Direct Contact Condenser
This type of condenser is suitable where conditions permit condensation of exhauststeam by direct contact with the cooling water. The vacuum is created in the chamber by an air ejector. The cooling water is sprayed into the chamber an the fine spray contacts the steam. The steam condenses and falls to the bottom of the condenser chamber with the injection water. The condensed steam and injection water is withdrawn using a centrifugal extraction pump
![Page 3: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/3.jpg)
Barometric Condenser
Barometric Counter-Current Condensers have no moving parts. Little maintenance is required and provision can be made for internal inspection of the unit. Because of the barometric leg, no water removal pump is required
![Page 4: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/4.jpg)
Barometric Condenser
Multi-Jet Barometric Condensers are generally employed where low cost water is available in ample quantity. It is the simplest design of all barometric
condensers, and requires no auxiliary air pump or pre-cooler. - Recommended for operation under fairly constant loads where there is
relatively little air leakage, and where water is not too scarce and does not need to be recirculated.
![Page 5: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/5.jpg)
Jet-Type Condenser
Multi-Jet Spray Type Barometric Condensers are generally employed where large capacities are required and where wide fluctuations in water temperature or steam load occur.
![Page 6: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/6.jpg)
Surface CondensersSurface condensers are the
most commonly used condensers in modern power
plants. The exhaust steam from the turbine flows on the
shell side (under vacuum) of the condenser, while the plant’s circulating water
flows in the tube side.
![Page 7: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/7.jpg)
Surface Condensers
The source of the circulating water can be either a closed-loop (i.e.
cooling tower, spray pond, etc.) or once
through (i.e. from a lake, ocean, or river). The
condensed steam from the turbine, called
condensate, is collected in the bottom of the
condenser, which is called a hot well. The
condensate is then pumped back to the steam
generator to repeat the cycle.
![Page 8: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/8.jpg)
Surface Condensers
![Page 9: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/9.jpg)
Surface CondensersSurface condensers are basically a shell and tube heat exchanger consisting of water boxes for directing the flow of cooling water to and from horizontal tubes. The tubes are sealed into fixed tube sheets at each end and are supported at intermediate points along the length of the tubes by tube support plates. Numerous tubes present a relatively large heat transfer and condensing surface to the steam. During operation at a very high vacuum, only a few kgs of steam are contained in the steam space and in contact with the large and relatively cold condensing surface at any one instant.
![Page 10: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/10.jpg)
surface condenser have improved by cutting down the bundle to half and making two smaller bundles beside each others to overcome the high pressure drop problem .
Baffles are used to help the steam distribution and accelerate condensation rate
The shell is fabricated from carbon steel plates and is stiffened as needed to provide rigidity for the shell.
Intermediate plates are installed to serve as baffle plates that provide the desired flow path of the condensing steam. The plates also provide support that help prevent sagging of long tube lengths.
At the bottom of the shell, where the condensate collects, an outlet is installed. In some designs, a sump (often referred to as the hot well) is provided. Condensate is pumped from the outlet or the hot well for reuse as boiler feed water.
![Page 11: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/11.jpg)
Shell OutletShell Outlet
Channel InletChannel Inlet
ChannelChannelOutletOutlet
Shell OutletShell Outlet
SINGLE SEGMENTAL TRANVERSE BAFFLESSINGLE SEGMENTAL TRANVERSE BAFFLES
![Page 12: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/12.jpg)
Tube sheets of sufficient thickness usually made of stainless steel is provided, with holes for the tubes to be inserted and rolled. This is to avoid eddies at the inlet of each tube giving rise to erosion, and to reduce flow friction. To take care of length wise expansion of tubes some designs have expansion joint between the shell and the tube sheet allowing the latter to move longitudinally.
Size: modern condensers use 7/8 or 1.0 in tube of 18 gauge thickness
Condensers may have up to four passes; one and two pass condensers are the most common. In a single pass condenser, the cooling water makes one passage from end to end, through the tubes. Single pass condensers have an inlet waterbox on one end and an outlet water box on the other end. Two pass condensers have the cooling water inlet and outlet on the same water box at one end of the condenser, with a return water box at the other end.
![Page 13: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/13.jpg)
A single pass condenser is commonly used where the water is supplied from natural sources such as rivers or oceans. If the source of circulating water is at all limited, a two pass condenser will probably be the best selection since a single pass condenser requires more cooling water per square foot of condenser surface and per kilowatt of electrical generation. Usually, a two pass condenser is used with cooling towers or a cooling lake.
Waterboxes: The tube sheet at each end with tube ends rolled, for each end of the condenser is closed by a fabricated box cover known as a waterbox, with flanged connection to the tube sheet or condenser shell. The waterbox is usually provided with man holes on hinged covers to allow inspection and cleaning. These waterboxes on inlet side will also have flanged connections for cooling water inlet butterfly valves, small vent pipe with hand valve for air venting at higher level, and hand operated drain valve at bottom to drain the waterbox for maintenance. Similarly on the outlet waterbox the cooling water connection will have large flanges, butterfly valves, vent connection also at higher level and drain connections at lower level.
![Page 14: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/14.jpg)
Condenser Temperature Profile
![Page 15: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/15.jpg)
Change in Condenser Temperature Profile
![Page 16: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/16.jpg)
Change in Turbine Load and Condenser Pressure
![Page 17: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/17.jpg)
Variation in Condenser Pressure
![Page 18: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/18.jpg)
Air Cooled Condensers
Inlet Inlet NozzlesNozzles
Return Return HeadersHeaders
Fan RingFan Ring
SupportsSupports
Drive AssemblyDrive Assembly
Tube BundleTube BundleOutlet Outlet
NozzlesNozzles
Outlet Outlet HeadersHeaders
Inlet Inlet HeadersHeaders
Hood or PlenumHood or Plenum
FanFan
![Page 19: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/19.jpg)
Dry Cooling
Steam ducted to air-cooled condenser
Condensation inside finned tubes - analogous to automobile radiator
Cold water approaches dry bulb temperature
![Page 20: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/20.jpg)
Steam Condensers
Water Cooled Condensers
Air Cooled Condensers
Internal Surfaces
External Surfaces
![Page 21: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/21.jpg)
Tube Fouling
Deposition or Particulates
Scaling or Crystallization
Microbiological
DebrisCorrosion Products
![Page 22: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/22.jpg)
Deposition or Particulates
Natural sediment Bio-growth Coal dust
Crystalline solids
Are fine particulates that settles on the tube surface due to gravity under low flow condition.
![Page 23: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/23.jpg)
Scaling or Crystallization Fouling• Scale occurs when the saturation point of dissolved
constituents in the
cooling water is exceeded.
• Scale can provide sites for local under scale corrosion
Pitting under scale in stainless steel tube
![Page 24: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/24.jpg)
Debris
Caused by any substance whose size is close to, or greater than,
tube
internal diameter.
• Rocks• Cooling tower materials
( Plastic fill , wood )• Large pieces of rusted
steel• Aquatic animals ( Small
fishes )• Any other substance
that enters the circulating water can obstruct
cooling water flow
Examples :
![Page 25: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/25.jpg)
Tubewall
Deposit Layer
Tube Metal Temperature
800ºF785ºF
700ºF
600ºF
500ºF
Film
Fluid
766ºF Inside Tube Temperature
730ºF Film Temperature
520ºF Bulk Fluid
Temperature
Temperature Profile in Heat Transfer
![Page 26: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/26.jpg)
Cleaning interior surfaces of tubes
Chemical Mechanical
Off Line Cleaning
On Line Cleaning
![Page 27: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/27.jpg)
Chemical treatment
• Several chemicals, often in combination, are used to control
condenser tube fouling.
• PH control ( lowering PH to 5.8 or 4 )
• Scale inhibitors
• Corrosion inhibitors ( Zinc & phosphates for carbon steel )
Chemical treatment methods :
![Page 28: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/28.jpg)
1) The concentration of dissolved constituents is significant,
increasing the
threat of scaling and corrosion.
2) Once-through cooling systems often discharge directly into a
river, lake,
or ocean where chemicals concentrations are restricted.
Utilized for recirculating cleaning system because of :
![Page 29: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/29.jpg)
Disadvantages of chemical treatment:
• Expensive.
• Job duration is excessive.
• Subsequent disposal of the chemicals requires serious
consideration due to potential environmental hazard.
![Page 30: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/30.jpg)
Mechanical cleaning
High Pressure Water
Molded Plastic Cleaners ( Pigs )
Brushes Metal Scrapers
Hydrodrilling
Off line cleaning
![Page 31: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/31.jpg)
High pressure water :
• The water is directed in a high pressure towards the tubes.
• Disadvantages:
The time taken to clean a condenser can become extended.
Could damage tube sheet or tube coatings.
![Page 32: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/32.jpg)
Pigs
• They are molded plastic cleaners .
• Quit popular for softest types of deposits such as mud , silt and microbiological fouling
Plastic tube cleaners
![Page 33: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/33.jpg)
Brushes
• Used to remove micro / macro fouling, soft organic scales, some corrosion by-products.
• Useful for cleaning tubes with thin wall metal inserts or epoxy type coatings.
![Page 34: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/34.jpg)
Metal Scrapers
• Used for harder types of deposits such as calcium carbonate.
• The blades are mounted on a spindle.
• One end of the spindle is a serrated plastic disc that allows a jet of water to propel the cleaners through the tube.
![Page 35: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/35.jpg)
Metal U-tube Cleaners
![Page 36: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/36.jpg)
How does this technique work?
• Spring loaded tube cleaner (Bullets) are shot through fouled Condenser tubes using specially designed water guns at 1.5-2.5 MPa water pressure with velocities 3-6 m/s.
• Tube cleaners exit at the end of the condensers, hitting a collection screen hung at the other end.
• These cleaners are collected, cleaned and used again. Normally a bullet can be used 10 to 15 times.
![Page 37: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/37.jpg)
Water Gun & its pumping system
![Page 38: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/38.jpg)
Hydrodrilling• Used to remove difficult deposits from the inside of tubes .
• Hard deposits such as ( Calcium, sulfur and oxides).
• Could be used on-site therefore eliminating the need for
bundles to
be sent off-site for cleaning treatments.
• Polishes tube internal diameter to as-new condition.
![Page 39: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/39.jpg)
Advantages of Hydrodrilling• It uses a small a volume of water (2 to 3 GPM at 200 to 300
PSI) that is filtered and recycled through a booster pump.
• Greater heat transfer efficiency.
• Less scheduled cleaning time and cost.
Cleaning effects for a calcium carbonate scale:
Before After
![Page 40: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/40.jpg)
In-Line Mechanical Cleaning
• Balls that are slightly larger in diameter than the tubes.• Ball injection nozzle. • Ball strainer.• Ball recirculating pump.• Ball collector.
• The tube cleaning system consists of:
![Page 41: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/41.jpg)
Ball Strainer
Sponged balls
![Page 42: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/42.jpg)
Air Cooled Condensers
![Page 43: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/43.jpg)
External surfaces fouling
Dirt, dust & debris
Pollen & Leaves
Insects & bird carcasses
![Page 44: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/44.jpg)
Cleaning External Tubes Surfaces
Fire hose High pressure handlance
Automated cleaning machine
![Page 45: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/45.jpg)
Fire hose
• Uses low pressurized water but with high volume flow rates.
• Has low washing effect.
Advantages:
• The galvanized surfaces of the tubes and fins are not damaged by this method.
Disadvantages:
• Unit must be taken out of service and scaffolding erected.• Improvements are quite small, since only a portion of debris is
removed, remainder being compacted between tube fins
![Page 46: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/46.jpg)
High pressure handlance
• Low water consumption and a high water pressure
• Latter can damage galvanized surfaces and/or snap off fins
• Unit must be taken out of service and scaffolding erected
• Again, improvements are quite small since only portion of
debris is
removed, remainder being compacted between tube fins
![Page 47: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/47.jpg)
Automated Cleaning Machine
• 60 GPM at 1,000-2,000 psi water pressure avoids fin and tube
surface
damage.
• Adjustable nozzle design, distance from surface and jet energy.
• Water contains no additives.
• Fouling removed effectively and uniformly.
• No need to shut unit down or erect scaffolding.
• Nozzle beam optimally matched to tube bundle geometry with
a constant jet angle.
![Page 48: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/48.jpg)
Forms of Automated Cleaning Machine
Permanently installed system
Semi-automatic
system
Portable service unit
![Page 49: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/49.jpg)
Permanently installed system
The system is supplied for each side of the ACC & controlled automatically
![Page 50: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/50.jpg)
Semi-automatic system
• The guide rails are permanently installed.
• The nozzle beam carriage being moved from section to section
by the labour.
![Page 51: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/51.jpg)
Portable service unit
The unit has a portable nozzle beam carriage and control unit
![Page 52: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/52.jpg)
Cleaning Results
Fouled
During cleaning
Cleaned
![Page 53: Prof. Osama El Masry Steam Condenser I Mechanical Engineering Department ME332 Operation and Management of Power Plants Prof. Osama A El Masry](https://reader036.vdocuments.us/reader036/viewer/2022081501/56649e185503460f94b04027/html5/thumbnails/53.jpg)
Conclusion
Surfaces should be kept clean to increase generation capacity & reduce the
associated costs.