1 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER iSAST OPEN RCT is made with high accurate coil winding technology on air core which shows precise quality from low current to high current and provides optimizing solution. It improves both conductor positioning error and influence by external magnetic field. As split clip flexible outfit, it can be easily installed even at limited space without cutting power lines. Main applications are power distribution monitoring, high current measuring, sub metering and etc. INPUT OUTPUT POWER : JRF333M-X : 333mVAC : 24VDC , 2VA POWER LED SINGLE PHASE output : 333mV AC THREE PHASE output : 333mV AC Power P1 P2 S1 S2 Input Output P1 P2 S1 S2 Input Output P1 P2 S1 S2 Input Output P1 P2 S1 S2 Input Output S1 S2 Vin - Vin + • Insulation CAT1000V, CAT600V AC • Accuracy Class 0.5S / 1.0 complying with IEC 61869-2 • Certificated for UL & CE complying with IEC61010-1 • IP65 or IP67 (International Protection code) New JRF MOI (Including a voltage integrator) for outdoor metering, Class 0.5S 35, 55, 75, 80, 105, 115, 120, 170, 180, 190, 295, 300, 305 Instantaneous Voltage / 333mV AC Secondary Output Current Range Inner Diameter(mm) 100 to 6,000A AC

Upload: others

Post on 09-Feb-2020

6 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

1

CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

PRECISION CLAMP ONFLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

iSAST OPEN RCT is made with high accurate coil winding technology on air core which shows precise quality from low current to high current and provides optimizing solution. It improves both conductor positioning error and influence by external magnetic field. As split clip flexible outfit, it can be easily installed even at limited space without cutting power lines. Main applications are power distribution monitoring, high current measuring, sub metering and etc.

I N P U TOUTPUTPOWER

: JRF333M-X: 333mVAC: 24VDC , 2VA

POWERLED

SINGLE PHASEoutput : 333mV AC

THREE PHASEoutput : 333mV AC

Power

P1 P2 S1 S2

Input Output

P1 P2 S1 S2

Input Output

P1 P2 S1 S2

Input Output

P1 P2 S1 S2

Input Output

S1

S2

Vin -

Vin +

• Insulation CATⅢ 1000V, CATⅣ 600V AC• Accuracy Class 0.5S / 1.0 complying with IEC 61869-2• Certi�cated for UL & CE complying with IEC61010-1• IP65 or IP67 (International Protection code)New JRF MOI (Including a voltage integrator) for outdoor metering, Class 0.5S

35, 55, 75, 80, 105, 115, 120,170, 180, 190, 295, 300, 305

Instantaneous Voltage / 333mV ACSecondary Output

Current Range

Inner Diameter(mm)

100 to 6,000A AC

Page 2: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

2CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

3

5

7

9

11

13

15

JRFS-XXXS/A(X-XXX) Series

JRFS-XXX(X-XXX) Series

JRFS-XXXY(X-XXX) Series

JRFS-XXX-M/P (X-XXX) Series

JRFS-XXX-R/U (X-XXX) Series

JRF MOI 333M Series

JRF-MOI-PU-333mV AC Series

PRECISION CLAMP ONFLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

CONTENTS

Page 3: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

SPECIFICATIONModel JRFS-120X JRFS-190X JRFS-305X

Accuracy

Phase Shift

Frequency Range

Output Sensitivity Tolerance

Output Sensitivity Tolerance

Linearity (10% to 100% of range)

Conductor Position Sensitivity

Influence of External Field

Working Temp.

Storage Temp.

Insulation Category

Safety Standards

Testing Voltage

A Type

S Type

< 1%

< 1° at 50/60Hz (typical < 0.5°)

10Hz to 20kHz

±10% maximum(Uncalibrated)

±0.5% of reading at 25°C (Calibrated)

±0.2% of reading

±2% maximum

±2% maximum

-30˚C ~ + 60˚C

-40˚C ~ + 60˚C

CATⅢ 1000V / CATIV 600V (PD2-Double Insulation)

EN/UL/cUL 61010-1, 61010-2-032

7400V/1min

• AC current probe utility by the Rogowski principle• Flexible and lightweight• Easy & quick installation in uninterruptible power line• Available shielding type on request• No danger from open-circuited secondary• High secondary output voltage & precise linearity error• Isolated plastic case recognized according to UL94-V0

APPLICATIONS• Very high current monitoring• DC ripple measurement• Harmonics and transients monitoring• Power monitoring & control systems• Applicable in eletronic Watt-hour meter

FEATURES

Clamp-on Flexible Rogowski coil Current Transformer has been designed for accurate measurement of wide AC current, pulsed DC or distorted waveforms. It may be used to measure AC current over a wide dynamic range and from 10Hz to 20kHz.

Rated Current 2kA ~ 6kA1kA ~ 4kA500A ~ 2kA

100mV(50Hz) [120mV(60Hz)] 1kA

333mV(50Hz) [399.6mV(60Hz)] 1kAOutput Voltage

Precision Clamp onFlexible Rogowski coil CTJRFS-XXXS/A(X-XXX) Series IP 67

PROBE HEAD ONLY

vac

Page 4: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

4CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

DIMENSIONS

OPTION : INTEGRATOR C/M/S/T-XXX SERIES

ONE TURNPRIMARY

AC OutputS1(OUT) S2(G)

Max. 240 cm

BLACK(COMMON)

WHITE(HIGH)

POWER SUPPLY:10 to 30V DC+ –BLACK

Shielded wire

WHITEONE TURNPRIMARY

* Diagnostic green LED to check power supply function

P1 P2 S1 S2 + −

I N P U TOUTPUTPOWER

: : :

POWERLED

Power supply : 24V DC

Power supply : 24V DC

S Series Output : 333mVAC

Output : 333mVAC

Output : 333mVAC

T Series Output: 333mVAC

C Type 333mVAC

102.2

21.7

15

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

48.8

074

.40

86.0

0

60.0070.00

2.505x5.00=25.005x5.00=25.00

1.25(72x)

- 0.20+0.00

1 2 3 4 5

6 7 8 9 10

41.9

0±0

.20

4.40

2.00

86.0

0

30.90 ±0.2035.00

1 2 3 4 5

6 7 8 9 10P1 P2 S1 S2

Input Output

Power

+ –

+ –

P1 P2 S1 S2

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Power

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

M Type 333mVAC

THREE PHASEI N P U TOUTPUTPOWER

SINGLE PHASEI N P U TOUTPUTPOWER

1 2

6 7 9 10

S1

S2

Vin -

Vin +

I N P U TOUTPUTPOWER

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Φ120~305

Φ6

Φ12

23.8

26

42

Input Output Input Output Input Output

Page 5: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

5 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

SPECIFICATIONModel

Rated Current

Output Voltage

JRFS-080 JRFS-115

1kA

104mV AC/[email protected] AC/1kA@60Hz

1kA ~ 2kA

136mV AC/[email protected] AC/2kA@60Hz

• Ø80, Ø115mm sensing aperture for non-contact measurement• Very low position sensitivity• No danger from open-circuited secondary• High secondary output voltage & precise linearity error• Isolated plastic case recognized according to UL94 -V0

APPLICATIONS• Energy sub-meters• Power meters• Power quality monitoring• Condition monitoring• Distributed measurement systems

FEATURES

J&D’s new Micro-accuracy flexible rogowski coil measures even sensitive error to use special magnetic winding technology with small size. It is very effective for small sized AC measuring utility since it reduces chronically affected errors on existed Rogowski coil by conductor’s position.

Accuracy

Phase Shift

Frequency Range

Output Sensitivity Tolerance

Output Sensitivity Tolerance

Linearity (10% to 100% of range)

Conductor Position Sensitivity

Influence of External Field

Working Temp.

Storage Temp.

Insulation Category

Safety Standards

Testing Voltage

< 1%

< 1° at 50/60Hz (typical < 0.5°)

10Hz to 20kHz

±10% maximum(Uncalibrated)

±0.5% of reading at 25°C (Calibrated)

±0.2% of reading

±2% maximum

±2% maximum

-30˚C ~ + 60˚C

-40˚C ~ + 60˚C

CATⅢ 1000V / CATIV 600V (PD2-Double Insulation)

EN/UL/cUL 61010-1, 61010-2-032

7400V/1min

Precision Clamp onFlexible Rogowski coil CT JRFS-XXX(X-XXX) Series IP 67

PROBE HEAD ONLY

vac

Page 6: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

6CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

DIMENSIONS

OPTION : INTEGRATOR C/M/S/T-XXX SERIES

Φ80~115Φ6

Φ7

18.5

20

40

ONE TURNPRIMARY

AC OutputS1(OUT) S2(G)

Max. 240 cm

BLACK(COMMON)

WHITE(HIGH)

POWER SUPPLY:10 to 30V DC+ –BLACK

Shielded wire

WHITEONE TURNPRIMARY

* Diagnostic green LED to check power supply function

P1 P2 S1 S2 + −

I N P U TOUTPUTPOWER

: : :

POWERLED

Power supply : 24V DC

Power supply : 24V DC

S Series Output : 333mVAC

Output : 333mVAC

Output : 333mVAC

T Series Output: 333mVAC

C Type 333mVAC

102.2

21.7

15

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

48.8

074

.40

86.0

0

60.0070.00

2.505x5.00=25.005x5.00=25.00

1.25(72x)

- 0.20+0.00

1 2 3 4 5

6 7 8 9 10

41.9

0±0

.20

4.40

2.00

86.0

0

30.90 ±0.2035.00

1 2 3 4 5

6 7 8 9 10P1 P2 S1 S2

Input Output

Power

+ –

+ –

P1 P2 S1 S2

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Power

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

M Type 333mVAC

THREE PHASEI N P U TOUTPUTPOWER

SINGLE PHASEI N P U TOUTPUTPOWER

1 2

6 7 9 10

S1

S2

Vin -

Vin +

I N P U TOUTPUTPOWER

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Input Output Input Output Input Output

Page 7: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

7 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

SPECIFICATIONModel JRFS-035Y

Current Ratio

Output Voltage

250A ~ 500A

48mV AC/[email protected] AC/500A@60Hz

JRFS-055Y JRFS-080Y JRFS-105Y

250A ~ 500A

50mV AC/500A@50Hz60mV AC/500A@60Hz

250A ~ 1kA

104mV AC/[email protected] AC/1000A@60Hz

1kA ~2kA

208mV AC/[email protected] AC/2000A@60Hz

• Ø35 / Ø55 / Ø80 / Ø105mm sensing aperture for non-contact measurement• Very low position sensitivity• No danger from open-circuited secondary• High secondary output voltage & precise linearity error• Isolated plastic case recognized according to UL94-V0

APPLICATIONS• Very high current monitoring• DC ripple measurement• Harmonics and transients monitoring• Power monitoring & control systems• Applicable in eletronic Watt-hour meter

FEATURES

J&D’s new Micro-accuracy flexible rogowski coil measures even sensitive error to use special magnetic winding technology with small size. It is very effective for small sized AC measuring utility since it reduces chronically affected errors on existed Rogowski coil by conductor’s position.

Accuracy

Phase Shift

Frequency Range

Output Sensitivity Tolerance

Output Sensitivity Tolerance

Linearity (10% to 100% of range)

Conductor Position Sensitivity

Influence of External Field

Working Temp.

Storage Temp.

Insulation Category

Safety Standards

Testing Voltage

< 1%

< 1° at 50/60Hz (typical < 0.5°)

10Hz to 20kHz

±10% maximum(Uncalibrated)

±0.5% of reading at 25°C (Calibrated)

±0.2% of reading

±2% maximum

±2% maximum

-30˚C ~ + 60˚C

-40˚C ~ + 60˚C

CATⅢ 1000V / CATIV 600V (PD2-Double Insulation)

EN/UL/cUL 61010-1, 61010-2-032

7400V/1min

Precision Clamp onFlexible Rogowski coil CTJRFS-XXXY(X-XXX) Series IP 67

PROBE HEAD ONLY

vac

S1 ●

S2

Vin -

Vin+ ●●

POWER SUPPLY 5, 12, 24V DC

Page 8: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

8CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

DIMENSIONS

OPTION : INTEGRATOR C/M/S/T-XXX SERIES

Φ35~115

Φ6

Φ7

41.8

41.6

12.2

ONE TURNPRIMARY

AC OutputS1(OUT) S2(G)

Max. 240 cm

BLACK(COMMON)

WHITE(HIGH)

POWER SUPPLY:10 to 30V DC+ –BLACK

Shielded wire

WHITEONE TURNPRIMARY

* Diagnostic green LED to check power supply function

P1 P2 S1 S2 + −

I N P U TOUTPUTPOWER

: : :

POWERLED

Power supply : 24V DC

Power supply : 24V DC

S Series Output : 333mVAC

Output : 333mVAC

Output : 333mVAC

T Series Output: 333mVAC

C Type 333mVAC

102.2

21.7

15

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

48.8

074

.40

86.0

0

60.0070.00

2.505x5.00=25.005x5.00=25.00

1.25(72x)

- 0.20+0.00

1 2 3 4 5

6 7 8 9 10

41.9

0±0

.20

4.40

2.00

86.0

0

30.90 ±0.2035.00

1 2 3 4 5

6 7 8 9 10P1 P2 S1 S2

Input Output

Power

+ –

+ –

P1 P2 S1 S2

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Power

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

M Type 333mVAC

THREE PHASEI N P U TOUTPUTPOWER

SINGLE PHASEI N P U TOUTPUTPOWER

1 2

6 7 9 10

S1

S2

Vin -

Vin +

I N P U TOUTPUTPOWER

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Input Output Input Output Input Output

Page 9: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

9 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

SPECIFICATION

ModelJRFS-080X

JRFS-075X

JRFS-115X

JRFS-105X

• AC current probe utility by the Rogowski principle• Flexible and lightweight• Easy & quick installation in uninterruptible power line• Insulation CATⅢ 1000V, Ⅳ 600V• Certificated for UL & CE complying with IEC 61010-1• Optional size is available from ID 75 to 115mm. (ex. ID 80mm)

APPLICATIONS• Revenue-Grade distribution transformer monitoring• Energy sub-meters• Power meters• Power quality monitoring• Condition monitoring• Distributed measurement systems

FEATURES

Clamp-on Flexible Rogowski coil Current Transformer has been designed for accurate measurement of AC current with a safe output voltage RMS. JRFS-XXX-M/P (X-XXX) series is the precision current probe for Revenue-Grade Distribution transformer monitoring. With voltage integrator configuration, it can replace the existing CT directly.

Accuracy

Phase Shift

Frequency Range

Output Sensitivity Tolerance

Output Sensitivity Tolerance

Linearity (10% to 100% of range)

Conductor Position Sensitivity

Influence of External Field

Working Temp.

Storage Temp.

Insulation Category

Safety Standards

Testing Voltage

M Type

P Type

< 1%

< 1° at 50/60Hz (typical < 0.5°)

10Hz to 20kHz

±10% maximum(Uncalibrated)

±0.5% of reading at 25°C (Calibrated)

±0.2% of reading

±2% maximum

±2% maximum

-30˚C ~ + 60˚C

-40˚C ~ + 60˚C

CATⅢ 1000V / CATIV 600V (PD2-Double Insulation)

EN/UL/cUL 61010-1, 61010-2-032

7400V/1min

Rated Current 250A ~ 1kA 1kA ~ 2kA

104mV(50Hz) [124.8mV(60Hz)] 1kA

35mV(50Hz) [42mV(60Hz)]1kAOutput Voltage

Precision Clamp onFlexible Rogowski coil CTJRFS-XXX-M/P (X-XXX) Series IP 67

PROBE HEAD ONLY

vac

Page 10: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

10CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

DIMENSIONS

OPTION : INTEGRATOR C/M/S/T-XXX SERIES

Φ75~115

Φ6

Φ8

38.7

54.4

28

ONE TURNPRIMARY

AC OutputS1(OUT) S2(G)

Max. 240 cm

BLACK(COMMON)

WHITE(HIGH)

POWER SUPPLY:10 to 30V DC+ –BLACK

Shielded wire

WHITEONE TURNPRIMARY

* Diagnostic green LED to check power supply function

P1 P2 S1 S2 + −

I N P U TOUTPUTPOWER

: : :

POWERLED

Power supply : 24V DC

Power supply : 24V DC

S Series Output : 333mVAC

Output : 333mVAC

Output : 333mVAC

T Series Output: 333mVAC

C Type 333mVAC

102.2

21.7

15

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

48.8

074

.40

86.0

0

60.0070.00

2.505x5.00=25.005x5.00=25.00

1.25(72x)

- 0.20+0.00

1 2 3 4 5

6 7 8 9 10

41.9

0±0

.20

4.40

2.00

86.0

0

30.90 ±0.2035.00

1 2 3 4 5

6 7 8 9 10P1 P2 S1 S2

Input Output

Power

+ –

+ –

P1 P2 S1 S2

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Power

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

M Type 333mVAC

THREE PHASEI N P U TOUTPUTPOWER

SINGLE PHASEI N P U TOUTPUTPOWER

1 2

6 7 9 10

S1

S2

Vin -

Vin +

I N P U TOUTPUTPOWER

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Input Output Input Output Input Output

Page 11: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

11 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

SPECIFICATION

ModelJRFS-080X

JRFS-075X

JRFS-115X

JRFS-105X

JRFS-180X

JRFS-170X

JRFS-300X

JRFS-295X

• AC current probe utility by the Rogowski principle• Flexible and lightweight• Easy & quick installation in uninterruptible power line• Insulation CATⅢ 1000V, Ⅳ 600V• Certificated for UL & CE complying with IEC 61010-1• Optional size is available from ID 75 to 300mm. (ex. ID 80mm)

APPLICATIONS• Revenue-Grade distribution transformer monitoring• Energy sub-meters• Power meters• Power quality monitoring• Condition monitoring• Distributed measurement systems

FEATURES

Clamp-on Flexible Rogowski coil Current Transformer has been designed for accurate measurement of AC current with a safe output voltage RMS. JRFS-XXX-R/U (X-XXX) series is the precision current probe for Revenue-Grade Distribution transformer monitoring. With voltage integrator configuration, it can replace the existing CT directly.

Accuracy

Phase Shift

Frequency Range

Output Sensitivity Tolerance

Output Sensitivity Tolerance

Linearity (10% to 100% of range)

Conductor Position Sensitivity

Influence of External Field

Working Temp.

Storage Temp.

Insulation Category

Safety Standards

Testing Voltage

R Type

U Type

< 1%

< 1° at 50/60Hz (typical < 0.5°)

10Hz to 20kHz

±10% maximum(Uncalibrated)

±0.5% of reading at 25°C (Calibrated)

±0.2% of reading

±2% maximum

±2% maximum

-30˚C ~ + 80˚C

-40˚C ~ + 80˚C

CATⅢ 1000V / CATIV 600V (PD2-Double Insulation)

EN/UL/cUL 61010-1, 61010-2-032

7400V/1min

Rated Current 500A ~ 6kA

104mV(50Hz) [124.8mV(60Hz)] 1kA

35mV(50Hz) [42mV(60Hz)]1kAOutput Voltage

Precision Clamp onFlexible Rogowski coil CTJRFS-XXX-R/U (X-XXX) Series IP 67

PROBE HEAD ONLY

vac

S1 ●

S2

Vin -

Vin+ ●●

POWER SUPPLY 5, 12, 24V DC

Page 12: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

12CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

DIMENSIONS

OPTION : INTEGRATOR C/M/S/T-XXX SERIES

Φ75~300

Φ6

Φ8

23

38Φ26

38

ONE TURNPRIMARY

AC OutputS1(OUT) S2(G)

Max. 240 cm

BLACK(COMMON)

WHITE(HIGH)

POWER SUPPLY:10 to 30V DC+ –BLACK

Shielded wire

WHITEONE TURNPRIMARY

* Diagnostic green LED to check power supply function

P1 P2 S1 S2 + −

I N P U TOUTPUTPOWER

: : :

POWERLED

Power supply : 24V DC

Power supply : 24V DC

S Series Output : 333mVAC

Output : 333mVAC

Output : 333mVAC

T Series Output: 333mVAC

C Type 333mVAC

102.2

21.7

15

13 14 15 16 17 18 19 20 21 22 23 24

1 2 3 4 5 6 7 8 9 10 11 12

48.8

074

.40

86.0

0

60.0070.00

2.505x5.00=25.005x5.00=25.00

1.25(72x)

- 0.20+0.00

1 2 3 4 5

6 7 8 9 10

41.9

0±0

.20

4.40

2.00

86.0

0

30.90 ±0.2035.00

1 2 3 4 5

6 7 8 9 10P1 P2 S1 S2

Input Output

Power

+ –

+ –

P1 P2 S1 S2

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Power

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

5.00

42.8

057

.30

58.9

0

45.5060.00

86.00

M Type 333mVAC

THREE PHASEI N P U TOUTPUTPOWER

SINGLE PHASEI N P U TOUTPUTPOWER

1 2

6 7 9 10

S1

S2

Vin -

Vin +

I N P U TOUTPUTPOWER

P1 P2 S1 S2 P1 P2 S1 S2 P1 P2 S1 S2

Input Output Input Output Input Output

Page 13: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

13 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

SPECIFICATIONModel

Current Ratio

Rated Current

Accuracy

Output Signal

Power Requirement

Phase Shift

Frequency

Linearity

Conductor Position Sensitivity

Influence of External Field

Operating Temp.

Insulation Category

JRF MOI 333M-80 JRF MOI 333M-115

Input from 250 Amp to 6,000 Amp

100, 150, 200, 250, 300, 400, 500, 600, 800, 1k, 1.2k, 1.5k, 2k, 2.4k, 2.5k, 3k, 4k, 5k, 6k

<1% typical at 2% to 120% of rated current

333mVAC

+ 5 VDC , 30mA Maximum

<1º at rated current

50/60Hz

±0.2%

±1% maximum

±1.5% maximum

-30°C ~ +80°C

CATⅢ 1000V, Ⅳ 600V

• AC current probe utility by the Rogowski principle• Flexible and lightweight• Easy & quick installation in uninterruptible power line• Insulation CATⅢ 1000V, Ⅳ 600V• Accuracy Class 0.5/1.0 complying with IEC61869-2• Certificated for & CE complying with IEC 61010-1• Optional size is available from ID 80 to 115mm.

APPLICATIONS• Revenue-Grade distribution transformer monitoring• Energy sub-meters• Power meters• Power quality monitoring• Condition monitoring• Distributed measurement systems

FEATURES

HOW TO USE

Clamp-on Flexible Rogowski coil Current Transducer has been designed for accurate measurement of AC current with a safe output voltage RMS. JRF MOI series is the precision current probe for Revenue-Grade Distribution transformer monitoring. With voltage integrator configuration, it can replace the existing CT directly.

JRF-M

OI

JRF-M

OI

Precision Clamp onFlexible Rogowski coil CTJRF MOI 333M Series IP 67

PROBE HEAD ONLY

vac

Page 14: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

14CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

OUTDOOR POWER & INDOOR POWER LOAD LINEARITY & PHASE ANGLE ERROR GRAPH

DIMENSION(CHOOSE JRF-MOI-XXC IF YOU REQUIRE TIES FOR ATTACHING TO THE CONDUCTOR)

THE ROGOWSKI LOOP CIRCUMFERENCE IS 19CM

OUTPUT VOLTAGE GRAPH

Rated Current : 1000A@60Hz

F(I)

[%]&

f[˚]

@25

˚C

-21 105 20 100 15050 120 200

-1

0

1

2IEC60044-1 A m p l i t u d e

P h a s eJRF-MOIP:Red S1:White S2:Black

+ 5VDC Power Supply

333mV ACoutput

AC main power

METER

P S1

P1

P2S2(G)

Power source (P) : +5VDC (±5%), connected to S2 (Ground)(Keep (P) should be under ±5% of +5VDC to avoid a damage on power supply)Output : S1, connected to S2 (Ground)P : Red OUTPUT : White S2(G) : Black

Percentage of Input Current

Out

put

Vol

tag

e

00 20 40 60 80 100 300

0.066

0.133

0.199

0.266

0.333

0.999

JRF-MOI

Adjacent to the inside coil edgeAdjacent to the clip together mechanismCentral in the Rogowski loop

Conductor Position

< 0.5%< 0.5%0.1%

Typical Error(%)

Note that with a larger conductor the variation of error with conductor position will decrease and approach the calivrated value.

P:Black S1:White S2:Red

ModelJRF MOI 333M-80C

JRF MOI 333M-115C

A80

115

B96

141

C285

385

D70

105

* Unit : mm

69.2

8

38.6

7

71̊

6

A D

B

C

ModelJRF MOI 333M-80

JRF MOI 333M-115

A80

115

B96

141

C285

385

D80

115

* Unit : mm

69.2

8

38.6

7

71̊

6

Ø 3

A D

B

C

Page 15: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

15 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

Precision Clamp onFlexible Rogowski coil CTJRF MOI XXXXPU Series IP 67

PROBE HEAD ONLY

vac

JRF-MOI-PU Rogowski coil current transformer are accurate, flexible, rope style air coils that can be connected around conduc-tors while the conductor is “lives”. They are easier to install and measure than traditional split and solid core CT.With their flexible design and light weight, they are ideal for bus bars and irregular-shaped bundles of multiple conductors. The Rogowski coil technology offers low phase shift error, inductance and excellent linearity while largely immune to electro-magnetic interference and pulsed DC, providing a high rate of accuracy.JRF-MOI-PU coils can be used in single and three-phase measurement applications. The output of the built-in voltage integrator provides an AC voltage of 333mV at the rated input current. There is an option to choose a different output voltage between 100-500mV AC at up to 6,000 Amps. The built-in integrator and DC power supply allows simple wiring installation. Multiple rogowski coils can be powered by one AC/DC power supply.※ Choose JRF-MOI-PUC if you require ties for fixing to the conductor

HOW TO USE

APPLICATIONS FEATURES• Revenue-Grade distribution transformer monitoring• Energy sub-meters• Power meters• Power quality monitoring• Condition monitoring• Distributed measurement systems

• AC current probe• Flexible and lightweight• Easy & quick installation on uninterruptible power lines• Insulation CATⅢ 1,000V AC, Ⅳ 600V AC.• Accuracy Class 0.5/1.0 complying with IEC61869-2, ANSI C57.13• In progress of certification for & CE complying with IEC61010-1• IP65, IP67, IP68 (International Protection code)• Several size are available from coil length from 285 to 385mm (aperture from 80 to 115 mm)

SPECIFICATIONModel

Current Range

Rated Currents

Max Output

Accuracy

Rated Output Voltage

Power Requirement

Phase Shift

Frequency

Linearity

Conductor Position Sensitivity

Influence of External Fields

Operating Temperature Range

Coil length

Connection Cable Type

Connection Cable length

JRF MOI XXXPU-80 JRF MOI XXXPU-115

250 Amp to 6,000 Amp

250, 300, 400, 500, 600, 800, 1k, 1.2k, 1.5k, 2k, 2.4k, 2.5k, 3k, 4k, 5k, 6k

1.3VAC

<1% typical at 2% to 120% of rated current

333 mV AC

+24V DC, ±5%, 70mA Maximum

<0.5° at rated current

50/60Hz

±0.2%

±1% maximum

±1.5% maximum

-25°C ~ +65°C

From 285 to 385mm

4 x AWG24

on request

Page 16: PRECISION CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMERsmartsensing.net/wp-content/uploads/2018/02/4-PRECISION... · 2018-02-27 · 3 CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT

16CLAMP ON FLEXIBLE ROGOWSKI COIL CURRENT TRANSFORMER

S1S2shield+DCGnd

5 Wire Cable: White: Black: Yellow: Red: Green

L1 L2 L3

DC

Pow

erSu

pply

GS1

S2(S

)S1

S2(S

)S1

S2(S

)

DIG

ITA

LPO

WER

MET

ER

CT1

CT2

CT3

ModelJRF MOI xxxPUC-80

JRF MOI xxxPUC-115

A80

115

B96

131

C285

385

D70

105

* Unit : mm

69.2

8

38.6

7

71̊

6

A D

B

C

ModelJRF MOI xxxPU-80

JRF MOI xxxPU-115

A80

115

B96

131

C285

385

D80

115

* Unit : mm

69.2

8

38.6

7

71̊

6

Ø 3

A D

B

C

Adjacent to the coil edgeAdjacent to the clip together mechanismCentral in the Rogowski loop

Conductor Position

< 0.5%< 0.5%

0.1%

Typical Error(%)

Note that with a larger conductor the variation of error withconductor position will decrease and approach the calibrated value.

Rated Current : 1000A@60Hz

F(I)

[%]&

f[˚]

@25

˚C +1˚

+2˚

-1˚

-2˚-2%1 5 10 20 50 100 120 150 200

-1%

0%

+1%

+2%IEC60044-1 R a t i o e r r o r

P h a s e e r r o r

Models

FWA020012A-10B

MDR-10-12

ApplicationDesktop power supply, For up to 24 pcsJRF-MOI xxxPU Conditioning Circuits

DIN-rail power supply, For up to 12 pcsJRF-MOI xxxPU Conditioning Circuits

AC Input Voltage (Nominal)

85-264 Vac (100-240)@1.67 amps

85-264 Vac (100-240)@0.84amps

Nominal Weight

11.5 oz (326 grams)

6 oz (170 grams)

OUTDOOR POWER & INDOOR POWER LOAD

AC/DC POWER SUPPLY

DIMENSIONS (CHOOSE JRF-MOI-PUC IF YOU REQUIRE TIES FOR ATTACHING TO THE CONDUCTOR)

RATIO & PHASE ERROR GRAPH

POSITIONING ERROR