potential for energy saving in building transition spaces
TRANSCRIPT
www.elsevier.com/locate/enbuild
Energy and Buildings 39 (2007) 815–822
Potential for energy saving in building transition spaces
Adrian Pitts *, Jasmi Bin Saleh
School of Architecture, University of Sheffield, Western Bank, Sheffield S10 2TN, United Kingdom
Abstract
This paper reports on an analytical investigation into the energy saving potential associated with modified comfort limits in transitional spaces
in buildings. Such spaces may not require the same high level and close environmental control of more fully occupied spaces and thus a wider
variation in conditions and interpretation of thermal comfort may be permitted. Estimations are made of energy saving potential based upon typical
floor area proportions utilised for transition spaces of various types in office/commercial buildings. The data are combined with suggested norms
for comfort expectation that have wider temperature limits than for normally occupied office zones. The method has been applied to a series of
building types situated in the climate of the East Pennines area of the UK using a thermal analysis tool. The results show that useful energy savings
(particularly for heating) are possible by allowing for a modest (and realistic) relaxation of prescribed comfort standards in transition spaces.
Further work is now required to confirm the limits and assess energy saving in practice.
# 2007 Elsevier B.V. All rights reserved.
Keywords: Thermal comfort; Transition spaces; Energy use; Heating; Cooling
1. Introduction
Transition spaces in buildings (including such areas as
foyers, lobbies, certain atria and ancillary spaces not directly
occupied in relation to the activity of the building) pose an
interesting and fruitful area for comfort research. Entrance and
transition areas of buildings are often perceived as some of the
most important in architectural design terms since they also
impact on a wide range of senses and perceptions of human
occupants; have an important role in control of circulation; and
are often associated with some of the longer lasting impressions
that occupants or visitors have of the building.
It is suggested in this paper that such spaces, whilst being
important, do not require the fine control of temperature or
comfort limits associated with the principal areas of a building;
and that they can also be actively designed to modify the
experience and expectation of persons moving through them.
Opportunities exist for such areas to be provided with
environmental conditions lying someway between internal
and external conditions. This may offer benefits such as
reduction of thermal shock for occupants moving into and out
of spaces as well as modifying comfort expectations.
* Corresponding author. Tel.: +44 114 222 0319; fax: +44 114 279 8276.
E-mail address: [email protected] (A. Pitts).
0378-7788/$ – see front matter # 2007 Elsevier B.V. All rights reserved.
doi:10.1016/j.enbuild.2007.02.006
An additional consideration is that such spaces are often
located at the perimeters of buildings; frequently have large
areas of glazing; and also experience significant air exchange
with the outside environment. As such they may generally
require considerably higher levels of building services
provision for comfort conditioning and consequently have
higher energy consumption. Some research has shown that
transitional spaces can help to save energy if they can be
developed according to their climatic needs [1].
2. Background
The inclusion of transitional spaces, in the form of corridors,
draught lobbies, atriums and stairwells, is unavoidable in the
design of most non-domestic buildings. A wide-ranging survey
of designed spaces carried out by the authors (but not yet
published) indicates the proportion of such areas may vary
between (a more typical) 10% to as high as 40% of the total
volume in different types of buildings. Such spaces are thus
important in many ways.
Transitional spaces are defined as spaces located in-between
outdoor and indoor environments acting as both buffer spaces
and physical links. Other than being functional as circulatory
routes for the building, the design of these spaces is considered
very important by architects for reasons of aesthetics and as
emergency exit routes in the event of fire. The importance of
optimum energy consumption in transitional spaces is also very
Table 1
The Fanger and comfort scale
Hot +3
Warm +2
Slightly warm +l
Neutral 0
Slightly cool �1
Cool �2
Cold �3
A. Pitts, J.B. Saleh / Energy and Buildings 39 (2007) 815–822816
relevant in non-domestic buildings, as these spaces do not
normally generate ‘income’ from the commercial activities
carried out, hence any wastage associated with higher energy
cost is economically difficult to justify.
Currently it is common to find that considerable amounts
of energy are required to sustain comfort levels for these
environments in line with various prescribed building
standards. The energy consumption may be comparable with
the energy use in all other occupied areas of the building taken
together in some extreme examples, and buildings that have
sizable circulatory spaces face higher operational costs. Indeed
some researchers have suggested that the energy consumption
in transitional spaces, per unit area or volume, may be as high
as three times that of the remainder of the inside of a building
[2,3].
This paper aims to investigate the impact of transitional
spaces and their influence on energy consumption in buildings
by means of a parametric study of variations in the layout and
orientation of the building and the transition spaces. Several
notional types of building layout that are commonly found have
been used for simple investigative modelling of energy
consumption. The calculations of energy use were initially
carried out for a base case building assuming temperatures in
the transitional spaces that conformed to the recognised
building environmental/comfort standards. These results are
then compared with varied internal temperatures; this range of
temperatures is based on a wider interpretation of what might
be considered acceptable for comfort. Some previous work has
already indicated that such potential might exist [4] and in this
paper the consequential effect on energy consumption is now
considered. This may lead to better understanding of how to
manage energy consumption in transitional spaces by making
adjustments and alterations or choosing alternatives to existing
design, as well as taking note of peoples’ sensation and
expectations.
In practice, the levels of energy consumption in buildings
and transitional spaces may differ from those anticipated at the
design stage, which are frequently based on assumption of
annual average thermal requirements of the building. The
investigation therefore also highlights the different levels of
energy consumption resulting from irreversible design deci-
sions made at the outset. These initial evaluations arising from
modelling of notional buildings and from evidence on energy
consumption may lead to development of a more holistic
energy analysis in the future and an associated cost-benefit
appraisal.
3. Review of comfort issues
Contemporary research on thermal comfort has been well
documented over a period of more than three decades, but most
research has been carried out in relation to human thermal
response to stable environmental conditions experienced over
sustained periods of time. However, the realities of building
design and building use by occupants have created a rather
more complex situation in practice. Fanger’s research in this
field, commencing over 30 years ago [5] led to the specification
of international standards for thermal comfort [6], which were
widely adopted. Further practical implementation has occurred
such as in ASHRAE Standard 55 [7]. A consequence of this is
that an approach to thermal comfort which is perhaps best
applied to well-controlled, mainly air-conditioned, buildings
might be used as a benchmark for thermal design of all space
types and across many parts of the world with varying climates.
Some application of adaptive approaches in less intensively
conditioned spaces is now included in the standards which is
beneficial, however more development is needed.
In his research, Fanger measured air temperature, mean
radiant temperature, relative humidity, and air speed together
with activity and clothing levels for groups of subjects situated
in controlled environmental chambers. At the same time the
subjects rated their comfort sensation on the scale shown in
Table 1. Correlations and analyses were then carried out that
resulted in the derivation of a comfort equation that predicted
the average sensation of a group of human occupants exposed to
a given set of circumstances and also predicted the number who
would be dissatisfied. The predicted mean vote (PMV) and
predicted percentage dissatisfied (PPD) are terms now
commonly used as a measure of the expected average response
from a large group of people to a specific experienced set of
environmental conditions. It must be recognised that the kinds
of environment in which the initial studies from which the
equations were developed (and many subsequent ‘laboratory’
studies), were somewhat different to the temporary and
transitional nature of building foyers and entrance/circulation
spaces. The limitations to use are normally clearly stated in the
various comfort standards, and transition spaces would
normally fall outside their remit; however it is still necessary
for building designers to make decisions about how to service
such spaces and in the absence of other information they are
likely to adopt the general approach of the standards. It is clear
that work is needed therefore to help define modified standards
and to examine the potential to influence energy use.
The PPD index provides a measure of the percentage of
people who will be dissatisfied in thermal comfort and this is
related mathematically to the PMV. Based on the analysis, there
is no condition where everyone is predicted to experience
comfort conditions, and there is an assumption that there will
always be a small proportion (at least 5%) of people who cannot
be satisfied. However expectation of comfort in a transition
space is rather different to expectation of conditions in a well
controlled air conditioned office and many other environments.
As the interaction of the occupant with the thermal environment
may be transitory; it might be suggested that wider than normal
A. Pitts, J.B. Saleh / Energy and Buildings 39 (2007) 815–822 817
variations in thermal conditions should be investigated.
Reviews of recent research reveal a relative lack of information
and investigation for occupant response to conditions in
transitional spaces. Such spaces increase the dimensions of
complexities in maintaining comfort levels and the time spent
in transit such as to give more variable results for what is a more
variable environment.
In the recent standards the expectation is that conditions will
be maintained within �0.5 for the PMV, representing a limit of
10% PPD. In fact several variations of limit exist depending on
space categorisation—this is discussed by Olesen et al. [8] in
relation to energy performance of buildings. The three
categories they refer to show PMV limits of �0.2 for category
A;�0.5 for category B; and�0.7 for category C environments,
which already indicates a willingness in some circumstances to
relax the PMV limits.
The research of a number of authors has also considered
methods that take into account human adaptability in various
environments and climates [9]. Such work is linked to transition
environments since research on adaptive approaches might also
be used to justify assumptions about how people using, or
passing through, transition spaces over relatively short periods
of time might react or adapt. It might also be inferred from the
existing comfort standards that occupants are willing to tolerate
wider ranges of comfort in certain situations; for example in the
ASHRAE Standard it is stated that in adaptive environments,
such as naturally conditioned spaces, an acceptability level as
low as 80% (PPD = 20%) can be used. Indeed there are a
number of circumstances in both main standards [6,7] when an
increase of PPD by 5 or 10% might be allowed for.
As a result of this information one can infer an opportunity for
transition spaces whereby a wider band of the normal PMV could
be acceptable. A variation to a larger PPD might also be used or
perhaps the mathematical relationship between PMV and PPD
could be revised for transition spaces. The approach to be taken in
this study is therefore to compare two bands of PMV variation:
�0.5 (for a limit of 10% PPD) and�1.0 (equivalent to a limit of
26% PPD). The variation is introduced through modification of
air temperature in the transition space. It seems obvious to
determine if such considerations are likely to produce significant
reductions in energy requirements, which is the purpose of the
work reported in this paper. The opportunity to improve the
energy performance of buildings may thus exist as well as the
opportunity to examine how entrance and circulation spaces in
buildings are designed. Internal thermal environments might be
conceived of as a series of sequential experiences for occupants
moderating their environment between exterior and interior
conditions. In this way both improved comfort as well as
optimised energy performance can be achieved.
4. Methodology
The method of investigation has been to examine variations
in temperatures in building spaces according to the foregoing
discussion together with variations in building design. Initially,
four different notional building types have been considered
(identified as A, B, C and D in this study)—in each case a single
floor level, of area 200 m2, has been investigated but with
different plan variations. These were selected to show options
often developed at the design stage that are based on a
building’s cost budget. Floor and ceiling/roof heat flows have
been excluded from the analysis since it is anticipated that in
practice multi-storey buildings would be designed and their
impact only relevant to the highest and lowest floors. In the four
types variations in orientation have also been included to assess
heat gains and losses. This approach to layout is part of the key
information often defined in design briefs and used by designers
a rule of thumb to develop a building design.
Type A has a linear foyer transition space along the shorter
facade of a rectangular plan building; the four principal
orientations (north, east, south and west) are considered for the
direction in which this foyer may face. In all orientations it is
the shorter facade that faces the specified direction. Type B has
its foyer area set into the middle portion of the longer facade of
a similar rectangular building; again four orientations (north,
east, south and west) are analysed for the longer transition space
containing facade. Type C has a circulation corridor set across
the shorter axis of the same rectangular floor area building with
two variations considered (east–west corridor and north–south
corridor; in each case the corridor runs across the shorter
width). A modification on type C was considered as a further
option in which the ‘corridor’ transition space ran parallel to the
longer axis of the building. This variation was discounted
however since it produced very similar results and was also felt
to be less likely to be found in practice due to the narrowness of
the corridor. Type D has external perimeter corridor running
around the outside of the building; two orientations are
considered with the main (longer) facades running either east–
west or north–south.
Diagrams of the basic layouts of each type are shown in
Figs. 1–4; in each case the transition zone is shown in position
relative to the overall floor plan; the orientation variations are
derived by rotating the whole building (not just moving the
location of the transition space). A further variation of enclosed
transition space as an ‘atrium’ type space was considered but
has not been analysed as the impact on building energy
consumption would require more details of the building height/
number of storeys to be included. The spaces identified in each
model are labelled as the normally occupied and usable ‘main’
space; and the associated ‘transition’ space for purpose of
differentiation in the diagrams.
5. Thermal analysis
Many tools are available for the thermal analysis of
buildings and the choice made in this study was to utilise an
option that was matched to needs without involving very
complex and detailed building data input. The buildings being
assessed are simple in form and function with the major
influences being those of internal heat gain and external climate
(particularly the sun). It was assessed as necessary to have some
inclusion of dynamic affects but not appropriate to use complex
full dynamic simulation (it not being clear that the additional
data input would yield any more accurate answer and with the
Fig. 1. Type A floor layout shown with transition space on south facade. Fig. 3. Type C floor layout shown with east–west transition space corridor.
A. Pitts, J.B. Saleh / Energy and Buildings 39 (2007) 815–822818
negative effect of perhaps narrowing the range of applicability
of any conclusions drawn). The method chosen for investiga-
tion of energy flows and heating and cooling requirements was
a spreadsheet analysis using the admittance procedure based
upon techniques and data specified in the CIBSE Guide [10].
The implementation of the tool was one that had been
developed and tested extensively at the authors’ institution and
it has been used successfully in many practical evaluations of
building design proposals.
Regarding input data, the external temperatures and solar
radiation levels were taken from an example year of data
(hourly values) for the East Pennines area of the UK (this area is
typical of average national climate in the UK). The energy use
analysis was performed on monthly basis and the results
subsequently summed to provide yearly outputs of energy
requirements for heating and cooling.
A glazing ratio of 20% of wall area is assumed for the main
usable space, and 50% of the transitional space wall area. Wall
Fig. 2. Type B floor layout shown with transition space on south facade.
U values are set at 0.35 W m�2 8C�1; glazing U values are
2.2 W m�2 8C�1; the other main input parameters for use in the
model are shown in Table 2. Much of the input data are based on
standards set in the UK. Heat gains are incorporated from solar
sources (using the weather data for the site) and also from
occupants, lighting, and other electrical loads. The schedule of
occupancy and lighting and equipment use follows a traditional
daily pattern with reductions at shoulder periods, typical data is
shown in Table 3. The transitional space occupants are specified
to have different and varied behaviours compared to those in the
main usable space as they would be walking and standing (as
part of the process of entering, leaving or moving about the
building), compared to the sedentary behaviour normally found
in an office space. This is consistent with findings for an atrium
study of occupant comfort and behaviour in which the atrium
acted as a circulation zone [11].
The frequent opening of doors that connect to the outdoors
would allow greater air-change in the transitional space. Hence,
Fig. 4. Type D floor layout sown in east–west orientation with surrounding
corridor transition space.
Table 2
Building statistics: data for example single storey office
Building statistics Type A Type B Type C Type D
Total floor area (m2) 200 200 200 200
Building volume (m3) 600 600 600 600
Total gross walled area (m2) 180 180 180 180
Main occupied space floor area (m2) 180 180 180 144
Transitional space floor area (m2) 20 20 20 56
Main occupied space exposed facade area (m2) 138 165 168 0
Transitional space exposed facade area (m2) 42 15 12 180
A. Pitts, J.B. Saleh / Energy and Buildings 39 (2007) 815–822 819
in this investigation a higher air-change was used for the
transition zone (1 air-change per hour during unoccupied periods
and 2 air changes per hour during occupied hours) as compared to
the usable space at half an air change per hour (unoccupied) and
one (occupied). The affect of sophisticated controls have been
ignored. The figures have been chosen to be representative of
conditions to permit comparisons rather than being exact.
The variations in internal temperatures chosen for investiga-
tion were determined by consideration of the heat balance
equation and prediction of PMV. Values for PMV were
determined according to the algorithms specified by ASHRAE
and ISO organisations [6,7]. The main usable space was
assumed to have the following conditions which equate closely
to a PMV of 0.
� a
Ta
In
H
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
ir temperature = mean radiant temperature = 23 8C
� r elative humidity = 50%� m
ean air velocity = 0.1 m s�1� m
etabolic rate = 1.0 met� c
lothing level = 1.0 cloble 3
ternal heat gain data
our No. of occupants Lights (W m�2) Equipment (W m�2)
Main Transition Main Transition Main Transition
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
1 1 5 5 5 5
10 2 8 10 10 10
20 4 8 10 10 10
20 4 8 10 10 10
20 4 8 10 10 10
10 4 8 10 10 10
10 4 8 10 10 10
20 4 8 10 10 10
20 4 8 10 10 10
20 4 8 10 10 10
10 2 8 10 10 10
1 1 5 5 5 5
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
0 0 0 0 0 0
For the transition space alternative values were chosen for
several parameters. Firstly the air movement was assumed to
be slightly higher at 0.3 m s�1; this is consistent with findings
from research for enclosed transition type spaces (for instance
0.27 m s�1 [12]). The metabolic rate was also assumed to be
slightly higher at 1.4 mets to account for movement (again
consistent with previous studies [4]); clothing level was
assumed to be unchanged as there is no reliable evidence to
suggest an alternative value. Under these conditions a PMVof 0
results when air temperature and mean radiant temperature are
both set at 21 8C, this transitional space temperature is used for
the base case analysis. As can be seen this is 2 8C lower than
required in the main occupied space and this immediately
offers scope for reducing heating energy consumption; the
effect of this is not analysed here however as the main concern
is with the variation from widening of PMV bands in the
transition zones.
In order to carry out the comparisons the temperature in the
transition space was varied from the value above in the thermal
analyses. The variations were calculated on the basis of
assuming air temperature to be the same as mean radiant
temperature and that the adjustment in these values would be
matched to the range of PMV that was defined for consideration
earlier in the paper. Air temperature and mean radiant
temperature adjusted to either 18 or 24 8C gives a range in
PMVof approximately �0.5; adjusting to 16 and 26 8C gives a
range in PMV of �1.0. Therefore for the energy analysis the
values for internal temperature in the transition spaces were
varied to take the following values: 16, 18, 21, 24, and 26 8C,
representing PMVs of �1.0, �0.5, 0, +0.5 and +1.0.
A range of thermal analyses were thus completed: four the
four main building/transition space type variations; for both
heating and cooling energy requirements (and for main and
transition space areas separately); for the variations in
orientation; and for the five different temperatures in each case.
6. Results presentation
The charts shown in Figs. 5–12 illustrate the findings of the
analysis—an attempt has been made to allow comparison of
the most important issues, therefore in each diagram the
energy use is shown as a bar in which the ‘main’ and
‘transition’ space energy use is differentiated by the shading.
Energy consumption is shown on the Y-axis and a variety of
information to differentiate the various cases is shown along
the X-axis.
Fig. 5. Annual heating energy use for type A layout (transition space tem-
peratures of 21, 18 and 16 8C for each orientation).
Fig. 6. Annual cooling energy use for type A layout (transition space tem-
peratures of 21, 24 and 26 8C for each orientation).
Fig. 8. Annual cooling energy use for type B layout (transition space tem-
peratures of 21, 24 and 26 8C for each orientation).
Fig. 9. Annual heating energy use for type C layout (transition space tem-
peratures of 21, 18 and 16 8C for each orientation).
A. Pitts, J.B. Saleh / Energy and Buildings 39 (2007) 815–822820
Along the X-axis the bars are grouped in sets of three and in
every case the first of the three bars represents the base case; the
second the relaxation to PMV �0.5; and the third bar PMV
�1.0. The title to each chart makes clear the internal
temperatures associated with the three bars: 21, 18 and
16 8C for the three heating alternatives; and 21, 24 and 26 8C
Fig. 7. Annual heating energy use for type B layout (transition space tem-
peratures of 21, 18 and 16 8C for each orientation).
for the three cooling alternatives. Each grouping of three bars
indicates a different orientation for the transition space. As an
example of explanation, Fig. 5 shows the type A design
predicted heating energy use for the orientations of the
transition space (marked in order North, East, South and West)
and within each orientation there are three bars representing the
Fig. 10. Annual cooling energy use for type C layout (transition space
temperatures of 21, 24 and 26 8C for each orientation).
Fig. 11. Annual heating energy use for type D layout (transition space
temperatures of 21, 18 and 16 8C for each orientation).
Table 4
Percentage reduction in heating energy use (averaged for all orientations)
Transition space alone Effect on whole building
A. Pitts, J.B. Saleh / Energy and Buildings 39 (2007) 815–822 821
energy use for 21, 18 and 16 8C (sequentially) as the
temperature of the transition space.
7. Analysis
It should be understood at the outset that energy use in
buildings with significant or larger transition spaces is generally
higher than for buildings with smaller or less significant such
spaces; also that buildings without any such spaces (and which
are designed to be thermally efficient) can have the lowest
overall energy use of all. However transition spaces are an
inevitable element of modern buildings and methods for
optimal operation should be sought. Further, other roles might
be associated with transition spaces, such as modifying the
thermal expectation of people passing through them, and may
permit operation of other parts of buildings in more efficient
ways.
It is clear from the outset that the widening of the range of
temperatures used in the transition space analysis means that
the servicing systems are not required to operate at such high
intensity to produce comfortable conditions. As a result the
energy use is diminished; however it is important to be able to
gain some understanding in a more precise way. The charts
presented show reductions in energy use as the temperatures are
Fig. 12. Annual cooling energy use for type D layout (transition space
temperatures of 21, 24 and 26 8C for each orientation).
allowed to vary, though the reductions are more marked for
heating energy use than for cooling energy use. Tables of data
have been compiled to present the differences in energy use—
these are given as average values taking account of all
variations in orientation. The impact of different orientations
had some effect on cooling energy use due to increasing solar
gains (this can be seen most markedly in Fig. 6 for type A
layout), though there was only modest variation in heating
energy use with orientation.
Table 4 illustrates the energy use reductions predicted.
Savings of up to 35% of transition space heating are possible
(types A and D). Types B and C have less impact made by the
change in temperature, principally because the lower external
area of these types means their heat loss is already relatively
low. The impact on the whole building heating energy use is
lower for all types of layout but still quite significant with a
reduction of over 11% for type A and over 32% for type D (with
its total enclosure by the transition space).
Table 5 shows the averaged energy saving potential based on
cooling energy usage; reductions in all cases are in single
figures indicating less potential. Though the variations in
internal temperature are of a similar magnitude to the heating
situation, the energy flows into the space are dominated by solar
and internal gains.
An approach that could yield more advantageous reductions
in cooling energy use would be to omit the use of cooling
systems from the transition spaces entirely. Some compensation
for this lack of cooling could be gained if it was possible to
increase the ventilation rate through greater use of opening
windows and doors thus allowing the transition space to operate
in a more natural, free-running state during warm months. The
benefits of such an approach can be seen if overall energy use is
considered with cooling operating only in the main building
area—this is shown in Table 6. These data indicate significant
benefits of up to about 13% energy reduction when the main
building is surrounded by the transition space acting as a buffer.
18 8Ca 16 8Ca 18 8Ca 16 8Ca
Type A 22% 35.4% 7.1% 11.4%
Type B 19% 31.1% 2.6% 4.2%
Type C 18% 29.4% 4% 6.6%
Type D 22% 35.6% 20.2% 32.7%
a Transition space temperature.
Table 5
Percentage reduction in cooling energy use (averaged for all orientations)
Transition space alone Effect on whole building
24 8Ca 26 8Ca 24 8Ca 26 8Ca
Type A 4.5% 7.5% 1.3% 2.2%
Type B 3.2% 5.3% 0.5% 0.9%
Type C 2.8% 4.6% 0.4% 0.7%
Type D 5.1% 8.5% 3.7% 6.1%
a Transition space temperature.
Table 6
Summary of reductions in annual whole building energy use when cooling
systems used only in main part of building
Transition space lower temperature
18 8C 16 8C
Type A 1.5% 2.4%
Type B 0.5% 0.8%
Type C 0.4% 0.6%
Type D 8.3% 13.3%
A. Pitts, J.B. Saleh / Energy and Buildings 39 (2007) 815–822822
8. Conclusions
This study has investigated energy saving potential if more
flexible approaches to defining comfort in transition spaces can
be accommodated in building design. This has been tested for
four basic building layouts. The results clearly show substantial
opportunity for heating energy saving which can be quantified
in the region of 7% for the building as a whole, if transition
space temperatures are allowed to reduce by 3 8C below that
required for a PMV of 0, and 11% if a 5 8C reduction is
permitted. The reductions in cooling energy use are rather
smaller though still potentially significant, with savings up to
about 2%.
In terms of layout and orientation a few conclusions may be
drawn by reference to Tables 4–6: firstly that those types of
transition space that extend over the widest proportion of the
facade of the building have the most impact and the greatest
potential to reduce energy use. This can be seen by the results of
types A and D layout. Secondly, the orientation of the glazing
within any part of the building, but particularly the transition
space (because of its propensity for larger areas of glass) is very
important. Referring to Figs. 5–12 it appears that orientation
has little impact on layout types C and D however in both A and
B options cooling energy is lowest for transition spaces
orientated towards the North.
These results have potential practical significance to the
building industry, especially in the current climate of energy
price uncertainties. This type of information will be valuable at
stages of making the irreversible decisions about basic
orientation, layout and circulation with implications for future
operational costs. It is clear that more work is necessary
however to develop the concept and determine more clearly just
how wide a variation in thermal conditions occupants will find
acceptable for transition spaces. There is also a need to
incorporate findings with design and control of building
services systems and occupant use of buildings.
In summary several conclusions relevant to designers may
be inferred from the data and the foregoing analysis.
� I
t is plausible and reasonable to suggest that transition spacesof buildings can be operated to a wider temperature tolerance
than their accompanying interior occupied spaces and still
achieve thermal comfort for those people passing through.
� S
ignificant reductions in heating energy use can be achievedthrough the operation of transition spaces at lower than
normal temperatures.
� O
rientation has only a modest effect on heating energy use inbuildings with transition spaces.
� R
elatively minor reductions in cooling energy use arepossible for transition space buildings due to the impact of
heat gains.
� C
ooling energy requirements vary more significantly withorientation—a southerly orientation for transition spaces
reduces energy use in the main occupied space by the greatest
amount but results in the highest transition cooling energy use
(the reverse being true for northerly orientated transition
spaces).
� W
here transition spaces are used they have greatest effectwhere they give protection or buffering to the largest facade
areas (shown in this study as types A and D).
It is important for building designers to recognise the
important role of transition spaces in design and in energy use and
thus costs for buildings. Further detailed analyses are still
required however to gain a more holistic picture for the energy
consumption of common non-domestic building configurations
and this should be linked to more detailed studies of occupant
reaction in dynamic thermal situations. It would also be valuable
to investigate a wider range of building types and arrangements to
gain a more full understanding of this complex topic area.
References
[1] C. Chun, C. Kwok, A. Tamura, Thermal comfort in transitional spaces—
basic concepts: literature review and trial measurement, Building and
Environment 39 (10) (2004) 1187–1192.
[2] C. Chun, A. Tamura, Thermal comfort in urban transitional spaces,
Building and Environment 40 (2005) 633–639.
[3] S. Miura, Study on thermal environment and energy consumption in
underground shopping centres, Journal of Architectural Institute of Japan
430 (1991) 13–22.
[4] K. Jitkhajornwanich, A.C. Pitts, Interpretation of thermal responses of
four subject groups in transitional spaces of buildings in Bangkok,
Building and Environment 37 (2002) 1193–1204.
[5] P.O. Fanger, Thermal Comfort—Analysis and Applications in Environ-
mental Engineering, McGraw-Hill Book Company, United States, 1970.
[6] ISO, Ergonomics of the Thermal Environment—Analytical Determina-
tion and Interpretation of Thermal Comfort Using Calculation of the PMV
and PPD Indices and Local Thermal Comfort Criteria ISO 7730, Inter-
national Organization for Standardization, 2005.
[7] ASHRAE, Thermal environmental conditions for human occupancy, in:
ANSI/ASHRAE Standard 55-2004, American Society of Heating, Refrig-
erating and Air-Conditioning Engineers, Atlanta, GA, 2004.
[8] B.W. Olesen, O. Seppanen, A. Boerstra, Criteria for the indoor environ-
ment for energy performance of buildings—a new European standard, in:
Proceedings on Comfort and Energy Use in Buildings—Getting Them
Right, Windsor, UK, April, 2006.
[9] J.F. Nicol, M.A. Humphreys, Adaptive thermal comfort and sustainable
thermal standards for buildings, Energy and Buildings 34 (6) (2002) 563–
572.
[10] Chartered Institution of Building Services Engineers, CIBSE Guide A:
Environmental Design, CIBSE, London, UK, 2006.
[11] A. Pitts, E. Douvlou-Beggiora, Post-occupancy analysis of comfort in
glazed atrium spaces, in: Proceedings on Closing the Loop: Ways Forward
for Post-Occupancy Evaluation, Windsor, UK, 2004.
[12] J. Nakano, K. Sakamoto, T. Iino, S. Tanabe, Thermal comfort conditions in
train stations for transit and short-term occupancy, in: Proceedings on
Comfort and Energy Use in Buildings—Getting Them Right, Windsor,
UK, April, 2006.