S7800A1035S7800A1043S7800A1050S7800A1068S7800A1118S7800A1126S7800B1009

DESCRIPTIONENGLISH LANGUAGEFRENCH LANGUAGEGERMAN LANGUAGEITALIAN LANGUAGESPANISH LANGUAGEKATAKANA (JAPANESE) LANGUAGEPORTUGUESE LANGUAGECHINESE LANGUAGE

O.S. NO.Q7700A1014

Q7700B1004

QS7800A1001QS7800B1000QS7800C1009QS7800D1008QS7850E1007QS7850A1006ZM7850A1001ZM7850B1000S7810A1009S7810B1007

DESCRIPTIONNETWORK INTERFACE UNIT, 120 VAC, 50/60 HZ APPLICATIONS.EXTERNAL MODEM REQUIRED.NETWORK INTERFACE UNIT, WITH UNIVERSAL 100-250 VAC, 50/60 HZEXTERNAL POWER SUPPLY, EXTERNAL MODEM REQUIRED.CONTROLBUS MODULE, STANDARDCONTROLBUS MODULE, MULTI DROPCONTROLBUS MODULE, DATA ACQUISITION MODULESCONTROLBUS MODULE, ARMSTRONGCONTROLBUS MODULE, PULSAFEEDERCONTROLBUS MODULE, GENERAL PURPOSE INTERFACECOMBUSTION SYSTEM MANAGER® SOFTWARESYSNET INTEGRATION SOFTWAREDATA CONTROLBUS™ MODULE (IF NO KEYBOARD DISPLAY IS USED)DATA CONTROLBUS™ MODULE, MULTI DROP SWITCH MODULE

O.S. NO.S7820A1007S7830A1005203541203765221729204718A204718B204718C

205321B221818A221818C

DESCRIPTIONREMOTE RESET MODULEEXPANDED ANNUNCIATIOR (120 VAC, 50/60 HZ)DATA CONTROLBUS CONNECTOR, 5-WIREREMOTE DISPLAY MOUNTING BRACKETDUST COVER, RELAY MODULEKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEARKEYBOARD DISPLAY MODULE COVER, CLEARKEYBOARD DISPLAY MODULE COVER, NEMA 4, CLEAR WITHRESET BUTTONFLUSH DISPLAY MOUNTING KITEXTENSION CABLE, DISPLAY 5FT (1524MM)EXTENSION CABLE, DISPLAY 10FT (3048MM)

USE WITHFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLSFLAME ROD, PHOTOCELLS*FLAME ROD, PHOTOCELLS*, C7012A, CC7012E, F**C7015C7015C7027, C7035C7027, C7035C7027, C7035C7027, C7035C7061A**C7061A**C7076A, D**

SELECT A PURGECARD

O.S. NO.ST7800A1005ST7800A1013ST7800A1021ST7800A1039ST7800A1047ST7800A1054ST7800A1062

DESCRIPTIONTIMING: 2 SECONDTIMING: 7 SECONDTIMING: 10 SECONDTIMING: 30 SECONDTIMING: 40 SECONDTIMING: 60 SECONDTIMING: 90 SECOND

O.S. NO.ST7800A1070ST7800A1088ST7800A1096ST7800A1104ST7800A1112ST7800A1120ST7800A1138ST7800A1146

DESCRIPTIONTIMING: 2.5 MINUTETIMING: 4 MINUTETIMING: 6 MINUTETIMING: 9 MINUTETIMING: 12 MINUTETIMING: 15 MINUTETIMING: 22 MINUTETIMING: 30 MINUTE

120VAC 50/60 HZRM7800E1010RM7840E1016RM7800L1012RM7840L1018RM7800L1053RM7840L1026

DESCRIPTIONENERGY SAVING PURGE, S7800A1001 KEYBOARD DISPLAY STANDARDENERGY SAVING PURGE WITHOUT KEYBOARD DISPLAYS7800A1001 KEYBOARD DISPLAY STANDARDWITHOUT KEYBOARD DISPLAYINTERMITTENT PILOT, S7800A1001 KEYBOARD DISPLAY STANDARDINTERMITTENT PILOT WITHOUT KEYBOARD DISPLAY

SELECT A FLAME

AMPLIFIER

* FLAME ROD AND PHOTOCELL LEADWIRES RUN GREATER THAN 50FT (1524 CM).** EC APPLICATIONS REQUIRE A 220-240 VAC TO 120 VAC, STEP DOWN, 10VA TRANSFORMER.

1.)

2.)

3.)

4.)

5.)

Page 17: Programador 7800 Series RM Completa

7800 SERIES Relay Modules

RM7888A Semi-Automatic Industrial Primary ControlMicroprocessor-based integratedburner control for industrial processsemi-automatically fired gas, oil,coal, or combination fuels for singleand multiple burner applications.Provides level of safety, functional ca-pability and features beyond conven-tional controls.

Functions include automatic burnerstartup sequencing, five user select-able run sequences, four line-voltage sequence control inputs,flame supervision, system status indication, system or self-diag-nostics and troubleshooting.Requires a relay module, subbase, and amplifier for operation.Options include PC interface, keyboard display module, DATACONTROLBUS MODULE™, remote display mounting, first-out expanded annunciator, and COMBUSTION SYSTEMMANAGER™ software.Use with master system control which determines purge timingand confirms air supply and air flow.Nonvolatile memory retains history files and sequencing statusafter power loss.Optional remote reset capability.Five LEDs provide sequence information.Interchangeable plug-in flame amplifiers.Local or remote annunciation of operation and fault information.

SEQUENCE TIMING FOR NORMAL OPERATION:

APPROVAL BODIES:Underwriters Laboratories Inc. Component Recognized.Factory Mutual Approved.Canadian Standards Association certified.

APPROXIMATE DIMENSIONS: 5 in. [127 mm] wide; 5 in. [127 mm]high; 5-1/4 in. [133 mm] deep with Q7800A Subbase, 6-3/32 in.[155 mm] deep with Q7800B Subbase.

WEIGHT: 1 lb., 10 oz. [737 grams].OPERATING AMBIENT TEMPERATURE RANGE: –40 F to +140 F

[–40 C to +60 C].ELECTRICAL RATINGS:

Voltage and Frequency: 120 Vac (+10/–15%), 50 or 60 Hz (±10%).REQUIRED COMPONENTS:

Q7800A or B Universal Wiring Subbase. R7847, R7848,R7849, R7861, or R7886 Plug-in Flame Signal Amplifier.

OPTIONAL COMPONENTS:A78001002 Tester.Q7700A1014 Communications Interface Base Unit.QS7800A1001 Communications Interface ControlBus Module.S7800A1001 Keyboard Display Module.S7810A1009 DATA CONTROLBUS MODULE™.S7820A1007 Remote Reset Module.S7830A1005 Expanded Annunciator.ZM7850A1001 COMBUSTION SYSTEM MANAGER™ (CSM™).123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A,B Remote Display Mounting

Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221818A Sixty-inch Extension Cable Assembly.221818C 120 inch Extension Cable Assembly.

Pilot Flame Main FlameRM7888A Sequence Initiate Standby Purge Establishing Period Establishing Period Pilot Relight Run

Pilot: PV Return 10 sec. a b 10 sec. 15 sec. 5 sec. to infinity a

Pilot: MV LoFire —

DSI Normal 4 sec. — —

DSI High/Low Stepfire — —

DSI On/Off Stepfire — —a STANDBY and RUN can be an infinite time period.b PURGE time is determined by the system master controller.

Order Number Description

RM7888A1027 Semi-automatic relay module, 50/60 Hz.

Page 18: Programador 7800 Series RM Completa

Primary Relay Modules—Automatic

NOTE: CONTROLS FOR USE IN 7800 SERIES BURNER CONTROL SYSTEMS ARE AVAILABLE ONLY THROUGHAUTHORIZED HONEYWELL 7800 SERIES DISTRIBUTORS.For the name of your nearest authorized Honeywell 7800 SERIES Distributor, please call 1-800-345-6770, ext. 2040.

NV17890A, B, C, D/EC7890A, B Primary ControlsMicroprocessor-based integrated primary burner control for automatically fired gas, oil, coal or combina-tion fuel single burner applications.

Functions include automatic burner sequencing, flamesupervision, system status indication, system or self-diagnostics and troubleshooting.

Five LEDs provide sequence information.

Selectable recycle or lockout on loss of flame.

Shutter drive output (RM7890B) for use with DynamicSelf-Check flame detectors.

Access for external electrical voltage checks.

Interchangeable plug-in flame amplifiers.

Nonvolatile memory retains history files and sequencestatus after loss of power.

Compatible with existing Honeywell flame detectors.

APPROVAL BODIES: RN17890Underwriters Laboratories Inc. listed, File No. MP268,

Guide No. MCCZ.Canadian Standards Association certified, LR9S329-3.Factory Mutual approved.IRI acceptable.Federal Communications Commission: Part 15, Class

B-Emissions.

DIMENSIONS: 5 in. [127 mm] wide, 5 in. [127 mm] high,3-1/32 in. [77 mm] deep.

WEIGHT: 1 lb., 13 oz.OPERATING AMBlENT TEMPERATURE RANGE: – 40 F to

+140 F [– 40 C to + 60 C].ELECTRICAL RATINGS:Voltage and Frequency: 120 Vac (+10/ -15%), 50/60 Hz

(±10%) RM7890A,B,C,D.220-240 Vac (+10/ -15%), 50/60 Hz (±10%)

EC7890A,B.

REQUIRED COMPONENTS:R7847, R7848, R7849, R7861, or R7886A Flame SignalAmplifiers.Q7800 Universal Wiring Subbase.

OPTIONAL COMPONENTS:Communciations (see Communications Section).S7800A Keyboard Display Module.S7810A DATA CONTROLBUS MODULE™.S7820A Remote Reset Module.S7830A First-out Expanded Annunciator Module.

REPLACEMENT PART: 221729 Dust Cover.

SEQUENCE TIMING FOR NORMAL OPERATION:

Pilot F l a m e Model Establishing

Number Initiate Standby Period (PFEP) Run

RM7890A/ 10 sec. aEC7890A

4 or 10 sec.b a

RM7890B/ 10 sec. a 4 or 10 sec. aEC7890B

RM7890C 10 sec. a Not Applic. a

RM7890D 10 sec. a 15/30 sec. a

a STANDBY & RUN can be an infinite time period. b RM7890A1031—30 PFEP

Order Number Description Replaces a

RM7890A1015/ Automation primary relay RA890F,EC7890A1011 module, 50/60 Hz G, H

RM7890A1031/ Automatic primary relay RA890F,module, 30 sec . PFEP G, H

RM7890B1014/ Automatic primary relay RA890F,EC7890B1010 module, shutter drive, 50/60 G, H

Hz

RM7890C1005 Automatic primary relaymodule, 60 Hz, standingpilot

RM7890D1004 Automatic primary relaymodule, 60 Hz for directspark infrared heaterapplication, Flame rods only

aTo replace RA890F, select R7847A Flame Signal Amplifier. To replaceRA890G, select R7849A Flame Signal AMplifier. To replace RA890H,select R7847B Flame Signal Amplifier. Check timings for applicationrequirements.

Page 19: Programador 7800 Series RM Completa

Primary Relay Modules—AutomaticRM7895A, B, C, D, E, F/EC7895A, C Primary Controls

Microprocessor-basedintegrated primary burnercontrol for automatically firedgas, oil, coil, or combinationfuel single burnerapplications.

Functions include automatic burner sequencing, flamesupervision, system status indication, system or self-diagnostics and troubleshooting.Five LEDs provide sequence information.Selectable recycle or lockout on loss of flame or airflow.Access for external electrical voltage checks.Interchangeable plug-in flame amplifiers.Nonvolatile memory retains history files and lockout statusafter loss of power.Delayed main valve on RM7895C, D.Airflow switch check feature on RM7895B, D.Compatible with existing Honeywell flame detectors.

APPROVALS:RM7895—

Underwriters Laboratories Inc. Listed: File No. MP268,Guide No. MCCZ.

Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: JIOW7A4.AF.Industrial Risk Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.Control Safety Devices Acceptable: CSD-1.

EC7895—Factory Mutual Approved.

DIMENSIONS: 5 in. (127 mm) wide, 5 in. (127 mm) high,3-1/32 in. (77 mm) deep.

WEIGHT: 1 lb., 13 oz.OPERATING AMBlENT TEMPERATURE RANGE: –40°F to

+140°F (–40°C to +60°C).

ELECTRICAL RATINGS:Voltage and Frequency: 120 Vac (+10/-15%), 50/60 Hz

(±10%) RM7895A, B, C, D, E, F.220 to 240 Vac (+10/-15%), 50/60 Hz (±10%) EC7895A, C.

REQUIRED COMPONENTS:Q7800 Universal Wiring Subbase.R7847, R7848, R7849, R7861, or R7886 Flame Signal

Amplifiers.ST7800 Plug-in Purge Timers.

OPTIONAL EQUIPMENT:Communications (see Communications Section).S7800 Keyboard Display ModuleS7810 DATA CONTROLBUS MODULE™.S7820 Remote Reset moduleS7830 First-out Expanded Annunciator.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A, B, C Remote Display Mounting

Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221729A Dust Cover.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.

REPLACEMENT PART: 221729 Dust Cover.

Flame Establishing Period Airflow Switch DelayModel Number Initiate Standby P u r g e Pilot Main Check (AFSC) Main Valve

RM7895A/EC7895 10 sec. a b 4 or 10 sec. No No NoA

RM7895BEC7895 10 sec. a b 4 or 10 sec. No Yes NoB

RM7895C 10 sec. a b 4 or 10 sec. 10 sec. No Yes

RM7895D 10 sec. a b 4 or 10 sec. 10 sec. Yes Yes

RM7895E 10 sec. a b 15 or 30 sec. No No No

RM7895F 10 sec. a b 15 or 30 sec. No Yes No

Order Number Description Replaces c

RM7895A1014 Intermittent primary relay module without AFSC, 50/60 Hz R7795A, B

EC7895A1010 Intermittent primary relay module without AFSC, 50/60 Hz

RM7895A1048 Intermittent primary relay module without AFSC, 50/60 Hz R7795A, BTermination of spark upon detection of flame

RM7895B1013 Intermittent primary relay module with AFSC, 50/60 Hz R7795E, F

EC7895C1000 Intermittent primary relay module with AFSC, 50/60 Hz

RM7895C1012 Interrupted primary relay module without AFSC, 50/60 Hz R7795C, D

RM7895C1020 Interrupted primary relay module without AFSC, fixed 10 sec. PFEP, R7795C, Dtermination of spark upon detection of flame, 50/60 Hz

RM7895D1011 Interrupted primary relay module with AFSC, 50/60 Hz R7795G, H

RM7895E1002 Intermittent primary relay module with AFSC, 50/60 Hz for direct sparkinfrared heater, flame rods only

RM7895F1001 Intermittent primary module with AFSC, 50/60 Hz for direct sparkinfrared heater, flame rods only

aSTANDBY and RUN can be an infinite time period. bPURGE will be determined by which ST7800 Purge card is selected.CTo replace R7795A C, E, F, select R7849A FIame Signal Amplifier. To replace R7795B, D, F, H, select R7847A Flame signal Amplifier.

Page 20: Programador 7800 Series RM Completa

Primary Relay Modules—Automatic

RM7824 Primary Controls

24 Vdc microprocessor-basedintegrated burner control forautomatically fired gas, oil, orcombination fuel single burnerapplications. Provides level ofsafety, functional capabilityand features beyond thec a p a c i t y o f conventionalcontrols.

For use with R7824C Amplifier with C7024E, F FlameDetectors and R7848A, B with C7015A Flame Detectors.Functions include automatic burner sequencing, flamesupervision, system status indication, system or self-diagnostics and troubleshooting.Five LEDs provide sequence information.Selectable recycle or lockout on loss of flame airflow.Shutter drive output for use with dynamic self-check Flamedetectors.Access for external electrical voltage checks.Plug-in flame amplifier.Nonvolatile memory retains history files and lockout statusafter loss of power.

APPROVALS:Underwriters Laboratories Inc. Component Recognized:

File No. MP268, Guide No. MCCZ.Canadian Standards Association Certified: LR95329-3.Federal Communications Commission: Part 15, Class B—

Emissions.DIMENSIONS, APPROXIMATE:

5 in. (127 mm) wide, 5 in. (127 mm) high, 5-1/4 in. (133mm) deep with subbase.

WEIGHT: 1 lb., 13 oz. (0.8 kg) with dust cover.TEMPERATURE RATINGS:

Ambient: –40°F to +140°F (–40°C to +60°C).

ELECTRICAL RATINGS:Power Supply: 24 Vdc, +7%, –8%.Load: 500 VA maximum.

TIMING SEQUENCE:

Model Initiate Standby Pilot Flame RunNumber Establishing

Period (PFEP)

RM7824A 10 sec. a 4 or 10 sec. aaSTANDBY and RUN can be an infinite time period.

REQUIRED COMPONENTS:Q7800A, B Universal Wiring Subbase.R7824C1002 Dynamic Self-Check Amplifier 3.0 sec. FFRT

used with C7024E, F.R7848A1008 Infrared or C7015A Infrared Flame Detector

3.0 sec. FFRT used with C7015A.F7848B1006 Dynamic AmpIi-Check® 3.0 sec. FFRT used

with C7015A.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A, B, C Remote Display

Mounting Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.204718A NEMA 4 Weatherproofing Kit for S7800.204718B NEMA 1 Weatherproofing Kit for S7800.221729A Dust Cover.221818A 60-inch Extension Cable Assembly to remote

mount S7800.221818C 120-inch Extension Cable Assembly.

REPLACEMENT PART: 221729 Dust Cover.

SEQUENCE TIMING FOR NORMAL OPERATION OF THE PRIMARY RELAY:Pilot Flame

Device Initiate Standby Establishing Period Run

RM7824A1006 10 sec. * 4 or 10 sec. *

*STANDBY and RUN can be an infinite time period.

AMPLIFIER:Order Number Description

R7824C1002 Amplifier for Primary Relay Module - 24 Vdc Input - used with C7024E, F

R7848A1008 Amplifier for Primary Relay Module - 3.0 FFRT- used with C7015A

R7848B1006 Amplifier for Primary Relay Module - 3.0 FFRT - AmpIi-Check®

Page 21: Programador 7800 Series RM Completa

Primary Relay Modules—Semi-Automatic

RM7823A/EC7823A Primary Flame Switch

Microprocessor-based integrated flame switch for detecting a flame using rectification, ultraviolet (UV) orinfrared (IR) source.

Can be fitted with any 7800 Series Amplifier to providerelay action from two single pole, double throw (spdt)relays when flame is present or not present.RM7823A is a flame detector relay only. Suitable primarycontrol must be used to provide safe-start check, safetylockout, load switching and other functions required inflame safeguard systems.Three LEDs to indicate power, flame and alarm.Access for external electrical voltage checks.Nonvolatile memory.Shutter drive output.Compatible with existing Honeywell flame detectors.

APPROVALS:RM7823A—

Underwriters Laboratories Inc. Listed: File No. MP268,Guide No. MCCZ.

Canadian Standards Association Certified: LR9S329-3.Factory Mutual Approved: JIOX4A5.AF.Industrial Risk Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.EC7823A—

Factory Mutual Approved: Repent No. JI1V94A0.AF.Industrial Risk Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) high, 5 in.(127 mm) wide, 5-1/4 in. (133 mm) deep with Q7800ASubbase, 6-3/32 in. (155 mm) deep wi th Q7800BSubbase.

WEIGHT: 1 lb., 13 oz. (0.8 kg).TEMPERATURE RATINGS:

Ambient: –40°F to +140°F (–40°C to +60°C).ELECTRICAL RATINGS:Power Supply: EC7823—220/240 Vac (+10%/-15%), 50/60

Hz (±10%); RM7823—120 Vac (+10%/-15%), 50/60 Hz(±10%).

REQUIRED COMPONENTS:Q7800A, B Universal Wiring Subbases.R7847, R7848, R7849, R7861, or R7886 Flame Signal

Amplifiers.OPTIONAL COMPONENTS:

Communications (see Communications Section).S7800 Keyboard Display Module.S7810 DATA CONTROLBUS MODULE™.S7820 Remote Reset Module.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A, B, C Remote Display

Mounting Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221729A Dust Cover.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.

REPLACEMENT PART: 221729 Dust Cover.

OrderNumber Voltage Switching Replaces a

RM7823A1016 120 Vac, Two spdt R7023B, C50/60 Hz

EC7823A1004 220-240 Vac, Two spdt —50/60 Hz

aTo replace R7023B, select R7847 Flame Signal Amplifier. Toreplace 7023C, select R7849 Flame Signal Amplifier.

Page 22: Programador 7800 Series RM Completa

Primary Relay Modules—Semi-Automatic

RM7885A/EC7885A Semi-Automatic Primary Control

Microprocessor-based integrated burner control for industrial semi-automatically fired, gas, oil, coal, orcombination fuel single burner applications.

● Functions include flame supervision, system statusindication, system or self-diagnostics and troubleshooting.

● Adaptable to continuous firing, high-low or modulatingfiring rate for semi-automatic burner sequencing.

● Operates with the following:◆ Torch-ignited main burner or torch-ignited pilot using

S445A Start-Stop Station, or conventional knee or footoperated station.

◆ Direct-ignition oil burner or electrically ignited pilot,using S445A Start-Stop Station.

● Five LEDs provide sequence information.● Nonvolatile memory.● Flame signal check during standby.● Shutter drive output.● Compatible with existing Honeywell flame detectors.● Terminal provided for external alarm to sound on flame

failure.

APPROVALS:RM7885A—

Underwriters Laboratories Inc. Listed: File No. MP268,Guide No. MCCZ.

Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: JIOX4A5.AF.Industrial Risk Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.EC7885A—

Factory Mutual Approved only.DIMENSIONS, APPROXIMATE:

5 in. (127 mm) high, 5 in, (127 mm) wide, 3-1/2 in. (77mm) deep.

WEIGHT: 1 lb., 13 oz. (0.8 kg).TEMPERATURE RATINGS:

Ambient: –40°F to +140°F (–40°C to +60°C).ELECTRICAL RATINGS:

Power Supply: EC7885A—220/240 Vac (+10%, –15%),50/60 Hz (±10%); RM7885A—120 Vac (+10%, –15%),50/60 Hz (±10%).

REQUIRED COMPONENTS:Q7800A, B Universal Wiring Subbases.R7847, R7848, R7849, R7861, or R7886 Flame Signal

Amplifiers.OPTIONAL COMPONENTS:

Communications (see Communications Section).S7800 Keyboard Display Module.S7810 DATA CONTROLBUS MODULE™.S7820 Remote Reset Module.S7830 First-out Expanded Annunciator.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A, B, C Remote Display

Mounting Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221729A Dust Cover.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.

TIMING SEQUENCE:

Model Number Initiate Standby Ignition Run

EC7885A; RM7885A 10 sec. a b a

aSTANDBY and RUN can be an infinite time period.blGNITION is the time the Start switch is pushed and is limitedto 15 minutes.

OrderNumber Description Replacesa

EC7885A1011 Semi-automatic primary control. R485

RM7885A1015 Semi-automatic primary control. R485

aTo replace R485, select R7847 Flame Signal Amplifier.

Page 23: Programador 7800 Series RM Completa

Primary Relay Modules—Semi-Automatic

RM7838A Semi-Automatic Industrial Primary Control

Microprocessor-based integratedburner control for industrial semi-automatically fired gas, oil, coal,or combination fuel single burnerapplications. Provides level ofsafety, functional capability andfeatures beyond conventionalcontrols.

Functions include purge, burner pilot startup, flamesupervision, system status indication, system or self-diagnosis and troubleshooting.Delays admission of fuel to combustion chamber until pilotflame has been proven and then monitors the flamethrough the run period while providing system statusindication.Includes Keyboard Display Module.Five LEDs provide sequence information.Intermittent pilot valve.Interchangeable plug-in flame amplifier.Access for external electrical voltage checks.Nonvolatile memory retains history files and lockout statusafter loss of power.Selectable pilot flame establishing period.Provides application flexibility and optional communicationinterface capability.Compatible with existing Honeywell flame detectors.

APPROVALS:Underwriters Laboratories Inc. Listed: File No. MP268,

Guide No. MCCZ.Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: Report No. JI1V9A0.AF.Industrial Risk Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.Control safety Devices Acceptable: CSD-1.

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.(127 mm) high, 5-1/4 in. (133 mm) deep with Q7800ASubbase, 6-3/32 in. (155 mm) deep with Q7800BSubbase,

WEIGHT: 1 lb., 10 oz. (0.7 kg).TEMPERATURE RATINGS:

Ambient: –40°F to +140°F (–40°C to +60°C).ELECTRICAL RATINGS:

Power Supply: 120 Vac (+10%/–15%), 50/60 Hz (±10%).REQUIRED COMPONENTS:

Q7800A, B Universal Wiring Subbases.R7847, R7848, R7849, R7861, or R7886 Flame Signal

Amplifiers.ST7800 Plug-in Purge Timer Card.

OPTIONAL COMPONENTS:Communications (see Communications Section).S7800 Keyboard Display Module.S7810 DATA CONTROLBUS MODULE™.S7820 Remote Reset Module.S7830 First-out Expanded Annunciator.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A, B, C Remote Display

Mounting Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221729A Dust Cover.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.

TIMING SEQUENCE:

Model Initiate Standby Purge Pilot Flame RunNumber Establishing

Period (PFEP)

RM7838A 10 sec. a b 4 or 10 sec. aaSTANDBY and RUN can be an infinite time period.bPURGE will be determined by ST7800A Plug-in Purge TimerCard.

OrderNumber Description Replaces

RM7838A1014 Semi-automatic industrial primaryrelay module with display.

R4138A, C

Page 24: Programador 7800 Series RM Completa

Primary Relay Modules—Semi-Automatic

RM7838B Semi-Automatic Programmer

Microprocessor-based integratedburner control with pilot holdfunct ion for industr ia l semi-automatically fired gas, oil, coal,or combination fuel single burnerapplications. Provides level ofsafety, functional capability andfeatures beyond conventionalcontrols.

Functions include automatic modulated high fire and lowfire proven purge, burner pilot start up with pilot valve hold,special pilot valve hold from the Run condition, flamesupervision, system status indication, system or self-diagnostics and troubleshooting.Access for external electrical voltage checks.Application flexibil i ty and communication interfacecapability.Five LEDs provide sequence information.Five function Run/Test Switch.Interchangeable plug-in flame amplifiers.Local or remote annunciation of operation and faultinformation.Nonvolatile memory retains history files and lockout statusafter loss of power.Compatible with existing Honeywell flame detectors.Includes Keyboard Display Module.Use with R7847C or R7886A Plug-in Flame SignalAmplifiers.

APPROVALS:Underwriters Laboratories Inc. Listed: File No. MP268,

Guide No. MCCZ.Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: Report No. Jl1V9AO.AF.Industrial Risks Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.Control Safety Devices Acceptable: CSD-1.

SEQUENCE TIMING FOR NORMAL OPERATION:

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.(127 mm) high, 5-1/4 in. (133 mm) deep with Q7800ASubbase; 6-3/32 in. (155 mm) deep with Q7800BSubbase.

WEIGHT: 1 lb., 10 oz. (0.7 kg).

TEMPERATURE RATINGS:Ambient: –40°F to +140°F (–40°C to +60°C).

ELECTRICAL RATINGS:Power Supply: 120 Vac (+10%, –15%), 50/60 Hz (±10%).

REQUIRED COMPONENTS:Q7800A, B Universal Wiring Subbases.R7847C, R7861, or R7886 Flame Amplifiers.ST7800 Plug-in Purge Timer Card.

OPTIONAL COMPONENTS:Communications (see Communications Section).S7810 DATA CONTROLBUS MODULE™.S7820 Remote Reset Module.S7830 First-out Expanded Annunciator.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321 B, 204718A, B, C Remote Display

Mounting Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221729A Dust Cover.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.

Device Initiate Standby Purge Pilot Flame Establishing Main Flame Establishing RunPeriod (PFEP) Period (MFEP)

RM7838B 10 sec. a b 4 sec. or 10 sec. 10 sec.c a

aSTANDBY and RUN can be an infinite time period.bPURGE will be determined by which ST7800A Plug-in Purge Timer Card is selected.blmmediate or deferred main flame.

Order Number Description

RM7838B1013 Enhanced semi-automatic industrial primary relay module with display; 50/60 Hz.

Page 25: Programador 7800 Series RM Completa

Programmers

RM7840 Programmer

Microprocessor-based integratedburner control for automaticallyfired gas, oil, coal, or combinationfuel single burner applications.Provides safety, functionalcapability and features beyondconventional controls.

Functions include automatic burner sequencing, flamesupervision, system status indication, system or self-diagnostics and troubleshooting.Access for external electrical voltage checks.Application flexibil i ty and communication interfacecapability.Five LEDs provide sequence information.Five function Run/Test Switch.Interchangeable plug-in flame amplifiers.Local or remote annunciation of RM7840 operation andfault information.Nonvolatile memory retains history files and lockout statusafter loss of power.Compatible with existing Honeywell flame detectors.

APPROVALS:Underwriters Laboratories Inc. Listed: File No. MP268,

Guide No. MCCZ.Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: Report No. JI1V9AO.AF.Industrial Risks Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.Control Safety Devices Acceptable: CSD-1.

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.(127 mm) high, 5-1/4 in. (133 mm) deep with Q7800ASubbase; 6-3/32 in. (155 mm) deep with Q7800BSubbase.

WEIGHT: 1 lb., 13 oz. (0.8 kg).

TEMPERATURE RATINGS:Ambient: –40°F to +140°F (–40°C to +60°C).

ELECTRICAL RATINGS:Power Supply: 120 Vac (+10%/–15%), 50/60 Hz (±10%).

REQUIRED COMPONENTS:Q7800A, B Universal Wiring Subbases.R7847, R7848, R7849, R7861, or R7886 Flame Signal

Amplifiers.ST7800 Plug-in Purge Timer Cards.

OPTIONAL COMPONENTS:Communications (see Communications Section).S7800 Keyboard Display Module.S7810 DATA CONTROLBUS MODULE™.S7820 Remote Reset Module.S7830 First-out Expanded Annunciator.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A, B, C Remote Display

Mounting Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221729A Dust Cover.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.

TIMING SEQUENCE:

Model Initiate Standby Purge Pilot Flame Establishing Main Flame Establishing Run PostpurgeNumber Period (PFEP) Period (MFEP)d

RM7840E a 10 sec. b c 4 or 10 sec. 10 or 15 sec. b 15 sec.

RM7840G 10 sec. b c 4 or 10 sec. 10, 15, or Intermittent b 15 sec.

RM7840L 10 sec. b c 4 or 10 sec. 10, 15, or Intermittent b 15 sec.

RM7840M 10 sec. b c 4 or 10 sec. 10 sec. or Intermittent b 15 sec.

aEnergy Saving Prepurge.bSTANDBY and RUN can be an infinite time period.cPURGE is determined by ST7800 Plug-in Purge Timer Card selected.dThe MFEP will be determined by terminal used, configuration jumper, or jumper wire addition. See instruction sheet.

Order Number Description Replaces

RM7840E1016 Relay module with ESPa; without display; 50/60 Hz

RM7840G1006 Relay module without display; 50 Hz R4140G

RM7840G1014 Relay module without display; 60 Hz R4140G

RM7840L1018 Relay module without display; 50/60 Hz R4140L

RM7840L1026 Relay module without display; Intermittent pilot; 50/60 Hz R4140L

RM7840M1009 Relay module without display; 50 Hz R4140M

RM7840M1017 Relay module without display; 60 Hz R4140M

aESP—Energy Saving Prepurge.

Page 26: Programador 7800 Series RM Completa

Programmers

RM7800E, G, L, M Programmers

Microprocessor-based inte-grated burner control for auto-matically fired gas, oil, coal, orcombination fuel single burnerapplications. Provides safety,functional capability andfeatures beyond conventionalcontrols.

Functions include automatic burner sequencing, flamesupervision, system status indication, system or self-diagnostics and troubleshooting.Access for external electrical voltage checks.Application flexibil i ty and communication interfacecapability.Five LEDs provide sequence information.Five function Run/Test Switch.Interchangeable plug-in flame amplifiers.Local or remote annunciation of operation and fault infor-mation (optional).Nonvolatile memory retains history files and lockout statusafter loss of power.Compatible with existing Honeywell flame detectors.Includes Keyboard Display Module.

APPROVALS:Underwriters Laboratories Inc. Listed: File No. MP268,

Guide No. MCCZ.Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: Report No. JI1V9AO.AF.Industrial Risks Insurers Acceptable.Federal Communications Commission: Part 15, Class B—

Emissions.

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.(127 mm) high, 5-1/4 in. (133 mm) deep with Q7800ASubbase; 6-3/32 in. (155 mm) deep wi th Q7800BSubbase.

WEIGHT: 1 lb., 10 oz. (0.7 kg).

TEMPERATURE RATINGS:Ambient: –40°F to +140°F (–40°C to +60°C).

ELECTRICAL RATINGS:Power Supply: 120 Vac (+10%/–15%), 50/60 Hz (±10%).

REQUIRED COMPONENTS:Q7800A, B Universal Wiring Subbases.R7847, R7848, R7849, R7861, or R7886 Flame Signal

Amplifiers.ST7800 Plug-in Purge Timer Card.

OPTIONAL COMPONENTS:Communications (see Communications Section).S7810 DATA CONTROLBUS MODULE™.S7820 Remote Reset Module.S7830 First-out Expanded Annunciator.

ACCESSORIES:123514A Rectifying Flame Simulator.203541 ControlBus 5-Wire Electrical Connector.203659 Ultraviolet Flame Simulator.203765, 205321B, 204718A, B, C Remote Display

Mounting Brackets.203968A Remote Display Power Supply (13 Vdc) Plug-in.221729A Dust Cover.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.

TIMING SEQUENCE:

Model initiate Standby Purge Pilot Flame Establishing Main Flame Establishing Run PostpurgeNumber Period (PFEP) Period (MFEP)d

RM7800E a

R M 7 8 0 0 G

R M 7 8 0 0 L

R M 7 8 0 0 M

10 sec.

10 sec.

10 sec.

10 sec.

b

b

b

b

c

c

c

c

4 or 10 sec.

4 or 10 sec.

4 or 10 sec.

4 or 10 sec.

10 or 15 sec.

10, 15, or Intermittent

10, 15, or Intermittent

10 sec. or Intermittent

b

b

b

b

15 sec.

15.sec.

15.sec.

15 sec.

aEnergy Saving Prepurge.bSTANDBY and RUN can be an infinite time period.cPURGE will be determined by which ST7800A Plug-in Purge Timer Card is selected.dThe MFEP will be determined by terminal used, cinfiguration jumper, or wire addition. See instruction sheet.

Order Number Description Replaces

RM7800E1010 Automatic programming control with ESPa and display; 50/60 Hz BC7000L; PM720L

RM7800G1000 Automatic programming control with display; 50 Hz BC7000L; PM720G

RM7800G1018 Automatic programming control with display; 60 Hz BC7000L; PM720G

RM7800L1012 Automatic programming control with display; 50/60 Hz BC7000L; PM720L

RM7800L1053 Automatic programming control with display, intermittent pilot; 50/60 Hz BC7000L; PM720L

RM7800M1003 Automatic programming control with display; 50 Hz BC7000L; PM720M

RM7800M1011 Automatic programming control with display; 60 Hz BC7000L; PM720M

aESP—Energy Saving Prepurge.

Page 27: Programador 7800 Series RM Completa

Integrated Burner Control

NEW!EC7810, EC7820 Integrated Burner Control

Microprocessor-based integratedburner control for automaticallyfired gas, oil, coal, or combinationfuel single burner atmospheric(EC7810A) or atmospheric withfan (EC7820A) applications. Pro-vides automatic burner sequenc-ing, flame supervision, systemstatus indication, system or self-diagnostics, and troubleshooting.

Access for external electrical voltage checks.Application flexibil i ty and communication interfacecapability.Four LEDs provide sequence information.Five function Run/Test Switch.Interchangeable plug-in amplifiers.Local or remote annunciation of operation and fault infor-mation (optional).Nonvolatile memory retains history files and lockout statusafter loss of power.Compatible with existing Honeywell flame detectors.

APPROVALS:Underwriters Laboratories Inc. Listed: File No. MP268,

Guide No. MCCZ.Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: Report No. JI1V9A0.AF.IRI: Acceptable.FCC: Federal Communications Commission: Part 15,

Class B—Emissions.

ELECTRICAL RATINGS:Power Supply: 220-240 Vac (+10%/–15%), 50/60 Hz

(±10%).Power Dissipation: 10W maximum.Connected Load: 2000 VA maximum total.Fusing: 20A maximum type FRN or equivalent.

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.(127 mm) high, 5-1/4 in. (133 mm) deep with Q7800ASubbase; 6-3/32 in. (155 mm) deep with Q7800BSubbase.

WEIGHT: 1 lb., 10 oz. (0.7 kg).

TEMPERATURE RATINGS:Operating: –40°F to +140°F (–40°C to +60°C).Shipping: –40°F to +150°F (–40°C to +66°C).

HUMIDITY RATINGS: 85% RH continuous, noncondensing.

VIBRATION: 0.5G environment

REQUIRED COMPONENTS:Q7800A, B 22-Terminal Wiring Subbase.R7824, R7847, R7848, R7849, R7861, or R7886 Flame

Amplifier.ST7800A Plug-in Purge Timer.

OPTIONAL COMPONENTS:Personal Computer Interface.S7800A Keyboard Display Module (KDM).S7810A Data ControlBus Module™.S7820 Remote Reset Module.ZM7850A Combustion System Manager™.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.221729C Dust Cover.204718C NEMA 4 Cover Assembly with Reset for S7800A.

SEQUENCE TIMING FOR NORMAL OPERATION:

Model Initiate Standby Purge Pilot Flame Main Flame Run PostpurgeNumber Establishing Period Establishing Period

(PFEP) (MFEP) a

EC7810A1022 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.

EC7810A1035 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.

EC7820A1026 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.

EC7820A1034 2 sec. b c 5 or 10 sec. 6 or 10 sec. b 5 sec.

aThe MFEP will be determined by terminals used, configuration jumper, or jumper wire addition. See instruction sheet.bSTANDBY and RUN can be an infinite time period.cPURGE will be determined by which ST7800A Purge Timer Card is selected.

Order Number Description Comments

EC7810A1022 Automatic Primary Relay Module for single atmospheric burner, 220-240, 50/60 Hz 1 ignition attempt

EC7810A1035 Automatic Primary Relay Module for single atmospheric burner, 220-240, 50/60 Hz 5 ignition attempts

EC7820A1026 Automatic Primary Relay Module for single atmospheric burner with fan, 220-240, 50/60 Hz 1 ignition attempt

EC7820A1034 Automatic Primary Relay Module for single atmospheric burner with fan, 220-240, 50/60 Hz 5 ignition attempts

Page 28: Programador 7800 Series RM Completa

Integrated Burner Control

NEW!EC7830, RM7830, EC7850, RM7850 Integrated Burner Control

Microprocessor-based integratedburner control for automaticallyfired gas, oil, coal, or combinationfuel single burner full modulation(EC/RM7830A) or on/of f (EC/RM7850A) applications. Providesautomatic burner sequencing,flame supervision, system statusindication, s y s t e m o r self-diagnostics, and troubleshooting.

Access for external electrical voltage checks.Application flexibil i ty and communication interfacecapability.Five LEDs provide sequence information.Five function Run/Test Switch.interchangeable plug-in amplifiers.Local or remote annunciation of operation and fault infor-mation (optional).Nonvolatile memory retains history files and lockout statusafter loss of power.Compatible with existing Honeywell flame detectors.

APPROVALS:RM7830A and RM7850A—

Underwriters Laboratories Inc. Listed: File No. MP268,Guide No. MCCZ.

Canadian Standards Association Certified: LR95329-3.Factory Mutual Approved: Report No. JI1V9A0.AF.Industrial Risk Insurers Acceptable.FCC: Federal Communications Commission: Part 15,

Class B—Emissions.EC7830A and EC7850A—

Factory Mutual Approved.

ELECTRICAL RATINGS:Power Supply: RM7830A and RM7850A—120 Vac

(+10/–15%), 50/60 Hz (±10%); EC7830A andEC7850A—220-240 Vac (+10/–15%), 50/60 Hz (±10%).

Power Dissipation: 10W maximum.Connected Load: 2000 VA maximum total.Fusing: 20A maximum type FRN or equivalent.

DIMENSIONS, APPROXIMATE: 5 in. (127 mm) wide, 5 in.(127 mm) high, 5-1/4 in. (133 mm) deep with Q7800ASubbase; 6-3/32 in. (155 mm) deep with Q7800BSubbase.

WEIGHT: 1 lb., 10 oz. (0.7 kg).

TEMPERATURE RATINGS:Operating: –40°F to +140°F (–40°C to +60°C).Shipping: –40°F to +150°F (–40°C to +66°C).

HUMIDITY RATINGS: 85% RH continuous, noncondensing.

VIBRATION: 0.5G environment

REQUIRED COMPONENTS:Q7800A, B 22-Terminal Wiring Subbase.R7824, R7847, R7848, R7849, R7861, or R7886 Flame

Amplifier.ST7800A Plug-in Purge Timer.

OPTIONAL COMPONENTS:Q7700 Network Interface Unit.S7800A Keyboard Display Module (KDM).S7810A Data ControlBus Module™.S7820 Remote Reset Module.ZM7850A Combustion System Manager™.221818A 60-inch Extension Cable Assembly.221818C 120-inch Extension Cable Assembly.221729C Dust Cover.204718A NEMA 4 Cover Assembly for S7800A.204718C NEMA 4 Cover Assembly with Reset for S7800A.

SEQUENCE TIMING FOR NORMAL OPERATION:

Model Initiate Standby Purge Pilot Flame Main Flame Run PostpurgeNumber Establishing Period Establishing Period

(PFEP) (MFEP) a

EC7830A1033 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 2 sec.

EC7830A1041 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 30 sec.

EC7830A1066 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 15 sec.

RM7830A1003 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 2 sec.

RM7830A1011 3 or 5 sec. b c 3 sec. 4 or7 sec. b 30 sec.

RM7830A1029 3 or 5 sec. b c 3 sec. 4 or 7 sec. b 15 sec.

EC7850A1064 2 sec. b c 3 sec. 6 or 7 sec. b d

EC7850A1072 2 sec. b c 3 sec. 6 or 7 sec. b 2 sec.

EC7850A1080 2 sec. b c 3 sec. 6 or 7 sec. b 30 sec.

EC7850A1122 2 sec. b c 3 sec. 6 or 7 sec. b 15 sec.

RM7850A1001 2 sec. b c 3 sec. 6 or 7 sec. b 2 sec.

RM7850A1019 2 sec. b c 3 sec. 6 or 7 sec. b 15 sec.

RM7850A1027 2 sec. b c 3 sec. 6 or 7 sec. b 30 sec.

aThe MFEP will be determined by terminals used, configuration jumper, or jumper wire addition. See instruction sheet.bSTANDBY and RUN can be an infinite time period.CPURGE will be determined by which ST7800A Purge Timer Card is selected.dDynamic damper check.

Page 29: Programador 7800 Series RM Completa

7800 SERIES Required Components

Q7800A,B 22-Terminal Universal Wiring SubbasesUniversal burner, panel or wall mount subbases for RM78xx and EC78xx SERIES relay modules andS7830A Expanded- Annunciator.

APPROVAL BODIES:Underwriters Laboratories Inc. component recognized

(Q7800A).Underwriters Laboratories Inc. listed (Q7800B).Canadian Standards Association certified.

DIMENSIONS:Q7800A: 4-31/32 in. [126 mm] wide, 4-31/32 in. [126 mm] high,

1-13/32 in. [36 mm] deep.

Makes electrical connections for 7800 SERIES relay mod-ules or S7830A Expanded Annunciator through bifurcatedcontacts.

Provides terminals for field wiring.

Q7800B has knockouts provided in back, top and bottom forconduit connections.

Twenty-two terminals.

Q7800B: 4-31/32 in. [126 mm] wide, 4-31/32 in. [126 mm] high,2-7/32 in. [56 mm] deep.

REPLACEMENT PART: 221779 Electrical Access Slot Covers.

OrderNumber Description

Q7800A1005 Universal wiring subbase, panel mounting.

Q7800B1003 Universal wiring subbase, burner/wall mounting.

Q7800B1011 Universal wiring subbase, burner/wall mounting.

R7847, R7848, R7849, R7861, R7886 Flame Signal AmplifiersSolid state plug-in amplifiers that respond to flame detector inputs to indicate the presence of flamewhen used with RM78xx and EC78XX SERIES relay modules.

Flame failure response time of 0.8 or 3 seconds.

Flame signal strength ranges from 0.0 to 5.0 Vdc.

Plug-in to 7800 relay module through printed circuit boardedge card connector keyed for proper orientation.

Flame signal test jacks to measure amplifier flame signalvoltage.

R7847B, R7848B, R7849B Dynamic AMPLI-CHECK™ cir-cuitry tests flame amplifier during burner operation; 7800SERIES relay module locks out on safety shutdown withamplifier failure.

R7847C Dynamic Self-Check Rectification Amplifier,R7861A Dynamic Self-Check Ultraviolet Amplifier, andR7886A Dynamic Self-Check Ultraviolet Amplifier testelectronic components in the flame detection system10 to 12 times per minute; 7800 SERIES relay modulelocks out on safety shutdown with flame detectionsystem failure.

APPROVAL BODIES:Underwriters Laboratories Inc. listed.Canadian Standards Association certified.Factory Mutual approved.Industrial Risks Insurers acceptable.

DIMENSIONS: 3-9/16 in. [91 mm] wide, 3-3/8 in. [85 mm] high,7/8 in. [23 mm] deep.

WEIGHT: 2.5 oz.OPERATING AMBlENT TEMPERATURE RANGE: – 40 F to

+140 F [–40 C to + 60 C].OPTIONAL COMPONENTS:123514A Rectification Flame Simulator.203659 Ultraviolet Flame Simulator.

Page 30: Programador 7800 Series RM Completa

7800 SERIES Required Components

R7847, R7846, R7649, R7886 continued

FLAME DETECTION SYSTEMS

Plug-in Flame Signal Amplifiers Applicable Flame Detectors

OrderNumber Type Color

Self-Checking

Flame FailureResponse Time Fuel Type Models

R7824C1002 DynamicSELF CHECK

3.0 sec. Gas, oil,coal

Ultraviolet (PurplePeeper)

C7024E, F.

R7847A1025

R7847A1074f1.0 sec. or0.8 sec.g

Gas Rectifying Flame RodHolder

C7004, C7007, C7011d,Complete assemblies:C7008, C7009, Q179.

R7847A1033R7847A1082f

No

2.0 sec. or3.0 sec.g

Gas, oil,coal

Ultraviolet (PurplePeeper)

C7012A, C.

R7847B1023c

R7847B1064f1.0 sec. or0.8 sec.g

Gas Rectifying Flame RodHolder

C7004, C7007, C7011d,Complete assemblies:C7008, C7009, Q179.

R7847B1031c

R7847B1072f

DynamicAMPLI-

CHECK™

Oil Rectifying Flame RodHolder, Photocelle,or Ultraviolet (PurplePeeper)

C7004, C7007, C7011d,Complete assemblies:C7008, C7009, Q179,C7003, C7010, C7013,C7014, C7012A, C.

R7847C1005b

Rectifi-cation

Green

DynamicSELF CHECK

Ultraviolet (PurplePeeper)

C7012E, F.

R7848A1008 No C7015.

R7848B1006

Infrared Red

DynamicAMPLI-

CHECK™

2.0 sec. or3.0 sec.g

Gas, oil,coal

Infrared (LeadSulfide) C7015.

R7849A1015 1.0 sec. or0.8 sec.g

R7849A1023

No

2.0 sec. or3.0 sec.g

R7849B1013 1.0 sec. or0.8 sec.g

R7849B1021

DynamicAMPLI-

CHECK™

C7027, C7035, C7044a

R7861A1026

2.0 sec. or3.0 sec.g

R7861A1034

Purple

0.8 sec. or1.0 sec.g

Gas, oil Ultraviolet(Minipeeper)

C7061.

R7886A1001

Ultra--violet

Blue

DynamicSELF CHECK

2.0 sec. or3.0 sec.g

Gas, oil,coal

Ultraviolet (AdjustableSensitivity)

C7076A, D.

aR7849A and C7027, C7035 and C7044 Flame Detectors should be used only on burners that cycle on-off at least once everytwenty-four hours. Appliances with burners that remain on for twenty-four hours continuously or longer should use C7061A FlameDetector with R7861A Amplifier.

bCircuitry tests all electronic components in flame detection system (amplifier and detector) 12 times a minute during burneroperation and shuts down burner if detection system fails.

cCircuitry tests flame signal amplifier at least 12 times a minute during burner operation and shuts down burner if amplifier fails.dSee instructions for holder.eUse only Honeywell Photocell, part number 38316.fFor use with C7012A, C parallel detectors, or flame rod applications with leadwire lengths greater than 50 feet.gThe 7800 Series amplifiers have been modified as of 1/15/98 to provide 0.8 sec/1.0 sec, or 2.0 sec/3.0 sec.

FLAME FAILURE RESPONSE TIME ON RM or EC78XX DEVICESFlame Failure Response Time (FFRT)Relay Module

0.8 or 1.0 sec 2.0 or 3.0 sec

EC/RM7810, 7820, 7830, 7850 1.0 2.0

EC/RM7823, 7885, 7890, 7895, 7896,7888, 7838, 7800, 7840

0.8 3.0

RM7824 NA 3.0

Page 31: Programador 7800 Series RM Completa

7800 SERIES Required Components

ST7800A Plug-In Purge Timer CardProvides prepurge timing for select RM78xx and EC78xx SERIES relay modules.

Prepurge TimingOrder Number Used With

ST7800A1005 2 seconds RM7800, RM7838, RM7840, RM7888, RM7895,

ST7800A1013 7 seconds EC7800, EC7810, EC7820, EC7830, EC7840, EC7850, EC7888,

ST7800A1021 10 seconds EC7895 Relay Modules.

ST7800A1039 30 seconds

ST7800A1047 40 seconds

ST7800A1054 60 seconds

ST7800A1062 90 seconds

ST7800A1070 2.5 minutes

ST7800A1088 4.0 minutes

ST7800A1096 6.0 minutes

ST7800A1104 9.0 minutes

ST7800A1112 12.0 minutes

ST7800A1120 15.0 minutes

ST7800A1138 22.0 minutes

ST7800A1146 30.0 minutes

S7810A DATA CONTROLBUS MODULE™Supports remote mounting of S7800 Keyboard Display Module, personal computer communicationsinterface and remote reset.

● Use with remotely mounted S7800 Keyboard Display

OPERATING AMBIENTTEMPERATURE RANGE: –40 F to+140 F [–40 C to +60 C].

ELECTRICAL RATINGS: 13 Vdc peak full-wave rectified(+20/–15%).

OPTIONAL COMPONENTS: 203968A Remote Display PowerSupply, plug-in.

REPLACEMENT PART:203541 ControlBus 5-Wire Electrical Connector.

Module.

● Installs directly on the front of 7800 SERIES relay modules.

● Provides communications bus interface and remote reset.

DIMENSIONS: 4-27/32 in. [123 mm] wide, 2-29/32 in.[73 mm] high, 29/32 in. [23 mm] deep.

WEIGHT: 4 oz.

OrderNumber Description Used With

S7810A1009 Remote mounting of 7800 SERIES Relaykeyboard display mod- Modules.ule, personal computercommunications inter-face and remote reset.

Page 32: Programador 7800 Series RM Completa

7800 SERIES Optional ComponentsS7800A Keyboard Display ModuleProvides current status of burner sequence, timing information, hold information and lockout in-formation, as well as selectable or preemptive messages.

Application flexibility.

Communication interface capability.

Dependable long-term operations provided by microcompu-ter technology.

First out annunciation and system diagnostics provided by 2row by 20 column Vacuum Fluorescent Display (VFD).

Local or remote annunciation of operation and faultinformation.

Optional first out expanded annunciation with 24 limit andinterlock LEDs enhances keyboard display module infor-mation.

Provides burner controller data.

Remote reset.

Report generation. Order Number Description Used With

APPROVAL BODIES:Underwriters Laboratories Inc. listed.

Canadian Standards Association certified.Factory Mutual approved.Industrial Risks Insurers acceptable.Federal Communications Commission, Part 15, Class B.

DIMENSIONS: 4-27/32 in. [123 mm] wide, 2-29/32 in.[73 mm] high, 29/32 [23 mm] deep.

WEIGHT: 4 OZ.

OPERATING AMBlENT TEMPERATURE RANGE: –40 F to+140 F [–40 C to +60 C].

ELECTRICAL RATINGS:Voltage and Frequency 13 Vdc peak fullwave rectified

(+20/–15%)

OPTIONAL COMPONENTS:S7810A1009 DATA CONTROLBUS MODULE.203541 ControlBus 5-Wire Electrical Connector.203765 Remote Display Mounting Bracket.203968A Remote Display Power Supply (plug-in).203969A Remote Display Power Supply (screw terminal).221818A Extension Cable Assembly to remote mount

keyboard display module. 60 inch cable.221818C Extension Cable Assembly.

120 inch cable.

S7800A1001

S7800A1035

English LanguageKeyboardDisplayModule

French LanguageKeyboardDisplayModule

S7800A1043 German LanguageKeyboardDisplayModule

S7800A1050 Italian LanguageKeyboardDisplayModule

S7800A1068 Spanish Language

DisplayModule

S7800A1118 Katakana(Japanese)

KeyboardDisplayModule

S7800A1126

S7800B1009

Portuguese

KeyboardDisplayModule

Chinese LanguageKeyboardDisplayModule - RemotelyMounted

RM7800, RM7823, RM7824,RM7838, RM7840, RM7885,RM7888, RM7890, RM7895Relay ModulesEC7810, EC7820, EC7823,EC7830, EC7850

Keyboard

Language

Language

Page 33: Programador 7800 Series RM Completa

7800 SERIES Optional Components

S7820A Remote Reset ModuleServes as link between remote reset pushbutton and relay module. Allows RM78xx and EC78xxSERIES relay modules to be reset from a remote location.

Allows resetting of 7800 SERIES relay module by a remotereset pushbutton up to 1000 feet away.

Installs directly on the front of 7800 SERIES relay module.

DIMENSIONS: 4-27/32 in. [123 mm] wide, 2-29/32 in.[73 mm] high, 29/32 in. [23 mm] deep.

WEIGHT 3 oz.OPERATING AMBlENT TEMPERATURE RANGE: –40 F to

+140 F [–40 C to +60 C].REPLACEMENT PART: 203541 ControlBus 5-Wire Electrical

Connector.

O r d e rNumber Description Used With

S7820A1007 Remote reset module 7800 SERIES relay modulesto reset 7800 SERIESrelay module.

S7830A First-Out Expanded AnnunciatorMicroprocessor-based expanded annunciator to support the RM78xx and EC78XX SERIES relaymodules for first-out annunciation, sequencing, system or self-diagnostics and troubleshooting.

● On/Off status of limits and interlocks.

● RS485 connection to 7800 SERIES relay module.

● Used with Q7800A,B subbases; 7800 SERIES relaymodules.

APPROVAL BODIES:Underwriters Laboratories Inc. listed.Canadian Standards Association certified.

Twenty-six Light Emitting Diodes (LEDs).

Twenty-two LEDs to annunciate Limits and Interlocks.Order Electrical

Number Dimensions Weight InputFour LEDs to annunciate Power, Current Status, First-out S7830A1005 5 in. [127 mm] wide, 1 lb., 13 oz. 120 Vac,Status and System Lockout. 5 in. [127 mm] high, [829 g]. 50/60 Hz

Enhances S7800A Keyboard Display Module sequence3-1/32 in. [77 mm]deep.

hold and lockout messages.

Page 34: Programador 7800 Series RM Completa

Q7700A, B Network Interface Unit

Q7700B

APPLICATIONThe Q7700A,B Network Interface Unit provides local andremote monitoring and diagnostics of the BCS 7700, 7800SERIES, Armstrong TrapScanTM, Pulsafeeder PULSAtrolTM

and QM40XX Data Acquisition devices with an lBM®

FEATURES●

Connect up to six BCS 7700 controls, ArmstrongTrapScan TM systems, Pulsafeeder PULSAtrolTM

systems. up to 900 QM40XX Data Acquisition Modules,and up to 222 multi-dropped 7800 SERIES devices orcombinations of the systems.

Local and remote annunciation of BCS 7700,7800SERIES safety shutdowns and Armstrong TrapScanTM,Pulsafeeder PULSAtrolTM and QM40XX DataAcquisition Alarms.

Autodial-out on BCS 7700,7800 SERIES, ArmstrongTrapScan lM, Pulsafeeder PULSAtrolTM, and QM40XXData Acquisition Alarms for up to three telephonenumbers.

Personal computer user-friendly, menu driven,Microsoft® Windows™ software-based user interface.

On-line data logging.

Modular construction.

Access controlled with password protection.

Light Emitting Diode (LED) status interface.

19,200 selectable baud personal computer/printerinteface.

19,200 selectable baud modem interface. Interfaceswith Hayes-compatible modems.

Fault-dating and time -stamping internal softwareclock.

Dial-out override for maintenance-induced alarms.

Dedicated RS-232 external modem port.

Universal power supply (Q7700B only).

SYSNet TM compatible.

equivalent personal computer. The Q7700 also provides localand remote configuration and control of BCS 7700,Pulsafeeder PULSAtrol™, or QM40XX Data Acquisitiondevices.

Page 35: Programador 7800 Series RM Completa

APPROVAL BODIES:Underwriters Laboratories Inc. component recognized.Canadian Standards Association certified.Factory Mutual approved.Industrial Risk Insurers acceptable.Federal Communications Commission: Part 15, Class A -

Emissions.Canadian Department of Communications certified.

OPERATING AMBlENT TEMPERATURE RANGE: 32 F to130 F [0 C to 54 C].

HUMIDITY: 85% relative humidity continuous, noncondensing.

COMPONENTS:221237 Cover Assembly, Baser Unit.221240 Cover Assembly, Electrical Enclosure.202433 Slot Inserts, ControlBus Slots.200603 ControlBus Module 3-Wire Electrical Connector.203541 ControlBus Module 5-Wire Electrical Connector.QS7700A Communications Interface ControlBus Module

(BCS7700).QS7800A Communications Interface ControlBus Module

(7800 SERIES).

QS7850A General Purpose Interface ControlBus Module.

ACCESSORIES:QM4520A: RS-232C to RS-485 Converter.QS7800B: ControlBus™ Module for multi-drop 7800

Series.QS7800C: ControlBus™ Module for QM40XX Data

Acquisition modules.QS7800D: ControlBus™ Module for Armstrong Trap

Scan™.QS7800E: ControlBus™ Module for Pulsafeeder

PULSAtrol™.ZM7850A: Combustion System Manager® Software for

personal computer.ZM7850B: SYSNet™ Operator Interface Software for

personal computer.200603: ControlBus™ Module Electrical Connector.202433: Slot Inserts, ControlBusTM Slots.221237/1698: Cover Assembly, Base Unit.221240/1698: Cover Assembly, Electrical Enclosure.

Null Modem Adaptor (obtain locally).209164: Power Supply, panel mounting, 85 to 132 Vac

or 170 to 264 Vac input voltage, switchable; 1.4Amaximum input current; 24 Vdc (±10%) outputvoltage; 3A maximum output current.

209162 Power Supply, DIN-Rail mounting, 110 Vacinput voltage; 225mA input current; 24 Vdc (±1%)output voltage; 1A output current.

209163 Power Supply, DIN-Rail mounting, 220 Vacinput voltage; 225mA input current; 24 Vdc (±1%)output voltage; 1A output current.

208670; IEC 120V power cord for universal powersupply (obtain other plug configuration locally).

208289: Universal Power Supply, 100 to 250 Vac,50/60 Hz.

Order Electrical Electrical Signal Direct TerminalNumber Dimensions Weight Ratings Connectors Characteristics Hookup

Q7700A1014 9 in. [229 mm] wide, 4 Ibs., Voltage and Frequency: RS232C Port 25 Selectable baud RS232C Connection,8 in. [203 mm] high, 10 oz. 120 Vac (+10/-15%),60 “D” pin connector; rate up to 19,200 PINS. 1 Ground:4-7/8 in. [123 mm] Hz (±10%) ControlBus Local Protective.deep. Communication: RS485 communications. 2 Transmit Data (TD).

Remote 3 Receive Data (RD).

Q77C0B1004 5 lbs., 100-250 Vac, 50/60 Hz communications 7 Ground: Signal.13 oz. Power Supply (part requires an external

number 208289 included) modem.

Page 36: Programador 7800 Series RM Completa

SPECIFICATIONSModels:Q7700A,B Network Interface Unit:

Q7700A1014 Network Interface Unit, 120 Vac only.Q7700B1004 Network Interface Unit with Universal 100 to

250 Vac power supply.

NOTE: 208670 Power Cord provided with 208289 Universal100 to 250 Vac Power Supply is equipped with astandard U.S. 120 Vac plug. Adapter plugs for otherpower systems, if needed, can be obtained locally.

Electrical Ratings:Voltage and Frequency:

Q7700A: 120 Vac (+10%/-15%), 50/60 Hz.Q7700B: 100 to 250 Vac, 50/60 Hz.

Universal Power Supply (Q7700B only):Rated Voltage: 100 to 250 Vac, 50/60 Hz.Rated Input: 0.7A to 0.3A.Secondary Voltages: +5V, +12V, -12V.Secondary Current: 4.0A, 1.0A, 0.6A maximum.

Electrical Connectors:RS-232C port, 25 D pin connector for local

communications.RS-232 port, 9 D pin connector for remote

communications.

Environmental Ratings:Ambient Temperature:

Operating: 32°F to 130°F (0°C to 54°C).Storage: -30°F to +150°F (-34°C to 66°C).

Humidity:Operating, 85 percent relative humidity, continuous,noncondensing.

Vibration:Continuous 0.5G.

Enclosure:NEMA 1.

Fig. 1. Network Interface unit dimensions in in. (mm).

Weight:Q7700A: 4 lb, 5 oz unpacked, without ControlBusTM

Modules.Q7700B: 5 lb. 13 oz unpacked, including power supply

and cord, without ControlBusTM Modules.

Approvals:Underwriters Laboratories Inc: File No. MP268, Guide No.

MCCZ2.Canadian Standards Association: LR95329.Factory Mutual: J.1. 2Q2A5.AF.

Dimensions:See Fig. 1.

Page 37: Programador 7800 Series RM Completa

7800 SERIES Communications

QS7800A/QS7850A Communications Interface ControlBus ModuleAllOWS remote monitoring and diagnostics of the RM78xx and EC78xx SERIES relaymodules with an lBM® compatible personal computer.

● Provides local and remote annunciation of 7800 SERIESfaults.

● QS7850A provides open protocol communicationswith third party systems.

● Provides user interface to personal computer.● Modular construction, NEMA #1 rated enclosure.

Electr icalOrder Connectors

Number I n c l u d e d Used With

APPROVAL BODIES:Underwriters Laboratories Inc. component recognized,

File No. MP268, Guide No. MCCZ2.Canadian Standards Association certified, LR80141.Federal Communications Commission, Part 15, Class

A-Emissions, Part 68; registered.FCC Registration Number HS92SJ-10735-D-T-E.Canadian Department of Communications certified.

DIMENSIONS: 4-21/32 in. [118 mm] wide, 3-29/32 in. [99 mm]high, 1 in. [25 mm] deep.

WEIGHT 8 oz.OPERATING AMBIENT TEMPERATURE RANGE: 32 F to 130

F [0 C to 54 C].ENCLOSURE: NEMA 1ELECTRICAL RATING: RS485 ControlBus. Current Draw:

7 mA.OPTIONAL COMPONENT:200603 ControlBus Module 3-Wire Electrical Connector.

QS7800A1001 ControlBus three-prong 7800 SERlES relayelectrical connector.

QS7800B1000 Network Interface 7800 SERIES RelayControlBus Module for Modules S7810Multi-dropping up to 31 Network Interfacemulti-dropped .7800Series.

QS7850A1006 ControlBus three-prong Provides open com-electrical connector. munication with third

party systems.

QS7800C1009 ControlBus three-prong SYSNet TM Dataelectrical connector. Acquisition Modules.

QS7800D1008 Control Bus three-prong Armstrongelectrical connector. International

TrapscanTM TrapMonitoring System.

QS7800E1007 ControlBus three-prong Pulsafeederelectrical connector. PULSAtrol™ Surface

Blowdown System.

modules.

ZM7850A Combustion System ManagerTM SoftwareThe ZM7850 is support software for connecting BCS7700, RM78xx, and EC78xx SERIES controls with anlBM® or equivalent personal computer running MicrosoftWindows™ 3.0 or greater. It is a graphical, mouse-drivensoftware package that is easy to use and understand. Itprovides data logging, remote interrogation, remote setpoint adjustment of non-safety parameters (BCS 7700only), history, real-time graphics, and control pointtrending.

and fault reporting for up to 6,000 individual burner/boilercontrols.

Order DescriptionNumber

ZM7850A1001 Combustion System Manager

ZM7850B1000 SYSNet™ Software to monitor Honeywell BBCPulsafeeder Controls, Armstrong Traps & AdamData Acq. modules. Microsoft windows based.Touch screen compatible faceplates, dynamicgraphics, instrumentation & multi-media.

Page 38: Programador 7800 Series RM Completa

A matrix listing the O. S. numbers obsoleted and their modified replacements if listedbelow:

Amplifiers ModifiedObsoleted Replacement

R7847A1058 R7847A1025R7847A1066 R7847A1033R7847A1090 R7847A1074R7847A1108 R7847A1082R7847B1049 R7847B1023R7847B1056 R7847B1031R7847B1080 R7847B1064R7847B1098 R7847B1072R7849A1049 R7849A1015R7849A1056 R7849A1023R7849B1039 R7849BI013R7849B1047 R7849B1021R7861A1000 R7861A1034R7861A1018 R7861A1026

A7800A TesterProvides quick operational check of the 7800 SERIES System components.

● Function switches and selectors simulate interlocks andcontrol functions that allow 7800 SERIES devices to oper-ate through sequences.

● Indicator lamps represent outputs as activated. Order Number ApplicationA7800A1002 Operational tests of 7800 SERIES relay mod-

OPERATING AMBlENT TEMPERATURE RANGE: 0 F to 120 F[–18 C to 49 C].

ELECTRICAL RATING: 120 Vac, 50/60 Hz.

REQUIRED COMPONENTS:203579A Configuration plug for RM7800/RM7840.203579B Configuration plug for RM7838A.203579C Configuration plug for RM7838B.203579D Configuration plug for RM7885.203579E Configuration plug for RM7890.203579F Configuration plug for RM7895.203579G Configuration plug for RM7823.

OPTIONAL COMPONENTS:123514A Rectification Flame Simulator.203659 Ultraviolet Flame Simulator.W136A Test Meter.

REPLACEMENT PARTS: 192128 Panel fuse, 1.0A.

ules.

Page 39: Programador 7800 Series RM Completa

7800 SERIES Accessories

Accessories

203968A221729A

Description/Title Part Number Used With

ControlBus Module Electrical Connector 200603 QS7800

Electrical Access Slot Covers 221779 Q7800

Dust Cover 221729A RM7800, RM7823, RM7824,RM7838, RM7840, RM7885,RM7888, RM7890, RM7895,EC7810, EC7820, EC7823,EC7830, EC7850 with S7800A

ControlBus 5-Wire Electrical Connector 203541

Remote Display Mounting Bracket 203765

Remote Display Power Supply (Plug-in) 13 Vdc 203968A

Extension Cable Assembly for Remote MountingKeyboard Display Module-60 in. Cable Length 221818A

120 in. Cable Length 221818C

NEMA 4 Cover Assembly with Waterproof Gasket 204718A

NEMA 4 Cover Assembly with Waterproof Gasket 204718Cand provides remote reset of the 7800 seriesdevice

Flush Mounting Bracket 205321B

Page 40: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

Intermittent Pilot Applications

VR8304 Intermittent Pilot Dual Automatic Valve Combination GasControlCombination gas control for use in24 Vac, gas-fired, intermittent pilotappliances with capacities from 30to 415 cfh.

Controls include safety shutoff,manual valve, two automatic oper-ators, pressure regulator and pilotadjustment.Use with S86F, H; S860D;S8600F,H; S8610 and S90A,B Con-trol Modules.Compact size.Provide two automatic valves.Solenoid operated first automatic valve opens on thermostat callfor heat; closes when call for heat ends. Diaphragm-operatedsecond automatic valve opens under control of regulator; closesif gas or power supply is interrupted.

Meet codes requiring dual safety shutoff.Standard and slow opening natural gas models include natural toLP gas conversion kit; LP to natural gas conversion kit alsoavailable.All adjustments, wiring connections and pilot outlet are acces-sible from top of control.Adjustable servo regulator effectively maintains almost constantgas output pressure under wide fluctuations in gas supply pres-sure.Compatible with ECO connector.ON-OFF lighting sequence.

VR8304 controls replace the following Honeywell and competitivecombination gas controls for applications requiring a minimumcapacity of 30 cfh and a maximum capacity of 415 cfh.

—Honeywell VR8440 and VR8204 —White Rodgers 36E36/38—Robertshaw 7100DER (700-070)

Typical wiring connections in 24V system with S8610.

POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.

ALTERNATE LIMIT CONTROLLER LOCATION.

MAXIMUM CABLE LENGTH 3ft. (0.9 m).

CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG TO TRANSFORMER.

REMOVE PLUG ONLY IF USING VENT DAMPER. FUSE BLOWS ON STARTUP WHEN PLUG IS REMOVED AND VENT DAMPERWIRING HARNESS IS INSTALLED; THEN MODULE WILL OPERATE ONLY WHEN VENT DAMPER IS CONNECTED.

REMOVE JUMER AND CONNECT SENSE TERMINAL ON TWO ROD APPLICATION ONLY.

lF THE EVENT DAMPER IS CONNECTED, WIRE 24V TERMINAL AS SHOWN. CONNECT VENT DAMPERCABLE IN PLACE OF PLUG SHIPPED WITH THE S8610U. M8150

Page 41: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

VR8304 continued

APPROVALS:American Gas Association Design Certified: File No. L2025007.Canadian Gas Association Design Certified: File No. L2025007.

MOUNTING: 0 to 90 degrees in any direction from upright positionof gas control knob, including vertically.

BODY PATTERN: Straight-through with 1/2 x 1/2 in., 1/2 x 3/4 in., and3/4 x 3/4 in. inlets and outlets.

PILOT GAS OUTLET: Compression fitting for 1/4 in. OD tubing.PRESSURE TAPPING: 1/8 in. NPT with plug.PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.TEMPERATURE RATINGS:

Ambient: VR8304H: 0 F to 175 F (–18 C to +79 C).VR8304K,M,P: –40 F to +175 F (–40 C to +79 C).

ELECTRICAL RATINGS:Power Supply: 24 Vac, 60 Hz.Electrical Connections: 1/4 in. male quick-connects.

THERMOSTAT HEAT ANTICIPATOR SETTING: 0.7A.

* TRADELINE models.

VR8304 dimensions in in. (mm).

CapacityA.G.A.

CertifiedaPressure Regulator

SettingOrder

Number

Inlet-OutletSize (in.)

Typeof

Gas

Type ofPressureRegulatorc f h m3/hr in. wc kPa Includes

a Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressuredrop).

b Use of 3/4 x 1/2 in. reducer bushing reduces capacity to 270 cfh (7.6 m3/hr).c Step pressure is not adjustable.

Page 42: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

VR8204 Intermittent Pilot Dual Automatic Valve Combination GasControlsCombination gas controls for use in24 Vac, gas-fired, intermittent pilot ap-pliances with capacities from 20 to200 cfh.

Controls include manual valve, two au-tomatic operators, servo pressure regu-Iator and pilot adjustment.Use with S86F,H; S8600F,H and S8610Control Modules.Compact size.Provide two automatic valves.Solenoid operated first automatic valve opens on thermostat callfor heat; closes when call for heat ends. Diaphragm operatedsecond automatic valve opens under control of regulator; closesif gas or power supply is interrupted.Meet codes requiring dual safety shutoff.Standard and slow opening natural gas models include natural toLP gas conversion kit; LP to natural gas conversion kit alsoavailable.All adjustments and wiring connections are accessible from top ofcontrol.ON-OFF lighting sequence.

VR8204 controls replace the following Honeywell and competitivecombination gas controls for applications requiring a minimumcapacity of 20 cfh and a maximum capacity of 200 cfh.

—Honeywell VR8440—White Rodgers 36E36/38—Robertshaw 7100DER (700-070)

APPROVALS:American Gas Association Design Certified: File No. L2025006.Canadian Gas Association Design Certified: File No. L2025006.

MOUNTING: 0 to 90 degrees from the upright position of gas controlknob, including vertically.

BODY PATTERN: Straight-through with 1/2 in. inlets and outlets.PRESSURE TAPPING: 1/8 in. NPT with plug.

PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.PILOT GAS OUTLET: Compression fitting for 1/4 in. OD tubing.TEMPERATURE RATINGS:

Ambient: VR8204A,C,H: 0 F to 175 F (–18 C to +79 C).VR8204M: –40 F to +175 F (–40 C to +79 C).

ELECTRICAL RATINGS:Power Supply: 24 Vac, 60 Hz.Electrical Connections: 1/4 in. male quick-connects.

THERMOSTAT HEAT ANTICIPATOR SETTING: 0.5A.

See VR8304 for typical wiring connections.

VR8204 dimensions in in. (mm).

CapacityA.G.A. Certifieda

Pressure RegulatorSetting Type of

Gas

Type ofPressureRegulatorOrder Number

Inlet-OutletSize (in.) c f h m 3/hr in. wc kPa Includes

Page 43: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

VR8204 continued

Capacity,A.G.A. Certifieda

Pressure RegulatorSettingInlet-Outlet

Size (in.)Order Number cfh m 3/hr in. wc kPaType of

Gas

Type ofPressureRegulator Includes

a Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressuredrop).

b Use of 1/2 x 3/8 in. reducer bushing reduces capacity to 130 cfh (3.7 m3/hr).c Step pressure is not adjustable.

Page 44: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

VR4304 Intermittent Pilot Dual Automatic Valve Combination GasControlCombination gas control for use in120 Vac, gas-fired, intermittent pilotappliances with capacities from 30to 415 cfh.

Control includes manual valve, twoautomatic operators, pressure regu-lator and pilot adjustment.Compact size.Provides two automatic valves.Solenoid operated first automaticvalve opens on thermostat call forheat; closes when call for heat ends. Diaphragm-operated sec-ond automatic valve opens under control of regulator; closes ifgas or power supply is interrupted.Meets codes requiring dual safety shut-off.Includes natural to LP gas conversion kit.All adjustments, wiring connections and pilot outlet are acces-sible from top of control.Adjustable servo regulator effectively maintains almost constantgas output pressure under wide fluctuations in gas supplypressure.ON/OFF lighting sequence.

VR4304 control replaces the following Honeywell combination gascontrols for 120 Vac applications requiring a minimum capacity of30 cfh and a maximum capacity of 415 cfh.

—Honeywell VR4440 and VR4204

NOTE: Conduit cover (included) must be used if control is notmounted in appliance.

APPROVALS:American Gas Association Design Certified: File No. L2025007.Canadian Gas Association Design Certified: File No. L2025007.

MOUNTING: 0 to 90 degrees in any direction from upright position ofgas control knob, including vertically.

BODY PATTERN: Straight-through with 3/4 x 3/4 in. inlet and outlet.PILOT GAS OUTLET: Compression fitting for 1/4 in. OD tubing.PRESSURE TAPPING: 1/8 in. NPT with plug.PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.TEMPERATURE RATINGS:

Ambient: –40 F to 175 F (–40 C to +79 C).ELECTRICAL RATINGS:

Power Supply: 120 Vac, 60 Hz.Electrical Connections: 1/4 in. male quick-connects; 24 in.

(610 mm) Ieadwires.THERMOSTAT HEAT ANTICIPATOR SETTING: 0.13A.

Typical wiring for 120V control in intermittent ignition system.

*TRADELINE model.

Inlet-Outlet

Size (in.)

CapacityA.G.A. Certifieda

Pressure RegulatorSettingOrder

Number

Typeo f

Gas

Type ofPressureRegulatorcfh m3/hr in. wc kPa Includes

*VR4304M4519 3/4 x 3/4 3 0 0 8.5 3.5 0.9 N a t . Standard 393691 Natural to LP gas conversionkit.

aCapacities based on 1,000 Btu/ft.3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressuredrop).

Page 45: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

Hot Surface/Direct Spark Applications

VR8305 Direct Ignition Dual Automatic Valve Combination GasControlsCombination gas control for usewith hot surface/direct spark sys-tems in 24 Vac, gas-fired appli-ances, with capacities from 30 to415 cfh.

Controls include manual valve, twoautomatic operators, and pressureregulator.Use with S89C,E,F and S87 series 5and later.Compact size.Provide two automatic valves.Solenoid-operated first automatic valve opens on thermostat callfor heat; closes when call for heat ends. Diaphragm-operatedsecond automatic valve opens under control of regulator; closesif gas or power supply is interrupted.Meet codes requiring dual safety shut-off.All adjustments, wiring connections and pilot outlet are acces-sible from top of control.Adjustable servo regulator effectively maintains almost constantgas output pressure under wide fluctuations in gas supply pres-sure.ON-OFF lighting sequence.

VR8305 controls replace the following Honeywell and competitivecombination gas controls for applications requiring a minimumcapacity of 30 cfh and a maximum capacity of 415 cfh.

—Honeywell VR8450 and VR8205—White Rodgers 36E36/38 and 36C68—Robertshaw 7200DER

APPROVALS:American Gas Association Design Certified: File No. L2025007.Canadian Gas Association Design Certified: File No. L2025007.

VR8305 dimensions in in. (mm).

Typical wiring connections for 24V system with S89/S890.

Page 46: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

VR8305 continued

MOUNTING: 0 to 90 degrees in any direction from upright position TEMPERATURE RATINGS:of gas control knob, including vertically. Ambient:

BODY PATTERN: Straight-through with 1/2 x 3/4 in. inlets and outlets. VR8305H: 0 F to 175 F (–18 C to +79 C).PRESSURE TAPPING: 1/8 in. NPT with plug. VR8305M,P: –40 F to +175 F (–40 C to +79 C).PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure. ELECTRICAL RATINGS:

Power Supply: 24 Vac, 60 Hz.Electrical Connections: 1/4 in. male quick-connects.

THERMOSTAT HEAT ANTICIPATOR SETTlNG: 0.7A.

Inlet-Outlet

Size (in.)

Capacity,A.G.A. Certifieda

Pressure RegulatorSetting Type of

G a s

Type ofPressureRegulatorOrder Number c f h m 3/hr in. wc k P a Includes

VR8305H4005 3/4 x 3/4 300 8.5 3.5 0.9 Nat. Slow-opening

VR8305M3506 1/2 x 3/4Standard

270 7.6

1/2 x 1/2VR8305P2208 240 6 . 8 1.2 Stepc; 0.34 Stepc; Step-3.5 full rate 0.9 full rate opening

VR8305P2224 4.0 Stepc; 1.0 Stepc; LP10.0 full rate 2.5 full rate

VR8305P4204 3/4 x 3/4 300 8.5 1.2 Stepc; 0.3 Stepc; Nat.3.5 full rate 0.9 full rate

VR8305P4212 2.5 Stepc; 0.62 Stepc; LP10.0 full rate 2.5 full rate

VR8305P4279 0.9 Stepc; 0.22 Stepc; Nat.3.5 full rate 0.9 full rate

One 3/4 x 1/2 in. reducerbushingb; 393691 Naturalto LP gas conversion kit.

a Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 Sp gr natural gas at 0.25 kPa pressuredrop).

b Use of 3/4 x 1/2 in. reducer bushing reduces capacity to 270 cfh (7.6 m3/hr).c Step pressure is not adjustable.

VR8205 Direct Ignition Dual Automatic CombinationGas ControlsCombination gas controls for usewith hot surface/direct spark sys-tems in 24 Vac, gas-fired applianceswith capacities from 20 to 200 cfh.

Controls include manual valve, twoautomatic operators and servopressure regulator.Compact size.Use with S87C,D and S89E,F Con-trol Modules.Provide two automatic valves.Solenoid operated first automatic valve opens on thermostat callfor heat; closes when call for heat ends. Diaphragm operatedsecond automatic valve opens under control of the regulator;closes if gas or power supply is interrupted.Meet codes requiring dual safety shutoff.Standard and slow opening natural gas models include natural toLP gas conversion kit; LP to natural gas conversion kit alsoavailable.Adjustments and wiring connections are accessible from top ofthe control.ON-OFF lighting sequence.

VR8205 controls replace the following Honeywell and competitivecombination gas controls for applications requiring a minimumcapacity of 20 cfh and a maximum capacity of 200 cfh.

—Honeywell VR8450—White Rodgers 36E36/38

APPROVALS:American Gas Association Design Certified: File No. L2025006.Canadian Gas Association Design Certified: File No. L2025006.

MOUNTING: 0 to 90 degrees in any direction from the uprightposition of the gas control knob, including vertically.

VR8205 dimensions in in. [mm].

continued next page

Page 47: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

VR8205 continued

BODY PATTERN: Straight-through. ELECTRICAL RATINGS:PRESSURE TAPPING: 1/8 in. NPT with plug. Power Supply: 24 Vac, 60 Hz.PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure. Electrical Connections: 1/4 in. male quick-connects.TEMPERATURE RATINGS: THERMOSTAT HEAT ANTICIPATOR SETTING: 0.5A.

Ambient: 0 F to 175 F (–18 C to +79 C).

Typical wiring connections for 24V system with S89C.

POWER SUPPLY. PROVIDE DISCONNECT MEANS CONTROLS IN 24V CIRCUIT MUST NOT BE IN GROUND LEG T0AND OVERLOAD PROTECTION AS REQUIRED. TRANSFORMER.MAKE SURE L1 AND L2 ARE NOT REVERSED:

THIS WOULD PREVENT FLAME DETECTION. SEN TERMINAL AND Q354 FLAME SENSOR ON D MODELS ONLY.

ALTERNATE LIMIT CONTROLLER LOCATION.

*TRADELINE model.

OrderNumber

Inlet-Outlet

Size (in.)

CapacityA.G.A. Certifieda

Pressure RegulatorSetting

Typeof

G a s

Type ofPressureRegulatorcfh m 3/hr in. wc kPa Includes

a Capacities based on 1,000 Btu/ft3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressuredrop).

b Use of 1/2 x 3/8 in. reducer bushings reduces capacity to 130 cfh (3.7 m3/hr).c Step pressure is not adjustable.d Lockout time required for module is 8.5 seconds.

Page 48: Programador 7800 Series RM Completa

Gas Burner Controls—Combination

VR4305 Direct Ignition Dual Automatic Valve Combination GasControlCombination gas control for use withhot surface/direct spark systems in 120Vac, gas-fired appliances, with capac-ities from 30 to 415 cfh.

Controls include manual valve, twoautomatic operators and pressureregulator.Compact size.Provides two automatic valves.Solenoid operated first automaticvalve opens on thermostat call for heat;closes when call for heat ends. Dia-phragm-operated second automatic valve opens under control ofregulator; closes if gas or power supply is interrupted.Meets codes requiring dual safety shut-off.Includes natural to LP gas conversion kit.All adjustments, wiring connections and pilot outlet are acces-sible from top of control.Adjustable servo regulator effectively maintains almost constantgas output pressure under wide fluctuations in gas supply pres-sure.ON/OFF lighting sequence.

VR4305 controls replace the following Honeywell combination gascontrols for applications requiring a minimum capacity of 30 cfh anda maximum capacity of 415 cfh.

—Honeywell VR4450 and VR4205

NOTE: Conduit cover (included) must be used if control is notmounted in the appliance.

APPROVALS:American Gas Association Design Certified: File No. L2025007.Canadian Gas Association Design Certified: File No. L2025007.

MOUNTING: 0 to 90 degrees in any direction from upright position ofgas control knob, including vertically.

BODY PATTERN: Straight-through with 3/4 x 3/4 in. inlet and outlet.PRESSURE TAPPING: 1/8 in. NPT with plug.PRESSURE RATINGS: 1/2 psi (3.5 kPa) inlet pressure.

*TRADELINE model.

TEMPERATURE RATINGS:Ambient: –40 F to +175 F (–40 F to +79 C).

ELECTRICAL RATINGS:Power Supply: 120 Vac, 60 Hz.Electrical Connections: 1/4 in. male quick-connects; 24 in.

(610 mm) leadwires.THERMOSTAT HEAT ANTICIPATOR SETTING: 0.13A.

Typical wiring for 120V control in direct ignition system.

POWER SUPPLY. PROVIDE DISCONNECT MEANS

AND OVERLOAD PROTECTION AS REQUIRED.

ALTERNATE LIMIT CONTROLLER LOCATION. M3088

CapacityA.G.A. Certifieda

Pressure RegulatorSetting

Type ofPressure

RegulatorOrder NumberIntlet-Outlet

Size (in.)Type of

Gasc f h m 3 / h r in. wc kPa Includes

*VR4305M4532 3/4 x 3/4 300 8.5 3.5 0.87 Nat. Standard 393691 Natural to LP conversion kit;390427 pipe bushing.

a Capacities based on 1,000 Btu/ft.3, 0.64 sp gr natural gas at 1 in. wc pressure drop (37.3 MJ/m3, 0.64 sp gr natural gas at 0.25 kPa pressuredrop).

Page 49: Programador 7800 Series RM Completa

Gas Burner Controls—lgnition Controls

S9301 Integrated Boiler ControlProvides control of a high efficiency gas boiler with a combus- ● Four LED lights indicate operating mode and help identify thetion air blower and a combination hot surface igniter/flame problem source during troubleshooting.sensor. ● Keyed plugs for wiring connections.

S9301 provides: NOTE: For use in residential boilers only; not for use with a ventSequencing of ignition and burner operation. damper.Two additional trials for ignition if initial Iightoff is unsuccessful.Wiring terminal board for all electrical connections. IMPORTANT: This control is configured for application to specificControl of circulator pump and combustion blower motors. appliance models. It is intended for direct replacement of OEMMonitoring of Aquastat and auxiliary limits to ensure proper water installed controls only; see order table. Do not attempt to applytemperature and of the air proving switch to ensure proper this control except as a direct replacement for the specific Honey-sequencing of combustion air before the ignition sequence starts. well models noted in the order table below.Continued circulator pump operation during lockout as long asthermostat calls for heat. Order Number Replaces Application

S9301A1027 S9301A1001S9301A1027

High efficiency gas boiler.

S8610U Universal Intermittent Pilot ModuleField service replacement formost Honeywell, Robertshaw,Johnson, and UTEC (HSC) in-termittent pilot ignition mod-ules. Provides electronic con-trol of most intermittent pilotignition systems used on gas-fired furnaces, boilers andother heating appliances.

Provides ignition sequence, flame monitoring and safety shutofffor intermittent pilot central furnaces and heating appliances.Provides 100 percent pilot gas shutoff if pilot fails to light; after6-minute delay, trial for ignition is repeated. Ignition trial/delaysequence is repeated until the appliance lights or call for heat isremoved.For use with natural or LP gas.For use in single rod or dual rod/remote sense applications.Includes relay contacts for use with any intermittent pilot gascontrol string with maximum 1.0A pilot or 2.0A main valve rating;Honeywell VR8204, VR8304 or VR8345M combination gas con-trol recommended.Functional equivalent of S86, S8600, S8610 and S90 modules.Includes spark cable adapters to allow field replacement of bothHoneywell and competitive controls without replacing existingspark cable.

Replaces most of the following intermittent pilot modules:—Honeywell S86, S90, S8600 and S8610—Robertshaw SP715, SP715A, SP735, SP735A, SP735L—Johnson GSA, G60, G65, G67, G600, G770

Refer to S8610 specification sheet for a complete list of modelnumbers.

● SUPER TRADELINE model.

APPROVALS:American Gas Association Design Certified.Canadian Gas Association Design Certified.Underwriters Laboratories Inc. Component Recognized.

TEMPERATURE RATINGS:Ambient: –40 F to +165 F (–40 C to +74 C).FLAME FAILURE RESPONSE TIME: 0.8 sec. at 1.0 µA flame current.ELECTRICAL CONNECTIONS: 1/4 in. male quick-connect terminals,

including ignition terminal (3/16 in. male quick-connect senseterminal).

ELECTRICAL RATINGS:Power Supply: 24V (nominal), 60 Hz.Current: 0.2ASpark Generator Output: 13 kV peak at 25 pf load.Contact (at 24 Vac):

Running Inrush

Pilot 1.0A 10.0A

Main 2.0A 20.0A

NOTE: Maximum ambient temperature is 175 F (79 C) if main valverelay load is 1.0A or less.

THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus pilot valverating plus main valve rating.

ACCESSORIES:394800-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-

connect on module end; Rajah connector receptacle,90 deg. rubber boot on igniter end.

394801-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-connect on module end; Rajah connector receptacle, straightrubber boot on igniter end.

ShutoffTimeOrder Number Description

S8610U1003 90 sec. max. 100 percent pilot gas shutoff and lockout on loss of pilot flame. Includes remote reset, and automaticvent damper plug. For use in systems with combination igniter-sensor (single rod or sense) or separateigniter and sensor (dual rod or remote sense).

Page 50: Programador 7800 Series RM Completa

Gas Burner Controls—Ignition Controls

S8610; S8670 Intermittent Pilot ModulesProvide electronic control of in-termittent pilot ignition systemsused on gas-fired furnaces,boilers and other heatingappliances.

Provide ignition sequence,flame monitoring and safetyshutoff for intermittent pilot central furnaces and heatingappliances.Functional equivalent of S86, S860 and S90 modules.Include spark cable adapter to allow field replacement of S86,S860 and S90 without replacing existing spark cable.Include relay contacts for use with any intermittent pilot gas con-trol string with maximum 1.0A pilot and 2.0A main valve rating;Honeywell VR8204, VR8304 or VR8440 combination gas controlrecommended.S8610F is for use with natural gas only; modules do not provide100 percent pilot gas shutoff if pilot fails to light.S8610H; S8670D are for use with natural or LP gas; modulesprovide 100 percent pilot gas shutoff and lockout if pilot fails tolight.

See Honeywell to S8610 Intermittent Pilot Modules Cross Referencefor a list of Honeywell intermittent pilot modules that S8610F,H;S8670D replace.

APPROVALS:American Gas Association Design Certified.Canadian Gas Association Design Certified.Underwriters Laboratories Inc. Component Recognized.

TEMPERATURE RATINGS:Ambient: –40 F to +165 (40 C to +74 C).

FLAME FAILURE RESPONSE TIME: 0.8 sec. at 1.0µA flame current.ELECTRICAL CONNECTIONS: 1/4 in. male quick-connect terminals,

including ignition terminal.ELECTRICAL RATINGS:

Power Supply: 24V (nominal), 60 Hz.Current: 0.2A.Spark Generator Output: 13 kV peak at 25 pf load.Contacts:

Running Inrush

Pilot 1.0A 10.0A

Main 2.0A 20.0A

NOTE: Maximum ambient temperature is 175 F (79 C) if main valverelay load is 1A or less.

THERMOSTAT HEAT ANTICIPATOR SETTlNG: 0.2A plus pilot valverating plus main valve rating.

ACCESSORIES:394800-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-

connect on module end; Rajah connector receptacle, 90 deg.rubber boot on igniter end.

394801-30 Ignition Cable; 30 in. (762 mm) cable with 1/4 in. quick-connect on module end; Rajah connector receptacle, straightrubber boot on igniter end.

Order Number Lockout Time Description

S8610F1008 None. Continuous trial for ignition. Non-100 percent shutoff if pilot fails to light. For use in systems with combina-tion igniter-sensor.

S8610H1004 15 sec. max. 100 percent pilot gas shutoff and lockout if pilot fails to light. Includes remote

S8610H1020 a 15 sec. max.reset. For use in systems with combination igniter-sensor.

S8670D1000 90 sec. max. 100 percent pilot gas shutoff and lockout if pilot fails to light. Includes remotereset. For use in systems with combination igniter-sensor where prepurgecycle is desired (45 second prepurge timing).

a Includes automatic vent damper plug for D892 Vent Damper.

Page 51: Programador 7800 Series RM Completa

Gas Burner Controls—Ignition Controls

Honeywell to S8610 Intermittent Pilot Modules Cross ReferenceExisting Model Number Replacement Model Number

S86A1001, S86A1019, S8610U1003, S8610F1008S86A1027, S86A1035,S86B1009, S86B1017,S86B1025

S86C1007, S86C1015 S8610U1003

S86C1023 S8610H1004

S86C1031, S86C1049, S8610U1003S86C1056, S86D1005

S86D1013 S8610H1004

S86D1021 S8610U1003

S86E1002, S86E1010, S8610U1003, S8610F1008S86E1028, S86E1036

S86E1044, S86E1051 S8610U1003

S86E1069, S86E1077, S8610U1003, S8610F1008S86E1101, S86E1119,S86E1127, S86F1000,S86F1018, S86F1026,S86F1042, S86F1059,S86F1067, S86F1075

S86F1083, S86F1091 S8610U1003

S86G1008, S86G1016 S8610U003

S86G1024 S8610H1004

S86G1032, S86G1057, S8610U1003S86G1073, S86H1006

S86H1014 S8610H1004

S86H1022, S86H1048, S8610U1003S86H1089, S86H1097,S86H1105

S86H1113 S8610H1004

S86H1121 S8610U1003

S86H1139 S8610H1020

S86H1147 S8610U1003

S90A1005 S8610U1003

S9OB1003, S90B1011 S8610U1003

S860C1000, S860D1009 S8670D1000

S8600A1001 S8610U1003

S8600B1009 S8610U1003

S8600C1065 S8610U1003

S8600F1000 S8610U1003, S8610F1008

S8600F1034 S8610U1003

aS8610U1003 does not have meter shunt.bReplacement control does not have continuous rety.

Existing Model Number Replacement Model Number

S8600F1042 S8610U1003, S8610F1008

S8600H1006 S8610U1003

S8600H1014 S8610H1004

S8600H1022 S8610U1003

S8600H1048, S8600H1055 S8610U1003

S8600H1063 S8610H1004

S8600H1071 S8610U1003

S8600H1089 S8610U1003

S8600H1097 S8610U1003

S8600H1105 S8610U1003 a

S8600M1005, S8600M1013 S8610U1003

S8610A1009 S8610U1003

S8610B1007, S8610B1015 S8610U1003

S8610C1005 S8610U1003

S8610F1008 S8610U1003, S8610F1008

S8610F1016 S8610U1003

S8610F1024 S8610U1003, S8610F1008

S8610F1032 S8610U1003

S8610H1004 S8610H1004

S8610H1012 S8610U1003

S8610H1020 S8610H1020

S8610H1038, S8610H1046 S8610U1003

S8610H1053 S8610U1003

S8610H1061 S8610H1004

S8610H1079 S8610U1003

S8610M1003 S8610U1003

S8610M1011 S8610H1004 b

S8610M1029 S8610U1003

S8610U1003 S8610U1003

S8620C1003 S8610H1004 b

S8620C1011 S8610H1020 b

S8620H1002 S8610U1003

S8620H1010 S8610H1004

S8620H1028 S8610U1003

S8660D1002, S8670D1000, S8670D1000S8670D1018

S8670E1007 S8670D1000 b

Page 52: Programador 7800 Series RM Completa

Gas Burner Controls—Ignition Controls

Y8610F and U Universal Retrofit Intermittent Pilot GasBurner Ignition Systems

Complete kits for converting conventional standing pilot sys-tems to intermittent pilot systems. For use with 24 Vac gas-firedatmospheric furnaces, boiler and heating appliances.

● Y8610F kits are for use with natural gas only: continue trial forignition until the pilot lights or the system is shutdown manually.

● Y8610U kits are for use with natural or LP gas: provides 100percent pilot gas shutoff if pilot fails to light; after 6-minute delay,trial for ignition is repeated. Ignition trial/delay sequence is repeat-ed until the appliance lights or call for heat is removed.

● SUPER TRADELINE model.

Each Y8610 system includes:—S8610F or U Intermittent Pilot Module.—VR8204 or VR8304 Intermittent Pilot Dual Valve Combination Gas

Control with an ON-OFF manual valve, pressure regulator and twoautomatic main gas valve operators. Includes reducer bushings.

—393691 LP Gas Conversion Kit with Y8610U.—392431 Igniter-Sensor Assembly. Includes ceramic-insulated

Kanthal rod that attaches to the existing pilot burner in place of thethermocouple.

—394800-30 Ignition Cable. 30 in. (762 mm) cable with connectors.—393690-14 Flange Assembly with Y8610U. Includes 3/4 in. straight

flange with O ring, 9/64 hex screws and wrench.—Wiring Harness. 30 in. (762 mm) wiring harness with 1/4 in. quick-

connect terminals.—Reducer bushings for gas control.—Adhesive mounting tape for S8610.—Miscellaneous installation hardware—screws, solderless con-

nectors, ground rod and adapter.

ELECTRICAL RATINGS:Power Supply: 24 Vac (nominal), 60 Hz.Current: 0.7A (includes both module and gas control).

THERMOSTAT HEAT ANTICIPATOR SETTING—0.7A plus currentratings of other devices in thermostat control circuit.

Compatible with all open-close switch type 24 Vac thermostatscapable of supplying rated voltage and current to the module. Alsocompatible with Honeywell electronic thermostats that directlyswitch the ignition module.

OrderNumber Includes

Capacity( B t u h )c

Inlet-Outlet

Size (in.)

Temperature Ratings

F CType

of Gas

Y8610F5003 S8610F1008 a Control Module and 150,000 1/2 x 1/2 0 to 175VR8204A2142 Combination Gas Control

–18 to +79 Natural

● Y86103003 S8610U1003 b,d Control Module and 270,000 1/2 x 3/4 –40 to +175 –40 to +79 NaturalVR8304M3558 Combination Gas Control, or LPtwo 3/4 x 1/2 in. reduce bushings.

a With non-100 percent shutoff. c 0.64 sp gr Nat. gas at 1 in. wc (0.25 kPa) pressure drop.b With 100 percent pilot gas shutoff and lockout, 90 second maxi- d Includes automatic vent damper plug.

mum timed trial for ignition.

Page 53: Programador 7800 Series RM Completa

Gas Burner Controls—lgnition Controls

S8910U Universal Hot Surface Ignition ModuleProvides operating control of adirect ignition system using a120 Vac hot surface igniter.

Provides easy field-replacementof a wide range of hot surfaceignition modules manufacturedby Honeywell, Robertshaw andWhite-Rodgers. Refer to theproduct specification sheet for specific models that can bereplaced by the S8910U.For 120 Vac (up to 5.0A) hot surface igniter (Norton 201/271 orequivalent).For local (single rod) or remote (dual rod) rectification type flamesensing.Contains easy-to-use instructions plus the accessories requiredto adapt the existing hot surface ignition module.

!WARNINGEXPLOSION HAZARD, CAN CAUSE INJURY OR EQUIPMENTDAMAGE.The S8910U can be used only for direct replacement of specificinstalled models. Check the product specification sheet and thecross-reference (page 77) before replacing an existing hot surfacemodule with the S8910U. If the existing module is not listed, do notuse the S8910U to replace it. Always use the selection tab specifiedin the product specification sheet for the existing module beingreplaced. Replacement of an unlisted module or use of a selectiontab other than specified can result in appliance malfunction.

APPROVALS:American Gas Association Certified: Report no. C3090002.Canadian Gas Association Certified: Report no. C3090002.

TEMPERATURE RATINGS:Ambient: –40 F to +175 F (–40 C to +79 C).

HOT SURFACE IGNITER OR IGNITER-SENSOR: Norton Model 201or 271 or equivalent.

SENSOR: Separate sensor required for remote sense applications.

WIRING: Use existing appliance wiring. If repair or replacement ofleadwires is required, follow instruction on appliance label. Useincluded quick-connect terminals and wiring adapters accordingto instructions.

ELECTRICAL RATINGS:Important: The S8910U is for use only in 60 Hz systems.

Power Supply: 24V, 60 Hz.Valve Contacts: 2A max.Current Draw: 0.4A plus valve load.Hot Surface Igniter Voltage: 120 Vac, 60 Hz.Igniter Contacts: 5A at 120 Vac.

PREPURGE: 32 seconds.IGNITER WARMUP: 34 seconds.BETWEEN TRIAL PURGE: 96 seconds (3 trial mode only).FLAME FAILURE RESPONSE TIME: 1.5 seconds maximum.IGNITION SEQUENCE: The number of trials for ignition and trial time

is determined by the selection tab. If a selection tab is not in-stalled, the module will operate at four seconds trial time and oneignition trial.

SELECTION TAB SPECIFICATIONS:

Trial Time Number ofSelection Tab (seconds) Ignition Trials

A 4 1

B 4 3

C 7 1

D 7 3

● SUPER TRADELINE model.

Order Number Application● S8910U1000 For direct replacement of a wide range of hot

surface ignition modules manufactured byHoneywell, White Rodgers and Robertshaw.Refer to the product specification sheet and theCross-Reference (page 77) for specific modelsthat can be replaced by the S8910U.

Page 54: Programador 7800 Series RM Completa

Gas Burner Controls—lgnition Controls

S89C,D,G,H,J; S890 Hot Surface Ignition ModulesProvide electronic control of 120V hotsurface ignition systems used in fur-naces, boilers and other heatingappliances.

S89C,G,J; S890G are for systems withcombination igniter-sensor; S89D,H andS890H are for systems with separate igni-ter and sensor.Use with Norton 201 Hot Surface Ignitersor equivalent.Lockout after one (S89C,D) or three(S89G,H; S890G,H) trials for ignition if main burner fails to ignite.Reset from thermostat after lockout.S89G,H; S890G,H have 30 second between trial purge time.

Other components needed to complete the system (order sep-arately):—VR845, VR854, VR8540, V845, V854, VR8205 or VR8305 Combi-

nation Gas Control, or any dual valve rated 1.0A or less.—24V Transformer.—24V Thermostat.—Hot surface igniter: Norton Model 201 or equivalent.—Q354 Flame Sensor for all D and H models.—High temperature limit controller.

APPROVALS:American Gas Association Design Certified.Canadian Gas Association Design Certified.Underwriters Laboratories Inc. Component Recognized.

TEMPERATURE RATINGS:Ambient: –40 F to +175 F (–40 C to +79 C).

FLAME FAILURE RESPONSE TIME: 2 seconds maximum with2.5 µA flame signal.

ELECTRICAL RATINGS:Power Supply: Requires two power supply connections: 24 and

120 Vac, 50/60 Hz.Current: 2.2A maximum at 24 Vac; 5.0A maximum at 120 Vac.Valve Contacts: 2.0A maximum at 24 Vac.Igniter Contacts: 5.0A maximum at 120 Vac.

WIRING CONNECTIONS:24 Vac—3/16 in. male quick-connects.120 Vac—1/4 in. male quick-connects.Sense Terminals (S89D,H; S890H only)—1/4 in. male quick-

connects.IGNITER WARMUP PERIOD: 34 seconds, nominal.THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus gas con-

trol current.

Order Number Application Lockout TimingS89C1087 For use in hot surface ignition systems to control hot surface igniter and flow of gas 6 sec.

S89C1095in appliances; provides single trial for ignition.

15 sec.

S89C1103 4 sec.

S89D1002 For use in hot surface ignition systems to control hot surface igniter and flow of gas 6 sec.in appliances; provides single trial for ignition; requires separate flame sensor.

S89G1005 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.

S89G1013in appliances; provides three trials for ignition. Not for use in atmospheric burnersystems. 6 sec.

S89G1021 11 sec.

S89H1003 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.

S89H1011in appliances; provides three trials for ignition; requires separate flame sensor. Notfor use in atmospheric burner systems. 6 sec.

S890G1003 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.

S890G1011in appliances; provides three trials for ignition. Use in systems with combinationigniter-sensor where a prepurge cycle is desired. Includes 30 seconds 6 sec.

S890G1029 minimum/37 seconds maximum (34 seconds nominal) prepurge. 11 sec.

S890H1002

S890H1010

S890H1028

For use in hot surface ignition systems to control hot surface igniter and flow of gasin appliances; provides three trials for ignition; requires separate flame sensor.Use in systems where prepurge cycle is desired. Includes 30 secondsminimum/37 seconds maximum (34 seconds nominal) prepurge.

4 sec.

6 sec.

11 sec.

S89J1008 For use in hot surface ignition systems to control hot surface igniter and flow of gas 6 sec.in appliances; provides single trial for ignition. Use in systems with combinationigniter-sensor. Provides 4 second maximum ignition activation period.

S89J1016 For use in hot surface ignition systems to control hot surface igniter and flow of gas 4 sec.in appliances; provides single trial for ignition. Use in systems with combinationigniter-sensor. Provides 2 second maximum ignition activation period. Includesplug for vent damper.

Page 55: Programador 7800 Series RM Completa

Gas Burner Controls—lcmition Controls

S89E,F Direct Spark Ignition ModulesProvide electronic control of directspark ignition systems, with externalspark transformers, used on gas-firedfurnaces, boilers, conversion burnersand other heating appliances.

Control ignition sequence and gascontrol operation in direct spark ignitionsystems.Control separate 120 Vac spark gener-ator that provides high voltage potentialfor main burner ignition.Lockout after one trial for ignition if main burner fails to ignite.Reset from thermostat after lockout.Use separate electrodes for spark ignition and flame sensing.Use any 24 Vac combination gas control designed for direct sparkapplications and rated at 2.0A or less.

Other components needed for a complete DSI system (orderseparately):—120 Vac spark generator with 1.5A or less current draw.—Q347 Spark Igniter.—Q354 Flame Sensor.

—VR8205 or VR8305 Combination Gas Control, or any 24 Vac dualvalve rated at 2.0A or less and designed for DSI applications.

APPROVALS:American Gas Association Design Certified.Canadian Gas Association Design Certified.Underwriters Laboratories Inc. Component Recognized.

TEMPERATURE RATINGS:Ambient: –40 F to +175 F (–40 C to +79 C).

FLAME FAILURE RESPONSE TIME: 2 seconds maximum.ELECTRICAL RATINGS:

Power Supply: Requires two power supply connections: 24 and120 Vac, 50/60 Hz.

Current: 2.2A maximum at 24 Vac; 1.5A maximum at 120 Vac.Valve Contacts: 2.0A maximum at 24 Vac.Spark Generator Relay Contacts: 1.5A at 120 Vac, 50/60 Hz.

ELECTRICAL CONNECTIONS:24 Vac—1/4 in. male quick-connects.120 Vac—12 in. (305 mm) color-coded leadwires.

THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus gas con-trol current.

OrderNumber

LookoutTiming Application Use With

S89E1058

S89E1066a

S89E1074

4 sec.4 sec.

11 sec.

For use in direct spark ignition systems on gas-firedatmospheric and power burners; provides safe startcheck before ignition.

S89F1098 4 sec. For use in direct spark ignition systems on gas-fired

S89F1106 aatmospheric and power-burners; provides safe start

4 sec. check and 30 second purge period prior to ignition.a Labels applied upside down for inverted mounting.

S87 Direct Spark Ignition ModulesProvide electronic control of direct sparkignition systems used on gas firedfurnaces, boilers, and other heatingappliances.

● Control ignition sequence and gas con-trol operation.

● Generate high voltage potential for mainburner ignition.

● Lockout after one trial for ignition if mainburner fails to ignite.

● Reset from thermostat after lockout.● Use modules (except S87C) with any combination gas control

designed for direct spark applications and rated at 2.0A or less.

Other components needed for a complete DSI system (order sep-arately):—Q347 Spark Igniter.—Q354 Flame Sensor (S87C,D,K systems only).—VR8205 or VR8305 Combination Gas Control, or any 24 Vac dual

valve rated at 2.0A or less and designed for DSI applications;S87C requires a Honeywell combination gas control designed forDSI applications.

VR8205 or VR8305 Combination Gas Con-trol, or any dual valve rated 2.0A or less forDSI applications.

—24 Vac thermostat.—High limit temperature controller.—24V transformer.

APPROVALS:American Gas Association Design Certified.Canadian Gas Association Design Certified.Underwriters Laboratories Inc. Component Recognized.

TEMPERATURE RATINGS:Ambient: –40 F to +175 F (–40 C to +79 C).

FLAME FAILURE RESPONSE TIME: 0.8 sec. max.ELECTRICAL RATINGS:

Power Supply: 24 Vac, 60 Hz.Current: At 24 Vac input 2.2A maximum.Contacts: Valve (S87B,D,J,K)—2.0A at 24 Vac.Contacts: Alarm (S87B,D)—0.5A maximum at 24 Vac.

ELECTRICAL CONNECTIONS: 1/4 in. male quick-connects for sys-tem; 1/4 in. diameter stud base for ignition cable.

THERMOSTAT HEAT ANTICIPATOR SETTING: 0.2A plus gas con-trol current.

Page 56: Programador 7800 Series RM Completa

Gas Burner Controls—Ignition Controls

S87 continued

Order Number Lockout Time Application

S87B1008 6 sec. Uses a single electrode for spark ignition and

S87B1016 11 sec.flame sensing. Includes optional alarm output.

S87B1024 21 sec.

S87B1065 4 sec.

S87C1006 6 sec.

S87C1014 11 sec.

S87C1022 4 sec.

Uses separate electrodes for spark ignitionand flame sensing. For use only with Honey-well gas controls designed for DSI application.For direct replacement of S825C.

S87C1030 21 sec.

S87D1004S87D1012S87D1020

6 sec.11 sec.4 sec.

Uses separate electrodes for spark ignitionand flame sensing. Includes optional alarmoutput. For direct replacement of S825C,D.

S87D1038 21 sec.

S87J1000 4 sec. Uses a single electrode for spark ignition and

S87J1018 6 sec.flame sensing. Includes a 30 second (mini-mum) delay for use with system prepurge.

S87J1026 11 sec.

S87J1034 21 sec.

S87K1008 4 sec. Uses separate electrodes for spark ignition

S87K1016 6 sec.and flame sensing. Includes a 30 second (mini-mum) delay for use with system prepurge.

S87K1024 11 sec.

S87K1032 21 sec.

Q345A Igniter-SensorNonprimary-aerated combination pilot burn-er and igniter. Used with the S86, S860,S8610 or S8670 in intermittent pilot systems.

● Includes pilot burner with bracket, ceramic-insulated Kanthal flame rod/spark igniter,and ground strap.

TEMPERATURE RATINGS:At electrode tip—1775 F (968 C) max.At ceramic insulator—1250 F (677 C) max.

OrderNumber

TipStyle

Typeof Gas

MountingBracket Includes

Mounting dimensions in in. (mm) and bracket type for Q345A.

*TRADELINE models.

*Q345A1305

*Q345A1313

*Q345A1321

Use WithQ347B Spark Igniter.

Q347A Spark Igniter and Q354AFlame Sensor.

Q347A Spark Igniter and Q354AFlame Sensor.

Q347B Spark Igniter.

Q347A Spark Igniter and Q354AFlame Sensor.

Nat.

Nat.

Nat.

B

B

B

1/4 in. ccinlet fittingand mountingadaptor.

Page 57: Programador 7800 Series RM Completa

Gas Burner Controls—Ignition Controls

Q347A Spark IgniterProduces spark for direct ignition of mainburner.

● Includes inner Kanthal electrode with ce-ramic insulator, bracket and Kanthalground strap.

● Use with S87C,D,K; S89E, F and Q354A.

TEMPERATURE RATINGS:

OrderNumber

Ground StrapOrientation Electrode Lengtha

At electrode tip—1775 F (968 C) max.At ceramic insulator—1250 F (677 C) max.

SPARK GAP: 5/32 in. (4 mm).

ELECTRICAL CONNECTIONS: 1/4 in. diameter stud for ignitioncable.

MOUNTING: One 3/16 in. (5 mm) slot, three 3/16 in. (5 mm) untappedscrew holes.

Q347A1004 Standard 2-1/32 in. (52 mm)

Q347A1012 90 degree right angle 2-1/32 in. (52 mm)a Bracket to tip.

Q354A Flame Rectification SensorDetects the presence of a main ELECTRICAL CONNECTIONS: One 1/4 in. (6 mm) quick-connectburner flame. terminal.

MOUNTING: One 3/16 in. (5 mm) slot, three 3/16 in. (5 mm) untapped● Includes Kanthal rod supported screw holes.

by ceramic insulator and mount-ing bracket.

● Use with S825, S87C,D,K orS89E,F.

TEMPERATURE RATINGS:At electrode tip—1775 F (968 C) max.

Flame Rod Length

Order Number in. mm

Q354A1000Q354A1018

2.5 641526

At ceramic insulator—1250 F (677 C) max.

Ignition System Cables

Order Number Description Use With

392125—1 25 in. (635 mm) ignition cable; right angle boot/terminal at igniter end, straight S86 Family; S87 Family.boot/terminaI at module end.

392125—2 36 in. (914 mm) ignition cable; right angle boot/terminal at igniter end, straight boot/terminal at module end.

392437—5 36 in. (914 mm) high temperature ignition cable; right angle terminal at igniter end,straight boot/terminal at module end.

393044 30 in. (762 mm) wiring harness; with 1/4 in. quick-connect terminals. S8600 Family.

394800-30 30 in. (762 mm) ignition cable; 90 degree boot on igniter end.

394803-2 36 in. cable with high temperature boot 750 F (400 C) on igniter end.

394801-30 30 in. (762 mm) ignition cable; straight boot on igniter end.

4074EPM Ignition cable adapter; connects S8600 family of ignition modules to existing cablesfor S86 systems.