profibox pib1000 & pib1001home.betalasermike.com/ftp/ls/man/1556-0122.pdf · lasermike...
TRANSCRIPT
Manual Part Number: MAN/E1556-0122 • Revision 8 • © Copyright May 2009
www.betalasermike.com
PROFIBOX PIB1000 & PIB1001
INSTRUCTION HANDBOOK - installation, setup, technical reference -
Beta LaserMike Inc. 8001 Technology Blvd. Dayton, OH 45424
USA
Beta LaserMike Limited Unit 3 First Avenue
Globe Park Marlow Buckinghamshire
SL7 1YA UK
Beta LaserMike Asia Unit 101, 102 & 201 XinAn Plaza, Building 13 No. 99 TianZhou Road
Shanghai, 200233 China
Instruction handbook - Profibox
MAN/E1556-0122 Page 2 of 52 Revision 8 (May 2009)
Contents
Proprietary Information .................................................................................................. 3
European Commission Requirements ........................................................................... 4
Declaration of Conformity .............................................................................................. 5
Safety Information .......................................................................................................... 6 Intended Use ............................................................................................................... 6
Introduction ..................................................................................................................... 6
Mechanical Installation ................................................................................................... 8 PIB1000 Mechanical Installation ................................................................................... 8 PIB1001 Mechanical Installation ..................................................................................13
Electrical Installation .....................................................................................................16 PIB1000 Connections and Gland termination ..............................................................16 PIB1001 Connections and Gland termination ..............................................................18 Earthing (PIB1000 / 1001) ...........................................................................................19 PIB1001 Wiring Diagrams ...........................................................................................20 Gauge Connectors (PIB1000 / PIB1001) .....................................................................22
GSD Software Installation..............................................................................................22
Configuration .................................................................................................................23 RS232 Configuration ...................................................................................................23 Configuration via DP Master ........................................................................................24
Common Status Codes ..................................................................................................25
General Profibus Communication .................................................................................26
General RS232 Communication with Gauges ...............................................................26
Data Format and Units ...................................................................................................27
Input Data .......................................................................................................................28
Output Data ....................................................................................................................28
Gauge Parameters .........................................................................................................30 CS Centerscan Gauges ..............................................................................................33 LD / MLD / AS3000 / AS5000 Diameter Gauges .........................................................35 LD Diameter Gauges in HELIX Mode ..........................................................................37 LN Fault Gauges .........................................................................................................40 LS LaserSpeed Gauges ..............................................................................................43 SI900 Sparktesters......................................................................................................45 Preheater MCS ...........................................................................................................46
Maintenance ...................................................................................................................47
Troubleshooting / LED Signals .....................................................................................48
Servicing and Returning your Equipment ....................................................................49
Disposal / Recycling ......................................................................................................50
Specification ..................................................................................................................51
Index ...............................................................................................................................52
Instruction handbook - Profibox
Proprietary Information
MAN/E1556-0122 Page 3 of 52 Revision 8 (May 2009)
Proprietary Information
Manufacturer/Distributor Beta LaserMike Inc.,8001 Technology Blvd., Dayton, OH 45424, USA.
Beta LaserMike Limited, Unit 3, First Avenue, Globe Park, Marlow, Buckinghamshire, SL7 1YA, U.K.
About This Manual
Comments or suggestions for possible improvements to the manual are appreciated. Please email
us at [email protected].
This manual contains descriptions, drawings, and specifications for a Beta LaserMike product. Equipment or
products made prior to or subsequent to the publication date of this manual may have parts, features,
options, or configurations that are not covered by this manual. Specifications contained herein are subject to
change by Beta LaserMike without prior notice. Beta LaserMike is not responsible for errors or omissions
that may be contained herein or for incidental or consequential damages in connection with the furnishing or
use of this information.
The information contained in this manual is the property of Beta LaserMike. The information disclosed in this
document is furnished in confidence and upon the condition that individual and corporate intellectual rights,
whether patented or not, will be respected. If this document is supplied on removable media (e.g. CD), an
electronic copy (stored on-site) and one printout is permitted. If this document is supplied in printed form, no
part of this document may be reproduced or scanned without the prior written consent of Beta LaserMike.
This document may not be distributed or circulated to third parties.
Limited Warranty Beta LaserMike will correct by repair, or at Beta LaserMike„s option, by replacement, F.O.B Beta
LaserMike‟s plant, any defect in workmanship or material in any equipment manufactured by Beta
LaserMike which appears under normal and proper use within twelve months from the date of shipment
(eighteen months for OEM‟s), provided Beta LaserMike is given reasonable opportunity to inspect the
alleged defective equipment at the place of its use and under conditions of its use.
EXCLUSIONS: This warranty does not cover products which have been modified, altered, or repaired by
any other party than Beta LaserMike or its authorized agents. Furthermore, any product which has been, or
is suspected of being damaged as a result of negligence, misuse, incorrect handling, servicing, or
maintenance; or has been damaged as a result of excessive current/voltage or temperature; or has had its
serial number(s), any other markings, or parts thereof altered, defaced, or removed will also be excluded
from this warranty.
WARRANTY SERVICE AT CUSTOMER SITE: Warranty service performed at the customer‟s facility will be
free of charge for parts and labor; however, the customer will be liable for transportation and living expenses
of personnel dispatched to effect such repair. A purchase order or other written confirmation of the
acceptance of these charges, signed by an authorized individual, will be required prior to commencement of
repairs. Additional charges may be assessed the customer if: 1) The equipment is not made available on a
timely basis, 2) The equipment is found to be without fault, and/or 3) It is determined the equipment is not
under warranty, whether by expiration of the warranty or any act which voids the warranty.
OTHER THAN AS SET FORTH HEREIN, BETA LASERMIKE MAKES NO WARRANTIES, EXPRESSED
OR IMPLIED, OF MERCHANTABILITY AS TO THE EQUIPMENT MANUFACTURED BY IT, AND THERE
ARE NO EXPRESSED OR IMPLIED WARRANTIES WHICH EXTEND BEYOND THE DESCRIPTION ON
THE FACE THEREOF. Beta LaserMike‟s obligation to correct defects in such equipment by repair or
replacement in accordance with the foregoing provisions is in lieu of any other warranties, expressed or
implied, and in no event shall Beta LaserMike be liable for incidental or consequential damages. No service
of Beta LaserMike‟s equipment is permitted during the warranty period without the specific written consent
of Beta LaserMike.
Note: For Unpacking/
Returns and Servicing – see section
“Servicing and Returning your Equipment”
at the back of
this manual.
Instruction handbook - Profibox
European Commission Requirements
MAN/E1556-0122 Page 4 of 52 Revision 8 (May 2009)
European Commission Requirements
This equipment is intended for use in a heavy industrial environment. The
equipment generates, uses and can radiate radio frequency energy and, if not
installed and used in accordance with the instructions, may cause harmful
interference to other equipment. There is no guarantee that interference will not
occur in a particular installation. If this equipment does cause harmful interference
to other equipment the user is encouraged to try to correct the interference by one
or more of the following measures:
Re-orientate or relocate the equipment.
Increase the separation between the pieces of equipment.
Connect the pieces of equipment on separate mains circuits.
Ensure that the relevant items of equipment are properly and securely earthed/grounded to a common earth point using adequately sized cable or other means of connection.
Where supplied or specified, shielded interconnection cables must be employed
with this equipment to ensure compliance with the pertinent RF limits. Changes or
modifications not expressly approved by the company could void the user‟s
authority to operate the equipment.
This product has been rigorously tested to comply with the European EMC
Directive (Electromagnetic Compatibility). With regard to this, Beta LaserMike
recommends that any non-Beta LaserMike peripheral equipment is CE marked for
the Heavy Industrial environment (EN50082-2). Beta LaserMike also recommends
that any cables not supplied by Beta LaserMike, but used for powering Beta
LaserMike equipment, be built using good EMC practices (i.e. cables with braided
shield, and connectors with 360 termination of the braid to a metal/metalised shell
connector at both ends). If you have any questions regarding this, contact the Beta
LaserMike Service Department.
Instruction handbook - Profibox
Declaration of Conformity
MAN/E1556-0122 Page 5 of 52 Revision 8 (May 2009)
Declaration of Conformity
Instruction handbook - Profibox
Safety Information
MAN/E1556-0122 Page 6 of 52 Revision 8 (May 2009)
Safety Information
Electrical Installation must be carried out by a person suitably qualified for the country of installation.
This equipment must be earthed
Relays and associated wiring are rated for SELV levels i.e. 60 Vdc and 30 vac rms. These levels must not be exceeded.
Intended Use
This equipment is intended for use on a production line for communication
between an individual Beta LaserMike (BLM) gauge and the industry Profibus
network, and thereafter to a master production control computer system or plc.
If the equipment is not used in a manner specified by the manufacturer, the
protection provided by the equipment may be impaired.
Introduction
Profibus is a Process Field Bus industry standard communications network. The
Profiboxes (described in this manual) are modular interface devices for
communication between an individual Beta LaserMike (BLM) gauge and the
standard Profibus network, and thereafter to a master production control
computer system or plc.
The Profibox continuously monitors and controls the connected gauge for which
it has been configured. The most recent data from the gauge is instantaneously
made available to other computers on the Profibus network using the DP
protocol. This protocol allows a clean interface between gauge and computer,
and removes the overhead and complexity of gauge management from
computers requesting data or making setpoint changes. In this way the Profibox
forms a compact and modular front-end processor for BLM gauges.
The precise nature of the data transferred through the Profibox will vary
according to the type of gauge and customer requirements.
All Profiboxes are shipped with the network address 126 to allow for
configuration via the network.
The type of the BLM gauge to be connected to the Profibox is defined at time of
ordering. Prior to delivery the Profibox is tested with the relevant BLM Gauge
Series.
Instruction handbook - Profibox
Introduction
MAN/E1556-0122 Page 7 of 52 Revision 8 (May 2009)
A BLM Gauge Series is defined according to commonality in function. More than one gauge type may exist within a particular series:
BLM Gauge types Profibus Part No. Description
Serial communications (PIB1000)
LD, CS and LN GA1556-0050-1/A LD Diameter gauges, Centerscan and Lump and Neck gauges
SI900RC GA1556-0050-2/A Sparktester indicator
LaserSpeed GA1556-0050-5/A LaserSpeed Gauge
Analog (PIB1001)
MCS120/190/280 (C580) GA1556-0058-1/A Preheater
S 1525/2550/25100/40100/50150 -I GA1556-0058-2/A Intelligent Gaugehead Sparktester series
HFS GA1556-0058-3/A High Frequency Sparktester
Profibox Features
Integration of Profibus network to BLM range of instruments. Connects to serial communications gauges (PIB1000) or analog gauges (PIB1001). BLM Digital Interface PIB1001 option. Configurable serial ports (PIB1000). Automatic reconfiguration on serial gauge change (between gauges of same series). Modular design for cost effectiveness and future expansion. Well-defined interface language for speedy inclusion of new gauges and configurations. Operable in harsh industrial environments - having extended temperature range capability. High speed data transfer rate of up to 12 Mbits/sec across the network. Autodetect network data rate. Remote address change capability.
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 8 of 52 Revision 8 (May 2009)
Mechanical Installation
PIB1000 Mechanical Installation
PIB1000 Dimensions - mm (inches)
160 (6.29)
100 (3.93)
22 (0.86)
22 (0.86)
60 (2.36)
160 (6.29)
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 9 of 52 Revision 8 (May 2009)
Preparing the PIB1000 for Installation
Remove the PIB1000 lid to expose fixing holes:
Fixing hole centres are 145 x 63mm (5.7 x 2.48in)
If the Profibox is the last one on the line, the OUT cable will not be needed. Hole blanking plugs should then be fitted to ensure IP rating.
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 10 of 52 Revision 8 (May 2009)
Securing PIB1000 next to an LD or LN
As the above gauges commonly use a mechanical height stand (light duty or
standard), it is recommended that the PIB1000 is secured to the stem of this stand.
1. See heading Preparing PIB1000 for Installation above. 2. Feed 4 M4x20mm (0.79in long) bolts through Profibus fixing holes and
through adapter plate (see illustration below).
Clamping Handle Fixing Clamp Height stand column Adapter plate
3. Determine optimal position of Profibox on height stand column, taking into account cable length to gauge and tighten bolts.
4. Attach interface plate to fixing bracket and tighten with clamping handle. 5. Secure Profibus lid tightly with the 4 screws -this will ensure specified IP rating.
100 (
3.9
4)
143 (
5.6
3)
184 (
7.2
4)
+ 1
0
160 (6.30)
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 11 of 52 Revision 8 (May 2009)
Securing PIB1000 next to the Centerscan (CS)
The PIB1000 should be secured to the Centerscan height stand using the L-
shaped fixing bracket as illustrated. See heading "Preparing PIB1000 for
Installation" above. Use 4 M4 (Hank Bush) bolts. Dimensions are in mm (in).
Height stand
L-shaped Fixing
Bracket
Side View
Top View
Height stand interface plate
Centerscan
Profibox
149 (5.87) 156 (6.14)
126 (
4.9
6)
148 (5.83)
8 (0.31)
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 12 of 52 Revision 8 (May 2009)
Securing PIB1000 next to a SI900RC (Sparktester) or LaserSpeed
The PIB1000 can be fixed to any secure metalwork next to gauge using the 4
fixing holes provided.
1. See heading Preparing the PIB1000 for installation. 2. Locate secure metalwork for securing gauge. 3. Use schematic drawing below to determine drilling points on metalwork. 4. Drill 4 holes (for 4 M4 CapHeads with M4 plain washer and M4 Nylock screw) 5. Secure Profibox to well-earthed metalwork (it is recommended that the 3 cable
glands face downwards to reduce strain on the cables). Note: the PIB1000 should not be located too close to the sparktester as this may result in interference.
6. Before refitting the Profibus lid refer to Electrical Installation.
Bottom view of Profibox
Fixing hole centres: 63mm (2.48 in)
Fixing hole centres: 145 mm (5.7 in)
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 13 of 52 Revision 8 (May 2009)
PIB1001 Mechanical Installation
PIB1001 Dimensions - mm (inches)
22 (0.86) 160(6.29) 90 (3.54) 260 (10.23)
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 14 of 52 Revision 8 (May 2009)
Securing PIB1001 to the Preheater (C580)
1. Remove 4 hole blanking plugs from the predrilled holes in side of Preheater. 2. Remove the PIB1001 lid to expose fixing holes which are located similarly to
the PIB1000 (for picture please refer to Preparing the PIB1000 for installation). The fixing centres are 240 x 110 mm (9.44 x 43.3in); O.D = 7 mm (0.27in).
3. Use the 4 mounting bolts to secure the Profibox onto the side of the Preheater. 4. Remove dome plug and connect the analog cable as shown. 5. Before refitting Profibox lid refer to Electrical Installation.
Profibox
Mounting bolt
(4 in total)
Preheater side
Position of access hole and orientation of
Profiboxes varies on different Preheater
models. Remove dome plug prior to fitting cable
gland.
4 holes (blind fasteners)
Cable gland
Analog Cable (refer also to Electrical
Installation)
Instruction handbook - Profibox
Mechanical Installation
MAN/E1556-0122 Page 15 of 52 Revision 8 (May 2009)
Securing PIB1001 to the Sparktester
The following applies to the Sparktester intelligent gaugehead and to the HFS series sparktesters. For SI900 Sparktesters see relevant heading above.
1. Remove the 4 hole blanking plugs from the predrilled holes on Sparktester rear panel.
2. Remove the PIB1001 lid to expose fixing holes which are located similarly to the PIB1000 (for picture please refer to Preparing the PIB1000 for installation). The fixing centres are 240 x 110 mm (9.44 x 43.3in); O.D = 7 mm (0.27in).
3. Use the 4 mounting bolts to secure the Profibox onto the rear panel of the Sparktester.
4. Before refitting Profibox lid refer to Electrical Installation.
Sparktester rear access panel
Mounting bolt (4 in total)
4 holes
(blind fasteners) Profibox
Cable gland (for connection see
Electrical installation)
Instruction handbook - Profibox
Electrical Installation
MAN/E1556-0122 Page 16 of 52 Revision 8 (May 2009)
Electrical Installation
Electrical installations must be carried out by a suitable technician for the country of installation.
This equipment must be earthed.
Relays and associated wiring in the PIB1001 are rated for SELV levels i.e. 60 Vdc and 30 Vac rms. These levels must not be exceeded.
Connectors must be correctly terminated. Inadequate termination can degrade equipment performance and may lead to equipment damage.
PIB1000 Connections and Gland termination
1. Use screened i.e. shielded cable with correct specification and determine required length (in particular the RS232 cable). See fig 2 for cable specification and connections.
2. Unscrew gland cover nut and remove washers. 3. Insert cable through gland cover nut and rubber insert over the cable. 4. Insert cable through washer with largest hole (8.4mm, O.D15mm). 5. Remove 4 screws from top of Profibox. 6. Touch Profibox casing to discharge any static electricity. 7. Feed cable through cable connector to determine length of cores to expose. 8. Remove sheath. 9. Push back braid/foil and remove excess - leaving about 1 cm (2.54 in) of braid. 10. Insert washer with smaller hole (7.6mm, OD15mm) over cores.
Fig.1
Washer with larger hole
Braid Washer with smaller hole Sheath Cores
Instruction handbook - Profibox
Electrical Installation
MAN/E1556-0122 Page 17 of 52 Revision 8 (May 2009)
11. Clamp braid between washers and cut off any excess braid and foil. 12. Insert cores through hole and check required length of cores.
(The cores leading to the connector should be as short as possible.) 13. Screw on the gland cover nut and tighten. 14. Remove excess plastic and drawstring/drawwire 15. Strip cores to expose about 5mm (0.2 in) of wire. 16. Connect correct core to appropriate screw terminal..
If the Profibox is connected to the last gauge on the production line, then do not connect the 'OUT' gland. The terminating switch should in this case be in the ON position.
17. Cut off any superfluous cores, which will not be connected.
Fig. 2
18. When all connections have been correctly done, ensure all gland cover nuts are
tightly fastened to ensure IP65 protection. 19. Fit on lid and fix tightly with the 4 screws to provide protection to IP65.
24 Vdc Power Cable 16/0.2 2 core screened O.D. = 5 - 7 mm (0.23 - 0.27in)
Profibus DP Cable
O.D. = 6 - 8 mm
RS232 cable 7/0.2, 6 core screened O.D. = 5 - 7 mm (0.23 - 0.27in)
Terminating switch
OUT IN
Instruction handbook - Profibox
Electrical Installation
MAN/E1556-0122 Page 18 of 52 Revision 8 (May 2009)
PIB1001 Connections and Gland termination
Apart from connecting the analog/digital input (see below), the connections and
gland termination of PIB1001 glands does not, in principle, differ from the 360
Termination of the PIB1000 (see PIB1000 - Electrical Installation).
Profibus DP Cable O.D. = 6-8mm [0.24-0.31in]
Note: either side can
be used as IN or OUT
Terminating switch
24 vdc Power Cable 16/0.2 2 core screened O.D. = 5 - 7 mm [0.23-0.27in]
See below for Earthing
details. Analog/Digital Cable. 7/0.2
12 core screened.
Instruction handbook - Profibox
Electrical Installation
MAN/E1556-0122 Page 19 of 52 Revision 8 (May 2009)
Earthing (PIB1000 / 1001)
This equipment must be connected to a suitable earth. Use a 2.5 mm2 (0.1
inch2) cable. The cable should be as short as possible and less than 3 m (10
feet) in length. This should then be attached to a good earth or grounding box.
An example of a connected Profibox Earth stud is shown below.
Instruction handbook - Profibox
Electrical Installation
MAN/E1556-0122 Page 20 of 52 Revision 8 (May 2009)
PIB1001 Wiring Diagrams
The following diagrams are not normally essential for installation (with the
exception of the Preheater wiring diagram) but serve as wiring information in
case the cables are modified on site at a later stage.
PIB1001 to C580 Preheater Controller
PIB1001 C580 PIN # CONTACT1 5 CONTACT1 6
CONTACT2 7 CONTACT2 8 24V . NC DIGITAL1+ 11 DIGITAL1 - 10
9 RETURN . NC 14 DIGITAL2 - . NC DIGITAL2+ . NC ANALOG O/P 1 1 ANALOG RTN 2
ANALOG I/P - 16 ANALOG I/P + 15
Instruction handbook - Profibox
Electrical Installation
MAN/E1556-0122 Page 21 of 52 Revision 8 (May 2009)
PIB1001 to Sparktester Gaugehead
PIB1001 Sparktester Gaugehead CONTACT1 . NC CONTACT1 . NC Pin
CONTACT2 J CONTACT2 24V DIGITAL1 + R DIGITAL1 - RETURN D
N DIGITAL2 - DIGITAL2 + H ANALOG O/P 1 A ANALOG RTN B ANALOG I/P - F ANALOG I/P + E
Terminate screen
in cable gland. 14-19F connector CA 5100-0343
RED
GREEN
YELLOW
BLACK
BROWN
ORANGE
VIOLET
WHITE
BLUE
Instruction handbook - Profibox
GSD Software Installation
MAN/E1556-0122 Page 22 of 52 Revision 8 (May 2009)
Gauge Connectors (PIB1000 / PIB1001)
PIB1000 (RS232 cable)
CE compliant version
Older version
LD CON3 SKT2
CS SK1 SK1
LN CON3 SK1
LaserSpeed and SI900RC See relevant manual
PIB1001 (Analog-digital cable)
MCS (preheater) For these gauges please refer to documentation which came with the gauges.
S-series sparktester (Intelligent Gaugehead)
HFS series
GSD Software Installation
Copy file specified on disk (provided by Beta LaserMike) to directory specified in
Profibus System Documentation.
Instruction handbook - Profibox
Configuration
MAN/E1556-0122 Page 23 of 52 Revision 8 (May 2009)
Configuration
Two levels of configuration are supported: via RS232 or via Profibus DP.
RS232 Configuration
RS232 configuration is available through the RS232 port at 9600,7,n,2, no hand
shaking. Only TxD, RxD and GND are required. This facility is only available
after powering up the Profibox and before a DP master first establishes a
connection to the Profibox. It is recommended that the Profibus network be
disconnected from the Profibox prior to restarting the Profibox to ensure that the
DP master cannot establish a connection.
The RS232 configuration provides facilities for setting:
Profibus DP „Slave Address‟
Profibus DP „No Address Change‟
Analogue IO calibration (if fitted)
The RS232 configuration protocol is always initiated by the terminal emulator or
setup utility. The Profibox will only transmit characters in response to requests:
Request Profibox Response Description
?X1/1<CR> *X1/1=<n><CRLF> Query DP slave address
=X1/1=<N><CR> *X1/1=<N><CRLF> Set DP slave address to N (1..126)
?X1/2<CR> *X1/2=<n><CRLF> Query DP no address change
=X1/2=<N><CR> *X1/2=<N><CRLF> Set DP no address change (0..1). 0=allow set slave address telegram 1=disable set slave address telegram
?X1/3<CR> *X1/3=<n><CRLF> Query AOUT1 zero volt calibration point (response only if fitted)
?X1/4<CR> *X1/4=<n><CRLF> Query AOUT1 +10 volt calibration point (response only if fitted)
?X1/5<CR> *X1/5=<n><CRLF> Query AOUT2 zero volt calibration point (response only if fitted)
?X1/6<CR> *X1/6=<n><CRLF> Query AOUT2 +10 volt calibration point (response only if fitted)
?X1/7<CR> *X1/7=<n><CRLF> Query AIN1 zero volt calibration point (response only if fitted)
?X1/8<CR> *X1/8=<n><CRLF> Query AIN1 +10 volt calibration point (response only if fitted)
The analogue calibration points are updated using a secure procedure that is
only available to Beta LaserMike engineers. It is not possible for users to
change the analogue calibration information.
The DP slave settings are stored to EEPROM immediately after being received
and validated by the Profibox. However, it is necessary to restart the Profibox
before the new settings will take effect.
Instruction handbook - Profibox
Configuration
MAN/E1556-0122 Page 24 of 52 Revision 8 (May 2009)
Configuration via DP Master
The Profibox must be dynamically configured by the DP master using the
parameterisation and configuration telegrams. It is possible for the master to
change the configuration information between DP sessions without needing to
restart the Profibox.
The DP parameterisation telegram contains the information for determining:
The baud rate to use for communication with an RS232 gauge
The FG gauge version
Selection between RS232 or Analogue for Sparktester profile type
The Centigrade / Fahrenheit jumper settings for the Pre-
heater/Rotatemp
A flag to indicate if DP profile parameters are to be stored to
EEPROM (if this is disabled the DP master must update all DP
parameters after the start of every DP session).
The kV generated by an analogue Sparktester for a +10V set-point *
LD emulation selection to allow the LD profile to be used for normal
LD gauges, IntelliPak gauges, LI indicators, WI indicators, or
AS3000/AS5000 gauges.
The provided „SGDP332.GSD‟ file contains the necessary information to allow
the selection and entry of the above information using the point-and-click
facilities available in the Siemens “COM PROFIBUS” database creation utility.
The DP configuration telegram is used to select the profile / gauge type to be
used by the Profibox. Only a single profile / gauge type is allowed, and the
configuration information must be understood by the Profibox. Again, the
„SGDP332.GSD‟ contains the necessary information to allow the selection of
profile type using the point-and-click facilities available in the Siemens “COM
PROFIBUS” database creation utility.
If the Profibox does not have analogue facilities it will reject a configuration
request for the Preheater/Rotatemp profile, or the Sparktester profile if „DS:
Analogue Sparktester‟ was selected in the parameterisation.
* The EHT set point voltage for all HFS sparktesters is scaled 25kV = +10V.
Therefore the Profibus parameterisation should be set to "25kV for 10V", a preset
of 6000V will then give an output to the HFS of 2.4V which will set the EHT to
6kV.
Instruction handbook - Profibox
Common Status Codes
MAN/E1556-0122 Page 25 of 52 Revision 8 (May 2009)
Common Status Codes
Although each gauge type has a set of unique status codes, there are some
additional status codes that may be generated by the Profibox that are common
to all gauge types:
COMMON STATUS CODES
Mnemonic Code Description
GST_RS232_PROTO 32 The gauge is not responding to a specific cell poll request. Either an old or incompatible gauge has been connected by mistake.
GST_RS232_PARAM 33 The Profibox only performs simple parameter verification, and has accepted a parameter value that the gauge will not accept via RS232. The master control computer‟s „recipe‟ should be checked to make sure all presets, tolerances, etc are within the limits acceptable by the associated gauge.
GST_DATA_INVALID 34 Not all gauge data within the „inputs‟ is valid yet. Either the master hasn‟t set the units (and/or Centerscan measurement type), or the Profibox hasn‟t collected all the required input data from the gauge.
GST_WRONG_GAUGE_TYPE 35 The RS232 data stream produced by the gauge is not understood or is known to be from an incompatible gauge. See if the wrong gauge is connected or whether the baud rate is correct.
GST_NOT_CONNECTED 36 The gauge is disconnected or turned off. Ensure the gauge is connected to the correct port and the baud rate properly configured. It is also possible to get this error if an incompatible gauge type has been connected by mistake.
Instruction handbook - Profibox
General Profibus Communication
MAN/E1556-0122 Page 26 of 52 Revision 8 (May 2009)
General Profibus Communication
The Profibox supports freeze and sync requests. It is unlikely that using freeze
and sync will be of any real value to a DP master, but the facilities are provided
nevertheless.
The Profibox supports „Set Slave Address‟ telegrams. The „Slave Address‟ and
„No Address Change‟ information may also be configured via RS232 as
discussed in an earlier section.
After a communications timeout all connected machines (for example the
Centerscan, Capstan Preheater, Preheater and Sparktester) are stopped.
No additional diagnostic data is provided by the DP Profibox. All gauge status
information is provided within the normal input data.
General RS232 Communication with Gauges
Communication is always 7 data bits, no parity, 2 stop bits.
Prior to the first parameterisation/configuration, the Profibox responds to any
valid configuration/calibration requests received at 9600,7,n,2. After the first
parameterisation/configuration the Profibox changes to gauge control mode.
The Profibox remains in gauge control mode even if the DP connection is
closed or lost.
The baud rate to use when communicating with a gauge is specified as part of
the DP parameterisation process. The gauge must be correctly configured to
match the selected baud rate.
Only TxD, RxD and GND are required for connection to the gauge. An RTS
output is provided by the Profibox, but the use of this signal is not required as
the Profibox can process data faster than a gauge can supply it, even at 19200
baud. The Profibox does not monitor the CTS input, instead it only sends data
requests to an RS232 gauge at a carefully controlled rate.
Instruction handbook - Profibox
Data Format and Units
MAN/E1556-0122 Page 27 of 52 Revision 8 (May 2009)
Data Format and Units
All data is received and transmitted in network byte order. Multi-byte values are
ordered with the most significant byte lowest in memory, and the least
significant byte higher in memory.
Wherever possible values are represented using unsigned words, but some
values are represented using 32-bit IEEE floating point numbers. Unfortunately
this means that some parameter lists are a mix of word and floating point
representations.
Wherever possible values and parameters are specified in standard units:
Measurement Type Metric Imperial
Voltage volts volts
Current amps amps
Percent percent percent
Rotational speed revs/minute revs/minute
Frequency Hz Hz
Tension Newtons Newtons
Diameter metres inches
Eccentricity (linear) metres inches
Capacitance pF/metre pF/foot
Linear speed metres/minute feet/minute
Temperature degrees Centigrade degrees Fahrenheit
Instruction handbook - Profibox
Input Data
MAN/E1556-0122 Page 28 of 52 Revision 8 (May 2009)
Input Data
The input data is provided by the Profibox and passed to the DP master on
every data-exchange.
The length and meaning of the input data depends on the Profibox
configuration. The PKW header is always present, and is followed by the gauge
data for the configured profile.
Output Data
The output data is provided by the DP master and passed to the Profibox on
every data-exchange.
The length and meaning of the output data depends on the Profibox
configuration. The PKW header is always present, and is followed by the output
control word for the configured profile.
As with all data, the output control word is in network byte order. Some bits in
the output control word are common/reserved for all profile types. The following
table shows the common output control bits:
Mnemonic Bit Number
Description Applicable Profile Types
0 Reserved
OCF_START 1 Machine on/off CS, CPH, Analogue ST, Analogue PH,
OCF_ZERO 2 Zero fault counts impulse LN, ST
OCF_THREADING 3 Line threading - suppress gauge status
All except CPH
The output control word contains additional bits that apply to individual profile
types. Please refer to the profile descriptions for the meaning of these bits.
The OCF_START bit functions as described in the following table:
OCF_START Description
0 Analogue PH / RT / ST off. Manual on/off of RS232 machine possible.
Analogue RT / ST on. Analogue PH on pulse generated. Single „on‟ request sent to RS232 machine.
1 Analogue RT / ST on. Manual on/off of RS232 machine possible.
Analogue PH / RT / ST off. Several „off‟ requests sent to RS232 machine.
Instruction handbook - Profibox
Output Data
MAN/E1556-0122 Page 29 of 52 Revision 8 (May 2009)
Each machine has safety interlocks such that a machine cannot be turned on by
the Profibox if the lid is open etc. However, it is possible that a machine can be
started by the Profibox, as a result of a request from the DP master, if the
gauge interlocks are correct, and it is therefore very important to ensure
operators are clear of machines before issuing „on‟ requests from the DP
master.
The RS232 Spark Test Indicator does not provide facilities for remote starting or
stopping, but the corresponding DP profile defines the start bit because the
profile is shared by the Analogue Spark Tester.
If it is required to disable remote starting of an analogue machine, then the
wiring of the analogue machine must be arranged such that the machine is
started by means other than a Profibox relay.
The OCF_ZERO bit in the output control word uses impulses from the DP
master to reset fault counts for a DP profile:
OCF_ZERO Description
Analogue gauge: fault count reset. RS232 gauge: counter reset request sent
other No change, fault counting continues.
The OCF_THREADING bit in the output control word is used to suppress non-
fatal gauge errors whilst the line is being threaded. This facility is provided only
as a means of assisting the DP master in alarm handling. There is no
requirement to use the facility.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 30 of 52 Revision 8 (May 2009)
Gauge Parameters
The Profibox attempts to recover DP parameters from EEPROM each time it is
configured at the start of a DP session, but only if EEPROM storage was
enabled as part of the DP parameterisation.
Each parameter may only be recovered if a CCITT 32-bit CRC and the profile
type used at the time the parameter was stored are correct.
If the units parameter could not be recovered from EEPROM, then it will be
internally marked as „not valid‟. In this case the gauge status will remain as
SGDP_GST_DATA_INVALID because the Profibox does not know the type of
units to use for DP communication. The SGDP_GSF_PARAMS_OK flag will
also be reset.
Parameters that are sensitive to units selection cannot be recovered from
EEPROM if the units parameter was not recovered, or if the recovered units do
not match the units in use at the time the sensitive parameter was stored.
When writing to parameters, the DP master must update a gauge‟s UNITS
parameter first. If this is not done the Profibox will ignore write requests to
parameters that are sensitive to units, and the SGDP_GSF_PARAMS_OK flag
will remain reset. It is recommended that the DP master updates all write-
enabled parameters in ascending numerical order.
For simple control systems it is recommended that whenever the
SGDP_GSF_PARAMS_OK bit is clear then the DP master writes to all write-
enabled parameters in numeric order.
The gauge status is only set to a number lower than
SGDP_GST_DATA_INVALID when the units [and Centerscan measurement-
type] have been recovered or written by the master and the relevant input data
has been obtained from the RS232 gauge. Whenever the master writes the
units [or measurement type] the SGDP_GST_DATA_INVALID status will prevail
until new data has been obtained from the RS232 gauge using the new units.
The SGDP_GSF_PARAMS_OK status bit is zero until all parameters have been
recovered from EEPROM or the master has (re)written all parameters that are
write-enabled.
If a parameter has not been recovered from EEPROM or written by the master,
then the corresponding gauge value is regularly polled and stored to the
parameter, and can be read by the master if required. This also allows valid
data and units sensitive parameters to be read by the master after the master
has selected or changed the measurement units [and/or measurement type]. In
these circumstances the SGDP_GSF_PARAMS_OK bit will remain reset as not
all parameters have been written by the master.
When the master writes a parameter, and if the write is valid, the Profibox also
updates the corresponding gauge parameter. The Profibox continually monitors
the gauge's value, and if it differs from the value request by the master, then the
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 31 of 52 Revision 8 (May 2009)
Profibox re-writes the value to the gauge. Therefore, once the master has
written a parameter, the corresponding gauge parameter is kept at that value by
the Profibox using closed loop control.
It should also be noted that when a serial port gauge head type changes (e.g.
LD1040 to LD1080) then all parameters that may be affected by the gauge
head change are invalidated and the SGDP_GSF_PARAMS_OK flag will be
cleared.
Parameters are stored to EEPROM only after they have been written by the DP
master (and not subsequently altered for 30 seconds), and if EEPROM storage
is enabled as part of DP parameterisation
Parameters are updated/monitored using the parameter control headers in the
output/input data respectively. The header, in either direction, is referred to as
PKW. The first word within PKW is referred to as PKE and contains information
regarding request/response type and parameter number. The second and third
words contain the read/write parameter data or a response error code and are
referred to as PWE1 and PWE2 respectively.
PKW DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
PKE BASE+0
AK SPN PRM
PWE1 BASE+1
Parameter value MSW
PWE2 BASE+2
Parameter value LSW
AK Task/reply identifier, detailed in tables below SPN Spontaneous bit, reserved for future use. PRM Parameter number within profile position
Requests are issued by the DP master using the following AK request codes in
the PKW header within the „outputs‟ telegram:
AK task codes
(Master Slave) Description
0 No task. The DP master is making no request and the PKW interface is idle. The Profibox make no use of PRM and therefore this value may be zero.
1 Request to read a parameter value.
2 Request to write a word parameter.
3 Request to write a float parameter.
The DP master recognises the response to a request when PRM in the PKW
header within the input data matches that requested. The Profibox will respond
with the same PRM value, even if the PRM value was not valid.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 32 of 52 Revision 8 (May 2009)
Responses to requests are acknowledged by the Profibox using the following
AK response codes in the PKW header within the input data:
AK response codes
(Slave Master) Description
0 No reply. Issued in response to „no task‟.
1 Cannot complete task. An error code is provided in PWE2. PWE1 is zero. See subsequent table for a description of response error codes.
2 Response to a read or write request for a word parameter. The word parameter value (after the write operation) is contained in PWE2, and PWE1 is zero.
3 Response to a read or write request for a float parameter. The float parameter value (after the write operation) is contained in PWE1 and PWE2.
For an AK response code of 1, „task cannot be completed‟, the following error
codes are returned in PWE2:
AK error codes
Description
0 No error. Issued in response to „no task‟.
1 AK request code is invalid.
2 Reserved.
3 PRM does not specify a valid parameter number for the configured profile.
4 Cannot write parameter: it is read-only.
5 Cannot write parameter: the value provided by the master is outside of limits imposed by the Profibox.
6 Cannot write parameter: the data type (AK request code) is not compatible with the parameter.
7 Cannot write parameter: the parameter is sensitive to units selection and the master has not written to the units parameter.
8 Cannot read parameter, the Profibox has not yet received any valid value for the parameter from the DP master or the gauge.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 33 of 52 Revision 8 (May 2009)
CS Centerscan Gauges
OUTPUT CONTROL WORD
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 CA r r r r r r r r r r r TH r ST r
r Bit is reserved, and should be set to zero by DP master. TH If set the Profibox will convert gauge status codes 1 through 6 to code 0,
thereby suppressing non-fatal errors during threading. ST The Profibox sends a single start command to the Centerscan for a 0 to 1
transition of this bit, and several stop commands for a 1 to 0 transition. The state of this bit is ignored if a calibration is in progress, but will be recognised after calibration has completed or timed-out. The Centerscan may be started and stopped manually at any time.
CA The Profibox begins the Centerscan calibration process upon a 0 to 1 transition of this bit. Other states or transitions of this bit are ignored. The ST and CA bits are ignored during the calibration process. The Profibox imposes a 10-second time limit on the calibration cycle, and ends calibration mode if the gauge has not completed within this time. Please refer to Centerscan documentation for further details about calibrating a Centerscan gauge.
INPUT DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 0 0 0 0 CS CP 0 PO STATUS
Base+4 Eccentricity MSW (bits 31...16 of float)
Base+5 LSW (bits 15...0 of float)
Base+6 Maximum wall position (MSB) and minimum wall position (LSB), 1 … 24 each
PO Bit set if all parameters are OK and have been written by the master, bit reset if at least one parameter must be re-written
CP Calibration is in progress. The Profibox has recognised the CA transition, and the calibration procedure is in progress. This bit is cleared when the calibration succeeds or if the procedure times-out after 10 seconds.
CS Cleared when the calibration procedure begins, and set only if the calibration procedure succeeded. This bit is only cleared if the calibration procedure is restarted or the Profibox is reset.
STATUS Status code, 0..255. Either a common Profibox status code or one of the following: 0 Gauge OK 1 Product out of tolerance 2 No cable 3 Motor starting 4 Motor stopping 5 Motor stopped 6 Lid open 7 Fatal fault
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 34 of 52 Revision 8 (May 2009)
PARAMETERS
Parameter Type Description
1 word DP/RS232 units: 0=metric, 1=imperial
2 word Measurement type: 0=linear, 1=eccentricity %, 2=concentricity %
3 word Rotation direction. 0=clockwise, 1=counter clockwise
4 float Preset eccentricity (tolerance), linear or percent
5 float Preset core diameter
6 float Preset outer diameter
7 word Torsion setting: 1 … 24
8 word Number of rotations to average: 20 … 100
9 word Preset RPM: 600 … 1200 (CS1010), 100 … 300 (CS1015)
10* float Calibration factor: 0.5 … 2.0
11* float Cable type gain: 0.5 … 2.0
12 float Calibration result / base frequency, for information, read-only
* Transmitted value = Measured value x [parameter 10] x [parameter 11]
Please refer to the Centerscan manual for more information regarding the use of these gauges.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 35 of 52 Revision 8 (May 2009)
LD / MLD / AS3000 / AS5000 Diameter Gauges
For Helix mode see next page.
The 'LD' profile may be used when the PIB1000 is connected to an AccuScan LD,
IntelliPak gauges, LI indicators, WI indicators, or AS3000/AS5000 gauges. The DP
parameterisation data contains an 'LD emulation' field that is used to adjust the
PIB1000's RS232 protocol and behaviour when communicating with the gauge. To
ensure correct operation the correct 'LD emulation' setting must be selected.
OUTPUT CONTROL WORD
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 r r r r r r r r r r r r TH r r r
r Bit is reserved, and should be set to zero by DP master. TH If set the Profibox will convert gauge status codes 1 through 4 to code 0,
thereby suppressing non-fatal errors during threading.
INPUT DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 0 0 0 0 0 0 XY PO STATUS
Base+4 X diameter MSW (bits 31...16 of float)
Base+5 LSW (bits 15...0 of float)
Base+6 Y diameter MSW (bits 31...16 of float), valid for dual plane gauges only
Base+7 LSW (bits 15...0 of float), valid for dual plane gauges only
XY Bit set if gauge is dual plane, bit reset if gauge is single plane. PO Bit set if all parameters are OK and have been written by the master,
bit reset if at least one parameter must be re-written STATUS Status code, 0..255. Either a common Profibox status code or one of
the following gauge status codes: 0 Gauge OK 1 No cable detected 2 Gate obscured 3 Lens dirty 4 Too many cables detected 5 Unspecific gauge error
When using the PIB1000 with an AS3000 or AS5000 the gauge status codes between 5 and 9 have a different meaning (refer to ASx000 manual): 5 Gauge too hot inside casing 6 Wrong motor speed 7 Measured width of gauge gate incorrect 8 Wrong gauge type (internal gauge configuration error) 9 Unspecific gauge error
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 36 of 52 Revision 8 (May 2009)
PARAMETERS
Parameter Type Description
1 word DP/RS232 units: 0=metric, 1=imperial
2 word X gate position: -99 … +99, read only
3 word Y gate position: -99 … +99, read only (valid for dual plane gauges only)
4 word Number of samples for gauge to average: 1 … 1000 - LD, IntelliPak, LI indicator, WI indicator 1 … 6000 - ASx000 LD emulation mode
5 float Preset (target) diameter: range according to gauge, affects gauge relay output only
6 float Diameter tolerance: range according to gauge, affects gauge relay output only. Not used for ASx000 LD emulation mode.
7 - Reserved (helix table size). Read/write requests will be rejected.
8 word
Controller mode. 6=reset, 7=freeze, 8=running. The validity of this parameter does not affect the state of the PO bit. Not used for IntelliPak, LI indicator, WI indicator, or ASx000 LD emulation modes.
9 float
Preset I-Term for controller. 0.0% through 100.0%. The validity of this parameter does not affect the state of the PO bit. Not used for IntelliPak, LI indicator, WI indicator, or ASx000 LD emulation modes.
10 word
Controller output: 0=normal, 1=inverted. The validity of this parameter does not affect the state of the PO bit. Not used for IntelliPak, LI indicator, WI indicator, or ASx000 LD emulation modes.
11 float Moisture filter setting 0.00 through 999.99. The validity of this parameter does not affect the state of the PO bit. Used only for IntelliPak LD emulation mode.
12 word
Percentage of valid scans, 0...100, read only. As with all read-only parameters the validity of this parameter does not affect the state of the PO bit. Used only for IntelliPak LD emulation mode.
13 - Reserved (STAC logic). Read/write requests will be rejected.
14 - Reserved (STAC logic). Read/write requests will be rejected.
15 - Reserved (STAC logic). Read/write requests will be rejected.
16 word X optics condition 0..99%, read only. Only available for WI900 and ASx000 LD emulation modes.
17 word Y optics condition 0..99%, read only. Only available for WI900 and ASx000 LD emulation modes.
Please refer to the relevant manual for more information regarding the use of these gauges.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 37 of 52 Revision 8 (May 2009)
LD Diameter Gauges in HELIX Mode
OUTPUT CONTROL WORD
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 r r r r r r r r r r r r TH r r r
r Bit is reserved, and should be set to zero by DP master. TH If set the Profibox will convert gauge status codes 1 through 4 to code 0,
thereby suppressing non-fatal errors during threading.
INPUT DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 0 0 0 0 0 0 XY PO STATUS
Base+4 Y cycle count X cycle count
Base+5 Max X diameter MSW (bits 31...16 of float)
Base+6 LSW (bits 15...0 of float)
Base+7 Min X diameter MSW (bits 31...16 of float)
Base+8 LSW (bits 15...0 of float)
Base+9 Mean X diameter MSW (bits 31...16 of float)
Base+10 LSW (bits 15...0 of float)
Base+11 Max Y diameter MSW (bits 31...16 of float), valid for dual plane gauges only
Base+12 LSW (bits 15...0 of float), valid for dual plane gauges only
Base+13 Min Y diameter MSW (bits 31...16 of float), valid for dual plane gauges only
Base+14 LSW (bits 15...0 of float), valid for dual plane gauges only
Base+15 Mean Y diameter MSW (bits 31...16 of float), valid for dual plane gauges only
Base+16 LSW (bits 15...0 of float), valid for dual plane gauges only
XY Bit set if gauge is dual plane, bit reset if gauge is single plane. PO Bit set if all parameters are OK and have been written by the master,
bit reset if at least one parameter must be re-written STATUS Status code, 0..255. Either a common Profibox status code or one of
the following: 0 Gauge OK 1 No cable detected 2 Gate obscured 3 Lens dirty 4 Too many cables detected 5 Unspecific gauge error
A maximum diameter is the maximum diameter within the helix table for the corresponding plane (see the description of the helix table size parameter on the following page). A minimum diameter is the minimum diameter within the helix table for the corresponding plane. The mean diameters are the average of the mean diameters within the helix table
The X/Y cycle counters are 8 bit numbers that represent the number of RS232 continuous data messages received from the gauge for each plane. The counters operate independently, and wrap back to 0 after 255. On a single plane gauge only the X cycle count will increment (every 100ms), whilst on a dual plane gauge each increments alternately (every 200ms each). There is no guarantee that the X and Y cycle counts will remain in step - a counter will not advance if a continuous packet is lost because of RS232 transmission errors.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 38 of 52 Revision 8 (May 2009)
A DP master may be programmed to only extract max, min, and mean data for a particular plane when it detects a change in the corresponding cycle counter. This allows the 100ms (200ms) timing for each set of measurements to be preserved, regardless of RS232 or Profibus DP propagation delays. Normally this would be done using a helix table size of 1.
PARAMETERS
Parameter Type Description
1 word DP/RS232 units: 0=metric, 1=imperial
2 word X gate position: -99 … +99, read only
3 word Y gate position: -99 … +99, read only (valid for dual plane gauges only)
4 word Number of samples for gauge to average: 1 … 1000. Note that this has no effect on helix measurements, but may affect locally displayed diameters or analogue outputs
5 float Preset (target) diameter: range according to gauge, affects gauge relay output only
6 float Diameter tolerance: range according to gauge, affects gauge relay output only
7 word Helix table size: 1 ... 200. See description below.
8 word
Controller mode. 6=reset, 7=freeze, 8=running. This parameter is only used by the Profibox when the DP parameterisation data (as per the GSD file) indicates that the Profibox is being used with an LD device. The validity of this parameter does not affect the state of the PO bit.
9 float
Preset I-Term for controller. 0.0% through 100.0%. This parameter is only used by the Profibox when the DP parameterisation data (as per the GSD file) indicates that the Profibox is being used with an LD device. The validity of this parameter does not affect the state of the PO bit.
10 word
Controller output: 0=normal, 1=inverted. This parameter is only used by the Profibox when the DP parameterisation data (as per the GSD file) indicates that the Profibox is being used with an LD device. The validity of this parameter does not affect the state of the PO bit.
11 float
Moisture filter setting 0.00 through 999.99. This parameter is only used by the Profibox when the DP parameterisation data (as per the GSD file) indicates that the Profibox is being used with an IntelliPak device. The validity of this parameter does not affect the state of the PO bit.
12 word
Percentage of valid scans, 0...100, read only. This read-only parameter is only updated by the Profibox when the DP parameterisation data indicates that the Profibox is being used with an IntelliPak device. As with all read-only parameters the validity of this parameter does not affect the state of the PO bit.
13 - Reserved (STAC logic). Read/write requests will be rejected.
14 - Reserved (STAC logic). Read/write requests will be rejected.
15 - Reserved (STAC logic). Read/write requests will be rejected.
16 word Reserved (X optics condition). Read/write requests will be rejected.
17 word Reserved (Y optics condition). Read/write requests will be rejected.
The DP Profibox can calculate the max, min and mean values over a period of time using internal tables of historical information. This can relieve the DP master of the burden of maintaining such tables, and could be particularly useful for slow DP masters that could miss a set of max, min and mean information.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 39 of 52 Revision 8 (May 2009)
The helix tables within the DP Profibox hold the historic values for the helix
information parsed from the gauge‟s RS232 continuous data for each plane.
Each entry in a table corresponds to a time span of 100ms for single plane
gauges or 200ms for dual plane gauges. The DP Profibox always stores historic
values up to the maximum helix table size. Each time new data is entered into a
table the max, min, mean and cycle count values for the corresponding plane
are calculated and returned in the input data area. The number of most recent
historic values used in the computation is referred to as the helix table size, and
can be set by the DP master using parameter 7.
At startup, or if an RS232 communications timeout occurs, the count of entries
within the internal helix tables are reset. When gauge communications begins,
only the most recent valid entries within the helix tables are used in the
calculations, and therefore the window sizes used for the calculations may not
be as large as the „helix table size‟ parameter. The correct window sizes will be
used once the gauge/Profibox combination has been running smoothly for a
short period (e.g. 20 seconds for a dual-plane gauge and a window size of 100).
A DP master would normally set the helix table size to 1 if it maintains its own
historical helix information tables.
Note that an RS232 communications timeout does not affect the X/Y cycle
counts. These counts are always 0 after a Profibox restart and are incremented
after a corresponding continuous data message is received from the gauge.
They are unaffected by any other activity.
Please refer to the AccuScan LD manual for more information regarding the use
of these gauges.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 40 of 52 Revision 8 (May 2009)
LN Fault Gauges
Gauge (DP profile) type 6. Note that this profile can have two different sizes of „input data words‟: „Input size‟ = 6 input words - LN without fault information „Input size‟ = 13 input words - LN with fault information
The Profibox implements a 64-fault deep internal FIFO for fault information received from the LN gauge. This FIFO can be controlled using either the short or long profile size, but use of the FIFO is only meaningful with the longer profile size.
When the shorter profile (without fault information) is specified, the Profibox will turn off the gauge‟s continuous data (fault event reports). The shorter profile size should be used with an LN-D style gauge since the Profibox does not support the LN-D continuous data format; received fault information from an LN-D would cause an RS232 protocol error status. The shorter profile can also be used with an LN-DL if the additional fault information is not required.
When the longer profile (with fault information) is specified, the Profibox turns on continuous data from the gauge using serial port mode 2 („event mode‟). The received fault information is entered into the Profibox‟s fault FIFO without any filtering, even if the event is a duplicate of an earlier event. Only the LN-DL fault event format is supported.
OUTPUT CONTROL WORD
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 r r r r r r r r r r r RB TH ZF r r
r Bit is reserved, and should be set to zero by DP master. TH If set the Profibox will convert gauge status code 1 to code 0, thereby
suppressing errors during threading. ZF On a 0 to 1 transition of this bit the Profibox zeroes/clears:
the lump and neck fault counts the distance counter the internal fault FIFO. The 0 to 1 transition takes precedence over the „RB‟ bit, and will reset the internal fault FIFO before the state of the RB bit is checked. Therefore, if the RB bit changes simultaneously with a 0 to 1 transition of the ZF bit then the Profibox will return „FIFO empty‟ for the fault type. It is recommended that the master leave the bit set for several data cycles to ensure the transition is recognised at the Profibox. Fault counting is unaffected when this bit is a steady 1, undergoing a 1 to 0 transition, or a steady 0.
RB Request Buffer. Toggled by the master to solicit fault information from the fault FIFO. See also the definition of the AB bit below, and the subsequent RB/AB description below.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 41 of 52 Revision 8 (May 2009)
INPUT DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 0 0 0 0 0 AB 0 PO STATUS
Base+4 Number of lump faults, unsigned word
Base+5 Number of neck faults, unsigned word
----------------------
------------------------------------------------------------------------------------------------------------------------
Base+6 0 0 0 0 0 0 0 0 0 0 0 0 0
Fault Type 0 = FIFO empty 1 = X lump 2 = X neck 3 = Y lump 4 = Y neck 5,6,7 = resvd
Base+7 Fault number, unsigned word
Base+8 Fault position MSW (bits 31..16 of float) (m or ft)
Base+9 Fault position LSW (bits 15..0 of float)
Base+10 Fault height MSW (bits 31..16 of float) (m or inches)
Base+11 Fault height LSW (bits 15..0 of float)
Base+12 Fault length MSW (bits 31..16 of float) (m or inches)
Base+13 Fault length LSW (bits 15..0 of float)
AB Acknowledge Buffer. When the Profibox detects a change in the RB bit it places the next fault information from its internal FIFO (if any) into the input data words, and then sets this bit to the same state as the master‟s RB bit. When the RB and AB bits are equal the master should check the fault information in the input data and then toggle the RB bit. If „fault type‟ is zero it indicates that the Profibox‟s fault FIFO was empty. The RB/AB bits work with either the shorter or longer profile size, but the fault information is only returned when using the longer profile size.
PO Bit set if all parameters are OK and have been written by the master, bit reset if at least one parameter must be re-written
STATUS Status code, 0..255. Either a common Profibox status code or one of the following: 0 Gauge OK 1 Unspecific gauge error
The Profibox reacts to changes in the RB bit by putting the oldest fault information from its internal fault FIFO into the „input data‟. If the FIFO is empty then the fault information fields in the „input data‟ are cleared. The Profibox then sets the AB bit to the same state as the RB bit.
When the master‟s RB and AB bits are equal it should check the fault information and then toggle the RB bit. When the RB and AB bits are different then the master should ignore the fault information make no change to the state of the RB bit.
There is no guarantee that the number of faults returned through the RB/AB mechanism will match the sum of the lump and neck fault counts:
a. The fault counts are solicited from the LN gauge on a regular basis, whilst fault information arrives asynchronously. Transient RS232 errors do not cause the loss of fault counts, whereas they can cause the total loss of one or more fault information reports.
b. The gauge‟s internal fault FIFO may become full causing the loss of one or more fault information reports. This happens only if the rate of fault detection exceeds the rate at which the faults can be reported over the RS232 link for a sustained period.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 42 of 52 Revision 8 (May 2009)
c. The Profibox‟s internal fault FIFO may become full causing the loss of one or more fault information reports. This happens only if the rate of received fault information exceeds the rate at which the master solicits them for a sustained period.
The Profibox‟s fault information FIFO is cleared when the master re-configures
(or first connects) to the Profibox, there is a 0 to 1 transition of the „ZF‟ bit, or
when the master changes the DP/RS232 units parameter.
The fault counts and distance are cleared on a 0 to 1 transition of the „ZF‟ bit, or
by cycling the LN gauge‟s power.
The fault information will not be collected if the master hasn‟t set the „units‟
parameter (parameter number 1).
PARAMETERS
Parameter Type Description
1 word DP/RS232 units: 0=metric, 1=imperial
2 float X Lump threshold
3 float X Neck threshold
4 float Y Lump threshold
5 float Y Neck threshold
Please refer to the LN manual for more information regarding the use of these
gauges.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 43 of 52 Revision 8 (May 2009)
LS LaserSpeed Gauges
OUTPUT CONTROL WORD
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 r r r r r r r r r r r FR r ZL r r
r Bit is reserved, and should be set to zero by DP master. ZL A 0 to 1 transition of this bit will cause the Profibox to send a 'reset length'
command to the LaserSpeed. FR Final length mode request. Set this bit to 1 to use the LaserSpeed in 'Final
Length' mode. This bit will be ignored, and the Profibox will continue to use polled mode, if the connected gauge does not support the LaserSpeed 'TF' RS232 command. Clear the FR bit at any time to return the Profibox to using 'polled' mode. See also the FA acknowledgement bit. Any changes made to profile parameters when FR=1 and FA=1 will not be communicated to the LaserSpeed until FR=0. Wen FA=1 it is not possible for the Profibox to detect that a LaserSpeed has been disconnected or has been power-cycled.
INPUT DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 0 0 0 0 0 FA 0 PO STATUS
Base+4 Length MSW (bits 31...16 of a long)
Base+5 LSW (bits 15...0 of a long)
Base+6 Velocity MSW (bits 31…16 of a long)
Base+7 LSW (bits 15…0 of a long)
Base+8 Gauge Status Flags Quality Factor
Base+9 Data Cycle Counter, unsigned word
PO Bit set if all parameters are OK and have been written by the master, bit reset if at least one parameter has not been written to by the master.
FA Final length mode acknowledgement. Set to 1 if the Profibox has accepted the FR bit and placed the LaserSpeed into 'TF' mode. This bit will be 0 if the FR bit is 0, if no LaserSpeed is connected, or if a connected LaserSpeed does not support 'TF' mode. Note that any changes made to profile parameters made when FR=1 and FA=1 will not be communicated to the LaserSpeed until FR=0. Wen FA=1 it is not possible for the Profibox to detect that a LaserSpeed has been disconnected or has been power-cycled.
STATUS Status code, 0..255. For the LaserSpeed this will only be 0 (Gauge OK), or one of the common Profibox status codes.
Length The LaserSpeed's length value, -999999999 through +999999999. Note that there are three implied decimal places within this value, regardless of the selected units of measurement.
Velocity The LaserSpeed's velocity value, -999999999 through +999999999. Note that there are three implied decimal places within this value, regardless of the selected units of measurement. This value will be zero when the Profibox updates the input data with 'final length' data (FR=1, FA=1, and at least one 'TF' response has been received from the LaserSpeed).
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 44 of 52 Revision 8 (May 2009)
Gauge Status Flags is a bit field, as defined by the LaserSpeed manual. The number and meaning of the bits varies slightly between differing LaserSpeed versions. This value will have its most significant bit clear when the input data is updated using 'polled' gauge data, whereas the value will have its most significant bit set and all other bits clear when the input data is updated with 'final length' gauge data. Thus Gauge Status Flags will typically be between 0 and 63 for polled mode, and will always be 128 for final length mode. Since the profile data is always consistent, it is therefore possible to determine if the 'length' field is a polled reading or a final length reading.
Data Cycle Counter starts at zero, and counts up by 1 for every received polled
mode or final length mode response received from the gauge. Note that because the Profibox uses 'polled' mode for a short while, regardless of the FR bit, to establish the connected LaserSpeed type, then there will always be some polled readings and a non-zero Data Cycle Counter within the input data prior to any FR request being acknowledged and the first final reading being received by the Profibox. New final length readings can be detected by noting a change in the Data Cycle Counter and ensuring that the most significant bit of the Gauge Status Flags is set.
PARAMETERS
Parameter Type Description
1 word LaserSpeed units of measurement: 0…N
2 word Calibration Trim: 5000. 20000
3 long Index pulse (OPR) setting: 1…999999999
4 word Material present threshold: 0…255 or 0…4095 (if relevant)
Note that although it is possible to read/write the Profibus parameters at any time, the parameter values are only communicated between the Profibox and the LaserSpeed when the Profibox is being used in 'polled' mode. Therefore if any parameter values are written when FR=1 and FA=1, the Profibox will only communicate the changes to the LaserSpeed when (and if) FR is reset to 0.
Later LaserSpeed gauges support a greater range of 'units' than earlier versions. Consult the appropriate LaserSpeed manual for detailed information.
The Material Present Threshold parameter varies significantly between LaserSpeed versions. It is important that this parameter is updated with a value relevant to the connected LaserSpeed. This parameter is ignored for versions of the LaserSpeed that do not support 'final length' mode. Again, consult the appropriate LaserSpeed manual for detailed information.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 45 of 52 Revision 8 (May 2009)
SI900 Sparktesters
An additional bit in the DP parameterisation is used to select between SI (RS232)
and DS (Analog) machine types.
For DS Sparktesters the analogue connections are: RLY1: „Count Enable‟. Closed to enable counting. Opened to reset count. RLY2 „EHT Enable‟. Closed to enable EHT. DIG1: Input for „Operation Status‟. Current flow indicates OK. DIG2: Input for „Spark Fault‟. Current flow indicated Spark Fault. AOUT: 0 to 10V representing requested kV (0V if OCF_START is 0). AIN: 0 to 10V representing Sparktester‟s actual measured kV.
OUTPUT CONTROL WORD
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+4 r r r r r r r r r r r r TH ZF ST r
r Bit is reserved, and should be set to zero by DP master. TH If set the Profibox will convert gauge status code 1 to code 0, thereby
suppressing errors during threading. ZF The Profibox zeroes the spark count for a 0 to 1 transition of this bit. It is
recommended that the master leave the bit set for several data cycles to ensure the transition is recognised at the Profibox. Fault counting is unaffected when this bit is a steady 1, undergoing a 1 to 0 transition, or a steady 0.
ST This bit is ignored for the RS232 based SI Spark Tester as this indicator provides no facilities for remote EHT enable. For the analogue DS Sparktester, the Profibox activates the EHT enable relay when this bit is set, and deactivates the relay when the bit is clear. To disable remote enabling of the DS Sparktester it is necessary to alter the electrical connections between the machine and the Profibox.
INPUT DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 0 0 0 0 0 0 0 PO STATUS
Base+4 Measured voltage MSW (bits 31...16 of float)
Base+5 LSW (bits 15...0 of float)
Base+6 Number of spark faults, unsigned word
PO Bit set if all parameters are OK and have been written by the master, bit reset if at least one parameter must be re-written
STATUS Status code, 0..255. Either a common Profibox status code or one of the following: 0 Gauge OK 1 Unspecific gauge error
PARAMETERS
Parameter Type Description
1 word DP/RS232 units: 0=metric, 1=imperial
2 float Preset voltage
Please refer to the relevant Sparktester manual for more information regarding the use of these machines.
Instruction handbook - Profibox
Gauge Parameters
MAN/E1556-0122 Page 46 of 52 Revision 8 (May 2009)
Preheater MCS
RLY1: „Start Preheater‟. Normally open. Pulsed closed to start machine. RLY2: „Stop Preheater‟. Normally open. Held closed when OCF_START is 1. DIG1: Input for „Preheater Operation Status‟. Current flow indicates „OK‟. DIG2: Input for „Rotatemp within 10 degrees‟. Current flow indicates „OK‟. AOUT: 0 to 10V output signal representing requested temperature (the
Profibox sets this to 0V if OCF_START is 0).
OUTPUT CONTROL WORD
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 r r r r r r r r r r r r TH r ST r
r Bit is reserved, and should be set to zero by DP master. TH If set the Profibox will convert gauge status codes 1 or 2 to code 0,
thereby suppressing errors during threading. ST If clear the Profibox‟s preset temperature output signal will be 0V and the
„Stop Preheater‟ relay output will be open. If set, the Profibox‟s output control signal will reflect the temperature requested through parameter number 2, and the „Stop Preheater‟ relay output will be closed. A 0 to 1 transition also causes the „Start Preheater‟ relay output to be closed for 500ms.
INPUT DATA WORDS
15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0
Base+3 0 0 0 0 0 0 0 PO STATUS
Base+4 Measured temperature, unsigned word
PO Bit set if all parameters are OK and have been written by the master, bit reset if at least one parameter must be re-written
STATUS Status code, 0..255. Either a common Profibox status code or one of the following: 0 Gauge OK 2 Preheater non-operational
PARAMETERS
Parameter Type Description
1 word DP units: 0=metric, 1=imperial. See note below.
2 word Preset wire / oven temperature
Note: the Profibox parameterisation must correctly specify if the Preheater/Rotatemp gauges have been configured for metric or imperial
operation (0 to 10V representing either 0 to 1000 C or 0 to 1000 F). The Profibox provides all necessary conversions to match the Preheater/Rotatemp units to the selected DP units.
Please refer to the relevant Beta LaserMike manuals for more information regarding the use of these gauges.
Instruction handbook - Profibox
Maintenance
MAN/E1556-0122 Page 47 of 52 Revision 8 (May 2009)
Maintenance
The Profibox does not require cleaning or any regular maintenance by the
customer. There are no internal fuses. In the event the PIB1000 stops
functioning due to a hardware fault, please send the whole unit back to your
local BLM Service centre. However, in the case of a PIB1001 having a
hardware fault, new parts can be ordered (see table below).
Spares for PIB1001
Description Part number Quantity per
unit
2 PIB1001 PCBs with adaptor plate (assembled). SA1556-0066 1 assembly
Cable assembly (Analog interconnection lead for PIB1001 to Sparktesters)
CA5100-0343.M600 1
12 core screened cable – 1 metre. (Interconnection lead for PIB1001 to Preheaters)
405141217 1
Replacing the PIB1001 PCBs
1. Isolate Profibox from mains supply.
2. Remove 4 screws securing Profibox lid.
3. Use antistatic wrist band or touch Profibox casing to discharge any static
electricity.
4. Using small screwdriver loosen screws on PCB connectors and remove all
cable cores.
5. Remove 4 screws securing PCB adaptor plate to bottom of Profibox housing
and lift out both PCBs together with adaptor plate. (do not remove any screws
on PCB itself)
6. Fit new PCB assembly.
7. Ensure Profibox lid screws are tightly fastened to ensure IP rating.
Instruction handbook - Profibox
Troubleshooting / LED Signals
MAN/E1556-0122 Page 48 of 52 Revision 8 (May 2009)
Troubleshooting / LED Signals
Symptoms Possible cause Solution *
Unit not functioning
Power supply failure Check power supply at connector pins.
Faulty cable Check and replace cable if necessary
LED2 continuously flashing
Faulty PCB.
Contact Beta LaserMike Service.
The EPROMs have not been programmed correctly.
Contract Beta LaserMike Service to order new EPROMs.
LED3 (PIB1000) off LED9 (PIB1001) off
No power is going into Profibox Test cable and 24V supply
Incorrect power supply Check 24V power supply.
* Recycling the power may also solve some problems.
PIB1000 LED locations:
PIB1001 LED locations:
Watchdog LED (LED2)
Flashes once upon Power up.
If this LED flashes
continuously
off/on, there is a fault with the processor.
Power ON LED (LED3)
After Power up, should be continuously on.
Hole for viewing LED2
Flashes once on startup and
should turn off.
If flashing indicates problem
with PCB or
EPROMs.
Hole for viewing LED9
Should be permanently on
(+5V). If off,
indicates problem
with power.
Instruction handbook - Profibox
Servicing and Returning your Equipment
MAN/E1556-0122 Page 49 of 52 Revision 8 (May 2009)
Servicing and Returning your Equipment
Your instrument was carefully inspected electrically and mechanically prior to shipment. It should be free of surface mars and scratches, and it should be in perfect working order upon receipt. If any indication of damage is found, file a claim with the carrier immediately, prior to using the instrument. If no damage is apparent, proceed by using this manual to install and setup this instrument.
Save the shipping carton and packing material for future storing or shipment of the instrument. If, at some future time, the instrument must be returned to the factory for service, include a full description of the instrument failure and the mode of operation the instrument was in at the time of failure. Also include a contact person to discuss the instrument failure.
Field warranty service is available, if the customer pays travel expenses by advance purchase order. All service operations should be performed by skilled electronics technicians, who have been trained by Beta LaserMike.For more information see under heading Proprietary Information at the beginning of this manual.
WHEN RETURNING EQUIPMENT FOR SERVICE, IT IS IMPORTANT TO FIRST OBTAIN A RETURN MATERIAL AUTHORIZATION (RMA) NUMBER. The RMA number is needed for proper handling of returned equipment.
To get an RMA,
Go to www.betalasermike.com
Select “Service”
Select “Equipment Return / RMA” from the drop-down menu and follow the instructions.
Ship the instrument in the original carton, or, if the original carton is unavailable, ship in a carton providing sufficient protection. Send the instrument to the Asia, Europe, or USA office (addresses listed in the supplied Contacts/CE Manual), whichever is closest to you or to the office indicated by your sales engineer. Place the RMA number on the outside of the carton, and include a purchase order number and any other information specific to your instrument.
Instruction handbook - Profibox
Disposal / Recycling
MAN/E1556-0122 Page 50 of 52 Revision 8 (May 2009)
Disposal / Recycling
Please check the following before disposing of your equipment:
Is the equipment worth repairing? If in doubt, contact Beta LaserMike
Service.
Does the equipment contain any hazardous materials? If you are aware of
any hazardous materials in your equipment, ensure qualified personnel
take responsibility for its disposal. Some examples of hazardous
substances are lead, mercury, cadmium, chromium VI, flame retardants,
fluorescent tubes, monitors containing cathode ray tubes and products
containing capacitors.
Can you re-use or recycle any constituent parts?. For example, if the
housing/chassis is made of metal, it can be recycled by your local
authority. Ensure qualified personnel take responsibility for dismantling
the equipment.
If the equipment does need to be disposed of, please dispose of it in a way
that doesn’t harm the environment.
Instruction handbook - Profibox
Specification
MAN/E1556-0122 Page 51 of 52 Revision 8 (May 2009)
Specification
General
Net weight PIB1000 = 0.781 kg (1.72 lb), PIB1001 = 2.5 kg (5.5 lb)
Noise <70 dBa
Expected life
Up to 10 years (Time frame does not exclude possible replacements of serviceable parts and is based on routine maintenance/calibration of equipment).
Environmental Conditions
Altitude Unlimited
Ambient operating temp. 5-40 C (41- 104 F)
Ambient storage temp. -40 C - +50 C (-40 F - +122 F)
Max relative humidity 80% for temp. up to 31 C or 88 F (decreasing linearly to 50% relative humidity at 40 C or 104 F)
Installation category
Installation Category 2
Pollution degree Pollution Degree 1 (Equipment has been designed for operation with a level of pollution of its
internal micro-environment, which corresponds with the definition of Pollution Degree 1 in BSEN 61010-1:1993)
IP rating
IP65 (as defined in BSEN 60529)
Voltage fluctuations +10 % of nominal voltage
Digital inputs
Voltage range 5-24vdc
Frequency range 50Hz nominal
Power <3W
Sampling rate 100Hz
Input impedance 2.2
Analog inputs
Voltage range 0-10V
Frequency 50Hz
Impedance >50Hz
Resolution 12 bit
Analog outputs
Voltage range ± 10V
Frequency 5Hz (1000Hz for fast analog output)
Impedance <10
Min load resistance 5 k
Output range Adjustable to +10V max.
Resolution 14 bit (12 bit for fast analog output)
Relay contacts
Max supply level 60 Vdc and 30 Vac rms
Instruction handbook - Profibox
Index
MAN/E1556-0122 Page 52 of 52 Revision 8 (May 2009)
Index
AS3000 ........................................................ 35 AS5000 ........................................................ 35 Cable .............................................................4 Cable Specifications ...................................... 17 Centerscan Gauges
Connecting to PIB1000 ............................. 11 Parameters............................................... 33
Common status codes ................................. 25 Configuration ............................................... 23 Configuration via DP Master......................... 24 Data Format and Units ................................. 27 Dimensions
PIB1000 .....................................................8 Disposal ....................................................... 50 Earthing.................................................... 4, 19 EMC Directive .................................................4 Environmental Conditions .............................. 51 European Commission Requirements ............4 Expected Life ............................................... 51 Gauge Parameters ....................................... 30 Gland Termination
PIB1000 ................................................... 16 PIB1001 ................................................... 18
Industrial environment .....................................4 Input Data .................................................... 28 Intended Use .................................................6 Interference ....................................................4 Introduction ....................................................6
LaserSpeed gauges ..................................... 43 LD Gauge
Connecting to Height Stand ...................... 10 Parameters............................................... 35
LEDs ........................................................... 48 LN Fault Gauges
Connecting to Height Stand ...................... 10 Maintenance ................................................ 47 Output Data ................................................. 28 Positioning the PIB1000 next to the LD or LN
................................................................ 10 Preheater Gauge
Parameters............................................... 46 Recycling ..................................................... 50 Returning your Equipment ............................ 49 RS232 Communication ................................ 26 RS232 Configuration .................................... 23 Safety ............................................................6 Securing PIB1000 next to the Centerscan .... 11 SELV levels ....................................................6 Service ...........................................................4 Servicing ...................................................... 49 SI/DS Sparktesters
Parameters............................................... 45 Specification ................................................ 51 Troubleshooting ........................................... 48 WI900 .......................................................... 36