  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    1/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    1 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    SSDAC Unit Sl. No (SF UNIT) ---------------- (EF UNIT) --------------

    0 General Information:

    0.1 Station / Section Name0.2 Division / Zonal Railway

    0.3 Contact Details of Railways at site0.4 Contact Details of Railways at HQr / Division 0.5 Total No of Detection point / Section0.6 Contract No./PO No.0.7 Date of Pre commissioning inspection0.8 Name of firms authorized Rep

    Note : 1. System should be installed and commissioned by authorized

    technical staff of manufacturer only.2. Installation practices of SSDAC model SSDAC-G36 for Phase Reversal

    should be strictly adhered to and checked before commissioningcovering all points in the following document

    1 Out door(Location Box)

    ObservedOK / Not

    OKSl.No.

    Item RequiredSF

    UNITEF

    UNIT

    1.1Relay used inRelay Box VR &PR

    Q type, 24V, 1000 Ohm(Printed Sticker of VR/PR either onfront cover or inside bottom of relaybox.)

    1.2Diode across eachrelay coil inreverse bias.

    Should be provided with BY127/ IN4007 / IN5408

    1.3 Unused Quad pair To be terminated on terminals.

    1.4Dressing of Quadpair

    To be properly dressed withinsulated tape

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    2/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    2 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    2 Outdoor (track device)

    ObservedOK / Not

    OKSl.No.

    Item RequiredSF

    UNITEF

    UNIT

    2.1

    Wiring of TX / RX

    coils & MS couplercables

    Wired on approved Wago/

    Phoenix make terminals.

    2.2

    Condition of wornout of Rail60 Kg - 13 mm52 Kg - 8 mm90 R - 5 mm

    Should be within vertical limit ofworn out159 -172 mm148 -156 mm138 -143 mm

    2.3

    Marking of holeson rail(From bottom ofthe rail)

    GGT Jig as per drawing no.DRG-23 of Installation ManualVersion 1.0 Revision 1 to beused as per rail section.60 Kg - 84 mm52 Kg - 68 mm90 R - 57 mmFrom the bottom of the rail.

    2.4Drilling of holes in

    the web of rail

    Should be of 14mm dia. Shouldbe square (perpendicular),

    should not be oblong.

    2.5

    Torque applied tofix track deviceusing Torquewrench

    Jaicom make JPR65 orequivalent - 88 Nm.

    2.6 Fixing of TX Outside the rail

    2.7 Fixing of RX Inside the rail

    2.8 Fixing of axledetectors at entry& exit end

    On the same rail as per

    drawing no. DRG-12 ofInstallation ManualVersion 1.0Revision 1

    2.9Laying of axledetector cable

    In corrugated / HDPE pipe

    2 10Screen of axle

    Should be earthed

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    3/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    3 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    Observed

    S.No. Item Required SFUNIT

    EFUNIT

    RemarksOK /

    NOT OK

    2.12 Rail section 60 Kg / 52 Kg / 90 R

    2.13Nuts, bolts &washers for fixing

    rail contacts

    Insertion of bolt from RX coilside i.e., inside of the rail

    2.14Position ofdeflector

    30 cm away from TX / RX coilsin the next sleeper

    2.15 Height of deflectorShould not be higher than therail top

    2.16Clearancebetween sleepers

    400 mm between sleepers

    2.17 Embossing on railShould not be covered by Track

    device

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    4/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    4 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    3 Outdoor Quad Cable

    3. Outdoor (Quad Cable / PIJF twisted pairs telecom cable for Axle countersystem working in station area, As per RDSO letter no. STS / E / SSDAC /

    SPN / 177 dated-28 / 30.08.2006)

    3.1 Test format for testing of QUAD cable / PIJ F twisted pair telecom cable

    before commissioning of SSDAC in Station area

    Sl.No.

    Item ExpectedMeasured /Observed

    Remarks(OK / Not OK)

    3.1.1CommunicationMediaType of Cable

    Only Quad cable / PIJF twistedpair telecom cable is to beused between field units.No Signaling Cable is to beused in totality / parts.

    3.1.2 Use of pair

    Proper pair of wires to be usedfor connectivity.Annexure 1 for Quad cablemay be referred

    3.1.3

    Duplication of

    Wires

    No wires to be paralleled for

    reducing conductor resistance.

    3.1.4Insulationresistance ofQuad cable

    Shall be greater than / equal to10 M ohm.

    3.1.5Loop resistanceof designatedpair

    Not to exceed 56 ohm / Kmsfor Quad Cable at 200 C &_______* ohms / Kms for PIJFtelecom cable.

    Annexure 2 for correctionfactor may be referred.

    3.1.6Attenuation lossmeasured at 2KHz

    Shall not be greater than 30.0dB for full length of the cableused.

    3.1.7Near End CrossT lk (NEXT)

    Shall be better than 55 dB ford bl

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    5/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    5 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    Sl.No.

    Item ExpectedMeasured /Observed

    Remarks(OK / Not OK)

    3.1.10Separate Earth ofQuad / PIJFtelecom cable

    Shall be less than One ohm

    3.1.11Cable allocationtable

    Shall be filled up & attached

    3.1.12Unused Quadpair

    To be terminated on terminals.

    3.1.13Dressing of Quadpair

    To be properly dressed withinsulated tape.

    3.1.14Spiral beforetermination.

    No individual conductor to bemade spiral

    3.2 Test format for testing of QUAD cable before commissioning ofSSDAC /BPAC / SSBPAC (D) used in between Station to station

    Sl.No.

    Item ExpectedMeasured /Observed

    Remarks(OK / Not OK)

    3.2.1Block sectionlength limit

    12 Km.

    3.2.2CommunicationMediaType of Cable

    Only Quad cable is to beused between field units.No Signaling Cable is to beused in totality / parts.

    3.2.3 Use of pair

    Proper pair of wires to beused for connectivity.Annexure 1 may bereferred

    3.2.4Duplication ofWires

    No wires to be paralleledfor reducing conductorresistance.

    3.2.5Insulationresistance ofQ d bl

    Shall be greater than /equal to 10 M ohm.

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    6/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    6 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    Sl. No. Item ExpectedMeasured /Observed

    Remarks(OK / Not OK)

    3.2.6Loop resistance of

    designated pair

    Not to exceed 56 ohm/Kms at20

    0C.

    See Annexure 2 forcorrection factor.

    3.2.7Attenuation lossmeasured at 2KHz

    Shall not be greater than 30.0dB for full length of the cableused.

    3.2.8Near End CrossTalk (NEXT)

    Shall be better than 55 dB forquad cable.

    3.2.9 Far End CrossTalk (FEXT)

    Shall be better than 55 dB forquad cable.

    3.2.10Continuity of cablearmour

    Continuity shall be there

    3.2.11Separate Earth ofquad cable

    Shall be less than One ohm

    3.2.12Cable allocation

    tableShall be filled up & attached

    3.2.13 Unused Quad pairTo be terminated onterminals.

    3.2.14Dressing of Quadpair

    To be properly dressed withinsulated tape.

    3.2.15Spiral beforetermination.

    No individual conductor to bemade spiral

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    7/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    7 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    3.3 Test format for testing of local QUAD / PIJF twisted pair telecom cable & OFC before

    commissioning of SSDAC/BPAC/SSBPAC (D)on OFC in betweenstation to station.

    Sl. No. Item ExpectedMeasured /Observed

    Remarks(OK / Not OK)

    3.3.1 QUAD / PIJF

    3.3.1.1CommunicationMediaType of Cable

    Jelly filled telecom cable /Quad cable to be usedbetween field units &OFC Equipment room.Signaling Cable shall notbe used at all.

    3.3.1.2 Use of pairProper pair of wires to beused for connectivity.Annex-1 may be referred

    3.3.1.3Duplication ofWires

    No wires to be paralleledfor reducing conductorresistance.

    3.3.1.4Insulationresistance ofQuad cable

    Shall be greater than/equal to 10 M ohm.

    3.3.1.5

    Loop

    resistance ofdesignated pair

    Not to exceed 56ohm/Kms at 20

    0C for

    Quad cable & _____*

    ohm / Kms for PIJFtelecom cable.See Annexure 2 forcorrection factor.

    3.3.1.6Earth of quadcable

    Shall be less than Oneohm

    3.3.1.7Cableallocation table

    Shall be filled up &attached

    3.3.1.8

    Unused Quad

    pair

    To be terminated on

    terminals.

    3.3.1.9Dressing ofQuad pair

    To be properly dressedwith insulated tape.

    3.3.1.10Spiral beforetermination.

    No individual conductor tobe made spiral

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    8/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    8 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    Sl. No. Item ExpectedMeasured /Observed

    Remarks(OK / Not OK)

    3.3.2 OFC

    3.3.2.1Channel lineup

    For 0 dB Trans signallevel, the receivedsignal level at otherend shall not be more

    than-15dB.

    3.3.3 Test format for testing of QUAD cable before commissioning ofSSDAC /BPAC / SSBPAC (D) used in between Station to Location Unit

    Measured / ObservedSl. No. Item Expected

    SF EF

    Remarks(OK / Not

    OK)

    CommunicationMedia

    Only Quad cable / PIJFtwisted pair telecom cableis to be used between fieldunit to Reset Box.3.3.3.1

    Type of CableNo Signaling Cable is to beused in totality / parts.

    3.3.3.2 Use of pairProper pair of wires to beused for connectivity.Annexure 1 for Quadcable may be referred

    3.3.3.3Duplication ofWires

    No wires to be paralleledfor reducing conductorresistance.

    3.3.3.4Insulationresistance ofQuad cable

    Shall be greater than /

    equal to 10 M ohm.

    3.3.3.5

    Loopresistance ofdesignatedpair

    Not to exceed 56 ohm /Kms for Quad Cable at 200

    C & _______* ohms / Kmsfor PIJF telecom cable.Annexure 2 for correction

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    9/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    9 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    Measured / ObservedSl. No. Item Expected

    SF EF

    Remarks(OK / Not

    OK)

    3.3.3.9Continuity ofcable armour

    Continuity shall be there

    3.3.3.10Separate Earthof Quad / PIJF

    telecom cable

    Shall be less than One ohm

    3.3.3.11Cableallocation table

    Shall be filled up & attached

    3.3.3.12Unused Quadpair

    To be terminated onterminals.

    3.3.3.13Dressing ofQuad pair

    To be properly dressed withinsulated tape.

    3.3.3.14Spiral beforetermination.

    No individual conductor to bemade spiral

    * PIJF telecom cable is available with three types of Conductor dia-

    Sl. No Condr Dia used in PIJFcable

    Resce at 200 C Loop Resce /KM

    1 0.50 mm 86 ohm +/- 6 172 ohm / Kms2 0.63 mm 58 ohm +/- 4 116 ohm / Kms3 0.90 mm 28 ohm +/- 2 56 ohm / Kms

    Note: Procedure for test-

    Attenuation Loss: The output/Input impedance of signal generator / dB meter shall be 600ohm.

    Near End Crosstalk:Test tone of 150 KHz to be fed in the adjacent pa ir of the same quad &

    NEXT to be measured at the same end on the other pair of the same quad.

    Far End Cross talk: Test tone of 150 KHz to be fed in the adjacent pa ir of the same quad &FEXT to be measured at the far end on the other pa ir of the same quad.

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    10/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    10 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    4 Outdoor electronics

    ObservedSl. No Item Required

    SF UNIT EF UNIT

    OK /Not OK

    4.1

    a. Sl. No. ofSSDAC units

    b. Details of Trackcircuit

    Same serial number pairs.Example 001 (SF Unit),

    001 (EF Unit)

    Track circuit No.

    4.2Placement of Cards/ modules

    Should be in proper position

    4.3Firmness of card /Modules

    Should be tightened with screw /clip provided

    4.4 MS Couplers Installed and tightened properly

    4.5 MS coupler cablesWired properly as per color / label

    code

    4.6Earthing of SSDACunits

    Should be provided firmly throughcopper strips or other standardcopper cable.Value < 1 Ohms

    4.7Earthing of RelayBox

    Should be provided firmly throughcopper strips or other standardcopper cable.

    Value < 1 Ohms4.8

    Fixing of SSDACunit

    Should be firmly fixed usingclamp

    4.9Fixing of RelayBox

    Should be firmly fixed usingclamp

    4.10

    Cable for taking24v D.C. fromcentral location to

    SSDAC unit.

    2 X 25 sq. mm Al.

    4.11

    External SurgeProtection Deviceson input, outputand power supplylines

    Indicative type, plug able or easyto install on a DIN rail. Non plugable shall be connected inparallel.

    Address pair should be different

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    11/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    11 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    ObservedOK /

    Not OKSl. No Item Required

    SF Unit EF Unit

    4.16

    Input voltage withChargerOFF.(Keep chargerOFF for 15 minutes

    before takingreading )

    22 V to 30 V DC

    4.17Ripple of InputPower Supply

    Less than 10 mV rms /50 mV peak to peak.

    4.18

    Relay drive outputto the Vital Relay.(This may be

    checked across R1& R2 of coil of vitalrelay in relay box).

    4.18 aSectionUnoccupied (Clear)

    >20V

    4.18 b Section Occupied < 2V

    4.19

    Relay drive outputto the Preparatory

    Relay. (This maybe checked acrossR1 & R2 of coil ofPreparatory relay inrelay box).

    4.19 a Section Clear >20V

    4.19 b Section Occupied < 2V

    4.20

    Drive voltage ofrepeater relays inpicked upcondition, whencharger is OFF for15 minutes.

    4.21 VPR >22V

    4 22 PPR >22V

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    12/21

    PageDate of

    issue

    Pre Commissioning C hec k List for Single Section Digital Axle

    Counter SIGVer 1

    12 of 2117.08.2007

    {2DP1S Configuration}(SW Version: S002)

    Of M/s G.G.TRONICS, Bangalore

    0606

    5.0 INDOOR POWER SUPPLY / CT RACK

    ObservedSl.No

    Item Required SFUNIT

    EFUNIT

    RemarksOK / Not

    OK

    5.1 PPR & VPR RelaysShall be of Q type 24 V ,

    1000 ohms5.2 Fuse Ratings 2.0 Amps

    5.3 Power supply for axlecounter

    a) Charger should be fit foraxle counter use.b) There should not be anyother load on the powersupply except axle counter.c) Class B & C types surge

    protection must beprovided on 230 V mainsline.

    5.4Ripple of Input PowerSupply

    Less than 10 mV rms / 50mV peak to peak.

    5.5Glitch in Input PowerSupply by putting ON /OFF the charger

    No glitch should be there

    5.6Drive voltage of theVPR. (This may bechecked across R1 &R2 of coil of relay).

    >22V

    5.7

    Drive voltage of thePPR. (This may bechecked across R1 &R2 of coil of relay).

    >22V

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    13/21

    Page 13 of 21

    Date of

    issue

    17.08.2007

    Pre-commissioning C heck List for Single-Section Digital Axle

    Counter

    {2DP1S configuration}(SW Version: S002)

    Of M/s GG TRONICS, BangaloreSIG 0606 Ver 1

    6.0 INDOOR(Reset Box Location)

    ObservedSl.No.

    Item RequiredSF UNIT EF UNIT

    RemarksOK / Not OK

    6.1 Reset BoxWired as per drg given inInstallation Manual

    6.2 Reset BoxEarthing.

    Connected to earthproperly.

    a) Reset not possible whenAxle Counter section isclear and healthy.

    6.3Reset function b) Reset not possible when

    Axle counter section is inPreparatory reset mode.

    6.424 VDC level atReset boxinput.

    22V DC to 30 V DC

    6.5Level of resetsignal fromreset box.

    48 V 4 V DC

    6.6

    Level of resetsignal atSSDAC unit

    input.

    38 V to 50V DC 2V DC

    7.0 COMMISSIONING

    Sl.No.

    Item RequiredMeasured /Observed

    Remarks (OK/ Not OK)

    7.1 CommissioningSystem should be installed &commissioned by personal trainedby the manufacturer.

    7.2 TrainingRailway personnel should be trainedbefore commissioning.

    System to be monitored for 72 hoursfor trouble free operation before

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    14/21

    Page 14 of 21

    Date of

    issue

    17.08.2007

    Pre-commissioning C heck List for Single-Section Digital Axle

    Counter

    {2DP1S configuration}(SW Version: S002)

    Of M/s GG TRONICS, BangaloreSIG 0606 Ver 1

    Commissioning Log sheet of SSDAC [Phase reversal detection Type]Model : SSDAC-G36, Software version : S002

    The following card version should be checked:

    Sl.No. Type of Card Part No. Version SFUNIT

    EFUNIT

    RemarksOK / Not

    OK

    1 Phase Detector Card 1 H001M01R1 00

    2 Phase Detector Card 2 H001M02R1 00

    3 CPU Card 1 of SF H001M09R1 00 * NA *

    4 CPU Card 2 of SF H001M10R1 00 * NA *

    5 CPU Card 1 of EF H001M11R1 00 * NA *

    6 CPU Card 2 of EF H001M12R1 00 * NA *

    7SMCPU/Event LoggerCard

    H001M03R1 00

    8 Communication Card 1 H001M04R1 00 * NA *

    9 Communication Card 2 H001M05R1 00 * NA *10 Relay Driver Card 1 H001M07R1 00 * NA *

    11 Relay Driver Card 2 H001M06R1 00 * NA *

    12DC-DC ConverterCard

    H001M08R1 00

    13 LCD Display Box H001M24R1 00

    14Relay Box with Q-type;24 V ; 1000 Ohmrelay-6F/6B

    G36-RB2R00 00

    15 Filter Box G36-RSFL00 00

    16Axle detectors(Web type TX Coils)

    G36-T212500 00

    Axle detectors

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    15/21

    Page 15 of 21

    Date of

    issue

    17.08.2007

    Pre-commissioning C heck List for Single-Section Digital Axle

    Counter

    {2DP1S configuration}(SW Version: S002)

    Of M/s GG TRONICS, BangaloreSIG 0606 Ver 1

    Annexure-I

    Precautions to be taken care during the wiring/connections are to be done at the time ofcommissioning of SSDAC/BPAC/SSBPAC (D)

    Position of One Quad in Quad cable:

    White(A)X

    Red (C) X X (D) Grey

    X(B)

    Quad color

    1st

    pair = White & Quad colour i.e A & B Wires2

    ndpair= Red & Grey colour i.e C & D Wires of designated colour of Quad.

    Each Quad is binded by the respective Quad colour binder

    Table-1

    Colour scheme of PE insulated Quads

    Quad Colour

    QuadNo

    PairNo.

    A - Wire B -Wire PairNo.

    C- Wire D - Wire

    Orange 1 1A White Orange 1B Red Grey

    Blue 2 2A White Blue 2B Red Grey

    Brown 3 3A White Brown 3B Red Grey

    Green 4 4A White Green 4B Red Grey

    Yellow 5 5A White Yellow 5B Red Grey

    Black 6 6A White Black 6B Red Grey

    Precautions to be taken for using QUAD Cable:

    Designated pair of wire of the same quad (mentioned in Table -1) should be used.

    Do not use one wire from one quad and another wire from some other quad.

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    16/21

    Page 16 of 21

    Date of

    issue

    17.08.2007

    Pre-commissioning C heck List for Single-Section Digital Axle

    Counter

    {2DP1S configuration}(SW Version: S002)

    Of M/s GG TRONICS, BangaloreSIG 0606 Ver 1

    Annexure-II

    TEMPERATURE CORRECTION FACTOR FOR CONDUCTOR RESISTANCE FOR ANNEALEDHIGH CONDUCTIVITY COPPER

    Temp.Deg C

    1.

    Corre.factor

    2.

    Temp.deg C

    1.

    Corre.Factor

    2.

    Tempdeg C

    1.

    Corre.factor

    2.

    Temp.deg C

    1.

    Corre.factor

    2.

    Temp.deg C

    1.

    Corre.Factor

    2

    5. 1.0638 17 1.0122 29 0.9653 41 0.9225 53 0.8834

    5.5 1.0618 17.5 1.0101 29.5 0.9634 41.5 0.9208 53.5 0.8818

    6. 1.0593 18 1.0081 30 0.9615 42 0.9191 54 0.8803

    6.5 1.0571 18.5 1.0060 30.5 0.9597 42.5 0.9174 54.5 0.8787

    7. 1.0549 19. 1.0040 31. 0.9579 43. 0.9158 55. 0.8772

    7.5 1.0526 19.5 1.0020 31.5 0.9560 43.5 0.9141 55.5 0.8757

    8. 1.0504 20. 1.0000 32. 0.9542 44.. 0.9124 56. 0.8741

    8.5 1.0482 20.5 0.9980 32.5 0.9524 44.5 0.9107 56.5 0.8726

    9. 1.0460 21. 0.9960 33. 0.9506 45. 0.9091 57. 0.8711

    9.5 1.0438 21.5 0.9940 33.5 0.9488 45.5 0.9074 57.5 0.8696

    10. 1.0417 22. 0.9920 34. 0.9470 46. 0.9058 58. 0.8681

    10.5 1.0395 22.5 0.9900 34.5 0.9452 46.5 0.9048 58.5 0.8667

    11. 1.0373 23. 0.9881 35. 0.9434 47. 0.9025 59. 0.8651

    11.5 1.0352 23.5 0.9862 35.5 0.9416 47.5 0.9009 59.5 0.8636

    12. 1.0331 24. 0.9843 36. 0.9398 48. 0.8993 60. 0.8621

    12.5 1.0309 24.5 0.9823 36.5 0.9380 48.5 0.8977 60.5 0.8606

    13. 1.0288 25. 0.9804 37. 0.9363 49. 0.8961 61. 0.8591

    13.5 1.0267 25.5 0.9785 37.5 0.9346 49.5 0.8945 61.5 0.8576

    14. 1.0246 26. 0.9766 38. 0.9328 50. 0.8929 62. 0.8562

    14.5 1.0223 26.5 0.9747 38.5 0.9311 50.5 0.8913 62.5 0.8547

    15. 1.0204 27. 0.9728 39. 0.9294 51. 0.8897 63. 0.8532

    15.5 1.0183 27.5 0.9709 39.5 0.9276 51.5 0.8881 63.5 0.8518

    16. 1.0163 28. 0.9690 40. 0.9259 52. 0.8863 64. 0.8503

    16 5 1 0142 28 5 0 9671 40 5 0 9242 52 5 0 8850 64 5 0 8489

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    17/21

    Page 17 of 21

    Date of

    issue

    17.08.2007

    Pre-commissioning C heck List for Single-Section Digital Axle

    Counter

    {2DP1S configuration}(SW Version: S002)

    Of M/s GG TRONICS, BangaloreSIG 0606 Ver 1

    Annexure-III

    Response test of digital Axle Counter with different type of TrolleyWheels done jointly with railways

    S.No. Type of Trolley wheelObserved Result( No

    influence / Goes to error/ Counted / other)

    Remarks

    4 spoke wheel

    Wheel Dia with flange

    Wheel base

    Flange thickness

    Wheel Flange

    1

    Spoke width

    6 spoke wheel

    Wheel Dia with flange

    Wheel Width

    Flange width

    Flange depth

    2

    Spoke width

    Solid Wheel with 6

    holes

    Wheel Dia with flange

    Wheel Width

    Flange width

    3

    Flange depth

    8 spoke wheel

    Wheel Dia with flange

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    18/21

    Page 18 of 21

    Date of

    issue

    17.08.2007

    Pre-commissioning C heck List for Single-Section Digital Axle

    Counter

    {2DP1S configuration}(SW Version: S002)

    Of M/s GG TRONICS, BangaloreSIG 0606 Ver 1

    S.No. Type of Trolley wheelObserved Result( No

    influence / Goes to error/ Counted / other)

    Remarks

    8 spoke with slots

    Wheel Dia with flange

    Wheel Width

    Flange width

    Flange depth

    5

    Spoke width

    Perforated

    No. of perforation withdia.

    Wheel Dia with flange

    Wheel Width

    Flange width

    Flange depth

    6

    Spoke width Solid wheel

    Wheel Dia with flange

    Wheel Width

    Flange width

    7

    Flange depth

    Motor trolley wheel ,Solid

    Wheel Dia with flange

    Wheel Width

    Flange width

    8

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    19/21

    Page 19 of 21

    Date of

    issue

    17.08.2007

    Pre-commissioning C heck List for Single-Section Digital Axle

    Counter

    {2DP1S configuration}(SW Version: S002)

    Of M/s GG TRONICS, BangaloreSIG 0606

    S.No. Type of Trolley wheel

    Observed Result( Noinfluence / Goes toerror / Counted /

    other)

    Remarks

    Material Trolley solid

    wheel

    Wheel Dia with flange

    Wheel Width

    Flange width 10

    Flange depth

    Motor Trolley wheel with6holes

    Wheel Dia with flange

    Wheel Width

    Flange width

    11

    Flange depth

    Tower Wagon

    Wheel Dia with flange Wheel Width

    Flange width

    12

    Flange depth

    13 Motor trolley following a train

    Ver 1

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    20/21

    Page 20 of 21

    Date of

    issue

    Pre-commissioning Check List for Single-Section Digital Axle

    Counter{2DP1S configuration}(SW Version: S002)

    SIG 0606 Ver 117.08.2007

    Of M/s GG TRONICS, Bangalore

    Signature of G.G.Tronics Rep Signature of Railway RepWith Name, Designation & Date with Name, Designation & Date

    Maintenance log sheet for SSDAC (SF UNIT)

    DC DC Converter

    DC Volts

    Description.

    Ba

    ttery(24V)

    Tx1

    Vrms /

    freq

    Tx2Vrms /

    freq

    Rx1Vrms

    Rx2Vrms

    Phase Detector 1DC Volts

    Phase Detector2

    DC Volts

    With PushTrolley on

    axle detectors

    (4 spokes) 5 V 12 V -12 V +18V 24 V

    RX PH-SIG &GND Socket

    RX PH-SIG &GND Socket

    RX PH-SIG &GND Socket

    Test

    Points FTB

    1 & 2

    FTB31 &32

    FTB33 &34

    FTB35 &36

    FTB37 &38 Normal

    Dummywheel

    NormalDummywheel

    PD1 PD2

    Monitoring Sockets on DC-DC convertercard

    (Limit)

    for

    Phase

    Date

    22-30V

    40 to

    70 V

    20.802to

    21.302KHz

    40 V to

    70V

    24.750to

    25.250KHz

    300mV to1.2V(AC)

    300mV to1.2V(AC)

    10 V to12 V

    < 1 V 10 V to12 V

    < 1 V10 Vto 12

    V10 Vto 12

    V4.75to

    5.25V

    11.75Vto12.25V

    -11.75

    Vto

    -12.25V

    17.75V

    to18.25

    V22Vto

    26V

  • 7/29/2019 Pre Commission Check List for 2DP1S-Ver1 PDF

    21/21

    Page 21 of 21

    Date of

    issue

    Pre-commissioning Check List for Single-Section Digital Axle

    Counter{2DP1S configuration}(SW Version: S002)

    SIG 0606 Ver 117.08.2007

    Of M/s GG TRONICS, Bangalore

    Signature of G.G.Tronics Rep Signature of Railway RepWith Name, Designation & Date with Name, Designation & Date

    Maintenance log sheet for SSDAC (EF UNIT)

    DC DC Converter

    DC Volts

    De

    scription.

    Battery(24V)

    Tx1

    Vrms /

    freq

    Tx2Vrms /

    freq

    Rx1Vrms

    Rx2Vrms

    Phase Detector 1DC Volts

    Phase Detector2

    DC Volts

    With PushTrolley on

    axle detectors

    (4 spokes) 5 V 12 V -12 V +18V 24 V

    RX PH-SIG &GND Socket

    RX PH-SIG &GND Socket

    RX PH-SIG &GND Socket

    Test

    Points FTB

    1 & 2

    FTB31 &32

    FTB33 &34

    FTB35 &36

    FTB37 &38 Normal

    Dummywheel

    NormalDummywheel

    PD1 PD2

    Monitoring Sockets on DC-DC convertercard

    (Limit)

    for

    Phase

    Date

    22-30V

    40 to

    70 V

    20.802to

    21.302KHz

    40 V to

    70V

    24.750to

    25.250KHz

    300mV to1.2V(AC)

    300mV to1.2V(AC)

    10 V to12 V

    < 1 V 10 V to12 V

    < 1 V10 Vto 12

    V10 Vto 12

    V4.75to

    5.25V

    11.75Vto12.25V

    -11.75

    Vto

    -12.25V

    17.75V

    to18.25

    V22Vto

    26V