Medium Voltage Distribution Product Environmental Profile Premset 15 kV D02N, D06H and I06T functional units PE90545 D02N D06H I06T

Upload: lymien

Post on 23-Apr-2018

275 views

Category:

Documents


7 download

TRANSCRIPT

Page 1: Product Environmental Profile - Schneider Electric · Product Environmental Profile. Premset 15 kV D02N, D06H and I06T functional units . ... D06H and I06T functional units are manufactured

Medium Voltage Distribution

Product Environmental Profile Premset 15 kV D02N, D06H and I06T functional units

PE

9054

5

D02N D06H I06T

Page 2: Product Environmental Profile - Schneider Electric · Product Environmental Profile. Premset 15 kV D02N, D06H and I06T functional units . ... D06H and I06T functional units are manufactured

Product Environmental Profile - PEP

Premset 15kV D02N and D06H core units are dedicated to protection, disconnection and earthing of circuits. They associate a disconnecting Circuit Breaker and a downstream earthing switch.

Product overview

D02N The D02N is dedicated to MV/LV transformer protection with a 200Amp Circuit Breaker.

D06H The D06H is dedicated to incoming lines or feeders protection with 630 Amp Circuit Breaker.

I06T

The representative products used for the analysis are the Premset 15 kV D02N, D06H and I06T functional units, including these items.

Rated voltage Ur (kV) 12 15 Rated current Ir (A rms) 100 (D01N) - 200 (D02N) Rated short-time withstand current and duration

Ik (kA rms) 25 25 20 21 21

tk (s) 1 2 4 1 3

Short-circuit breaking capacity Isc (kA rms) 25 25 20 21 21 Rated making capacity of Circuit Breaker and earthing switches

Icm (kA peak) 65 65 52 54 54

No-load mechanical endurance of Circuit Breaker

M1 class (IEC 62271-100)

Number of operations

2000

Electrical endurance of Circuit Breaker

E2 class (IEC 62271-100)

Number of operations

Acc. E2 class, without reclosing duty

Operating sequence O - 15 s - CO Maximum number of operations at Isc 5 Total clearing time at Isc Fault detection to

arc extinguishing (ms) < 60

No-load mechanical endurance of earthing switch

M0 class (IEC 62271-102)

Number of operations

1000

Making capacity endurance of earthing switch

E2 class (IEC 62271-102)

Number of operations

5

Rated voltage Ur (kV) 12 15 Rated current Ir (A rms) 630 Rated short-time withstand current and duration

Ik (kA rms) 25 25 20 21 21

tk (s) 1 2 4 1 3

Short-circuit breaking capacity Isc (kA rms) 25 25 20 21 21 Rated making capacity of Circuit Breaker and earthing switches

Icm (kA peak) 65 65 52 54 54

Capacitive breaking capacity (IEC 62271-100) Capacitive break class

CC2 / LC2

No-load mechanical endurance of Circuit Breaker

M2 class (IEC 62271-100)

Number of operations

10000

Electrical endurance of Circuit Breaker

E2 class (IEC 62271-100)

Number of operations

Acc. E2 class, without reclosing duty

Operating sequence O - 0.3 s - CO -15 s - CO Maximum number of operations at 100% Isc > 50 Total clearing time at Isc Fault detection to

arc extinguishing (ms) < 100

No-load mechanical endurance of earthing switch

M0 class (IEC 62271-102)

Number of operations

1000

Making capacity endurance of earthing switch

E2 class (IEC 62271-102)

Number of operations

5

Premset 15kV I06T core unit is dedicated to switching, disconnection and earthing of circuits. They associate a disconnecting load-break switch and a downstream earthing switch.

Rated voltage Ur (kV) 12 15 Rated current Ir (A rms) 630 Rated short-time withstand current and duration

Ik (kA rms) 25 25 20 21 21

tk (s) 1 2 4 1 3

Rated making capacity of main and earthing switches

Icm (kA peak) 65 65 52 54 54

No-load mechanical endurance of main switch

M1 class (IEC 62271-103)

Number of operations

1000

Electrical endurance of main switch

E3 class (IEC 62271-103)

Number of operations

100

Making capacity endurance of main switch

E3 class (IEC 62271-103)

Number of operations

5

No-load mechanical endurance of earthing switch

M0 class (IEC 62271-102)

Number of operations

1000

No-load capacity endurance of earthing switch

E2 class (IEC 62271-102)

Number of operations

5

• D02N functional unit and D06H functional unit: - The Core unit with embedded and screened vacuum bottles, the 3-position mechanism CI1 type (D02N) or 0-C0 type (D06H), the earthing switch. - The bottom compartment and the cable connections. - The VIP 40 (D02N) or VIP 400 (D06H) protection, with relay, current transformers, and actuator. - The busbar system. • I06T functional unit: - The Core unit with embedded and screened vacuum bottles, the 3-position mechanism CIT type, the earthing switch. - The bottom compartment and the cable connections. - The cable testing device. - The busbar system.

The environmental impacts of thesereferenced productsare representativeof the impactsof the other productsof the range whichare developed witha similar technology.The environmental analysis was performedin conformitywith ISO 14040.

Page 3: Product Environmental Profile - Schneider Electric · Product Environmental Profile. Premset 15 kV D02N, D06H and I06T functional units . ... D06H and I06T functional units are manufactured

Constituent materials The mass of the Premset 15 kV D02N functional unit is 162 kg, including the packaging. The constituent materials are distributed as follows:

DE

9021

9

Steel 45.2% Epoxy resin 21.8 %

PC polycarbonate 1.6%

PE polyethylene 1.0%

Wood 7.4 % Elastomer 4.1% Other materials under 0.4% with a total of 0.6 %

PBT polybutylene terephtalate 0.6 % PA polyamide 0.5% PET polyethilene terephtalate 0.4%

Aluminium 6.5 % Copper 5.7% Stainless steel 2.1% Ferrous alloys 1.6 % Zinc 0.4% Brass 0.4%

The mass of the Premset 15 kV D06H functional unit is 162 kg, including the packaging. The constituent materials are distributed as follows:

PBT polybutylene terephtalate 0.6% Wood 7.4% Elastomer 4.1% Other materials under 0.4%

DE

9021

9

Steel 45.4% Epoxy resin 21.8 %

PC polycarbonate 1.6%

PE polyethylene 1.0%

with a total of 0.7% PA polyamide 0.5% PET polyethilene terephtalate 0.4%

Aluminium 6.5 % Copper 5.9% Stainless steel 2.2% Ferrous alloys 1.1 % Zinc 0.4% Brass 0.4%

The mass of the Premset 15 kV I06T functional unit is 168 kg, including the packaging. The constituent materials are distributed as follows:

DE

9022

0

Steel 45.0% Epoxy resin 21.1 %

PC polycarbonate 2.9%

PE polyethylene 1.1%

Wood 7.1 % Elastomer 4.0% Other materials under 0.06% with a total of 0.1%

PA polyamide 0.4% PP polypropylene 0.1% PBT polybutylene terephtalate 0.1 %

Copper 8.3% Aluminium 6.2% Stainless steel 2.1% Brass 0.9 % Zinc 0.4% Non ferrous alloys 0.2%

Page 4: Product Environmental Profile - Schneider Electric · Product Environmental Profile. Premset 15 kV D02N, D06H and I06T functional units . ... D06H and I06T functional units are manufactured

The mass of the Premset 15 kV D02N functional unit is 162 kg, including the packaging.The constituent materials are distributed as follows:

Substance assessment Products of this range are designed in conformity with the requirements of the RoHS directive (European Directive 2002/95/EC of 27 January 2003) and do not contain, or only contain in the authorised proportions, lead, mercury, cadmium, hexavalent chromium or flame retardants (polybrominated biphenyls - PBB, polybrominated diphenyl ethers - PBDE) as mentioned in the directive.

Manufacturing The Premset 15 kV D02N, D06H and I06T functional units are manufactured at Schneider Electric production sites on which an ISO14001 certified environmental management system has been established.

Distribution The Premset 15 kV D02N, D06H and I06T functional units weight and volume of the packaging have been optimized, based on the European Union’s packaging directive. The packaging weight is 13.7kg. It consists of 12kg of wood and 1.7kg of polyethylene.

Use The products of the 15 kV D02N, D06H and I06T functional units do not generate environmental pollution (noise, emissions) requiring special precautionary measures in standard use. The dissipated power depends on the conditions under which the product is implemented and used. • For the referenced 15kV D02N functional unit, it is 44.4W at the nominal intensity and 3.996W at 30% of the nominal intensity. • For the referenced 15kV D06H functional unit it is 440.6W at the nominal intensity and 39.65W at 30% of the nominal intensity. • For the referenced 15kV I06T functional unit it is 440.6W at the nominal intensity and 39.65W at 30% of the nominal intensity. These thermal dissipations are negligible compared with the power which passes through the product.

End of life At end of life, the products in the 15 kV D02N, D06H and I06T functional units have been optimized to decrease the amount of waste and allow recovery of the product components and materials. This product range contains battery, external electric cables, Printed Circuit Boards that should be separated from the stream of waste so as to optimize end-of-life treatment by special treatments. The location of these components and other recommendations are given in the End of Life Instruction document which is available for this product range. The recyclability potential of the products has been evaluated using the “Codde- BV recyclability and recoverability calculation method” (version V1, 20 Sep. 2008 presented to the French Agency for Environment and Energy Management: ADEME). According to this method, the potential recyclability ratio is: 66%. As described in the recyclability calculation method this ratio includes only metals and plastics which have proven industrial recycling processes.

Distribution (D), Installation (I) Use (U), and End of life (E). • Modeling hypothesis and method: - The calculation was performed on the 15 kV D02N, D06H and I06T functional units. - Product packaging is included. - Installation components: no special components included. - Scenario for the Use phase: this product range is included in the category 1 Energy passing product and the assumed service life is 20 years. • The dissipated power depends on the conditions under which the product is implemented and used. - For the referenced 15kV D02N functional unit, it is 3,996 W At 30% of the nominal intensity and 44,4 W at the nominal intensity. - For the referenced 15kV D06H and I06T functional units, it is 39,65 W at 30% of the nominal intensity and 440,6 W at the nominal intensity. • These thermal dissipations are negligible compared with the power which passes through the product. • The electrical power model used for calculation is European model. • End of life impacts are based on a worst case transport distance to the recycling plant (1000km).

Environmental impacts Life cycle assessment has been performed on the following life cycle phases: Materials and Manufacturing (M),

Page 5: Product Environmental Profile - Schneider Electric · Product Environmental Profile. Premset 15 kV D02N, D06H and I06T functional units . ... D06H and I06T functional units are manufactured

Indicator Unit Sum M D I U e

Raw Material Depletion Y-1 2.01E-12 2.00E-12 1.26E-15 0.00E+00 9.10E-15 3.31E-16

Energy Depletion MJ 2.34E+04 1.42E+04 9.20E+02 0.00E+00 8.01E+03 2.42E+02

Water depletion dm3 6.90E+03 5.64E+03 8.74E+01 0.00E+00 1.16E+03 2.30E+01

Global Warming g≈CO 2 1.03E+06 5.31E+05 7.29E+04 0.00E+00 4.05E+05 1.92E+04

Ozone Depletion g≈CFC-11 2.17E-01 1.30E-01 5.15E-02 0.00E+00 2.20E-02 1.36E-02

Air Toxicity m3 3.19E+08 2.34E+08 1.37E+07 0.00E+00 6.71E+07 3.62E+06

Photochemical Ozone Creation g ≈ C 2H4 4.41E+02 2.26E+02 6.23E+01 0.00E+00 1.37E+02 1.64E+01

Air acidification g ≈ H + 1.92E+02 1.26E+02 9.29E+00 0.00E+00 5.46E+01 2.45E+00

Water Toxicity dm3 2.79E+05 1.52E+05 9.11E+03 0.00E+00 1.15E+05 2.40E+03

Water Eutrophication g≈PO 4 4.04E+01 3.80E+01 1.21E+00 0.00E+00 9.51E-01 3.19E-01

Hazardous waste production kg 2.22E+01 1.54E+01 2.71E-02 0.00E+00 6.71E+00 7.14E-03

Product Environmental Profile - PEP

Presentation of productenvironmental impacts D02N functional unit: 15 kV

Indicator Unit Sum M D I U e

Raw Material Depletion Y-1 2,36E-12 2,27E-12 7,79E-16 0,00E+00 9,03E-14 3,43E-16

Energy Depletion MJ 9,45E+04 1,41E+04 5,71E+02 0,00E+00 7,95E+04 2,51E+02

Water depletion dm3 1,77E+04 6,13E+03 5,42E+01 0,00E+00 1,15E+04 2,39E+01

Global Warming g≈CO2 4,61E+06 5,29E+05 4,52E+04 0,00E+00 4,01E+06 1,99E+04

Ozone Depletion g≈CFC-11 3,73E-01 1,09E-01 3,20E-02 0,00E+00 2,18E-01 1,41E-02

Air Toxicity m3 9,65E+08 2,86E+08 8,52E+06 0,00E+00 6,66E+08 3,75E+06

Photochemical Ozone Creation g ≈ C2H4 1,61E+03 1,98E+02 3,87E+01 0,00E+00 1,36E+03 1,70E+01

Air acidification g ≈ H+ 6,92E+02 1,41E+02 5,77E+00 0,00E+00 5,42E+02 2,54E+00

Water Toxicity dm3 1,32E+06 1,65E+05 5,66E+03 0,00E+00 1,15E+06 2,49E+03

Water Eutrophication g≈PO4 5,03E+01 3,97E+01 7,52E-01 0,00E+00 9,43E+00 3,31E-01

Hazardous waste production kg 8,43E+01 1,77E+01 1,68E-02 0,00E+00 6,66E+01 7,40E-03

Indicator Unit Sum M D I U e

Raw Material Depletion Y-1 2.10E-12 2.01E-12 6.89E-16 0.00E+00 9.03E-14 3.31E-16

Energy Depletion MJ 9.41E+04 1.38E+04 5.05E+02 0.00E+00 7.95E+04 2.43E+02

Water depletion dm3 1.72E+04 5.66E+03 4.80E+01 0.00E+00 1.15E+04 2.30E+01

Global Warming g≈CO2 4.60E+06 5.24E+05 4.00E+04 0.00E+00 4.01E+06 1.92E+04

Ozone Depletion g≈CFC-11 3.89E-01 1.29E-01 2.83E-02 0.00E+00 2.18E-01 1.36E-02

Air Toxicity m3 9.14E+08 2.37E+08 7.54E+06 0.00E+00 6.66E+08 3.62E+06

Photochemical Ozone Creation g ≈ C2H4 1.62E+03 2.14E+02 3.42E+01 0.00E+00 1.36E+03 1.64E+01

Air acidification g ≈ H+ 6.76E+02 1.26E+02 5.10E+00 0.00E+00 5.42E+02 2.45E+00

Water Toxicity dm3 1.31E+06 1.53E+05 5.00E+03 0.00E+00 1.15E+06 2.40E+03

Water Eutrophication g≈PO4 4.87E+01 3.83E+01 6.65E-01 0.00E+00 9.43E+00 3.19E-01

Hazardous waste production kg 8.22E+01 1.56E+01 1.49E-02 0.00E+00 6.66E+01 7.14E-03

I06T functional unit: 15 kV

D06H functional unit: 15 kV

• Life cycle assessment has been performed with the EIME software (Environmental Impact and Management Explorer), version 4.1, and with its database version 11. •The Manufacturing phase is the life cycle phase which has the greatest impact on the majority of environmental indicators. • This product range gets the benefit of not using SF6 gas, thank to the use of vacuum and air technologies for breaking and disconnection and solid insulation.

(European Directive 2002/95/EC of 27 January 2003), they can be incorporated without any restriction within an assembly or an installation submitted to this Directive. Please note that the values given above are only valid within the context specified and cannot be used directly to draw up the environmental assessment of an installation.

System approach As the product of the range are designed in accordance with the ROHS Directive

Page 6: Product Environmental Profile - Schneider Electric · Product Environmental Profile. Premset 15 kV D02N, D06H and I06T functional units . ... D06H and I06T functional units are manufactured

Product Environmental Profile - PEP Glossary Raw Material Depletion (RMD)

Energy Depletion (ED)

Water Depletion (WD)

Global Warming (GW)

Ozone Depletion (OD)

Air Toxicity (AT)

Photochemical Ozone Creation (POC)

Air Acidification (AA)

Water Toxicity (WT)

Hazardous Waste Production (HWP)

This indicator quantifies the consumption of raw materials during the life cycle of the product. It is expressed as the fraction of natural resources that disappear each year, with respect to all the annual reserves of the material.

This indicator gives the quantity of energy consumed, whether it be from fossil, hydroelectric, nuclear or other sources. This indicator takes into account the energy from the material produced during combustion. It is expressed in MJ.

This indicator calculates the volume of water consumed, including drinking water and water from industrial sources. It is expressed in dm3.

The global warming of the planet is the result of the increase in the greenhouse effect due to the sunlight reflected by the earth’s surface being absorbed by certain gases known as "greenhouse-effect" gases. The effect is quantified in gram equivalent of CO2.

This indicator defines the contribution to the phenomenon of the disappearance of the stratospheric ozone layer due to the emission of certain specific gases. The effect is expressed in gram equivalent of CFC-11.

This indicator represents the air toxicity in a human environment. It takes into account the usually accepted concentrations for several gases in the air and the quantity of gas released over the life cycle. The indication given corresponds to the air volume needed to dilute these gases down to acceptable concentrations.

This indicator quantifies the contribution to the "smog" phenomenon (the photochemical oxidation of certain gases which generates ozone) and is expressed in gram equivalent of methane (C2H4).

The acid substances present in the atmosphere are carried by rain. A high level of acidity in the rain can cause damage to forests. The contribution of acidification is calculated using the acidification potentials of the substances concerned and is expressed in mode equivalent of H+.

This indicator represents the water toxicity. It takes into account the usually accepted concentrations for several substances in water and the quantity of substances released over the life cycle. The indication given corresponds to the water volume needed to dilute these substances down to acceptable concentrations.

This indicator calculates the quantity of specially treated waste created during all the life cycle phases (manufacturing, distribution and utilization). For example, special industrial waste in the manufacturing phase, waste associated with the production of electrical power, etc. It is expressed in kg.

We are committed to safeguarding our planet by "combining innovation and continuous improvement to meet the new environmental challenges".

©20

12 -

Sch

neid

er E

lect

ric In

dust

ries

SA

S -

All

right

s re

serv

ed

Schneider Electric Industries SAS • Registration No.: SCHN-2011-502-V0 • Writing rules: PCR PEPecopassport 2010 :1.0 35, rue Joseph Monier • Accreditation No. of verifier: VH05 CS 30323 • Programme information: www.pep-ecopassport.org F-92505 Rueil-Malmaison cedex (France) • Period of validity: 4 years Tel.: +33(0)1 41 29 70 00 • Independent verification of the declaration and data, in compliance with ISO 14025:2006 RCS Nanterre 954 503 439 • In compliance with the ISO 14025:2006 type III environmental declaration standard Capital social 896 313 776 E • The critical review of the PCR was conducted by a panel of experts chaired by. J. Chevalier (CSTB)www.schneider-electric.com • The information in the present PEP cannot be compared with information from another programme

ENVPEP 110602EN_V0 02/2012