powercube type pb - arianbc.net

36
PowerCube type PB Pre-assembled modules and enclosures for constructing medium voltage switchgear

Upload: others

Post on 29-May-2022

7 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PowerCube type PB - arianbc.net

PowerCube type PBPre-assembled modules and enclosures forconstructing medium voltage switchgear

Page 2: PowerCube type PB - arianbc.net
Page 3: PowerCube type PB - arianbc.net

1

1

2

3

4

2

6

12

22

524

630

GENERAL CHARACTERISTICS

MAIN COMPONENTS

TYPES AVAILABLE AND APPARATUS

OVERALL DIMENSIONS AND WEIGHTS

COMPLETION OF THE SWITCHGEAR

ELECTRIC CIRCUIT DIAGRAM

Page 4: PowerCube type PB - arianbc.net

2

1 GENERAL CHARACTERISTICS

GeneralThe PowerCube modules allow construction of metal-cladmedium voltage air-insulated switchgear with the same ratedcurrents as those of the enclosure.

In fact, the rated currents of the enclosures refer to versionstested in ABB UniSafe type switchgear.

In particular, the 4000 A PB3 enclosure means it is possible toconstruct switchgear with the same rated current as long as asuitable fan is applied in the back of the switchgear (for furtherinformation, please ask ABB).

The PB type PowerCubes are available in two different versions:PB/M and PB/E.

PB/M: complete module including the cable access compart-ment which can also be prepared to house the withdrawable VTcompartment.

PB/E: compounded enclosure with the cable access compart-ment and therefore without the possibility of housing the with-drawable VT compartment, but, thanks to its smaller overalldimensions, more flexible and suited to developing double-levelswitchgear.

The PowerCube modules are pre-assembled and factory-testedand comply with IEC 62271-200, CEI 17-1, IEC 60694 and CEI17-6 Standards.

PowerCube type PB/M Module.

The following apparatus can be installed in thePowerCube modules:• VD4, VM1, eVM1 and Vmax series vacuum

circuit-breakers• HD4 series gas circuit-breakers• V-Contact series vacuum contactors• service trucks.All the operations of the apparatus are carried outfrom the front of the module/enclosure.

Degrees of protection The degrees of protection of the PowerCubemodules comply with the IEC 60529 Standards.

The following standard degrees of protection areguaranteed on the front:

– external housing: IP4X– inside the units: IP2X.

PowerCube type PB/M enclosure.

They are available with the following characteristics:

Rated voltage (kV) ... 17.5 24

Rated current (A) ... 4000 ... 2500

Rated short-time main circuit ... 40 x 3s ... 31.5 x 3s withstand current (kA) ... 50 x 1s

Page 5: PowerCube type PB - arianbc.net

3

InterlocksThe PowerCube module is fitted with the interlocks needed toprevent incorrect operations which might jeopardise safety ofthe personnel in charge of running the installation, as well asthe efficiency and reliability of the apparatus.In particular, locking devices to prevent the following operationsare provided:– circuit-breaker closing in the intermediate position– racking-out of closed circuit-breaker– racking-in of closed circuit-breaker– circuit-breaker compartment door opening in the connected or

intermediate position– circuit-breaker racking-in with compartment door open.

And, if the unit is fitted with an earthing switch:– earthing switch closing with the circuit-breaker in the con-

nected or intermediate position– racking-in the circuit-breaker with the earthing switch closed– feeder compartment door opening with the earthing switch

open (only for PowerCube PB/M module)– earthing switch opening with the feeder compartment door

open (only for PowerCube PB/M module).

Note: some of the interlocks listed above are supplied on request or areonly available for some versions.

Quality SystemComplies with ISO 9001 Standards, certified by anindependent external organisation.

Test laboratoryComplies with ISO 45001 Standards, accredited by anindependent external organisation.

Environmental Management SystemComplies with ISO 14001 Standards, certified by anindependent external organisation.

Health and Safety Management SystemComplies with OHSAS 18001 Standards, certified by anindependent external organisation.

Page 6: PowerCube type PB - arianbc.net

4

1 2 3

6

B

9

8

7

A

4

5

1

A Circuit-breaker compartment1 Voltage signalling device (on request – only

for PowerCube PB/M module)2 Circuit-breaker/contactor/truck3 Metal shutters4 Lower and upper monoblocs5 Earthing switch (on request)6 Door7 Fan (only for 3600 A and 4000 A PB3 and for

2500 A PB5)

B Feeder compartment8 VT compartment (on request – only for

PowerCube PB/M module)9 Door

GENERAL CHARACTERISTICS

Page 7: PowerCube type PB - arianbc.net

5

Electrical characteristics of PowerCube modules

PowerCube Module/Enclosure PB1 PB2 PB3 PB4 PB5 PB1/R PB2/R PB3/R PB4/R PB5/R

Module width mm 600 750 1000 750 1000 600 750 1000 750 1000

Rated voltage 12 kV

17.5 kV

24 kV

Test voltage 28 kV

at industrial frequency 38 kV

50 kV

Impulse withstand 75 kV

voltage 95 kV

125 kV

Short-time 25 kA (3s)

withstand current 31.5 kA (3s) (2) (2)

40 kA (3s)

50 kA (1s)

Peak current 63 kA

79 kA

100 kA

125 kA

Rated currents 630 A

1250 A

1600 A

2000 A

2500 A (1)

3150 A

3600 A (1)

4000 A (1)

Electrical characteristics of earthing switch (on request)

(1) With forced ventilationof the circuit-breakercompartment: for 4000A, an additional fan isrequired in the back ofthe switchgear.

(2) Ask ABB - Available forPB/E enclosure; notavailable for PB/Menclosure.

PowerCube Module/Enclosure PB1 PB2 PB3 PB4 PB5 PB1/R PB2/R PB3/R PB4/R PB5/R

Module width mm 600 750 1000 750 1000 600 750 1000 750 1000

Short-time 25 kA (3s)

withstand current / 31.5 kA (3s) (2) (2) (2) (2)

Short-circuit 40 kA (1s)

making capacity 50 kA (1s)

Peak current 63 kA

79 kA

100 kA

125 kA

NOT

APPLICABLE

Page 8: PowerCube type PB - arianbc.net

6

2

HD4 series gas circuit-breaker.

VD4 series vacuum circuit-breaker.

Circuit-breakersThe PowerCube units can be fitted with HD4 series SF6withdrawable and VD4, VM1, eVM1 and eVmax series vacuumcircuit-breakers.The circuit-breakers are fitted with a truck which allows theirracking-in and out of the switchgear with the door closed.Both types have a compact and light structure which ensuresgreat sturdiness and excellent mechanical reliability.The operating mechanism and poles are fixed to the metalstructure which also acts as a support for the moving contactactuation kinematics.

HD4 series SF6 Circuit-breakersThe HD4 series of medium voltage circuit-breakers use sulphurhexafluoride gas (SF6) to extinguish the electric arc and as theinsulating medium.The breaking principle of HD4 circuit-breakers is based oncompression and self-blast techniques to obtain top perform-ances at all service current values, with gradual arc extinction,no restriking, operating overvoltages or chopped currents.These characteristics guarantee long electrical life for thecircuit-breaker and limited dynamic, dielectric and thermalstresses on the installation.The circuit-breaker poles, which make up the interruption part,are sealed for life pressure systems (IEC 62271-100 and CEI17.1 Standards) and are maintenance-free.The stored energy mechanical operating mechanism has freetrip and allows opening and closing operations independent ofthe operator’s actions.

VD4, VM1 and eVM1 series vacuum circuit-breakersThe VD4, VM1 and eVM1 circuit-breakers use vacuum as theinterruption and insulating medium.Thanks to the advanced techniques used for their construction,the vacuum circuit-breakers ensure high performances underall service conditions.The vacuum interrupters are embedded in the poles made ofepoxy resin. This construction means the interrupters areunaffected by shocks, humidity and environmental pollution.The circuit-breaker poles, making up the interruption part, aresealed for life pressure systems (IEC 62271-100 and CEI 17.1Standards) and are maintenance-free.The VD4 circuit-breakers use a mechanical type of operatingmechanism, the VM1 and eVM1 circuit-breakers use anoperating mechanism with a magnetic actuator.They are both stored energy operating mechanisms with freetrip and allow opening and closing operations independent ofthe operator’s actions.The eVM1 circuit-breakers are also fitted with an integratedmeasurement and protection system which can be configuredby means of a personal computer, directly by the customerusing some simple software.

MAIN COMPONENTS

eVM1 series vacuum circuit-breaker.

Page 9: PowerCube type PB - arianbc.net

7

V-Contact seriesvacuum contactors VSC/P and V/P.

Vmax/W series vacuum circuit-breakersVmax circuit-breakers are made up of an insulating monoblocin which three vacuum interrupters are fixed. The monoblocand the operating mechanism are fixed to a frame.The vacuum interrupters house the contacts and make up theinterruption chambers of the circuit-breaker.Vmax circuit-breakers use a mechanical stored energy operat-ing mechanism with free trip which allows opening and closingoperations independent of the operator’s actions. The mechani-cal operating mechanism is of simple concept and use and canbe personalised with a wide range of easily and rapidly in-stalled accessories.This simplicity characterised the apparatus for its reliability,duration and limited maintenance.Vmax circuit-breakers are used in power distribution for controland protection of cables, overhead lines, transformer anddistribution substations, motors, transformers, generators andcapacitor banks.The circuit-breaker vacuum interrupters, which make up theinterruption part, are sealed for life pressure systems (IEC62271-100 and CEI 17.1 Standards) and are maintenance-free.

Vmax/W series vacuum circuit-breaker.

V-Contact V/P and V-Contact VSC/P series vacuum contactorsUse of V-Contact series withdrawable contactors is foreseen in the PB1 PowerCube units up to 12 kV.The contactors are suitable for controlling alternating current users which require a high number ofoperations.They consist of a resin monobloc where the vacuum interrupters, moving equipment, operating mecha-nism, multivoltage feeder and auxiliary accessories are housed.The monobloc is also the support for installation of the fuses.Fuses according to DIN or BS Standards of different dimensions can be used thanks to special adapters.The type of fuseholder (BS or DIN) must be specified when ordering.Contactor closing is prevented when even a single fuse is missing. Opening is automatic when one of thethree fuses blows.They are of compact and sturdy construction and guarantee very long electrical and mechanical life.

Page 10: PowerCube type PB - arianbc.net

8

2 MAIN COMPONENTS

Service trucksThe PowerCube range is equipped with all theservice trucks needed to complete the switchgearand required for service operations and duringmaintenance work.The trucks are divided into four different types:• earthing without making capacity.• earthing with making capacity.• cable testing.• isolation.

Note: the earthing trucks with making and isolationcapacity are available derived from the HD4 series only.

• Earthing truck without making capacity “E”These trucks carry out the same function as theearthing switches without making capacity.They therefore have no capacity to earth livecircuits in fault conditions.They are used to ensure an additional fixed earth,as is required by the installation service andmaintenance procedures, as a further guaranteefor personnel.The use of these trucks foresees removal of theswitching apparatus from the switchgear (circuit-breaker or contactor) and its replacement with thetruck. The units preset for use of the earthingtrucks can be provided with a key lock which,when activated, prevents their racking-in.This truck is available in two versions:• earthing of the main busbar system (E/U series).• earthing of the power cables (E/L series).During the racking-in phase, the main busbarearthing truck only actuates the top shutter andearths the contacts connected to the top branchconnections (and therefore to the main busbarsystem) by means of the switchgear structure.

During the racking-in phase, the power cableearthing truck only actuates the bottom shutterand earths the contacts connected to the bottombranch connections (and therefore to the powercables) by means of the switchgear structure.These trucks can be used in incoming or outgoingunits or in dedicated units.They can also be used in bus-tie units. In thiscase, they earth one of the two sides of the mainbusbar system.

• Earthing truck with making capacity “EM”These trucks carry out the same function as theearthing switches with making capacity.They consist of circuit-breakers only fitted withtop (main busbar earthing) or bottom (power cableearthing) terminals. The contacts without termi-nals are short-circuited by means of a copper barand connected to earth by means of the appara-tus truck.

They keep all the characteristics of the circuit-breakers, such as full making capacity on livecircuits under fault conditions.They allow closing operations to be carried outrapidly with remote electric control.The use of these trucks foresees removal of theswitching apparatus from the switchgear (circuit-breaker or contactor) and its replacement with thetruck. The units preset for use of the earthingtrucks can be provided with a key lock which,when activated, prevents their racking-in.This truck is available in two versions:• main busbar system earthing (EM/U series)• power cable earthing (EM/L series).During the racking-in phase, the main busbarearthing truck only lifts the top shutter andprepares the contacts connected to the topbranch connections (and therefore to the mainbusbar system) to close to earth by means of acontrol.During the racking-in phase, the power cableearthing truck only lifts the bottom shutter andprepares the contacts connected to the bottombranch connections (and therefore to the powercables) to close to earth by means of a control.These trucks can be used in incoming or outgoingunits or in dedicated units.They can also be used in bus-tie units. In thiscase, they earth one of the two sides of the mainbusbar system.

Page 11: PowerCube type PB - arianbc.net

9

Main busbar systemearthing truck, withoutmaking capacity.

Power cable earthingtruck, without makingcapacity.

Main busbar systemearthing truck, withmaking capacity.

Power cable earthingtruck, with makingcapacity.

Cable testing truck.

Isolating truck.

Connection is made extremely safe by using thepoles of the circuit-breakers to insulate theconnection busbars from the external environ-ment.In the incoming/outgoing units, the isolating truckconnects the main busbar system to the powercables, whereas in the bus-tie units, it connectsthe two sides of the busbar system.This truck has its application in switchgear formaking incoming/outgoing units without a circuit-breaker in radial networks, for making cableconnections between two switchgear placed infront of each other, in making interconnectionunits and in creating bus-tie-riser units withdouble isolation (in this case, both units are madeup of bus-ties, the former fitted with acircuit-breaker and the latter with an isolatingtruck).The units preset for using isolating trucks arefitted with a key lock which, when activated,prevents their being racked-in.

• Power cable testing truck “T”These trucks allow the insulation tests on thepower cables to be carried out without accessingthe feeder compartment or disconnecting thecables from the switchgear. The use of thesetrucks foresees removal of the switching appara-tus from the switchgear (circuit-breaker or contac-tor) and its replacement with the truck.During the racking-in phase, the truck only liftsthe bottom shutter and, by means of the connec-tors it is fitted with, allows connection of the testapparatus cables by means of a special insulatingrod (testing apparatus and insulating rod must beprovided by the customer).This truck can only be used in incoming/outgoingunits.

• Isolating truck “S”The isolating truck allows the top switchgearcontacts to be connected directly to the bottomones.

Page 12: PowerCube type PB - arianbc.net

10

2 MAIN COMPONENTS

Earthing switchesThe PB type PowerCube units canbe fitted with an earthing switch. Theearthing switch is fitted withmaking capacity on short-circuit.The opening and closing operationscan be locked, on request, bymeans of key locks.Earthing switch control is carried outfrom the front of the module withmanual operation suitably inter-locked with the position of thecircuit-breaker.For availability of the accessories,please see the table on page 21.

Monoblocs and shuttersThe monoblocs consist of insulating bushings containing thepower connections - top and bottom - of the circuit-breakercompartment, towards the feeder and busbar compartmentsrespectively.The shutters are of the metal type and are activated automati-cally during movement of the circuit-breaker from the test/isolated position to the connected position and vice versa.They can be fitted with a fail-safe safety device (optional) toprevent their manual opening with the circuit-breaker removed.Each shutter can be locked by means of two independentpadlocks (optional).

Insulating monoblocs (seen from the rear).

Metal segregation shutters.

Page 13: PowerCube type PB - arianbc.net

11

VT compartment with withdrawable voltage transformers.

VT Compartment (only PB/M units)The PowerCube modules can be fitted with a VTcompartment with withdrawable voltage trans-formers.The voltage transformers are of the dedicatedtype and are protected by fuses. Fuse replace-ment can be carried out with the switchgear inservice as the fuse compartment is segregatedmetallically from the other compartments.The VT compartment is available for PowerCubemodules 750 mm and 1000 mm wide.For availability of the accessories, please see thetable on page 21.

Certain signalling of the earthing switch position (open/closed) visible from the front ofthe enclosure.

Earthing switch open.

Earthing switch closed.

Page 14: PowerCube type PB - arianbc.net

12

1

3

3

2

Notes for using PowerCube type PB/E unitsTo construct incoming, outgoing and bus-tie type switchgear units, selec-tion of PB1 ... PB5 type PowerCube units is recommended (see Tables 1to 8 on the following pages).

To construct bus riser, measurement and direct busbar incoming switch-gear units, selection of PR1 ... PR5 type PowerCube units is recom-mended (see Table 9 further on).

1. Monoblocs with contacts for ratedcurrent up to 2500 A.

2. Monoblocs with contacts for ratedcurrent up to 4000 A.

3. Fan. Pre-installed in the 3600 A PB3and 2500 A PB5 units. For 4000 A PB3it is necessary to install another fan inthe back of the switchgear (by thecustomer).

Example of PB1 ... PB5 type PowerCube units (front and rear views).

Example of PR1 ... PR5 PowerCube units (front and rear views).

TYPES AVAILABLE AND APPARATUS

Page 15: PowerCube type PB - arianbc.net

13

Rated current of the VD4 circuit-breakers (A - 40 °C)

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Circuit-breaker PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=275

u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

12-17.5 16 16 630 VD4/P 12.06.16 p150 VD4/P 17.06.16 p150 PB 1/E20 20 630 VD4/P 12.06.20 p150 VD4/P 17.06.20 p150 PB 1/M25 25 630 VD4/P 12.06.25 p150 VD4/P 17.06.25 p15031.5 31.5 630 VD4/P 12.06.32 p150 VD4/P 17.06.32 p15016 16 1250 VD4/P 12.12.16 p150 VD4/P 17.12.16 p15020 20 1250 VD4/P 12.12.20 p150 VD4/P 17.12.20 p15025 25 1250 VD4/P 12.12.25 p150 VD4/P 17.12.25 p15031.5 31.5 1250 VD4/P 12.12.32 p150 VD4/P 17.12.32 p15016 16 630 VD4/W 12.06.16 p210 VD4/W 17.06.16 p210 PB 2/E20 20 630 VD4/W 12.06.20 p210 VD4/W 17.06.20 p210 PB 2/M25 25 630 VD4/W 12.06.25 p210 VD4/W 17.06.25 p21031.5 31.5 630 VD4/W 12.06.32 p210 VD4/W 17.06.32 p21016 16 1250 VD4/W 12.12.16 p210 VD4/W 17.12.16 p21020 20 1250 VD4/W 12.12.20 p210 VD4/W 17.12.20 p21025 25 1250 VD4/W 12.12.25 p210 VD4/W 17.12.25 p21031.5 31.5 1250 VD4/W 12.12.32 p210 VD4/W 17.12.32 p21040 40 1250 – –50 50 1250 – –40 40 1250 VD4/P 12.12.40 p210 VD4/P 17.12.40 p210 (3)50 50 1250 VD4/P 12.12.50 p210 –20 20 1600 VD4/P 12.16.20 p210 VD4/P 17.16.20 p21025 25 1600 VD4/P 12.16.25 p210 VD4/P 17.16.25 p21031.5 31.5 1600 VD4/P 12.16.32 p210 VD4/P 17.16.32 p21040 40 1600 VD4/P 12.16.40 p210 (3) VD4/P 17.16.40 p210 (3)50 50 1600 VD4/P 12.16.50 p210 (3) –20 20 2000 VD4/P 12.20.20 p210 VD4/P 17.20.20 p21025 25 2000 VD4/P 12.20.25 p210 VD4/P 17.20.25 p21031.5 31.5 2000 VD4/P 12.20.32 p210 VD4/P 17.20.32 p21040 40 2000 VD4/P 12.20.40 p210 (3) VD4/P 17.20.40 p210 (3)50 50 2000 VD4/P 12.20.50 p210 (3) –20 20 2500 VD4/P 12.25.20 p275 VD4/P 17.25.20 p275 PB 3/E25 25 2500 VD4/P 12.25.25 p275 VD4/P 17.25.25 p275 PB 3/M31.5 31.5 2500 VD4/P 12.25.32 p275 VD4/P 17.25.32 p27540 40 2500 VD4/P 12.25.40 p275 (3) VD4/P 17.25.40 p275 (3)50 50 2500 VD4/P 12.25.50 p275 (3) –31.5 31.5 3150 VD4/P 12.32.32 p275 (3) VD4/P 17.32.32 p275 (3)40 40 3150 VD4/P 12.32.40 p275 (3) VD4/P 17.32.40 p275 (3)50 50 3150 VD4/P 12.32.50 p275 (3) –31.5 31.5 3600 (1) VD4/P 12.32.32 p275 (3) VD4/P 17.32.32 p275 (3)40 40 3600 (1) VD4/P 12.32.40 p275 (3) VD4/P 17.32.40 p275 (3)50 50 3600 (1) VD4/P 12.32.50 p275 (3) –31.5 31.5 4000 (1) VD4/P 12.32.32 p275 (3) VD4/P 17.32.32 p275 (3)40 40 4000 (1) VD4/P 12.32.40 p275 (3) VD4/P 17.32.40 p275 (3)50 50 4000 (1) VD4/P 12.32.50 p275 (3) –

24 16 16 630 VD4/P 24.06.16 p210 – PB 4/E20 20 630 VD4/P 24.06.20 p210 – PB 4/M25 25 630 VD4/P 24.06.25 p210 –16 16 1250 VD4/P 24.12.16 p210 –20 20 1250 VD4/P 24.12.20 p210 –25 25 1250 VD4/P 24.12.25 p210 –16 16 1600 VD4/P 24.16.16 p275 – PB 5/E20 20 1600 VD4/P 24.16.20 p275 – PB 5/M25 25 1600 VD4/P 24.16.25 p275 –16 16 2000 VD4/P 24.20.16 p275 –20 20 2000 VD4/P 24.20.20 p275 –25 25 2000 VD4/P 24.20.25 p275 –16 16 2500 (2) VD4/P 24.25.16 p275 –20 20 2500 (2) VD4/P 24.25.20 p275 –25 25 2500 (2) VD4/P 24.25.25 p275 –

Table 1 - VD4 withdrawable circuit-breakers for PowerCube type PB units (*)

(*) The PowerCube units are not prepared for application of the “motorised truck”for VD4 circuit-breakers

(1) 3600 A with fan pre-installed in the PB3 units. For 4000 A it is necessary toinstall another fan in the back of the switchgear (by the customer).

(2) 2500 A with fan pre-installed in the PB5 units.(3) Please ask ABB for availability.

W = Width of PowerCube unit.P = Horizontal centre distance between circuit-breaker poles.U/L = Distance between top and bottom terminal.H = Distance between bottom terminal and earth.Ø = Diameter of the contacts in the PowerCube unit monbloc.

Page 16: PowerCube type PB - arianbc.net

14

3 TYPES AVAILABLE AND APPARATUS

Table 2 - Withdrawable HD4 circuit-breakers for PowerCube type PB units

Rated current of the HD4 circuit-breakers (A - 40 °C)

(1) 3600 A with fan pre-installed in the PB3 modules. For 4000 A it is necessary toinstall another fan in the back of the switchgear (by the customer).

(2) 2500 A with fan pre-installed in the PB5 modules.(3) Please ask ABB for availability. Not available for PB/M.

W = Width of PowerCube unit.P = Horizontal centre distance between circuit-breaker poles.U/L = Distance between top and bottom terminal.H = Distance between bottom terminal and earth.Ø = Diameter of the contacts in the PowerCube unit monbloc.

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Circuit-breaker PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=275

u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

12 16 16 630 HD4/W 12.06.16 p150 HD4/W 17.06.16 p150 PB 1/E17.5 25 25 630 HD4/W 12.06.25 p150 HD4/W 17.06.25 p150 PB 1/M

31.5 31.5 630 HD4/W 12.06.32 p150 HD4/W 17.06.32 p15016 16 1250 HD4/W 12.12.16 p150 HD4/W 17.12.16 p15025 25 1250 HD4/W 12.12.25 p150 HD4/W 17.12.25 p15031.5 31.5 1250 HD4/W 12.12.32 p150 HD4/W 17.12.32 p15016 16 630 HD4/W 12.06.16 p210 HD4/W 17.06.16 p210 PB 2/E25 25 630 HD4/W 12.06.25 p210 HD4/W 17.06.25 p210 PB 2/M31.5 31.5 630 HD4/W 12.06.32 p210 HD4/W 17.06.32 p21016 16 1250 HD4/W 12.12.16 p210 HD4/W 17.12.16 p21025 25 1250 HD4/W 12.12.25 p210 HD4/W 17.12.25 p21031.5 31.5 1250 HD4/W 12.12.32 p210 HD4/W 17.12.32 p21040 40 1250 HD4/W 12.12.40 p210 HD4/W 17.12.40 p21050 50 1250 HD4/W 12.12.50 p210 HD4/W 17.12.50 p21040 40 1250 – –50 50 1250 – –16 16 1600 HD4/W 12.16.16 p210 HD4/W 17.16.16 p21025 25 1600 HD4/W 12.16.25 p210 HD4/W 17.16.25 p21031.5 31.5 1600 HD4/W 12.16.32 p210 HD4/W 17.16.32 p21040 40 1600 HD4/P 12.16.40 p210 HD4/P 17.16.40 p21050 50 1600 HD4/P 12.16.50 p210 HD4/P 17.16.50 p21016 16 2000 HD4/W 12.20.16 p210 HD4/W 17.20.16 p21025 25 2000 HD4/W 12.20.25 p210 HD4/W 17.20.25 p21031.5 31.5 2000 HD4/W 12.20.32 p210 HD4/W 17.20.32 p21040 40 2000 HD4/P 12.20.40 p210 HD4/P 17.20.40 p21050 50 2000 HD4/P 12.20.50 p210 HD4/P 17.20.50 p21025 25 2500 HD4/P 12.25.25 p275 HD4/P 17.25.25 p275 PB 3/E31.5 31.5 2500 HD4/P 12.25.32 p275 HD4/P 17.25.32 p275 PB 3/M40 40 2500 HD4/P 12.25.40 p275 HD4/P 17.25.40 p27550 50 2500 HD4/P 12.25.50 p275 HD4/P 17.25.50 p27531.5 31.5 3150 HD4/W 12.32.32 p275 HD4/W 17.32.32 p27540 40 3150 HD4/W 12.32.40 p275 HD4/W 17.32.40 p27550 50 3150 HD4/W 12.32.50 p275 HD4/W 17.32.50 p27531.5 31.5 3600 (1) HD4/W 12.32.32 p275 HD4/W 17.32.32 p27540 40 3600 (1) HD4/W 12.32.40 p275 HD4/W 17.32.40 p27550 50 3600 (1) HD4/W 12.32.50 p275 HD4/W 17.32.50 p27531.5 31.5 4000 (1) HD4/W 12.32.32 p275 HD4/W 17.32.32 p27540 40 4000 (1) HD4/W 12.32.40 p275 HD4/W 17.32.40 p27550 50 4000 (1) HD4/W 12.32.50 p275 HD4/W 17.32.50 p275

24 16 16 630 HD4/W 24.06.16 p210 – PB 4/E20 20 630 HD4/W 24.06.20 p210 – PB 4/M25 25 630 HD4/W 24.06.25 p210 –16 16 1250 HD4/W 24.12.16 p210 –20 20 1250 HD4/W 24.12.20 p210 –25 25 1250 HD4/W 24.12.25 p210 –31.5 31.5 1250 (3) HD4/P 24.12.32 p275 –16 16 1600 HD4/P 24.16.16 p275 – PB 5/E20 20 1600 HD4/P 24.16.20 p275 – PB 5/M25 25 1600 HD4/P 24.16.25 p275 –31.5 31.5 1600 (3) HD4/P 24.16.32 p275 –16 16 2000 HD4/P 24.20.16 p275 –20 20 2000 HD4/P 24.20.20 p275 –25 25 2000 HD4/P 24.20.25 p275 –31.5 31.5 2000 (3) HD4/P 24.20.32 p275 –16 16 2500 (2) HD4/P 24.25.16 p275 –20 20 2500 (2) HD4/P 24.25.20 p275 –25 25 2500 (2) HD4/P 24.25.25 p275 –31.5 31.5 2500 (2)(3) HD4/P 24.25.32 p275 –

Page 17: PowerCube type PB - arianbc.net

15

Table 3 - Withdrawable VM1 circuit-breakers for PowerCube type PB units

Rated current of the VM1 circuit-breakers (A - 40 °C)

(1) 3600 A with fan pre-installed in the PB3 modules. For 4000 A it is necessary toinstall another fan in the back of the switchgear (by the customer).

(2) 2500 A with fan pre-installed in the PB5 modules.(3) Please ask ABB for availability.

W = Width of PowerCube unit.P = Horizontal centre distance between circuit-breaker poles.U/L = Distance between top and bottom terminal.H = Distance between bottom terminal and earth.Ø = Diameter of the contacts in the PowerCube unit monobloc.

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Circuit-breaker PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=275

u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

12 16 16 630 VM1/P 12.06.16 p150 VM1/P 17.06.16 p150 PB 1/E17.5 20 20 630 VM1/P 12.06.20 p150 VM1/P 17.06.20 p150 PB 1/M

25 25 630 VM1/P 12.06.25 p150 VM1/P 17.06.25 p15031.5 31.5 630 VM1/P 12.06.32 p150 VM1/P 17.06.32 p15016 16 1250 VM1/P 12.12.16 p150 VM1/P 17.12.16 p15020 20 1250 VM1/P 12.12.20 p150 VM1/P 17.12.20 p15025 25 1250 VM1/P 12.12.25 p150 VM1/P 17.12.25 p15031.5 31.5 1250 VM1/P 12.12.32 p150 VM1/P 17.12.32 p15016 16 630 VM1/W 12.06.16 p210 VM1/W 17.06.16 p210 PB 2/E20 20 630 VM1/W 12.06.20 p210 VM1/W 17.06.20 p210 PB 2/M25 25 630 VM1/W 12.06.25 p210 VM1/W 17.06.25 p21031.5 31.5 630 VM1/W 12.06.32 p210 VM1/W 17.06.32 p21016 16 1250 VM1/W 12.12.16 p210 VM1/W 17.12.16 p21020 20 1250 VM1/W 12.12.20 p210 VM1/W 17.12.20 p21025 25 1250 VM1/W 12.12.25 p210 VM1/W 17.12.25 p21031.5 31.5 1250 VM1/W 12.12.32 p210 VM1/W 17.12.32 p21040 40 1250 – –50 50 1250 – –40 40 1250 – –50 50 1250 – –20 20 1600 VM1/P 12.16.20 p210 VM1/P 17.16.20 p21025 25 1600 VM1/P 12.16.25 p210 VM1/P 17.16.25 p21031.5 31.5 1600 VM1/P 12.16.32 p210 VM1/P 17.16.32 p21040 40 1600 – –50 50 1600 – –20 20 2000 VM1/P 12.20.20 p210 VM1/P 17.20.20 p21025 25 2000 VM1/P 12.20.25 p210 VM1/P 17.20.25 p21031.5 31.5 2000 VM1/P 12.20.32 p210 VM1/P 17.20.32 p21040 40 2000 – –50 50 2000 – –20 20 2500 VM1/P 12.25.20 p275 VM1/P 17.25.20 p275 PB 3/E25 25 2500 VM1/P 12.25.25 p275 VM1/P 17.25.25 p275 PB 3/M31.5 31.5 2500 VM1/P 12.25.32 p275 VM1/P 17.25.32 p27540 40 2500 – –50 50 2500 – –31.5 31.5 3150 – –40 40 3150 – –50 50 3150 – –31.5 31.5 3600 (1) – –40 40 3600 (1) – –50 50 3600 (1) – –31.5 31.5 4000 (1) – –40 40 4000 (1) – –50 50 4000 (1) – –

24 16 16 630 VM1/P 24.06.16 p210 – PB 4/E20 20 630 VM1/P 24.06.20 p210 – PB 4/M25 25 630 VM1/P 24.06.25 p210 –16 16 1250 VM1/P 24.12.16 p210 –20 20 1250 VM1/P 24.12.20 p210 –25 25 1250 VM1/P 24.12.25 p210 –16 16 1600 VM1/P 24.16.16 p275 – PB 5/E20 20 1600 VM1/P 24.16.20 p275 – PB 5/M25 25 1600 VM1/P 24.16.25 p275 –16 16 2000 VM1/P 24.20.16 p275 –20 20 2000 VM1/P 24.20.20 p275 –25 25 2000 VM1/P 24.20.25 p275 –16 16 2500 (2) VM1/P 24.25.16 p275 (3) –20 20 2500 (2) VM1/P 24.25.20 p275 (3) –25 25 2500 (2) VM1/P 24.25.25 p275 (3) –

Page 18: PowerCube type PB - arianbc.net

16

3 TYPES AVAILABLE AND APPARATUS

Table 4 - Withdrawable eVM1 circuit-breakers for PowerCube type PB units

W = Width of PowerCube unit.P = Horizontal centre distance between circuit-breaker poles.U/L = Distance between top and bottom terminal.H = Distance between bottom terminal and earth.Ø = Diameter of the contacts in the PowerCube unit monobloc.* Please contact us for availability.

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Circuit-breaker type Circuit-breaker type PowerCubekA) (kA) p=150 p=210 p=210 p=275 p=210 p=2753s u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310

H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

16 16 630 eVM1/P 12.06.16 p150 eVM1/P 17.06.16 p150 PB1/E20 20 630 eVM1/P 12.06.20 p150 eVM1/P 17.06.20 p150 PB1/M25 25 630 eVM1/P 12.06.25 p150 eVM1/P 17.06.25 p15031.5 31.5 630 eVM1/P 12.06.32 p150 eVM1/P 17.06.32 p150

16 16 1250 eVM1/P 12.12.16 p150 eVM1/P 17.12.16 p15020 20 1250 eVM1/P 12.12.20 p150 eVM1/P 17.12.20 p15025 25 1250 eVM1/P 12.12.25 p150 eVM1/P 17.12.25 p15031.5 31.5 1250 eVM1/P 12.12.32 p150 eVM1/P 17.12.32 p150

Rated current of the eVM1 circuit-breakers inserted in thePowerCube units (40°C) [A]

Withdrawable eVM1 for PowerCube unit

Table 5 - Withdrawable Vmax circuit-breakers for PowerCube type PB units

Rated current of the circuit-breakers Vmax inserted in thePowerCube units (40°C) [A]

Withdrawable Vmax for PowerCube units

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Circuit-breaker type Circuit-breaker type PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=2753s u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310

H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

16 16 630 Vmax/W 12.06.16 p150 Vmax/W 17.06.16 p150 * PB1/E20 20 630 Vmax/W 12.06.20 p150 Vmax/W 17.06.20 p150 * PB1/M25 25 630 Vmax/W 12.06.25 p150 Vmax/W 17.06.25 p150 *31.5 31.5 630 Vmax/W 12.06.32 p150 Vmax/W 17.06.32 p150 *

16 16 1250 Vmax/W 12.12.16 p150 Vmax/W 17.12.16 p150 *20 20 1250 Vmax/W 12.12.20 p150 Vmax/W 17.12.20 p150 *25 25 1250 Vmax/W 12.12.25 p150 Vmax/W 17.12.25 p150 *31.5 31.5 1250 Vmax/W 12.12.32 p150 Vmax/W 17.12.32 p150 *

Page 19: PowerCube type PB - arianbc.net

17

Table 6 - V-Contact withdrawable contactors for PowerCube type PB units

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Contactor PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=275(3) u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310

H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

7.2 16 6 400 (4) V7/W PB 1/E20 6 400 (4) VSC7/P PB 1/M25 6 400 (4)31.5 6 400 (4)

12 16 6 400 (4) V12/W20 6 400 (4) VSC12/P25 6 400 (4)31.5 6 400 (4)

Rated current of the V-Contact contactors (A - 40 °C)

Table 7 – Isolating trucks for PowerCube type PB units

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Isolating truck PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=275

u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

12 16 16 ...1250 S-HD4/W 17.12.32 p150 PB 1/E17.5 20 20 PB 1/M

25 2531.5 31.516 16 ...1250 S-HD4/W 17.12.32 p210 PB 2/E20 20 PB 2/M25 2531.5 31.540 40 S-HD4/W 17.12.50 p21050 5016 16 ...2000 S-HD4/W 17.20.32 p21020 2025 2531.5 31.540 40 S-HD4/P 17.20.50 p21050 5016 16 ...2500 S-HD4/P 17.25.50 p275 PB 3/E20 20 PB 3/M25 2531.5 31.540 4050 5016 16 ...3150 S-HD4/P 17.32.50 p27520 2025 2531.5 31.540 4050 5031.5 31.5 ...3600 (1) S-HD4/P 17.32.50 p27540 40 ...3600 (1)50 5031.5 31.5 ...4000 (1) S-HD4/P 17.32.50 p27540 40 ...4000 (1)50 50

24 16 16 ...1250 S-HD4/W 24.12.25 p210 PB 4/E20 20 PB 4/M25 2516 16 ...2000 S-HD4/P 24.20.25 p275 PB 5/E20 20 PB 5/M25 2516 16 ...2500 (2) S-HD4/P 24.25.25 p27520 2025 25

Rated current of the isolating trucks (A - 40 °C)

(1) 3600 A with fan pre-installed in the PB3 modules. For 4000 Ait is necessary to install another fan in the back of the switch-gear (by the customer).

(2) 2500 A with fan pre-installed in the PB5 modules.(3) Guaranteed using suitable fuses.(4) The rated current is subject to derating according to the rated

current of the fuses.

W = Width of PowerCube unit.P = Horizontal centre distance between circuit-breaker poles.U/L = Distance between top and bottom terminal.H = Distance between bottom terminal and earth.Ø = Diameter of the contacts in the PowerCube unit monobloc.

Page 20: PowerCube type PB - arianbc.net

18

3 TYPES AVAILABLE AND APPARATUS

Table 8 – Earthing trucks with making capacity for PowerCube type PB units

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Earthing PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=275 truck (1)

u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

12 16 16 ...1250 PB 1/E17.5 20 20 EM-U/W 17.12.32 p150 PB 1/M

25 25 EM-L/W 17.12.32 p15031.5 31.516 16 ...1250 PB 2/E20 20 EM-L/W 17.12.32 p210 PB 2/M25 25 EM-U/W 17.12.32 p21031.5 31.540 40 EM-L/W 17.12.50 p210 (2)50 50 EM-U/W 17.12.50 p210 (2)16 16 ...200020 20 EM-L/W 17.20.32 p21025 25 EM-U/W 17.20.32 p21031.5 31.540 40 EM-L/P 17.20.50 p21050 50 EM-U/P 17.20.50 p21016 16 ...2500 PB 3/E20 20 PB 3/M25 25 EM-L/P 17.25.50 p27531.5 31.5 EM-U/P 17.25.50 p27540 4050 5016 16 ....315020 2025 25 EM-L/P 17.32.50 p27531.5 31.5 EM-U/P 17.32.50 p27540 4050 50

24 16 16 ...1250 PB 4/E20 20 PB 4/M25 2516 16 ...2000 PB 5/E20 20 PB 5/M25 2516 16 ...2500 (2)20 2025 25

EM-L/W 24.12.25 p210EM-U/W 24.12.25 p210

EM-L/P 24.20.25 p275EM-U/P 24.20.25 p275

EM-L/P 24.25.25 p275EM-U/P 24.25.25 p275

Rated current of the earthing trucks (A - 40 °C)

(1) - EM-L... = Earthing truck with making capacity with bottom bush-ings (for cable earthing).

- EM-U... = Earthing truck with making capacity with top bush-ings (for earthing the busbar system).

(2) Ask ABB.

W = Width of PowerCube unit.P = Horizontal centre distance between circuit-breaker poles.U/L = Distance between top and bottom terminal.H = Distance between bottom terminal and earth.Ø = Diameter of the contacts in the PowerCube type PB unit

monobloc.

Page 21: PowerCube type PB - arianbc.net

19

Table 9 - Earthing trucks without making capacity for PowerCube type PB units

E-L/W 24.12.25 p210E-U/W 24.12.25 p210

E-L/P 24.20.25 p275E-U/P 24.20.25 p275

E-L/P 24.25.25 p275E-U/P 24.25.25 p275

(1) - EM-L... = Earthing truck without making capacity with bot-tom bushings (for cable earthing).

- EM-U... = Earthing truck without making capacity with topbushings (for earthing the busbar system).

(2) Ask ABB.

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Earthing PowerCube(kA) (kA) p=150 p=210 p=210 p=275 p=210 p=275 truck (1)

u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

12 16 16 ...1250 PB 1/E17.5 20 20 E-U/W 17.12.32 p150 PB 1/M

25 25 E-L/W 17.12.32 p15031.5 31.516 16 ...1250 PB 2/E20 20 E-L/W 17.12.32 p210 PB 2/M25 25 E-U/W 17.12.32 p21031.5 31.540 40 E-L/W 17.12.50 p210 (2)50 50 E-U/W 17.12.50 p210 (2)16 16 ...200020 20 E-L/W 17.20.32 p21025 25 E-U/W 17.20.32 p21031.5 31.540 40 E-L/P 17.20.50 p21050 50 E-U/P 17.20.50 p21016 16 ...2500 PB 3/E20 20 PB 3/M25 25 E-L/P 17.25.50 p27531.5 31.5 E-U/P 17.25.50 p27540 4050 5016 16 ...315020 2025 25 E-L/P 17.32.50 p27531.5 31.5 E-U/P 17.32.50 p27540 4050 50

24 16 16 ...1250 PB 4/E20 20 PB 4/M25 2516 16 ...2000 PB 5/E20 20 PB 5/M25 2516 16 ...250020 2025 25

Rated current of the earthing trucks (A - 40 °C)

W = Width of PowerCube unit.P = Horizontal centre distance between circuit-breaker poles.U/L = Distance between top and bottom terminal.H = Distance between bottom terminal and earth.Ø = Diameter of the contacts in the PowerCube unit monobloc.

Page 22: PowerCube type PB - arianbc.net

20

3 TYPES AVAILABLE AND APPARATUS

Table 10 – Cable testing trucks for PowerCube type PB units

kV Isc Icw W=600 W=750 W=750 W=1000 W=750 W=1000 Cable PowerCube(kA) (kAx3s) p=150 p=210 p=210 p=275 p=210 p=275 testing truck

u/l=205 u/l=310 u/l=310 u/l=310 u/l=310 u/l=310H=260 H=280 H=280 H=280 H=325 H=345ø=35 ø=35 ø=79 ø=109 ø=35 ø=79

12 16 16 ...1250 PB 1/E17.5 20 20 PB 1/M

25 2531.5 31.516 16 ...1250 PB 2/E20 20 PB 2/M25 2531.5 31.5

40 4050 5016 16 ...200020 2025 2531.5 31.540 4050 5016 16 2500 PB 3/E20 20 PB 3/M25 2531.5 31.540 4050 5016 16 315020 2025 2531.5 31.540 4050 50

24 16 16 ...1250 PB 4/E20 20 PB 4/M25 2516 16 ...2000 PB 5/E20 20 PB 5/M25 2516 16 ...2500 (1)20 2025 25

Table 11 - PowerCube type PB units without apparatus

Rated current of the cable testing trucks (A - 40 °C)

Enclosure characteristics Configuration

Rated Width Rated Isc (kA) Icw Bus riser or direct Bus riser or direct Measuring (2) Measuring (2)voltage current (kA x 3s/1s) incoming feeder incoming feeder with(kV) (mm) (A) (1) (1) earthing switch

12-17.5 600 1250 31.5 31.5 PB1/RE - PB1/RM PB1/RE - PB1/RM PB1/RE - PB1/RM PB1/RE - PB1/RM

12-17.5 750 2000 31.5 31.5 PB2/RE - PB2/RM PB2/RE - PB2/RM PB2/RE - PB2/RM PB2/RE - PB2/RM

12-17.5 750 2000 40-50 40-50 PB2/RE - PB2/RM PB2/RE - PB2/RM PB2/RE - PB2/RM PB2/RE - PB2/RM

12-17.5 1000 4000 31.5 31.5 PB3/RE - PB3/RM PB3/RE - PB3/RM PB3/RE - PB3/RM PB3/RE - PB3/RM

12-17.5 1000 4000 40-50 40-50 PB3/RE - PB3/RM PB3/RE - PB3/RM PB3/RE - PB3/RM PB3/RE - PB3/RM

24 750 1250 25 25 PB4/RE - PB4/RM PB4/RE - PB4/RM PB4/RE - PB4/RM PB4/RE - PB4/RM

24 1000 2500 25 25 PB5/RE - PB5/RM PB5/RE - PB5/RM PB5/RE - PB5/RM PB5/RE - PB5/RM

W = Width of PowerCubeunit.

P = Horizontal centre dis-tance between circuit-breaker poles.

U/L = Distance between topand bottom terminal.

H = Distance between bot-tom terminal and earth

Ø = Diameter of the contactsin the PowerCube unitmonobloc.

(1) Ask ABB.

(1) On earthing switch, if provided.(2) For units PB/RE end for PB1/RM, the VT compartment is not available. Construction at customer care.

T/W 17.12 p150

T/W 17.12 p210

T/W 17.12 p210 (1)

T/W 17.20 p210

T/P 17.20 p210

T/P 17.32 p275

T/W 24.12 p210

T/W 24.20 p275

T/P 24.25 p275

Page 23: PowerCube type PB - arianbc.net

21

PB type PowerCube unit PB1 PB2 PB3 PB4 PB5 PB1/R PB2/R PB3/R PB4/R PB5/R

Width (mm) 600 750 1000 750 1000 600 750 1000 750 1000

Rated 12 kV - - - -

voltage 17.5 kV - - - -

24 kV - - - - - -

Unit Incoming/outgoing/bus-tie - - - - -

Bus-riser/measurements/direct incoming - - - - -

Standard 1a Group of auxiliary contactsfittings connected/isolated - - - - -

1b Anti-racking-in lock for circuit-breakers withlower rated current than that of thecompartment or for apparatus not foreseenfor the compartment itself - - - - -

2 Circuit-breaker anti-racking-in lock - - - - -

3 VT compartment (only PB/M units) - -

4 Earthing switch

5 Key locks open or closed or open andclosed for earthing switch

6 Electro-mech. lock for earthing switch- 24-30-48-60-110-125-220-250 V c.c.- 110-220 V c.a.

7 Earthing switch auxiliarycontacts (5 or 10)

8 Safety device for the metalshutters (Fail Safe) - - - - -

9 Voltage signalling device (2)

10 Anti-condensation heater

(110-220 Vca 50 Hz) - - - - -

11 Contact for earthing truckracked-in position - - - - -

12 Electromechanical interlock forcircuit-breaker compartment door- 24-30-48-60-110-125-220-250 V c.c.- 110-220 V c.a. - - - - -

13 Padlock for metal shutters(top or bottom or top and bottom) - - - - -

14 Key lock for racking in earthing truck - - - - -

15 Earthing switch operating lever- extra in relation to normal supply (1)

16 Lifting eyebolts (2)

17 Apparatus transport and racking/in truck - - - - -

Acc

esso

ries

to b

e sp

ecif

ied

at

the

tim

e o

f o

rder

ing

(as

sem

bly

by

AB

B)

Acc

esso

ries

on

req

ues

t(a

ssem

bly

by

the

cust

om

er)

AccessoriesThe table shows the accessories available and the relative possible combinations of the PowerCube type PB units.

(1) Remember that the standard supply provides up to 10 levers per order position with a maximum of 1 lever per enclosure (prepared for earthing switch).(2) Only for PowerCube type PB/M modules. Capacitive dividers at customer care.

Page 24: PowerCube type PB - arianbc.net

22

4 OVERALL DIMENSIONS AND WEIGHTS

PB/E type units

Rated Rated Isc Table of WeightModule voltage current Icw dimensions A [mm] B [mm] C [mm] [kg]

[kV] [A] [kV] (1)

12 630 - 1250 31.5 1VCD003369 600 1016 1120PB1/E 17.5 630 - 1250 31.5 1VCD003369 600 1016 1120 180

12 630...2000 31.5 1VCD003370 750 1016 1120

12 1250...2000 40-50 1VCD003370 750 1016 1120PB2/E 17.5 630...2000 31.5 1VCD003370 750 1016 1120 200...240

17.5 1250...2000 40-50 1VCD003370 750 1016 1120

12-17.5 2500 31.5 1VCD003371 1000 1030 1120 300

12-17.5 3150 31.5 1VCD003372 1000 1030 1120 320

12-17.5 3600...4000 31.5 1VCD003373 1000 1030 1120 350...380PB3/E 12-17.5 2500 40-50 1VCD003371 1000 1030 1120 300

12-17.5 3150 40-50 1VCD003372 1000 1030 1120 320

12-17.5 3600 - 4000 40-50 1VCD003373 1000 1030 1120 350...380

PB4/E 24 630 - 1250 31.5 1VCD003374 750 1246 (2) 1230 250

24 1600 - 2000 31.5 1VCD003376 1000 1246 (2) 1230 310PB5/E 24 2500 31.5 1VCD003376 1000 1246 (2) 1230 340

PB1/RE 17.5 31.5 1VCD003377 600 1016 (2) 1120 165

17.5 31.5 1VCD003378 750 1016 (2) 1120 165...215

PB2/RE 17.5 40-50 1VCD003378 750 1016 (2) 1120 165...215

12-17.5 31.5 1VCD003379 1000 1030 (2) 1120 270

PB3/RE 12-17.5 40-50 1VCD003379 1000 1030 (2) 1120 270

PB4/RE 24 31.5 1VCD003380 750 1310 (2) 1230 215

PB5/RE 24 31.5 1VCD003381 1000 1246 (2) 1230 250

(1) Weight without earthing switch.(2) Dimension with earthing switch.

NOT

APPLICABLE

Page 25: PowerCube type PB - arianbc.net

23(*)

PB/R type unitsPB/M type units

(1) Weight without earthing switch and without VT compartment.(2) Dimension with earthing switch.

Rated Rated Isc Table of WeightModule voltage current Icw dimensions A [mm] B [mm] C [mm] [kg]

[kV] [A] [kV] (1)

12 630 - 1250 31.5 1VCD000023 600 1016 1680PB1/M 17.5 630 - 1250 31.5 1VCD000028 600 1016 1680 200

12 630...2000 31.5 1VCD000024 750 1016 1680

12 1250...2000 40-50 1VCD000027 750 1016 1680PB2/M 17.5 630...2000 31.5 1VCD000029 750 1016 1680 220...260

17.5 1250...2000 40-50 1VCD000030 750 1016 1680

12-17.5 2500 31.5 1VCD000025 1000 1030 1680 320

12-17.5 3150 31.5 1VCD000026 1000 1030 1680 340

12-17.5 3600...4000 31.5 1VCD000043 1000 1030 1680 370...400PB3/M 12-17.5 2500 40-50 1VCD000037 1000 1030 1680 320

12-17.5 3150 40-50 1VCD000038 1000 1030 1680 340

12-17.5 3600 - 4000 40-50 1VCD000039 1000 1030 1680 370...400

PB4/M 24 630 - 1250 31.5 1VCD000031 750 1510 1745 270

24 1600 - 2000 31.5 1VCD000032 1000 1246 1745 330PB5/M 24 2500 31.5 1VCD000044 1000 1246 1745 360

Rated Rated Isc Table of WeightModule voltage current Icw dimensions A [mm] B [mm] C [mm] [kg]

[kV] [A] [kV] (2) (1)

PB1/RM 17.5 31.5 1VCD000033 600 1016 1745 185

12 31.5 1VCD000034 750 1016 1745 185...235

PB2/RM 17.5 40-50 1VCD000040 750 1016 1745 185...235

12-17.5 31.5 1VCD000041 1000 1030 1680 290

PB3/RM 12-17.5 40-50 1VCD000042 1000 1030 1680 290

PB4/RM 24 31.5 1VCD000035 750 1310 1745 270

PB5/RM 24 31.5 1VCD000036 1000 1246 1745 270

NOT

APPLICABLE

Page 26: PowerCube type PB - arianbc.net

24

5

Diagrams of the applications

ELECTRIC CIRCUIT DIAGRAM

Page 27: PowerCube type PB - arianbc.net

25

Page 28: PowerCube type PB - arianbc.net

26

5 ELECTRIC CIRCUIT DIAGRAM

Diagrams of the applications

Page 29: PowerCube type PB - arianbc.net

27

Reference designations

Reference designations (in compliance with IEC 61346-2 Standard and with the ABB 2NBA000001technical standard).

Designation Description

Number of the diagram figure-BC Current transformer-BE Earthing switch auxiliary contacts (see note B)-BT4 Contacts on the switchgear for signalling truck in connected position (see note C)-BT5 Contacts on the switchgear for signalling truck in isolated position (see note C)-BW1 Position contact of the front fan-BW2 Position contact of the rear fan-CC1 Condenser for the front fan-CC2 Condenser for the rear fan-KA3 Current measuring relay-KA4 Auxiliary contactor for operation of the front fan-KA5 Auxiliary contactor for operation of the rear fan-KT1, -KT2 Timed auxiliary relays for control of front forced ventilation-KT3, -KT4 Timed auxiliary relays for control of rear forced ventilation-KT5 Timed auxiliary relay for signalling alarm of front forced ventilation not working-KT6 Timed auxiliary relay for signalling alarm of rear forced ventilation not working-MV1 Front fan (see note E)-MV2 Rear fan (see note E)-PA Ammeter-PR1 Red lamp for signalling alarm of front forced ventilation not working-PR2 Red lamp for signalling alarm of rear forced ventilation not working-PT1 White lamp for signalling alarm of front forced ventilation working-PT2 White lamp for signalling alarm of rear forced ventilation working-RL3 Electro-mechanical lock on earthing switch closing operation-RL4 Locking magnet. When de-energised it mechanically prevents door opening-SL Contact for the earthing switch operation lock-SU3 Delayed pushbutton for enabling earthing switch operation (maximum delay allowed is 1

minute)-SU3 Pushbutton for releasing the door-XF1 Connector for isolation of the front forced ventilation circuits-XF2 Connector for the rear forced ventilation circuits-XF3 Connector for the front forced ventilation circuits

Page 30: PowerCube type PB - arianbc.net

28

5 ELECTRIC CIRCUIT DIAGRAM

Figure Description

Fig. 1 Contacts for electrical signalling of circuit-breaker in connected position (see note C)

Fig. 3 Contacts for electrical signalling of circuit-breaker in isolated position (see note C)

Fig. 20 Circuit of the electro-mechanical lock on the earthing switch closing operation: operation is onlyallowed with coil -RL3 energised

Fig. 21 First pack of earthing switch auxiliary contacts (see note B)

Fig. 22 Second pack of earthing switch auxiliary contacts (see note B)

Fig. 23 Circuit of the electro-mechanical lock on door opening: opening is only allowed with coil -RL4energised

Fig. 41 Front forced ventilation circuit

Fig. 43 Front and rear forced ventilation circuit

Notes

A) The switchgear is only fitted with the applications specified in the order confirmation.

B) The -BE auxiliary contacts are supplied in the position indicated on the diagram. However, they caneasily be converted by the user from break contacts into make contacts or vice versa.

C) The -BT4 and BT5 position contacts are changeovers. Therefore the break and make contact belongingto the same position contact cannot be supplied with different voltages.

D) When fig. 23 is required, the -BT5 contact (terminals 51-52-53-54) in fig. 3 is not available.

E) Connection of the fans must take place when at least one phase exceeds the following thresholds fora time of 60 seconds:

- UniSafe 12-17.5 kV 3600 A = 3000 A (front fan)

- UniSafe 12-17.5 kV 4000 A = 3000 A (front fan) e 3600 A (rear fan)

- UniSafe 24 kV 2500 A = 2250 A (front fan).

Disconnection of the fans must take place when all three phases have currents lower than the followingvalues for a time of 300 seconds:

- UniSafe 12-17.5 kV 3600 A = 2900 A (front fan)

- UniSafe 12-17.5 kV 4000 A = 2900 A (front fan) and 3500 A (rear fan)

- UniSafe 24 kV 2500 A = 2150 A (front fan).

Page 31: PowerCube type PB - arianbc.net

29

Graphic symbols (in compliance with IEC 60617 and CEI EN 60617 Standards)

Break contact

Mechanical, pneumaticor hydraulic connection

Connection of conductors

Delayed movement(in the direction the arc movestowards its centre)

Control coil with two separatewindings

Socket and plug(female and male)

Pushbutton actuator

Closing position contact(limit switch)

Opening position contact(limit switch)

Control coil (general symbol)

Ammeter

Current transformer

Semi-conductor diode(general symbol)

Capacitor (general symbol)

Make contact

Earth (general symbol)

Conductive electric part, frame

Terminal

Single-phase asynchronousmotor, rotor under short-circuit,terminals for aux. phase takenoutside

Position changeover breakbefore make contact(limit switch)

Control coil of a relay with delayon relapse ritardo alla ricaduta

Control coil of a relay with delayon attraction

Lamp (general symbol)

Page 32: PowerCube type PB - arianbc.net

30

6

PR512 switchgear protection deviceWith regard to the functionality of protections 50/51/50N/51N, the PR512 are self-supplied typereleases. To guarantee operation of the ammeterand of the dialogue function, an auxiliary powersupply must also be provided.They are available in the following versions:– PR512/P. Protection against overload (51) and

instantaneous or delayed short-circuit (50).– PR512/P. Protection against overload (51),

instantaneous or delayed short-circuit (50),earth fault (51N) and instantaneous or delayedearth fault (50N).

– PR512/PD. Protection against overload (51),instantaneous or delayed short-circuit (50),earth fault (51N) and instantaneous or delayedearth fault (50N). Dialogue function to beconnected to the electrical installation manage-ment system.

For the characteristics of the current transformersto be combined with the PR512, please refer totechnical catalogue 1VCP000055.

Voltage transformersThe voltage transformers are of the type insulatedin resin and are used to supply measuring andprotection devices.The are available for fixed assembly or for instal-lation on withdrawable trucks.They comply with the IEC 60044-2 Standards.Their dimensions are usually according to the DIN42600 Standard. The transformers installed onwithdrawable trucks are, on the other hand, of thededicated type.These transformers can have one or two poles,with performances and precision classes suitablefor the functional requirements of the instrumentsconnected to them.When they are installed on withdrawable trucks,they are fitted with medium voltage protectionfuses.Replacement of the fuses can be carried out withthe switchgear in service.

Current transformersThe current transformers are of the type insulatedin resin and are used to supply measuring andprotection devices. These transformers can eitherhave a wound core or a through bar with one ormore cores, with performance and precisionclasses suited to the installation requirements.They comply with IEC 60044-1 Standards.

For completion of the switchgear, ABB can also offer the components indicated below.For further details, please consult us.

COMPLETION OF THE SWITCHGEAR

Their dimensions are usually according to the DIN42600 Standard.The current transformers can also be fitted with acapacitive socket for connection to the voltagesignalling lamps.

Measurement sensors (for applicationwith REF542plus electronic or similarprotection units)The introduction of digital technologies intoelectrical measuring and protection instrumentshas considerably modified the performancesrequired of transformers.The analog input levels of the instruments havebeen notably reduced when compared with thoseof traditional systems.For this reason, ABB has introduced a new rangeof sensors which best covers the characteristicsof the new generations of instruments.The switchgear can be equipped with ABBKEVCD Block Type sensors up to 24 kV.The current sensors comply with the IEC 60044-8(CDV) Standards, whereas the voltage sensorscomply with the IEC 60044-7 Standards.The dimensions are in accordance with the DIN42600 Narrow Type standard.Both the current and voltage sensors or just thecurrent sensors can be integrated simultaneouslyin the same resin body. The voltage divider forconnection to the voltage signalling lamps is alsoinserted.The measurement sensors and the multi-purposeABB units have Cl. 1 class of precision.

• Current sensorThe current sensor consists of a Rogowski coilwithout the ferromagnetic core, so it is not af-fected by saturation phenomena.When a coil is formed by a uniform winding over aclosed non-magnetic core of constant cross-section, the induced voltage in the secondarycircuit is directly proportional to the variation inthe let-through current. To obtain a signal propor-tional to the current given, this voltage must beintegrated. The multi-purpose devices carry outthis function and use the signal obtained both forthe measurements and for the protections.

Page 33: PowerCube type PB - arianbc.net

31

ABB KEVCD type combined voltage-current sensors.

Main characteristics of the current sensors

– Linear response over the whole measurement range;– no saturation phenomenon;– no hysterisis phenomenon;– a single instrument for protections and measurements;– high class of precision;– high degree of immunity to electromagnetic inter-

ferences;– the output signal is a voltage (150 mV) proportional

to the variation in the current time. Measurement ofthe current is obtained by integrating the signal;

– just two coils cover the range of rated currents from0 to 3200 A;

– the winding can remain open even with the switch-gear in service.

• Voltage sensor

The voltage sensor consists of a resistive dividerthrough which the signal is taken up. This sensor,too, is the of the unsaturable and linear type overthe whole measurement range.The output signal is a voltage directly proportionalto the primary voltage. The resistive elementconsists of a bar made of ceramic material.The voltages sensors are used for taking measure-ments and for supplying the protections with powersimultaneously.

Main characteristics of the voltage sensors– Linear response over the whole measurement range;– no saturation phenomenon;– no ferroresonance phenomenon;– a single instrument for protections and measure-

ments;– high class of precision;– high degree of immunity to electromagnetic

interferences;– the output signal is a voltage directly proportion-

al to the primary voltage;– the division ratio is 10000/1;– a single divider covers the range from 0 to 24 kV

rated voltage.

REF542plus electronic unit (Product guide1MRS 755859)The REF542plus unit integrates all the secondaryfunctions relative to a switchgear unit in a singlemodule fitted with watchdog. Thanks to theflexibility of its software, the unit is able to satisfya vast range of installation requirements: protec-tion measurement, control and signalling.The user interface is simple and easy to use.

REF542plus in a kit for OEMThe integrated protection and control unit is basedon the REF542plus platform - multi-purpose unitfor medium voltage switchgear.The REF542plus unit uses the latest microelec-tronic and information technology discoveries. Themain functions carried out by the REF542plus unitare as follows:• protection• control• measurement• monitoring• quality of the energy• communication.Thanks to the exceptional flexibility and scalabilityof this advanced unit, all the functions are inte-grated in a single configurable environment.This unit therefore makes targeted and intelligentsolutions possible, with limited cabling require-ments, in those places where the traditionalapproach would be costly and inefficient.

IndustrialIT

REF542plus has been tested and certified asconforming with IndustrialIT, Level 0 - Information.All the information about the product is provided inan interactive electronic format, compatible withABB Aspect ObjectTM technology.ABB’s commitment to respecting the IndustrialIT

conformity guarantees that each construction unitis provided with all the instruments needed toensure efficient installation, function andmaintenance operations throughout the useful lifeof the product.For further information about IndustrialIT please goto the site www.abb.com/industrialit.

Page 34: PowerCube type PB - arianbc.net

32

6

Configuration of the primary part is structured asshown in the single-line diagram at the side.The circuit-breaker can be fixed or withdrawable.The earthing switch is manual. Configurationswith a contactor in place of the circuit-breaker arealso provided for motor outgoing feeders.

The ATEX certified version, in accordance withdirective 94/9/EC for explosive environments,is also available. Please contact ABB.

NoteSpecific and customised solutions and protectiondiagrams are possible. Please contact ABB.

FusesFuses to be combined with apparatus such as the contactor,are available for protection of feeders, motors, capacitors,instrument voltage transformers, etc.The fuses comply with DIN or BS Standards.For the contactor-fuse combination and coordination, pleaserefer to the 1VCP000049 technical catalogue.

Fixed or withdrawablecircuit-breaker.

Single-line diagramof the primary part.

Manual earthingswitch.

Preconfigured solutions based on REF542plusSome solutions already configured for protection and control of most of the common medium voltageapplications are defined here.These solutions are based on the REF542plus unit and do not require any programming.The REF542plus unit is supplied already programmed and ready for installation.Only the protection parameter setting remains to be carried out.The REF542plus unit, already configured, can only be ordered as part of the medium voltage kit.It cannot be sold separately.

COMPLETION OF THE SWITCHGEAR

Page 35: PowerCube type PB - arianbc.net
Page 36: PowerCube type PB - arianbc.net

ABB Power Technologies S.p.A.Unità Operativa SaceVia Friuli, 4I-24044 DalmineTel: +39 035 395111Fax: +39 035 395874E-mail: [email protected]://www.abb.com

ABB AGCalor Emag Medium Voltage ProductsOberhausener Strasse 33 Petzower Strasse 8D-40472 Ratingen D-14542 GlindowPhone: +49(0)2102/12-1230, Fax: +49(0)2102/12-1916E-mail: [email protected]:http://www.abb.de/calor

The

dat

a an

d ill

ustr

atio

ns a

re n

ot b

indi

ng. W

e re

serv

e th

e ri

ght t

o m

ake

chan

ges

in t

he c

ours

e of

tec

hnic

al d

evel

opm

ent

of t

he p

rodu

ct.

1VC

P00

0091

- R

ev. D

, en

- T

echn

ical

Cat

alog

ue -

200

6.11

(P

ower

Cub

e P

B)