Page 1: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

This Microgeneration Guidance Document is the property of Department for Business, Energy and

Industrial Strategy (BEIS), 1 Victoria Street, London, SW1H 0ET.

© BEIS 2018

MCS 012

Product Certification Scheme Requirements: Pitched Roof

Installation Kits

Issue 2.3

Page 2: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 2 of 49

This Standard has been approved by the Standards Management Group of the Microgeneration Certification Scheme.

This Standard was prepared by the Microgeneration Certification Scheme Working Group 10 ‘Roofing Issues’.

REVISION OF MCS PRODUCT SCHEME DOCUMENTS

The MCS Product Scheme documents will be revised by issue of revised editions or amendments. Details will be posted on the website at www.microgenerationcertification.org

Technical or other changes which affect the requirements for the approval or certification of the product or service will result in a new issue. Minor or administrative changes (e.g. corrections of spelling and typographical errors, changes to address and copyright details, the addition of notes for clarification etc.) may be made as amendments.

The issue number will be given in decimal format with the integer part giving the issue number and the fractional part giving the number of amendments (e.g. Issue 3.2 indicates that the document is at Issue 3 with 2 amendments).

Users of this Standard should ensure that they possess the latest issue and all amendments.

Page 3: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 3 of 49

TABLE OF CONTENTS

FOREWORD ............................................................................................................. 5

1. INTRODUCTION ................................................................................................ 5

2. SCOPE .............................................................................................................. 6

2.1 General Requirements ............................................................................. 6

2.2 Definitions ................................................................................................ 7

3. APPLICATIONS TO JOIN THE SCHEME .......................................................... 8

4. MANAGEMENT SYSTEMS CERTIFICATION .................................................... 8

5. CERTIFICATION AND APPROVAL ................................................................... 8

6. TECHNICAL DOCUMENTATION ..................................................................... 10

7. PERFORMANCE CRITERIA ............................................................................ 11

7.1 Resistance to wind uplift ......................................................................... 11

7.2 Fire ......................................................................................................... 11

7.3 Weathertightness.................................................................................... 11

7.4 Installation instructions ........................................................................... 11

8. CERTIFICATE CONTENT ................................................................................ 12

9. MAINTENANCE OF CERTIFICATION AND LISTING ...................................... 12

9.1 Supplier / manufacturer audits ................................................................ 13

9.2 Product audits ........................................................................................ 13

10. CERTIFICATION MARK AND LABELLING .................................................. 13

APPENDIX A........................................................................................................... 15

TABLE OF CONTENTS .......................................................................................... 16

A1. INTRODUCTION .............................................................................................. 19

A2. SCOPE ............................................................................................................. 19

A3. INSTALLATION INSTRUCTIONS ..................................................................... 20

A4. RESISTANCE TO WIND UPLIFT ..................................................................... 21

A4. 1 Test method .................................................................................................. 21

A4.2 Test criteria .................................................................................................... 22

A5. FIRE PERFORMANCE ..................................................................................... 24

A5.1 Roof integrated Systems ................................................................................ 24

A5.1.1 Alternative Methods .................................................................................... 25

A5.2 Above-roof Systems ....................................................................................... 25

A6. WEATHERTIGHTNESS .................................................................................... 26

A6.1 General .......................................................................................................... 26

Page 4: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 4 of 49

A6.2 Test methods ................................................................................................. 28

A6.2.1 Roof integrated systems .............................................................................. 28

A6.2.1.1 Test Procedure ......................................................................................... 28

A6.2.1.2 Test Criteria.............................................................................................. 30

A7. TEST REPORT ................................................................................................. 31

A7.1 Product and System Details: .......................................................................... 32

A7.2 Resistance to wind uplift ................................................................................. 33

A7.3 Fire performance ............................................................................................ 34

A7.4 Weathertightness ........................................................................................... 34

A8. REFERENCES ................................................................................................. 37

Appendix 1 .............................................................................................................. 38

Test arrangement for carrying out tests to BS EN 14437: 2004 .............................. 38

Appendix 2 .............................................................................................................. 39

Annexes A and C of BS 476 -3 : 2004 .................................................................... 39

Appendix 3 .............................................................................................................. 40

Test procedure for wind driven rain performance based upon PD CEN/TR

15601:2012 ............................................................................................................ 40

1.1 Rain and Wind Driven Rain Effects ................................................................. 40

1.2 Test Procedure ............................................................................................... 44

Appendix 4 .............................................................................................................. 46

An example of an underlay sealing ring in test for water-tightness ......................... 46

Informative Annexes................................................................................................ 47

Annex 1 ................................................................................................................... 47

Resistance to Wind Uplift ....................................................................................... 47

2. System Requirements ........................................................................................ 47

AMENDMENTS ISSUED SINCE PUBLICATION .................................................... 49

Page 5: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 5 of 49

FOREWORD 1

The following document contains provisions which, through reference in this text, constitute 2

normative or informative provisions of this document [MCS 012]. At the time of publication, the 3

editions indicated were valid. All documents are subject to revision, and parties applying this 4

document [MCS 012] are encouraged to investigate the possibility of applying the most recent 5

editions of the documents referenced. 6

7

The following document [MCS 012 issue 2.3] is a minor update to [MCS 012 issue 2.2, 8

published 10/01/2018]. Issue 2.3 is available for reference from the date of publication 9

[18/09/2018]. 10

11

Newly certified products shall comply with [MCS 012 issue 2.3] from the date of publication 12

[18/09/2018]. Issue 2.3 is mandatory from [18/03/2019] for manufacturers or importers who 13

have products currently certified to Issue 2.2. 14

15

MCS committed to working with industry when it first published MCS 012 issue 1.0 on 16th 16

March 2012, and a formal review of this Standard is currently being undertaken. Industry 17

feedback is still requested with regards to exceptions which may not fall under the remit of MCS 18

012. 19

20

1. INTRODUCTION 21

• This document identifies the evaluation and assessment requirements and practices for 22

the purposes of certification and listing of installation kits and individual components for 23

pitched roof mounted Solar PV Modules and Solar Collectors. Certification and listing of 24

products is based on evidence acceptable to the Certification Body: that the product 25

meets the Standard; 26

• that the manufacturer has staff, processes and systems in place to ensure that the 27

product delivered meets the Standard. 28

And on: 29

• periodic audits of the manufacturer and / or supplier, including testing as appropriate; 30

Page 6: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 6 of 49

• compliance with the contract with the Certification Body for listing and approval 31

including agreement to rectify faults as appropriate. 32

33

34

2. SCOPE 35

This Scheme provides ongoing independent, third party assessment and approval of companies 36

who wish to demonstrate that their pitched roof installation kits or components meet and 37

continue to meet the requirements of this standard. 38

39

The requirements of this Scheme document are not applicable to installations on flat roofs which 40

will be covered by a separate document. 41

42

2.1 General Requirements 43

2.1.1 Products which require the use of through bolts are only eligible for certification to MCS 44

012 subject to meeting the following requirements: 45

46

1. The bolt or flashing shall not transfer any load on the slates / tiles (excluding metal tiles or 47

sheets) beneath; 48

2. The system shall not rely on site applied silicone, mastic or other similar type sealants as the 49

sole method to provide a weather-tight seal; 50

3. The system must durably seal every layer of roof covering that is perforated by the bolt 51

system; 52

4. The system shall not rely on a sealing washer or plate that presses down on the slate/tile 53

(excluding metal tiles or sheets) to ensure a weather tight seal; 54

5. The bolt fixings shall not be into battens. 55

56

NOTE: This wording takes precedence over Section 4.3.9 bullets 1-5 in the MCS PV Guide. 57

Page 7: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 7 of 49

2.2 Definitions 58

2.2.1 Roof installation kit - a collection of parts or components designed to mount (a) Solar 59

Collector(s) or PV Module(s) on the roof of a building. The kit comprises all parts required to 60

provide a structurally stable fixing and ensure the weathertightness, and fire performance of the 61

roof meets the requirements of the building regulations. 62

63

2.2.2 Roof integrated installations - an installation where the Solar Collector or PV Module 64

replaces some or all of the roof covering. Including PV tiles or Thin-film PV modules bonded to 65

roof coverings such as standing seam roof sheets. 66

67

2.2.3 Above roof installations - an installation where the Solar Collector or PV Module is 68

mounted above the roof covering and fixed to the underlying roof structure through the roof 69

covering. 70

71

2.2.4 Bespoke building integrated installations - a bespoke PV unit that is manufactured in 72

varying sizes, shapes and configurations for the purpose of being built into the fabric of a 73

building - such as PV glazing, PV façade units or PV shading units. Furthermore, a BBIPV 74

product is one that is tailored and manufactured to a specific project, with a size and 75

configuration specific to that project. 76

77

2.2.5 Solar panel - this document uses the term solar panels as a collective term for solar 78

thermal collectors and PV modules. 79

80

2.2.6 Component* – an identifiable part of the solar system which may be sourced separately 81

and made available on the market, for example: 82

• Brackets/roof hooks 83

• Rails/profiles 84

• Joiners 85

• Clamps 86

• Clips 87

• Rafter bolts 88 89

Page 8: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 8 of 49

*The Component may require the use of a Solar Panel during testing to provide an indication of 90

the intended use of the component so that this can be specified on the MCS Certificate for the 91

component. The Solar Panel is not to be tested directly. 92

93

3. APPLICATIONS TO JOIN THE SCHEME 94

3.1 Applications should be made to an accredited Certification Body operating this Scheme, 95

who will provide the appropriate application form and details of the applicable fees. 96

97

4. MANAGEMENT SYSTEMS CERTIFICATION 98

4.1 Manufacturers and /or suppliers* shall operate a certified documented manufacturing quality 99

control system, in accordance with the requirements of MCS 010 “Generic Factory Production 100

Control Requirements”. 101

102

* The factory production control exercised by the manufacturers of the various components 103

must be confirmed as adequate in all cases. 104

105

4.2 Where a supplier is gathering together various components manufactured by other 106

companies, for sale as a kit, it may be possible to restrict the audit to the supplier’s office, 107

provided that they can demonstrate that they have adequate procedures in place to confirm that 108

the quality of these components is being maintained. Should this prove not to be the case, then 109

further audits may be required at some or all of the manufacturing locations. 110

111

4.3 The level of control operated for individual components should be commensurate with the 112

nature and significance of these components. For example, that exercised over a standard 113

screw and nut combination may be lower than those for specialised fixing brackets. 114

115

5. CERTIFICATION AND APPROVAL 116

5.1 Certification and approval is based on the following: 117

118

a) Evidence of compliance with: 119

Page 9: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 9 of 49

120

Roof performance tests for solar thermal collectors and PV modules (see Appendix A) 121

122

5.2 Evidence of compliance is generally accepted as independent third party testing by a UKAS 123

(or equivalent) accredited test laboratory. However, other evidence of compliance may be 124

considered at the discretion of the Certification Body (see document MCS 011 ‘Testing 125

Acceptance Criteria’). 126

127

b) Verification of the establishment and maintenance of the manufacturing company’s quality 128

management system in accordance with the Factory Production Control requirements (FPC). 129

130

c) Review of the technical documentation relating to the material, product or component. 131

132

5.3 Applications for a range of common products (product families) will be dealt with on a case 133

by case basis. For example, where one or more characteristics are the same for products with 134

similar design, construction and functionality then the results of tests for these characteristics on 135

one product may be applied to other similar products, as agreed between the 136

manufacturer/supplier and the Certification Body. 137

138

5.4 A certificate can be awarded following: 139

(i) demonstration of satisfactory compliance with this Scheme document, taking into account 140

any limitations imposed and other appropriate guidelines and satisfactory 141

verification/assessment of the manufacturer's Factory Production Control and technical 142

documentation, and 143

(ii) the submission of a complete MCS012 Performance Data Template including all relevant 144

fields to the Scheme Administrator by the Certifying Body. 145

146

Note: Please refer to the example column given in the template as a guideline. 147

148

5.5 Certificates are valid from the date of issue and are maintained and held in force subject to 149

satisfactory completion of the requirements for maintenance of certification (see Item 10), but 150

remain the property of the issuing Certification Body. 151

Page 10: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 10 of 49

152

5.6 Details of the manufacturer and the certificated product(s) are listed on the website at 153

www.microgenerationcertification.org, upon receipt of a completed MCS012 Performance Data 154

Template as provided for in Section 5.4. 155

156

6. TECHNICAL DOCUMENTATION 157

6.1 Technical documentation for the product must be submitted for review. This documentation 158

shall be presented in English, and shall be such that it can be assured that the products 159

submitted for test are equivalent to those that are to be manufactured for normal production. 160

The documentation must consist of the following as a minimum: 161

162

a) Details of intended use, application, classifications and restrictions (such as minimum roof 163

pitch) required; 164

165

b) Manufacturing drawings and/or specifications including tolerances, issue and revision 166

numbers; 167

168

c) The revision number of the product; 169

170

d) Raw material and components specifications; 171

172

e) Details of the quality plan applied during manufacture to ensure ongoing compliance; 173

174

f) Where historical test data is requested to be considered for the application, full test report and 175

details of any existing approvals (Note: each application will be dealt with on a case by case 176

basis, and further information about the acceptance of previous testing is available on request); 177

178

g) Installation, use and maintenance instructions. 179

180

Page 11: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 11 of 49

7. PERFORMANCE CRITERIA 181

The performance may be declared for whole systems tested or for individual components, 182

where appropriate and when those components are to be offered for incorporation into a wide 183

range of systems. In the latter case all uses of the components must be clarified, and it is the 184

responsibility of those supplying the whole system to show the whole system also satisfies the 185

performance criteria. 186

187

7.1 Resistance to wind uplift 188

7.1.1 A maximum wind uplift resistance shall be declared when assessed in accordance with 189

Section 4 of Appendix A. 190

7.2 Fire 191

7.2.1 A fire rating shall be declared in accordance with Section 5.1 of Appendix A, except for 192

above roof mounting kits satisfying the requirements of Section 5.2 of Appendix A. 193

7.3 Weathertightness 194

7.3.1 The mounting of the solar panels on or in the roof shall not decrease the weather 195

performance of the declared roof types when tested in accordance with section 6 of Appendix A. 196

7.4 Installation instructions 197

7.4.1 Guidance must be given on compatible solar panels and roof systems. The information 198

provided to the installer must clearly indicate how the kit is installed with different solar panels 199

and roof types including the type and number of fixings and maximum recommended spacing of 200

brackets/rails. 201

7.4.2 In particular, the following information shall be clearly and prominently shown in the 202

product installation instructions: 203

Page 12: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 12 of 49

• The maximum wind load the system achieved when assessed according to this 204

document, using the standard procedure and fixing details as described in the 205

manufacturer’s instructions; 206

• For products that can be used with a variety of different solar panels these instructions 207

should clearly describe the array design constraints (e.g. maximum module area, fixings 208

per m² etc) that need to be met in order to achieve the stated wind load result. 209

8. CERTIFICATE CONTENT 210

8.1 Certificates shall contain the name and address of the manufacturer/supplier, model and 211

reference number of the roof installation kit or components the test standard, a unique certificate 212

reference number and the issue number and date. 213

214

8.2 In addition, the certificate will include the following information: 215

216

• Roofing substrates compatible with the system and any minimum requirements e.g. 217

minimum timber size; 218

• Minimum permissible roof pitch; 219

• Whether the product is suitable for use as in roof or above roof installations; 220

• Maximum design wind uplift resistance as defined in Section 4.2.1 of Appendix A (this 221

may be a single value or a table of values for different installation configurations); 222

• The value of the partial (safety) factor(s) that have been used in determining the wind 223

uplift resistance for the product as defined in section 4.2.1 of Appendix A; 224

• Fire test result in accordance with Section 5 of Appendix A (for roof integrated only or 225

where an above roof system is assessed for use on combustible substrates). 226

227

9. MAINTENANCE OF CERTIFICATION AND LISTING 228

Certificates and listing are maintained and held in force subject to satisfactory completion of the 229

below requirements for maintenance of certification. 230

Page 13: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 13 of 49

9.1 Supplier / manufacturer audits 231

9.1.1 Certification is maintained through annual FPC quality system audits*, which shall include 232

a detailed check that the product being manufactured is to the same specification as the product 233

tested. 234

235

* Carried out in accordance with the principles discussed in Section 5. 236

237

9.2 Product audits 238

9.2.1 Product audits will be conducted as follows: 239

• review of the product technical data files including materials; 240

• review of end of line tests in accordance with the manufacturer's quality plan; 241

• repeat testing of elements from the product standard as appropriate to confirm that the 242

product continues to meet the requirements for certification and listing. 243

244

10. CERTIFICATION MARK AND LABELLING 245

10.1.1 All approved products listed under this Scheme shall be traceable to identify that they 246

have (and marked with a label to confirm that the product has) been tested and certificated in 247

accordance with the requirements of the test standard. See below for details. 248

249

10.1.2 The supplier shall use (the) Certification Mark(s) (only) in accordance with the 250

Certification Body’s instructions. 251

252

10.1.3 An example of the Certification Mark that can be used for this Scheme is as follows: 253

254

Page 14: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 14 of 49

255 256

Certificate Number MCS "XXX" 257

“Description of the Technology certificated” 258

259

10.1.4 Where ‘XXX’ is the certificate number and the logo of the Certification Body issuing the 260

certification would sit in the right hand box. 261

262

10.1.5 Companies may only use the Mark while the certification is maintained 263

264

Page 15: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 15 of 49

265

APPENDIX A 266

267

Pitched roof performance tests for solar thermal collectors 268

and PV modules 269

270

271

272

273

Page 16: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 16 of 49

TABLE OF CONTENTS 274

FOREWORD ............................................................................................................................. 5 275

1. INTRODUCTION ................................................................................................................. 5 276

2. SCOPE ............................................................................................................................... 6 277

2.1 General Requirements ............................................................................. 6 278

2.2 Definitions ................................................................................................ 7 279

3. APPLICATIONS TO JOIN THE SCHEME ........................................................................... 8 280

4. MANAGEMENT SYSTEMS CERTIFICATION .................................................................... 8 281

5. CERTIFICATION AND APPROVAL .................................................................................... 8 282

6. TECHNICAL DOCUMENTATION ......................................................................................10 283

7. PERFORMANCE CRITERIA ..............................................................................................11 284

7.1 Resistance to wind uplift ......................................................................... 11 285

7.2 Fire ......................................................................................................... 11 286

7.3 Weathertightness ................................................................................... 11 287

7.4 Installation instructions ........................................................................... 11 288

8. CERTIFICATE CONTENT .................................................................................................12 289

9. MAINTENANCE OF CERTIFICATION AND LISTING ........................................................12 290

9.1 Supplier / manufacturer audits ................................................................ 13 291

9.2 Product audits ........................................................................................ 13 292

• review of the product technical data files including materials; .............................13 293

• review of end of line tests in accordance with the manufacturer's quality plan; ...13 294

• repeat testing of elements from the product standard as appropriate to confirm 295

that the product continues to meet the requirements for certification and listing. ................13 296

10. CERTIFICATION MARK AND LABELLING ....................................................................13 297

APPENDIX A ............................................................................................................................15 298

TABLE OF CONTENTS ............................................................................................................16 299

A1. INTRODUCTION ................................................................................................................19 300

A2. SCOPE ...............................................................................................................................19 301

A3. INSTALLATION INSTRUCTIONS .......................................................................................20 302

A4. RESISTANCE TO WIND UPLIFT .......................................................................................21 303

A4. 1 Test method .................................................................................................. 21 304

Page 17: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 17 of 49

A4.2 Test criteria .................................................................................................... 22 305

A4.2.1 Method ...................................................................................................................22 306

A4.2.2 Alternative methods ................................................................................................23 307

A5. FIRE PERFORMANCE .......................................................................................................24 308

A5.1 Roof integrated Systems ................................................................................ 24 309

A5.1.1 Alternative Methods .................................................................................... 25 310

A5.2 Above-roof Systems ....................................................................................... 25 311

A6. WEATHERTIGHTNESS .....................................................................................................26 312

A6.1 General .......................................................................................................... 26 313

A6.2 Test methods ................................................................................................. 28 314

A6.2.1 Roof integrated systems ............................................................................. 28 315

A6.2.1.1 Test Procedure ........................................................................................ 28 316

A6.2.1.2 Test Criteria ............................................................................................. 30 317

A6.2.2 The performance of underlay penetrations ..............................................................30 318

A6.2.3 Above Roof Systems ..............................................................................................31 319

A6.2.3.1 Weathertightness of the penetrations through the outer surface ..........................31 320

A7. TEST REPORT ..................................................................................................................31 321

A7.1 Product and System Details: .......................................................................... 32 322

A7.2 Resistance to wind uplift ................................................................................ 33 323

A7.3 Fire performance............................................................................................ 34 324

A7.4 Weathertightness ........................................................................................... 34 325

A7.4.1 Roof integrated systems: ........................................................................................34 326

A7.4.2 Underlay penetration (both roof integrated and above roof solar systems) ..............35 327

A7.4.3 Above roof systems ................................................................................................36 328

A8. REFERENCES ...................................................................................................................37 329

Appendix 1 ................................................................................................................................38 330

Test arrangement for carrying out tests to BS EN 14437: 2004 .............................. 38 331

Appendix 2 ................................................................................................................................39 332

Annexes A and C of BS 476 -3 : 2004 .................................................................... 39 333

Appendix 3 ................................................................................................................................40 334

Test procedure for wind driven rain performance based upon PD CEN/TR 15601:2012335

40 336

Page 18: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 18 of 49

1.1 Rain and Wind Driven Rain Effects ................................................................ 40 337

1.1.1 Test specimens .......................................................................................................40 338

1.1.2 Preparation of the test specimen .............................................................................41 339

1.1.6 Rain generating facility ............................................................................................42 340

1.2 Test Procedure ............................................................................................... 44 341

Appendix 4 ................................................................................................................................46 342

An example of an underlay sealing ring in test for water-tightness ......................... 46 343

Informative Annexes .................................................................................................................47 344

Annex 1.....................................................................................................................................47 345

Resistance to Wind Uplift ....................................................................................... 47 346

2. System Requirements ........................................................................................ 47 347

AMENDMENTS ISSUED SINCE PUBLICATION ......................................................................49 348

349

350

Page 19: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 19 of 49

A1. INTRODUCTION 351

352

With the drive for low energy buildings and the greater functionality of roofs, solar panels are 353

being used in ever increasing numbers. It is important that, whilst providing additional 354

functionality, the solar panel systems do not degrade the fundamental function of the roof, which 355

is the long-term protection of the building interior from the elements. 356

357

NOTE: This document uses the term solar panels as a collective term for solar thermal collectors and PV 358

modules. 359

360

361

A2. SCOPE 362

363

This document specifies the test procedures which shall be used to demonstrate the 364

performance of solar panels and/or their installation kits or individual components under the 365

action of: 366

367

• Wind loads – resistance to wind uplift forces 368

• Fire – resistance to external fire 369

• Rainfall and wind driven rain – weather-tightness 370 371

These procedures apply to ‘in roof’ and ‘above roof’ systems fixed to pitched roofs. They do not 372

apply to systems mounted inclined above flat roofs or mounted on vertical walls. 373

374

The results of these tests shall be compared with the required performance. The informative 375

annexes provide some guidance on the performance levels necessary. 376

377

Satisfactory performance in the tests described in this document does not necessarily imply 378

compliance with the requirements of the Building Regulations. 379

Page 20: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 20 of 49

The results of the roof mounting kit’s performance against the test procedures shall be made 380

publicly available on the MCS product certificate holder’s website. 381

382

383

A3. INSTALLATION INSTRUCTIONS 384

385

The product and installation kit must come with installation instructions. The installation 386

instructions must be followed when preparing the product and installation kit for test. 387

388

389

Page 21: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 21 of 49

A4. RESISTANCE TO WIND UPLIFT 390

A4. 1 Test method 391

In the absence of a test method specifically for assessing the uplift resistance of solar panels, 392

the test method shall follow the principles and, where appropriate, the details of BS EN 14437: 393

2004 (Determination of the uplift resistance of installed clay or concrete tiles for roofing — Roof 394

system test method) (Reference 1). Note that a trial test, as specified in BS EN 14423: 2004, is 395

not always necessary – this should be decided by the test house, depending on the system. 396

Appendix 1 shows a typical PV system under test. 397

398

The test shall determine the wind uplift resistance and the following details shall be followed: 399

400

I. Where the flashing or sealing kits provide any uplift resistance then these should be 401

included in the test. 402

II. The roof pitch shall be 45deg +/- 2 degrees. 403

III. A minimum of one solar panel should be tested (or two if shared components are 404

employed) and the test shall be repeated a minimum of three times with new fixings 405

each time. 406

IV. The uplift load shall be applied using a cable(s) or equivalent methods to provide uniform 407

loads. This/these may be fixed to the solar collector by drilling a hole(s) through the 408

collector or by using suction cup devices attached to the glass cover plate, as shown in 409

Appendix 1. 410

V. The detailed construction of the test rig in terms of the batten sizes, rafter spacing and 411

all fixings shall satisfy the minimum specification (worst case) of the 412

manufacturer/supplier of the solar panel and all materials shall be of a quality typical of 413

real construction. The minimum requirements of BS 5534: 2014+A1:2015 shall also be 414

satisfied. 415

VI. Where there is a choice of fixing positions, the most onerous (weakest) shall be tested. 416

VII. The test roof should include all components of typical construction, including the 417

adjacent tiles. Alternatively, technical justification shall be provided as to why these are 418

omitted. 419

Page 22: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 22 of 49

A4.2 Test criteria 420

A4.2.1 Method 421

The characteristic value(1) of the uplift resistance shall be determined from the measured failure 422

loads and reported. 423

(1) The characteristic value has a prescribed probability of not being attained in a hypothetical 424

unlimited test series. This is defined in Annex D of BS EN 14437: 2004 for a 95% confidence 425

limit of being attained. 426

For design purposes the characteristic uplift resistance load shall be divided by an appropriate 427

partial factor (safety factor) from the relevant Euro-Code: 428

• For failure in steel or metal components – EN 1993-1-1: 2005 Design of steel structures 429

— General rules and rules for buildings. 430

• For failure in timber – EN 1995-1-1: 2004 Design of timber structures — General rules 431

and rules for buildings. 432

The certificate shall declare the maximum design uplift resistance in kilo Pascals (kPa) for 433

systems or Newtons (N) for individual fixings – the characteristic resistance divided by the 434

partial factor for the failure mode in the test. 435

436

In summary: 437

• Ultimate Limit State (the system actually fails i.e. failure criteria a, b or c below): 438

• For failure in a metal component the partial factor is 1.1 439

• For pull out from a metal component (eg. self-tapping screw or rivet) the partial 440

factor is 1.25 441

• For failure in a timber component or pull out from a timber component the partial 442

factor for design against wind loads is 1.44(2) 443

(2) This value has taken into account the influence of load duration and other parameters in-line 444

with EN1995-1 Table 2.2 and clause 2.3.1. 445

• Serviceability Limit State (no failure but the system is no longer fit for purpose, i.e. 446

failure criteria d or e below). 447

• The partial factor is 1.0 448

449

Page 23: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 23 of 49

As written, the failure criteria specified in BS EN 14437: 2004 are not appropriate to solar 450

systems and MCS 012 failure criteria shall be taken as follows: 451

452

a) Breakage of a mechanical component between the panel and the roof structure. 453

b) Pulling out or breakage of the connection of the mechanical fixing to the roof. 454

c) Breakage of elements of the solar panel. 455

d) If the maximum displacement of any roofing element exposes the under-roof then the 456

maximum deflection shall be 75 millimetre (mm). 457

e) The remaining displacement of any roofing element after releasing the force to zero exceeds 458

5mm and degrades the weathertightness of the roof. (When the 5mm limit is achieved, the test 459

should be continued until the applied load is at least 1.5 times the load measured at the 5mm 460

limit or until ultimate failure occurs. This is to ensure that the design resistance derived does not 461

exceed the ultimate resistance divided by the appropriate partial factor). 462

NOTE: 463

1. Annex 1 gives guidance regarding the required uplift resistance for a given site 464

2. When assessing the adequacy of the system, partial factors must also be applied to the design 465

loads, increasing them in accordance with Tables A1.1 and A1.2 of EN 1990: 2002. For the 466

design against wind uplift the partial factor for self-weight shall be 1.0 and for wind suction loads 467

1.5. However, in normal use solar panels may be designated with a lower consequence of failure 468

than for the supporting building structure, in accordance with Table B1 of EN 1990: 2002 + 469

A1:2005 Consequence Class CC1. As a result the partial factor for design wind loads may be 470

multiplied by 0.9 (Factor KFI for Reliability Class RC1 from Table B3 of EN 1990: 2002 + A1: 471

2005) giving a net increase of 1.35 applied to the design wind suction loads. 472

473

A4.2.2 Alternative methods 474

Where it can be demonstrated that alternative methods provide equivalent or conservative 475

(safe) values of the resistance to wind uplift then these may be used. Alternative methods may 476

be appropriate when testing individual components. 477

Depending upon the failure mode and the method of mounting other acceptable methods may 478

include: 479

480

Page 24: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 24 of 49

i) DD CEN TS 15087: 2005 Determination of the uplift resistance of installed clay and concrete 481

interlocking tiles for roofing – Test method for mechanical fasteners. (Reference 9) 482

NOTE: This test method may be appropriate for some designs of roof integrated systems. It is not suitable 483

for above-roof systems. 484

485

ii) ISO 9806: 2006 Thermal solar systems and components — Solar Collectors — Test 486

methods, or BS EN 61215: 2005, or EN 61646: 2008 providing the mounting arrangement 487

complies with the requirements of Clause 4.1 v) and vi) above. 488

489

iii) Validation by calculation alone. In some simple cases it may be possible to validate the 490

system against wind loads by calculation only. However, this is often not possible because, for 491

instance, a) the failure modes are not wholly predictable, b) tabulated fastener withdrawal loads 492

from standards are often not applicable due to the fastener diameter/timber thickness ratio. 493

494

495

A5. FIRE PERFORMANCE 496

497

The test requirements are different for roof integrated and above roof systems. 498

A5.1 Roof integrated Systems 499

Roof integrated systems shall be tested in accordance with BS 476-3: 2004 (Reference 3) or 500

DD ENV 1187: 2002 Test 4 (Reference 11), and the rating must be declared. Appendix 2 shows 501

the test arrangement. 502

503

NOTE: 504

i) Applying this test to solar systems is not without its problems and guidance is provided in 505

Annex C (normative) of BS 476-3: 2004. 506

507

ii) Past experience suggests that the flashings around and between the panels often pose the 508

greatest risk due to unprotected gaps. 509

510

Page 25: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 25 of 49

iii) For large systems it may be necessary to test more than one section to ensure the most 511

vulnerable areas are all tested. 512

A5.1.1 Alternative Methods 513

Where the PV module forms part of the fire barrier for the fire test, the certificate must also 514

state: 515

a) The make and model of each module that the fire testing of the system has been 516

performed with, and the rating in each case. 517

b) That the fire performance rating applies only to the roofing kit when used with the family 518

of modules (family as referenced within MCS005) from which the tested module(s) 519

came, or other modules that have identical material specification and design of: frame, 520

coversheet, encapsulant, backing sheet and sealant. 521

522

NOTE: 523

(i) Work is ongoing to define the module characteristics that would conserve the fire rating 524

when substituting one type of module for another. Section A5 1.1 provides interim 525

guidance. 526

(ii) An alternative means for an installer to achieve a fire rating is to use a substrate with an 527

independent fire rating (for example a barrier material with AA rating) beneath a 528

roofing kit/module combination that does not have a declared fire rating. It is 529

important to be able to verify that the system achieves a sufficient rating as a whole. 530

531

A5.2 Above-roof Systems 532

If the solar system is only used on roofs whose outer covering is non-combustible, as defined in 533

the Building Regulations, then in general no external fire test is required, otherwise the solar 534

system together with the outer roof covering shall be tested in accordance with BS 476-3: 2004 535

or DD ENV 1187: 2002 Test 4. The Certification Body is to specify whether an external fire test 536

is required in consultation with the manufacturer. 537

538

An external fire test is required on the fixings into the roof if these are perceived as increasing 539

the fire risk to the roof, for instance by large increases in the gaps between roofing components. 540

Page 26: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 26 of 49

A6. WEATHERTIGHTNESS 541

A6.1 General 542

543

The presence of the solar panel system must not decrease the weather performance of the roof 544

covering or the roof structure. 545

546

The manufacturer/supplier shall declare which generic product classes their system can be 547

used with: 548

• Profiled or flat single lapped tiles (profiled are recommended for test) 549

• Plain tiles (double lapped product) 550

• Double lapped slates (natural or synthetic) 551

• Profiled metal sheets or standing seam roof coverings 552

• Any other generic roofing type 553

554

Where a single flashing kit is specified for use with more than one generic class of roof 555

covering, then the class representing the worst case shall be tested. If the worst class is not 556

certain then other generic classes shall also be tested. 557

558

Note: Based on past experience the biggest risks of water entry are as follows: 559

560

Roof integrated systems: 561

i) The risk of water entry over the flashing kit which is around, between and, in some 562

cases, under the panels. This water entry can be, for instance, at the interface with the roof 563

covering, at the interface with the panels, or through joints in the flashings. 564

565

ii) Water entry through the roof covering related to increased gapping of the roofing 566

elements due to the presence of the solar panel system, including its fixing system. 567

568

Page 27: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 27 of 49

iii) Penetrations through the underlay can also pose a risk. Such penetrations must not 569

jeopardise the role of the underlay, as specified in BS 5534: 2014+A1:2015 (Sections 4.9 and 570

6.2) and should therefore be sealed in an appropriate and durable manner, preferably with a 571

purpose designed product. 572

573

Above roof systems: 574

i) Water entry via the penetrations through the outer roof covering. 575

576

ii) Spray entry through any gaps in the outer-roof covering created by the mounting 577

arrangement. 578

579

iii) Penetrations through the underlay can also pose a risk. Such penetrations must not 580

jeopardise the role of the underlay, as specified in BS 5534:2014+A1:2015 (Sections 581

4.9 and 6.2) and should therefore be sealed in an appropriate and durable manner, 582

preferably with a purpose designed product. 583

584

Page 28: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 28 of 49

A6.2 Test methods 585

The test methods address the leakage mechanisms. 586

587

A6.2.1 Roof integrated systems 588

A6.2.1.1 Test Procedure 589

The principles of the draft European wind driven rain test for roofs (PD CEN/TR 15601:2012) 590

shall be used to determine the wind driven rain performance of the roof integrated solar panel 591

systems. 592

593

The test shall be carried out at the minimum pitch of the tile/solar panel combination. 594

595

CEN TR15601 specifies 4 different wind-rain combinations (A – D), covering a range of severe 596

UK coastal conditions (referred to as N. European coastal in CEN TR 15601). These conditions 597

are summarised in Appendix 3. 598

599

For solar panels, provided all unprotected gaps caused by the mounting and installation 600

arrangement are no greater than those pre-existing in the roof covering before the installation of 601

the solar panels, then only Test D is mandatory; providing there is no reason to believe the 602

gapping will increase due to wind. Tests A – C are then optional. 603

604

NOTE: 605

Test D is the test with the largest rainfall rate (225mm / hour). Since the limit on the flashing is often the 606

water carrying capacity, this is a sensible compromise, addressing the highest risk leakage mechanism. 607

608

If only Test D is to be carried out then a simplified test facility may be used, which does not have the 609

pressure chamber, suction device, or fan system required in CEN TR15601. 610

611

Page 29: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 29 of 49

If the installation of the system creates unprotected gaps larger than those pre-existing then, as 612

a minimum, wind-rain combinations B and D must be tested. 613

614

The test specimen shall be constructed in accordance with the manufacturer’s laying 615

specifications (complete with tiles or other outer roof covering elements) but without the roofing 616

underlay present, so that any water entry may be observed and collected. The tiles or roofing 617

elements used shall be well established in the market with known satisfactory field performance. 618

619

The test specimen shall be mounted in the test apparatus and subjected to the chosen wind-rain 620

combination. In the case of wind-rain combinations A, B and C, a uniform suction pressure is 621

then applied to the underside of the test specimen, in increasing steps (one step every five 622

minutes) until a leakage rate of 10 grams per square metre per 5-minute (g/m2/5min) time step 623

is observed. The amount of suction required to bring about this level of leakage is the test result 624

for that wind-rain combination and provides a measure of the rain tightness of the system. 625

626

In the case of wind-rain combination D there is no applied suction, as this is simulating a zero 627

wind condition. The test specimen is subjected to the Test D rainfall for 2 minutes and any water 628

entry is noted and weighed. 629

630

The quantity of water running onto the top of the solar panel (‘run-off water’) shall be adjusted to 631

simulate the worst case (widest panel and longest rafter length of roof). The minimum simulated 632

additional rafter length above the solar panel shall be 5 metres (m). 633

634

NOTE: 635

Due to the complexity and size of solar systems, it can be difficult to get a whole panel or panels onto the 636

test rig for test. It is often necessary to make up special samples which ensure the most vulnerable parts 637

of the solar array are tested. It is necessary to ensure that all joints and other vulnerable parts of the test 638

sample are representative of normal production. Alternatively, more than one configuration should be 639

tested in order to ensure that one of each joint and interface type is tested. 640

Page 30: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 30 of 49

A6.2.1.2 Test Criteria 641

The performance of the surrounding roof covering elements which are unaffected by the 642

presence of the solar panels shall be taken as a benchmark against which to judge the 643

performance of the solar panels. To be acceptable the solar panel system shall have a level of 644

performance at least equal to that of the unaffected roofing elements, or equal to that of any 645

other roofing element of known acceptable performance. If necessary a reference test shall be 646

carried out with the test roof constructed wholly of roofing elements. The reference test must be 647

carried out at the same laboratory as the test on the solar panel system. 648

649

For wind-rain combinations A, B and C, the comparison shall be made on the basis of the level 650

of suction necessary to bring about a leakage rate of 10g/m2/5min time step. The higher the 651

level of suction required the better the performance of the system. 652

653

For wind combination D, the comparison shall be made on the basis of any water entry during 654

the two minute test period. 655

656

A6.2.2 The performance of underlay penetrations 657

The sealing arrangement for the underlay penetrations shall be tested for weather-tightness. 658

This shall be done with the underlay system fitted in place of the solar panel and tiles. The test 659

shall follow the same test procedure as the Test D of Section A6.2.1.1 but should use a rainfall 660

rate of 50 millimetres per hour (mm/hr) instead of 225mm/hr. In addition there should be no 661

direct rainfall, only run-off water applied at the top of the inclined roof rig, assuming a rafter 662

length of 5m. The product shall be deemed to have passed the test if there is no water leakage 663

through the joint with the underlay after five minutes. 664

Note: Appendix 4 shows an example of an underlay sealing device undergoing a test. 665

666

667

668

669

Page 31: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 31 of 49

A6.2.3 Above Roof Systems 670

671

Provided all unprotected gaps caused by the mounting and installation arrangement are no 672

greater than those pre-existing in the roof covering before the installation of the solar panels, 673

then only the weathertightness of the outer surface penetrations and the underlay penetrations 674

need be tested. 675

676

The penetrations through the outer surface shall be tested in accordance with Section A6.2.3.1, 677

whilst the penetrations through the underlay shall be tested in accordance with Section A6.2.2. 678

679

If the installation of the system creates unprotected gaps lager than those pre-existing, then the 680

system, including the solar panels, shall be tested in accordance with Section A6.2.1.1 and no 681

separate test is required for the penetrations through the outer roof covering. 682

683

A6.2.3.1 Weathertightness of the penetrations through the outer surface 684

685

Carry out Test D (Section A6.2.1.1) on the outer roof covering, with one or more penetrations 686

installed but without the solar panel system in place. There should be no dripping from the 687

penetration into the batten space during the two minute test period. 688

689

For some designs of penetrations a simpler ‘impermeability test’ can be considered as 690

equivalent and sufficient. This simple test follows the principles of the water impermeability test 691

in BS EN 490: 2011 or BS EN 491: 2011 (European concrete tile standard and associated test 692

methods – References 7 and 8). 693

694

A7. TEST REPORT 695

The test report shall include the following details: 696

Page 32: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 32 of 49

A7.1 Product and System Details: 697

Solar panel: 698

• Manufacturer 699

• Model 700

• Dimensions 701

o Specify roof integrated or above roof design: 702

• Supplied by (company/person) 703

• Date received 704

• Laying instructions – publication date/version/edition 705

Flashing kit (where appropriate): 706

• Manufacturer 707

• Model 708

• Supplied by (company / person) 709

• Fitting instructions – publication date/version/edition 710

Outer roof penetrations/fixings (where appropriate): 711

• Manufacturer 712

• Model 713

• Supplied by (company / person) 714

• Fitting instructions – publication date/version/edition 715

Roof covering elements included in tests: 716

• Manufacturer 717

• Model 718

719

Page 33: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 33 of 49

Performance parameters tested: 720

721

Yes / No Test dates

Resistance to wind uplift

Fire performance

Weather tightness

722

A7.2 Resistance to wind uplift 723

Specify all details of the system considered: 724

(All details influencing the uplift resistance are to be given, including all timber sizes, 725

fixings, roof covering elements and fixings of those.) 726

727

State method of assessment: 728

729

BS EN 14437:

2004

DD CEN

TS15087: 2005

EN 12975-2: 2006 or

EN 61215: 2005 or EN

61646: 2008

Calculation Other

730

State the results and conclusions including all failure modes found or considered. When an 731

appropriate EN standard or equivalent is used, the reporting should be in accordance with that 732

Standard. 733

734

735

Page 34: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 34 of 49

A7.3 Fire performance 736

Where required, report the results in accordance with BS 476-3: 2004 or DD ENV 1187: 2002 737

Test 4. 738

739

A7.4 Weathertightness 740

741

A7.4.1 Roof integrated systems: 742

State whether whole panels with flashing tested or sections. 743

(in the case of a section of a panel state the reason and the specific items tested) 744

745

Manufacturer’s declaration of generic product classes the system is suitable for: 746

747

Generic class Yes/No Minimum pitch specification

Profiled or flat single lapped tiles

Plain tiles

Double lapped slate (natural and

synthetic)

Profiled metal sheets or standing seam

Any other generic class (state)

748

Roof covering elements used as a reference (manufacturer, model, pitch and headlap) 749

Gapping information 750

Roof covering elements (without solar system): 751

• Maximum unprotected gapping (mm to an accuracy of ±1.0mm) 752

Page 35: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 35 of 49

Solar system: 753

• Maximum unprotected gapping (mm to an accuracy of ±1.0mm) 754

755

Tests carried out and result: 756

757

Test Test pitch Test Result for

system

Test Result

for

Reference

product

A Applied suction (Pascal (Pa))

at leakage rate at10g/m2/5min

B Applied suction (Pa) at

leakage rate (Pa) at

10g/m2/5min

C Applied suction (Pa) at

leakage rate (Pa) at

10g/m2/5min

D Leakage observed after 2 min

758

759

Additional Rafter length simulated (m) 760

Panel width simulated if greater than physical width of panel tested (m) 761

762

Performance assessment compared with test criteria 763

764

A7.4.2 Underlay penetration (both roof integrated and above roof solar systems) 765

Product specification (underlay seal): 766

Page 36: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 36 of 49

Manufacturer of product used 767

Model 768

Supplied by (company/person) 769

Underlay used in the test (manufacturer/product name) 770

771

Test result 772

773

A7.4.3 Above roof systems 774

If the whole system is tested then report in accordance with the roof integrated system. 775

776

If only the outer roof penetrations are tested then report as follows: 777

Gapping information 778

Roof covering elements (without solar system): 779

Maximum unprotected gapping (mm to an accuracy of ±1.0mm) 780

781

Solar system (roof covering elements with outer roof penetrations fitted): 782

Maximum unprotected gapping (mm to an accuracy of ±1.0mm) 783

784

Test carried out 785

786

Test result 787

788

Performance assessment compared with criteria 789

790

Page 37: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 37 of 49

A8. REFERENCES 791

792

• BS EN 14437: 2004 Determination of the uplift resistance of installed concrete or clay 793

tiles for roofing-roofing system test method 794

• BS 5534:2014+A1:2015 Slating and tiling for pitched roofs and vertical cladding – Code 795

of practice 796

• BS 476-3: 2004 Fire tests on building materials and structures — Classification and 797

method of test for external fire exposure to roofs 798

• BS EN 13501-1: 2007 Fire classification of construction products and building elements 799

— Classification using test data from reaction to fire tests 800

• BS EN 13501-5: 2005 Fire classification of construction products and building elements 801

— Classification using data from external fire exposure to roofs tests 802

• PD CEN/TR 15601:2012 Hygrothermal performance of buildings — Resistance to wind-803

driven rain of roof coverings with discontinuously laid small elements — Test Method 804

• BS EN 490: 2011 Concrete roofing tiles and fittings for roof covering and wall cladding 805

— Product specifications 806

• BS EN 491: 2011 Concrete roofing tiles and fittings for roof covering and wall cladding 807

— Test methods 808

• DD CEN TS15087: 2005 Determination of the uplift resistance of installed clay and 809

concrete interlocking tiles for roofing — Test method for mechanical fasteners 810

• EN 12975-2: 2006 Thermal solar systems and components — Solar collectors — Test 811

methods 812

• DD ENV 1187: 2002 Test methods for external fire exposure of roofs 813

• BS 6399-2: 1997 Loading for buildings. Code of practice for wind loads 814

• EN 1991-1-4: 2005 Eurocode 1. Actions on Structures. General actions. Wind loads. 815

• BRE Digest 489 Wind loads on roof-based photovoltaic systems 816

817

818

Page 38: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 38 of 49

Appendix 1

Test arrangement for carrying out tests to BS EN 14437: 2004

Figure A1.2 Typical PV System undergoing a wind uplift test according to the principles of BS

EN 14437 : 2004

Page 39: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 39 of 49

Appendix 2

Annexes A and C of BS 476 -3 : 2004

Figure: A2.1 A typical PV system ready for testing to BS 476-3 2004.

Page 40: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 40 of 49

Appendix 3

Test procedure for wind driven rain performance based upon PD CEN/TR

15601:2012

Figure A3.1 A PV system laid ready for wind driven rain tests

1.1 Rain and Wind Driven Rain Effects

A solar energy specimen is fitted into the wind-driven rain apparatus, the external

surface of the specimen is exposed to wind and continuously sprayed with water and

run-off water is continuously applied at the top of the specimen. At the same time an

air pressure difference between the upper and lower sides of the test specimen is

increased or decreased in specific steps. Water leakage through the test specimen

which may occur at certain air pressure differences is observed and measured.

1.1.1 Test specimens

Samples for the test specimen shall comply with the product specifications and be

representative of normal production.

The dimensions of the test specimen shall be as large as necessary to be

representative of the intended use. The test specimen shall include at least one of

every type of joint between the solar energy specimen and the surrounding roof

surface (where appropriate). In some cases with large solar energy specimens, it

might not be possible to test all of the joints simultaneously in the same test. In such

cases the testing shall be repeated to ensure that each joint is fully tested. The

Page 41: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 41 of 49

minimum number of tests shall be one. The test specimen shall include all

representative joints, where this is not possible then additional tests will be required

to test each joint separately.

1.1.2 Preparation of the test specimen

Construct the test specimen according to the manufacturer/supplier’s specification

representative of its intended use (such as roof pitch, fixing systems, etc). The test

specimen may be built in a surrounding frame to facilitate transport and fitting to the

opening of the driving rain test apparatus. The joint between test specimen and

surrounding frame shall be sealed to prevent water leakage during the test, without

disturbance to the normal occurring gaps in the specimen. If a frame is used, it shall

be able to resist the pressures applied during the test without deflecting to an extent

to influence the test results. The surround shall be prepared and installed so that any

water penetration through the test specimen is readily detectable.

1.1.3 Apparatus

The test apparatus shall consist of:

• a pressure chamber sealed to the underside of the test specimen and

connected to a pressure generator, as specified in 1.1.4 below;

• a fan system to create wind on the outside of the test specimen, as specified

in 1.1.5 below;

• a facility for generating rain, as specified in 1.1.6 below;

• provisions for creating run-off water as specified in 1.1.7 below; and

• a facility for observation and measurement of leakage as specified in 1.1.8

below.

NOTE. Apparatus of different design may produce different wind driven rain test

results, but can produce consistent comparisons of performance between different

roof covering products.

1.1.4 Pressure chamber

The pressure generator connected to the pressure chamber shall be capable of

creating a stable negative or positive pressure difference, maintained for five minutes

±10seconds (s), across the test specimen. The pressure difference shall be

measured to a maximum inaccuracy of 1% or 2.5Pa, whichever is greater. The

volume of the pressure chamber shall be sufficient to ensure uniform pressure

Page 42: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 42 of 49

conditions. A water collector shall be provided connected to the pressure chamber

capable of recording the amount of leakage water during any pressure step in the

test to a maximum inaccuracy of 2 % or 1 gram (g), whichever is greater. The

surfaces of the pressure chamber shall allow leakage water to flow freely into the

water collector.

1.1.5 Fan system

The fan system shall be capable of generating wind directed parallel to the

longitudinal axis of the test specimen. The wind flow may be horizontal or parallel to

the surface of the test specimen. The spatial variation of the wind speed shall be not

more than 10% over the test specimen. Calibrate the fan system for spatial variation

of the wind speed, by taking measurements at not less than 9 positions uniformly

distributed at a height of 200 + 10 mm over a flat boarded area which replaces the

test specimen, at the relevant roof pitch. The calibration wind speed shall be 10 + 0.5

metre per second (m/s) at the centre of the test specimen.

The wind speed (Vi) shall be measured to a maximum inaccuracy of 0.5 m/s.

The turbulence intensity (t) in the oncoming wind shall be less than 10 %.

NOTE: The turbulence intensity t (%) is expressed as t = 100u/U, where u and U are

the RMS and mean wind speeds respectively, measured over a duration of not less

than 5 minutes for this purpose.

RMS (root mean square) wind speed 1

)(1

2

==

n

U

u

n

iiV

Mean wind speed n

U

n

iiV

== 1

Where Vi is the individual wind speed;

n is the number of measurements

1.1.6 Rain generating facility

Page 43: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 43 of 49

The facility shall be capable of supplying a stable rain rate. The spatial variation shall

be not more than ±35% over the area of the test specimen during a time period of 5

min±10s. During the same time period of 5min ±10s the rainfall rate shall vary by not

more than ±2%. The rain droplet size shall be representative of natural rain,

predominantly in the range of 0.6mm to 2.5mm diameter.

The variation of rainfall over the specimen can be measured using rain collectors with

an area of 0.10 square metre (m2) to 0.20 m2 in area and arranged so that they do

not collect any run-off water during calibration. To calibrate the rain falling directly on

the test specimen, replace the test specimen with a flat board which incorporates the

rain collectors in its upper surface. The calibration should be carried out for each

wind-rain combination used. The rain shall be measured to a maximum inaccuracy of

3% or 0.2 mm/h, whichever is larger.

NOTE 1. Water droplets introduced into a high velocity air stream tend to break up

over distance. Accordingly it is recommended that the droplets are introduced far

enough above the test specimen for this process to be completed and for the

droplets to achieve the required velocity prior to impact with the test specimen.

NOTE 2: A variation of ±35% in wind driven rain distribution when combined with run-

off water (see 8.3.3.4) results in a combined variation of not more than 10%.

1.1.7 Run-off water

Run-off water shall be evenly distributed across the top of the test specimen. The

run-off rate shall not vary by more than 10% over the width of the test specimen. The

quantity of run-off water shall be measured to a maximum inaccuracy of 3%.

The run-off rate Rro shall be calculated by the formula:

Rro = Rtest W L / 60

where:

Rro is the run-off rate, in litres per minute (l/m);

Rtest is the rainfall on the roof surface in mm/h;

W is the effective width of the test specimen, in m;

L is the simulated additional rafter length above the test specimen, in m.

Unless otherwise specified, L shall be not less than 5 m.

Page 44: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 44 of 49

1.1.8 Observation and measurement of leakage

The pressure chamber shall be provided with:

a) a transparent under-surface for clear visual observation of the nature and position

of leakages which may appear on the underside of the test specimen during the test.

b) an apparatus to continuously collect and measure the amount (by weight or by

volume) of leakage water which may fall from the test specimen into the pressure

chamber during the test.

To minimise surface tension, absorption and retention of water on the internal

surfaces of the pressure chamber, the surfaces shall be smooth, non-absorbent and

inclined at a vertical angle of not less than 15° from the horizontal towards the lower

collecting apparatus during testing.

1.2 Test Procedure

Carry out the test in an environment with a temperature of between 5 degrees

Celsius (°C) to 35°C with the test specimen installed in the apparatus at the specified

roof pitch. Seal the edges of the test specimen as appropriate to prevent leakage of

water or air into or out of the pressure chamber. The test specimen shall be surface

dry before each test.

Select and continuously apply the relevant wind speed, rain-fall rate, and amount of

run-off water for each wind-rain combination as specified in Table 6.1

Table 6.1 Wind-rain conditions for Northern Europe Coastal climate zone

Climate zone Wind-rain

combination

Test conditions +

Approach Wind

speed

Vr (m/s)

Rainfall on horizontal

Rh (mm/h)

Northern

Europe Coastal

A 5 110

B 13 60

C 25 6

D 0 225

Page 45: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 45 of 49

+ Note: See PD CEN/TR 15601:2012 for the methodology to determine the wind and

rain over the roof surface, as a function of roof pitch.

In summary these combinations are:

Combination A: Low wind speed with severe rainfall rate

Combination B: High wind speed with high rainfall rate

Combination C: Severe wind speed with low rainfall rate

Combination D: Maximum rainfall rate with no wind (deluge)

In the wind-rain combinations A, B and C, measure initially the pressure difference

with the pressure box closed and adopt this pressure difference as the reference

zero for subsequent pressure changes during the test. Then reduce the pressure in

the box in steps of not less than 5 Pa and maintain each pressure step for 5 minutes

+ 10 seconds, until leakage is observed. Measure the amount of leakage water at

each pressure step, or continuously, up to the reference leakage rate.

In the deluge test, Combination D, apply the rainfall and run-off without wind and with

the pressure box open to the atmosphere, for 2 minutes + 10 seconds. Observe any

leakage and measure the amount of leakage water.

NOTE 1: The sub-test may be continued at greater pressure differences to observe

more leakage.

NOTE 2: Fine spray may leak through the joints in certain types of solar energy

specimens. Its occurrence should be recorded. Such fine spray may or may not be

regarded as leakage depending on the leakage criterion adopted.

Page 46: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 46 of 49

Appendix 4

An example of an underlay sealing ring in test for water-tightness

Figure: A4.1 An underlay sealing ring in test and subject to a very large volume of

water.

(This product is designed to seal around a rigid pipe and when used with a smaller

flexible pipe a durable flashing material is used to make the seal between the lip of

the sealing ring and the flexible pipe.)

Page 47: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 47 of 49

Informative Annexes

Annex 1

Resistance to Wind Uplift

2. System Requirements

2.1 System requirement Design Loads

The method of mechanical fixing of the collectors to the roof, and the fixing

components, must be adequate to resist the design loads derived from the relevant

parts of BS 6399 or EN 1991-1. These design loads relate to dead and imposed

loads, wind loads and other environmental loads such as snow loads. The fixings

shall be capable of resisting these loads, preferably without maintenance for their full

service lifetime.

The test method described is intended to assess the adequacy of the fixings against

wind uplift loads only.

2.2 Design wind speed

The design wind speed (and wind dynamic pressure) is used to calculate the design

wind load and may either be:

a) determined using BS 6399-2 : 1997 or EN 1991-1-4 : 2005 for a particular site

in question;

Or;

b) taken as a sensible upper estimate which will cover all buildings up to three

storeys in height anywhere in the UK, provided that topographical features

(eg; hills and valleys) are not significant. A 1 second gust wind speed with an

annual probability of 0.02 and equal to 58 ms-1 is suggested.

Where topographical features are significant the design wind speed must be checked

using BS 6399-2 : 1997 or EN 1991-1-4 : 2005.

Page 48: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 48 of 49

2.3 Design wind loads

BRE Digest 489 “Wind loads on roof-based photovoltaic systems” also provides

additional guidance on deriving the wind loads on the solar panels and their fixings.

The design wind load shall then be derived as follows:

I. For roof integrated designs;

II. For air permeable roof integrated systems, which replace roof tiles, BS 5534:

2014+A1:20151 may be used to derive the design wind loads acting on the

collectors and fixings. BS 5534: 2014+A1:2015 takes account of the

reduction in the wind loads due to the air permeability of the installed panels

and surrounding roof tiles. BS 5534: 2014+A1:2015 also presents the

principles and a test methodology for measuring the level of air permeability;

III. For non air permeable systems use BS 6399-2: 1997 or BS EN 1991-1-4:

2005 to derive the design wind loads;

IV. For on-roof systems, the wind loads shall be assessed using BS 6399-2:

1997 or EN 1991-1-4: 2005.

Additional guidance is given in BRE Digest 489.

2.4 Other requirements not tested

In addition the collector fixings have to:

• possess sufficient shear strength to resist gravitational sliding of the panel

due to its weight and imposed snow loads;

• withstand other effects such as fatigue loading due to variation in the wind

forces and differential thermal movements;

• resist abrasion against roof tiles and other nearby materials;

• be resistant to corrosion due to rain and accumulated debris.

These properties are not tested in the test method proposed.

Page 49: Product Certification Scheme Requirements: Pitched Roof ... · 129 management system in accordance with the Factory Production Control requirements (FPC). 130 131 c) Review of the

Issue: 2.3 PRODUCT CERTIFICATION SCHEME REQUIREMENTS: MCS 012

MCS 012

Date: 18/09/2018 Page 49 of 49

AMENDMENTS ISSUED SINCE PUBLICATION

Document Number: Amendment Details: Date:

Issue 1.0 First Issue 16/03/2012

Issue 1.1 Update to date of

implementation from

16/09/2012 to 31/03/2014

21/06/2013

Issue 1.2 Scope and definitions

clarified

16/12/2013

Issue 2.0 A5.1.1 Alternative Methods

for fire testing

02/11/2015

Issue 2.1 Updated implementation

timeline in FOREWARD

05/04//2016

Issue 2.2 Updated references, Minor

clarifications to A2 Scope,

A4.2.1 Method, A5.1.1,

A7.2.

10/01/2018

Issue 2.3 Update Clause 5.4 and

Clause 5.6

18/09/2018