Phasors in New Zealand
NASPI February 2013
Transpower: Victor Lo, Richard Sherry OSIsoft: Ann Moore
![Page 2: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/2.jpg)
New Zealand Grid
Two 50Hz asynchronous systems - North and South Island Joined by HVDC (1200MW). Long and skinny, high impedance, 220kV, 110kV, 66kV
South: Hydro, Wind
North: Hydro, Thermal, Wind
4500MW
2200MW
![Page 3: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/3.jpg)
Why Phasors?
• Situational awareness
• Early warning on emerging stability issues
• Monitor equipment performance
• Validate power system models
![Page 4: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/4.jpg)
PMU Locations (14) North Island
1. Otahuhu (Gen & Load) 2. Huntly (Gen) 3. Whakamaru (Gen) 4. Stratford (Gen) 5. Bunnythorpe 6. Haywards (HVDC terminal) 7. Westwind (Windfarm)
South Island 1. Kikiwa (STATCOM) 2. Islington (SVC & Load) 3. Twizel (Gen) 4. Benmore (HVDC terminal) 5. Roxburgh (Gen) 6. Tiwai (Smelter) 7. North Makarewa
![Page 5: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/5.jpg)
Phasor measurements • Synchronised recording of phasor data – time
stamped by GPS clock
• Real Time measurement of 3 phase Voltage & Current – both magnitude and phase angle
• Sampled 50 times per second (50 Hz is nominal system frequency)
• Phasors are extracted from our protection relays
![Page 6: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/6.jpg)
Data access 1. PI (OSIsoft) – Main data source
SCADA, PMUs, protection logs, system logs, etc.
2. Psymetrix – Phasor-only data source
Real-time monitoring and alarms Oscillation frequency, damping (stability) Locus plots Monthly system stability reports
![Page 7: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/7.jpg)
1. PI (OSIsoft) data access • Main data source with SCADA, PMU, logs, etc.
• Screens • EXCEL link • MATLAB link
![Page 8: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/8.jpg)
1. PI (OSIsoft) data access
![Page 9: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/9.jpg)
1. PI (OSIsoft) data access
Custom screens are relatively easy to make
![Page 10: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/10.jpg)
2. Psymetrix data access • More specialized phasor applications.
• Real time monitoring, eg alarms • Oscillations (freq and decay), locus plots
Alarms
![Page 11: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/11.jpg)
PMU Usage • An investigation tool (not used in real time
operations) • Event analysis • Power system model validation • Monitoring oscillations (Psymetrix)
![Page 12: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/12.jpg)
System Under-frequency event
6.5Hz oscillation “Generator Pole
slipping”
![Page 13: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/13.jpg)
Monitoring SVC performance during grid faults
-100.000
-50.000
0.000
50.000
100.000
150.000
200.000
200.000
205.000
210.000
215.000
220.000
225.000
230.000
235.000
240.000
245.000
250.000
36:0
9 AM
36:0
9 AM
36:0
9 AM
36:0
9 AM
36:0
9 AM
36:1
0 AM
36:1
0 AM
36:1
0 AM
36:1
0 AM
SVC
(M
var)
Islin
gton
220
kV
bus
volta
ge (k
V)
![Page 14: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/14.jpg)
Undampped Oscillation in South Island (with mainly Hydro)
15MW
1.5Hz
![Page 15: Phasors in New Zealand - naspi. · PDF fileJoined by HVDC (1200MW). Long and skinny, ... • MATLAB link . 1. PI (OSIsoft) ... Monitoring SVC performance during grid faults -100.000](https://reader031.vdocuments.us/reader031/viewer/2022030509/5ab81b377f8b9ad13d8c2db4/html5/thumbnails/15.jpg)
Phasors, to finish… • 14 PMU sites give good grid coverage • Plans to add 2 new sites at top of North Island • Used for investigations:
• Fault analysis, oscillation monitoring • Model validation • Equipment monitoring
• Storage / Data processing with PI & Psymetrix • Developing more uses as time goes on, e.g.
Anti-islanding detection