powpak™ relay module...rmm-5r-dv-b 220-240 v~ 868.125 – 868.475 mhz china and singapore powpak...
TRANSCRIPT
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak™ Relay Module Energi TriPak™ Series Wireless Lighting Control
369-549b 1 01.23.12
PowPak™ Relay Module
The PowPak™ Relay Module is a radio frequency (RF) device capable of controlling up to 5 A of general-purpose load based on input from Pico® controls and Radio Powr Savr™ occupancy and daylight sensors. An optional, low-voltage dry contact closure output is available to communicate occupancy status to 3rd-party systems such as HVAC controllers.
Communication with RF input devices, such as Pico® controls and Radio Powr Savr™ sensors, is accomplished using Lutron Clear Connect™ RF Technology.
Features
•Capableofswitching5 Aofgeneral-purposeloads•Optionallow-voltagedrycontactclosureoutputprovides
integration to building management systems, HVAC, VAV, etc.•Variousoperatingvoltagesavailable—refertomodelnumber
chart below for details on voltage requirements•ReceiveswirelessinputsfromuptoninePico® controls, six
Radio Powr Savr™ occupancy/vacancy sensors, and one Radio Powr Savr™ daylight sensor
•UtilizesLutronClearConnect™RFTechnology—refertomodelnumber chart below for frequency band data
•Mountstoajunctionboxthroughastandardhalf-inch(NPT tradesize)knockout
•Complieswithrequirementsforuseinacompartment handling environmental air (plenum) per NEC® 2011 300.22(C)(3)
Description Model Number Operating Voltage
Frequency Band Region
PowPak™ Relay Module RMJ-5R-DV-B 120 / 277 V~ 431.0–437.0MHz U.S.A.,Canada,Mexico
RMQ-5R-DV-B 220 -240 V~ 433.05–434.79MHz Hong KongRMM-5R-DV-B 220 -240 V~ 868.125–868.475MHz China and
SingaporePowPak™ Relay Module withOccupancy-StatusCCO
RMJ-5RCCO1-DV-B 120 / 277 V~ 431.0–437.0MHz U.S.A.,Canada,Mexico
RMQ-5RCCO1-DV-B 220 -240 V~ 433.05–434.79MHz Hong KongRMM-5RCCO1-DV-B 220 -240 V~ 868.125–868.475MHz China and
Singapore
NOTE: Contact Lutron for frequency band compatibility for your geographic region if it is not indicated above.
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak™ Relay Module Energi TriPak™ Series Wireless Lighting Control
369-549b 2 01.23.12
Specifications
Regulatory Approvals
RMJ- models only•ULListed•UL2043PlenumRated•FCCapproved.ComplieswiththelimitsforaClass B
device, pursuant to Part 15 of the FCC rules.•CSAandIC•COFETEL•NOM
Power
•Operatingvoltage: RMJ- models 120/277 V~ 50/60Hz RMQ- models 220-240 V~ 50/60Hz RMM- models 220-240 V~ 50/60Hz
System Communication
•OperatesusingClearConnect™ RF Technology for reliable wireless communication; refer to model number chart on page 1 for frequency band details
•RFrangeis30ft(10m)
Environment
•Ambientoperatingtemperature:32°Fto131 °F (0°Cto55 °C)
•0%to90%humidity,non-condensing•Forindooruseonly
Load
•Maximumload:5Ageneralpurpose.Nominimumload requirements.
•Loadtypesinclude(butarenotlimitedto): –Incandescent – MLV – ELV – Resistive –Inductive – Magnetic fluorescent – Electronic fluorescent•Motorrating:
RMJ- models 1/6 HP (120 V~), 1/3 HP (277 V~) RMQ- models 1/2 HP (220-240 V~) RMM- models 1/2 HP (220-240 V~)
•Loadrelayisnon-latching
Key Design Features
•LEDstatusindicatorshowscurrentloadstatusandprovides programming feedback
•Powerfailurememory:Ifpowerisinterrupted,connected loads will return to the previous level prior to interruption
•DaylightingcanbeoverriddenbypressingtheONbutton on any associated Pico®
– Daylighting will be re-enabled after 2 hours or after the area becomes unoccupied
Contact Closure Output (CCO version only)
•Providesoccupancystatusto3rd-partyequipmentsuch as building management systems, HVAC, and VAV controllers
•Providesbothnormallyopen(NO)andnormallyclosed (NC) dry contacts
•Maintainedoutputtype•CCOterminalsaccept20to16AWG(0.5 to 1.5 mm2)
solid or stranded wire•Outputislatching•Notforvoltagesgreaterthan24V
•TheCCOisnotratedtocontrolunclamped,inductiveloads.Inductiveloadsinclude,butarenotlimited to, relays, solenoids, and motors. To control these types of equipment, a flyback diode must be used (DC voltages only). See diagram below. For more information, please see Application Note #434 (p/n 048434).
SwitchingVoltage
0-24 V-
0-24 V~
24 V- max.
Inductive Load
CCO Output
NO NC
COM
Flyback Diode
(required for inductive
loads)
Resistive Load
1.0 A0.5 A
R
+-
SwitchingVoltage
0-24 V-
0-24 V~
24 V- max.
Inductive Load
CCO Output
NO NC
COM
Flyback Diode
(required for inductive
loads)
Resistive Load
1.0 A0.5 A
R
+-
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak™ Relay Module Energi TriPak™ Series Wireless Lighting Control
369-549b 3 01.23.12
Test
System Diagram
Radio Powr Savr™OccupancySensor(upto6)
Radio Powr Savr™ Daylight Sensor (up to 1)
Pico® Control (up to 9)
To 3rd-Party Equipment
To power source and load
Wiring Diagram
HOT
NEUTRAL
SWITCHED HOTLOAD
COM
NO
NC
To 3rd-PartyEquipment
Occupancy-Status CCO(RM__-5RCCO1-DV-B only)
Junction Box
Black
Red
White
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak™ Relay Module Energi TriPak™ Series Wireless Lighting Control
369-549b 4 01.23.12
Wiring Diagram
Input Voltage
Conduit Nut
White (Neutral)
Black (Hot)
Red (Switched Hot)
NOTE:WhenwiringCCOto3rd-partysystems,use20to16AWG(0.5to1.5mm2) solid or stranded wire.
To 3rd Party Equipment
To Load
NO(NormallyOpen)
NC(Normally Closed)
COM(Common)
PowPak™InstallationInsideJunctionBox (Dimming Module RMJ-ECO32-DV-B shown)
Antenna
BOXA
BOXB
Insomeapplications,aPowPak™modulecanbeinstalledinsidea4 in x 4 in(102 mm x 102 mm)junctionbox.Forinformation about how to perform this installation, please see Application Note #423 (p/n 048423).
CCOoperationaffectedonlybyassociatedoccupancyorvacancysensors.Room Occupied: NO=CloseNC=OpenRoom Unoccupied: NO=OpenNC=Close
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak™ Relay Module Energi TriPak™ Series Wireless Lighting Control
369-549b 5 01.23.12
Dimensions Dimensionsareshownas:in(mm)
Range Diagram
•ContactLutronfirstforapplicationsusingfoil-backedormetallicceilingtiles.
1.25(31.8)
2.82(71.6)
3.42(86.9)
3.94(100.1)
All Wireless Transmitters must be installed within 30 ft (10 m) of the PowPakTM Relay Module.
30 ft (10 m)
Maximum
40 ft (12 m)
30 ft
(10
m)
PowPak™ Relay Module
InstallincenterofroomtomaximizeRFcoverage.
Pico® Wireless Transmitter
Half-inchNPTTradeSize
Radio Powr Savr™ Occupancy Sensor
® SPECIF ICAT ION SUBMITTAL Page
Job Name:
Job Number:
Model Numbers:
PowPak™ Relay Module Energi TriPak™ Series Wireless Lighting Control
369-549b 6 01.23.12
Default Operation
Transmitting Device Transmitted Command Load Relay Default Action CCO Default ActionPico® On Close No Action
Off Open No ActionRaise No Action No ActionLower No Action No ActionPreset Close No Action
Radio Powr Savr™ OccupancySensor
Occupied Close NO=Close,NC=OpenUnoccupied Open NO=Open,NC=Close
Radio Powr Savr™Vacancy Sensor
Occupied No Action NO=Close,NC=OpenUnoccupied Open NO=Open,NC=Close
Radio Powr Savr™ Daylight Sensor
Ambient Light Below Target Level
Close No Action
Ambient Light Above Target Level
Open No Action