plumbing fixture rough-in schedule ltdapr 11, 2019  · 8. seal all floor, wall, and roof...

8
PLUMBING SYMBOL LIST SYMBOL: DESCRIPTION: PIPE SERVING FIXTURE ON FLOOR ABOVE (EXAMPLE: FD = FLOOR DRAIN) FD PITCH PIPE IN DIRECTION UNION/FLANGE BALANCING VALVE (NUMBER INDICATES GPM) GPM CHECK VALVE REDUCER - REFERENCE SPECIFICATION FOR CONCENTRIC/ECCENTRIC AND FOT/FOB PIPE DOWN PIPE UP OR UP/DOWN DIRECTION OF FLOW IN PIPE SHUTOFF VALVE NORMALLY OPEN COLD WATER CW HOT WATER HW HOT WATER CIRCULATING HWC SANITARY DRAINAGE SAN VENT V NOT ALL SYMBOLS MAY APPLY. SAFETY/RELIEF VALVE VACUUM BREAKER THERMOMETER WITH WELL (FILLED TYPE) PUMP SERVICE WATER - POTABLE W PIPE CONTINUATION OSAN SANITARY DRAINAGE - OIL LADEN P/T PLUG PUMPED DISCHARGE PD PLUMBING ABBREVIATION KEY CO CLEANOUT FLOOR CLEANOUT FCO FLOOR DRAIN FD HOSE BIBB HB I.E. INVERT ELEVATION (FOR REFERENCE ONLY) LAVATORY LAV MOP BASIN MB MIXING VALVE MV URINAL UR WATER CLOSET WC WATER HEATER WH YARD CLEANOUT YCO DRINKING FOUNTAIN DF VENT THROUGH ROOF VTR BFP BACKFLOW PREVENTER ABBR: DESCRIPTION: TYPICAL TYP OIL SEPARATOR OS HUB DRAIN HD PLAN OR DETAIL NUMBER PLAN OR DETAIL NAME PLAN OR DETAIL SCALE 1 VIEW NAME 1/8" = 1'-0" 1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL N O R H T INDICATES DIRECTION OF TRUE NORTH VIEW KEY NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE) LINE TYPE KEY: NEW WORK BY OTHER CONTRACTOR (LIGHT SOLID LINE) NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR (DARK LONG DASHED LINE) MECHANICAL GENERAL NOTES: THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO PLUMBING AND MECHANICAL. 1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT. 2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES. 3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS. 4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS. 5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS. 6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN. 7. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH. 8. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE. 9. CAULK ALL PIPE PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS. 10. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC. 11. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES. 12. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR STARTERS, SWITCHES, AND DISCONNECTS. 13. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT. 14. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS. 15. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO EACH OTHER. 16. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN / HUB DRAIN. 17. ELECTRIC HEAT IS PROVIDED TO THE BUILDING TO MAINTAIN A MINIMUM SPACE TEMPERATURE TO PREVENT PIPES FROM FREEZING AND IS NOT INTENDED FOR SPACE COMFORT. 1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT. 2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN. 3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES. 4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.3874 5. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO PLUMBING FIXTURES. 6. ALL PLUMBING PIPING, FIXTURES, ETC. SHALL COMPLY WITH ILLINOIS PLUMBING CODE. PLUMBING GENERAL NOTES: TEMPERATURE CONTROLS CONTRACTOR T.C.C. CIVIL CONTRACTOR C.C. PLUMBING CONTRACTOR P.C. MECHANICAL CONTRACTOR M.C. ELECTRICAL CONTRACTOR E.C. CONTRACTOR ABBREVIATION KEY ABBR: DESCRIPTION: PLUMBING SHEET INDEX P0.0 PLUMBING COVERSHEET P1.0 SITE PLAN - PLUMBING P2.0 RESTROOM BUILDING PLANS - PLUMBING P2.1 STORAGE BUILDING PLANS - PLUMBING P3.0 PLUMBING DETAILS P4.0 PLUMBING SCHEDULES P4.1 PLUMBING SCHEDULES P5.0 PLUMBING RISER DIAGRAM 815-254-0091 www.uplanddesign.com Park Planning and Landscape Architecture 24042 Lockport St, Plainfield, Illinois 60544 ltd 320 W. Jackson Avenue Naperville, IL 60540 Phone: 630-848-5000 CIVIL ENGINEER / SURVEYOR / STRUCTURAL ENGINEER Engineering Resource Associates 3s701 West Avenue, Suite 150 Warrenville, IL 60555 ARCHITECT Charles Vincent George Architects 1245 E Diehl Rd, Suite 101 Naperville, Iliinois 60563 AQUATIC Innovative Aquatic Design, LLC (WT Group) 2675 Pratum Avenue Hoffman Estates, Illinois 60192 MECHANICAL / ELECTRICAL ENGINEER IMEG 1100 Warrenville Road, Suite 400W Naperville, Illinois 60563 IRRIGATION FRS Design Group, LLC 167 South Lexington Street Spring Green, Wisconsin 53588 SHEET TITLE PROJECT TEAM Wolf's Community Park Development 3252 Wolf's Crossing Road PROJECT LANDSCAPE ARCHITECT DRAW / REVISION SHEET NUMBER Project Number 620 © Copyright 2019 Upland Design Ltd. Bid / Permit Resubmittal 15APR2019 14MAR2019 Issue for Permit RS RS Crossing P0.0 PLUMBING COVERSHEET REFERENCE SCALE IN INCHES 0 1 2 3 PROJECT # Illinois Design Firm Registration # 184007637 - 0014 IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOW N THEREON. SAID DRAW ING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP. 1100 WARRENVILLE RD, SUITE 400W NAPERVILLE, IL 60563 630.527.2320 FAX: 630.527.2321 www.imegcorp.com 18003960.00 IN THE SCHEDULE SHALL DICTATE THE ROUGH-IN SIZE. 3. SIZES SHOWN ARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED TO VERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" INCH UNLESS NOTED OTHERWISE. 2. 1/2" CW AND HW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE. BRANCH PIPING 1. SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINIMUM OF 2". NOTES: HOSE BIBB 3/4" - - - - FLOOR DRAIN (FD-3) - - 6" 3" - FLOOR DRAIN (FD-2) - - 2" 1-1/2" - FLOOR DRAIN (FD-1, HD-1) - - 4" 2" - EMERGENCY SHOWER / EYEWASH 1-1/2" 1-1/4" 2" 1 1/2" - DRINKING FOUNTAIN 1/2" - 1 1/2" 1 1/4" NOTE 1 & 2 MOP BASIN 3/4" 3/4" 3" 1 1/2" - LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2 SHOWER 1/2" 1/2" 2" 1 1/2" NOTE 1 & 2 URINAL 1" - 2" 1 1/2" (FLUSH VALVE - SYPHON JET) WATER CLOSET 1" - 4" 2" (FLUSH VALVE) FIXTURE DESCRIPTION DOMESTIC C.W. (NOTE 3) DOMESTIC H.W. (NOTE 3) SANITARY (NOTE 3) VENT (NOTE 3) REMARKS PLUMBING FIXTURE ROUGH-IN SCHEDULE

Upload: others

Post on 12-Nov-2020

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

PLUMBING SYMBOL LIST

SYMBOL: DESCRIPTION:

PIPE SERVING FIXTURE ON FLOOR ABOVE(EXAMPLE: FD = FLOOR DRAIN)FD

PITCH PIPE IN DIRECTION

UNION/FLANGE

BALANCING VALVE (NUMBER INDICATES GPM)GPM

CHECK VALVE

REDUCER - REFERENCE SPECIFICATIONFOR CONCENTRIC/ECCENTRIC AND FOT/FOB

PIPE DOWN

PIPE UP OR UP/DOWN

DIRECTION OF FLOW IN PIPE

SHUTOFF VALVE NORMALLY OPEN

COLD WATERCW

HOT WATERHW

HOT WATER CIRCULATINGHWC

SANITARY DRAINAGESAN

VENTV

NOT ALL SYMBOLS MAY APPLY.

SAFETY/RELIEF VALVE

VACUUM BREAKER

THERMOMETER WITH WELL (FILLED TYPE)

PUMP

SERVICE WATER - POTABLEW

PIPE CONTINUATION

OSAN SANITARY DRAINAGE - OIL LADEN

P/T PLUG

PUMPED DISCHARGEPD

PLUMBING ABBREVIATION KEY

CO CLEANOUT

FLOOR CLEANOUTFCO

FLOOR DRAINFD

HOSE BIBBHB

I.E. INVERT ELEVATION (FOR REFERENCE ONLY)

LAVATORYLAV

MOP BASINMB

MIXING VALVEMV

URINALUR

WATER CLOSETWC

WATER HEATERWH

YARD CLEANOUTYCO

DRINKING FOUNTAINDF

VENT THROUGH ROOFVTR

BFP BACKFLOW PREVENTER

ABBR: DESCRIPTION:

TYPICALTYP

OIL SEPARATOROS

HUB DRAINHD

PLAN OR DETAIL NUMBER

PLAN OR DETAIL NAME

PLAN OR DETAIL SCALE

1VIEW NAME1/8" = 1'-0"

1 INDICATES NOTE USED TO DESCRIBE ADDITIONAL INFORMATION ABOUT WORK REQUIRED, SPECIFIC TO THE SHEET AND/OR DETAIL

NO R HT

INDICATES DIRECTION OF TRUE NORTH

VIEW KEY

NEW WORK BY THIS CONTRACTOR (DARK SOLID LINE)

LINE TYPE KEY:

NEW WORK BY OTHER CONTRACTOR (LIGHT SOLID LINE)

NEW WORK UNDERFLOOR OR UNDERGROUND BY THIS CONTRACTOR (DARK LONG DASHED LINE)

MECHANICAL GENERAL NOTES:THESE NOTES APPLY TO ALL MECHANICAL SHEETS AND TRADES, INCLUDING BUT NOT LIMITED TO PLUMBING AND MECHANICAL.

1. DRAWINGS SHOWING LOCATIONS OF EQUIPMENT, DUCTWORK, PIPING, ETC. ARE DIAGRAMMATIC AND MAY NOT ALWAYS REFLECT EXACT INSTALLATION CONDITIONS. DRAWINGS SHOW THE GENERAL ARRANGEMENT OF DUCTWORK, PIPING, EQUIPMENT, ETC., AND MAY NOT INCLUDE ALL OFFSETS AND FITTINGS REQUIRED FOR COMPLETE INSTALLATION. THE DRAWINGS SHALL BE FOLLOWED AS CLOSELY AS ACTUAL BUILDING CONSTRUCTION AND THE WORK OF OTHERS WILL PERMIT.

2. DO NOT SCALE DRAWINGS. VERIFY ALL DIMENSIONS AND CLEARANCES FROM ARCHITECTURAL, STRUCTURAL, SUBMITTALS, AND OTHER APPROPRIATE DRAWINGS OR PHYSICALLY AT SITE. REVIEW ALL DRAWINGS, INCLUDING THOSE OF OTHER TRADES.

3. COORDINATE ALL WORK WITH ALL OTHER TRADES PRIOR TO INSTALLATION TO PROVIDE CLEARANCES REQUIRED FOR OPERATION, MAINTENANCE, CODE COMPLIANCE, AND TO VERIFY NON-INTERFERENCE WITH OTHER WORK. DO NOT FABRICATE PRIOR TO VERIFICATION OF NECESSARY CLEARANCES FOR ALL TRADES. BRING ANY INTERFERENCES OR CONFLICTS TO THE ATTENTION OF THE ARCHITECT/ENGINEER BEFORE PROCEEDING WITH FABRICATION OR EQUIPMENT ORDERS.

4. REVIEW SPACE REQUIREMENTS OF EQUIPMENT SPECIFIED OR SUBSTITUTED AND MAKE REASONABLE ACCOMMODATIONS IN LAYOUT AND POSITIONING TO PROVIDE PROPER ACCESS.

5. ANY CHANGES REQUIRED TO ELIMINATE CONFLICTS OR THAT RESULT FROM A FAILURE TO COORDINATE SHALL BE MADE BY THE CONTRACTOR WITHOUT ADDITIONAL COST OR EXPENSE TO OTHERS.

6. EACH CONTRACTOR IS RESPONSIBLE FOR ALL COSTS ASSOCIATED WITH ELECTRICAL CHANGES REQUIRED FOR EQUIPMENT PROPOSED THAT DIFFERS FROM THE BASIS OF DESIGN.

7. EACH CONTRACTOR IS RESPONSIBLE FOR DAMAGE CAUSED BY THEIR ACTIONS TO WALLS, FLOORS, CEILINGS, AND ROOFS. THE CONTRACTOR WHOSE WORK CAUSES DAMAGE IS RESPONSIBLE FOR PATCHING TO MATCH ORIGINAL CONSTRUCTION, FIRE RATING, AND FINISH.

8. SEAL ALL FLOOR, WALL, AND ROOF PENETRATIONS AIRTIGHT WHERE CONDUITS, PIPING, AND DUCTS PENETRATE. PENETRATIONS THROUGH EXTERIOR WALLS AND ROOF SHALL BE SEALED AIRTIGHT WITH WATERPROOFING MATERIALS RECOMMENDED BY MANUFACTURER FOR OUTDOOR USE.

9. CAULK ALL PIPE PENETRATIONS OF FULL HEIGHT NON-FIRE RATED WALL, PARTITION, FLOOR, AND ROOF ASSEMBLIES. THIS IS ESSENTIAL TO PREVENT NOISE TRANSMISSION FROM ONE ROOM TO ANOTHER AND TO PROVIDE THE DESIRED NC LEVELS WITHIN ROOMS.

10. EQUIPMENT SIZES AND SERVICE CLEARANCE REQUIREMENTS VARY AMONG DIFFERENT MANUFACTURERS. CONSULT APPROVED SHOP DRAWINGS FOR EQUIPMENT SIZES AND REQUIRED SERVICE CLEARANCES. COORDINATE WITH LAYOUT OF EQUIPMENT PADS, PIPING, DUCTWORK, ETC.

11. DO NOT BLOCK EQUIPMENT SERVICE CLEARANCES. 12. MAINTAIN MINIMUM 3'-6” CLEARANCE IN FRONT OF ALL ELECTRICAL PANELS, MOTOR

STARTERS, SWITCHES, AND DISCONNECTS.13. PROVIDE CONCRETE EQUIPMENT PAD FOR ALL FLOOR MOUNTED EQUIPMENT. PAD SHALL

EXTEND MINIMUM 6” BEYOND ALL SIDES OF EQUIPMENT.14. DO NOT SUPPORT EQUIPMENT, PIPING, OR DUCTWORK FROM METAL DECKING OR OTHER

NON-STRUCTURAL BUILDING ELEMENTS. ANCHORS EMBEDDED IN CONCRETE SHALL BE CRACKED CONCRETE APPROVED IN ACCORDANCE WITH SPECIFICATIONS.

15. ALIGN TEMPERATURE SENSORS WITH LIGHT SWITCHES AND WHEN IN CLOSE PROXIMITY TO EACH OTHER.

16. PIPE DRAIN LINES FROM EQUIPMENT TO NEAREST FLOOR DRAIN / HUB DRAIN.17. ELECTRIC HEAT IS PROVIDED TO THE BUILDING TO MAINTAIN A MINIMUM SPACE

TEMPERATURE TO PREVENT PIPES FROM FREEZING AND IS NOT INTENDED FOR SPACE COMFORT.

1. THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

2. CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR A COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

3. CONTRACTOR SHALL VERIFY THAT FIXTURES SUPPLIED ARE APPROVED PER ALL APPLICABLE STATE, LOCAL AND GOVERNING AUTHORITIES.

4. ALL FIXTURES SHALL CONFORM TO FEDERAL ACT S.38745. REFER TO THE PLUMBING ROUGH-IN SCHEDULE FOR THE SIZES OF BRANCH PIPES TO

PLUMBING FIXTURES.6. ALL PLUMBING PIPING, FIXTURES, ETC. SHALL COMPLY WITH ILLINOIS PLUMBING CODE.

PLUMBING GENERAL NOTES:

TEMPERATURE CONTROLS CONTRACTORT.C.C.

CIVIL CONTRACTORC.C.

PLUMBING CONTRACTORP.C.

MECHANICAL CONTRACTORM.C.

ELECTRICAL CONTRACTORE.C.

CONTRACTOR ABBREVIATION KEY

ABBR: DESCRIPTION:

PLUMBING SHEET INDEXP0.0 PLUMBING COVERSHEET

P1.0 SITE PLAN - PLUMBING

P2.0 RESTROOM BUILDING PLANS - PLUMBING

P2.1 STORAGE BUILDING PLANS - PLUMBING

P3.0 PLUMBING DETAILS

P4.0 PLUMBING SCHEDULES

P4.1 PLUMBING SCHEDULES

P5.0 PLUMBING RISER DIAGRAM

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for PermitRS

RS

Crossing

P0.0

PLUMBINGCOVERSHEET

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

IN THE SCHEDULE SHALL DICTATE THE ROUGH-IN SIZE.

3. SIZES SHOWN ARE MINIMUMS. SIZES SHOWN ON THE DRAWING THAT ARE LARGER THAN THE SIZES LISTED

TO VERTICAL RISE-DROP SHALL BE A MINIMUM OF 3/4" INCH UNLESS NOTED OTHERWISE.

2. 1/2" CW AND HW APPLIES ONLY TO THE FINAL VERTICAL RISE-DROP TO EACH FIXTURE. BRANCH PIPING

1. SANITARY RISER UP IN WALL TO FIXTURE SHALL BE A MINIMUM OF 2".

NOTES:

HOSE BIBB 3/4" - - - -

FLOOR DRAIN (FD-3) - - 6" 3" -

FLOOR DRAIN (FD-2) - - 2" 1-1/2" -

FLOOR DRAIN (FD-1, HD-1) - - 4" 2" -

EMERGENCY SHOWER / EYEWASH 1-1/2" 1-1/4" 2" 1 1/2" -

DRINKING FOUNTAIN 1/2" - 1 1/2" 1 1/4" NOTE 1 & 2

MOP BASIN 3/4" 3/4" 3" 1 1/2" -

LAVATORY 1/2" 1/2" 1 1/4" 1 1/4" NOTE 1 & 2

SHOWER 1/2" 1/2" 2" 1 1/2" NOTE 1 & 2

URINAL 1" - 2" 1 1/2" (FLUSH VALVE - SYPHON JET)

WATER CLOSET 1" - 4" 2" (FLUSH VALVE)

FIXTURE DESCRIPTIONDOMESTIC

C.W.(NOTE 3)

DOMESTICH.W.

(NOTE 3)

SANITARY(NOTE 3)

VENT(NOTE 3)

REMARKS

PLUMBING FIXTURE ROUGH-IN SCHEDULE

Page 2: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

2

P2.0

2

P2.1

1

P2.1

1

P2.0

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for PermitRS

RS

Crossing

P1.0

SITE PLAN - PLUMBING

NO R HT

1" = 60'-0"1 SITE PLAN - PLUMBING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

Page 3: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

A

B

C

D

1 2

UTILITY / STORAGE

105

SPLASH PAD MECH.

106

WOMEN

104

MEN

103

MEN

101

MEN

102

3" W UP

FCO

FD

LAVWC WC

FD

LAV

FCO

FCO

FD

FD

LAV

LAV

UR

WC

WCWC

FCO

FD

WC

WC

FD

FCO

4"SAN

4"SAN

WC

2" V UP

2" V UP

FCO

2" V UP

1-1/2" V UP

1-1/2" V UPFD

FD

HD

4"SAN4"SAN

2" V UP2" V UP

2" V UP

2" V UP

4"SAN

1-1/2" V UP

DF

2"S

AN

MB

1 1/2" V UP

HD

2" PD UP

SP-1

2" V DN

HD

2" V UP

FD

3" V UP

REFER TO CIVIL PLANS FOR CONTINUATION.

YCO

HD4"S

AN

FD

FD

4"ST

YCO

REFER TO CIVIL PLANS FOR CONTINUATION.

UR

2" V UP(TYP.3)

1-1/2" V UP

2" V UP(TYP.5)

COORDINATE UNDERGROUND PIPING WITH RESERVOIR.

2"V

2"V

1" CW TO DRINKING FOUNTAINS

1" CW UP

4"SAN

4"SAN

4"SAN

FCO 4"SAN

4"SAN

BY

P.C

.B

Y C

.C.

BY

P.C

.B

Y C

.C.

BY

P.C

.B

Y C

.C.

REFER TO CIVIL PLANS FOR CONTINUATION.

REFER TO CIVIL PLANS FOR CONTINUATION.

BY P.C. BY C.C.

I.E. SAN = -3.5'

I.E. SAN = -3.09'

I.E. SAN = -2.98'

I.E. SAN = -2.98'

3"W

1"C

W

3" V UP

ESE

A

B

C

D

1 2

UTILITY / STORAGE

105

SPLASH PAD MECH.

106

WOMEN

104

MEN

103

MEN

101

MEN

102

BFP-1

HB-1 3" W DN

WC-2

WC-1

UR-2

UR-1

FD-1

FD-1

WC-1

WC-1

WC-1

L-1

WC-2 L-2

DF-1

HB-1

WC-2L-2

FD-1

FD-1

FD-1

FCO-1

FCO-1

FCO-1

2"V

3" V UP TO 5" VTR

FD-3

3" V DN

L-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

2" V DN

2 1/2"CW

HD-1

2" V DN

WHA-1

1 1/2"CW

WHA-1

HB-2

FCO-11-1/2" V DN

1-1/2" V DN

SH-1SH-1

FCO-1

FCO-1

FD-1

0.5

2" V DN

WHA-1

WHA-1

WHA-1

2"CW3/4"HW3/4"HWC

2"CW3/4"HW3/4"HWC

1"HW

1"HW

1 1/4"HW

FD-2FD-2

2"CW

2"CW

SHUTOFF VALVE, BALANCING VALVE AND CHECK VALVE SHALL BE LOCATED WITHIN PLUMBING CHASE.

2"V

1 1/4"HW

2" V DN WC-2

2" V DN

2" V DN

1 1/2" V DN

MB-1

2" V DN

2" PD DN

2" PD TO HUB DRAIN WITH 2" AIR GAP.

SH-2

FD-2

FD-2

SH-2

HD-1

HD-1

YCO-1

HD-1

1-1/2" V DN

2 1/2"CW

1 1/2"HW3/4"HWC

1

2

2" V DN(TYP.5)

YCO-1

1 1

/2"H

W

2"CW

ET-1WH-1

PROVIDE 2" WATER METER AS REQUIRED PER ILLINOIS PLUMBING CODE 890 APPENDIX A TABLE O.

REFER TO 2/P3.0 FOR FOR WATER HEATER DETAIL.

COORDINATE ALL FIXTURES/PIPING IN SPLASH PAD ROOM WITH SPLASH PAD DRAWINGS.

1" CW DN TO SPLASH PAD FRESH WATER FILL PIPE. COORDINATE LOCATION WITH SPLASH PAD EQUIPMENT. REFER TO 6/P3.0 FOR WATER LEVEL CONTROLLER DETAIL.

REFER TO 4/P3.0 FOR YARD CLEANOUT DETAIL. (TYP.)

REFER TO 1/P3.0 FOR PIPE SUPPORT DETAIL. (TYP.)

REFER TO 3/P3.0 FOR LAVATORY MIXING VALVE DETAIL. (TYP.)

1"CW

1" CW DN TO DRINKING FOUNTAINS

CP-1

1"CW

WHA-1

HB-2

HB-2

WHA-1

3/4"CW3/4"CW

WHA-1

WHA-1

HB-2

HB-2

DS-1

DS-1

3

3

MV-1

MV-1

MV-1

MV-1

3/4"HWC

1 1/2"HW

COORIDNATE ALL PIPING WITH DUCTWORK WITHIN CHASE. PIPING SHALL BE ROUTED TO ALLOW PERSONNEL ACCESS UP AND DOWN THE CHASE. ALL SHUTOFF VALVES SHALL BE ACCESSIBLE.

2"CW

3/4"CW

1 1/4"V

2"CW

3/4"CW

FCO-1

2" V DN

2" V DN

2" V DN

3/4" CW

FINISH FLOORFINISH FLOOR

0.00'

4

4

2 1/2"CW

3"CW

1 1/2"V

3"V

2"V3"V

3" V DN

3"V

3" V UP TO 5" VTR

2"V

ESE-1

3/4" CW & 3/4" HW TO SERVE MOP BASIN

PROVIDE CHECK VALVE AND BALANCING VALVE IN HWC LINE WITHIN "UTILITY/STORAGE 105" SPACE. BALANCE THE BALANCING VALVE TO 0.5 GPM.

REFER TO 7/P3.0 FOR EMERGENCY SHOWER & EYEWASH DETAIL DETAIL.

0.5

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for PermitRS

RS

Crossing

P2.0

RESTROOM BUILDINGPLANS - PLUMBING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

GENERAL SHEET NOTES :

1. ALL DOMESTIC WATER PIPING SHALL BE 3/4" UNLESS NOTED OTHERWISE.

2. HWC PIPING SHALL CONNECT WITHIN 2 FEET OF HW CONNECTION TO FIXTURE.

NO R HT

1/4" = 1'-0"1

RESTROOM BUILDING PLANS -PLUMBING - UNDERFLOOR

NO R HT

1/4" = 1'-0"2

RESTROOM BUILDING PLANS -PLUMBING

KEYNOTES:

1. ROUTE DOMESTIC WATER PIPING SERVING FAMILY RESTROOMS TO BE FULLY DRAINABLE, SO SPACES CAN BE WINTERIZED. SLOPE PIPING TO LOW POINT ON SOUTH END WITHIN THE PLUMBING CHASE. PROVIDE NORMALLY CLOSED SHUTOFF VALVE AND CAPPED THREADED CONNECTION.

2. ROUTE DOMESTIC WATER PIPING TO ALLOW SYSTEM TO BE FULLY DRAINABLE SO THE BUILDING CAN BE WINTERIZED. SLOPE PIPING TO LOW POINT. PROVIDE NORMALLY CLOSED SHUTOFF VALVE AND CAPPED THREADED CONNECTION.

3. CONNECT DOWNSPOUT WITH CAST IRON BOOT. ROUTE UNDERGROUND AND CONNECT TO SITE STORM PIPING. REFER TO ARCHITECTURAL AND CIVIL PLANS FOR ADDITIONAL INFORMATION.

4. PROVIDE CHECK VALVE AND BALANCING VALVE IN HWC LINE. BALANCE THE BALANCING VALVE TO 0.5 GPM. ALL VALVES SHALL BE LOCATED WITHIN PLUMBING CHASE.

#

Page 4: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

STORAGE

101

HD-1

BFP-1

2"W2" W DN

YCO-1

3/4"CW

1

3" V DN

3" V UP TO 5" VTR

ROUTE 3" V UP ALONG THE WALL TO MEZZANINE SPACE.

ROUTE VENT TIGHT TO STRUCTURE IN MEZZANINE SPACE TO VTR.

TD-1

FCO-1

2" V DN

3/4"CW

WH-2

MB-1

1 1/2"V DN

HB-1

TRANSISITON TO 3/4" DOWNSTREAM OF WATER METER.

REFER TO 5/P3.0 FOR INSTANTANEOUS WATER HEATER DETAIL.

3"V

ROUTE CW TIGHT TO WALL.

DS-1

DS-1

2

2

FINISH FLOORFINISH FLOOR

0.00'

WHA-1

2" V DN

2"V

2"V

PROVIDE 3/4" WATER METER AS REQUIRED PER ILLINOIS PLUMBING CODE 890 APPENDIX A TABLE O.

3"V

3"V

3"V DN

MISC. STORAGE

7

STORAGE

101

HD

YCO

4"S

AN

REFER TO CIVIL PLANS FOR CONTINUATION.

OS-1

3" V UP

FCO

4"O

SA

N

2" V UP

4"SAN

TD

MB

3"SAN

1 1/2"V UP

2" W UP

2"WBY

P.C

.B

Y C

.C.

BY

P.C

.B

Y C

.C.

I.E. SAN = -3.5'

I.E. SAN = -3.18'

2" V UP

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for PermitRS

RS

Crossing

P2.1

STORAGE BUILDINGPLANS - PLUMBING

NO R

HT

1/4" = 1'-0"2

STORAGE BUILDING PLANS -PLUMBING

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

NO R

HT

1/4" = 1'-0"1

STORAGE BUILDING PLANS -PLUMBING - UNDERFLOOR

KEYNOTES:

1. ROUTE DOMESTIC WATER PIPING TO ALLOW SYSTEM TO BE FULLY DRAINABLE SO THE BUILDING CAN BE WINTERIZED. SLOPE PIPING TO LOW POINT AT WATER ENTRANCE. PROVIDE NORMALLY CLOSED SHUTOFF VALVE AND CAPPED THREADED CONNECTION.

2. CONNECT DOWNSPOUT WITH CAST IRON BOOT. ROUTE UNDERGROUND AND CONNECT TO SITE STORM PIPING. REFER TO ARCHITECTURAL AND CIVIL PLANS FOR ADDITIONAL INFORMATION.

#

Page 5: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

THREADED ROD.(TYP.)

OVERSIZE HANGER TO ALLOW LONGITUDINAL PIPE EXPANSION AND PIPE INSULATION TO PASS THROUGH UNBROKEN. (TYP.)

UNI-STRUT OR EQUIVALENT

HIGH DENSITY INSULATION INSERT OR STEEL SADDLE FILLED WITH INSULATION. (TYP.)

THREADED ROD.(TYP.)

PIPE INSULATION(TYP.)

INSULATION SHIELD (TYP.)

INSULATION SHIELD

INSTALL CLAMP ON ALL PIPES LESS THAN 4"Ø

THREADED ROD

INSULATION

CLEVIS HANGER

HIGH DENSITY INSULATION INSERT OR STEEL SADDLE FILLED WITH INSULATION.

DRAIN

EXPANSION TANK ET-1 HW

CW

THERMOMETER IN WELL

A.S.M.E. PRESSURE AND TEMPERATURE RELIEF VALVE

VACUUM RELIEF VALVE. WATTS N36 OR EQUAL.

PIPE DIRECTLY OVER HUB DRAIN

HOUSEKEEPING PAD

UNION (TYP.)

CIRCULATING PUMP CP-1

HWC

GRADE

BLACKTOP OR CLEAN TAMPED EARTH.

ALL AROUND

MINIMUM 9"

FLEXIBLE PVC COUPLING WITH STAINLESS STEEL BAND CLAMPS. SUITABLE FOR UNDERGROUND INSTALLATION. INDIANA SEAL, MODEL NO. 156-88 OR EQUIVALENT.

NEOPRENE GASKET

LINE OF UNDISTURBED EARTH.

8" SAN PIPE

1/8 BEND.

CLEANOUT ASSEMBLY. SEE PLUMBING MATERIAL LIST.

CONCRETE SLAB (5") REINFORCED WITH WIRE MESH OR 3/8" DIAMETER RODS 6" CENTERS EACH WAY. SLOPE AWAY FROM CLEANOUT ASSEMBLY TOP.

EXTEND CONCRETE PAD 6" BEYOND THE LINE OF UNDISTURBED EARTH.

SAND BACKFILL OR CLEAN TAMPED EARTH.

FROST SLEEVE

PREDICTED DEPTH OF FROST.

.

FROST SLEEVE TO BE 6" BELOW PREDICTED DEPTH OF FROST, .

6" TO 12" ABOVE SEWER

-OR-

COUNTERTOP LAVATORY

PROVIDE SEPARATE CW AND HW SUPPLIES TO LAVATORY IF APPLICABLE.ANGLE STOP

ROUTE 1/2" TEMPERED WATER BACK IN TO WALL CAVITY.

PROVIDE HOT AND COLD WATER ANGLE STOPS ON VALVE INLETS.

MOUNT MIXING VALVE UNDER LAVATORY, IN ENCLOSURE.

3/4

" C

W

3/4

" H

W

3/4" HWC

WATER HEATER

CHECK VALVE

CW

STRAINER

NOTES:1. INSTALL STRAINER UPSTREAM OF WATER HEATER.

HW140 TO FIXTURE

TOP OF RESERVOIR

SHUTOFF VALVE

SHUTOFF VALVE

SLOW CLOSE NORMALLY OPEN SOLENOID VALVE

SHUTOFF VALVE

1" CW

1" CW

6" M

IN.8" OPENING

IN GRATING FOR FILL

1" CW

TO DOMESTIC MAIN. REFER TO PLAN FOR MORE INFORMATION.

SHOWER HEAD

EYEWASH BOWL

PUSH FLAG HANDLE

SECURE FLANGE TO FLOOR

36"

82"

-96"

1 1/2" TEMPERED WATER

SHOWER AND EYEWASH IDENTIFICATION SIGNS

FLOOR

SEE FLOOR PLANS FOR CONTINUATION.

WALL

SEE FLOOR PLANS FOR CONTINUATION.

SEE FLOOR PLANS FOR CONTINUATION.

1 1/2" CW

1-1/4" HW

EMERGENCY MIXING VALVE

LOCKABLE SHUT OFF VALVE

2" SAN

CHECK VALVE

TEMPERATURE GAUGE

SH

OW

ER

H

AN

DLE

48"

MA

X.

P-TRAP

NOTES:

1. EYEWASH AND SHOWER PERFORMANCE AND ROUGH-IN SHALL MEET THE CURRENT VERSION OF ANSI Z358.1.

2. GENERAL CONTRACTOR SHALL PAINT AREA AROUND AND BEHIND SHOWER/EYEWASH A BRIGHT COLOR AS DIRECTED BY THE ARCHITECT.

1-1/2" V

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for PermitRS

RS

Crossing

P3.0

PLUMBING DETAILS

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

NO SCALE1 PIPE SUPPORT DETAIL

NO SCALE2 WATER HEATER DETAIL

NO SCALE4 YARD CLEANOUT DETAIL

NO SCALE3 LAVATORY MIXING VALVE DETAIL

NO SCALE5 INSTANTANEOUS WATER HEATER DETAIL

NO SCALE6 WATER LEVEL CONTROLLER DETAIL

NO SCALE7 EMERGENCY SHOWER & EYEWASH DETAIL

Page 6: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

THE SYMBOLS AND THE MATERIAL LIST ARE FOR THE CONVENIENCE OF THE CONTRACTOR. CONTRACTOR SHALL VERIFY QUANTITIES AND FURNISH ALL MATERIALS REQUIRED FOR FULLY OPERATIONAL SYSTEMS, WHETHER SPECIFIED OR NOT.

CATALOG NUMBERS SHALL NOT BE CONSIDERED COMPLETE, BUT ARE GIVEN AS AN AID TO THE CONTRACTOR AND TO INDICATE THE QUALITY REQUIRED. CONTRACTOR IS RESPONSIBLE FOR COMPLETE DESCRIPTION OF MATERIAL ON THESE DRAWINGS AND IN THE SPECIFICATIONS BEFORE ORDERING. THE DESCRIPTION OF THE MATERIAL TAKES PRECEDENCE OVER THE CATALOG NUMBER. THE FIRST MANUFACTURER LISTED IS THE BASIS OF DESIGN.

PLUMBING MATERIAL LIST

BFP-1

BACK FLOW PREVENTER - REDUCED PRESSURE ZONE, LEAD FREE BRONZE OR STAINLESS STEEL CONSTRUCTION, SIZE SAME AS PIPE, NON-CORROSIVE INTERNAL PARTS, STAINLESS STEEL SPRINGS, DIFFERENTIAL PRESSURE RELIEF VALVE BETWEEN SPRING-LOADED CHECK VALVES, SHUT-OFF VALVES ON INLET AND OUTLET OF UNIT, BALL STYLE SHUTOFF VALVES FOR 3/4"-2" AND GATE STYLE VALVES FOR 2 1/2"-10", AIR GAP DRAIN FITTING, TEST PORTS WITH SHUT-OFF VALVES, RATED FOR 175 PSI AT 33°F TO 140°F, 15 PSI (MAXIMUM) PRESSURE DROP AT 10 FPS, FACTORY TESTED, ALL PARTS TO BE SERVICEABLE WITHOUT REMOVING UNIT FROM LINE, APPROVED BY USC FCCC & HR, AWWA C511-92, ASSE 1013, IAPMO AND SBCCI LISTED.

MOUNT WITHIN 60" OF FINISHED FLOOR. PROVIDE AND INSTALL BRONZE OR EPOXY COATED STRAINER UPSTREAM OF EACH UNIT AND ADDITIONAL VALVE UPSTREAM OF EACH STRAINER. FLOW PRESSURE DROP CURVES SHALL BE SUBMITTED.

ACCEPTABLE MANUFACTURERS: APOLLO (RPLF4A), WATTS (LF919 / 994), WILKINS (975XL2 / 375AST)

PLUMBING MATERIAL LIST (CONTINUED) PLUMBING MATERIAL LIST (CONTINUED)

FD-1

FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 6" ROUND, 4" BOTTOM OUTLET, FLASHING COLLAR, SURFACE MEMBRANE CLAMP, DEEP SEAL TRAP.

ACCEPTABLE MANUFACTURERS: ZURN (Z-415), SMITH (2005), WADE (1100), JOSAM (30000), WATTS (FD-100), MIFAB (F1100), SUN (FD1000)

HD-1

HUB DRAIN - OPEN SITE HUB DRAIN, CAST IRON BODY, SEDIMENT BUCKET, 4" BOTTOM OUTLET, DEEP SEAL TRAP.

ACCEPTABLE MANUFACTURERS: ZURN (Z-211-S-Y), SMITH (2005-HUB), SUN (FD1000 W/S100-U)

L-1

LAVATORY - MODULAR WASH STATION, SOLID SURFACE BOWL WITH TWO WASH STATIONS, WALL MOUNT WITH STAINLESS STEEL MOUNTING FRAME, PREPIPED FOR SINGLE HOT, COLD, AND DRAIN CONNECTION, INFRARED SENSOR ACTIVATED FAUCET WITH ASSE 1070 RATED THERMOSTATIC MIXING VALVE, COMBINATION CHECK VALVE AND STOP ASSEMBLY WITH REMOVABLE STRAINER, 3/8" NPT CONNECTIONS, FLEXIBLE STAINLESS STEEL SUPPLY LINES, GRID STRAINER, TAILPIECE, 1-1/2" 17 GAUGE CAST BRASS P-TRAP.

ELECTRICAL REQUIREMENTS - 110V PLUG-IN TRANSFORMER AND SOLENOIDS

ANCHOR TO WALL PER MANUFACTURER'S REQUIREMENTS. PROVIDE 29" CLEARANCE FROM FLOOR TO BOTTOM OF APRON IN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. TOP OF BASIN RIM SHALL BE AT 34" (MAXIMUM) ABOVE FLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS. MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 1992 AND AMSE/ANSI STANDARD A112.18.1M. VERIFY COLOR SELECTION WITH ARCHITECT.

ACCEPTABLE MANUFACTURERS: BRADLEY (SS-2N)

UR-1

URINAL - ACCESSIBLE, WALL MOUNTED, WHITE VITREOUS CHINA, FLUSH VALVE TYPE, WASHOUT ACTION, ELONGATED RIM, EXTENDED SIDE SHIELDS, 3/4" TOP SPUD, 2" OUTLET.

FLUSH VALVE - EXPOSED, SENSOR OPERATION, HARD WIRED, 0.5 GALLON PER FLUSH, 11-1/2" ROUGH-IN, CHROME-PLATED, 3/4" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, NON-HOLD-OPEN HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW, MANUAL OVER-RIDE, RANGE ADJUSTMENT SCREW, BEAM DEFLECTOR, CHROME-PLATED COVER PLATE WITH TAMPER-PROOF SCREWS, TRANSFORMER AND LOW VOLTAGE WIRING, TRANSFORMER CAPABLE OF OPERATING UP TO 10 UNITS, LOW VOLTAGE WIRING FROM TRANSFORMER TO EACH FLUSH VALVE, CHLORAMINE RESISTANT MATERIALS, 3-YEAR WARRANTY.

ELECTRICAL REQUIREMENTS - 120VAC INPUT

ACCESSORIES - SUPPORT CARRIER WITH TOP AND BOTTOM BEARING PLATES.

MOUNT WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF BOWL RIM SHALL BE AT 17" (MAXIMUM) ABOVE FLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS. FLUSH HANDLE SHALL BE AT 44" (MAXIMUM) ABOVE FLOOR AND OPERATE WITH NO GREATER THAN 5 LB FORCE IN COMPLIANCE WITH LATEST ADA STANDARDS. VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.

ACCEPTABLE MANUFACTURERS: URINAL - AMERICAN STANDARD (6590.001), KOHLER (K-4991-ET), SLOAN (SU-1006/SU-1005), GERBER (27-780), TOTO (UT447), ZURN (Z5750)

FLUSH VALVE - SLOAN (ROYAL 186 ES-S)

DF-1

DRINKING FOUNTAIN - WALL HUNG, SUITABLE FOR OUTDOOR USE, ADA COMPLIANT WITH MATCHING STAINLESS STEEL APRON INSTALLED UNDER UPPER UNIT, BI-LEVEL STAINLESS STEEL ROUND BASINS WITH STAINLESS STEEL FINISH, PERFORATED DRAINS,STREAM PROJECTOR WITH PROTECTIVE HOOD, PUSH BAR OR LEVER OPERATING CONTROLS ON FRONT AND SIDES, BUILT-IN FLOW REGULATOR, PLASTIC P-TRAP ASSEMBLY, MOUNTING ACCESSORIES, TANK DRAIN AND ANGLE STOPS, COMPLIANT TO LATEST ANSI A117.1 AND ADA STANDARDS. UNIT SHALL COMPLY WITH FEDERAL ACT S.3874. UNIT COLOR SHALL BE TEXTURED PYRITE.

BOTTLE FILLING STATION - UNIT MOUNTED, STAINLESS STEEL CONSTRUCTION AND FINISH, INTEGRAL DRAIN, MANUAL SHUTOFF.

WATER SYSTEM SHALL BE OF LEAD FREE CONSTRUCTION. TANK SHALL BE TESTED TO 125 PSIG.

ORIFICE SHALL BE AT 36" (MAXIMUM) ABOVE FINISHED FLOOR ON LOWER UNIT AND 40" ABOVE FINISHED FLOOR ON UPPER UNIT. BOTTOM OF LOWER UNIT SHALL BE AT 27" ABOVE FINISHED FLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS.

PROVIDE WITH CUT OFF VALVE AND LOW POINT DRAIN, SEASONAL COVER.

ACCEPTABLE MANUFACTURERS: MOST DEPENDABLE (10485 WMSS)

ET-1

EXPANSION TANK - WELDED BLACK STEEL CONSTRUCTION, ASME STAMPED, GUARANTEED AIRTIGHT AND LEAKPROOF, STAINLESS STEEL SYSTEM CONNECTION, HEAVY DUTY BUTYL DIAPHRAGM AND RIGID POLYPROPYLENE LINER MECHANICALLY BONDED TO TANK TO PROVIDE A 100% NON-CORROSIVE WATER RESERVOIR, DIAPHRAGM AND LINER SHALL BE APPROVED FOR USE IN POTABLE WATER SYSTEMS, ALL WETTED COMPONENTS OF FDA APPROVED MATERIALS. PROVIDE STANDARD SCHRADER AIR VALVE FOR FIELD CHARGING. TANK SHALL COMPLY WITH FEDERAL ACT S.3874.

MINIMUM TANK VOLUME TO BE 6.4 GALLONSMINIMUM ACCEPTING VOLUME TO BE 3.2 GALLONS

TANK SHALL HAVE A WORKING TEMPERATURE OF 200°F AND A WORKING PRESSURE OF 125 PSIG. FACTORY PRE-CHARGED FOR SHIPPING. FIELD CHARGE TANK TO 55 PSIG.

ACCEPTABLE MANUFACTURERS: AMTROL (THERM-X-TROL), B&G (PT), ELBI (DT), FLEXTRON (FLEXTROL), TACO (PAX SERIES), WATTS (DETA), WESSELS (TX)

FCO-1

FLOOR CLEANOUT - ADJUSTABLE, CAST IRON HOUSING, ANCHOR FLANGE, TAPERED THREAD PLUG, SECURED NICKEL BRONZE TOP. TOP STYLE SHALL MATCH FLOOR FINISH AS FOLLOWS:

TILE OR TERRAZZO - ROUND RECESSED TOP

ACCEPTABLE MANUFACTURERS: ZURN (Z1400), JOSAM (55000), MIFAB (C1100), SMITH (4000), WADE (6000), WATTS (CO-200)

CP-1

CIRCULATING PUMP - BRONZE CONSTRUCTION, PERMANENTLY LUBRICATED SEALED BEARINGS, MECHANICAL SEAL, OIL LUBRICATED, OPEN DRIP-PROOF NON OVERLOADING MOTOR WITH THERMAL OVERLOAD PROTECTION, FLANGED CONNECTIONS, RATED FOR 125 PSIG AT 225°F, UL LISTED.

2.5 GPM @ 15 FEET OF HEAD. MOTOR SHALL BE 1/12 HP OPERATING AT 2650 RPM.

ACCEPTABLE MANUFACTURERS: B&G (PL SERIES), TACO (OO SERIES), GRUNDFOS (UP SERIES)

AQUASTAT - LINE VOLTAGE, ADJUSTABLE SETTING OF 90-180°F WITH STRAP-ON REMOTE SENSOR BULB, UL LISTED. PROVIDE WITH TRANSFORMER IF REQUIRED. INSTALL PER MANUFACTURERS INSTRUCTIONS.

ACCEPTABLE MANUFACTURERS: HONEYWELL, WHITE-RODGERS, JOHNSON CONTROLS, SAME AS PUMP MANUFACTURER

ELECTRICAL REQUIREMENTS - 115V-1 PHASE (HARD-WIRE)

TD-1

TRENCH DRAIN - MODULAR, PRE-SLOPED, POLYESTER FIBERGLASS CHANNEL, 6" WIDE, HEAVY DUTY CAST IRON GRATE WITH A DIN 1433 CLASS E RATING OR HIGHER, INTERLOCKING ENDS, HEAVY DUTY STEEL FRAME AND ANCHORING DEVICE, CATCH BASIN WITH 4" BOTTOM OUTLET, 14 FEET LONG.

ACCEPTABLE MANUFACTURERS: ZURN (Z806), SMITH (9812), ACO (FG200)

HB-2

HOSE BIBB - FOR INDOOR USE, BRASS CONSTRUCTION, STANDARD FINISH, VACUUM BREAKER, 3/4" MALE HOSE THREAD, METAL WHEEL HANDLE, ASSE 1011 LISTED AND APPROVED.

MOUNT AT 18" ABOVE FINISHED FLOOR UNLESS NOTED OTHERWISE ON DRAWINGS.

ACCEPTABLE MANUFACTURERS: WOODFORD (24), CHICAGO FAUCET (293), ACORN (8121), PRIER (C-135AS), T&S BRASS (B-0736), MIFAB (MHY-90)

HB-1

HOSE BIBB - FREEZELESS WALL HYDRANT, BRASS VALVE BODY AND SEAT, STANDARD FINISH, NON-FERROUS METAL STEM, AUTOMATIC DRAINING, VACUUM BREAKER, 3/4" MALE HOSE THREAD, WALL CLAMP, CONCEALED IN FLUSH MOUNTED LOCKABLE WALL BOX, KEY OPERATED, ASSE 1019 OR 1052 LISTED AND APPROVED.

VERIFY NUMBER OF KEY OPERATORS TO BE PROVIDED WITH OWNER. BOX COVER AND HYDRANT SHALL USE A COMMON KEY. MOUNT AT 18" ABOVE GRADE UNLESS NOTED OTHERWISE ON DRAWINGS.

ACCEPTABLE MANUFACTURERS: PRIER (C-634BX), WOODFORD (B67), ZURN (Z1300), WATTS (HY-725), MIFAB (MHY-20), SMITH (5509QT), WADE (8700)

UR-2

URINAL - WALL MOUNTED, WHITE VITREOUS CHINA, FLUSH VALVE TYPE, WASHOUT ACTION, ELONGATED RIM, EXTENDED SIDE SHIELDS, 3/4" TOP SPUD, 2" OUTLET.

FLUSH VALVE - EXPOSED, SENSOR OPERATION, HARD WIRED, 0.5 GALLON PER FLUSH, 11-1/2" ROUGH-IN, CHROME-PLATED, 3/4" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, NON-HOLD-OPEN HANDLE, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW, MANUAL OVER-RIDE, RANGE ADJUSTMENT SCREW, CHROME-PLATED COVER PLATE WITH TAMPER-PROOF SCREWS, TRANSFORMER AND LOW VOLTAGE WIRING, TRANSFORMER CAPABLE OF OPERATING UP TO 10 UNITS, LOW VOLTAGE WIRING FROM TRANSFORMER TO EACH FLUSH VALVE, CHLORAMINE RESISTANT MATERIALS, 3-YEAR WARRANTY.

ELECTRICAL REQUIREMENTS - 120VAC INPUT

ACCESSORIES - SUPPORT CARRIER WITH TOP AND BOTTOM BEARING PLATES.

MOUNT WITH CARRIER BOLTED SECURELY TO FLOOR. TOP OF BOWL RIM SHALL BE AT 22" ABOVE FLOOR. VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.

ACCEPTABLE MANUFACTURERS: URINAL - AMERICAN STANDARD (6590.001), KOHLER (K-4991-ET), SLOAN (SU-1006/SU-1005), GERBER (27-780), TOTO (UT447), ZURN (Z5750)

FLUSH VALVE - SLOAN (ROYAL 186 ES-S)

SP-1

SUMP PUMP - SIMPLEX SUBMERSIBLE, SINGLE-STAGE, CENTRIFUGAL, END-SUCTION PUMP, STAINLESS STEEL FASTENERS, GUARDS AND HANDLES, UL LISTED.

CASING: CAST IRON, INTEGRAL SUPPORT FEET, MINIMUM 2" VERTICAL DISCHARGE.IMPELLER: CAST IRON STATICALLY AND DYNAMICALLY BALANCED, SEMIOPEN NONCLOG DESIGN, KEYED AND SECURED TO SHAFT, PASSES 1/2" SOLIDS MINIMUM.SHAFT: STAINLESS STEEL WITH FACTORY SEALED, GREASE-LUBRICATED SLEEVE OR BALL BEARINGS, CARBON AND CERAMIC SEAL.MOTOR: 3450 RPM, OIL OR AIR-FILLED, HERMETICALLY SEALED WITH AUTO THERMAL OVERLOAD PROTECTION, THREE CONDUCTOR WATERPROOF POWER CABLE OF SUFFICIENT LENGTH.

CAPACITY : 100 GPM, 10 FEET OF HEAD.

ELECTRICAL REQUIREMENTS - 1-1/2 HP, 230 VOLTS, 1 PHASE

CONTROLS - WALL MOUNTED NEMA 1 ENCLOSURE, SIMPLEX (3) FLOAT. RUN LIGHT, TEST-OFF-AUTO AND DISCONNECTING MEANS FOR PUMP, HIGH WATER ALARM WITH HORN, STROBE, SILENCING BUTTON AND DRY CONTACTS FOR ALARM AND PUMP STATUS, UL LISTED. FLOATS SHALL BE MERCURY-FREE.

FLOAT SHALL BE INSTALLED JUST ABOVE THE RESOVIOR OPERATING LEVEL. REFER TO SPLASH PAD DRAWINGS.

ACCEPTABLE MANUFACTURERS:

PUMP - WEIL (2443), ZOELLER (SERIES 180), BARNES (EH), HYDROMATIC (SPD), GOULDS (WE)

CONTROLS - SAME AS PUMP MANUFACTURER

SH-2

SHOWER VALVE - SINGLE HANDLE PRESSURE BALANCED MIXING FAUCET, BRASS OR BRONZE CONSTRUCTION, POLISHED CHROME CAST METAL LEVER HANDLE, WASHERLESS DESIGN, OFF-COLD-HOT TEMPERATURE RANGE INDICATOR DIAL, INTEGRAL CHECK STOPS, ADJUSTABLE TEMPERATURE LIMIT STOP, ASSE 1016 LISTED.

ACCESSORIES - CHROME-PLATED PLASTIC SHOWERHEAD WITH SWIVEL BALL JOINT, CHROME-PLATED BRASS ARM AND FLANGE.

INSTALL BOTTOM OF SHOWERHEAD AT 72" ABOVE FINISHED FLOOR. MAXIMUM FLOW TO BE 2.0 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005 AND ASME/ANSI STANDARD A112.18.1M. SET SAFETY LIMIT STOP TO 110 DEGREE F DISCHARGE.

COORDINATE WITH SHOWER BASIN ON ARCHITECTURAL PLANS.

ACCEPTABLE MANUFACTURERS:

SHOWER VALVE - SYMMONS (BP-56-1), AMERICAN STANDARD (T372.240), CHICAGO FAUCETS (1900), DELTA (R10000-UNWS/T13H132), LEONARD (4500 SERIES), POWERS (P910-J1)

FD-2

FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 5" ROUND, 2" BOTTOM OUTLET, FLASHING COLLAR, SURFACE MEMBRANE CLAMP, DEEP SEAL TRAP.COORDINATE WITH SHOWER BASIN ON ARCHITECTURAL PLANS.

ACCEPTABLE MANUFACTURERS: ZURN (Z-415), SMITH (2005), WADE (1100), JOSAM (30000), WATTS (FD-100), MIFAB (F1100), SUN (FD1000)

DS-1

DOWNSPOUT BOOT- 5"x4"x24" DOWNSPOUT BOOT, DURA-COATED CAST IRON BODY AND STRAP WITH 1/4" ø HOLES FOR FLAT HEAD BOLTS.

CONNECT TO GUTTER. PROVIDE WITH CLEANOUT ACCESS WITH PLUG.

REFER TO FLOOR PLAN FOR QUANTITY OF DOWNSPOUTS. PROVIDE ONE (1) DOWNSPOUT FOR SHELTER AREA (NOT SHOWN ON FLOOR PLAN). REFER TO ARCHITECTURAL PLAN FOR MORE INFORMATION.

ACCEPTABLE MANUFACTURERS: ZURN (Z191) OR APPROVED EQUAL

FD-3

FLOOR DRAIN - CAST IRON BODY, NICKEL BRONZE ADJUSTABLE TOP, 8" ROUND, 6" BOTTOM OUTLET, FLASHING COLLAR, SURFACE MEMBRANE CLAMP, DEEP SEAL TRAP.COORDINATE WITH SHOWER BASIN ON ARCHITECTURAL PLANS.

ACCEPTABLE MANUFACTURERS: ZURN (Z-415), SMITH (2005), WADE (1100), JOSAM (30000), WATTS (FD-100), MIFAB (F1100), SUN (FD1000)

ESE-1

EMERGENCY SHOWER & EYE/FACE WASH - COMBINATION UNIT, FREESTANDING, FLOOR MOUNTED WITH TOP INLET, PLASTIC SHOWER HEAD, BRASS/BRONZE STAY OPEN BALL VALVE, STAINLESS STEEL/ALUMINUM PULL ROD, PLASTIC BOWL WITH HINGED DUST COVER, PLASTIC SPRAY HEADS WITH CAPS AND RETAINING CHAINS/STRAPS, BRASS SUPPLY ARMS, BRASS/BRONZE STAY OPEN BALL VALVE, METAL FLAG, INTEGRAL FLOW CONTROL FITTINGS, GALVANIZED STEEL SUPPLY PIPING AND FITTINGS, UNIVERSAL IDENTIFICATION SIGN, ANSI Z358.1-2004 COMPLIANT.

MINIMUM FLOW RATE OF SHOWER SHALL BE 20 GPM AT 30 PSI. MINIMUM FLOW RATE OF EYE/FACE WASH SHALL BE 3.0 GPM AT 30 PSI. ACTIVATION TIME SHALL BE 1 SECOND OR LESS. BRASS/BRONZE PIPING, FITTINGS, AND VALVES SHALL BE CHROME-PLATED OR CHEMICAL-RESISTANT POWDER COATED.

MOUNT SHOWER HEAD BETWEEN 82"-96" AND PULL ROD AT MAXIMUM 69" ABOVE FINISH FLOOR. EYE/FACE WASH OUTLET HEADS SHALL BE 33-45" ABOVE FINISH FLOOR.

MIXING VALVE - THERMOSTATIC MIXING VALVE FOR EMERGENCY SHOWER OR COMBINATION SHOWER/EYEWASH FIXTURE, BRONZE BODY CONSTRUCTION, COLD WATER BYPASS, INLET AND OUTLET THERMOMETERS, COMBINATION CHECK STOPS OR SEPARATE SUPPLY CHECK VALVES AND SHUT OFF VALVES, OUTLET ISOLATION VALVE, MOUNTING BRACKET. SUPPLY SHUT OFF VALVES SHALL BE LOCKED OPEN OR CONTRACTOR SHALL PROVIDE A LOCKING CABINET TO PREVENT UNAUTHORIZED CLOSURE. CABINET SHALL BE SURFACE MOUNTED 18 GAUGE STAINLESS STEEL WITH 16 GAUGE LOCKING DOOR TO ENCLOSE VALVE, INLET CHECK STOPS, OUTLET THERMOMETER, AND OUTLET VALVE. DUAL THERMOSTATIC MIXING AND PRESSURE REGULATING VALVE TO DELIVER 25 GPM OF TEMPERED WATER (60-100 DEGREE F) WITH 10 PSI PRESSURE DIFFERENTIAL. UNIT SHALL BE ASSE 1071 LISTED AND APPROVED. VALVE SHALL COMPLY WITH FEDERAL ACT S.3874.

ACCEPTABLE MANUFACTURERS: EMERGENCY SHOWER & EYE/FACE WASH - GUARDIAN (G1900 SERIES), BRADLEY (S19314 SERIES), ACORN SAFETY (S13/S23 SERIES), HAWS (8300 SERIES), SPEAKMAN (SE-1200 SERIES), ENCON

MIXING VALVE - LEONARD (TM-LF), ACORN CONTROLS (ET71 SERIES), ARMSTRONG (Z358), BRADLEY (S19), HAWS (9201H), LAWLER (911), POWERS (ETV400), OR PRE-PACKAGED WITH EMERGENCY SHOWER FROM SAME MANUFACTURER.

PLUMBING MATERIAL LIST (CONTINUED)

L-2

LAVATORY - ACCESSIBLE, WALL MOUNTED, WHITE VITREOUS CHINA, 21-7/16"x17-3/4", 4" HIGH CONTOURED BACKSPLASH, CENTER HOLE FOR FAUCET, DRILLED FOR CONCEALED ARM CARRIER.

LAVATORY TRIM - SENSOR ACTIVATED MIXING FAUCET, HARD-WIRED, BRASS CONSTRUCTION, CHROME-PLATED FINISH, CONVENTIONAL SPOUT WITH AERATOR, SINGLE HOLE, PERFORATED GRID STRAINER WITH 1-1/4" 17 GAUGE TAILPIECE, SOLID BRASS SOLENOID WITH BUILT-IN FILTER, WATERPROOF CONNECTORS AND CABLE, UL APPROVED TRANSFORMER.

ELECTRICAL REQUIREMENTS - 120 VAC INPUT

MOUNT CONTROLS IN WATERPROOF VANDAL-RESISTANT ENCLOSURE BELOW LAVATORY. PROVIDE TRANSFORMER WITH CABLE EXTENSIONS (AS REQUIRED) OR PLUG-IN TRANSFORMER. COORDINATE LOCATION WITH ELECTRICAL CONTRACTOR. SELECT TRANSFORMER TO SERVE MAXIMUM NUMBER OF ELECTRONIC VALVES TO REDUCE AMOUNT OF TRANSFORMERS.

MAXIMUM FLOW TO BE 0.5 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005 AND ASME/ANSI STANDARD A112.18.1M. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874. PROVIDE RESTRICTIVE DEVICE AS REQUIRED.

PROGRAMMING UNIT - HAND HELD, CAPABLE OF CHANGING SETTINGS, RUNNING DIAGNOSTICS, AND SCAN FAUCETS WITH ISSUES. PROVIDE ONE CONTROLLER.

INSULATION KIT - PRE-MANUFACTURED FOR P-TRAP, STOP VALVES AND SUPPLY LINES.

MIXING VALVE - POINT-OF-USE ANTI-SCALD THERMOSTATIC MIXING VALVE FOR TEMPERED WATER CONTROL, ALL BRONZE/BRASS CONSTRUCTION, ROUGH FINISH, THREADED INLETS, TAMPER RESISTANT SETPOINT, 3/8" COMPRESSION INLETS AND OUTLETS, COLD WATER BYPASS IF USED WITH MIXING FAUCET.

CABINET - SURFACE MOUNTED 18 GAUGE PAINTED STEEL CABINET WITH 16 GAUGE LOCKING DOOR TO ENCLOSE VALVE, INLET STOPS, OUTLET THERMOMETER, AND OUTLET VALVES.

0.5 GPM OUTPUT. UNIT TO MIX 140 DEGREE F HOT WATER SUPPLY AND 40 DEGREE F COLD WATER SUPPLY FOR 110 DEGREE F OUTLET.

UNIT SHALL BE ASSE 1070 LISTED AND APPROVED. VALVE SHALL COMPLY WITH FEDERAL ACT S.3874.

ACCESSORIES - QUARTER-TURN 3/8" CHROME PLATED HEAVY BRASS ANGLE SUPPLY LOOSE KEY STOPS, CHROME PLATED SOFT COPPER SUPPLY LINES, DRAIN & OFFSET TAILPIECE, 1-1/4" 20 GAUGE CAST BRASS P-TRAP, SUPPORT CARRIER.

MOUNT LAVATORY WITH SUPPORT CARRIER BOLTED SECURELY TO FLOOR. TOP OF RIM SHALL BE AT 34" (MAXIMUM) ABOVE FLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS. PROVIDE 29" MINIMUM CLEARANCE FROM FLOOR TO BOTTOM OF APRON IN COMPLIANCE WITH LATEST ANSI A117.1 AND ADA STANDARDS. ARMAFLEX WITH TAPE IS NOT ACCEPTABLE IN LIEU OF INSULATION KIT.

ACCEPTABLE MANUFACTURERS: LAVATORY - AMERICAN STANDARD (0955.001EC), KOHLER, SLOAN, TOTO, ZURN

LAVATORY TRIM - DELTA (590T0), AMERICAN STANDARD (775B.205/PK00.HAC), CHICAGO FAUCET (116.706.AB.1), HYDROTEK (H-2603C-LR), MOEN (8302), SLOAN (ETF-610), SPEAKMAN (S-8800), ZURN (Z6913-XL)

MIXING VALVE - WATTS (LFUSG-B), LAWLER (TMM-1070T), ACORN CONTROLS (ST70), APOLLO (34DLF), LEONARD (170-BP-LF), POWERS (LFE480), SLOAN (MIX-135-A), SYMMONS (7-210), WILKINS (ZW3870XLT)

INSULATION KIT - TRUEBRO (LAV-GUARD), BROCAR PRODUCTS (TRAP WRAP), MCGUIRE (PROWRAP), PLUMBEREX (PRO-EXTREME)

MB-1

MOP BASIN - PRECAST TERRAZZO, 24"x24"x12", STAINLESS STEEL INTEGRAL DRAIN WITH REMOVABLE STRAINER, 3" OUTLET, CONTINUOUS STAINLESS STEEL CAP ON ALL EDGES.

TRIM - EXPOSED TWO HANDLE MIXING FAUCET, BRASS CONSTRUCTION, CHROME-PLATED FINISH, SINGLE WING HANDLES, 1/4 TURN CERAMIC DISC CARTRIDGE, 3/4" HOSE THREAD SPOUT WITH INTEGRAL VACUUM BREAKER, WALL BRACE, PAIL HOOK, CHECK STOPS OR INLINE CHECK VALVES TO PREVENT THERMAL CROSSOVER. FAUCET SHALL COMPLY WITH FEDERAL ACT S.3874.

ACCESSORIES - MOP HANGER, HOSE AND HOSE BRACKET, DEEP SEAL TRAP

ACCEPTABLE MANUFACTURERS: MOP BASIN - FIAT (TSB), MURDOCK (TSH), CREATIVE INDUSTRIES (MC), WILLIAMS (SB)

TRIM - DELTA (28C2383), AMERICAN STANDARD (8344.012), CHICAGO FAUCETS (897-CP), MOEN (8124), SPEAKMAN (SC-5812), SYMMONS (S-2490), ZURN (Z841M1-XL)

OS-1

OIL SEPARATOR - GRAVITY TYPE, FABRICATED STEEL HOUSING, EPOXY COATING, REMOVABLE BAFFLE AND SEDIMENT BUCKET, ADJUSTABLE GRAVITY DRAW OFF, DOUBLE VENT CONNECTIONS, VISIBLE DEEP SEAL TRAP, PROVIDE WITH H-20 RATED COVER.

CAPACITY SHALL BE 10 GPM, 21-1/4"x11-1/2"x13-1/4" DEEP OVERALL, 2" INLET/OUTLET, TWO (2) 1-1/2" DRAW OFF, AND TWO (2) 3" VENT CONNECTIONS.

ACCEPTABLE MANUFACTURERS: SMITH (8500 SERIES), WADE (W-5400), ZURN (Z-1188), JOSAM (6000 SERIES), ROCKFORD (OS SERIES), MIFAB (MI-O), SCHIER (SOS SERIES)

MV-1

MIXING VALVE - POINT-OF-USE ANTI-SCALD THERMOSTATIC MIXING VALVE ARRANGEMENT FOR TEMPERED WATER CONTROL, ALL BRONZE/BRASS CONSTRUCTION, ROUGH FINISH, UNION/THREADED INLETS WITH STRAINERS, COMBINATION CHECK STOPS OR SEPARATE SUPPLY CHECK VALVES AND SHUT OFF VALVES.

CABINET - SURFACE MOUNTED 18 GAUGE PAINTED STEEL CABINET WITH 16 GAUGE LOCKING DOOR TO ENCLOSE VALVE, INLET STOPS, OUTLET THERMOMETER, AND OUTLET VALVES.

RATED FOR 2.0 GPM OUTPUT MAXIMUM AT 5 PSI DIFFERENTIAL AND 0.5 GPM OUTPUT MINIMUM. UNIT TO MIX 140 DEGREE F HOT WATER SUPPLY AND 40 DEGREE F COLD WATER SUPPLY FOR 110 DEGREE F OUTLET.

UNIT SHALL BE ASSE 1070 LISTED AND APPROVED. VALVE SHALL COMPLY WITH FEDERAL ACT S.3874.

ACCEPTABLE MANUFACTURERS: LEONARD (170-LF/270-LF/370-LF), ACORN CONTROLS (ST7069), APOLLO (34BLF), BRADLEY (S59 SERIES), LAWLER (310/570), POWERS (SERIES LFLM495), SYMMONS (MAXLINE SERIES), WATTS (LFMMV), WILKINS (ZW1070XL)

SH-1

SHOWER VALVE - ACCESSIBLE, SINGLE HANDLE PRESSURE BALANCED MIXING FAUCET, BRASS OR BRONZE CONSTRUCTION, WASHERLESS DESIGN, OFF-COLD-HOT TEMPERATURE RANGE INDICATOR DIAL, POLISHED CHROME CAST METAL LEVER HANDLE, INTEGRAL CHECK STOPS, ADJUSTABLE TEMPERATURE LIMIT STOP. ASSE 1016 LISTED.

ACCESSORIES - CHROME-PLATED BRASS SHOWERHEAD WITH SWIVEL BALL JOINT, CHROME-PLATED BRASS ARM AND FLANGE, HAND HELD SHOWER WITH ON/OFF CONTROL AND NON-POSITIVE SHUT OFF, 69" CHROME-PLATED METAL HOSE AND QUICK DISCONNECT, CHROME-PLATED BRASS SWIVEL CONNECTOR, 30" CHROME-PLATED MOUNTING RAIL, CHROME-PLATED BRASS SUPPLY ELBOW FLANGE, CHROME-PLATED IN-LINE VACUUM BREAKER WITH CHROME-PLATED PIPING AND FLANGES, CHROME-PLATED BRASS 2 FUNCTION TRANSFER VALVE.

INSTALL ALL CONTROLS BETWEEN 38" AND 48" ABOVE FINISHED FLOOR IN COMPLIANCE WITH LATEST ADA STANDARDS. INSTALL BOTTOM OF SHOWERHEAD AT 72" ABOVE FINISHED FLOOR. MAXIMUM FLOW TO BE 2.0 GPM IN COMPLIANCE WITH ENERGY POLICY ACT OF 2005 AND ASME/ANSI STANDARD A112.18.1M. SET SAFETY LIMIT STOP TO 110 DEGREE F DISCHARGE.

COORDINATE WITH SHOWER BASIN ON ARCHITECTURAL PLANS.

ACCEPTABLE MANUFACTURERS:

SHOWER VALVE - MOEN COMMERCIAL (8342/52236GBM25), SYMMONS (9605-PLR), AMERICAN STANDARD (1662.223), DELTA (R10700-UNWS/T13H323-20), LEONARD (PAM-II-ST-F/51-3D/62003)

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for PermitRS

RS

Crossing

P4.0

PLUMBING SCHEDULES

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

Page 7: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

PLUMBING MATERIAL LIST (CONTINUED)

WC-1

WATER CLOSET - FLOOR MOUNTED, FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET, HIGH EFFICIENCY RATED FOR 1.28 GPF, ELONGATED BOWL, 1-1/2" TOP SPUD, BOLT CAPS.

FLUSH VALVE - EXPOSED, WALL MOUNTED SENSOR OPERATION, HARD WIRED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN, CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW, MECHANICAL OVER-RIDE BUTTON, CHLORAMINE RESISTANT MATERIALS, CHROME PLATED COVER PLATE WITH TAMPER-PROOF SCREWS, TRANSFORMER AND LOW VOLTAGE WIRING, TRANSFORMER CAPABLE OF OPERATING UP TO 10 UNITS, LOW VOLTAGE WIRING FROM TRANSFORMER TO EACH FLUSH VALVE, ADA COMPLIANT, 3 YEAR WARRANTY.

ELECTRICAL REQUIREMENTS - 120VAC INPUT

SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID ANTI-MICROBIAL PLASTIC, SELF-SUSTAINING HINGE, STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS.

ACCESSORIES - WATER CLOSET SUPPORT CARRIER RATED FOR 500 LBS.

TOP OF SEAT SHALL BE AT 16"-17" ABOVE FINISHED FLOOR (VERIFY EXACT MOUNTING HEIGHT WITH MANUFACTURER. VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.

ACCEPTABLE MANUFACTURERS: WATER CLOSET - AMERICAN STANDARD (2234.001), SLOAN (ST-2000), ZURN (Z5655), KOHLER (K-4406), TOTO (CT705EN)

FLUSH VALVE - SLOAN (111 ES-S)

SEAT - BEMIS (3155C), CHURCH (3155C), BENEKE (533PC), OLSONITE (95), SAME AS WATER CLOSET MANUFACTURER

WC-2

WATER CLOSET - ACCESSIBLE, FLOOR MOUNTED, FLUSH VALVE TYPE, WHITE VITREOUS CHINA, SIPHON JET, HIGH EFFICIENCY RATED FOR 1.28 GPF, ELONGATED BOWL, 1-1/2" TOP SPUD, BOLT CAPS.

FLUSH VALVE - EXPOSED, WALL MOUNTED SENSOR OPERATION, HARD WIRED, 1.6 GALLONS PER FLUSH, 11-1/2" ROUGH-IN, CHROME PLATED, 1" I.P.S. SCREWDRIVER STOP-CHECK VALVE WITH VANDAL RESISTANT CAP, HIGH BACK PRESSURE VACUUM BREAKER, ADJUSTABLE TAILPIECE, SPUD COUPLING AND FLANGE, WALL FLANGE WITH SET SCREW, MECHANICAL OVER-RIDE BUTTON, CHLORAMINE RESISTANT MATERIALS, CHROME PLATED COVER PLATE WITH TAMPER-PROOF SCREWS, TRANSFORMER AND LOW VOLTAGE WIRING, TRANSFORMER CAPABLE OF OPERATING UP TO 10 UNITS, LOW VOLTAGE WIRING FROM TRANSFORMER TO EACH FLUSH VALVE, ADA COMPLIANT, 3 YEAR WARRANTY.

ELECTRICAL REQUIREMENTS - 120VAC INPUT

SEAT - WHITE, EXTRA HEAVY, OPEN FRONT, INJECTION MOLDED SOLID ANTI-MICROBIAL PLASTIC, SELF-SUSTAINING HINGE, STAINLESS STEEL OR PLATED STEEL POSTS AND NUTS.

ACCESSORIES - WATER CLOSET SUPPORT CARRIER RATED FOR 500 LBS.

TOP OF SEAT SHALL BE AT 17"-19" ABOVE FINISHED FLOOR (VERIFY EXACT MOUNTING HEIGHT WITH MANUFACTURER. FLUSH HANDLE SHALL BE LOCATED ON THE WIDE SIDE OF THE TOILET STALL AND BE AT 12" (MAXIMUM) ABOVE BOWL RIM AND OPERATE WITH NO GREATER THAN 5 LB FORCE IN COMPLIANCE WITH LATEST ADA STANDARDS. VERIFY EQUIPMENT REQUIREMENTS AND ROUGH-IN LOCATIONS.

ACCEPTABLE MANUFACTURERS: WATER CLOSET - AMERICAN STANDARD (3043.001), SLOAN (ST-2020), ZURN (Z5665), KOHLER (K-4405), TOTO (CT705ELN)

FLUSH VALVE - SLOAN (111 ES-S)

SEAT - BEMIS (3155C), CHURCH (3155C), BENEKE (533PC), OLSONITE (95), SAME AS WATER CLOSET MANUFACTURER

WHA-1

WATER HAMMER ARRESTER - BELLOWS TYPE, PRE-CHARGED, ALL STAINLESS STEEL CONSTRUCTION, ASSE 1010 APPROVED, PDI CERTIFIED, RATED FOR 1-11 FIXTURE UNITS.

ACCEPTABLE MANUFACTURERS: ZURN (Z1700), SMITH (5005-5050), WADE (W5-100), JOSAM (75000 SERIES), WATTS (SS), MIFAB (WHB)

WH-1

WATER HEATER - ELECTRIC, VERTICAL, METAL CABINET, BAKED ENAMEL FINISH, GLASS-LINED ASME STAMPED WELDED STEEL TANK, 150 PSI WORKING PRESSURE, FIBERGLASS OR FOAM INSULATION, BRASS WATER CONNECTIONS AND DRAIN VALVE, ASME APPROVED T&P RELIEF VALVE, MAGNESIUM ANODE ROD, INDIVIDUAL FLANGE-MOUNTED IMMERSION HEATING ELEMENTS SHEATHED WITH CORROSION-RESISTANT METAL ALLOY, EXTERNALLY ADJUSTABLE AUTOMATIC IMMERSION WATER THERMOSTAT, MANUAL RESET HIGH TEMPERATURE CUTOFF SWITCH, ENCLOSED CONTROLS, VENTILATED CONTROL CABINET, PILOT LIGHTS INDICATING MAIN POWER AND HEATING STEPS, CONTROL CIRCUIT TOGGLE SWITCH, SEQUENCING STEP CONTROLLER, CONTROL TRANSFORMER, POWER CIRCUIT FUSES, MAGNETIC CONTACTORS, CERAMIC TERMINAL BLOCK, FACTORY ASSEMBLED AND WIRED, 3-YEAR WARRANTY, UL LISTED, NEC COMPLIANT ELECTRICAL COMPONENTS, COMPLIANT TO NAECA, ASHRAE 90.1 AND ASHRAE 90A.

120 GALLON CAPACITY, 12 KW ELEMENT(S), 46 GPH RECOVERY RATE AT 100°F TEMPERATURE RISE. HEATING ELEMENTS RATED FOR LESS THAN 75 WATTS PER SQUARE INCH.

ELECTRICAL REQUIREMENTS - 480V-3 PHASE HEATING CIRCUIT, 120V CONTROL CIRCUIT.

SET WATER TEMPERATURE AT 140°F.

ACCEPTABLE MANUFACTURERS: A.O. SMITH (DVE), AMERICAN (ITCE31), BOCK (F SERIES), BRADFORD WHITE (M-II), RHEEM/RUUD (E SERIES), STATE (SSE), HTP (CGE SERIES HEAVY DUTY)

YCO-1

YARD CLEANOUT - ROUND, DURA-COATED CAST IRON, SIZE AS LISTED ON DRAWINGS, DOUBLE FLANGED HOUSING, HEAVY DUTY SECURED SCORIATED DURA-COATED CAST IRON COVER, LIFTING DEVICE, BRONZE CLEANOUT PLUG WITH GAS/WATER-TIGHT SEAL.

ACCEPTABLE MANUFACTURERS: ZURN (Z1474), SMITH (4261), WADE (8401), JOSAM (58680), WATTS (CO-300-MF)

WH-2

WATER HEATER - ELECTRIC INSTANTANEOUS POINT-OF-USE, HIGH STRENGTH REINFORCED PLASTIC BODY, 1/2" COMPRESSION FITTINGS, THERMOSTATICALLY CONTROLLED, NEMA 4 PAINTED STEEL WATERPROOF ENCLOSURE , FULLY ADJUSTABLE THERMOSTAT (100-140°F), HIGH TEMPERATURE LIMIT SWITCH, 150 PSI WORKING PRESSURE, REPLACEABLE ELEMENT, 1-YEAR WARRANTY ON ELEMENT, 5-YEAR WARRANTY ON HEATER BODY/ELEMENT ASSEMBLY, UL LISTED.

100°F RISE AT 2.0 GPM, 32 KW ELEMENT, 38 AMPS/PHASE - TURN ON AT 0.3 GPM OR LESS

ELECTRICAL REQUIREMENTS - 480 V-3 PHASE, HARD-WIRED

SET OUTPUT WATER TEMPERATURE AT 140°F.

ACCEPTABLE MANUFACTURERS: EEMAX (ED032480T2T ML), BRADFORD WHITE (EFT), CHRONOMITE (S)

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for Permit

Crossing

P4.1

PLUMBING SCHEDULES

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

Page 8: PLUMBING FIXTURE ROUGH-IN SCHEDULE ltdApr 11, 2019  · 8. seal all floor, wall, and roof penetrations airtight where conduits, piping, and ducts penetrate. penetrations through exterior

3"W

1"CW

HB-1

WHA-1

WHA-11"CW

3/4

"CW

HB-2

BFP-1

ET-1

WH-1

1 1

/2"H

W1 1

/2"C

W

3/4

"CW

3"C

W

CP-1

2 1/2"CW

MB-1WC-21 1/4"CW1 1/2"HW3/4"HWC

1" CW TO SPLASH PAD

ESE-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

WHA-1

HB-2

HB-2

L-2

HB-1

HB-2

HB-2

L-1

SH-1

SH-1

WC-2

DF-1

WC-2

WC-2

SH-1

SH-1

WC-1

WC-1

WC-1

WC-2

UR-2

UR-1

L-1

L-2

2 1/2"CW1 1/2"HW3/4"HWC

2"CW

1 1/4"HW

2"CW3/4"HW3/4"HWC

2"CW1"HW3/4"HWC3/4"HW

WHA-1

WHA-1

1" CW TO DRINKING FOUNTAIN.

REFER TO CIVIL PLANS FOR CONTINUATION.

1"CW

3/4"HWC

1 1/4"HW2"CW

3/4"HW3/4"CW

3/4"HWC1 1/2"HW2 1/2"CW

3/4"HWC1 1/2"HW

1 1/4"CW

PROVIDE 2" WATER METER AS REQUIRED PER ILLINOIS PLUMBING CODE 890 APPENDIX A TABLE O.

1

1

1 1/4" TEMPERED WATER

ESE-1

YCO-1

2"SAN

6"SAN

4"SAN

6"SAN

FD-3

HD-1

HD-1

4"SAN

FD-1FCO-1

FD-1

FCO-1

FCO-1

FD-1

FD-2

FD-2

FCO-1

HD-1

FD-1

FCO-1

FD-1

FD-1

FCO-1

FD-2

1 1/2"V

2"V 3"V

3"V

3"V3"V

2"V

2"V

VTR

VTR

3"V

REFER TO CIVIL PLANS FOR CONTINUATION

MB-1

WC-2

WC-2

FD-2

WC-1

WC-1

WC-1

UR-2

UR-1

L-1WC-1

L-1

L-2

WC-2

L-2

WC-2

FCO-1

DF-1

2"V

2"V

2"V

4"SAN

4"SAN

4"SAN

4"SAN

4"SAN

2"V 3"V

2"V

2"V

2"V3"V

2"V2"V

2"V

HB-1

3/4"CW

WHA-1

3/4"CW

2"W

2"C

W

BFP-1

3/4" CW TO WH

REFER TO CIVIL PLANS FOR CONTINUATION.

PROVIDE 3/4" WATER METER AS REQUIRED PER ILLINOIS PLUMBING CODE 890 APPENDIX A TABLE O.

4"OSAN

2"V

2"V

HD-1

YCO-1

VTRVTR

3"V

3"V

3"V1 1/2"V

OS-1

MB-1

REFER TO CIVIL PLANS FOR CONTINUATION.

FCO-1

TD-1

4"SAN

4"SAN

815-254-0091 www.uplanddesign.com

Park Planning and Landscape Architecture

24042 Lockport St, Plainfield, Illinois 60544

ltd

320 W. Jackson Avenue

Naperville, IL 60540Phone: 630-848-5000

CIVIL ENGINEER / SURVEYOR /

STRUCTURAL ENGINEER

Engineering Resource Associates

3s701 West Avenue, Suite 150

Warrenville, IL 60555

ARCHITECT

Charles Vincent George Architects

1245 E Diehl Rd, Suite 101

Naperville, Iliinois 60563

AQUATIC

Innovative Aquatic Design, LLC (WT

Group)

2675 Pratum Avenue

Hoffman Estates, Illinois 60192

MECHANICAL / ELECTRICAL ENGINEER

IMEG

1100 Warrenville Road, Suite 400W

Naperville, Illinois 60563

IRRIGATION

FRS Design Group, LLC

167 South Lexington Street

Spring Green, Wisconsin 53588

SHEET TITLE

PROJECT TEAM

Wolf's

CommunityParkDevelopment3252 Wolf's Crossing Road

PROJECT

LANDSCAPE ARCHITECT

DRAW / REVISION

SHEET NUMBER

Project Number 620

© Copyright 2019 Upland Design Ltd.

Bid / Permit Resubmittal 15APR2019

14MAR2019Issue for Permit

Crossing

P5.0

PLUMBING RISERDIAGRAM

REFERENCE SCALE IN INCHES

0 1 2 3

PROJECT #

Illinois Design Firm Registration #184007637-0014

IMEG CORP RESERVES PROPRIETARY RIGHTS, INCLUDING COPYRIGHTS, TO THIS DRAWING AND THE DATA SHOWN THEREON. SAID DRAWING AND/OR DATA ARE THE EXCLUSIVE PROPERTY OF IMEG CORP AND SHALL NOT BE USED OR REPRODUCED FOR ANY OTHER PROJECT WITHOUT THE EXPRESS WRITTEN APPROVAL AND PARTICIPATION OF IMEG CORP. © 2019 IMEG CORP.

1100 WARRENVILLE RD, SUITE 400WNAPERVILLE, IL 60563630.527.2320 FAX: 630.527.2321www.imegcorp.com

18003960.00

NO SCALE1 RESTROOM BUILDING PLAN RISER - DOMESTIC

NO SCALE2 RESTROOM BUILDING PLAN RISER - SAN/VENT

NO SCALE3 STORAGE BUIDING PLAN RISER - DOMESTIC

NO SCALE4 STORAGE BUIDING PLAN RISER - SAN/VENT

KEYNOTES:

1. ROUTE DOMESTIC WATER PIPING TO ALLOW SYSTEM TO BE FULLY DRAINABLE SO THE BUILDING CAN BE WINTERIZED. SLOPE PIPING TO LOW POINT. PROVIDE NORMALLY CLOSED SHUTOFF VALVE AND CAPPED THREADED CONNECTION.

#

1