Air Circuit Breaker
IS: 8828
We touch your everyday!electricity
ACB-B Type
7/31/2019 Air Circuit Breakers - B Type
http://slidepdf.com/reader/full/air-circuit-breakers-b-type 2/4
Technical Overview
High Breaking & Short Time Withstand Capacity
Full utilization of electromagnetic repulsive force
Even though it is sound and compact in design, it provides high
breaking capacity and short - time withstand current capacity by fully
utilizing electromagnetic repulsive force.
The contact spring normally provides an adequate contact
pressure.
A large current flow causes an electromagnetic repulsive force
between the contact lead halves.
This repulsive force works in a direction to turn the moving contact
clockwise about the contact shaft, giving it more contact pressure.
Hence this unique design ensures a high short-time withstand
current capacity.
When interrupting a large current, the electromagnetic repulsive force
works in a direction to separate the moving contact from the
stationary contact.
A separating force resulting from the electromagnetic repulsive force
adds to that by the trip spring, assisting a high-speed interruption.
This is why our design provides a high breaking capacity
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
n
400~1600A in single frame size
Light & compact
High breaking capacity - 45/50kA
Reliable system protection thru:
a) Thermal Magnetic (TOMCR)
b) Microprocessor Release (mIT-100)
Fast acting mechanism (total breaking time less than 30ms including arcing time of less than 10ms) minimizes installation stress
under fault condition
Easy termination - horizontal Bus bar connection.
High mechanical & electrical life.
High dielectric strength due to use of class 'B' and 'F' insulating material ensures reliable performance in tropical conditions
Comply with utilization category B & pollution degree 3 group 1 of IEC60947-Part1
Tested for seismic conditions .
Wide range of accessories offered-Shunt trip, UVT, Auxiliary Switch, Trip indication switches to meet market specifications.
Salient Features
Amperes Frame (based on IEC / IS) 400 630 800 1000 1250 1600
Type (3 Poles) AH-4B AH-6B AH-8B AH-10B AH-12B AH-16B* *
Insulation Voltage Ui (V) AC 1000 1000 1000 1000 1000 1000
Impulse Voltage Uimp (V) AC (Peak) 8 8 8 8 8 8
Dielectric strength (for a minute) kV 3.5 3.5 3.5 3.5 3.5 3.5
Rated Making Capacity Icm (Peak) kA 105 105 105 105 105 105
Rated Breaking Capacity Icu=Ics (RMS) kA 415V AC 50 50 50 50 50 50
Short time withstand current Icw kA for 1 sec. RMS 50 50 50 50 50 50
Total breaking time/closing time (m.sec.) 30/40 30/40 30/40 30/40 30/40 30/40
Weight (kg) 40 40 40 42 42 44
Overall Dimension (H x W x D) (mm) 483 x 332 x 323
* 630A & 800A ACBs are also available in 45kA breaking capacity at 415V AC operating voltage & 690V insulation voltage.
Technical Specifications
Contact Pressure by Repulsive Force
Contact Pressure by Contact Spring
Mechanical Retaining Force
Contact Spring
Current
Contact Lead
Stationary Contact
Moving Contact
Contact Shaft
Current
Electromagnetic
Repulsive Force
Arc
Trip Spring
Separating Force Resulting from
Repulsive Force
Separating Force by Trip Spring
Contact Holder Shaft
Stationary Contact
Moving Contact
Current
Electromagnetic
Repulsive Force
7/31/2019 Air Circuit Breakers - B Type
http://slidepdf.com/reader/full/air-circuit-breakers-b-type 3/4
A direct acting electromagnetic instantaneous trip
device with fixed current setting for Short Circuit
Protection.
CT actuated thermal Overload relay offers
Protection along with Shunt trip. Current setting are
60-100% or 80-120%.
O/L
Microprocessor Release
Salient Features
IT-100
supply for its basic function.
Error free and user friendly setting of current/time.
Provides highest degree of system protection coordination.
Self powered by built in current transformer.
No mal-operation due to external disturbances.
Built in operation check function.
Visual fault discrimination by LEDs.
Three phase and earth fault in one single compact unit.
Self monitoring of trip unit with blinking indication.
Function Blocking facility provided.
is a true RMS sensing overcurrent trip device, requires no external
n
n
n
n
n
n
n
n
n
Over Load Current (LTD)
LTD Current Setting range: 0.5, 0.55 ...1.15 In (in steps of 0.05)
LTD Time Setting range: 2.5, 5 ....... to 35 sec. (in steps of 2.5 sec.)
Short Circuit Current (STD)
STD Current Setting range: 4, 5 ... 10 In (in steps of 1)
STD Time Setting Range: 50, 100, ... 550 ms. (in steps of 50 ms)
Instantaneous Current (INS)
Current (INS) Setting Ranges: 4, 5, ... 11In (in steps of 1)
Ground Fault (GFT)
GFT Current Setting Range: 15, 20, ... 50% In (in steps of 5%)
GFT Time Setting Range: 50, 100, ... 550 ms (in steps of 50ms)
Function Blocking In normal running operation of unit, any of the four function
can be blocked by turning the DIP switches to ON position
Thermal Magnetic Release
MAGNETIC INST. S/C TRIP
T I M E
40ms.
30ms.
Rated Current
% Rated Current of Base Current
Note: Applicable where rated current of
over current trip devices is not less than 250A
Current setting of non-adjustable magnetic instantaneous trip
Applicable Breaker AH-6B
AH-8B
AH-10B
AH-16B
AH-12B
Tripping Characteristics
Accuracy of Time & Current Setting ±20%Calibrated at40°C:
Balanced (Cold Start)
------ Balanced (Hot Start)
6 0
7 0
8 0
1 0 0
1 2 5
1 5 0
2 0 0
2 5 0
3 0 0
4 0 0
5 0 0
6 0 0
1 2 0
2
3
5.0
4.0
3.0
2.0
6.0
8.0
10
20
30
40
50
1
2
3
4
5
6
8
2050
1
4
h o u r
m i n u t e
s e c o n d
8 0 %
1 0 0 %
1 2 0 %
Long Time Delay Trip
Current setting range
O p e r a t i n g
T i m e
1 . 0
5
1 . 3
Protection Release
Tripping Characteristics
7/31/2019 Air Circuit Breakers - B Type
http://slidepdf.com/reader/full/air-circuit-breakers-b-type 4/4
+91-11- , +91-11-2684 8241, 2684 73423088 7520-29
222, Okhla Industrial Estate, New Delhi - 110 020
+91-11-4161 3503, 3088 7520-29, +91-11-2683 8291, 2684 7342
C&S Electric Ltd.
We touch your electricity everyday!
www.cselectric.co.in
Panel Cutout
Air Circuit Breakers - B Series
151.5
166166
151.5
332
1515
Front View
Rear ViewSide View
Overall Dimensions (AH-4B~AH-16B)
1 0 2 S G R / B / 0 6
2 0 1 1