PHASOR MEASUREMENT UNITS, WAMS, AND THEIR APPLICATIONS A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Upload: others

Post on 20-Jan-2021

1 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

PHASOR MEASUREMENT UNITS,

WAMS,

AND THEIR APPLICATIONS

A.G. Phadke

Virginia Tech, Blacksburg, VA, USA

Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Page 2: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

5. Wide Area Measurement Systems - WAMS

Lecture outline

6. Applications of PMUs and WAMS

1. Birth of PMUs – Virginia Tech

2. Phasor Measurement Techniques

3. Synchronization

7. Conclusions

4. Standards

Page 3: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

1. Birth of PMUs – Virginia Tech

Page 4: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

DISTANCE RELAYS FOR 3-PHASE SYSTEMS

• Six distance relays at each terminal

• Three ground distance relays: a-g, b-g, c-g

• Three phase distance relays: a-b, b-c, c-a

• Need to cover 10 fault types

Symmetrical Component Distance Relay Development

We at AEP wanted to work on line relaying using IBM System 7, and

it was necessary to fit the algorithm in one cycle to make a high-speed

relay.

Page 5: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

DISTANCE RELAYS ON 3-PHASE SYSTEMS

Six equations have to be solved:

• a-g relay responds to Ea/(Ia + mI0)

• b-g relay responds to Eb/(Ib + mI0)

• c-g relay responds to Ec/(Ic + mI0)

• a-b relay responds to (Ea-Eb)/(Ia-Ib)

• b-c relay responds to (Eb-Ec)/(Ib-Ic)

• c-a relay responds to (Ec-Ea)/(Ic-Ia)

R

I

E

x a-g

b-g

a-b

b-c c-g c-a

Page 6: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

ONE equation (instead of six) with symmetrical components (SCDR):

k0 etc. are defined in terms of symmetrical

component voltages and currents. Then the

distance to the fault is given by:

Fault distance = k1 + k2k2’ + k0k0’

1 + k1 + k2’ + k0’

FOR ALL FAULT TYPES!

This was a nice algorithm, and I did get a patent on this.

Made some money too.

Page 7: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Computer relaying development laboratory at AEP

Ted Hlibka and Mark Adamiak

Page 8: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Structure of SCDR algorithm

Structure of PMU

Filters

&

Sampling

Phasors

By

DFT

VA, VB, Vc

IA, IB, IC

V1, I1

V2, I2

V0, I0

k Relaying

Logic

Currents

&

Voltages

Filters

&

Sampling

Currents

&

Voltages

Phasors

By

DFT

VA, VB, Vc

IA, IB, IC

V1, I1

V2, I2

V0, I0

k Relaying

Logic

The microcomputers became quite fast in time, and there was no particular benefit

in making SCDR for distance relaying. However, a realization came that the

sequence measurement part of the algorithm is very valuable in many power system

applications. That was the birth of the PMU.

Page 9: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

(b)

GPS

receiver

PMU

Signal

conditioning

unit

User

Interface

Proto-type of complete PMUs at Virginia Tech

Page 10: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Virgilio Centeno went to

Macrodyne after getting

his Ph.D. and

worked with Jay Murphy

to design the first

commercial PMU.

Page 11: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

2. Phasor Measurement Techniques

Page 12: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Introduction to phasors

q

Real

Ima

gin

ary

• The starting time defines the phase angle of the phasor.

• This is arbitrary.

• However, differences between phase angles are

independent of the starting time.

q

t=0

Page 13: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Sampling process, Fourier filter for phasors

sin and cos

functions

t

Input signal

xn

xn-1

.

.

x1

Data

sam

ple

s

co

sin

es

sin

es

Phasor X = --S xk(coskq - j sinkq)

2

N

Page 14: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Non-recursive phasor calculations

t

q1

q1

q2

q2 = q1 + kf

The non-recursive phasor rotates in the forward

direction, one sample angle per sample.

Page 15: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Recursive phasor calculations

t

q1

q1

The recursive phasor remains fixed if the input

waveform is constant.

q2= q1

q2 = q1

Page 16: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Effect of noise on phasor calculations

• Harmonics eliminated correctly if Nyquist

criterion is satisfied.

• Non-harmonic components

• Random Noise

True Phasor

Circle of

uncertainty

Siz

e o

f cir

cle

of

un

cert

ain

ty

Measurement

data window

Page 17: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Measurement of frequency and rate of change of frequency:

Phase angle of positive sequence voltage is constant when input is at nominal frequency and constant.

At constant off-nominal frequencies, the phase angle changes linearly.

Slope of angle is (w-w0)

60 Hz

58 Hz

59 Hz

61 Hz

62 Hz

Using angles over a window, and assuming them to be a quadratic function of time, the

Rate of change of angle provides frequency measurement, and the second derivative

Provides rate of change of frequency very accurately.

Page 18: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

3. Synchronization

Page 19: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Motivation for synchronization

By synchronizing the sampling processes for

different signals - which may be hundreds of miles

apart, it is possible to put their phasors on the same

phasor diagram.

Substation A Substation B

At different locations

Page 20: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Sources for Synchronization

• Pulses

• Radio

• GOES

• GPS

Page 21: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Anti-aliasing

filters

16-bit

A/D conv

GPS

receiver

Phase-locked

oscillator

Analog

Inputs

Phasor

micro-

processor

Modems

• A phasor measurement unit

Except for synchronization, the hardware is the same

as that of a digital fault recorder or a digital relay.

Page 22: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

4. Standards

Page 23: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

IEEE standard for

SYNCHROPHASORS for

Power Systems

IEEE Std 1344-1995

IEEE Std C37.118-2005

IEEE Std C37.118.1-2011

IEEE Std C37.118.2-2011

IEC 61850-90-5-2011

Evolution of

Synchrophasor

Standards

Page 24: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

C37.118.1

Synchrophasor Measurements for Power Systems

Page 25: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Measurement accuracy defined: Total Vector Error (TVE)

A pure sinusoid is generated and input to the PMU

It corresponds to a theoretical phasor value X = Xr + j Xi

PMU produces a measurement at t0 : X(t0)

X(t0) = Xr(t0) + j Xi(t0)

TVE is defined as follows:

TVE = √ [Xr(t0) - Xr]

2 + [Xi(t0) - Xi]2

Xr2 + Xi

2

Page 26: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Measurement accuracy defined: Total Vector Error (TVE)

Two classes of PMU performance are defined:

P class: Fast responding, minimum filtering,

minimum delay (Mainly used for

protection and control)

M class: Slower responding, significant filtering,

longer delay (Mainly used for

measurements in the presence of out-

of-band signals)

P and M classes replace the ‘0’ and ‘1’ classes of C37.118

Page 27: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Dynamic tests:

• Sinusoidal modulation

• Ramp variation of frequency

• Step changes in magnitude and phase

Steady State tests:

• Off-nominal frequency

• Harmonic signals

• Non-harmonic signals

Page 28: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

DYNAMIC TESTS FOR PMUS

Signals to be generated

according to formulas

Anti-aliasing Filter

PMU

Expected output Positive sequence Phasor magnitude and angle. Frequency, rate of change of frequency

PMU output Positive sequence Phasor magnitude and angle. Frequency, rate of change of Frequency At designated reporting instants

Error Report

Balanced three phase inputs

1. Sinusoidal modulations

2. Ramps

Page 29: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

ya = √2×67×{1+0.2×sin(2π×0.2×t)} × sin{120×π×t + 2π×1.0×sin(2π×0.2×t)}

yb = √2×67×{1+0.2×sin(2π×0.2×t)} × sin{120×π×t + 2π×1.0×sin(2π×0.2×t) – 2π/3}

yc = √2×67×{1+0.2×sin(2π×0.2×t)} × sin{120×π×t + 2π×1.0×sin(2π×0.2×t) – 4π/3}

67 volt rms nominal signal

Amplitude modulation 0.2 pu

Modulation frequency 0.2 Hz

Frequency modulation amplitude 1.0 Hz

Example: Sinusoidal modulation

0 1 2 3 4 5 6 7 8 9 10 Nominal cycles Reporting times

Initial Phasor Estimate

df/dt f

Final Phasor Estimate corrected for ‘f’, f, df/dt

0 2 4 6 8 10 df/dt f P

Page 30: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

0 1 2 3 4 5 6 7 8 9 10-20

0

20

40

60

80

100

Example: Sinusoidal modulation; Simulation Results from Matlab

True Phasor rms amplitude

True Phasor Phase Angle

Errors in Phasor Magnitude and Phase angles Frequency Estimates df/dt estimates

Seconds

Volts, R

adia

ns,

Radia

ns/s

ec,

Radia

ns/s

ec

2

Page 31: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

ya = √2×67× sin{120×π+ 2π×(0.2/2) ×t} ×t)

yb = √2×67× sin{120×π+ 2π×(0.2/2) ×t} ×t– 2π/3}

yc = √2×67× sin{120×π+ 2π×(0.2/2) ×t} ×t– 4π/3}

67 volt rms nominal signal

Nominal frequency 120 ×π

Ramp rate of 0.2 Hz/sec

Example: Ramp modulation

0 1 2 3 4 5 6 7 8 9 10 Nominal cycles Reporting times

Initial Phasor Estimate

df/dt f

0 2 4 6 8 10 df/dt f P

Final Phasor Estimate corrected for ‘f’, f, df/dt

Page 32: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

0 1 2 3 4 5 6 7 8 9 10-10

0

10

20

30

40

50

60

70

True Phasor rms amplitude

Errors in Phasor Magnitude and Phase angles

Frequency Estimates

True Phasor Phase Angle

Seconds

Volts, R

adia

ns,

Radia

ns/s

ec,

Radia

ns/s

ec

2

Example: Ramp modulation; Simulation Results from Matlab

df/dt estimates

Page 33: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

C37.118.2

Synchrophasor Data Transfer for Power Systems

Page 34: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Phasor reporting rates:

Data reporting frequency Fs is in data frames per

second, and is defined for a 50 Hz or 60 Hz system:

System 50 Hz 60 Hz

frequency

Fs 10 25 50 10 12 15 20 30 60

The first reporting instant is at the roll-over of the UTC

second, and all others follow at multiples of the nominal

power frequency period T. Example: Fs = 30, for 60 Hz.

UTC roll-over

2T 4T 6T 8T

Page 35: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Reporting time and data window:

Data samples used for phasor estimation

The standard does not specify the positioning of the

data window in relation to the reporting instant.

Page 36: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Bandwidth requirements:

Bits per second using UDP/IP over Ethernet

Fs 10 12 15 25 30 50 60

2 phasors

integer

2 phasors

fl-point

12 phasors

integer

12 phasors, 2 an.

2 dig. integer

6720 8064 10080 16800 20160 33600 40320

7680 9216 11520 19200 23040 38400 46080

9920 11904 14880 24800 29760 49600 59520

10560 12762 15840 26400 31680 52800 63360

Page 37: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

IEC 61850-90-5-2011

Complete 61850 solution for synchrophasor

communication

Page 38: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

5. Wide Area Measurement Systems - WAMS

Page 39: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Wide Area Measurement System

PMU

PMU

PMU PMU

PMU PMU

PMU

PMU

PMU

Page 40: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Wide Area Measurement System

System Architecture

Super Data

Concentrator

Data

Concentrator

PMU PMU PMU PMU PMU PMU

Data

Concentrator

PMUs located in substations

Data storage

Applications

Page 41: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

6. Applications of PMUs and WAMS

Page 42: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Wide Area Measurement System

PMUs measure (synchronously):

• Positive sequence voltages and currents

• Phase voltages and currents

• Local frequency

• Local rate of change of frequency

• Circuit breaker and switch status

PMU data reporting rates:

• Data reported at up to once per cycle

Page 43: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• State estimation

• Instrument transformer calibration

• Network parameter estimation

• Protection systems

• System Control

Page 44: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Three-phase transducer calibration

Page 45: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Three-phase transducer calibration

•PMUs are installed at two substation

•Voltages: PT CVT

•Currents: CT

a a a ab ac a a ab ac a

q0 p0 pq pq pq pq0 p p p p0

b b ab b bc b ab b bc b

q0 p0 pq pq pq pq0 p p p p0

c c ac bc c c ac bc c c

q0 p0 pq pq pq pq0 p p p p0

E E Z Z Z I B B B E

E = E - Z Z Z I - B B B E

E E Z Z Z I B B B E

Page 46: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Error model of transducers

• Error model of PTs and CTs:

Here, e and i are the ratio correction factor (RCF)

|e|,|i|~Uniform(0.96,1.04) ; angle(e), angle(i) ~ Uniform(-3,3) degree

• Simple error model. With the assumption, in short time period, the errors

of transducers are constants.

• Several sets of measurements by PMUs, during 24 hour under different

load conditions, provide redundancy to solve the errors. (20 cases for

47-bus and 53-branch system)

a a a

b b b

c c c

m

m

m

E e 0 0 E

E 0 e 0 E

E 0 0 e E

=

a a a

b b b

c c c

m

m

m

0 0

0 0 I

0 0 I

I i I

I = i

I i

Page 47: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

24-hour load cases • At each point, the load condition changes. PMUs can measure three-phase voltages

and currents under each condition. And all of these set satisfy OHM law.

0

0.2

0.4

0.6

0.8

1

1.2

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Lo

ad

perc

en

t (%

)

Hour

Average 24-hour load in winter

qm

m

m

a a a a ab ac a a a ab ac

p pq pq pq m p p p

b b b ab b bc b b ab b bc

q p pq pq pq m p p p

c c c ac bc c c c ac bc c

q p pq pq pq m p p p

e 0 0 E E Z Z Z i 0 0 I B B B

0 e 0 E = E - Z Z Z 0 i 0 I - B B B

0 0 e E E Z Z Z 0 0 i I B B B

a

p0

b

p0

c

p0

E

E

E

Page 48: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

No NR iteration • Get linear equations

Branch with perfect PT

Branch with two buses to be calibrated

12 12 1 12 12 12 2 2

12 1 21 21 12 12 2 2

(Y + B )E = i I + Y e E

Y E = -i I + (Y + B )e E

rs rs rs rs r r rs s s

sr sr rs rs s s rs r r

0 = -i I + (Y + B )e E - Y e E

0 = -i I + (Y + B )e E - Y e E

0 0 0 0 0

0 0 0 0 0

0 0 0 0 0

0 0 0 0 0

r

r

12

21

12 12 2 rs 12 12 1

21 12 12 2 sr 12 1

rs rs rs rs s

sr rs s rs rs 2

r

s

i

i

I Y E i (Y + B )E

I (Y + B )E i Y E

-I (Y + B )E Y E

-I Y E (Y + B )E e

e

e

L L

L L

L L M

L L

M M M M M M M L M M

M

D(I) YAE

X Eref

X=([D(I) YAE)-1Eref

Page 49: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

DVP 500kv system

Page 50: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

abc abc

true calibratede - e

abc abc

true calibratede eangle( ) -angle( )

Page 51: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Network parameter estimation

Page 52: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Protection system improvements

with WAMS

Page 53: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• Moving towards fewer and less intense blackouts

Protection system performance issues

(1) Inappropriate settings for prevailing conditions

(2) Hidden failures in protection systems

(3) Security-Dependability balance

Page 54: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

1. Equipment Protection (Primary)

Example: Lines, Transformers, Generators, Buses

Fairly straight forward: Protect against faults to

avoid damage to the equipment, to get the fault

off the system as quickly as possible to avoid

cascading failures of the network.

Modern relays are autonomous, fast acting,

and often duplicated or even triplicated to

avoid failure to clear a fault.

Relay times may be as short as a cycle, and

circuit breaker times may be 2-3 cycles.

These are primary protection systems.

Overview of protection systems and practices

Page 55: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Overview of protection systems and practices

1. Equipment Protection (Primary)

Contest between security and dependability

Biases

2. Equipment Protection (Back-up)

Of necessity it is slower

It trips larger part of the system

Back-up operation is more damaging

It is more difficult to set, depends too much on

conditions of the network.

Page 56: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Overview of protection systems and practices

3. System Protection The aim is to protect the power system from hurtful faults

Load shedding and restoration

Loss of field

Out-of-step

Islanding

It has the same performance characteristics as the Back-up systems:

Of necessity it is slower

It trips larger part of the system

It is more difficult to set, depends too much on

conditions of the network.

4. Remedial Action Schemes More complex, a start on wide area measurement based

protections

Page 57: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Preliminary Remarks

• Wide area measurements: PMU data

• High-speed protections not affected

• Slow speed protections – Back-up,

Stability, Loss-of-field, RAS

• Adequate communication facilities

implied: within substation, with

neighboring substations,

with remote substations,

system-wide

Page 58: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Topics for WAMS based protection

(2) Alarming for relay characteristic penetration

(3) Adaptive out-of-step relaying

(1) Adjusting balance of security-dependability

Balance to be shifted when the power system

is in emergency state as determined from

wide area measurements.

Wide area measurements to determine

trajectories and trends of relaying parameters.

Wide area measurements to determine

trajectories and predict outcome of stability

swings in real-time.

Page 59: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Other possibilities:

(4) Supervision of back-up zones

(5) Intelligent load shedding using load-

generation imbalance estimate in real

time

(6) Adaptive loss-of-field relay

(7) System-wide integration of Remedial

Action Schemes (RAS or SIPS)

Topics for WAMS based protection

Page 60: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Protection system bias:

High dependability

Corresponding

best possible security

System State

Assessment PMU data PMU data

Critical System

Locations

Supervisory

signals

Adjustment of Dependability-Security

balance under stressed system

conditions.

Relay 1

Relay 2

Relay 3

OR

VOTE

AND

Supervisory

signal

See detail

below

(1) Adjusting balance of security-dependability

To

Circuit

Brealer

(Dealing with Hidden Failures)

Page 61: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

(2) Alarming for relay characteristic penetration

Static: Load encroachment Dynamic: Swings

How close?

Revise settings? How close?

Revise settings?

Critical Relay locations

Page 62: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

•R

•X

•Inner zone

•Outer zone

•Stable swing

•Unstable swing •Unstable swing

•Stable swing

•T1 •T2

Traditional out-of-step relay parameters using reactance type relays

and timers.

Impedance relays and timers are used to detect

and protect against unstable oscillations

Setting are determined

from results of a large

number of simulations

under different conditions

(3) Adaptive Out-of-Step Relays

Inadequacies in present systems

Page 63: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Georgia

Out of step

condition

S-PMU

Relay

S-PMU

Relay

Previous Experience

1993-1994

System behaving as a 2-machine system

Page 64: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

0 1 2 3 4 Seconds

Equivalents Angle Difference, September 8, 1994

50

48

46

44

42

40

38

Measured

Algorithm

Improved

Algorithm

Original

Equal Area Criterion

Swing Prediction

for

Florida-Georgia

Interconnection

Pre-disturbance power-angle curve

P

d

P m

Post-disturbance

power-angle curve

Accelerating

area A 1

Decelerating area A

2

max A

d o o

Page 65: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Out-of-step relaying for complex networks

(1) Identify critical PMU placement sites

(2) Real-time coherency determination

(3-a) Two machine equivalent

(4-a) Extended Equal Area

Criterion application

(3-b) Two machine equivalent

(4-b) Time-series of swing curves

and prediction

Page 66: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Out-of-step relaying for complex networks

(2) Real-time coherency determination

PMU data

Observation window

Page 67: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Out-of-step relaying for complex networks

(3-a) Two machine equivalent

(4-a) Extended Equal Area

Criterion application

Pre-disturbance power-angle curve

P

d

P m

Post-disturbance

power-angle curve

Accelerating

area A 1

Decelerating area A

2

max A

d o o

PMU

Relay

PMU

Relay

Page 68: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Out-of-step relaying for complex networks

(3-b) Two machine equivalent

(4-b) Time-series of swing curves

and prediction

PMU PMU

Processing

Center

Time

d1 - d2

Observation

Interval

Prediction

Interval

Page 69: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

(4) Supervision of back-up zones

Zone 3 picks-up

Balanced Conditions?

Any Zone-1 picked up?

Yes.

If not Block Zone-3 }

Page 70: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

(5) Intelligent load shedding using load-

generation imbalance estimate in real

time

ACE = DT-BDF

Dynamic ACE measures

Load needed to be shed

To return to pre-disturbance state

Page 71: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

(6) Adaptive loss-of-field relay

System

Thevenin Z

Determined

In real time

R

X

Weak system

Strong system

Page 72: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

(7) System-wide integration of Remedial

Action Schemes (RAS or SIPS)

RAS 1 RAS 2

Are RAS 1 and RAS 2

In conflict with each

other?

Make one RAS which

Will combine the

Objectives of the two

RAS schemes and

Create a unified

response.

Page 73: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Concluding remarks on protection system improvements

• Protection systems can be improved

with the help of wide-area measurements

• Only slow-responding protections are

appropriate candidates for such improvements

• Many improvements occur as steps to

improve response to next contingencies,

and are not intended to operate when a

fault has occurred.

With careful implementation, frequency and intensity

of blackouts can be reduced, and service restoration

can be more rapid.

Page 74: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

SYSTEM CONTROL WITH PHASORS

Page 75: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

• This lecture is theoretical in nature. A number

of studies have been reported in literature, although as

yet there is no field implementation of these ideas.

• We will consider control of

HVDC systems

Excitation Control

Power System Stabilizer

FACTS control

Control with phasor feed-back.

Page 76: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Control with phasor feed-back.

Controlled Device

Controller

Measurements

Page 77: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Phasor feed-back

• Expect to be less dependent on model of

the system being controlled.

• Processes being controlled are relatively slow.

• Process frequencies in the range of 0.2-2.0 Hz.

These are representative of electromechanical

oscillations, transient stability, and certain

overload phenomena.

• The frequency of phasor measurements is

expected to be of the order of 15-30 Hz, which

is certainly sufficient to handle the control task.

Page 78: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example of control with phasor feed-back

System A System B

Power demand Controller

dA- dB

time

Performance with

constant power

control law

Desired

performance

Page 79: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 1: HVDC Controller

1640 MW

820 MW

(200+j20) MVA

590 MVAR

680 MVAR

3 phase fault

cleared in 3 cycles

G1

G2

Page 80: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 1: HVDC Controller

Control law 1: Constant current, constant voltage on HVDC

Control law 2: Optimal controller

d1

d2

t (seconds) 5

Page 81: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 2: Excitation Controller

G1

G2

G3

G4 G5

G6

G7

G8

G9

G10

Page 82: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 2: Excitation Controller

Centralized optimal controller

Network

real-time

phasor

data

Optimal

Controller

Control

vector

for all

generator

excitation

and governor

systems

Page 83: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 2: Excitation Controller

All generator angles plotted with G10 angle as reference.

Control law 1: Without optimal feed-back vector

Control law 2: Optimal controller vector feed-back

d1

t (seconds) 5

d2

d3

d4

Page 84: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 3: Power System Stabilizer

AVR

AVR

AVR

AVR

Phasor

feed-

back

PSS

Control modes:

1. AVR alone

2. PSS on one machine

3. Phasor feed-back on one machine

100 ms

fault cleared

Page 85: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 3: Power System Stabilizer

Small signal analysis for tie flows of 158 MW

Mode Frequency Damping ratio Mode shape

-0.5977j7.0365 1.1199 0.0849 local area 1

-0.6060j7.2470 1.1534 0.0833 local area 2

+0.0296j4.1784 0.665 -0.0071 inter-area

0 Real

Imagin

ary

158 MW 50 MW

Eigenvalues

Page 86: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 3: Power System Stabilizer

MW

tie

-lin

e

Time

1. AVR alone

2. PSS on one machine

3. Phasor feed-back on one machine

Page 87: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Example 4: FACTS controller

G1

G2 G3

TCSC Phasor

feed-

back

• Simulation scenario:

- Determine loading levels which are dynamically

unstable

- Use phasor feedback to stabilize that operating

condition

Page 88: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

References:

(1) Niusha Rostamkolai, Ph.D. dissertation, Virginia Tech 1986,

“Adaptive Optimal Control of AC/DC Systems.

(2) N. Rostamkolai, A.G. Phadke, J.S. Thorp, W.F. Long, “Measurement

based optimal control of high voltage AC/DC systems”, IEEE Trans.

on Power Systems, Vol. 3 No. 3, August 1988, pp 1139-1145.

(3) Edgardo Manansala, Ph.D. dissertation, Virginia Tech August 1989,

“Adaptive power system control”.

(4) Edgardo C. Manansala, A.G. Phadke, “An optimal centralized

controller with nonlinear voltage control”, Electric Machines and

Power Systems, 19, 1991, pp 139-156.

(5) L. Mili, T. Baldwin, A.G. Phadke, “Phasor measurements for voltage

and transient stability monitoring and control”, Workshop on

Application of advanced mathematics to Power Systems, San

Francisco, Sept. 4-6, 1991.

(6) A.F. Snyder, N. Hadjsaid, D. Georges, L. Mili, A.G. Phadke,

O. Faucon, S. Vitet, “Inter-area oscillation damping with power

system stabilizers and synchronized phasor measurements”,

PowerCon 1998, China.

(7) M.A. Smith, “Improved Dynamic Stability Using FACTS devices with

phasor measurement feedback”, MS Thesis, Virginia Tech, 1994.

Page 89: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Multi-infeed HVDC Systems in China

North China

South

Northeast

Tibet

Northwest

Central ChinaEast

China

Hainan

Shanghai

Tianshengqiao

Gezhouba

Three-Gorge

Kunming

Wuhan

Chinese

Taiwan

Five HVDC links Terminating in

China Southern POWER GRID

Guangzhou

11.4% annual growth in GDP –doubling time 6.42 years

16 times bigger in less than 26 years

Page 90: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

WAMS Based Wide-area Coordinated

Modulation Control of Multi-infeed HVDC

YN

GZ

GX

GZ

Control signals

control server

PMU signal

Control Unit

Increase the damping of inter-area oscillation in CSG

Page 91: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Wide-area Coordinated HVDC Control System

– Control Unit in Converter Substation

Control Unit

PMU

GPS

Communication

Interface

Page 92: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

Wide-area Coordinated HVDC Control System

– Centralized Control Server

Event Archives Real-time Control Server

Page 93: PHASOR MEASUREMENT UNITS, WAMS, AND THEIR … · 2017. 8. 2. · A.G. Phadke Virginia Tech, Blacksburg, VA, USA Seminario Internacional de Medición Fasorial Sincronizada - Medellin

7. CONCLUSIONS

• PMUs have introduced a game-changing technology in power

system engineering.

• Power grids throughout the world have launched ambitious

programs to introduce WAMS on their systems.

• State Estimation will see the first applications.

• Instrument transformer calibration, network parameter

estimation will likely be the next steps.

• Protection and control are likely to be tried on an

experimental basis, before they are integrated in the normal

power system EMS applications.