powerpoint presentation€¦ · overview of alhambra there are 42 circuits that serve alhambra 1...

31
Circuit Reliability Review Alhambra 2020

Upload: others

Post on 14-Aug-2020

15 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

Circuit Reliability Review

Alhambra

2020

Page 2: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

2

• Southern California Edison (SCE) is an Edison International company

• One of the nation’s largest electric utilities

• More than 130 years of history

• Headquartered in Rosemead, California

• Regulated by the California Public Utilities Commission (CPUC) and the Federal Energy Regulatory Commission (FERC)

• 50,000 square miles of SCE service area across Central, Coastal, and Southern California

• 15 million residents in service territory

• 5 million customer accounts in 445 cities and communities

Who We Are

Page 3: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

Our Grid

To deliver power safely, reliably and affordably, we monitor and maintain a vast electricity system.

730,000 Transformers

119,000 Miles of Transmission and Distribution Lines

4,600 Circuits

1.5 Million Poles

50,000 Square Miles

3

Page 4: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

Strengthening and Modernizing the Grid

• Infrastructure reliability – updating underground

cables, poles, switches, and transformers

• Wildfire mitigation – hardening infrastructure,

bolstering situational awareness capabilities, and

enhancing operational practices

• Transmission – connecting renewables, installing

new substations, and updating lines

• Grid readiness – updating the grid for impacts

from new technologies

• Long-term energy policy – supporting energy

storage, electric vehicles, and renewables

SCE plans to spend more than $5B each

year to maintain, improve, and harden

its infrastructure.

SCE’s investments support safe, reliable, affordable, and clean energy for our customers

2019 Capital Investments

179 miles of underground cable replaced

502 miles of overhead conductor replaced for public safety

16.4k distribution poles replaced

4.3k transmission poles replaced

71 underground structure replacements

4

Page 5: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

PATHWAY 2045SCE’S vision to help California achieve a carbon neutral future

Carbon neutrality is achieved through deep decarbonization of

electricity, transportation and building electrification,

and the use of low-carbon fuels

Meeting California’s Climate Change Goals

5

Page 6: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

• SCE filed its second Wildfire

Mitigation Plan in February 2020

• It builds on the progress made

in 2019 to reduce the risk of fire

ignitions caused by utility

infrastructure

• SCE crews will continue to work

to install hi-tech wildfire

mitigation tools and

technologies to make

communities safer, more

resilient, and to help reduce the

number of Public Safety Power

Shutoffs (PSPS)

Addressing Wildfire Risk

6

Page 7: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

• De-energizing power lines to prevent ignitions

• Used during elevated fire conditions

• Primarily impacts circuits in high fire risk areas

• Use of multiple methods to notify people in affected areas before, during and after a de-energization event

Public Safety Power Shutoffs (PSPS)

7

4-7 DAYS AHEAD

3 DAYSAHEAD

2 DAYSAHEAD

1 DAY AHEAD POWER SHUTOFF

POWER RESTORATION

PLANNING AND MONITORING OUTAGE

*Erratic or sudden onset of conditions may impact our ability to provide advanced notice to customers.

Forecast Weather & Fire

Conditions

SCE Incident Management Team on Alert

County Operational Areas

informed of potential activation

SCE Incident Management

Team Activated

1st Notification PSPS Possible sent

to agencies and customers

2nd Notification PSPS

Possible

3rd Notification Power Shutoff

4th Notification Power Restored After Inspection

Page 8: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

Reliability Overview

8

Page 9: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

What is Reliability?

• In simplest terms:

Having dependable electricity when you need it.

• Outages:

• Maintenance outages (aka planned outages)

• Repair outages (aka unplanned outages)

• Sustained Outage = An outage lasting > 5 minutes

• Momentary Outage = An outage lasting ≤ 5 minutes

9

Major Event Day (MED) : A day in which the daily system SAIDI exceeds a threshold value. For the purposes of calculating daily system SAIDI, any interruption that spans multiple calendar days is accrued to the day on which the interruption began. Statistically, days having a daily system SAIDI greater than a threshold value are days on which the energy delivery system experienced stresses beyond that normally expected (such as severe weather).

Public Safety Power Shutoff (PSPS) : An operational protocol that SCE implements under extreme weather conditions in order to minimize the threat of wildfires and keep communities safe from potentially dangerous situations. These types of sustained outages are temporary and usually involve situations where high fire areas are experiencing adverse weather or public safety is at risk.

Page 10: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

How Do We Measure Reliability?

SAIDI SAIFI MAIFI CAIDI

10

Page 11: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CityList1Communities in the MONTEBELLO District

EAST LOS ANGELES

EL MONTE

LOS ANGELES

MONTEBELLO

MONTEREY PARK

NORTH EL MONTE

ALHAMBRA

PICO RIVERA

ROSEMEAD

SOUTH EL MONTE

SOUTH SAN GABRIEL

11

Page 12: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

*”Exclusions” are days which utilities are allowed to remove from their metrics because the outages on those days were caused by a severe acts of nature.**In the columns showing “Rank,” lower numbers indicate poorer performance.

12

Page 13: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitList1Overview of AlhambraThere are 42 circuits that serve Alhambra 1

Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type Customers

ALMANSOR(16KV) 2,080 PEDESTRIAN(4.16KV) 1,106 - -

ASTEROID(16KV) 4,505 ROANOKE(4.16KV) 378 - -

BILTON(16KV) 3,254 SARAH(4.16KV) 715 - -

BRAUN(16KV) 1,365 SHORB(4.16KV) 996 - -

BRUNNER(4.16KV) 835 ST. CHARLES(16KV) 1,280 - -

CHUCKER(4.16KV) 863 STORY(4.16KV) 588 - -

COMMONWEALTH(4.16KV) 983 TAKNING(16KV) 3,152 - -

CORDOVA(4.16KV) 222 TEST(16KV) 4,125 - -

CRESTA(16KV) 3,090 TRI CITY(16KV) 2,831 - -

DEERFIELD(16KV) 2,745 TRIUMPH(16KV) 1,571 - -

DOLGEVILLE(4.16KV) 310 WILMAR(4.16KV) 942 - -

ELGIN(4.16KV) 380 WOODWARD(4.16KV) 409 - -

FLORAL(16KV) 2,079 - - -

GERONA(16KV) 3,070 - - -

GLENDON(4.16KV) 691 - - -

GRAVES(4.16KV) 316 - - -

GUEST(4.16KV) 695 - - -

HAMPTON(4.16KV) 487 - - -

HELLMAN(4.16KV) 628 - - -

HIDALGO(4.16KV) 394 - - -

HONOR(16KV) 2,115 - - -

HOOVER(4.16KV) 261 - - -

KAY(16KV) 2,248 - - -

MARENGO(4.16KV) 187 - - -

MARGUERITA(16KV) 1,559 - - -

MAYFAIR(4.16KV) 922 - - -

MERCER(16KV) 3,859 - - -

MIDWICK(4.16KV) 736 - - -

PALJAY(16KV) 1,941 - - -

PAT(16KV) 2,896 - - -

Grand Total 63,809

13

Page 14: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

BarChart

SCE SYSTEMWIDE

**Data is as of 02/14/2020, data

can be slightly different due to

outage data validation process

Alhambra

Reliability History of Circuits Serving Alhambra (No Exclusions)

**“Exclusions” are days which

utilities are allowed to

remove from their metrics

because the outages on

those days were caused by

acts of nature.

150.3

111.5

152.2

117.0

134.5 139.7 136.8

178.0

0.0

50.0

100.0

150.0

200.0

2016 2017 2018 2019

SAIDI

(average

minutes of

sustained

interruptions)

1.7

1.0 1.0

1.31.1

1.2

0.91.0

0.0

0.5

1.0

1.5

2.0

SAIFI

(average

frequency of

sustained

interruptions)

2.42.2

2.1

1.51.61.8

1.4 1.4

0.0

0.5

1.0

1.5

2.0

2.5

3.0

MAIFI

(average

frequency of

momentary

interruptions)

14

Page 15: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

SAIDIChart

SAIDI = the cumulative amount of time the average customer is interrupted by “sustained” outages each year.

Causes of Repair Outages in Alhambra

2019

3rd Party

19.1%

Equipment Failure

45.8%

Operation

3.8%

Other

5.7%

Vegetation /Animal

3.5%

Weather /Fire

/Earthquake

22.0%

PSPS

0.0%

Contributions to SAIDI by Outage Cause

3rd Party

Equipment Failure

Operation

Other

Vegetation /Animal

Weather /Fire /Earthquake

PSPS

Equipment Failure

e.g., in-service failure of transformer, switch, or conductors

Vegetation/Animale.g., tree branch, rodent, or bird

causing a short circuit between conductors

Othere.g., patrolled but no cause found,

PSPS Operations

e.g., urgent maintenance w/o 3-daynotice

3rd Party e.g., balloon, car hit pole, dig-in

PSPS

e.g., Public Safety Power Shutoff

15

Page 16: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

SAIFIChart

SAIFI = the number of times the average customer is interrupted by “sustained” outages each year

Causes of Repair Outages in Alhambra

2019

3rd Party

12.8%

Equipment Failure

47.8%

Operation

2.6%

Other

8.3%

Vegetation /Animal

2.9%

Weather /Fire

/Earthquake

25.6%

PSPS

0.0%

Contributions to SAIFI by Outage Cause

3rd Party

Equipment Failure

Operation

Other

Vegetation /Animal

Weather /Fire /Earthquake

PSPS

Equipment Failure

e.g., in-service failure of transformer, switch, or conductors

Vegetation/Animale.g., tree branch, rodent, or bird

causing a short circuit between conductors

Othere.g., patrolled but no cause found

Operationse.g., urgent maintenance w/o 3-day

notice 3rd Party

e.g., balloon, car hit pole, dig-in

PSPS

e.g., Public Safety Power Shutoff

16

Page 17: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

17

Page 18: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

18

Page 19: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

Back-up Slides

Reliability Histories of Circuits Serving Alhambra

Updated through Dec 2019

19

Page 20: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CitySummary

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

150.3 1.7 2.4 111.5 1.0 2.2 152.2 1.0 2.1 44.9 0.4 0.4 6.5 0.1 0.3 14.7 0.2 0.4 50.9 0.5 0.4 117.0 1.3 1.5

3rd Party 19% 16% 11% 22% 19% 15% 9% 21% 9% 4% 4% 4% 2% 1% 8% 7% 3% - 38% 29% 16% 19% 13% 7%

Equipment Failure 55% 56% 29% 38% 39% 12% 67% 39% 24% 32% 29% 11% 67% 67% 5% 75% 78% 12% 47% 47% 46% 46% 48% 20%

Operation 6% 9% 4% 6% 12% 3% 6% 8% 0% 5% 3% - 8% 10% 25% 2% 1% - 3% 1% - 4% 3% 5%

Other 10% 8% 31% 7% 10% 32% 11% 16% 19% 4% 2% 48% 4% 1% 50% 13% 16% 44% 5% 13% 6% 6% 8% 36%

Vegetation/Animal 5% 7% 20% 4% 5% 30% 4% 4% 34% 2% 1% - 19% 21% 12% 1% 0% 27% 4% 1% 32% 3% 3% 18%

Weather/Fire/Earthquake 5% 4% 5% 22% 16% 9% 4% 11% 14% 52% 61% 37% - - - 3% 2% 16% 4% 10% - 22% 26% 14%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

SCE SYSTEMWIDE 134.5 1.1 1.6 139.7 1.2 1.8 136.8 0.9 1.4 28.1 0.3 0.4 18.9 0.2 0.4 31.8 0.2 0.3 99.3 0.3 0.3 178.0 1.0 1.4

2nd Qtr 2019 3rd Qtr 2019

42 Circuits Serving Alhambra -- Total Customers:

63,809

Average Reliability of 42 Circuits Serving Alhambra

4th Qtr 2019 20192016 2017 2018 1st Qtr 2019

Notes:

No outages are excluded from the metrics.

Outage Causes: Other: e.g., patrolled but no cause could be foundOperations: e.g., urgent maintenance w/o 3-day notice to customers3rd Party: e.g., balloons, car hit pole, dig-inVegetation/Animal: e.g., tree branch, rodent, or bird causing short circuit across conductorsPSPS: e.g., Public Safety Power Shutoff

SAIDI (minutes) = the cumulative amount of time the average customer is interrupted by “sustained” (longer than 5 minutes) outages.

SAIFI (interruptions) = the number of times the average customer is interrupted by “sustained” outages.

MAIFI (interruptions) = the number of times the average customer is interrupted by “momentary " (lasting 5 minutes or less) outages.

20

Page 21: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory1

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

ALMANSOR(16KV) - Customers: 2,080 190.1 2.6 1.6 228.1 1.8 0.3 2.5 0.0 - 19.4 0.1 - 84.7 1.3 0.3 0.8 0.0 - - - - 105.0 1.4 0.3

3rd Party 6% 0% 27% 31% 48% 49% - - - - - - - - - - - - - - - - - -

Equipment Failure 85% 96% 73% 61% 49% 51% - - - - - - 93% 99% 100% - - - - - - 75% 93% 100%

Operation 0% 1% - 7% 2% - 100% 100% - - - - - - - 100% 100% - - - - 1% 1% -

Other 4% 1% - 1% 2% - - - - - - - 7% 1% - - - - - - - 6% 1% -

Vegetation/Animal 4% 1% - - - - - - - 100% 100% - - - - - - - - - - 19% 5% -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

ASTEROID(16KV) - Customers: 4,505 300.0 5.0 4.0 108.3 2.1 5.0 991.0 4.4 6.0 10.9 0.0 1.0 - - - 8.4 0.0 1.0 197.7 1.1 1.6 217.0 1.2 3.6

3rd Party 49% 40% - - - - 5% 23% - - - - - - - 100% 99% - 2% 1% - 5% 4% -

Equipment Failure 27% 40% 25% 90% 51% - 92% 55% 33% 7% 4% 2% - - - - - - 93% 90% 100% 85% 85% 46%

Operation 18% 20% - 3% 1% - 0% 0% - - - - - - - 0% 1% - 0% 0% - 0% 0% -

Other - - 25% - - 40% - - 33% - - - - - - - - - 4% 6% - 3% 5% -

Vegetation/Animal 0% 0% 25% 0% 0% 40% - - 17% - - - - - - - - - 1% 2% - 1% 2% -

Weather/Fire/Earthquake 6% 0% 25% 7% 48% 20% 4% 23% 16% 93% 96% 98% - - - - - 100% 0% 1% - 5% 3% 54%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

BILTON(16KV) - Customers: 3,254 400.6 3.0 2.4 45.7 1.0 4.0 147.6 3.3 2.9 7.0 0.0 1.0 1.1 0.0 - 5.0 0.0 1.0 128.7 1.0 1.0 141.8 1.0 3.0

3rd Party 37% 36% 54% 97% 100% 25% 42% 37% 66% 100% 100% - - - - - - - 100% 100% 100% 96% 99% 33%

Equipment Failure 43% 37% 46% 3% 0% 25% 21% 1% - - - - - - - 100% 100% - - - - 4% 1% -

Operation 1% 0% - - - 25% 29% 32% - - - - - - - - - - - - - - - -

Other 2% 1% - - - 25% 8% 30% 34% - - 100% 100% 100% - - - 100% - - - 1% 0% 67%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake 17% 26% - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

BRAUN(16KV) - Customers: 1,365 213.5 3.0 2.0 537.5 0.6 2.8 0.4 0.0 - 101.4 1.1 - 0.4 0.0 1.0 - - - 9.5 0.0 - 111.3 1.1 1.0

3rd Party - - - - - - - - - - - - - - 100% - - - - - - - - 100%

Equipment Failure 15% 36% 50% 16% 18% 64% - - - 100% 100% - 100% 100% - - - - - - - 91% 98% -

Operation - - - 6% 30% - 100% 100% - - - - - - - - - - 100% 100% - 9% 2% -

Other 85% 64% 50% - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - 0% 1% 36% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 78% 52% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 1 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

21

Page 22: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory2

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

BRUNNER(4.16KV) - Customers: 835 21.9 1.0 - 45.5 0.1 1.0 - - - - - - 1.4 0.0 - - - - 12.7 0.1 - 14.1 0.1 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 91% 97% - 70% 35% - - - - - - - - - - - - - 77% 78% - 69% 57% -

Operation 9% 3% - 30% 65% 100% - - - - - - 100% 100% - - - - 23% 22% - 31% 43% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

CHUCKER(4.16KV) - Customers: 863 96.6 0.6 1.5 141.8 2.0 3.1 1.1 0.0 4.0 14.1 0.1 - - - - - - - - - - 14.1 0.1 -

3rd Party 98% 79% 94% - - 32% - - - - - - - - - - - - - - - - - -

Equipment Failure 1% 16% 6% 66% 51% 3% 100% 100% 75% 100% 100% - - - - - - - - - - 100% 100% -

Operation 2% 5% - 34% 49% - - - - - - - - - - - - - - - - - - -

Other - - - - - 65% - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - 25% - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

COMMONWEALTH(4.16KV) - Customers: 983 116.4 2.2 1.0 15.4 0.0 5.0 - - - 0.7 0.0 1.0 - - - - - - - - - 0.7 0.0 1.0

3rd Party 4% 3% - - - 20% - - - - - 100% - - - - - - - - - - - 100%

Equipment Failure - - - 100% 100% - - - - - - - - - - - - - - - - - - -

Operation 0% 3% - - - - - - - - - - - - - - - - - - - - - -

Other 96% 94% 100% - - 60% - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - 20% - - - 100% 100% - - - - - - - - - - 100% 100% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

CORDOVA(4.16KV) - Customers: 222 526.2 2.3 1.0 67.9 0.2 - 336.3 2.0 - - - - 0.7 0.1 1.1 3.7 0.0 - 5.6 0.0 - 10.0 0.1 1.1

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 26% 86% 100% - - - - - - - - - - - - - - - 100% 100% - 56% 16% -

Operation 74% 14% - 100% 100% - - - - - - - 100% 100% 8% 100% 100% - - - - 44% 84% 8%

Other - - - - - - - - - - - - - - 92% - - - - - - - - 92%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - 100% 100% - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

2019

Reliability Histories for Individual Circuits Serving Alhambra - 2 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019

22

Page 23: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory3

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

CRESTA(16KV) - Customers: 3,090 28.8 1.1 2.2 90.2 0.2 0.8 10.3 0.0 1.0 17.3 0.0 - - - - 2.6 0.0 - - - - 19.9 0.0 -

3rd Party - - - 8% 28% - - - - - - - - - - - - - - - - - - -

Equipment Failure 99% 99% 49% 17% 7% - 84% 35% - 100% 100% - - - - 100% 100% - - - - 100% 100% -

Operation 1% 1% 51% - - - 3% 22% - - - - - - - - - - - - - - - -

Other - - - 0% 0% - 13% 43% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - 75% 65% 100% - - 100% - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

DEERFIELD(16KV) - Customers: 2,745 107.2 1.6 5.4 46.3 0.0 2.0 92.2 0.1 3.0 119.5 0.6 0.4 32.5 1.0 - - - - 4.0 0.0 1.0 156.0 1.6 1.4

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 76% 37% 26% 3% 7% 50% 96% 88% - 100% 100% 100% 96% 98% - - - - 95% 97% - 99% 99% 28%

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - 37% - - - - - 33% - - - - - - - - - - - - - - -

Vegetation/Animal 24% 63% 18% - - 50% - - - - - - 4% 2% - - - - 5% 3% 100% 1% 1% 72%

Weather/Fire/Earthquake - - 18% 97% 93% - 4% 12% 67% - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

DOLGEVILLE(4.16KV) - Customers: 310 34.5 1.7 - - - 1.0 0.3 0.0 - - - - - - - - - - 2.8 0.0 - 2.8 0.0 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - - - - - - - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - 100% 100% - 100% 100% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - 100% 100% - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - 100% - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

ELGIN(4.16KV) - Customers: 380 137.8 2.0 1.0 11.3 0.0 1.0 - - - - - - - - - 6.4 0.0 - - - - 6.4 0.0 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% 100% - - - - - - - - - - - - - - - - - - - - -

Operation - - - 100% 100% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - 100% - - - - - - - - - 100% 100% - - - - 100% 100% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 3 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

23

Page 24: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory4

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

FLORAL(16KV) - Customers: 2,079 303.5 2.1 7.0 81.7 0.4 3.0 94.0 0.1 - 21.3 0.1 0.1 - - 1.0 1.1 0.0 - 55.3 0.6 - 77.8 0.7 1.1

3rd Party - - 14% - - 33% - - - - - - - - - - - - - - - - - -

Equipment Failure 46% 5% - 40% 25% - 99% 59% - - - - - - - 100% 100% - 100% 100% - 73% 89% -

Operation 5% 48% - 18% 23% - 1% 40% - - - - - - - - - - - - - - - -

Other 49% 48% 71% 43% 52% - 0% 1% - - - - - - 100% - - - - - - - - 90%

Vegetation/Animal - - 14% - - 67% - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - 100% 100% 100% - - - - - - - - - 27% 11% 10%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

GERONA(16KV) - Customers: 3,070 9.4 0.0 2.3 244.4 3.2 0.5 165.5 0.9 0.2 23.7 0.8 1.0 - - 0.8 9.0 0.1 - 3.6 0.0 - 36.3 0.9 1.8

3rd Party - - - - - - - - - - - - - - - 100% 100% - - - - 25% 7% -

Equipment Failure 100% 100% 36% 100% 100% 100% 42% 3% - - - - - - - - - - 87% 33% - 9% 0% -

Operation - - - 0% 0% - 0% 0% - - - - - - 100% - - - 13% 67% - 1% 0% 45%

Other - - 64% - - - - - - - - 100% - - - - - - - - - - - 55%

Vegetation/Animal - - - - - - 58% 97% 100% - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - 100% 100% - - - - - - - - - - 65% 93% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

GLENDON(4.16KV) - Customers: 691 29.3 0.0 1.0 73.2 1.0 2.0 0.7 0.0 4.0 59.0 1.0 - 4.7 0.1 - - - - - - - 63.8 1.1 -

3rd Party - - - - - 50% - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - - - - - - 75% - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - 100% 100% - - - - - - - 7% 13% -

Other - - 100% - - - 100% 100% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 100% 100% 50% - - 25% 100% 100% - - - - - - - - - - 93% 88% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

GRAVES(4.16KV) - Customers: 316 20.0 1.0 1.0 13.4 0.0 1.0 314.8 3.9 - - - - - - - 74.6 0.2 - - - - 74.6 0.2 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - 100% 100% - 64% 69% - - - - - - - 100% 100% - - - - 100% 100% -

Operation - - - - - - 28% 6% - - - - - - - - - - - - - - - -

Other - - 100% - - - 9% 25% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - 100% - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 4 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

24

Page 25: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory5

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

GUEST(4.16KV) - Customers: 695 15.2 0.0 2.0 9.9 0.0 3.0 51.0 0.1 - - - 1.0 2.8 0.0 - - - - 7.0 1.0 - 9.8 1.0 1.0

3rd Party - - - - - 67% - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% 50% 64% 42% - 100% 100% - - - - - - - - - - - - - - - -

Operation - - 50% 36% 58% - - - - - - - 100% 100% - - - - - - - 28% 2% -

Other - - - - - 33% - - - - - 100% - - - - - - 100% 100% - 72% 98% 100%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

HAMPTON(4.16KV) - Customers: 487 154.0 2.2 1.0 - - - 100.5 0.1 - - - - - - - - - - - - - - - -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 88% 92% 100% - - - 100% 100% - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other 12% 8% - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

HELLMAN(4.16KV) - Customers: 628 293.6 1.0 1.0 - - 1.0 519.3 1.0 5.0 20.5 0.1 - - - - - - - 342.5 1.0 - 362.9 1.1 -

3rd Party - - - - - - - - 20% - - - - - - - - - 100% 100% - 94% 95% -

Equipment Failure - - - - - - 0% 3% 60% 100% 100% - - - - - - - - - - 6% 5% -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other 100% 100% 100% - - 100% 100% 97% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - 20% - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

HIDALGO(4.16KV) - Customers: 394 172.3 2.2 1.0 574.0 1.1 - 114.5 0.8 1.2 - - - 39.7 0.0 1.0 0.7 0.1 - - - - 40.4 0.1 1.0

3rd Party - - - 95% 91% - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% 100% - - - - - - - - - 100% 100% 100% - - - - - - 98% 30% 100%

Operation - - - 1% 5% - 100% 100% 16% - - - - - - 100% 100% - - - - 2% 70% -

Other - - - - - - - - 84% - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 4% 4% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 5 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

25

Page 26: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory6

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

HONOR(16KV) - Customers: 2,115 24.1 0.0 1.0 95.3 1.2 5.0 41.4 0.3 1.0 - - 2.0 1.4 0.0 1.0 0.1 0.0 - - - - 1.5 0.0 3.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - 45% 3% - - - - - - - - - - - - - - - - - - -

Operation 95% 70% - 0% 0% - 93% 98% - - - - - - - - - - - - - - - -

Other 5% 30% 100% 44% 16% 80% - - - - - 50% - - - 100% 100% - - - - 6% 3% 33%

Vegetation/Animal - - - 10% 81% 20% - - - - - - 100% 100% 100% - - - - - - 94% 97% 34%

Weather/Fire/Earthquake - - - - - - 7% 2% 100% - - 50% - - - - - - - - - - - 33%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

HOOVER(4.16KV) - Customers: 261 104.5 1.2 0.8 21.8 0.0 1.0 725.6 3.4 - - - - - - - 0.4 0.0 - - - - 0.4 0.0 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 19% 86% - 87% 75% - - - - - - - - - - 100% 100% - - - - 100% 100% -

Operation - - - 13% 25% 100% 1% 21% - - - - - - - - - - - - - - - -

Other - - - - - - 99% 79% - - - - - - - - - - - - - - - -

Vegetation/Animal 81% 14% 100% - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

KAY(16KV) - Customers: 2,248 169.3 1.1 4.0 277.4 2.0 6.1 2.5 0.1 5.0 379.1 1.6 0.7 - - - 188.2 3.1 2.0 - - - 567.3 4.6 2.7

3rd Party 0% 0% - 74% 75% 51% - - - - - - - - - - - - - - - - - -

Equipment Failure 90% 94% 50% 10% 1% - 100% 100% 40% 0% 0% - - - - 100% 100% 50% - - - 33% 66% 37%

Operation 1% 4% - 12% 23% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal 9% 2% 50% 2% 0% 33% - - 60% - - - - - - - - 50% - - - - - 37%

Weather/Fire/Earthquake - - - 3% 0% 16% - - - 100% 100% 100% - - - - - - - - - 67% 34% 25%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MARENGO(4.16KV) - Customers: 187 133.7 0.2 1.0 0.8 0.0 5.0 1.5 0.0 1.8 3.0 0.0 - - - - - - - - - - 3.0 0.0 -

3rd Party - - - - - 20% 100% 100% 100% - - - - - - - - - - - - - - -

Equipment Failure 77% 70% - - - - - - - 100% 100% - - - - - - - - - - 100% 100% -

Operation 5% 20% - 100% 100% - - - - - - - - - - - - - - - - - - -

Other - - - - - 60% - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake 18% 10% 100% - - 20% - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 6 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

26

Page 27: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory7

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

MARGUERITA(16KV) - Customers: 1,559 613.4 2.4 3.0 69.8 2.1 5.0 226.3 1.4 2.0 - - - 21.7 1.0 - - - - 181.0 0.3 2.7 202.7 1.3 2.7

3rd Party - - - - - - - - - - - - - - - - - - 100% 100% 25% 89% 25% 25%

Equipment Failure 100% 100% 33% 100% 100% 60% 64% 6% 50% - - - - - - - - - - - - - - -

Operation - - 33% - - - - - - - - - - - - - - - - - - - - -

Other - - 34% - - - 36% 94% - - - - - - - - - - - - 37% - - 37%

Vegetation/Animal - - - - - 40% - - 50% - - - 100% 100% - - - - - - 37% 11% 75% 37%

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MAYFAIR(4.16KV) - Customers: 922 1.2 0.0 1.0 21.2 0.0 - 226.1 1.2 6.0 31.2 0.1 - - - - 15.6 0.0 - - - - 46.9 0.1 -

3rd Party - - - - - - - - 33% - - - - - - - - - - - - - - -

Equipment Failure - - - 47% 16% - 7% 1% 50% 21% 40% - - - - 100% 100% - - - - 48% 57% -

Operation 100% 100% - - - - 48% 17% - 79% 60% - - - - - - - - - - 52% 43% -

Other - - 100% 53% 84% - 44% 82% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - 17% - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MERCER(16KV) - Customers: 3,859 2.2 0.0 3.0 6.0 0.0 - 103.6 1.1 4.0 64.7 1.0 - 2.1 0.0 1.0 - - - 51.6 0.1 1.0 118.3 1.1 2.0

3rd Party - - - - - - - - - - - - 95% 72% - - - - - - - 2% 2% -

Equipment Failure - - - 100% 100% - 78% 93% - 96% 97% - - - - - - - - - - 52% 88% -

Operation 24% 67% - - - - 3% 1% - - - - 5% 28% - - - - 2% 3% - 1% 1% -

Other - - 35% - - - - - 25% - - - - - 100% - - - 42% 35% - 18% 3% 50%

Vegetation/Animal 76% 33% 65% - - - 19% 5% 75% 4% 3% - - - - - - - 56% 62% 100% 27% 7% 50%

Weather/Fire/Earthquake - - - - - - - - - 0% 0% - - - - - - - - - - 0% 0% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

MIDWICK(4.16KV) - Customers: 736 24.6 1.0 1.0 33.6 1.0 - 120.7 2.1 - - - - 1.2 0.0 - - - - 7.0 1.0 - 8.1 1.0 -

3rd Party - - - - - - 37% 48% - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - 12% 2% - - - - - - - - - - - - - - - -

Operation - - - 64% 4% - - - - - - - 100% 100% - - - - - - - 14% 1% -

Other 100% 100% 100% 36% 96% - 51% 49% - - - - - - - - - - 100% 100% - 86% 99% -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 7 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

27

Page 28: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory8

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

PALJAY(16KV) - Customers: 1,941 - - - 10.3 0.0 1.0 107.2 1.3 2.0 67.4 0.3 - - - - 1.2 0.0 2.0 147.5 1.0 1.0 216.1 1.3 3.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - 16% 14% - 100% 100% 51% - - - - - - - - - 100% 100% 100% 68% 76% 33%

Operation - - - 84% 86% - - - - 96% 98% - - - - 100% 100% - - - - 30% 24% -

Other - - - - - 100% - - 49% 4% 2% - - - - - - 50% - - - 1% 0% 33%

Vegetation/Animal - - - - - - - - - - - - - - - - - 50% - - - - - 33%

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

PAT(16KV) - Customers: 2,896 112.2 1.2 1.0 290.0 3.2 1.6 11.8 0.1 - - - - 3.7 0.2 1.7 40.7 0.7 0.3 63.2 2.1 - 107.5 3.0 2.0

3rd Party - - - 64% 32% - - - - - - - - - - - - - - - - - - -

Equipment Failure 88% 95% - 15% 22% 18% 95% 96% - - - - - - - - - - 32% 51% - 19% 35% -

Operation 2% 1% - 0% 0% - 5% 4% - - - - 100% 100% 41% - - - 2% 0% - 4% 7% 35%

Other 10% 4% 100% 20% 44% 82% - - - - - - - - 59% 100% 100% 100% - - - 38% 24% 65%

Vegetation/Animal 0% 0% - 0% 1% - - - - - - - - - - 0% 0% - - - - 0% 0% -

Weather/Fire/Earthquake - - - 1% 0% - - - - - - - - - - - - - 66% 49% - 39% 34% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

PEDESTRIAN(4.16KV) - Customers: 1,106 410.3 4.0 4.0 24.9 2.0 4.0 126.7 2.0 2.0 266.4 3.0 1.0 - - - 194.4 3.0 2.0 - - - 460.8 6.0 3.0

3rd Party - - 25% - - 50% 100% 100% - 35% 33% - - - - - - - - - - 20% 17% -

Equipment Failure 75% 75% 25% - - - - - 51% - - - - - - 100% 100% 50% - - - 42% 50% 33%

Operation 1% 1% - 100% 100% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - 50% - - - - - 33%

Vegetation/Animal - - 50% - - 25% - - 49% - - - - - - - - - - - - - - -

Weather/Fire/Earthquake 23% 25% - - - 25% - - - 65% 67% 100% - - - - - - - - - 38% 33% 33%

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

ROANOKE(4.16KV) - Customers: 378 145.0 2.1 2.0 145.5 1.0 - 175.5 1.6 - - - - - - - 5.5 0.1 - - - 1.0 5.5 0.1 1.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 99% 51% - - - 100% 100% - - - - - - - - - - - - - - - -

Operation 0% 1% 49% - - - - - - - - - - - - 100% 100% - - - - 100% 100% -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - 100% - - 100%

Weather/Fire/Earthquake - - - 100% 100% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 8 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

28

Page 29: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory9

SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

SARAH(4.16KV) - Customers: 715 - - - 584.9 2.0 - - - 5.0 0.6 0.0 - - - - - - - - - - 0.6 0.0 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - - - 60% - - - - - - - - - - - - - - -

Operation - - - 6% 49% - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - 20% 100% 100% - - - - - - - - - - 100% 100% -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 94% 51% - - - 20% - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

SHORB(4.16KV) - Customers: 996 98.2 1.0 2.0 - - 4.0 - - - 10.0 0.0 1.0 4.2 0.0 - - - - 6.9 1.0 - 21.1 1.0 1.0

3rd Party - - 100% - - 25% - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - - - - - - - 100% 100% 100% 100% 100% - - - - - - - 67% 5% 100%

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - 75% - - - - - - - - - - - - 100% 100% - 33% 95% -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

ST. CHARLES(16KV) - Customers: 1,280 94.2 2.2 4.0 - - - 155.1 1.0 - 1.6 0.1 - - - - 2.5 0.0 - 0.3 0.0 - 4.3 0.2 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 21% 47% 50% - - - - - - 100% 100% - - - - - - - - - - 37% 87% -

Operation 60% 7% - - - - - - - - - - - - - 100% 100% - 100% 100% - 63% 13% -

Other - - - - - - 100% 100% - - - - - - - - - - - - - - - -

Vegetation/Animal 19% 46% 50% - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

STORY(4.16KV) - Customers: 588 234.9 2.0 6.0 108.4 1.2 6.0 0.0 0.0 1.0 337.3 1.9 1.0 - - - - - - - - - 337.3 1.9 1.0

3rd Party - - 17% - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% 17% - - - 100% 100% - 45% 50% 100% - - - - - - - - - 45% 50% 100%

Operation - - - 24% 13% - - - - - - - - - - - - - - - - - - -

Other - - 67% 76% 87% 67% - - 100% 55% 50% - - - - - - - - - - 55% 50% -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - 33% - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 9 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

29

Page 30: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory10SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

TAKNING(16KV) - Customers: 3,152 36.3 1.2 2.0 7.2 0.1 2.0 175.1 1.9 3.0 4.9 0.0 1.0 - - - 0.1 0.0 2.0 63.3 1.0 1.0 68.3 1.0 4.0

3rd Party 4% 0% 50% - - - 44% 46% 33% - - - - - - - - - - - - - - -

Equipment Failure 93% 99% 50% 17% 3% - 55% 54% - 100% 100% 1% - - - 100% 100% - 98% 99% 100% 98% 99% 25%

Operation 3% 0% - 64% 71% - 0% 0% - - - - - - - - - - - - - - - -

Other - - - - - - 1% 0% - - - 99% - - - - - 50% 2% 1% - 2% 1% 50%

Vegetation/Animal - - - - - 100% - - 67% - - - - - - - - 50% 0% 0% - 0% 0% 25%

Weather/Fire/Earthquake - - - 19% 26% - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

TEST(16KV) - Customers: 4,125 179.7 1.7 3.5 270.7 2.4 2.4 49.5 0.5 1.4 66.6 2.0 - 5.0 0.0 - 6.2 0.1 - 93.5 1.1 - 171.3 3.2 -

3rd Party 83% 60% - 3% 2% - - - - - - - - - - - - - 78% 95% - 42% 32% -

Equipment Failure 12% 38% 28% 49% 30% 17% 46% 5% - 3% 1% - 30% 54% - - - - 1% 0% - 3% 1% -

Operation 5% 3% - 7% 24% - - - - 3% 2% - 70% 46% - 16% 21% - 14% 3% - 12% 3% -

Other - - 28% 6% 0% 41% - - - 4% 0% - - - - - - - 3% 1% - 3% 0% -

Vegetation/Animal - - 44% 2% 1% 41% 2% 1% 75% - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - 33% 44% - 51% 94% 25% 89% 97% - - - - 84% 79% - 5% 1% - 40% 63% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

TRI CITY(16KV) - Customers: 2,831 202.2 4.0 2.0 31.2 0.2 1.4 183.1 1.4 4.6 0.1 0.0 - 14.3 0.0 - 6.6 0.0 - 3.1 0.0 - 24.1 0.1 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 53% 51% 50% 23% 3% - 52% 74% 23% 59% 82% - - - - - - - - - - 0% 3% -

Operation 4% 24% - 0% 0% - 40% 12% 2% - - - - - - - - - 47% 41% - 6% 9% -

Other - - 50% 6% 11% 26% - - 21% - - - - - - 47% 77% - 53% 59% - 19% 38% -

Vegetation/Animal 43% 25% - - - 74% - - 43% - - - 100% 100% - 53% 23% - - - - 74% 49% -

Weather/Fire/Earthquake - - - 70% 85% - 8% 14% 11% 41% 18% - - - - - - - - - - 0% 1% -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

TRIUMPH(16KV) - Customers: 1,571 68.5 1.3 0.5 11.9 0.0 - 10.3 0.0 - - - - - - - - - - - - - - - -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 0% 0% 100% 100% 100% - 100% 100% - - - - - - - - - - - - - - - -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - - - - - - - - - - - - - - - - - - -

Vegetation/Animal 100% 100% - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 10 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

30

Page 31: PowerPoint Presentation€¦ · Overview of Alhambra There are 42 circuits that serve Alhambra 1 Circuit Type Customers Circuit Type Customers Circuit Type Customers Circuit Type

CircuitHistory11SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI SAIDI SAIFI MAIFI

WILMAR(4.16KV) - Customers: 942 2.6 0.0 - - - 1.0 - - - - - - - - - - - 2.0 7.0 1.0 - 7.0 1.0 2.0

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure - - - - - - - - - - - - - - - - - - - - - - - -

Operation 100% 100% - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - 100% - - - - - - - - - - - 100% 100% 100% - 100% 100% 100%

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

WOODWARD(4.16KV) - Customers: 409 19.6 1.0 - - - - 11.5 1.0 - - - - - - - 8.5 0.2 - - - - 8.5 0.2 -

3rd Party - - - - - - - - - - - - - - - - - - - - - - - -

Equipment Failure 100% 100% - - - - - - - - - - - - - 100% 100% - - - - 100% 100% -

Operation - - - - - - - - - - - - - - - - - - - - - - - -

Other - - - - - - 100% 100% - - - - - - - - - - - - - - - -

Vegetation/Animal - - - - - - - - - - - - - - - - - - - - - - - -

Weather/Fire/Earthquake - - - - - - - - - - - - - - - - - - - - - - - -

PSPS - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

- - - - - - - - - - - - - - - - - - - - - - - - -

Reliability Histories for Individual Circuits Serving Alhambra - 11 of 11

2016 2017 2018 1st Qtr 2019 2nd Qtr 2019 3rd Qtr 2019 4th Qtr 2019 2019

31