Electrical Ground actually a path forcurrent to return from some load back
to the source.
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
4/24
A Ground to earth is REQUIRED of mostelectrical equipment to protect against
shock hazard!
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
5/24
Proper Grounding is EXTREMELYIMPORTANT for minimizing EMI
problems.
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
6/24
Grounds Symbol :
1. Signal/Earth Ground2. Chassis Ground3. Special Ground
(1) (2) (3)
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
7/24
Bond Wires
Circuit connected to Ground using bondwires.
Keep leads short and keep impedancelow.
Lower inductance is attained using flat,wide-cross-section conductive straps.
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
8/24
Signal Grounds
1. Single-Point
Tying the grounds together at a singlepoint,so all signal ground will be at the
same potential. The facility ground may not be
equipotential.
Avoid significant difference in the groundpotential in some case (ex: lightning strike).
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
9/24
Ground Loop
Circuit
FacilityGround
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
10/24
1. Single-Point
a) Series-Connected Single-Point
Circuit 1 Circuit 3Circuit 2
Source
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
11/24
Very commonly used.
Can see a potential difference at
the ground level that can affectoperation and cause EMIproblems. For this reason, the
bond leads must be kept as shortas possible.
a) Series-Connected Single-
Point
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
12/24
1. Single-Point
b) Parallel-Connected Single-Point
Circuit 1 Circuit 3Circuit 2
Source
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
13/24
b) Parallel-Connected Single-
Point Offers much better EMI control.
The circuit operates best at lowfrequency where the wireinductance is low.
Can require an excessive amountof wire for a large system.
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
14/24
Signal Grounds
2. Multipoint Arrangement
Circuit 1 Circuit 3Circuit 2
Source
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
15/24
2. Multi-Point Arrangement
A better approach for highfrequency.
Work best for frequencies above10 MHz.
It is CRITICAL that the groundleads from circuit to the commonground plane be as short as
possible (preferably less than
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
16/24
Loop Area
IC
+5V
IC IC
IC
+5V
SmallerLoop AreaLarger
Loop Area
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
17/24
Loop Area
A circuit containing : a source,connecting wire, load, and groundcreates a current loop that resemblesa loop antenna. It can serve an
unintentional source of radiatedemissions and also susceptible toreception of incident fields (ex: fromradio transmitters)
Because of radiated power from a loopantenna is proportional to the looparea squared, the area enclosed by
these current loops should beminimized to reduce EMI.
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
18/24
Shields
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
19/24
Shields is metal or metal screen boxplaced around circuit to block radiation.
Metal/ metal box/ metal braid Shield attenuate electromagnetic
wave and reflect waves
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
20/24
Fundamentals of Electromagnetics With Engineering Applicationsby Stuart M. Wentworth
Copyright 2005 by John Wiley & Sons. All rights reserved.
Figure 9-23 (p. 479)Some of a field Ei incident on a shield will be reflected at the air -shield boundary,
some will be transmitted and attenuated within the shield, some will be reflected at
the shield-air boundary, and finally some will be transmitted as Et.
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
21/24
Shielding effectiveness = SE
SE adalah tingkat performa Shield,didefinisikan sebagai desibel
SE = 10log (Pns/Ps) = 20log (|Ens|/|Es|)= 20log (|Hns|/|Hs|)
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
22/24
Atenuasi (attenuation) atau absorsimengkonfersi energi electromagneticmenjadi panas dalam materi Shield
Material dengan permebealitas tinggimembuat proses absorsi yang bagus,karena
=
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
23/24
SE tergantung dari : komposisi dan ketebalan Shield itu
sendiri
Frekuensi radiasi gelombangelektromagnetik
Bentuk dari Shield itu sendiri
Diskontinuitas yang mungkin beradadalam Shield
-
7/31/2019 Presentasi Elektromagnetika Ground & Shield
24/24
Dalam Shield terkadang terpadatbeberapa lubang yaitu: Opening untuk mnejalankan sinyal,
power dan koneksi grounding
Ventilasi Shield
Lubang yg tidak tertutup sempurna pada
penggabungan dua Shields
Lubang-lubang ini terkadangmengurangi integritas SE