Combined Overcurrent &Earth Fault Relay
Overcurrent Relay
Earth Fault Relay
Earth Leakage Relay
Digital Power Meter
Voltage Relay
Reverse Power Relay
Power Factor Regulator
Annunciator
Motor Protection Relay
MK 3000LMK 2200LNX 1000A
NX 233ANX 234ANX 203ANX 204A
NX 231ANX 232ANX 201ANX 202AN 201N 202
N302 / 301NX 300A / 300EANX 330ANX 302A / 301A / 301EDIN 330DIN 310 / 310EDIN 300 / 300EZCT 40S / 60S / 80S / 120S / 210S
DPM 680DPM 380 / 380BDM 38
MU 2300MU 350MU 250 / 150MX 210MX 100 / 50
RPR 415ARPR 415B
PFR 140 / 120 / 80 / 60PFR 96 / 96P
AN 112 / 120 / 128 / 136
MPR 500
reference colour tags
contents
Print Edition2018V1.2
( 423468-T )No.1 Jalan TP 7/7, Sime UEP Industrial Park,40400 Shah Alam, Selangor, Malaysia.Website: www.itmikro.comTel: +60-3-5192-7155Fax: +60-3-5192-7166
Mikro® reserves the right to make changes without further noticeto any products herein to improve reliability, function or design.The figures shown are without obligation.
w w w . i t m i k r o . c o m
3000LFeatures
Technical Data
• Multifunction numerical relay • Three-phase, three stages setting for phase
overcurrent and earth fault • Negative sequence overcurrent • IDMT and definite time • Multi-shot autoreclose • Thermal overload protection • Two groups of protection settings • Disturbance records • Inrush blocking • Trip circuit supervision • Circuit breaker failure protection • Circuit breaker monitoring and alarm • Circuit breaker open/close control • Programmable LED • RS232 and RS485 MODBUS-RTU communication • Fault, alarm and event records with timestamp • Multifunction programmable outputs • Multifunction digital inputs • Complies with IEC 60255 standard • ANSI code: 46N, 49RMS, 50P, 50G, 51P, 51G, CLP,
50BF, 74TC, 79
RATINGS AUXILIARY SUPPLYModel MK3000L-150DRated voltage : 30 ~ 120 V DCOperating voltage : 24 ~ 150 V DCModel MK3000L-240DRated voltage : 100 ~ 240 V AC or 140 ~ 340 V DCOperating voltage : 85 ~ 265 V AC or 110 ~ 370 V DCRated frequency : 50 or 60HzOperating frequency : 45 ~ 65 HzPower consumption : 8 VA max
CURRENT INPUTSRated current In, Ion : 1 or 5 A by connectionFrequency : 50 or 60 Hz nominalBurden : < 0.025 VA (1A) : < 0.3 VA (5A)Thermal withstand : 4 x In continuous : 40 x In for 2 s : 100 x In for 1 s
DIGITAL INPUTSInput type : Optically isolatedRated voltage : 20 ~ 380 V DC : 50 ~ 270 V AC
OUTPUT CONTACTSTrip Contact Relay (R1), R2, R3, R4, IRF RelayRated voltage : 250 V AC/DCContinuous carry : 5 AExpected electrical life : 100,000 operations at rated loadExpected mechanical life : 5 x 106 operations
RECORDSFault Record : Up to 50 recordsEvent Record : Up to 250 recordsAlarm Record : Up to 30 recordsDisturbance : 6 x 3s, 4 x 4s, 3 x 5s, 2 x 7s, 1 x 9sRecord Pre-Time 0.1s to [record length - 0.1s]
SETTING RANGES GENERALPhase CT primary : 1 to 10000 A Earth CT primary : 1 to 10000 AFrequency : 50 or 60 Hz
PHASE OVERCURRENTI> : 0.1 to 25 x In (Recommended up to 2 x In for IDMT delay)I> Delay type : IDMT or Definite TimetI> : 0 to 100 sI> IDMT curve : NI, VI, EI, LTI, NI 1.3/10ktI : 0.01 to 1.00I>> : 0.5 to 40 x IntI>> : 0 to 100 sI>>>? : Yes or NoI>>> : 0.5 to 40 x InI>>> Sample : Yes or NotI>>> : 0 to 100 s EARTH FAULTIo> : 0.02 to 2 x Ion (Recommended up to 0.5 x Ion for IDMT delay)Io> Delay type : IDMT or Definite TimetIo> : 0 to 100 sIo> IDMT curve : NI, VI, EI, LTI, NI 1.3/10ktIo : 0.01 to 1.00Io>> : 0.1 to 10 x IontIo>> : 0 to 100 sIo>>> : 0.1 to 10 x InIo>>> Sample : Yes or NotIo>>> : 0 to 100 s NEGATIVE SEQUENCE OVERCURRENTI2> : 0.1 to 40 x In(Recommended up to 2 x In for IDMT delay)I2> Delay type : IDMT or Definite TimetI2> : 0 to 100 sI2> IDMT curve : NI, VI, EI, LTI, NI 1.3/10ktI2 : 0.01 to 1.00I2>> : 0.1 to 40 x IntI2>> : 0 to 100 s
MK
THERMAL OVERLOADIθ> : 0.1 to 3 x InTθ : 1 to 200 minutesk : 1 to 1.5θ Trip : 50 to 200%θ Alarm : 50 to 200%
AUTORECLOSEDead Time tD1-tD4 : 0.05 to 600 sReclaim Time tR : 0.02 to 600 sInhibit Time tI : 0.02 to 600 sPhase Cycles : 0-4Earth Cycles : 0-4
MEASUREMENT RANGEPhase Current Secondary5A input : 0 to 200 A1A input : 0 to 40 A
EARTH CURRENT SECONDARY5A input : 0 to 50A1A input : 0 to 10A
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 142(w) x 165(h) x 198(d)Enclosure protection : IP54 at the panelApproximate weight : 3kg
ACCURACYCurrent accuracy : ± 3% of the set value or 20mA secondaryTiming accuracy : ± 5% or ± 30ms
COMMUNICATIONRS232 (front) : MODBUS-RTU RS485 (back) : MODBUS-RTU
Com
bined Overcurrent &
Earth Fault R
elayM
K 3000L
w w w . i t m i k r o . c o m
MK
3000LC
ombined O
vercurrent & E
arth Fault Relay
142 mm
165
mm
Front
Panel Cutout
198 mm34 mm
136
mm
Side13
9 ±1
mm
129 ±1 mm
Normal Inverse Very Inverse Long Time Inverse Extremely Inverse
Case Dimensions
Ordering Information
Typical Application Diagram 1
Typical Application Diagram 2
MODEL DESCRIPTION MK3000L - 150D For 50/60 Hz, auxiliary voltage 24 ~ 150V DCMK3000L - 240AD For 50/60 Hz, auxiliary voltage 85 ~ 265 V AC or 110 ~ 370 V DC
w w w . i t m i k r o . c o m
2200LFeatures
Technical Data
• Multifunction numerical relay
• Three-phase, three stages setting for phase overcurrent
• Two stages setting for earth fault
• IDMT and definite time
• Thermal overload protection
• Two groups of protection settings
• Trip circuit supervision
• Circuit breaker failure protection
• RS232 and RS485 MODBUS-RTU communication
• Fault, alarm and tripping records with timestamp
• Multifunction programmable outputs
• Multifunction digital inputs
• Complies with IEC 60255 standard
• ANSI code : 49RMS, 50P, 50G, 51P, 51G, CLP, 50BF, 74TC
AUXILIARY SUPPLYModel MK2200L-150DRated voltage : 30 ~ 120 V DCOperating voltage : 24 ~ 150 V DC
Model MK2200L-240ADRated voltage : 100 ~ 240 V AC or 140 ~ 340 V DCOperating voltage : 85 ~ 265 V AC or 110 ~ 370 V DCRated frequency : 50 or 60 HzOperating frequency : 45 ~ 65 HzPower consumption : 8 VA max
CURRENT INPUTSRated current, In, Ion: 1 or 5 A by connectionFrequency : 50 or 60 Hz nominalBurden : < 0.025 VA (1 A) : < 0.3 VA (5 A)Thermal withstand : 4 x In continuous : 40 x In for 2s : 100 x In for 1s
DIGITAL INPUTSInput type : Optically isolatedRated voltage : 20 ~ 380 V DC : 50 ~ 270 V AC
OUTPUT CONTACTSTrip Contact Relay R1, R2, R3, R4, IRF RelayRated voltage : 250 V AC / DCContinuous carry : 5 AExpected electrical life : 100,000 operations at rated loadExpected mechanical life : 5 x 106 operations
RECORDSFault Record : Up to 50 recordsEvent Record : Up to 250 recordsAlarm Record : Up to 30 records
SETTING RANGES
GENERALLine CT primary : 1 to 10,000 AEarth CT primary : 1 to 10,000 AFrequency : 50 or 60 Hz
PHASE OVERCURRENTI> : 0.1 to 25 x In (Recommended up to 2 x In for IDMT delay) *(Variable Steps)I> Delay type : IDMT or definite timetI> : 0 to 100 s *(Variable Steps)I> IDMT curve : NI, VI, EI, LTI, NI 1.3/10ktI : 0.01 to 1.00 (Step 0.01) I>> : 0.5 to 40 x In *(Variable Steps)tI>> : 0 to 100 s *(Variable Steps)I>>> : 0.5 to 40 x In *(Variable Steps)I>>> Sample : Yes or NotI>>> : 0 to 100 s *(Variable Steps)
EARTH FAULTIo> : 0.02 to 2 x Ion (Recommended up to 0.5 x Ion for IDMT delay)Io> Delay type : IDMT or definite timetIo> : 0 to 100 s *(Variable Steps)Io> IDMT curve : NI, VI, EI, LTI, NI 1.3/10ktIo : 0.01 to 1.00 (Step 0.01)Io>> : 0.1 to 10 x Ion *(Variable Steps)tIo>> : 0 to 100 s *(Variable Steps)
Com
bined Overcurrent &
Earth Fault R
elay
MK
THERMAL OVERLOADIθ > : 0.1 to 3 x In *(Variable Steps)Tθ : 1 to 200 minutes (Step 1)k : 1 to 1.5 (Step 0.01)θ Trip : 50 to 200% (Step 1%)θ Alarm : 50 to 200% (Step 1%)
* Variable Steps: 0.1-1.00: Step 0.01; 1.00-20: Step 0.1; >20: Step 1
MEASUREMENT RANGESPhase Current Secondary:5 A input : 0 to 200 A1 A input : 0 to 40 A
Earth Current Secondary:5 A input : 0 to 50 A1 A input : 0 to 10 A
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 142(w) x 165(h) x 198(d)Enclosure protection : IP54 at the panelApproximate weight : 2.2 kg
ACCURACYCurrent accuracy : ± 3% of the set value or 20mA secondaryTiming accuracy : ± 5% or ± 30ms
COMMUNICATIONRS232 (front) : MODBUS-RTU RS485 (back) : MODBUS-RTU
MK
2200L
w w w . i t m i k r o . c o m
142 mm
165
mm
Front
Panel Cutout
198 mm34 mm
136
mm
Side13
9 ±1
mm
129 ±1 mm
Normal Inverse Very Inverse Long Time Inverse Extremely Inverse
Case Dimensions
Ordering Information
Typical Application Diagram 1
Typical Application Diagram 2
MODEL DESCRIPTION MK2200L - 150D For 50/60 Hz, auxiliary voltage 24 ~ 150 V DCMK2200L - 240AD For 50/60 Hz, auxiliary voltage 85 ~ 265 V A or 110 ~ 370 V DC
Com
bined Overcurrent &
Earth Fault R
elayM
K 2200L
w w w . i t m i k r o . c o m
1000AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Three-phase, low-set overcurrent
• Three-phase, high-set overcurrent
• Low-set earth-fault
• High-set earth-fault
• Definite time for low-set and high-set
• Five selectable IDMT characteristic curves
• Local display of measured and set values
• Programmable relay outputs
• Non-volatile fault values recording
• Complies with IEC 60255 standard
• ANSI Code : 50P, 50N, 51P, 51N
RATINGSRated current ( In ) : 5 ARated frequency : 50 or 60 HzBurden : < 0.3 VA at InThemal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX1000A-240A(6) : 198 ~ 265 V ACModel NX1000A-240AD(6) : 85 ~ 265 V AC 110 V DC ~ 340 V DCModel MK1000A-150D(6) : 24 ~ 150 V DCSupply frequency : 50 or 60 HzV A rating : 3 VA typical
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
OUTPUT CONTACTSTrip Contacts ( R1 & R2 )Rated voltage : 250V AC / DCContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
SETTING RANGESI ) OVERCURRENT ELEMENTSLow-set ( I> ) : 0.5 A to 10.0 A, step 0.05 A : 10% to 200%, step 1%Low-set time multiplier ( kt>) : 0.05 to 1.0, step 0.01Low-set definite time ( t> ) : 0.05 to 99sHigh-set ( I>> ) : 0.5 A to 99.9 A, step 0.10 A or disable : 10% to 1998%, step 2%High-set delay time ( t>> ) : 0.05 sec to 2.5 sec, step 0.01
II ) EARTH-FAULT ELEMENTLow-set ( Io> ) : 0.10 A to 5.0 A, step 0.05 A : 2% to 100%Low-set time multiplier(kto>) : 0.05 to 1.0, step 0.01Low-set definite time ( to> ) : 0.05 to 99sHigh-set ( Io>> ) : 0.10 A to 50 A, step 0.10 A or disable : 2% to 1000%, step 2%High-set delay time ( to>> ) : 0.05 sec to 2.5 sec, step 0.01
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : 7-segment display and Red indicators
ENVIRONMENTAL CONDITIONSTemperature : -10˚C to +55˚CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Enclosure protection : IP54 at the panelApproximate weight : 0.8 kg
Com
bined Overcurrent &
Earth Fault R
elayN
X 1000A
NX
w w w . i t m i k r o . c o m
Typical Application Diagram Case Dimensions
Ordering Information
MODEL DESCRIPTION
NX1000A-240A For 50Hz system, auxiliary voltage 198 ~ 265 V AC
NX1000A-240AD For 50Hz system, auxiliary voltage 85 ~ 265 V AC or 110~340 V DC
NX1000A-150D For 50Hz system, auxiliary voltage 24 ~ 150 V DC
NX1000A-240AD6 For 60Hz system, auxiliary voltage 85 ~ 265 V AC or 110~340 V DC
NX1000A-150D6 For 60Hz system, auxiliary voltage 24 ~ 150 V DC
Com
bined Overcurrent &
Earth Fault R
elayN
X 1000A
96 mm
110 mm100 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Front
Side
Panel Cutout
96 m
m
Normal Inverse
Normal Inverse 1.3/10
Very Inverse Long Time Inverse Extremely Inverse
NX1000A
w w w . i t m i k r o . c o m
233AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Three-phase, low-set overcurrent
• Three-phase, high-set overcurrent
• Local display of measured and set values
• Definite time for low-set and high-set
• Non-volatile fault value recording
• Programmable relay outputs
• Five selectable IDMT characteristic curves
• Complies with IEC 60255 standard
• ANSI Code : 50P, 51P
RATINGSRated current ( In ) : 5 ARated frequency : 50 or 60 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX233A-240A (6) : 198 ~ 265 V ACModel NX233A-110A (6) : 94 ~ 127 V ACSupply frequency : 50 or 60 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 0.5 A to 6.0 A, step 0.05 A / 10% to 120%, step 1%Low-set time multiplier ( kt > ) : 0.05 to 1.0, step 0.01Low-set definite time (t >) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99)High-set ( I >> ) : 0.5 A to 99.9 A or disable, step 0.10 A / 10% to 1998%, step 2%High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
OUTPUT CONTACTS ( R1 & R2 )Rated voltage : 250V AC / DCContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : 7-segment display and Red indicators
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Enclosure protection : IP54 at the panelApproximate weight : 0.8 kg
Overcurrent R
elayN
X 233A
NX
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION NX233A - 240A For 50 Hz system, auxiliary voltage198 ~ 265 V ACNX233A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V ACNX233A - 240A6 For 60 Hz system, auxiliary voltage198 ~ 265 V ACNX233A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
Overcurrent R
elayN
X 233A
Typical Application Diagram Case Dimensions96 mm
110 mm100 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Front
Side
Panel Cutout
96 m
m
Normal Inverse
Normal Inverse 1.3/10
Very Inverse Long Time Inverse Extremely Inverse
NX 233A
w w w . i t m i k r o . c o m
234AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Three-phase, low-set overcurrent
• Three-phase, high-set overcurrent
• Local display of measured and set values
• Definite time for low-set and high-set
• Non-volatile fault value recording
• Programmable relay outputs
• Complies with IEC 60255 standard
• ANSI Code : 50P, 51P
NX
Overcurrent R
elayN
X 234A
RATINGSRated current ( In ) : 5 ARated frequency : 50 or 60 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX234A-240A (6) : 198 ~ 265 V ACModel NX234A-110A (6) : 94 ~ 127 V ACSupply frequency : 50 or 60 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 0.5 A to 6.0 A, step 0.05 A / 10% to 120%, step 1%Low-set definite time (t >) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99)High-set ( I >> ) : 0.5 A to 99.9 A or disable, step 0.10 A / 10% to 1998%, step 2%High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
OUTPUT CONTACTS ( R1 & R2 )Rated voltage : 250V AC / DCContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : 7-segment display and Red indicators
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Enclosure protection : IP54 at the panelApproximate weight : 0.8 kg
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION
NX234A - 240A For 50 Hz system, auxiliary supply 198 ~ 265 V AC
NX234A - 110A For 50 Hz system, auxiliary supply 94 ~ 127 V AC
NX234A - 240A6 For 60 Hz system, auxiliary supply 198 ~ 265 V AC
NX234A -110A6 For 60 Hz system, auxiliary supply 94 ~ 127 V AC
Overcurrent R
elayN
X 234A
Typical Application Diagram Case Dimensions96 mm
110 mm100 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Front
Side
Panel Cutout
96 m
m
NX 234A
w w w . i t m i k r o . c o m
203AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Low-set IDMT normal inverse relay
• High-set instantaneous relay
• Separate low-set and high-set trip indicators
• Option to disable high-set element
• Front panel access to test function
• Complies with IEC 60255 standard
• ANSI Code : 50P, 51P
Overcurrent R
elayN
X 203A
RATINGSRated current ( In ) : 5 ARated frequency : 50 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX203A-240A : 198 ~ 265 V ACModel NX203A-110A : 94 ~ 127 V ACSupply frequency : 50 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 2.0 A to 6.0 A : 40% to 120%Time multiplier ( TM ) : 0.05 to 1.0High-set ( I >> ) : I > to 10 x I > or disableHigh-set delay time (t >>) : Instantaneous
TIME CURRENT CHARACTERISTIC CURVE- Normal Inverse
OUTPUT CONTACTSTrip contact (R1) : Manual reset type Rated voltage : 250V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : Red indicator
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
ENVIRONMENTAL CONDITIONSTemperature : -10˚C to +55˚CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Approximate weight : 0.8 kg
NX
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION
NX203A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
NX203A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
Overcurrent R
elayN
X 203A
Typical Application Diagram Combined IDMT Overcurrent & Earth Fault Relays
Case Dimensions96 mm
110 mm100 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Front
Side
Panel Cutout
96 m
mNormal Inverse
NX 203A NX 203A NX 202A
w w w . i t m i k r o . c o m
204AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Low-set inverse definite time relay ( IDT )
• High-set instantaneous relay
• Separate low-set and high-set trip indicators
• Option to disable high-set element
• Front panel access to test function
• Complies with IEC 60255 standard
• ANSI Code : 50P, 51P
Overcurrent R
elayN
X 204A
RATINGSRated current ( In ) : 5 ARated frequency : 50 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX204A-240A : 198 ~ 265 V ACModel NX204A-110A : 94 ~ 127 V ACSupply frequency : 50 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 2.0 A to 6.0 A : 40% to 120%Time multiplier ( TM ) : 0.05 to 1.0High-set ( I >> ) : I > to 10 x I > or disableHigh-set delay time (t >>) : Instantaneous
OUTPUT CONTACTSTrip contact (R1) : Manual reset type Rated voltage : 250V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : Red indicator
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Approximate weight : 0.8 kg
NX
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION
NX204A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
NX204A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
Overcurrent R
elayN
X 204A
Typical Application Diagram Combined Overcurrent & Earth Fault Relays
Case Dimensions96 mm
110 mm100 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Front
Side
Panel Cutout
96 m
mInverse Definite Time
NX 204ANX 204A NX 201A
w w w . i t m i k r o . c o m
231AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Two stages settings for earth fault
• Local display of measured and set values
• Definite time for low-set and high-set (DTL)
• Non-volatile fault value recording
• Programmable relay outputs
• Complies with IEC 60255 standard
• ANSI Code : 50N, 51N
Earth Fault R
elayN
X 231A
RATINGSRated current ( In ) : 5 ARated frequency : 50 or 60 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX231A-240A (6) : 198 ~ 265 V ACModel NX231A-110A (6) : 94 ~ 127 V ACSupply frequency : 50 or 60 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 0.1 A to 5.0 A, step 0.05 A / 2% to 100%, step 1%Low-set definite time (t >) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99)High-set ( I >> ) : 0.1 A to 50 A or disable, step 0.1 A / 2% to 1000%, step 2%High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
OUTPUT CONTACTS Rated voltage : 250V AC / DCContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : 7-segment display and Red indicators
ENVIRONMENTAL CONDITIONSTemperature : -10˚C to +55˚CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Enclosure protection : IP54 at the panelApproximate weight : 0.7 kg
NX
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION
NX231A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
NX231A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
NX231A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V AC
NX231A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
Earth Fault R
elayN
X 231A
Typical Application Diagram 1 Typical Application Diagram 2
Case Dimensions96 mm
110 mm100 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Front
Side
Panel Cutout
96 m
m
NX 231A NX 231A
w w w . i t m i k r o . c o m
232AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Two stages settings for earth fault
• Local display of measured and set values
• Definite time for low-set and high-set
• Non-volatile fault value recording
• Programmable relay outputs
• Complies with IEC 60255 standard
• ANSI Code : 50N, 51N
Earth Fault R
elayN
X 232A
RATINGSRated current ( In ) : 5 ARated frequency : 50 or 60 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX232A-240A (6) : 198 ~ 265 V ACModel NX232A-110A (6) : 94 ~ 127 V ACSupply frequency : 50 or 60 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 0.1 A to 5.0 A, step 0.05 A / 2% to 100%, step 1%Low-set time multiplier (kt >) : 0.05 to 1.0, step 0.01Low-set definite time (t >) : 0.05 to 99 sec, step 0.01 (0.05 to 1.0) / 0.1 (1.0 to 99)High-set ( I >> ) : 0.1 A to 50 A or disable, step 0.1 A / 2% to 1000%, step 2%High-set delay time ( t >> ) : 0.05 sec to 2.5 sec, step 0.01
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
OUTPUT CONTACTS Rated voltage : 250V AC / DCContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : 7-segment display and Red indicators
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Enclosure protection : IP54 at the panelApproximate weight : 0.7 kg
NX
w w w . i t m i k r o . c o m
Earth Fault R
elayN
X 232A
Ordering Information
MODEL DESCRIPTION
NX232A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
NX232A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
NX232A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V AC
NX232A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
Typical Application Diagram 1 Typical Application Diagram 2
Case Dimensions96 mm
110 mm100 mm
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Front
Side
Panel Cutout
96 m
m
Normal Inverse
Normal Inverse 1.3/10
Very Inverse Long Time Inverse Extremely Inverse
NX 232A NX 232A
w w w . i t m i k r o . c o m
201AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Low-set definite time relay
• High-set instantaneous relay
• Separate low-set and high-set indicators
• Option to disable the high-set element
• Front panel access to the test function
• Complies with IEC 60255 standard
• ANSI Code : 50N, 51N
Earth Fault R
elayN
X 201A
RATINGSRated current ( In ) : 5 ARated frequency : 50 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX201A-240A : 198 ~ 265 V ACModel NX201A-110A : 94 ~ 127 V ACSupply frequency : 50 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 0.1 A to 2.0 A : 2% to 40 %Low-set delay time( DELAY ) : 0.05 to 1.0High-set ( I >> ) : I > to 10 x I > or disableHigh-set delay time (t >>) : Instantaneous
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
OUTPUT CONTACTS Trip contact (R1) : Manual reset type Rated voltage : 250V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Approximate weight : 0.6 kg
NX
w w w . i t m i k r o . c o m
Earth Fault R
elayN
X 201A
Ordering Information
MODEL DESCRIPTION
NX201A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
NX201A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
Typical Application Diagram Combined IDMT Overcurrent & Earth Fault Relays
Case Dimensions96 mm
Front96
mm
90 mm70 mm
Side
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
NX 204ANX 201A NX 201A
w w w . i t m i k r o . c o m
202AFeatures
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Low-set IDMT normal inverse relay
• High-set instantaneous relay
• Separate low-set and high-set trip indicators
• Option to disable the high-set element
• Front panel access to the test function
• Complies with IEC 60255 standard
• ANSI Code : 50N, 51N
Earth Fault R
elayN
X 202A
RATINGSRated current ( In ) : 5 ARated frequency : 50 HzBurden : < 0.3 VA at InThermal withstand : 4 x In continuous
AUXILIARY SUPPLYModel NX202A-240A : 198 ~ 265 V ACModel NX202A-110A : 94 ~ 127 V ACSupply frequency : 50 HzVA rating : 3 VA typical
SETTING RANGESLow-set ( I > ) : 0.1 A to 2.0 A : 2% to 40%Time multiplier ( TM ) : 0.05 to 1.0High-set ( I >> ) : I > to 10 x I > or disableHigh-set delay time (t >>) : Instantaneous
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50 ms
OUTPUT CONTACTS Trip contact (R1) : Manual reset type Rated voltage : 250V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
TIME CURRENT CHARACTERISTIC CURVE- IDMT normal inverse
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -10˚C to +55˚CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Approximate weight : 0.6 kgEnclosure protection : IP40 at the panel
NX
w w w . i t m i k r o . c o m
Earth Fault R
elayN
X 202A
Ordering Information
MODEL DESCRIPTION
NX202A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V AC
NX202A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V AC
Typical Application Diagram Combined IDMT Overcurrent & Earth Fault Relays
Case Dimensions96 mm
Front
96 m
m
90 mm70 mm
Side
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
Normal Inverse
NX 202A NX 203A NX 202A
w w w . i t m i k r o . c o m
201Features
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Low-set definite time relay
• High-set instantaneous relay
• Separate low-set and high-set indicators
• Option to disable the high-set element
• Front panel access to the test function
• Complies with IEC 60255 standard
• ANSI Code : 50N, 51N
Earth Fault R
elayN
201
RATINGS
Auxiliary SupplyModel N201-240ADRated voltage : 100 ~ 240 V AC or 140 ~ 340 V DCOperating voltage : 85 ~ 265 V AC or 110 ~ 370 V DCRated frequency : 50 or 60 HzPower consumption : <3 VA max
Current InputsRated current, In, Ion : 5 AFrequency : 50 or 60 Hz nominalBurden : < 0.3 VAThermal withstand : 4 x In continuous
Output ContactsTrip Contact Relay R1, R2Rated voltage : 250 V AC / DCContinuous carry : 5 AExpected electrical life : 100,000 operations at rated loadExpected mechanical life : 5 x 106 operations
SETTING RANGESLow-set (I>) : 0.1 to 2.0 A : 2% to 40%Low-set delay time(DELAY) : 0.05 to 1.0 secHigh-set (I>>) : I> to 10 x I> or disableHigh-set delay time (t>>) : Instantaneous
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50ms
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 72(w) x 72(h) x 97(d)Enclosure protection : IP40 at the panelApproximate weight : 0.3k g
N
w w w . i t m i k r o . c o m
Earth Fault R
elayN
201
Ordering Information
MODEL DESCRIPTION
N201 - 240AD For 50 Hz system, auxiliary voltage 85~265 V AC / 110~370 V DC
N201 - 240AD For 60 Hz system, auxiliary voltage 85~265 V AC / 110~370 V DC
Typical Application Diagram Case Dimensions
w w w . i t m i k r o . c o m
Features
Technical Data
• Microprocessor based numerical relay
• Current measurement based on fundamental frequency
• Low-set IDMT normal inverse relay
• High-set instantaneous relay
• Separate low-set and high-set trip indicators
• Option to disable the high-set element
• Front panel access to the test function
• Complies with IEC 60255 standard
• ANSI Code : 50N, 51N
Earth Fault R
elayN
202
RATINGS
Auxiliary SupplyModel N202-240ADRated voltage : 100 ~ 240 V AC or 140 ~ 340 V DCOperating voltage : 85 ~ 265 V AC or 110 ~ 370 V DCRated frequency : 50 or 60 HzPower consumption : <3 VA max
Current InputsRated current, In, Ion : 5 AFrequency : 50 or 60 Hz nominalBurden : < 0.3 VAThermal withstand : 4 x In continuous
Output ContactsTrip Contact Relay R1, R2Rated voltage : 250 V AC / DCContinuous carry : 5 AExpected electrical life : 100,000 operations at rated loadExpected mechanical life : 5 x 106 operations
SETTING RANGESLow-set (I>) : 0.1 to 2.0 A : 2% to 40%Low-set delay time(TM) : 0.05 to 1.0High-set (I>>) : I> to 10 x I> or disableHigh-set delay time (t>>) : Instantaneous
ACCURACYProtection thresholds : ± 5%Time delay : ± 5% with a minimum of 50ms
TIME CURRENT CHARACTERISTIC CURVE- IDMT Normal Inverse
INDICATORSAuxiliary supply : Green indicatorPick-up : Red indicatorTrip : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 72(w) x 72(h) x 97(d)Enclosure protection : IP40 at the panelApproximate weight : 0.3kg
202N
w w w . i t m i k r o . c o m
Earth Fault R
elayN
202
Ordering Information
MODEL DESCRIPTION
N202 - 240AD For 50 Hz system, auxiliary voltage 85 ~ 265 V AC / 110 ~ 370 V DC
N202 - 240AD6 For 60 Hz system, auxiliary voltage 85 ~ 265 V AC / 110 ~ 370 V DC
Typical Application Diagram Case Dimensions
Normal Inverse
w w w . i t m i k r o . c o m
N301
N302
Features
Features for N302 only
Technical Data
• Trip starting indicator
• Detection of no connection to current transformer for extra safety
• Relay tripped indicator
• High immunity to electrical interference
• Earth leakage level indicators
• Safety output contact
• Earth leakage level indicators
Earth Leakage R
elayN
302 / 301
AUXILIARY SUPPLYModel N301/302 -240AD : 85 ~ 265 V AC/ 110 ~ 370V DCRated frequency : 50 / 60 HzVA rating : 3 VA typical
SETTING RANGESSensitivity adjustment : 0.03 A to 30 ADelay time adjustment : 0 sec to 3.0 sec
PERFORMANCESetting accuracy : -15% to +0%Timing accuracy : ±5%
OUTPUT CONTACTSContact arrangement : 2 x manual reset type : NC and NO contacts availableRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorTime delay : Red indicatorTrip : Red indicatorReal-time leakage current : Red in dicator
ZERO - PHASE CURRENT TRANSFORMERTo operate with Mikro’s ZCT series of currenttransformer
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 72(w) x 72(h) x 97(d)Enclosure protection : IP40 at panelApproximate weight : 0.3kg (excluding ZCT)
302301
N
w w w . i t m i k r o . c o m
Earth Leakage R
elayN
302 / 301
Ordering Information
MODEL DESCRIPTION
N301 - 240AD For 50 Hz system, auxiliary voltage 85 ~ 265 V AC / 110 ~ 370 V DC
N302 - 240AD For 50 Hz system, auxiliary voltage 85 ~ 265 V AC / 110 ~ 370 V DC
N301 - 240AD6 For 60 Hz system, auxiliary voltage 85 ~ 265 V AC / 110 ~ 370 V DC
N302 - 240AD6 For 60 Hz system, auxiliary voltage 85 ~ 265 V AC / 110 ~ 370 V DC
Typical Application Diagram Case Dimensions
w w w . i t m i k r o . c o m
NX 300EA
NX 300A
300A300EAFeatures for NX 300A / 300EA
Features for NX 300EA only
Technical Data
• Numerical earth leakage relay
• Programmable current sensitivity and time delay
• Detection of no connection to ZCT
• Relay trip indicator
• Relay alarm indicator
• Real-time leakage current display
• 50% pre-fault indicator
• Leakage fault current recording
• Standard DIN 96x96mm panel mounting
• Protected against nuisance tripping
• Positive safety output contact
• Pre-fault alarm contact
• Remote reset function
NX
Earth Leakage R
elayN
X 300A / 300E
A
AUXILIARY SUPPLYModel NX300A / 300EA -230A : 184 ~ 276 V ACModel NX300A / 300EA -110A : 94 ~ 127 V ACRated frequency : 50 HzVA rating : 3 VA typical
SETTINGSensitivity adjustment : 30mA, 50mA, 0.10~1.00A(Step=50mA) 1.00~10.0A (Step=1.00A)Time delay adjustment : Instantaneous, 0.1~3.0sec (Step=0.1s)
PERFORMANCESetting accuracy : -15% to +0%Timing accuracy : ±5%
RECORDFault record : 3 latest tripped fault currents or “tSt” for manual test tripStorage : Non-volatile memory
INPUTRemote Reset : N.O. dry contact *
OUTPUTSTrip contact : Activated during leakage trip, manual test trip or ZCT connection errorPositive safety contact*: Activated when powerup and relay function correctlyAlarm contact* : Activated when measured leakage current exceeded 50% of IΔn.
OUTPUT CONTACTSRated voltage : 240 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSPre-fault alarm : Red indicator (Normal blink)Time delay : Red indicator (Fast blink)Leakage trip : 7-segment display and red indicatorZCT connection error : 7-segment display and red indicatorReal-time leakage current : 7-segment display
ZERO - PHASE CURRENT TRANSFORMERTo operate with Mikro’s ZCT series of currenttransformer
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensingMECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Enclosure protection : IP54 at the panelApproximate weight : 0.4 kg (excluding ZCT)
*Applicable to NX300EA series only
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION NX300A - 240AD For 50Hz system, auxiliary voltage 85~265 V AC or 110~340 V DCNX300EA - 240AD For 50Hz system, auxiliary voltage 85~265 V AC or 110~340 V DCNX300A - 230A For 50Hz system, auxiliary voltage 184~276 V ACNX300EA - 230A For 50Hz system, auxiliary voltage 184~276 V ACNX300A - 110A For 50Hz system, auxiliary voltage 94~127 V ACNX300EA - 110A For 50Hz system, auxiliary voltage 94~127 V ACNX300A - 240AD6 For 60Hz system, auxiliary voltage 85~265 V AC or 110~340 V DCNX300EA - 240AD6 For 60Hz system, auxiliary voltage 85~265 V AC or 110~340 V DCNX300A - 230A6 For 60Hz system, auxiliary voltage 184~276 V ACNX300EA - 230A6 For 60Hz system, auxiliary voltage 184~276 V ACNX300A - 110A6 For 60Hz system, auxiliary voltage 94~127 V ACNX300EA - 110A6 For 60Hz system, auxiliary voltage 94~127 V AC
Typical Application Diagram For NX 300A
Typical Application Diagram For NX 300EA
Case Dimensions96 mm
Front
96 m
m
90 mm70 mm
Side
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
Earth Leakage R
elayN
X 300A / 300E
A
NX300A
NX300EA
w w w . i t m i k r o . c o m
330AFeatures
Technical Data
• Numerical earth leakage relay
• Incorporated positive safety feature into trip contact
• One programmable contact for flexibility
• Detection of no connection to ZCT
• Relay trip / alarm indicator
• Real-time leakage current display
• Leakage fault current recording
• Remote reset function
• Standard DIN 96x96mm panel mounting
• Protected against nuisance tripping
Earth Leakage R
elayN
X 330A
AUXILIARY SUPPLYModel NX330A-230A : 184~276 V ACModel NX330A-110A : 94~127 V ACRated frequency : 50HzVA rating : 3VA typical
PERFORMANCESetting accuracy : -15% to +0%Timing accuracy : ±5%
SETTINGSensitivity adjustment : 30mA, 50mA, 0.10~1.00A (Step=50mA) 1.00~10.0A (Step=1.00A)
Time delay adjustment : Instantaneous, 0.1~3.0sec (Step=0.1s)
Number of shots : 0~30 (Step=1, 0=Disable auto re-close function)
Dead time : 1~500sec (Step=1sec)Persistent fault time : 0~500sec (Step=1sec, 0=Disable function)
Reclaim time : 0~500min (Step=1min, 0=Disable function)
Lockout auto reset time : 0~200hour (Step=1Hr, 0=Disable function)
Programmable : Option 0 = Disablecontact Option 1 = All (Option 2 to 6) Option 2 = ZCT error Option 3 = Leakage trip, test trip, re-close lockout Option 4 = Re-close lockout Option 5 = Pre-fault alarm, leakage trip, test trip, re-close lockout Option 6 = Re-close lockout, ZCT error
RECORDFault record : 3 latest tripped fault currents or “tSt” for manual test tripStorage : Non-volatile memory
INPUTRemote reset : N.O. dry contact
OUTPUTSTrip safe contact : Activated when the relay is in normal power-up condition with the measured leakage current less than 0.85 IΔn.Programmable contact : Activated according to user setting
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 A (NO) 3 A (NC)Expected electrical life : 100,000 operations at rated currentExpected mechanical life: 5 x 106 operations
INDICATORSPre-fault alarm : Red indicator (Normal blink)Time delay : Red indicator (Fast blink)Leakage trip : 7-segment display and red indicatorRe-close lockout : 7-segment display and red indicatorZCT connection error : 7-segment display and red indicatorReal-time leakage current: 7-segment display
ZERO-PHASE CURRENT TRANSFORMERTo operate with Mikro’s ZCT series of currenttransformer
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Enclosure protection : IP54 at the panelApproximate weight : 0.6 kg (excluding ZCT)
NX
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION NX330A-230A For 50Hz system, auxiliary voltage 184~276 V ACNX330A-110A For 50Hz system, auxiliary voltage 94~127 V ACNX330A-230A6 For 60Hz system, auxiliary voltage 184~276 V ACNX330A-110A6 For 60Hz system, auxiliary voltage 94~127 V AC
Typical Application Diagram Case Dimensions96 mm
Front
96 m
m
90 mm70 mm
Side
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
Earth Leakage R
elayN
X 330A
NX330A
w w w . i t m i k r o . c o m
Technical Data
Earth Leakage R
elayN
X 302A / 301A
/ 301E
AUXILIARY SUPPLYModel NX301A / 302A -240A : 198 ~ 265 V ACModel NX301A / 301E -110A : 94 ~ 127 V ACRated frequency : 50 / 60 HzVA rating : 3 VA typical
SETTING RANGESSensitivity adjustment : 0.03 A to 30 ADelay time adjustment : 0 sec to 3.0 sec
PERFORMANCESetting accuracy : -15% to +0%Timing accuracy : ±5%
OUTPUT CONTACTSContact arrangement : 1 x manual reset type : 1 x safety contact* : NC and NO contacts availableRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INPUTSRemote Test* / Reset Inputs*: N.O. dry contact
INDICATORSAuxiliary supply : Green indicatorTime delay : Red indicatorTrip : Red indicatorReal-time leakage current : Red indicator
ZERO - PHASE CURRENT TRANSFORMERTo operate with Mikro’s ZCT series of currenttransformer
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Approximate weight : 0.4 kg (excluding ZCT)
* Applicable to NX302A series only** Applicable to NX301E series only
302A301A301EFeatures
Features for NX 302A only
• Trip starting indicator
• Detection of no connection to current transformer for extra safety
• Relay tripped indicator
• High immunity to electrical interference
• Safety output contact
• Earth leakage level indicators
• Remote reset and remote test functions
NX 301E
NX 301A
NX 302A
NX
w w w . i t m i k r o . c o m
Ordering InformationMODEL DESCRIPTION NX301A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V ACNX301A - 110A For 50 Hz system, auxiliary voltage 94 ~ 127 V ACNX302A - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V ACNX302A -110A For 50 Hz system, auxiliary voltage 94 ~ 127 V ACNX301E - 240A For 50 Hz system, auxiliary voltage 198 ~ 265 V ACNX301E -110A For 50 Hz system, auxiliary voltage 94 ~ 127 V ACNX301A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V ACNX301A - 110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V ACNX302A - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V ACNX302A -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V ACNX301E - 240A6 For 60 Hz system, auxiliary voltage 198 ~ 265 V ACNX301E -110A6 For 60 Hz system, auxiliary voltage 94 ~ 127 V AC
Typical Application Diagram Case Dimensions96 mm
Front
96 m
m
90 mm70 mm
Side
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
Earth Leakage R
elayN
X 302A / 301A
/ 301ENX 301E
NX 302A
NX 301A or NX302A
w w w . i t m i k r o . c o m
Technical Data
DIN
Earth Leakage R
elayD
IN 330
AUXILIARY SUPPLYModel DIN330-230 A(6) : 184 ~ 276 V ACRated frequency : 50 or 60 HzVA rating : 3 VA typical
PERFORMANCESetting accuracy : -15% to +0%Timing accuracy : ±5%
SETTINGSensitivity adjustment : 30 mA, 50 mA, 0.10 A –1.00 A (Step = 50 mA), 1.00 A – 10.0 A (Step = 1.00 A)Time delay adjustment : Instantaneous, 0.1s – 3.0s Step = 0.10 sec.Number of shots : 0 - 30. Step = 1. 0 = Disable auto reclose functionDead time : 1 - 500 sec. Step = 1 sec.Permanent fault time : 0 - 500 sec. Step = 1 sec. 0 = Disable functionReclaim time : 0 - 500 minute Step = 1 min 0 = Disable functionLockout auto reset time : 0 - 200 hour Step = 1 Hrs 0 = Disable function
Programmable : Option 0 = Disablecontact Option 1 = All(Option 2 to 6) Option 2 = ZCT error Option 3 = Leakage trip, test trip, re-close lockout Option 4 = Re-close lockout Option 5 = Pre-fault alarm, leakage trip, test trip, reclose lockout Option 6 = Re-close lockout, ZCT error
RECORDFault record : 3 latest tripped fault currents or “tSt” for manual test tripStorage : Non-volatile memory
INPUTRemote reset : N.O. dry contact
OUTPUTSTrip safe contact : Activated when the relay is in normal power-up condition with the measured leakage current less than 0.85 IΔn.Programmable contact: Activated according to user setting
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 A (NO) 3 A (NC)Expected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORS50% pre-fault alarm : Red indicator (Normal blink)Time delay : Red indicator (Fast blink)Leakage trip : 7-segment display and red indicatorReclose lockout : 7-segment display and red indicatorZCT fault : 7-segment display and red indicatorReal time leakage current : 7-segment display
ZERO - PHASE CURRENT TRANSFORMERTo operate with Mikro’s ZCT series of currenttransformer
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : DIN rail mountingDimension (mm) : 71(w) x 85(h) x 70(d)Approximate weight : 0.4 kg (excluding ZCT)
330
Features • Numerical auto-reclosing earth leakage relay
• Incorporated positive safety feature into trip contact
• Detection of no connection to ZCT
• Relay trip / alarm indicator
• Real-time leakage current display
• Leakage fault current recording
• Remote reset function
• Standard 35mm DIN rail mounting
• Protected against nuisance tripping
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION DIN330 - 230 A For 50 Hz system, auxiliary voltage 230 V ACDIN330 - 230 A6 For 60 Hz system, auxiliary voltage 230 V AC
Typical Application Diagram Case Dimensions
Earth Leakage R
elayD
IN 330
w w w . i t m i k r o . c o m
Technical Data
DIN
Earth Leakage R
elayD
IN 310 / 310E
AUXILIARY SUPPLYDIN310-230 A(6) : 184 ~ 276 V ACDIN310E-230 A(6) : 184 ~ 276 V ACRated frequency : 50 or 60 HzVA rating : 3 VA typical
PERFORMANCESetting accuracy : -15% to +0%Timing accuracy : ±5%
SETTINGSensitivity adjustment : 30mA, 50mA, 0.10~1.00A (Step=50mA) 1.00~10.0A (Step=1.00A)Time delay adjustment : Instantaneous, 0.1~3.0sec Step=0.10 sec
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 A (NO) 3 A (NC)Expected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
RECORDFault record : 3 latest tripped fault currents or “tSt” for manual test tripStorage : Non-volatile memory
INPUTRemote reset* : N.O. dry contact
OUTPUTSTrip Contact : Activated if relay tripped or ZCT faultPositive safety contact* : Activated when ZCT is connected properly to the relayPre-fault alarm contact* : Activated when leakage current exceeded 50% of sensitivity setting
INDICATORS50% pre-fault alarm : Red indicator Time delay : Red indicatorLeakage trip : 7-segment display and red indicatorZCT fault : 7-segment display and red indicatorReal time leakage current : 7-segment display
ZERO - PHASE CURRENT TRANSFORMERTo operate with Mikro’s ZCT series of currenttransformer
ENVIRONMENTAL CONDITIONSTemperature : -5˚C to +55˚CHumidity : 56 days at 93% RH and 40˚C non-condensing
MECHANICALMounting : DIN rail mountingDimension (mm) : 71(w) x 85(h) x 70(d)Approximate weight : 0.4 kg (excluding ZCT)
310310EFeatures
Features for DIN 310E only
• Numerical earth leakage relay
• Programmable current sensitivity and time delay
• Detection of no connection to ZCT
• Relay trip indicator
• Relay alarm indicator
• Real-time leakage current display
• Leakage fault current recording
• 50% pre-fault indicator
• Standard DIN rail mounting
• Protected against nuisance tripping
• Positive safety output contact
• 50% pre-fault output contact
• Remote reset function
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION DIN310 - 230 A For 50 Hz system, auxiliary voltage 230 V ACDIN310E - 230 A For 50 Hz system, auxiliary voltage 230 V ACDIN310 - 230 A6 For 60 Hz system, auxiliary voltage 230 V ACDIN310E - 230 A6 For 60 Hz system, auxiliary voltage 230 V AC
* 60Hz system, auxiliary voltage 110V AC model available upon special request.
Typical Application Diagram For DIN 310
Typical Application Diagram For DIN 310E
Case Dimensions
Earth Leakage R
elayD
IN 310 / 310E
w w w . i t m i k r o . c o m
Technical Data
DIN
Earth Leakage R
elayD
IN 300 / 300E
AUXILIARY SUPPLYModel DIN300 / 300E -240A : 198 ~ 265 V ACModel DIN300 / 300E -110A : 94 ~ 127 V ACRated frequency : 50 / 60 HzVA rating : 3 VA typical
SETTING RANGESSensitivity setting : 30 mA, 50 mA, 75 mA, 100 mA, 125 mA, 150 mA, 200 mA, 250 mA, 300 mA, 500 mA, 750 mA, 1 A, 1.25 A, 1.5 A, 2 A, 2.5 A, 3 A, 5 A, 7.5 A, 10 A, 12.5 A, 15 A, 20 A, 25 A, 30 A.
Time delay setting : Instantaneous, 50 ms, 100 ms, 150 ms, 250 ms, 350 ms, 500 ms, 1 s, 3 s.
PERFORMANCESetting accuracy : -15% to +0%Timing accuracy : ±5%
OUTPUT CONTACTSContacts ( Trip / 50% pre-fault* )Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INPUTRemote test* / Reset inputs* : N.O. dry contacts
ZERO - PHASE CURRENT TRANSFORMERTo operate with Mikro’s ZCT series of currenttransformer
INDICATORSAuxiliary supply : Green indicatorTime delay : Red indicatorTrip : Red indicatorLeakage current* : 5 red indicators forleakage levels
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : DIN rail mounting Dimension (mm) : 71(w) x 85(h) x 70(d)Approximate weight : 0.4 kg (excluding ZCT)
* Applicable to DIN300E model only
300300EFeatures
Features For DIN 300E only
• 25 selectable sensitivity settings: 30 mA to 30 A
• 9 selectable time delays: 0 to 3s
• Earth leakage level indicators
• Detection of no connection to ZCT
• Relay tripped indicator
• Trip starting indicator
• Protected against nuisance tripping
• 50% pre-fault output contact
• Remote test and remote reset functions
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCRIPTION DIN300 - 240A For 50 Hz system, auxiliary voltage 240 V AC DIN300 - 110A For 50 Hz system, auxiliary voltage 110 V ACDIN300E - 240A For 50 Hz system, auxiliary voltage 240 V ACDIN300E - 110A For 50 Hz system, auxiliary voltage 110 V ACDIN300 - 240A6 For 60 Hz system, auxiliary voltage 240 V ACDIN300 - 110A6 For 60 Hz system, auxiliary voltage 110 V ACDIN300E - 240A6 For 60 Hz system, auxiliary voltage 240 V ACDIN300E - 110A6 For 60 Hz system, auxiliary voltage 110 V AC
Typical Application Diagram For DIN 300
Typical Application Diagram For DIN 300E
Case Dimensions
Earth Leakage R
elayD
IN 300 / 300E
w w w . i t m i k r o . c o m
Ordering Information
MODEL DESCTRIPTION WEIGHT
ZCT40S 40mm inner diameter 0.16 kgZCT60S 60mm inner diameter 0.20 kgZCT80S 80mm inner diameter 0.28 kgZCT120S 120mm inner diameter 0.57 kgZCT210S 210mm inner diameter 1.5 kg
DIMENSION(mm) ZCT Model 40S 60S 80S 120S 210SA 40 60 80 120 210B 89 105 130 180 310C 94 110 135 195 311D 6 6 6 6 6E 37 37 37 37 37F 75 87 112 159 292G 27 27 27 27 18
D d3, 3wire d4, 4wireMODEL ZCT inner Up till wire Up till wire diameter (mm) diameter (mm) diameter (mm)
ZCT 40S 40 14 12 ZCT 60S 60 23 21 ZCT 80S 80 32 29 ZCT 120S 120 51 46 ZCT 210S 210 93 83
ZCT
Earth Leakage R
elayZC
T 40S / 60S
/ 80S / 120S
/ 210S
40S60S80S120210SCase Dimensions
Example:For a single core CU / PVC insulated, non-sheathed 450 / 750 V 50mm2 conductor,it’s nominal overall diameter is 11.7mm. To pass 4 wires through the ZCT, we can useZCT40S as the maximum diameter it can support is up till 12mm.
Calculation to determine Inner Diameter of ZCT required
40S
60S
120S
80S
210S
w w w . i t m i k r o . c o m
Earth Leakage R
elayD
IN 300 / 300E
Earth Leakage R
elay
w w w . i t m i k r o . c o m
Technical Data
DPM
WIRING SYSTEMS3-phase 4-wire system3-phase 3-wire system
CURRENT MEASUREMENT (TRMS)Nominal current : 5 AMin. measurement : 5 mAAccuracy : 0.2% of full scaleBurden : < 0.05 VA at 5 AMeasurement range : 10 APulsed withstand : 100 A for 1 secCT primary : 5 ~ 50,000 A
VOLTAGE MEASUREMENT (TRMS)Nominal phase voltage : 0 ~ 300 V ACMinimum measurement : 10 VAccuracy : 0.2% at full scalePhase voltage via VT : 60 ~ 50,000 V
POWER MEASUREMENTReal power, apparent power, reactive powerAccuracy : 0.5%
POWER FACTOR MEASUREMENTTotal and displacement power factorAccuracy : 0.5%
POWER & THERMAL CURRENT DEMANDInterval : 1 ~ 30 mins
VOLTAGE AND CURRENT SEQUENCECOMPONENTSPositive, negative and zero sequence
FREQUENCY MEASUREMENTMeasurement range : 45 ~ 65 HzAccuracy : 0.2%
ENERGY MEASUREMENT ACCURACYActive : IEC 62053-22 class 0.5Reactive : IEC 62053-23 class 2
HARMONICS DISPLAYFundamental up to 32nd order
VOLTAGE & CURRENT WAVEFORMDISPLAYSimultaneous 3-phase voltage orcurrent waveforms
COMMUNICATIONProtocol : Modbus RTUInterface : Isolated RS485Protocol : Modbus TCP/IPInterface : Ethernet 10M/100M BaseTProtocol : HTTP ServerInterface : Ethernet 10M/100M BaseT
AUXILIARY POWER SUPPLYAC voltage : 90 ~ 415 V ACFrequency : 50 / 60 HzDC voltage : 100 ~ 300 V DCPower consumption : 3W typicalSustained overload : 500 V AC
ENVIRONMENTAL CONDITIONSOvervoltage category : IVPollution degree : 2Temperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : According to DIN 43700 / ANSI C39.1Dimension (mm) : 96(w) x 96(h) x 100(d)Enclosure protection : IP63 at the panel IP20 at the bodyApproximate weight : 0.5 kg
680FeaturesMeasurement Parameters: • Phase & Line Voltages (L-N, Max. and Min.) • Phase Current & Neutral Current (Max. and Min.) • Bidirectional kW, kVAR & kVA • Bidirectional kWh, kVARh & kVAh • Frequency • Total & Displacement Power Factor • Voltage Total Harmonic Distortion • Current Total Harmonic Distortion • Avg. and Max. Thermal Current Demand • Avg. and Max. Power (kW, kVA, kVAR) Demand • Current Sequence Components • Voltage Sequence Components
TFT Colour LCD DisplaySerial RS-485 Modbus RTUModbus TCP/IPBuilt-in WebserverVoltage & Current Waveform DisplayVoltage & Current Harmonics Display
Digital P
ower M
eterD
PM
680
680B
w w w . i t m i k r o . c o m
Test Standards
Ordering Information
IEC 61010-1Safety requirements.
IEC 61326-1 EMC requirements.
MODEL DESCRIPTION
DPM 680-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC, with Modbus TCP/IP and Modbus RS485 DPM 680B-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC, with Modbus RS485
Typical Application Diagrams Case Dimensions
Cut-Out Recommendations
Digital P
ower M
eterD
PM
680
101.6±0.5mm
91±0.5mm
91±0.5mm
w w w . i t m i k r o . c o m
Technical Data
DPM
DISPLAY TYPELCD display
MEASUREMENTS3-phase 4-wire system3-phase 3-wire system
CURRENT MEASUREMENT (TRMS)CT primary : 5 ~ 8000 ACT secondary : 5 AMinimum measurement : 5 mAAccuracy : 0.5% from 1A to 6 A (secondary)Burden : < 0.05 VA at 5 ASustained overload : 6 A
VOLTAGE MEASUREMENT (TRMS)Nominal phase voltage : 20 ~ 300 V ACMinimum measurement :10 VAccuracy : 0.5% at full scalePhase voltage via VT : 60 ~ 33,000 V
POWER MEASUREMENTReal power, apparent power, reactive powermeasurementMeasuring updating period : 1 sAccuracy : 1.0%
ACTIVE POWER DEMANDInterval : 1 ~ 30 mins
POWER FACTOR MEASUREMENTTotal and displacement power factorAccuracy : 1.0%
FREQUENCY MEASUREMENTMeasurement range : 45 ~ 65 HzMeasurement updating period : 1sAccuracy : 0.5%
ENERGY ACCURACYActive (according to IEC 62053-21) : class 1Reactive (according to IEC 62053-23) : class 2
AUXILIARY POWER SUPPLYAC voltage : 90 ~ 415 V ACFrequency : 50 / 60 HzDC voltage : 100 ~ 300 V DCPower consumption : <3 VA
COMMUNICATIONHardware interface : Isolated RS485Protocol : Modbus-RTUBaud rate : 2400, 4800, 9600, 19200, 38400
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 100(d)Approximate weight : 0.5 kgEnclosure protection : IP54 at the panel IP20 at the body
380380BFeaturesLCD display with back lightingModbus-RTU communication(for DPM380 only)
MEASUREMENT PARAMETERS:• Phase Voltage (L-N)• Line Voltage (L-L)• Phase Current and Neutral Current• Bidirectional kW (per phase & total)• Bidirectional kVAR (per phase & total)• Bidirectional kVA (per phase & total)• Frequency• Power Factor (per phase & total)• Energy (+ and - ) for kWh, kVARh and kVAh• THD Phase Voltage ( L-N )• THD Phase Current• Active Power (kW) Demand • Maximum Active Power (kW) Demand
Digital P
ower M
eterD
PM
380 / 380B
w w w . i t m i k r o . c o m
Electromagnetic Compatibility (EMC)
Ordering Information
Part 6-2: Generic Standards IEC61000-6-2Immunity for industrial environments.
Part 6-4: Generic Standards IEC61000-6-4Emission standard for industrial environments.
MODEL DESCRIPTION DPM 380-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC, with RS 485DPM 380B-415AD Auxiliary Voltage 90 ~ 415 V AC or 100 ~ 300 V DC
Typical Application Diagram Case Dimensions
Cut-Out Recommendations
Digital P
ower M
eterD
PM
380 / 380B
101.6±0.5mm
91±0.5mm
91±0.5mm
w w w . i t m i k r o . c o m
Technical Data
DM
DISPLAY TYPELCD display
MEASUREMENTS3-phase 4-wire system
CURRENT MEASUREMENT (TRMS)CT primary : 5 ~ 8000 ACT secondary : 5 AMinimum measurement : 10 mAAccuracy : 0.5% from 1A to 6 A (secondary)Burden : < 0.03 VA at 5 ASustained overload : 6 A
VOLTAGE MEASUREMENT (TRMS)Nominal phase voltage : 70 ~ 300 V ACMinimum measurement :10 VAccuracy : 0.5% at full scale
POWER MEASUREMENTReal power, apparent power, reactive powermeasurementMeasuring updating period : 1 sAccuracy : 1.0%
POWER FACTOR MEASUREMENTTotal and displacement power factorAccuracy : 1.0%
FREQUENCY MEASUREMENTMeasurement range : 45 ~ 65 HzMeasurement updating period : 1sAccuracy : 0.5%
ENERGY ACCURACYActive (according to IEC 62053-21) : class 1Reactive (according to IEC 62053-23) : class 2
POWER SUPPLYSelf supplied : 100 ~ 240 V ACFrequency : 50 / 60 HzPower consumption : <3 VA
COMMUNICATIONHardware interface : Isolated RS485Protocol : Modbus-RTUBaud rate : 2400, 4800, 9600, 19200, 38400
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : DIN railDimension (mm) : 65(w) x 85(h) x 50(d)Approximate weight : 0.3 kg
38
FeaturesLCD display with back lightingModbus-RTU communicationDIN rail type
MEASUREMENT PARAMETERS:• Phase Voltage (L-N)• Line Voltage (L-L)• Phase Current• Bidirectional kW (per phase & total)• Bidirectional kVAR (per phase & total)• Bidirectional kVA (per phase & total)• Frequency• Power Factor (per phase & total)• Energy (+ and - ) for kWh, kVARh and kVAh• THD Phase Voltage ( L-N )• THD Phase Current
Digital P
ower M
eterD
M 38
w w w . i t m i k r o . c o m
Electromagnetic Compatibility (EMC)
Ordering Information
Part 6-2: Generic Standards IEC61000-6-2Immunity for industrial environments.
Part 6-4: Generic Standards IEC61000-6-4Emission standard for industrial environments.
MODEL DESCRIPTION DM 38-240A Self Powered 100~240 V AC
Typical Application Diagram
Case Dimensions
Digital P
ower M
eterD
M 38
65 mm
85 mm
45.5 mm
71 mm
Front
15.5 mm
50 mm
Side
w w w . i t m i k r o . c o m
Technical Data
MU
INPUTSMeasuring input:Rated voltage input : 57 ~ 130 VRated frequency : 50 / 60 Hz
Rated auxiliary voltage:Model MU2300-150D : 24 ~ 150 V DCModel MU2300-240AD : 85 ~ 265 V AC 110 ~ 340 V DC
Power consumption:AC auxiliary voltage : 6 ~ 10 VA typicalDC auxiliary voltage : 5 ~ 9 W typical
Binary Input:External binary input : 85 ~ 265 V AC/DC
COMMUNICATIONRS485 Modbus - RTU
OUTPUT CONTACTS5 programmable contacts +1 IRF contact:Rated voltage : 250 V AC / DCContinuous carry : 5 AMake and carry for 0.2 s : 30 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
UNDER-VOLTAGE ELEMENTLow set setting U< : 5 - 130 VHigh set setting U<< : 5 - 130 VTime multiplier, TMS : 0.5 - 100Low-set definite time tU< : 0 - 600 sHigh-set definite time tU<< : 0 - 600 s
OVER-VOLTAGE ELEMENTLow set setting U> : 5 - 200 VHigh set setting U>> : 5 - 260 VTime multiplier, TMS : 0.5 - 100Low-set definite time tU> : 0 - 600 sHigh-set definite time tU>> : 0 - 600 s
NEGATIVE SEQUENCE OVER-VOLTAGEELEMENTNegative sequence over-voltage setting, U2> : 5 - 200 VTime multiplier, TMS : 0.5 - 100Negative sequence over-voltage definite time tU2> : 0 - 600 s
RESIDUAL OVER-VOLTAGE ELEMENTResidual over-voltage setting, U0> : 0.5 - 130 VTime multiplier, TMS : 0.5 - 100Residual over-voltage definite time tU0> : 0 - 600 s
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 142(w) x 165(h) x 198(d)Enclosure protection : IP54 at the panelApproximate weight : 2.7 kg
2300Features
Introduction
• Multifunction numerical voltage protection relay
• Low-set undervoltage stage (U<) with definite- time or inverse-time characteristic
• High-set undervoltage stage (U<<) with definite- time
• Low-set overvoltage stage (U>) with definite- time or inverse-time characteristic
• High-set overvoltage stage (U>>) with definite- time
• Negative sequence overvoltage protection (U2>) with definite-time or inverse-time characteristic
• Neutral displacement / residual overvoltage protection (U0>) with definite-time or inverse- time characteristic
• Can be used in single-phase or three-phase operation
• Multi-function isolated digital input with wide input voltage range
• Fault record and event code recording
• Five programmable voltage-free output contacts
• Isolated RS485 Modbus - RTU communication
• ANSI Code : 27, 47, 59, 60
Voltage Relay
MU
2300
The MU2300 is a microprocessor based numericalrelay for voltage protection functions in electricaldistribution network.
w w w . i t m i k r o . c o m
Typical Application Diagrams
Undervoltage Characteristic Overvoltage Characteristic Case Dimensions
Ordering Information
Voltage Relay
MU
2300
MODEL DESCRIPTION MU2300-150D For 50 / 60 Hz system, auxiliary voltage 24 ~ 150 V DC
MU2300-240AD For 50 / 60 Hz system, auxiliary voltage 85 ~ 265 V AC or 110~340 V DC
w w w . i t m i k r o . c o m
Technical Data
MU
SETTING RANGESUndervoltage : Off, 1% to 25%Time delay for undervoltage : 0.1s to 30sOvervoltage : Off, 1% to 20%Time delay for overvoltage : 0.1s to 30sStart time delay : 0s to 999sUnbalance : Off, 3% to 20%Time delay for unbalance : 0.5s to 30sPhase loss : Fixed time <0.5sPhase sequence : Fixed time <0.5s
AUXILIARY SUPPLYMU350-415V : 380 V (-25%) to 415 V (+20%) ACSupply frequency : 45 Hz to 65 HzMaximum power consumption : 3VA
MEASURING INPUTLine to line : 100 to 415 (+20%) VACLine to Neutral : 58 to 240 (+20%) VAC
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPickup indicator : Red indicatorTrip : 7-segment display and red LED indicators
ACCURACYProtection thresholds : ± 3%Time delay : 0 to 0.5s, ± 15% with minimum 40ms : 0.6s and above, < ± 3%Measurements : ± 3%
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Approximate weight : 0.31 kg
350
Features
Product Description
• Undervoltage • Overvoltage • Delay-on • 2 voltage-free output contacts • Voltage and frequency display • 3-Phase • Unbalance • Phase loss • Phase sequence • With or without neutral connection • Phase to phase or phase to neutral monitoring • Programmable relay outputs • ANSI Code : 27, 47, 59, 60
Voltage Relay
MU
350
MU350 is 3-phase voltage relay that combinesvarious protections and starting delay.
w w w . i t m i k r o . c o m
Voltage Relay
MU
350
Ordering Information
MODEL DESCRIPTION MU350-415V 3-Phase, auxiliary voltage 380 ~ 415 V AC, 45-65 HzMU350-240V 3-Phase, auxiliary voltage 220 ~ 240 V AC, 45-65 Hz
Typical Application Diagrams Case Dimensions
w w w . i t m i k r o . c o m
Technical Data
MU
SETTING RANGESUndervoltage : 1% to 25%Time delay for undervoltage : 0.1s to 30sOvervoltage : 1% to 20%Time delay for overvoltage : 0.1s to 30sStart time delay : 0s to 999s
For MU250 only:Unbalance : 3% to 20%Time delay for unbalance : 0.5s to 30sPhase loss : Fixed time <0.5sPhase sequence : Fixed time <0.5s
POWER SUPPLY INPUTInput voltage:MU150-110V & MU250-110V : 100 V (-25%) to 120 V (+20%) ACMU150-240V & MU250-220V : 220 V (-25%) to 240 V (+20%) ACMU250-415V : 380 V (-25%) to 415 V (+20%)Supply frequency :45 Hz to 65 Hz
Maximum power consumption:MU250 : 3VAMU150 : 2.5VA
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSAuxiliary supply : Green indicatorPickup indicator : Red indicatorTrip : 7-segment display and red LED indicators
ACCURACYProtection thresholds : ± 3%Time delay : 0 to 0.5s, ± 15% with minimum 40ms : 0.6s and above, < ± 3%Measurements : ± 3%
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : DIN railDimension (mm) : 71(w) x 85(h) x 70(d)Approximate weight : 0.4 kg
250150
Voltage Relay
MU
250 / 150
Features
Features For MU 250 only
Product Description
• Microprocessor based numerical relay • Undervoltage • Overvoltage • Delay-on • 2 voltage-free output contacts • Voltage and frequency display • ANSI Code : 27, 47, 59, 60
• 3-Phase • Unbalance • Phase loss • Phase sequence • With or without neutral connection • Phase to phase or phase to neutral monitoring
MU150 and MU250 are voltage relays thatcombine various protections and starting delay.
MU150 is used for single-phase monitoring whileMU250 is used for 3-phase monitoring.
MU 250
MU 150
w w w . i t m i k r o . c o m
Voltage Relay
MU
250 / 150
Ordering Information
MODEL DESCRIPTION MU150-110V Single-Phase, 100/110/120 V AC, 45-65 Hz power supply
MU150-240V Single-Phase, 220/230/240 V AC, 45-65 Hz power supply
MU250-110V 3-phase, 100/110/120 V AC 45-65 Hz power supply
MU250-220V 3-phase, 220/230/240 V AC 45-65 Hz power supply
MU250-415V 3-Phase, 380/400/415 V AC, 45-65 Hz power supply
Typical Application Diagrams
Case Dimensions
w w w . i t m i k r o . c o m
Technical Data
MX
POWER SUPPLY INPUT3-Phase SystemPhase-to-phase voltage : 380 V (-25%) to 415 V (+20%) AC
Single PhasePhase-to-neutral voltage : 220 V (-25%) to 240 V (+20%) ACFrequency range : 45 to 65 HzMax. power consumption : 3 VA maximum
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
SETTING RANGESUndervoltage : 78% - 98%Overvoltage : 102% - 122%Delay time : 0.1 - 10sNormal voltage : 380, 400, 415 Vp-p, 220, 230, 240, Vp-n3-phase / Single-phase
ACCURACYProtection thresholds : ± 3%Hysteresis : 1%Delay time : 0-0.5s, ± 15%, 40ms minimum : 0.5s and above, ± 3%Measurements : ± 3%
INDICATORSPower supply ON : Green indicatorOutput ON : Green indicatorUndervoltage : Red indicatorOvervoltage : Red indicatorPhase error : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : DIN railDimension (mm) : 71(w) x 85(h) x 70(d)Approximate weight : 0.3 kg
210
Features
Product Description
• Numerical voltage protection relay • Undervoltage • Overvoltage • Phase loss • Phase sequence • 3-Phase/Single-phase • ANSI Code: 27, 47, 59
MX210 is voltage relay that combines overvoltage, undervoltage, phase loss, phase sequence and delay start functions.MX210 can be programmed by user to set nominal voltage as well as set into 3-phase or Single-phase mode.
Voltage Relay
MX 210
w w w . i t m i k r o . c o m
3 - Phase Voltage R
elayM
X 210
Case Dimensions
MODEL DESCRIPTION MX210 - 415V 3-Phase 380-415V AC Single-Phase 220-240V AC 45-65Hz
Wiring Diagram
Operations Diagram
Ordering Information
w w w . i t m i k r o . c o m
MODEL DESCRIPTION MX210 - 415V 3-Phase 380-415V AC Single-Phase 220-240V AC 45-65Hz
Technical Data
MX
POWER SUPPLY INPUTPhase-to-phase voltage : 230 V AC ±20% : 400 V AC ±20%Frequency range : 45 to 65 HzMax power consumption : 3 VAInput connections : Phase L1 to pin 5 Phase L2 to pin 6 Phase L3 to pin 7 Neutral (optional) to pin 11
OUTPUT CONTACTSRated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
INDICATORSPower supply ON : Green indicatorOutput ON : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -5˚C to +55˚CHumidity : 56 days at 93% RH and 40˚C non-condensing
MECHANICALMounting : Circular 11-pin plug-in socketDimension (mm) : 35(w) x 80(h) x 72.5(d)Approximate weight : 0.3 kg
Voltage Relay
MX 100 / 50
10050Features
Product Description
• Electronic monitoring relay
• Phase sequence monitoring*
• Phase failure monitoring
• Plug-in type module
• Indicators for power and alarm status
• ANSI Code : 47
This phase sequence and phase failure relay isdesigned for application where the 3-phase supply needs to be continuously monitored for propersequencing and phase loss. Commonly used toprotect a 3-phase motor.
w w w . i t m i k r o . c o m
Voltage Relay
MX 100 / 50
Case Dimensions
MODEL DESCRIPTION
MX100 - 230 Auxiliary voltage 184~276 V AC
MX100 - 400 Auxiliary voltage 320~480 V AC
MX50 - 230 Auxiliary voltage 184~276 V AC
MX50 - 400 Auxiliary voltage 320~480 V AC
Wiring Diagram
Function Table
Ordering Information
Condition Pin 5 Pin 6 Pin 7 Relay Remark
1 L1 L2 L3 ON System healthy 2 Loss L2 L3 OFF Phase failure 3 L1 Loss L3 OFF Phase failure 4 L1 L2 Loss OFF Phase failure 5 L2 L1 L3 OFF Sequence fault* 6 L3 L2 L1 OFF Sequence fault* * Applicable to MX100 model only
w w w . i t m i k r o . c o m
Technical Data
RPR
INPUTRated Phase-neutral voltage : 220V to 240V ACRated Phase-phase voltage : 380V to 415V ACRated frequency : 50 or 60 HzRated current (In) : 5ABurden : < 0.3 VA at InThermal withstand : 1.2 x Un , 2 x In continuous : 1.2 x Un , 10 x In for 3 secPower consumption : 3 VA maximum
OUTPUT CONTACTSRated voltage : 250 V AC/DCContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
SETTING RANGESRange : 2% to 20% reverse current with 1% HysteresisTime delay : 0 sec to 20 sec3-Phase 4-wire (star) or 3-Phase 3-wire (delta)
ACCURACYProtection thresholds Hysteresis : ± 3%Delay time : 1% : 0-0.5s, ± 15%, 40ms minimum.Measurements : 0.5s and above, ± 3% : ± 3%
INDICATORSAuxiliary supply : Green indicatorDelay : Red indicatorTrip : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : DIN railDimension (mm) : 71(w) x 85(h) x 70(d)Approximate weight : 0.3 kg
Reverse P
ower R
elayR
PR
415A
415A
Features
Product Description
• Reverse power monitoring
• 3-phase, 3 or 4-wire system
• Adjustable reverse power setting
• Adjustable tripping time delay
• Indicators for auxiliary power, trip delay and trip status
• Test button
• ANSI Code: 32
RPR 415A relay is a directionally controlled timing relay used to protect AC generators from motor-ing. When such condition occurs and the reverse current exceeded the customer adjustable preset limit for a predetermined delay time, the trip relayoperates to disconnect the circuit.
w w w . i t m i k r o . c o m
Reverse P
ower R
elayR
PR
415A
Case Dimensions
Ordering Information
MODEL DESCRIPTION
RPR415A 380-415Vpp AC / 220-240Vpn AC, 45-65Hz
Typical Application Diagram
w w w . i t m i k r o . c o m
Reverse P
ower R
elayR
PR
415B
RPR415B
Features
Product Description
• Reverse power monitoring
• 3-phase-4-wire system
• Adjustable reverse power setting
• Adjustable tripping time delay
• Indicators for auxiliary power, trip delay and trip status
• Test button
• ANSI Code : 32
The RPR 415B relay is a directionally controlled tim-ing relay used to protect AC generators from motor-ing. When such a condition occurs and the reversecurrent exceeded the customer adjustable preset limit and the current persists for a predetermined delay time, the trip relay operates to diconnect the circuit.
Technical Data
INPUTRated Phase-neutral voltage : 220V to 240V ACRated Phase-phase voltage : 380V to 415V ACRated frequency : 50 or 60 HzRated current (In) : 5ABurden : < 0.3 VA at InThermal withstand : 1.2 x Un , 2 x In continuous : 1.2 x Un , 10 x In for 3 secPower consumption : 3 VA maximum
OUTPUT CONTACTSRated voltage : 250 V AC/DCContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
SETTING RANGESRange : 2% to 20% reverse current with 1% HysteresisTime delay : 0 sec to 20 sec3-Phase 4-wire (star) or 3-Phase 3-wire (delta)
ACCURACYProtection thresholds Hysteresis : ± 3%Delay time : 1% : 0-0.5s, ± 15%, 40ms minimum.Measurements : 0.5s and above, ± 3% : ± 3%
INDICATORSAuxiliary supply : Green indicatorDelay : Red indicatorTrip : Red indicator
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 71(w) x 85(h) x 70(d)Approximate weight : 0.6 kg
w w w . i t m i k r o . c o m
Reverse P
ower R
elayR
PR
415B Ordering Information
MODEL DESCRIPTION
RPR415B Auxiliary voltage 380 ~ 440 V AC
Typical Application Diagram
96 mm
Front
96 m
m
90 mm70 mm
Side
91.0 ± 0.5 mm
91.0
± 0
.5 m
m
Panel Cutout
Case Dimensions
w w w . i t m i k r o . c o m
Technical Data
PFR
RATINGS AUXILIARY POWER SUPPLYCurrent Supply voltage : 220~240 V AC / 380~415 V ACOperating Limits : -15% + 10%Consumption : 10 VA maxRated frequency : 50 Hz or 60 Hz
OUTPUT CONTACTSNumbers of outputs : 6 / 8 / 12 / 14 (PFR60/PFR80 /PFR120/PFR140 )Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operationsMax current for thecommon terminals : 12 A continuous
CURRENT INPUTRated current ( In ) : 5 AOperating Limits : 0.05 A to 6.5 ARated Frequency : 50 Hz or 60 Hz
CONTROL RANGEPower factor setting : 0.8 Ind - 0.8 CapC/K setting : 0.03 - 1.20 / AutomaticSwitching sensitivity : 5 - 600 s/stepReconnection time forsame step : 5 - 240 sTHD threshold : 0.20 - 3.00 ( 20% - 300% ) / OFFSwitching Program : Automatic / Automatic Rotate / 4-quadrant / ManualRated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 / 8 / 12 / 16 ( Automatic if C/K set to Auto )
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 144(w) x 144(h) x 90(d)Enclosure protection : IP54 at the panelApproximate weight : 1.2 kg
Features • Microprocessor based intelligent auto switching
control • Automatic C/K and rated step adjustment • Automatic CT polarity correction • Display of power factor, current & total harmonic
distortion of current • Programmable sensitivity • Last step can be used as alarm/fan output • Under/over voltage alarm, under/over compensate
alarm & high harmonic distortion alarm • User-friendly setting • Complies with IEC 61000-6-2 standard
Pow
er Factor Regulator
PFR
140 / 120 / 80 / 60
140 120 80 60
w w w . i t m i k r o . c o m
Pow
er Factor Regulator
PFR
140 / 120 / 80 / 60
Case Dimensions
MODEL DESCRIPTION
PFR60 - 415 - 50 6 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR80 - 415 - 50 8 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR120 - 415 - 50 12 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR140 - 415 - 50 14 Steps, 50 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 50 6 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR80 - 220 - 50 8 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR120 - 220 - 50 12 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR140 - 220 - 50 14 Steps, 50 Hz system, auxiliary voltage 220~240 V AC
PFR60 - 415 - 60 6 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR80 - 415 - 60 8 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR120 - 415 - 60 12 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR140 - 415 - 60 14 Steps, 60 Hz system, auxiliary voltage 380~415 V AC
PFR60 - 220 - 60 6 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
PFR80 - 220 - 60 8 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
PFR120 - 220 - 60 12 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
PFR140 - 220 - 60 14 Steps, 60 Hz system, auxiliary voltage 220~240 V AC
Typical Application Diagram
Ordering Information
w w w . i t m i k r o . c o m
Technical Data
RATINGS AUXILIARY POWER SUPPLYModel PFR96 : 110 ~ 120 V AC / 220 ~ 240 V ACModel PFR96P : 380 ~ 415 V ACOperating Limits : -15% + 10%Consumption : 10 VA maxRated frequency : 50 Hz or 60 Hz
OUTPUT CONTACTSNumbers of outputs : 6Rated voltage : 250 V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operationsMax current for thecommon terminals : 12 A continuous
CURRENT INPUTRated current ( In ) : 5 AOperating Limits : 0.15 A to 6.5 ARated frequency : 50 Hz or 60 Hz
CONTROL RANGEPower factor setting : 0.8 Ind - 0.8 CapC/K setting : 0.03 - 1.20 / AutomaticSwitching sensitivity : 5 - 600 s/stepReconnection time forsame step : 5 - 240 sSwitching Program : Automatic / Automatic Rotate / 4-quadrant / ManualRated step coefficient : 0 / 1 / 2 / 3 / 4 / 5 / 6 / 8 / 12 / 16 (Automatic if C/K set to Auto )
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 90(d)Approximate weight : 0.6 kg
Features
For PFR 96
For PFR 96P
• Microprocessor based intelligent auto switching control • Automatic C/K and rated step adjustment • Automatic CT polarity correction • Display of power factor & current • Programmable sensitivity • Last step can be used as alarm/fan output • Under/over voltage alarm, under/over
compensate alarm • User-friendly setting • Complies with IEC 61000-6-2 standard
• For single-phase system
• For 3-phase system
9696P
Pow
er Factor Regulator
PFR
96 / 96P
PFR
w w w . i t m i k r o . c o m
MODEL DESCRIPTION
PFR96 - 220 - 50 6 Steps, for 50 Hz system, auxiliary voltage 220~240 V AC
PFR96 - 220 - 60 6 Steps, for 60 Hz system, auxiliary voltage 220~240 V AC
PFR96 - 110 - 50 6 Steps, for 50 Hz system, auxiliary voltage 110~120 V AC
PFR96 - 110 - 60 6 Steps, for 60 Hz system, auxiliary voltage 110~120 V AC
PFR96P - 415 - 50 6 Steps, for 50 Hz system, auxiliary voltage 380~415 V AC
PFR96P - 415 - 60 6 Steps, for 60 Hz system, auxiliary voltage 380~415 V AC
Typical Application Diagram
Pow
er Factor Regulator
PFR
96 / 96P
Case Dimensions Ordering Information
w w w . i t m i k r o . c o m
Technical Data
AN
WINDOWWindow Dimension : 50 x 30 mm.Type : White translucent lens.Colours : Red, Amber. Coloured by field replaceable LED module.Windows Flash Fast : 1.4 Hz (0.4s on, 0.4s off), Slow : 0.45 Hz (1.1s on, 1.1s off), Intermittent: (0.4s on, 1.8s off),
ALARM SEQUENCESM, A, R, R-12, F1A, F1M, F2A, F2M, F3A, F3M, Follower
AUXILIARY POWER INPUTFuse protected.AN1xx-30 : 24-36 V DC or 18-27 V AC.AN1xx-110 : 88-132 V DC or 64-95 V AC.Power consumption : AN112: 6 W, AN120: 8 W, AN128: 10W, AN136: 12W
ALARM CONTACT INPUTSOpto-isolated inputsAN1xx-30 : 24-36 V DCAN1xx-110 : 88-132 V DCInput current : 3 mA typical
OUTPUT CONTACTSRepeat relays : Potential free for each alarm point. 5 A at 250 V AC, 3 A at 30 V DC. Resistive load.AUX1-AUX3,RBACK, SSP : 5 A at 250 V AC, 5 A at 30 V DC. Resistive load.
TERMINALSWire size : 28-14 AWG. ( 0.08mm2 to 2.5mm2 ) Removable screw type terminal block
COMMUNICATIONHardware interface : AN1xx - xx - x - A: RS232 AN1xx - xx - x - B : Isolated RS485Protocol : Modbus - RTUBaud rate : 300 to 57600
ENVIRONMENT CONDITIONSOperation temperature : -20 to 60˚CStorage temperature : -20 to 80˚CHumidity : 0 - 95% RH, non condensing
MECHANICALMounting : Panel MountingApproximate weight : AN 112 : 2.4 kg AN 120 : 3.1 kg AN 128 : 3.5 kg AN 136 : 3.9 kg
Features • 12, 20, 28 or 36 windows. Replaceable superbright
LED modules, with choice of amber or red illumination
• 11 Alarm Sequences as per ISA-18.1 standard
• Each channel/window fully field programmable, either from front panel built-in pushbutton or using PC
• Option of either RS232 or RS485 MODBUS-RTU communication. Comes with user-friendly configuration software.
• Repeat relay for each window as well as numerous configurable multifunction output relays for connection to external equipment to form alarm management system
• Sleep or unattended mode feature is available, for stations not permanently manned
• Auto-silence and auto-acknowledge features, with delay settable from 1 – 255 s
• Other amount of windows available upon request.
Annunciator
AN
112 / 120 / 128 / 136
112120128136
Programmable Alarm Annunciator
Tests And Standards
The AN1xx series Alarm Annunciator provides ideal solution for all your alarmsystem management and requirement. It comes with either 12, 20, 28 or 36 windows,and due to the use of microprocessor-based design, the alarm annunciator is highlyflexible in terms of functionality and programmability, suitable for all applicationand industries.
Electrostatic discharge IEC61000-4-2, Class III, air discharge.............. 8 KVElectrostatic discharge IEC61000-4-2, Class III, contact discharge...... 6 KVElectrical fast transient IEC61000-4-4................................................... 4 KV, 5/50nsSurge immunity IEC61000-4-5.............................................................. 4 KV, L to EEnclosure protection when panel mounted........................................ Front: IP41 Enclosure: IP30
w w w . i t m i k r o . c o m
Annunciator
AN
112 / 120 / 128 / 136
Ordering Information
Typical Connection Diagram
Case Dimensions
AN120 Front
237 mm
217
mm
AN112 Front
237 mm
157
mm
Bottom206 mm
1.5 mm
132
mm
132 mm126 m
m
AN112 Side
132 mm
186 mm
AN120 Side
AN128 Front
237 mm
277
mm
132 mm
246 mm
AN128 Side
AN136 Front
237 mm
337
mm
132 mm
306 mm
AN136 Side
36
A: RS 232 communicationB: RS 485 communication
0: without repeat relays1: with repeat relays
Power Supply: 30, 110 V DCNumber of Windows: 12, 20, 28, 36
Order code:
For example:
AN1
12 windows, 30 V DC, with repeat relays, RS232 communication:AN112-30-1-A
- - -
w w w . i t m i k r o . c o m
Technical Data
MPR
CT RATINGSRated current, IB : 2-10ARated frequency : 50 Hz or 60 HzBurden : <0.3 VA at rated currentThermal withstand : Continuous : 2x max rated 45s : 6x max rated 1s : 10x max rated
BINARY INPUTRated input voltage : 12V (Supplied internally)
AUXILIARY SUPPLYModel MPR 500-240AD : 85 ~ 265 V AC 110 ~ 370 V DCSupply frequency : 50 or 60 HzMaximum powerconsumption : 3 VA typical
OUTPUT CONTACTSRated voltage : 250V ACContact rating : 5 AExpected electrical life : 100,000 operations at rated currentExpected mechanical life : 5 x 106 operations
SETTING RANGESThermal Overloadtime constant, t6X : 1 – 40s. Step 0.1s for 1-10s, step 1s for 10-40s.Short circuit, I>> : off, 2-12 x lB. Step 1 x IBShort circuit delay time, t>> : 0 – 25s. Step 0.1s for 1-10s, step 1s for 10-25s.Undercurrent, I<< : off, 20-90% lB. Step 1%Undercurrent delay time, t<< : 0 – 60s. Step 0.1s for 1-10s, step 1s for 10-60s.Unbalance, : off, 10-50%. Step 1%Unbalance delay time, t : 0 – 25s. Step 0.1s for 1-10s, Step 1s for 10-25s.Earth fault, Iθ : off, 10-60% lB. Step 1%Earth fault delay time, tθ : 0 – 25s. Step 0.1s for 1-10s, step 1s for 10-25s.Phass loss : < 500msPhase sequence : < 200ms
Prolonged starting/stalled rotor, IS : off, 2-12 x lB. Step 0.1 x IB
Prolonged startingtime delay, tStart : 0 – 60s. Step 0.1s for 1-10s, step 1s for 10-60s.Stalled rotor delay time, tStall : 0 – 60s. Step 0.1s for 1-10s, step 1s for 10-60s.
INDICATORSRun : Green indicatorTrip/Pickup : 7-segment display and red indicatorThermal : Yellow indicator
ENVIRONMENTAL CONDITIONSTemperature : -10°C to 55°CHumidity : 5% to 95%, non-condensing ACCURACYCurrent accuracy : ± 5% (When IL = 2A, Io > 0.2A)Timing accuracy : ± 5% or ± 50 ms
MECHANICALMounting : Panel mountingDimension (mm) : 96(w) x 96(h) x 110(d)Approximate weight : 0.8 kg
Features • Microprocessor based numerical relay
• Thermal overload
• Overcurrent
• Undercurrent
• Unbalance
• Phase loss
• Phase sequence
• Earth fault
• Prolonged starting/stall rotor
• 2 voltage-free output contacts
• ANSI Code : 37, 46, 47, 49, 50P, 50G
Motor P
rotection Relay
MP
R 500
500
w w w . i t m i k r o . c o m
Motor P
rotection Relay
MP
R 500
Thermal Tripping Curve
Ordering InformationMODEL DESCRIPTION
MPR500-240AD For 50 / 60 Hz system, auxiliary voltage 85 ~ 265 V AC or 110 ~ 370 V DC
Typical Application Diagrams
Case Dimensions
Mikro Sdn BhdLot 1, Jalan TP7/7, Sime UEP Industrial Park,
40400 Shah Alam, Selangor, Malaysia.
www.itmikro.com