PERT NETWORK-Summery Sheet

NIT - 164/PR/NBPDCL/2014 KATIHAR

CONTRACTOR: ENERGO ENGINEERING PROJECTS LTD Date : 30/09/2014

LOA Nos.: Supply: 2732/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 1st Revision

Erection: 2733/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 2nd Revision Date : 31/10/2014

2014 2015 2016

Sl.

No.Item Description Unit

LOA

Quantity

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

Kick off Activities

1 Signing of contract

2 Site Office establishment

3 Deployment of Manpower

4Detail scope of work -DPR by

NBPDCL

Part-

I(c)New PSS

1Handing over of suitable land by

NBPDCL for New SubstationNos 9

2 Engineering and Design

3 Submission of construction drawings

4 Approval of construction drawings

5 Development of Land

6 Civil construction

7Submission of Vendor / GTP of

equipments & other items

8Approval of Vendor / GTP of

equipments & other items

9 Manufacturing ,Inspection & Supply

10Erection /installation/testing &

commissioning 1 1 1 1 1 1 1 1 1

Part-

II33 KV Line KM 195

1Fixation of source point and

allocation of 33KV Bay by NBPDCL

2Submission of survey/construction

drawings

3Approval of survey/construction

drawings

4Submission of Vendor / GTP of

equipments & other items

5Approval of Vendor / GTP of

equipments & other items

6 Manufacturing ,Inspection & Supply

7Erection /installation/testing &

commissioning 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15

Part-

III11 KV Line KM 1100

1Submission of survey/construction

drawings

2Approval of survey/construction

drawings

3Submission of Vendor / GTP of

equipments & other items

Date : 16/10/2014

Page 1 of 38

Page 3: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

2014 2015 2016

Sl.

No.Item Description Unit

LOA

Quantity

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

4Approval of Vendor / GTP of

equipments & other items

5 Manufacturing ,Inspection & Supply

6Erection /installation/testing &

commissioning 15 30 50 50 50 50 50 50 55 55 75 75 75 75 75 75 75 75 45.25

Part-

IV

New Distribution Transformer

SubstationSet 1738

1Submission of survey/construction

drawings

2Approval of survey/construction

drawings

3Submission of Vendor / GTP of

equipments & other items

4Approval of Vendor / GTP of

equipments & other items

5 Manufacturing ,Inspection & Supply

6Erection /installation/testing &

commissioning 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53

Part-

VLT Lines KM 1390.5

1Submission of survey/construction

drawings

2Approval of survey/construction

drawings

3Submission of Vendor / GTP of

equipments & other items

4Approval of Vendor / GTP of

equipments & other items

5 Manufacturing ,Inspection & Supply

6Erection /installation/testing &

commissioning 30 30 30 65 65 75 75 85 85 85 85 85 85 85 85 85 85 85 85.5

Part-

VIIPSS-Augmentation PSS 5

1Submission of SLD/LAYOUT &

proposal

2Approval of SLD/LAYOUT & proposal

3 Submission of construction drawings

4 Approval of construction drawings

5 Civil construction

6Submission & approval of Vendor /

GTP of equipments & other items

7 Manufacturing ,Inspection & Supply

8Erection /installation/testing &

commissioning 1 1 1 1 1

Part-

XBPL Connection Nos. 62068

1Handing over of BPL List of village by

NBPDCL

2Submission of Vendor / GTP of

equipments & other items

3Approval of Vendor / GTP of

equipments & other itemsPage 2 of 38

Page 4: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

2014 2015 2016

Sl.

No.Item Description Unit

LOA

Quantity

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

4 Manufacturing ,Inspection & Supply

5Erection /installation/testing &

commissioning 200 500 500 1500 1500 2000 2500 3500 3500 3500 3500 4500 4500 4500 4500 4500 4500 4500 4500 3368

Village ElectrificationHanding over of Villages

UE Nos 1271 20 25 45 67 65 60 60 60 85 85 85 85 80 75 75 125 125 49

PE Nos 269 5 8 10 15 15 15 15 15 15 15 20 25 25 25 25 21

Total Nos 1540 20 25 50 75 75 75 75 75 100 100 100 100 100 100 100 150 150 70

NOTE: The above pert chart is subject to timely approval of vendors/drawings, inspections, issuance of DI/road permit, releasing of payment, arranging statuary clearances, Right of Way and discharging of other contractual obligations by NBPDCL

Page 3 of 38

Page 5: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

CONTRACTOR: ENERGO ENGINEERING PROJECTS LTDLOA Nos.: Supply: 2732/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 Erection: 2733/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

PART-I (a)33/11 KV Substation Works (2X10 MVA) - Partly

outdoor type substation No. 0

1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil, Buchholtz relay, breather,

OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on

bushing end), isolating link, isolation with insulators}, Vent explosion

plug, control wiring between sensing equipment and marshalling box,

cable supporting tray on the body of transformer, transformer wheels,

LV/HV bushing etc as required as per technical specifications, approved

drawings and scope of the work.

a 10 MVA with off load tap changer No 2 0

0

2 100 KVA, 11/0.433 kV, 3 ph, 50 Hz, ONAN,copper wound, CRGO core,

outdoor type Station Transformer along with transformer oil and all

accessories as required as per technical specifications, scope of works and

approved drawings.

No 1 0

0

3 DP structure comprising of MS galvanised 2 Nos,2x175x85mm double

welded 8 meter long RS joists, transformer base channels, 11KV HG Fuse

structure, 11 KV Isolators, 11 KV Station Type LAs structures etc including

hardware etc all complete for erection of 11/0.433 KV Station

Transformer.

Set 1 0

0

4 Galvanised Gantry structures made of Lattice structures of equal angles

sections, flat as per approved drawings. State practices are to be adopted

in the design. All structural steel members and bolts shall be galvanized

after fabrication as per IS:4759 and zinc coating shall not be less than

610gm/sq. meter for all structural steel members. All L45x45x5 will have

23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring

washers are to be used under each nut, structural steel shall conform to IS

2026. All weld shall be 6mm filled weld unless specified otherwise. All nuts

and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be

as per IS 2016 & spring washers shall be IS: 3063.

MT 16 0

0

5

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1

Amps, 3 Nos outdoor type Current Transformers along with junction box

(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting

structures, permanent maintenance platform, marshalling box etc

required as per technical specifications, scope of works and approved

drawings

Set 4 0

0

6 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic

Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation

relays and other components etc as per approved drawings, specifications

and scope of works controlling:

0

a 33 kV feeder VCB with Static Tri-Vector Energy Meter No 2 0

b Power transformer 33 kV VCB with Static Tri-Vector Energy Meter with

differential relayNo 2 0

0

7 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings (without earth switch)

Set 7 0

0

8 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set= 3 nos.) Set 4 0

0

9 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set= 3

nos.)

Set 11 0

0

10 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos

indoor type Current Transformer,& PT indoor mounting type control panel

for Transformer breaker, control cabling between VCB and indoor control

panel and required accessories, A-meter, volt-meter, E/F & O/C , Relay &

accessories complete as per Technical specification( Volume-II) for

transformer breaker protection

Set 2 0

0

11 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor

type Current Transformer & PT, indoor mounting type control panel for

feeder protection, control cabling between VCB and indoor control panel

and required accessories, A-meter, volt-meter, 3-phase electronic energy

meter, E/F & O/C , Relay & accessories complete as per Technical

specification( Volume-II) for feeder breaker protection

Set 10 0

0

PERT NETWORK

NIT - 164/PR/NBPDCL/2014 KATIHAR

Date : 27/10/2014

Page 4 of 38

Page 6: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

12 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor

type Current Transformer & PT, indoor mounting type control panel for

bus coupler, control cabling between VCB and indoor control panel and

required accessories, A-meter, volt-meter, 3-phase electronic energy

meter, E/F & O/C , Relay & accessories complete as per specification(

Volume-II) for bus coupler protection

Set 1 0

0

13

30V, 100 AH Pb Acid battery, battery stand made of teak wood duly

painted with anti rusting paint, battery insulators, inter-battery wiring

using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal

connectors, & all other accessories and connectors as per technical

specifications, approved drawings and scope of works.

Set 1 0

0

14 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave

rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per technical specifications, approved drawings and scope of works. set 1 0

0

15 433V, ACDB along with three phase-neutral voltmeter, three phase

ammeter and Selector switches, 200 Amps TPN switch fuse unit as

incomer, 32 Amps TPN switches as outgoing feeders suited for number of

control panels, nos of VCB kiosk panel, having 20% spare outgoing

feeders, mounting arrangements etc as per technical specifications,

approved drawings and scope of works.

Set 1 0

0

16 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including

hardware fittings, hardware etc 0

a Wolf conductor (150 Sq. mm) km 0.3 0

b 50 mm dia Al. pipe Mtr. 50 0

0

17 Earthing & Grounding conductor as per Approved Electrical Layout for each

sub-station with 0

a 75 x 8 mm MS flat for ground mat MT 2.00 0.00

b 50 x 6 mm Galvanized GS flat (risers) MT 2.00 0.00

c 25mm dia MS rod 3 m long for earth mat MT 0.50 0.00

0

18 40 mm dia., 3000 mm long GI pipe earth electrode with test link, as per

technical specification. (for Power Transformer Neutral, Station

Transformer Neutral and Lightening Arresters direct earthing) Set 50 0

0

19 33 and 11 KV Insulator - Pin, Post and Disc insulators along with

Hardware & accessories suitable for Wolf conductors as per approved

drawings & specifications. (33 KV Disc Insulator of 70 KN, 1 set 33 KV Disc

Insulator=3 nos., for 33 KV Post Insulator 1 set = 2 nos.)

Set 1 0

0

20 Station Lighting System complete for switchyard, control room building,

main gate as per scope of work complete, 0

a Internal Electrification works of control room Set 1 0

b External Electrification including power receptacles, station yard lighting

with 4 Nos lightening mast (fitted with 2x250 watts SON fittings) made of

12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation

410 – SP - 60, complete as per technical specifications, approved drawings

and scope of the work.

Set 1 0

0

21 Fire Fighting Equipment comprises of Dry Chemical Powder Type (6 Kg) for

control room, CO2 Type of 4.5Kg Capacity for Control Room, two sets of

fire buckets set including their stand as per technical specifications, scope

of works and approved drawings (one sets= 3 nos. of fire Buckets)

Set 1 0

0

22 Power Cables including their termination materials like glands, lugs etc. 0

a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.07 0

b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.05 0

c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.75 0

0

23 Control cables including their termination materials like glands, lugs etc. 0

a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.2 0

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 1 0

c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.6 0

0

24 Outdoor type Distribution Box for station transformer comprising 200 A

incomer – switch fuse unit, 6 Nos Outgoing feeder – 63 A capacity switch

Fuse unit, 2 Nos 32 A Fuse switch fuse units, three phase, 63A, timer

control yard lighting contactor circuit, 3 phase, electronic Energy meter

for transformer power supply metering with suitable CT, 1 no., 20 A

Industrial socket and switch for local power supply requirements,

mounting channel clamps and hardware as per scope of work, technical

specifications and approved drawings,

Set 1 0

0

Page 5 of 38

Page 7: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

25.a 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings

Set 10 0

25..b 12 kV, 200A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings

Set 1 0

0

26 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential

Transformer including accessories etc., complete as per technical

specifications, approved drawings and scope of the works. Set 2 0

0

27 Substation Tools and Plants like megger, earth tester, Multimeter, Tong

tester, D-spanners, screw drivers, earthing rods, earth mat etc as required

as per scope of work.

Set per

PSS1 0

0

28 11 KV, XLPE, 3 phase power cable, aluminium conductor, stranded 0

1Cx 300 sqmm ( Un-armored) km 0.72 0.00

3Cx 185sqmm (armored) km 1.10 0.00

0

29 Cable termination kit suitable for termination in transformer cable box/

breaker panel/ outdoor 11 KV terminals complete with all accessories etc. 0

1Cx 300 sqmm set 18 0

3Cx 185sqmm set 24 0

0

30 3 Phase 11 KV HG Fuse complete 200 A capacity as per technical

specificationsSet 1 0

Sub Total

0

PART-I (b)33/11 KV Substation Works (3X5 MVA) - Partly

outdoor type substation No. 0

1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil, Buchholtz relay, breather,

OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on

bushing end), isolating link, isolation with insulators}, Vent explosion

plug, control wiring between sensing equipment and marshalling box,

cable supporting tray on the body of transformer, transformer wheels,

LV/HV bushing etc as required as per technical specifications, approved

drawings and scope of the work.

a 5 MVA with off load tap changer No 3 0

0

2 100 KVA, 11/0.433 kV, 3 ph, 50 Hz, ONAN,copper wound, CRGO core,

outdoor type Station Transformer along with transformer oil and all

accessories as required as per technical specifications, scope of works and

approved drawings.

No 1 0

0

3 DP structure comprising of MS galvanised 2 Nos,2x175x85mm double

welded 8 meter long RS joists, transformer base channels, 11KV HG Fuse

structure, 11 KV Isolators, 11 KV Station Type LAs structures etc including

hardware etc all complete for erection of 11/0.433 KV Station

Transformer.

Set 1 0

0

4 Galvanised Gantry structures made of Lattice structures of equal angles

sections, flat as per approved drawings. State practices are to be adopted

in the design. All structural steel members and bolts shall be galvanized

after fabrication as per IS:4759 and zinc coating shall not be less than

610gm/sq. meter for all structural steel members. All L45x45x5 will have

23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring

washers are to be used under each nut, structural steel shall conform to IS

2026. All weld shall be 6mm filled weld unless specified otherwise. All nuts

and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be

as per IS 2016 & spring washers shall be IS: 3063.

MT 16 0

0

5

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1

Amps, 3 Nos outdoor type Current Transformers along with junction box

(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting

structures, permanent maintenance platform, marshalling box etc

required as per technical specifications, scope of works and approved

drawings

No 5 0

0

6 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic

Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation

relays and other components etc as per approved drawings, specifications

and scope of works controlling:

0

a 33 kV feeder VCB with Static Tri-Vector Energy Meter No 2 0

b Power transformer 33 kV VCB with Static Tri-Vector Energy Meter No 3 0

0

7 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings (without earth switch)

Set 9 0

0

Page 6 of 38

Page 8: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

8 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set= 3 nos.) Set 5 0

0

9 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set= 3

nos.)

Set 10 0

0

10 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos

indoor type Current Transformer,& PT indoor mounting type control panel

for Transformer breaker, control cabling between VCB and indoor control

panel and required accessories, A-meter, volt-meter, Relay & accessories

complete as per specifications for transformer breaker protection

Set 3 0

0

11 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos

indoor type Current Transformer,& PT indoor mounting type control panel

for Transformer breaker, control cabling between VCB and indoor control

panel and required accessories, A-meter, volt-meter, E/F & O/C , Relay &

accessories complete as per Technical specification( Volume-II) for

transformer breaker protection

Set 9 0

0

12 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor

type Current Transformer & PT, indoor mounting type control panel for

bus coupler, control cabling between VCB and indoor control panel and

required accessories, A-meter, volt-meter, 3-phase electronic energy

meter, E/F & O/C , Relay & accessories complete as per specification(

Volume-II) for bus coupler protection

Set 2 0

0

13

30V, 100 AH Pb Acid battery, battery stand made of teak wood duly

painted with anti rusting paint, battery insulators, inter-battery wiring

using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal

connectors, & all other accessories and connectors as per technical

specifications, approved drawings and scope of works.

Set 1 0

0

14 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave

rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per technical specifications, approved drawings and scope of works. set 1 0

0

15 433V, ACDB along with three phase-neutral voltmeter, three phase

ammeter and Selector switches, 200 Amps TPN switch fuse unit as

incomer, 32 Amps TPN switches as outgoing feeders suited for number of

control panels, nos of VCB kiosk panel, having 20% spare outgoing

feeders, mounting arrangements etc as per technical specifications,

approved drawings and scope of works.

No 1 0

0

16 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including

hardware fittings, hardware etc 0

a Wolf conductor (150 Sq. mm) km 0.45 0

b 50 mm dia Al. pipe Mtr. 50 0

0

17 Earthing & Grounding conductor as per Approved Electrical Layout for each

sub-station with 0

a 75 x 8 mm MS flat for ground mat MT 2.5 0

b 50 x 6 mm Galvanized GS flat (risers) MT 2.5 0

c 25mm dia MS rod 3 m long for earth mat MT 0.5 0

0

18 40 mm dia., 3000 mm long GI pipe earth electrode with test linkas per

technical specification. (for Power Transformer Neutral, Station

Transformer Neutral and Lightening Arresters direct earthing) Set 50 0

0

19 33 and 11 KV Insulator - Pin, Post and Disc insulators along with

Hardware & accessories suitable for Wolf conductors as per approved

drawings & specifications. (33 KV Disc Insulator of 70 KN, 1 set 33 KV Disc

Insulator=3 nos., for 33 KV Post Insulator 1 set = 2 nos.)

Set 1 0

0

20 Station Lighting System complete for switchyard, control room building,

main gate as per scope of work complete, 0

a Internal Electrification works of control room Set 1 0

b External Electrification including power receptacles, station yard lighting

with 4 Nos lightening mast (fitted with 2x250 watts SON fittings) made of

12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation

410 – SP - 60, complete as per technical specifications, approved drawings

and scope of the work.

Set 1 0

0

21 Fire Fighting Equipment comprises of Dry Chemical Powder Type (6 Kg) for

control room, CO2 Type of 4.5Kg Capacity for Control Room, two sets of

fire buckets set including their stand as per technical specifications, scope

of works and approved drawings (one sets= 3 nos. of fire Buckets)

Set 1 0

0

22 Power Cables including their termination materials like glands, lugs etc. 0

a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.07 0

Page 7 of 38

Page 9: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.05 0

c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.75 0

0

23 Control cables including their termination materials like glands, lugs etc. 0

a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.2 0

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 1 0

c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.7 0

0

24 Outdoor type Distribution Box for station transformer comprising 200 A

incomer – switch fuse unit, 6 Nos Outgoing feeder – 63 A capacity switch

Fuse unit, 2 Nos 32 A Fuse switch fuse units, three phase, 63A, timer

control yard lighting contactor circuit, 3 phase, electronic Energy meter

for transformer power supply metering with suitable CT, 1 no., 20 A

Industrial socket and switch for local power supply requirements,

mounting channel clamps and hardware as per scope of work, technical

specifications and approved drawings,

Set 1 0

0

25.a 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings

Set 9 0

25..b 12 kV, 200A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings

Set 1 0

0

26 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential

Transformer including accessories etc., complete as per technical

specifications, approved drawings and scope of the works. Set 2 0

0

27 Substation Tools and Plants like megger, earth tester, Multimeter, Tong

tester, D-spanners, screw drivers, earthing rods, earth mat etc as required

as per scope of work.

Set per

PSS1 0

0

28 11 KV, XLPE, 3 phase power cable, aluminium conductor, stranded 0

1Cx 300 sqmm ( Un-armored) km 0.72 0

3Cx 185sqmm (armored) km 1.1 0

0

29 Cable termination kit suitable for termination in transformer cable box/

breaker panel/ outdoor 11 KV terminals complete with all accessories etc. 0

1Cx 300 sqmm set 24 0

3Cx 185sqmm set 22 0

0

30 3 Phase 11 KV HG Fuse complete 200 A capacity as per technical

specificationsSet 1 0

0

Sub total

PART-I (c)33/11 KV Substation Works -2 x 5 MVA, Partly

outdoor type substation No. 9

1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil, Buchholtz relay, breather,

OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on

bushing end), isolating link, isolation with insulators}, Vent explosion

plug, control wiring between sensing equipment and marshalling box,

cable supporting tray on the body of transformer, transformer wheels,

LV/HV bushing etc as required as per technical specifications, approved

drawings and scope of the work.

a 5 MVA with off load tap changer No 2 18 2 2 2 1 2 1 2 2 2 2

0

2 100 KVA, 11/0.433 kV, 3 ph, 50 Hz, ONAN,copper wound, CRGO core,

outdoor type Station Transformer along with transformer oil and all

accessories as required as per technical specifications, scope of works and

approved drawings.

No 1 9

1 1 1 1 1 1 1 1 1

0

3 DP structure comprising of MS galvanised 2 Nos,2x175x85mm double

welded 8 meter long RS joists, transformer base channels, 11KV HG Fuse

structure, 11 KV Isolators, 11 KV Station Type LAs structures etc including

hardware etc all complete for erection of 11/0.433 KV Station

Transformer.

Set 1 9

1 1 1 1 1 1 1 1 1

0

Page 8 of 38

Page 10: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

4 Galvanised Gantry structures made of Lattice structures of equal angles

sections, flat as per approved drawings. State practices are to be adopted

in the design. All structural steel members and bolts shall be galvanized

after fabrication as per IS:4759 and zinc coating shall not be less than

610gm/sq. meter for all structural steel members. All L45x45x5 will have

23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring

washers are to be used under each nut, structural steel shall conform to IS

2026. All weld shall be 6mm filled weld unless specified otherwise. All nuts

and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be

as per IS 2016 & spring washers shall be IS: 3063.

MT 14 126.00 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 6

0

5

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1

Amps, 3 Nos outdoor type Current Transformers along with junction box

(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting

structures, permanent maintenance platform, marshalling box etc

required as per technical specifications, scope of works and approved

drawings

Set 4 36 4 4 4 4 4 4 4 4 4

0

6 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic

Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation

relays and other components etc as per approved drawings, specifications

and scope of works controlling:

0

a 33 kV feeder VCB with Static Tri-Vector Energy Meter No 2 18 2 2 2 2 2 2 2 2 2

b Power transformer 33 kV VCB with Static Tri-Vector Energy Meter No 2 18 2 2 2 2 2 2 2 2 2

0

7 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings (without earth switch)

Set 7 63

7 7 7 7 7 7 7 7 7

0

8 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set= 3 nos.) Set 4 364 4 4 4 4 4 4 4 4

0

9 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set= 3

nos.)

Set 7 637 7 7 7 7 7 7 7 7

0

10 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos

indoor type Current Transformer,& PT indoor mounting type control panel

for Transformer breaker, control cabling between VCB and indoor control

panel and required accessories, A-meter, volt-meter, E/F & O/C , Relay &

accessories complete as per Technical specification( Volume-II) for

transformer breaker protection

Set 2 18 2 2 2 2 2 2 2 2 2

0

11 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor

type Current Transformer & PT, indoor mounting type control panel for

feeder protection, control cabling between VCB and indoor control panel

and required accessories, A-meter, volt-meter, 3-phase electronic energy

meter, E/F & O/C , Relay & accessories complete as per Technical

specification( Volume-II) for feeder breaker protection

Set 6 54 6 6 6 6 6 6 6 6 6

0

12 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor

type Current Transformer & PT, indoor mounting type control panel for

bus coupler, control cabling between VCB and indoor control panel and

required accessories, A-meter, volt-meter, 3-phase electronic energy

meter, E/F & O/C , Relay & accessories complete as per specification(

Volume-II) for bus coupler protection

Set 1 9 1 1 1 1 1 1 1 1 1

0

13

30V, 100 AH Pb Acid battery, battery stand made of teak wood duly

painted with anti rusting paint, battery insulators, inter-battery wiring

using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal

connectors, & all other accessories and connectors as per technical

specifications, approved drawings and scope of works.

Set 1 9 1 1 1 1 1 1 1 1 1

0

14 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave

rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per technical specifications, approved drawings and scope of works. set 1 9 1 1 1 1 1 1 1 1 1

0

15 433V, ACDB along with three phase-neutral voltmeter, three phase

ammeter and Selector switches, 200 Amps TPN switch fuse unit as

incomer, 32 Amps TPN switches as outgoing feeders suited for number of

control panels, nos of VCB kiosk panel, having 20% spare outgoing

feeders, mounting arrangements etc as per technical specifications,

approved drawings and scope of works.

Set 1 9 1 1 1 1 1 1 1 1 1

0

16 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including

hardware fittings, hardware etc 0

a Wolf conductor (150 Sq. mm) km 0.3 2.70 1.7 1

b 50 mm dia Al. pipe Mtr. 50 450.00 50 50 50 50 50 50 50 50 50

0

Page 9 of 38

Page 11: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

17 Earthing & Grounding conductor as per Approved Electrical Layout for each

sub-station with 0

a 75 x 8 mm MS flat for ground mat MT 2 18.00 2 2 2 2 2 2 2 2 2

b 50 x 6 mm Galvanized GS flat (risers) MT 2 18.00 2 2 2 2 2 2 2 2 2

c 25mm dia MS rod 3 m long for earth mat MT 0.5 4.50 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

0

18 40 mm dia., 3000 mm long GI pipe earth electrode with test link,as per

technical specification. (for Power Transformer Neutral, Station

Transformer Neutral and Lightening Arresters direct earthing) Set 40 360 40 40 40 40 40 40 40 40 40

0

19 33 and 11 KV Insulator - Pin, Post and Disc insulators along with

Hardware & accessories suitable for Wolf conductors as per approved

drawings & specifications. (33 KV Disc Insulator of 70 KN, 1 set 33 KV Disc

Insulator=3 nos., for 33 KV Post Insulator 1 set = 2 nos.)

Set 1 9 1 1 1 1 1 1 1 1 1

0

20 Station Lighting System complete for switchyard, control room building,

main gate as per scope of work complete, 0

a Internal Electrification works of control room Set 1 9

1 1 1 1 1 1 1 1 1

b External Electrification including power receptacles, station yard lighting

with 4 Nos lightening mast (fitted with 2x250 watts SON fittings) made of

12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation

410 – SP - 60, complete as per technical specifications, approved drawings

and scope of the work.

Set 1 9

1 1 1 1 1 1 1 1 1

0

21 Fire Fighting Equipment comprises of Dry Chemical Powder Type (6 Kg) for

control room, CO2 Type of 4.5Kg Capacity for Control Room, two sets of

fire buckets set including their stand as per technical specifications, scope

of works and approved drawings (one sets= 3 nos. of fire Buckets)

Set 1 9

1 1 1 1 1 1 1 1 1

0

22 Power Cables including their termination materials like glands, lugs etc. 0

a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.07 0.63

0.63

b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.05 0.45

0.45

c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.5 4.50

4.5

0

23 Control cables including their termination materials like glands, lugs etc. 0

a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.2 1.80

1.8

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.7 6.30

6.3

c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.5 4.50

4.5

0

24 Outdoor type Distribution Box for station transformer comprising 200 A

incomer – switch fuse unit, 6 Nos Outgoing feeder – 63 A capacity switch

Fuse unit, 2 Nos 32 A Fuse switch fuse units, three phase, 63A, timer

control yard lighting contactor circuit, 3 phase, electronic Energy meter

for transformer power supply metering with suitable CT, 1 no., 20 A

Industrial socket and switch for local power supply requirements,

mounting channel clamps and hardware as per scope of work, technical

specifications and approved drawings,

Set 1 9 1 1 1 1 1 1 1 1 1

0

25.a 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings

Set 6 54 6 6 6 6 6 6 6 6 6

25..b 12 kV, 200 A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings

Set 1 9 1 1 1 1 1 1 1 1 1

26 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential

Transformer including accessories etc., complete as per technical

specifications, approved drawings and scope of the works. Set 2 18

2 2 2 2 2 2 2 2 2

0

27

Substation Tools and Plants like megger, earth tester, Multimeter, Tong

tester, D-spanners, screw drivers, earthing rods, earth mat etc as required

as per scope of work.

Set per

PSS1 9

1 1 1 1 1 1 1 1 1

0

28 11 KV, XLPE, 3 phase power cable, aluminium conductor, stranded 0

1Cx 300 sqmm ( Un-armored)km 0.54 4.86

4.86

3Cx 185sqmm (armored)km 0.7 6.30

3 3.3

29 Cable termination kit suitable for termination in transformer cable box/

breaker panel/ outdoor 11 KV terminals complete with all accessories etc. 0

1Cx 300 sqmm set 18 162 18 18 18 18 18 18 18 18 18

Page 10 of 38

Page 12: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

3Cx 185sqmm set 14 126 14 14 14 14 14 14 14 14 14

0

30 3 Phase 11 KV HG Fuse complete 200 A capacity as per technical

specificationsSet 1 9

1 1 1 1 1 1 1 1 1

0

Sub total

PART II 33 KV Lines Dog 195

1 Support for 33 KV overhead line

a 9 meter/400 KG PSC Poles with RCC Base plate

No 16 3120100 100 100 100 200 200 200 200 250 250 250 250 200 200 200 200 120

b13 m long RS Joist 152x152 mm with RCC Base plate

No 1 19520 20 20 20 20 20 20 20 20 15

0

2

Galvanized pre-fabricated steel materials- Channels, angle, flats for over

head structures as per technical specification, approved drawings and

scope of work.

MT 0.67 130.65010 10 10 10 10 10 10 10 10 10 10 10.65 10

0

3

ACSR DOG Conductor of size 6/4.72 mm + 7/1.57 mm (100 mm² Al. Area)

including jointing sleeves and helicon formed fittings etc as required as

per technical specification, approved drawings and scope of work. km 3.09 602.55

50 50 50 50 50 50 50 50 50 50 50 52.55

0

4Galvanized Steel Nuts, bolts and washers as per technical specification,

approved drawings and scope of work. MT 0.024 4.680

2 2.68

0

5

33 KV porcelain Disc insulator 70 KN along with HW fittings as per

technical specification, approved drawings and scope of work.

(1set=3nos.)

Set 6 1170100 100 100 100 100 100 100 100 100 70 100 100

0

633 KV porcelain Pin Insulators with GI PIN as per technical specification,

approved drawings and scope of work. Set 48 9360

500 500 500 500 500 500 500 750 750 750 750 750 750 750 610

0

7

40 mm dia., 3000 mm long GI pipe earth electrode with test link as per

technical specification, approved drawings and scope of work, set 1 19520 20 20 20 20 20 20 20 20 15

0

8Coil earthing as per technical specification, approved drawings and scope

of work. Set 15 2925

195 100 100 100 100 200 200 200 200 200 200 200 200 200 200 200 200 125

0

98 SWG GI wire for earthing as per technical specification, approved

drawings and scope of work. MT 0.003 0.585

0.585

0

10

Galvanized Stay set with 50x8 mm stay clamp, HT stay guy insulator, nut

bolts, 2 Nos turn buckles, 1.8 m long, 20 mm diameter solid GS stay rod &

7/4.00 mm dia GI stranded wire complete as per technical specification,

approved drawings and scope of work.

Set 6 1170

100 100 100 100 100 100 100 100 100 70 100 100

0

11

36kV, 630A, 25kA, 3-ph, 3 Pin type, Vertical Mounting type, Gang

Operated, AB Switch along with Support Insulators, Base Channel down

Pipe, Arcing Horns etc. complete as per technical specifications, scope of

works and approved drawings

Set 0.1 20

100 100 100 100 100 100 100 100 100 70 100 100

Sub-Total (II)

Rabb

it405.00

Wea

sel695.25

1100.251 Support for 11 KV overhead line

a 8 m/200 kgs PSC Poles with RCC Base plate No 16.75 18429 400 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1029

b13 m long RS Joist 152x152 mm with RCC Base plate

No 0.25 27520 20 20 20 20 20 20 20 20 20 20 20 20 15

2

Galvanized pre-fabricated steel materials- channel, angle, flats for over

head structures as per technical specification, approved drawings and

scope of work.

MT 0.34 374.08510 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 24.08

0.000

3Galvanized Steel Nuts, Bolts with Washers as per technical specification,

approved drawings and scope of work. MT 0.0155 17.054

1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

0

4

ACSR Conductors with Jointing sleeves, binding materials etc as required

as per technical specification, approved drawings and scope of work. 0

a 7/3.35 mm (50 mm² Al. Area) ( Rabbit) km 3.09 1251.45 50 100 100 100 150 150 150 150 150 151.45

b7/2.59 mm (30 mm² Al. Area) (weasel)

km 3.09 2148.32 100 200 200 300 300 300 300 300 148.32

0

5Porcelain Insulators with mounting hardware, fittings as per technical

specification, approved drawings and scope of work. 0

11 KV 45 KN Disc Insulator with hardware fittings (1set=1no.) set 6 6602 200 300 300 300 300 500 500 500 500 500 300 300 300 300 300 300 300 300 302

11 KV Pin insulators with GI Pin set 48 52812 1000 1500 1500 1500 3000 3000 3000 3000 3000 3000 4000 4000 3000 3000 3000 3000 3000 3000 3312

0

PART III

11 KV Lines

Page 11 of 38

Page 13: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

6

Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut

bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &

7.3.15 mm dia GI stranded wire etc as required as per technical

specification, approved drawings and scope of work.

Set 6 6602

200 300 300 300 300 500 500 500 500 500 300 300 300 300 300 300 300 300 302

0

7 Earthing 0

a

40 mm dia., 3000 mm long GI pipe earth electrode with test link as per

technical specification, approved drawings and scope of work, Set 1 1100 50 50 100 100 100 100 100 100 100 100 100 100

bCoil earthing as per technical specification, approved drawings and scope

of work. Set 15 16504

500 500 500 500 500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1004

c8 SWG GI wire for earthing as per technical specification, approved

drawings and scope of work. MT 0.003 3.301

1 1 1.3

0

8

12kV, 200A, 25kA for 3sec, 3-ph, 3 Pin type, Vertical Mounting type, Gang

Operated, AB Switch along with Support Insulators, Base Channel down

Pipe, Arcing Horns etc. complete as per technical specifications, scope of

works and approved drawings

Set 0.1 110 5 5 10 10 10 10 10 10 10 10 10 10

Sub-Total (III)

63 KVA 1402

100

KVA336

Total 1738

1Distribution Transformer with all accessories as per as per technical

specification, approved drawings and scope of work. Nos

aThree Phase 63 KVA

No 1 1402 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 102

b Three Phase 100 KVA No 1 336 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 26

2Distribution Class 11KV Lightening Arrester for DT as per technical

specification, approved drawings and scope of work. Set 1 1738

70 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128

3 Substation Support Nos

a8 Mtr/200 KG PSC Poles with base plate

No 2 3476 140 140 140 140 240 240 240 240 240 240 240 240 240 250 250 256

4

Galvanized pre-fabricated steel materials- channel, angle, flats for over

head structures as per technical specification, approved drawings and

scope of work.

MT 0.255 443.1917.85 17.85 17.85 17.85 30.60 30.60 30.60 30.60 30.60 30.60 30.60 30.60 30.60 31.88 31.88 32.64

5Galvanized Steel Nuts, Bolts with Washers as per technical specification,

approved drawings and scope of work. MT 0.016 27.808

1.12 1.12 1.12 1.12 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 2.00 2.00 2.05

6

Porcelain Insulators with hardware fittings, hardware etc as required as

per technical specification, approved drawings and scope of work.

a11 KV, Disc Insulator with hardware fittings

Set 3 5214210 210 210 210 360 360 360 360 360 360 360 360 360 375 375 384

7

12 kV, 200A, 3-ph, 3 Pin type, Vertical Mounting type, Gang Operated, AB

Switch along with Support Insulators, Base Channel down Pipe, Arcing

Horns etc. complete as per technical specifications, scope of works and

approved drawings

Sets 1 1738 70 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128

811KV,200 AMP 3 pole, HG fuse set for 3-ph DTs as per technical

specification, approved drawings and scope of work. Sets 1 1738

70 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128

9

LT Distribution box with metering, One no. TPMCCB and LT control

mechanism as per scope of the work, technical specifications and

approved drawings suitable for following transformer:

a Three Phase 63 KVA No 1 1402 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 102

bThree Phase 100 KVA No 1 336 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 26

10

3 Nos pipe earthing using 40mm dia GI pipe 3000 mm long, as per IS 1161

and as per REC construction drawings as per approved drawings and

technical specifications,

Set 1 173870 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128

11

ACSR Rabbit Conductor for jumpering including PG Clamps, bi-metallic

connectors, hardware etc as per technical specification, approved

drawings and scope of work.

km 0.009 15.64215.642

12

XLPE Aluminium Cable Conductor, Stranded, unarmoured cable for

connection of transformer LV bushing to Distribution Box as per Scope of

work, technical specification and approved drawings:

0

a1CX50 sqm aluminium conductor cable for Three Phase 63 KVA

km 0.015 21.0310 11.03

b1Cx95 sqm aluminium conductor cable for Three Phase 100KVA

km 0.015 5.040 2 3.04

13MRI/CMRI for DT meter as per technical specifications and scope of the

work, Nos. 0.02 35

Sub-Total (IV)

ONE

PHASE556.2

THREE

PHASE834.3

Total 1390.5

1 Support for LT overhead Line

PART IVDistribution Transformer Substations

PART VLT Line

Page 12 of 38

Page 14: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

a8 m/200 Mg PSC Poles with RCC Base plate

No 21 29201500 500 1000 1000 1000 1000 1000 1000 1000 1500 1700 2000 2000 2000 2000 2000 2000 2000 2000 2001

0

2

Galvanized pre-fabricated steel materials - channel, angle, flats for over

head structures as per approved drawings, technical specifications and

scope of work

MT 0.02 27.811 1 1 1 1 1.25 1.25 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.75 1.75 1.81

3Nuts and Bolts with Washers as per approved drawings, technical

specifications and scope of workMT 0.001 1.3905

0.75 0.6405

4

Galvanised Stay Set with 50x8mm stay clamp, HT stay guy insulator, nut

bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod &

7/3.15 mm Dia GI stranded wire etc as requiredSet 7 9733.5

170 199 330 330 330 330 330 330 330 500 570 665 665 665 665 665 665 665 665 665

5 Earthing

Coil earthing as per technical specification, approved drawings and scope

of work. Set 5 6952.5

125 125 250 250 250 250 250 250 250 250 400 400 400 500 500 500 500 500 500 503

6

LT Line on AB Cables:(average span 40 m) including erection accessories

like Insulation Piercing Connectors, Anchoring Assembly, Suspension

Assembly, Service Clamp, Transformer Connection, Junction Sleeves and

Service Main Distribution boxes etc as required

a1-Phase ABC [1X16{Phase}+1x16 {Neutral}+{1x25 Messenger cum earth wire}] line

as per TS Km 1.03 572.886 10 10 20 20 20 20 20 20 20 30 30 40 40 40 40 40 40 40 40 32.886

b3-Phase ABC [3X50{Phase}+{1x35 Messenger cum earth wire}] line as per TS

Km 1.03 859.32915 15 35 35 35 35 35 35 35 35 55 55 55 55 55 55 55 55 55 54.329

Sub-Total (V)

PART VI Others

1 Line Crossing - Line to line / Road: Protective guarding as per REC construction standard drawing No A-1 to be provided

at locations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/

P&T lines etc. Supplying 2 Nos guarding cross arm made of ISMC 75 channel, 2 Nos

Y- guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 No earthing of

40mm dia GI pipe of 3 meter long, 8 SWG GI wires for earthing connection, 6 SWG

wire for guard wire, 8 SWG wire for cross lacing and 1 meter long extension piece of

ISMC 100 channel, MS clamps, hardware etc all complete including two coat red

oxide painting and two or more coats of aluminium oxide paint of reputed make.

SET 0.04 52 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3

Sub-Total

233 KV FEEDER BAY at 33/11 KV Grid Substations

using RS Joist supportsNo. 9

i

Supplying materials for extension of 33 KV feeder bay using 4 support (2 Joist

welded together to form a support) of 9 m long, 175 x 85 mm RS Joists Bus Bar

structure, 2x2 support ( 2 Joist welded together to form a support) of 9 m long

175x85 mm RS Joist supports each for Isolator and Metering equipment support

structure including provision of base plate (0.2x0.5x0.5m size), supporting galvanised

steel sections of channel, angle and flat, danger notice plate, 1 No. GI Pipe earthing,

4Nos spike earthing, earth connection with 50X5mm GS Flat & 8 SWG GI wires, PG

Clamps, ACSR WOLF conductors, insulators, clamps, channels, including line isolator

switch of 800 A & 3 Nos Station Class LAs etc as per specifications and tender

drawing complete as required,

SET 1 9 1 1 1 1 1 1 1 1 1

0

ii

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1

Amps, 3 Nos outdoor type Current Transformers along with junction box

(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting

structures, permanent maintenance platform, marshalling box etc

required as per technical specifications, scope of works and approved

drawings

SET 1 9 1 1 1 1 1 1 1 1 1

iii 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic

Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation

relays and other components etc as per approved drawings, specifications

and scope of works controlling: a 33 kV feeder VCB with Static Tri-Vector Energy Meter

No 1 91 1 1 1 1 1 1 1 1

Sub Total

311 KV FEEDER BAY at 33/11 KV Grid Substations

using RS Joist Supports No. 6

i

Supplying materials for extension of 11 KV Feeder bay using 4 Nos. (2 Joist welded

together to form a support) 9 m long, 175 x 85 mm RS Joist structure including

provision of base plate (0.2x0.5x0.5m size), danger notice plate, 1 No GI Pipe

earthing, 4 Nos Spike Earthing, earth connection with 50X6 mm GS flat & 8 SWG GI

wire, PG Clamps,ACSR Wolf conductors, insulators, clamps, channels etc as per

specifications complete as required including isolator switch of 400 A & 3 Nos Station

Class LAs etc as per specifications and tender drawing complete as required

set 1 6 1 1 1 1 1 1

0

1

Page 13 of 38

Page 15: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

ii 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker

along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos outdoor type Current

Transformer along with junction box (1 no junction box for 3 no of 1-phase CTs),

Jumpers, earthing, supporting structures, permanent maintenance platform,

marshalling box, control cabling between VCB and indoor control panel and required

accessories complete as per technical specifications, approved drawings and scope of

the works.

SET 1 6 1 1 1 1 1 1

0

iii Indoor type control and relay panel: 0

Indoor type control and relay panel for 11kV, 3phase, 630 A VCB (feeder Breaker)

consisting of A-meter, volt-meter, E/F & O/C Relay & accessories complete as per

specifications for transformer breaker protection

No. 1 6 1 1 1 1 1 1

Sub Total

PART VII 33/11 KV Substation Augumentation Works - Fully

outdoor type substation

Addl. 5

MVA2

Addl.10

MVA0

5-10 MVA 0

3.15-10

MVA0

3.15/1.6-

5 MVA 4

Total 6

pss 5

a 10 MVA with off load tap changer No 0 0

b 5 MVA with off load tap changer No 6 6

1 1 1 1 1 1

2 Gantry structures made of Lattice structures of equal angles sections, flat

as per approved drawings. State practices are to be adopted in the design.

All structural steel members and bolts shall be galvanized after fabrication

as per IS:4759 and zinc coating shall not be less than 610gm/sq. meter for

all structural steel members. All L45x45x5 will have 23 mm back mark. All

L50x50x6 will have 28mm back mark. 3.5mm spring washers are to be

used under each nut, structural steel shall conform to IS 2026. All weld

shall be 6mm filled weld unless specified otherwise. All nuts and bolts

shall be of property class 5.6 of IS 1367. Plain washers shall be as per IS

2016 & spring washers shall be IS: 3063.

MT 7 7.00 1 1.5 1.5 1 1 1

3

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-

1Amps, 3 Nos outdoor type Current Transformers along with junction box

(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting

structures, permanent maintenance platform, marshalling box etc

required as per technical specifications, scope of works and approved

drawings

Set 4 4 1 1 1 1

4 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic

Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation

relays and other components etc as per approved drawings, specifications

and scope of works controlling: a Power transformer 33 kV VCB with Static Tri-Vector Energy Meter

No. 6 61 1 1 1 1 1

b. Power transformer 33 kV VCB with Static Tri-Vector Energy Meter with differential

relayNo 0 0

5 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings (without earth switch)

Set 8 8 1 1 1 1 1 1 1 1

6 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set = 3

nos.)

Set 6 61 1 1 1 1 1

7 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical

specifications, approved drawings and scope of the works. ( 1 Set = 3

nos.)

Set 6 61 1 1 1 1 1

8.a 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos

outdoor type Current Transformer along with junction box (1 no junction

box for 3 no of 1-phase CTs), Jumpers, earthing, supporting structures,

permanent maintenance platform, marshalling box, control cabling

between VCB and indoor control panel and required accessories complete

as per technical specifications, approved drawings and scope of the works.

No 6 6 1 1 1 1 1 1

8.b 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos

outdoor type Current Transformer along with junction box (1 no junction

box for 3 no of 1-phase CTs), Jumpers, earthing, supporting structures,

permanent maintenance platform, marshalling box, control cabling

between VCB and indoor control panel and required accessories complete

as per technical specifications, approved drawings and scope of the works.

No 0 0

1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil, Buchholtz relay, breather,

OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on

bushing end), isolating link, isolation with insulators}, Vent explosion

plug, control wiring between sensing equipment and marshalling box,

cable supporting tray on the body of transformer, transformer wheels,

LV/HV bushing etc as required as per technical specifications, approved

drawings and scope of the work.

Page 14 of 38

Page 16: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

9 Indoor type control and relay panel:

i Indoor type control and relay panel for 11kV, 3phase, 630 A VCB (feeder Breaker)

consisting of A-meter, volt-meter, E/F & O/C Relay & accessories complete as per

specifications for transformer breaker protection

No. 6 61 1 1 1 1 1

10

30V, 100 AH Pb Acid battery, battery stand made of teak wood duly

painted with anti rusting paint, battery insulators, inter-battery wiring

using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal

connectors, & all other accessories and connectors as per technical

specifications, approved drawings and scope of works.

Set 3 3 1 1 1

11 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave

rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB

as per technical specifications, approved drawings and scope of works. set 3 3 1 1 1

12 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including

hardware fittings, hardware etc

a Wolf conductor (150 Sq. mm) km 0.4 0.4 0.4

13 Earthing & Grounding conductor as per Approved Electrical Layout for each

sub-station with

a 75 x 8 mm MS flat for ground mat MT 1.500 1.5

1.5

b 50 x 6 mm Galvanized GS flat (risers) MT 1.500 1.5

1.5

c 25mm dia MS rod 3 m long for earth mat MT 0.125 0.125

0.125

14 40 mm dia., 3000 mm long GI pipe earth electrode with test link as per

technical specification. (for Power Transformer Neutral, Station

Transformer Neutral and Lightening Arresters direct earthing) Set 40 40

20 20

0

15 33 and 11 KV Insulator - Pin, Post and Disc insulators along with

Hardware & accessories suitable for Wolf conductors as per approved

drawings & specifications.

Set 5 55

16 Power Cables including their termination materials like glands, lugs etc.

a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.125 0.125

0.125

b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.125 0.125

0.125

c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC

sheathed cable km 0.5 0.500

0.5

17 Control cables including their termination materials like glands, lugs etc.

a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.1 0.100

0.1

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.5 0.500

0.5

c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC

sheathed cable km 0.5 0.500

0.5

0

18 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support Insulators, Operating

Mechanism, Base Channel down Pipe and all required accessories

complete as per technical specifications, scope of works and approved

drawings

Set 12 12 2 2 2 2 2 2

0

19 3 Phase 33 KV HG Fuse complete 200 A capacity as per technical

specificationsset 5 5 1 1 1 1 1

Sub-Total

PART VIII 33 KV Railway Crossing NO. 11

1 33 kV grade XLPE, 3 core, 400 sqmm size power cable as per TS Mtr 230 2,530.00230 230 230 230 230 230 230 230 230 230 230

2 GI Pipe 150 mm dia (Light guage) for laying of cable over DP structure Mtr 12 132.0012 12 12 12 12 12 12 12 12 12 12

3Cast Iron spun pipe of 160mm dia in Pcs of 5.6 M and above long as per TS to be laid for

Under ground 33 kV Cable below Railway track at crossingMtr 120.0 1,320.00 120 120 120 120 120 120 120 120 120 120 120

4Outdoor type heat shrinkable termination kit complete with all accessories including lugs

suitable for 3 Core 400 Sqmm 33 kV grade Al conductor XLPE cable as per TSSet 4 44 4 4 4 4 4 4 4 4 4 4 4

Sub-Total

Part IX 11 KV Railway Crossing NO. 4

1 11 kV grade XLPE, 3 core, 300 sqmm size power cable as per TS Mtr 230 920.00230 230 230 230

2 GI Pipe 150 mm dia (Light guage) for Erection of cable over DP structure Mtr 12 48.00 12 12 12 12

3Cast Iron spun pipe of 160mm dia in Pcs of 5.6 M and above long as per TS to be laid for

Under ground 11 kV Cable below Railway track at crossingMtr 120.0 480.00

120 120 120 120

Page 15 of 38

Page 17: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

SUPPLY PERT CHART KATIHAR

Sr. No. DescriptionUnit

Unit Qty. Qty.2014 2015 2016

1 23 4.a 4

LOA date

21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

4Outdoor type heat shrinkable termination kit complete with all accessories including lugs

suitable for 3 Core 185 Sqmm 11 kV grade Al conductor XLPE cable as per TSSet 4 16 4 4 4 4

Sub-Total

Part X LT Single Phase Service connection Set 62068

1 Single phase service connection using PVC insulated cable of size 2 Core 2.5 sqmm

aluminium conductor (up to 35m length of house hold from LT line), 10 SWG GI

tension wire, 20 mm GI Pipe medium class to accept service cable at consumer

residence, A meter board (200x350x40mm) for 1ø ( single phase) energy

meter,Service board (200x150x40mm),Single phase (5-30A) fully static class-1

energy meter, 2nos. single piano type ISI marked 250 V/5A switch 1no. 250V/5A

socket of ISI marked, 250V/5A ISI marked holder, 144-288V, upto 9 watts, 710

lumen LED lamp 250V,5A capacity ISI mark lamp holder, Internal wiring using 1.5

sqmm copper multistrands PVC insulated ISI marked cable, 250V/16A double pole

MCB of ISI marked and a cut-out a 10mm dia earth terminal point, internal wiring in

ISI marked 12mm dia PVC rigid pipes including its clamps, fittings and fixtures as

required as per REC drawing and Specifications. Earth point would be connected with

existing earth potential maintained by DISCOM through 10 SWG GI wireetc. as per

detail scope of work.

Set 1 62068 2000 2000 2000 2000 2000 2000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 2068

Sub-Total

Grand Total Ex-works% DISCOUNT, IF ANY: _______

Note:

Page 16 of 38

Page 18: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

CONTRACTOR: ENERGO ENGINEERING PROJECTS LTDLOA Nos.: Supply: 2732/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 Erection: 2733/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

PART I

(a)33/11 KV Grid Substation works:

Partly - outdoor (2x10 MVA) 2

Nos. 33 KV bay and 10 nos. of 11

KV bay

0

A Civil works: Design, supply of all material, T&P,

labour etc for the following civil works complete as

per TS1 Soil Investigation & Contour Survey of Substation

area as per Technical Specification PER S/S 1 0

2 Earth Filling & Site Levelling

i Earth work in PSS site with ordinary soil (vide

classification of soil item - A) obtained from borrow pits

free from logs, stumps, roots, rubbish or any other

ingredients likely to deteriorate or affect the stability of

the (1.0 meter filling considered size 60*40) site surface

including breaking the clods maximum to 60 mm. cube,

placing the earth in layers not exceeding 225 mm in loose

thickness, rough dressing including cost of cutting and

removing shrubs, roots falling in borrow area all complete

as per approved design, as per technical specification

CUM 2400 0

3 Gravel filling in switchyard area excluding road

and footpath.CUM 60 0

4 Construction of Boundary Wall including Barbed

Wire Fencing on MS angle over the Boundary Wall

and one Gate per Substation, including Supply,

Fabrication, Fixing, Painting all complete as per

approved Drawing & Technical Specification in all

33/11 kV new sub-stations

Mtr 200 0

5 Security fencing along with one switchyard gate

per Substation as per Technical specifications in all

33/11 kV new sub-stations - to isolate electrical

yard

Mtr 40 0

6 Design, engineering and construction of Control

Room Building including supply of T&P, Labour,

Cement, Reinforcement Steel, Form Work,

Excavation etc, all complete as per Technical

Specification and Tender Drawing in 33/11 kV new

sub-stations

Sqm 250 0

7 Design, engineering and construction of Cable

Trench of 0.5 Mtr wide, 1.0 Mtr. depth, precast

RCC Trench Cover, Water stops, Brick Work

wherever required including supply of T&P,

Labour, Cement, Reinforcement Steel, Steel

Angles, Flats, Form Work, Excavation etc, all

complete as per Technical Specification and

approved Drawing.

Mtr 120 0

8 Design, engineering and construction of Drainage

System in the Substation premises including

supply of T&P, Labour, Cement, brick, Form Work,

Excavation etc, all complete as per design,

Technical Specification and Tender Drawings in all

33/11 kV new sub-station

Mtr 100 0

9 Design, engineering and construction of approach

road, footpath including supply of T and P, labour,

brick, stone, earth, RCC and excavation,

compaction etc. all complete as per Technical

specifications.a width of approach road 3.00 m Mtr 100.00 0

b width of footpath 1.5 m Mtr 10.00 0.00

10 Stone pitching over sloping including supply of

stone and surface preparation as per drawingSq. Meter 25.00 0.00

PERT NETWORK

NIT - 164/PR/NBPDCL/2014 KATIHAR

Date : 27/10/2014

Page 17 of 38

Page 19: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

11 Sinking of tube well and installation of motor

operated submersible pump of suitable capacity

along with water tank (1000 lit) and Medium grade

TATA make GI pipe and asseseries.

Set 1 0

B Substation works

12 Design, Engineering and construction of

transformer foundation, erection, filtration, testing

and commissioning of 33/11 kV, 3 ph, 50 Hz,

ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil,

Buchholtz relay, breather, OTI & WTI, Marshalling

Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips with

braided conductor on bushing end supported with

insulators, OTI & WTI Indicators, Vent explosion

plug, control wiring / cabling, cable supporting

tray on the body, transformer wheels, bushing etc

as required

a 10 MVA set 2 0

13 Design, Engineering, providing and construction of

transformer support/foundation, erection, testing

and commissioning of 100 KVA, 11/0.433 kV, 3 ph,

50 Hz, ONAN,copper wound, CRGO core, outdoor

type Station Transformer on double pole structure

(2x175x85 mm double welded) along with

transformer oil, Distribution Box, cabling,

substation earthing mat, equipment earthing,

substation equipment, 3 Nos. Station Class

Lighting Arresters, one set vertical mounting type

HG Fuse complete, one set horizontal operational

Isolator 12 KV (200A capacity) as required as per

specifications & drawings.

Set 1 0

14 Excavation, erection, cement concrete foundation,

erection, testing and commissioning of Galvanised

Gantry structures made of Lattice structures of

equal angles sections, flat as per approved

drawings. State practices are to be adopted in the

design. All structural steel members and bolts shall

be galvanized after fabrication as per IS:4759 and

zinc coating shall not be less than 610gm/sq.

meter for all structural steel members. All

L45x45x5 will have 23 mm back mark. All

L50x50x6 will have 28mm back mark. 3.5mm

spring washers are to be used under each nut,

structural steel shall conform to IS 2026. All weld

shall be 6mm filled weld unless specified

otherwise. All nuts and bolts shall be of property

class 5.6 of IS 1367. Plain washers shall be as per

IS 2016 & spring washers shall be IS: 3063 as per

approved drawings, technical specifications and

scope of the work.

MT 16.00 0.00

0

15 Design, Engineering and construction of foundation

(as per approved drawings), erection, testing and

commissioning of 36kV, 1250A, 25kA for 3 seconds,

3-ph, Outdoor type Vacuum Circuit breaker along

with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-

200/1-1-1 Amps outdoor type Current Transformer

along with junction box (1 no junction box for 3 no

of 1-phase CTs)], Jumpers, earthing, supporting

structures, maintenance platform, marshalling box,

control cabling between VCB and indoor control

panel and required accessories complete as per

approved drawings, technical specifications and

scope of the work.

Set 4 0

Page 18 of 38

Page 20: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

16 Design, Engineering providing and installation of

ISMC 75 channel on top of indoor trench, erection

of panels on ISMC 75 channels, welding, testing

and commissioning of 33kV indoor Control & Relay

panel along with E/F & O/C relays, control and

power supply cabling in trench between field

equipment and panels, Mimic Diagram, Voltmeter,

Ammeter, Annunciation Windows with

annunciation relays and other components etc as

per approved drawings, technical specifications

and scope of the work for controlling:

a 33 kV feeder VCB with Static Tri-Vector Energy Meter etc No 2 0

b 33 kV Power transformer VCB with Static Tri-Vector

Energy Meter, with differential relayNo 2 0

17 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph

double break center rotating type (DBCR), Gang

Operated, isolator along with Support Insulators,

Operating Mechanism, Base Channel down Pipe

and all required accessories complete as per

approved drawings, technical specifications and

scope of the work,

Set 7 0

18 Design & Engineering (as per approved drawings),

Erection, testing and commissioning of 3 phase, 11

kV, 200A, HG Fuses with Support Insulators, , Base

Channel and all required accessories complete as

per approved drawings, technical specifications

and scope of the work,

Set 1 0

19 Design & Engineering (as per approved

drawings), Erection, testing and Commissioning of

36kV, 10kA, 1-ph Station Class Lightening

Arresters with mounting platform on Gantry and

Bus structure , jumpering from bus bar, earthing

connection using 50x6mm GS flat, hardware etc as

required, as per approved drawings, technical

specifications and scope of the work,

Set 4 0

20 Design & Engineering (as per approved drawings),

Erection, testing and Commissioning of 9kV, 10kA,

1-ph Station Class Lightening Arrester with

mounting platform on Gantry and Bus structure ,

jumpering from bus bar, earthing connection using

50x6mm GS flat, hardware, etc as required as per

approved drawings, technical specifications and

scope of the work.

Set 11 0

21 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

Commissioning of 36 kV, 1-Phase, 33kV/110 volt,

Single core outdoor type Potential transformer

along with junction box (1 no junction box for 3 no

of 1-phase PTs) including control and power supply

cabling, earthing connection using 50x6mm GS

flat and required accessories etc., complete as per

as per approved drawings, technical specifications

and scope of the work,

Set 2 0

22 Design, Engineering and construction of foundation

(as per approved drawings), Design, Engineering

and construction of foundation, erection, wiring,

testing and commissioning of 12 kV, 1250 A, 25kA,

3-ph, indoor type Vacuum Circuit breaker along

with 12 kV, 1-Phase, 25kA for 3 seconds, 1200-

600-300/1-1-1 A or 600-300-150/5-5, indoor type

Current Transformer along with control and relay

panel consisting of A-meter, volt-meter, E/F & O/C

Relay & accessories complete cabling between VCB

and indoor control panel and required accessories

complete as per approved drawings, technical

specifications and scope of the work,

a Transformer Protection Breaker Panel No 2 0

b Feeder Protection Breaker Panel No 10 0

c Bus Coupler Panel No 1 0

Page 19 of 38

Page 21: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

23 Installation, initial charging, cabling,

interconnection cabling, testing and commissioning

of 30V, 100 AH Pb Acid battery on battery stand

made of teak wood duly painted with anti acid

rusting paint, battery insulators, inter-battery

wiring using 30 sqm copper single core multi

strand cable, terminal connectors, & all other

accessories and connectors as per as per approved

drawings, technical specifications and scope of the

work,

Set 1 0

24 Design, engineering, construction of foundation,

Installation, interconnection cabling, testing and

commissioning of 30V, 40 Amp. Float-Cum-Boost

Battery Charger with full wave rectification for

220 V, 1 phase, 50 Hz AC Input Supply with built

in DCDB as per approved drawings, technical

specifications and scope of the work,

No 1 0

25 Design, engineering, construction of foundation,

Installation, interconnection cabling, testing and

commissioning of 433V, ACDB as per approved

drawings, technical specifications and scope of the

work,

No 1 0

26 Excavation, laying, welding, refilling, earthing &

grounding conductor as per Approved Electrical

Layout for each sub-station and erection of riser up

to various equipment/gantry structures as per

scope of the work, specifications and approved

drawings,

a 75 x 8 mm MS flat for ground mat MT 2.0 0.0

b 50 x 6 mm Galvanized GS flat (risers) MT 2.0 0.0

c 25 mm dia MS Rod 3 m long for earth mat MT 0.5 0.0

27 Excavation, erection, testing and commissioning of

40 mm dia., 3000 mm long GI pipe earth electrode

by providing test link, RCC pit, RCC cover, placed

on GI frame, Charcoal, Salt and other accessories

complete as per approved drawings, technical

specifications and scope of the work for power

transformer neutral, station transformer neutral,

lightening arresters direct earthing.

Set 50.00 0.00

28 Erection, testing and commissioning of Bus

Conductor (wolf Conductor, Al pipe), bus jumpers

to various equipment using 11 KV and 33 KV

insulators, GI Pin, GI Hardware fittings, PG

Clamps, T-connectors etc as required as per

approved drawings, specifications and scope of the

work.

set 1.00 1.00

29 Erection, testing and commissioning through

erection of support, External Lighting work in the

substation yard with 4 No, 12m high steel tubular

lighting masts, 2x250 watts sodium vapour fittings

on each mast, Junction boxes of the fittings, area

lighting power distribution board, 2 nos. 3 Phase

63 Amp power receptacles, substation building

power supply, tube well power supply, etc as

required by laying power cables in

underground/above ground/trenches, construction

of foundations for receptacles, distribution boards

etc as required as per approved drawings,

specifications and scope of work.

Set 1 0

30 Erection, testing and commissioning of Fire

Fighting Equipment comprises of Dry Chemical

Powder Type (6 Kg) for control room; CO2 Type of

4.5Kg Capacity for Control Room and CO2 Type

Trolley Mounted of 22.5 Kg Capacity for Switch

Yard.

SET 1 0

31 Internal electrification work in Substation Control

room as per approved drawings, specifications and

scope of work by installing, erection, testing and

commissioning of fans, exhaust fans, fluorescent

lighting, LED lamps, L&F, power points, wiring

materials, Distribution Boards, Sub-distribution

boards etc. as per approved drawings

Set 1 0

0

Page 20 of 38

Page 22: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

32 Power Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required

0

a 3.5 Core 70 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.070 0.000

b 3.5 Core 35 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.050 0.000

c 2 Core 16 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.750 0.000

33 Control Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required a 2 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable Km 0.20 0.00

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable Km 1.00 0.00

c 10 Core 2.5 sqm armored, stranded copper conductor,

PVC insulated and PVC sheathed cable Km 0.60 0.00

34 Laying, erection, termination using indoor & outdoor

termination kit, 11KV XLPE, Power armored cables of

following sizes: a 1Cx300 sqmm km 0.72 0.00

b 3Cx185 sqmm km 1.10 0.00

35 Erection, testing and commissioning of 12 kV, 400A, 25kA

for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support

Insulators, Operating Mechanism, Base Channel down

Pipe and all required accessories complete as per technical

specifications, scope of works and approved drawings

Set 10.00 0.00

Sub Total

PART I

(b)33/11 KV Grid Substation works:

Partly - outdoor (3x5 MVA) 2 Nos.

33 KV bay and 09 nos. of 11 KV bay0

A Civil works: Design, supply of all material, T&P,

labour etc for the following civil works complete as

per TS1 Soil Investigation & Contour Survey of Substation

area as per Technical Specification PER S/S 1 0

2 Earth Filling & Site Levelling

i Earth work in PSS site with ordinary soil (vide

classification of soil item - A) obtained from borrow pits

free from logs, stumps, roots, rubbish or any other

ingredients likely to deteriorate or affect the stability of

the (1.0 meter filling considered size 60*40) site surface

including breaking the clods maximum to 60 mm. cube,

placing the earth in layers not exceeding 225 mm in loose

thickness, rough dressing including cost of cutting and

removing shrubs, roots falling in borrow area all complete

as per approved design, as per technical specification

CUM 2400 0

3 Gravel filling in switchyard area excluding road

and footpath.CUM 60 0

4 Construction of Boundary Wall including Barbed

Wire Fencing on MS angle over the Boundary Wall

and one Gate per Substation, including Supply,

Fabrication, Fixing, Painting all complete as per

approved Drawing & Technical Specification in all

33/11 kV new sub-stations

Mtr 200 0

5 Security fencing along with one switchyard gate

per Substation as per Technical specifications in all

33/11 kV new sub-stations - to isolate electrical

yard

Mtr 40 0

6 Design, engineering and construction of Control

Room Building including supply of T&P, Labour,

Cement, Reinforcement Steel, Form Work,

Excavation etc, all complete as per Technical

Specification and Tender Drawing in 33/11 kV new

sub-stations

Sqm 250 0

0

Page 21 of 38

Page 23: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

7 Design, engineering and construction of Cable

Trench of 0.5 Mtr wide, 1.0 Mtr. depth, precast

RCC Trench Cover, Water stops, Brick Work

wherever required including supply of T&P,

Labour, Cement, Reinforcement Steel, Steel

Angles, Flats, Form Work, Excavation etc, all

complete as per Technical Specification and

approved Drawing.

Mtr 120 0

8 Design, engineering and construction of Drainage

System in the Substation premises including

supply of T&P, Labour, Cement, brick, Form Work,

Excavation etc, all complete as per design,

Technical Specification and Tender Drawings in all

33/11 kV new sub-station

Mtr 100 0

9 Design, engineering and construction of approach

road, footpath including supply of T and P, labour,

brick, stone, earth, RCC and excavation,

compaction etc. all complete as per Technical

specifications.a width of approach road 3.00 m Mtr 100.00 0

b width of footpath 1.5 m Mtr 10.00 0

10 Stone pitching over sloping including supply of

stone and surface preparation as per drawingSq. Meter 25.00 0

11 Sinking of tube well and installation of motor

operated submersible pump of suitable capacity

along with water tank (1000 lit) and Medium grade

TATA make GI pipe and asseseries.

Set 1 0

B Substation works

12 Design, Engineering and construction of

transformer foundation, erection, filtration, testing

and commissioning of 33/11 kV, 3 ph, 50 Hz,

ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil,

Buchholtz relay, breather, OTI & WTI, Marshalling

Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips with

braided conductor on bushing end supported with

insulators, OTI & WTI Indicators, Vent explosion

plug, control wiring / cabling, cable supporting

tray on the body, transformer wheels, bushing etc

as required

a 5.0 MVA set 3 0

13 Design, Engineering, providing and construction of

transformer support/foundation, erection, testing

and commissioning of 100 KVA, 11/0.433 kV, 3 ph,

50 Hz, ONAN,copper wound, CRGO core, outdoor

type Station Transformer on double pole structure

(2x175x85 mm double welded) along with

transformer oil, Distribution Box, cabling,

substation earthing mat, equipment earthing,

substation equipment, 3 Nos. Station Class

Lighting Arresters, one set vertical mounting type

HG Fuse complete, one set horizontal operational

AB Switch (200A capacity) as required as per

specifications & drawings.

Set 1 0

0

Page 22 of 38

Page 24: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

14 Excavation, erection, cement concrete foundation,

erection, testing and commissioning of Galvanised

Gantry structures made of Lattice structures of

equal angles sections, flat as per approved

drawings. State practices are to be adopted in the

design. All structural steel members and bolts shall

be galvanized after fabrication as per IS:4759 and

zinc coating shall not be less than 610gm/sq.

meter for all structural steel members. All

L45x45x5 will have 23 mm back mark. All

L50x50x6 will have 28mm back mark. 3.5mm

spring washers are to be used under each nut,

structural steel shall conform to IS 2026. All weld

shall be 6mm filled weld unless specified

otherwise. All nuts and bolts shall be of property

class 5.6 of IS 1367. Plain washers shall be as per

IS 2016 & spring washers shall be IS: 3063 as per

approved drawings, technical specifications and

scope of the work.

MT 16.00 0.00

15 Design, Engineering and construction of foundation

(as per approved drawings), erection, testing and

commissioning of 36kV, 1250A, 25kA for 3 seconds,

3-ph, Outdoor type Vacuum Circuit breaker along

with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-

200/1-1-1 Amps outdoor type Current Transformer

along with junction box (1 no junction box for 3 no

of 1-phase CTs)], Jumpers, earthing, supporting

structures, maintenance platform, marshalling box,

control cabling between VCB and indoor control

panel and required accessories complete as per

approved drawings, technical specifications and

scope of the work.

Set 5 0

16 Design, Engineering providing and installation of

ISMC 75 channel on top of indoor trench, erection

of panels on ISMC 75 channels, welding, testing

and commissioning of 33kV indoor Control & Relay

panel along with E/F & O/C relays, control and

power supply cabling in trench between field

equipment and panels, Mimic Diagram, Voltmeter,

Ammeter, Annunciation Windows with

annunciation relays and other components etc as

per approved drawings, technical specifications

and scope of the work for controlling:

a 33 kV feeder VCB with Static Tri-Vector Energy Meter etc No 2 0

b 33 kV Power transformer VCB with Static Tri-Vector

Energy Meter, No 3 0

17 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph

double break center rotating type (DBCR), Gang

Operated, isolator along with Support Insulators,

Operating Mechanism, Base Channel down Pipe

and all required accessories complete as per

approved drawings, technical specifications and

scope of the work,

Set 8 0

18 Design & Engineering (as per approved drawings),

Erection, testing and commissioning of 3 phase, 11

kV, 200A, HG Fuses with Support Insulators, , Base

Channel and all required accessories complete as

per approved drawings, technical specifications

and scope of the work,

Set 1 0

19 Design & Engineering (as per approved

drawings), Erection, testing and Commissioning of

36kV, 10kA, 1-ph Station Class Lightening

Arresters with mounting platform on Gantry and

Bus structure , jumpering from bus bar, earthing

connection using 50x6mm GS flat, hardware etc as

required, as per approved drawings, technical

specifications and scope of the work,

Set 5 0

Page 23 of 38

Page 25: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

20 Design & Engineering (as per approved drawings),

Erection, testing and Commissioning of 9kV, 10kA,

1-ph Station Class Lightening Arrester with

mounting platform on Gantry and Bus structure ,

jumpering from bus bar, earthing connection using

50x6mm GS flat, hardware, etc as required as per

approved drawings, technical specifications and

scope of the work.

Set 10 0

21 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

Commissioning of 36 kV, 1-Phase, 33kV/110 volt,

Single core outdoor type Potential transformer

along with junction box (1 no junction box for 3 no

of 1-phase PTs) including control and power supply

cabling, earthing connection using 50x6mm GS

flat and required accessories etc., complete as per

as per approved drawings, technical specifications

and scope of the work,

Set 2 0

22 Design, Engineering and construction of foundation

(as per approved drawings), Design, Engineering

and construction of foundation, erection, wiring,

testing and commissioning of 12 kV, 1250 A, 25kA,

3-ph, indoor type Vacuum Circuit breaker along

with 12 kV, 1-Phase, 25kA for 3 seconds, 1200-

600-300/1-1-1 A or 600-300-150/5-5, indoor type

Current Transformer along with control and relay

panel consisting of A-meter, volt-meter, E/F & O/C

Relay & accessories complete cabling between VCB

and indoor control panel and required accessories

complete as per approved drawings, technical

specifications and scope of the work,

a Transformer Protection Breaker Panel No 3 0

b Feeder Protection Breaker Panel No 9 0

c Bus Coupler Panel No 2 0

23 Installation, initial charging, cabling,

interconnection cabling, testing and commissioning

of 30V, 100 AH Pb Acid battery on battery stand

made of teak wood duly painted with anti acid

rusting paint, battery insulators, inter-battery

wiring using 30 sqm copper single core multi

strand cable, terminal connectors, & all other

accessories and connectors as per as per approved

drawings, technical specifications and scope of the

work,

Set 1 0

24 Design, engineering, construction of foundation,

Installation, interconnection cabling, testing and

commissioning of 30V, 40 Amp. Float-Cum-Boost

Battery Charger with full wave rectification for

220 V, 1 phase, 50 Hz AC Input Supply with built

in DCDB as per approved drawings, technical

specifications and scope of the work,

No 1 0

25 Design, engineering, construction of foundation,

Installation, interconnection cabling, testing and

commissioning of 433V, ACDB as per approved

drawings, technical specifications and scope of the

work,

No 1 0

26 Excavation, laying, welding, refilling, earthing &

grounding conductor as per Approved Electrical

Layout for each sub-station and erection of riser up

to various equipment/gantry structures as per

scope of the work, specifications and approved

drawings,

a 75 x 8 mm MS flat for ground mat MT 2.5 0

b 50 x 6 mm Galvanized GS flat (risers) MT 2.5 0

c 25 mm dia MS Rod 3 m long for earth mat MT 0.5 0

27 Excavation, erection, testing and commissioning of

40 mm dia., 3000 mm long GI pipe earth electrode

by providing test link, RCC pit, RCC cover, placed

on GI frame, Charcoal, Salt and other accessories

complete as per approved drawings, technical

specifications and scope of the work for power

transformer neutral, station transformer neutral,

lightening arresters direct earthing.

Set 50.00 0

Page 24 of 38

Page 26: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

28 Erection, testing and commissioning of Bus

Conductor (wolf Conductor, Al pipe), bus jumpers

to various equipment using 11 KV and 33 KV

insulators, GI Pin, GI Hardware fittings, PG

Clamps, T-connectors etc as required as per

approved drawings, specifications and scope of the

work.

set 1.00 0

29 Erection, testing and commissioning through

erection of support, External Lighting work in the

substation yard with 4 No, 12m high steel tubular

lighting masts, 2x250 watts sodium vapour fittings

on each mast, Junction boxes of the fittings, area

lighting power distribution board, 2 nos. 3 Phase

63 Amp power receptacles, substation building

power supply, tube well power supply, etc as

required by laying power cables in

underground/above ground/trenches, construction

of foundations for receptacles, distribution boards

etc as required as per approved drawings,

specifications and scope of work.

Set 1 0

30 Erection, testing and commissioning of Fire

Fighting Equipment comprises of Dry Chemical

Powder Type (6 Kg) for control room; CO2 Type of

4.5Kg Capacity for Control Room and CO2 Type

Trolley Mounted of 22.5 Kg Capacity for Switch

Yard.

SET 1 0

31 Internal electrification work in Substation Control

room as per approved drawings, specifications and

scope of work by installing, erection, testing and

commissioning of fans, exhaust fans, fluorescent

lighting, LED lamps, L&F, power points, wiring

materials, Distribution Boards, Sub-distribution

boards etc. as per approved drawings

Set 1 0

32 Power Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required a 3.5 Core 70 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.070 0

b 3.5 Core 35 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.050 0

c 2 Core 16 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.750 0

33 Control Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required a 2 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable Km 0.20 0

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable Km 1.00 0

c 10 Core 2.5 sqm armored, stranded copper conductor,

PVC insulated and PVC sheathed cable Km 0.60 0

34 Laying, erection, termination using indoor & outdoor

termination kit, 11KV XLPE, Power armored cables of

following sizes: a 1Cx300 sqmm km 0.72 0

b 3Cx185 sqmm km 1.00 0

35 Erection, testing and commissioning of 12 kV, 400A, 25kA

for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support

Insulators, Operating Mechanism, Base Channel down

Pipe and all required accessories complete as per technical

specifications, scope of works and approved drawings

Set 9.00 0

Sub Total

PART I

(c)33/11 KV Grid Substation works:

Partly - outdoor (2x5 MVA) 2 Nos.

33 KV bay and 06 nos. of 11 KV bay9

A Civil works: Design, supply of all material, T&P,

labour etc for the following civil works complete as

per TS1 Soil Investigation & Contour Survey of Substation

area as per Technical Specification PER S/S 1 9 1 1 1 1 1 1 1 1 1

Page 25 of 38

Page 27: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

0

2 Earth Filling & Site Levelling

0

i Earth work in PSS site with ordinary soil (vide

classification of soil item - A) obtained from borrow pits

free from logs, stumps, roots, rubbish or any other

ingredients likely to deteriorate or affect the stability of

the (1.0 meter filling considered size 60*40) site surface

including breaking the clods maximum to 60 mm. cube,

placing the earth in layers not exceeding 225 mm in loose

thickness, rough dressing including cost of cutting and

removing shrubs, roots falling in borrow area all complete

as per approved design, as per technical specification

CUM 2400 21600 500 500 500 1000 1000 1000 1000 1000 1000 1000 1000 1500 1500 1500 1500 1500 1500 1500 1600

0

3 Gravel filling in switchyard area excluding road

and footpath.CUM 60 540 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30

0

4 Construction of Boundary Wall including Barbed

Wire Fencing on MS angle over the Boundary Wall

and one Gate per Substation, including Supply,

Fabrication, Fixing, Painting all complete as per

approved Drawing & Technical Specification in all

33/11 kV new sub-stations

Mtr 200 1800 50 50 100 100 100 100 100 100 100 100 100 100 100 100 125 125 125 125

0

5 Security fencing along with one switchyard gate

per Substation as per Technical specifications in all

33/11 kV new sub-stations - to isolate electrical

yard

Mtr 40 360 10 10 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25

0

6 Design, engineering and construction of Control

Room Building including supply of T&P, Labour,

Cement, Reinforcement Steel, Form Work,

Excavation etc, all complete as per Technical

Specification and Tender Drawing in 33/11 kV new

sub-stations

Sqm 250 2250 50 100 100 125 125 125 125 125 125 125 125 125 125 150 150 150 150 150

0

7 Design, engineering and construction of Cable

Trench of 0.5 Mtr wide, 1.0 Mtr. depth, precast

RCC Trench Cover, Water stops, Brick Work

wherever required including supply of T&P,

Labour, Cement, Reinforcement Steel, Steel

Angles, Flats, Form Work, Excavation etc, all

complete as per Technical Specification and

approved Drawing.

Mtr 120 1080 30 30 60 60 60 60 60 60 60 60 60 60 60 60 75 75 75 75

0

8 Design, engineering and construction of Drainage

System in the Substation premises including

supply of T&P, Labour, Cement, brick, Form Work,

Excavation etc, all complete as per design,

Technical Specification and Tender Drawings in all

33/11 kV new sub-station

Mtr 100 900 25 25 50 50 50 50 50 50 50 50 50 50 50 50 50 50 75 75

0

9 Design, engineering and construction of approach

road, footpath including supply of T and P, labour,

brick, stone, earth, RCC and excavation,

compaction etc. all complete as per Technical

specifications.

0

a width of approach road 3.00 m Mtr 100.00 900 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 75 75

b width of footpath 1.5 m Mtr 10.00 90 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 7.5 7.5

0

10 Stone pitching over sloping including supply of

stone and surface preparation as per drawingSq. Meter 25.00 225

12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 15 15 15 15 20 20

0

11 Sinking of tube well and installation of motor

operated submersible pump of suitable capacity

along with water tank (1000 lit) and Medium grade

TATA make GI pipe and asseseries.

Set 1 9 1 1 1 1 1 1 1 1 1

0

B Substation works 0

0

Page 26 of 38

Page 28: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

12 Design, Engineering and construction of

transformer foundation, erection, filtration, testing

and commissioning of 33/11 kV, 3 ph, 50 Hz,

ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil,

Buchholtz relay, breather, OTI & WTI, Marshalling

Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips with

braided conductor on bushing end supported with

insulators, OTI & WTI Indicators, Vent explosion

plug, control wiring / cabling, cable supporting

tray on the body, transformer wheels, bushing etc

as required

0

a 5.0 MVA set 2 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2

0

13 Design, Engineering, providing and construction of

transformer support/foundation, erection, testing

and commissioning of 100 KVA, 11/0.433 kV, 3 ph,

50 Hz, ONAN,copper wound, CRGO core, outdoor

type Station Transformer on double pole structure

(2x175x85 mm double welded) along with

transformer oil, Distribution Box, cabling,

substation earthing mat, equipment earthing,

substation equipment, 3 Nos. Station Class

Lighting Arresters, one set vertical mounting type

HG Fuse complete, one set horizontal operational

AB Switch (200A capacity) as required as per

specifications & drawings.

Set 1 9 1 1 1 1 1 1 1 1 1

0

14 Excavation, erection, cement concrete foundation,

erection, testing and commissioning of Galvanised

Gantry structures made of Lattice structures of

equal angles sections, flat as per approved

drawings. State practices are to be adopted in the

design. All structural steel members and bolts shall

be galvanized after fabrication as per IS:4759 and

zinc coating shall not be less than 610gm/sq.

meter for all structural steel members. All

L45x45x5 will have 23 mm back mark. All

L50x50x6 will have 28mm back mark. 3.5mm

spring washers are to be used under each nut,

structural steel shall conform to IS 2026. All weld

shall be 6mm filled weld unless specified

otherwise. All nuts and bolts shall be of property

class 5.6 of IS 1367. Plain washers shall be as per

IS 2016 & spring washers shall be IS: 3063 as per

approved drawings, technical specifications and

scope of the work.

MT 14.00 126 2 5 7 7 7 7 7 7 7 7 7 7 14 14 14 7

0

15 Design, Engineering and construction of foundation

(as per approved drawings), erection, testing and

commissioning of 36kV, 1250A, 25kA for 3 seconds,

3-ph, Outdoor type Vacuum Circuit breaker along

with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-

200/1-1-1 Amps outdoor type Current Transformer

along with junction box (1 no junction box for 3 no

of 1-phase CTs)], Jumpers, earthing, supporting

structures, maintenance platform, marshalling box,

control cabling between VCB and indoor control

panel and required accessories complete as per

approved drawings, technical specifications and

scope of the work.

Set 4 36 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3

0

16 Design, Engineering providing and installation of

ISMC 75 channel on top of indoor trench, erection

of panels on ISMC 75 channels, welding, testing

and commissioning of 33kV indoor Control & Relay

panel along with E/F & O/C relays, control and

power supply cabling in trench between field

equipment and panels, Mimic Diagram, Voltmeter,

Ammeter, Annunciation Windows with

annunciation relays and other components etc as

per approved drawings, technical specifications

and scope of the work for controlling:

0

a 33 kV feeder VCB with Static Tri-Vector Energy Meter etc No 2 18 2 2 2 2 2 2 2 2 2

b 33 kV Power transformer VCB with Static Tri-Vector

Energy Meter, No 2 18 2 2 2 2 2 2 2 2 2

0

Page 27 of 38

Page 29: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

17 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph

double break center rotating type (DBCR), Gang

Operated, isolator along with Support Insulators,

Operating Mechanism, Base Channel down Pipe

and all required accessories complete as per

approved drawings, technical specifications and

scope of the work,

Set 7 63 4 4 4 4 4 4 4 5 5 5 5 5 5 5

0

18 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

commissioning of 3 phase, 33 kV, 100A, HG Fuses

with Support Insulators, , Base Channel and all

required accessories complete as per approved

drawings, technical specifications and scope of the

work,

Set 1 9 1 1 1 1 1 1 1 1 1

0

19 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

Commissioning of 36kV, 10kA, 1-ph Station Class

Lightening Arresters with mounting platform,

jumpering from bus bar, earthing connection using

50x6mm GS flat, hardware etc as required, as per

approved drawings, technical specifications and

scope of the work,

Set 4 36 2 2 2 2 2 2 2 2 2 2 4 4 4 4

0

20 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

Commissioning of 9kV, 10kA, 1-ph Station Class

Lightening Arrester with mounting platform,

jumpering from bus bar, earthing connection using

50x6mm GS flat, hardware, etc as required as per

approved drawings, technical specifications and

scope of the work.

Set 7 63 3 4 3 4 3 4 3 4 3 4 7 7 7 7

0

21 Design & Engineering (as per approved drawings),

Erection, testing and Commissioning of 9kV, 10kA,

1-ph Station Class Lightening Arrester with

mounting platform on Gantry and Bus structure ,

jumpering from bus bar, earthing connection using

50x6mm GS flat, hardware, etc as required as per

approved drawings, technical specifications and

scope of the work.

Set 2 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2

0

22 Design, Engineering and construction of foundation

(as per approved drawings), Design, Engineering

and construction of foundation, erection, wiring,

testing and commissioning of 12 kV, 1250 A, 25kA,

3-ph, indoor type Vacuum Circuit breaker along

with 12 kV, 1-Phase, 25kA for 3 seconds, 1200-

600-300/1-1-1 A or 600-300-150/5-5, indoor type

Current Transformer along with control and relay

panel consisting of A-meter, volt-meter, E/F & O/C

Relay & accessories complete cabling between VCB

and indoor control panel and required accessories

complete as per approved drawings, technical

specifications and scope of the work,

0

a Transformer Protection Breaker Panel No 2 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2

b Feeder Protection Breaker Panel No 6 54 3 3 3 3 3 3 3 3 3 3 6 6 6 6

c Bus Coupler Panel No 1 9 1 1 1 1 1 1 1 1 1

0

23 Installation, initial charging, cabling,

interconnection cabling, testing and commissioning

of 30V, 100 AH Pb Acid battery on battery stand

made of teak wood duly painted with anti acid

rusting paint, battery insulators, inter-battery

wiring using 30 sqm copper single core multi

strand cable, terminal connectors, & all other

accessories and connectors as per as per approved

drawings, technical specifications and scope of the

work,

Set 1 9 1 1 1 1 1 1 1 1 1

0

Page 28 of 38

Page 30: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

24 Design, engineering, construction of foundation,

Installation, interconnection cabling, testing and

commissioning of 30V, 40 Amp. Float-Cum-Boost

Battery Charger with full wave rectification for

220 V, 1 phase, 50 Hz AC Input Supply with built

in DCDB as per approved drawings, technical

specifications and scope of the work,

No 1 9 1 1 1 1 1 1 1 1 1

0

25 Design, engineering, construction of foundation,

Installation, interconnection cabling, testing and

commissioning of 433V, ACDB as per approved

drawings, technical specifications and scope of the

work,

No 1 9 1 1 1 1 1 1 1 1 1

0

26 Excavation, laying, welding, refilling, earthing &

grounding conductor as per Approved Electrical

Layout for each sub-station and erection of riser up

to various equipment/gantry structures as per

scope of the work, specifications and approved

drawings,

0

a 75 x 8 mm MS flat for ground mat MT 2.0 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2

b 50 x 6 mm Galvanized GS flat (risers) MT 2.0 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2

c 25 mm dia MS Rod 3 m long for earth mat MT 0.5 4.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

0

27 Excavation, erection, testing and commissioning of

40 mm dia., 3000 mm long GI pipe earth electrode

by providing test link, RCC pit, RCC cover, placed

on GI frame, Charcoal, Salt and other accessories

complete as per approved drawings, technical

specifications and scope of the work for power

transformer neutral, station transformer neutral,

lightening arresters direct earthing.

Set 40.00 360 20 20 20 20 20 20 20 20 40 40 40 40 40

0

28 Erection, testing and commissioning of Bus

Conductor (wolf Conductor, Al pipe), bus jumpers

to various equipment using 11 KV and 33 KV

insulators, GI Pin, GI Hardware fittings, PG

Clamps, T-connectors etc as required as per

approved drawings, specifications and scope of the

work.

set 1.00 1 1

0

29 Erection, testing and commissioning through

erection of support, External Lighting work in the

substation yard with 4 No, 12m high steel tubular

lighting masts, 2x250 watts sodium vapour fittings

on each mast, Junction boxes of the fittings, area

lighting power distribution board, 2 nos. 3 Phase

63 Amp power receptacles, substation building

power supply, tube well power supply, etc as

required by laying power cables in

underground/above ground/trenches, construction

of foundations for receptacles, distribution boards

etc as required as per approved drawings,

specifications and scope of work.

Set 1 9 1 1 1 1 1 1 1 1 1

0

30 Erection, testing and commissioning of Fire

Fighting Equipment comprises of Dry Chemical

Powder Type (6 Kg) for control room; CO2 Type of

4.5Kg Capacity for Control Room and CO2 Type

Trolley Mounted of 22.5 Kg Capacity for Switch

Yard.

SET 1 9 1 1 1 1 1 1 1 1 1

0

31 Internal electrification work in Substation Control

room as per approved drawings, specifications and

scope of work by installing, erection, testing and

commissioning of fans, exhaust fans, fluorescent

lighting, LED lamps, L&F, power points, wiring

materials, Distribution Boards, Sub-distribution

boards etc. as per approved drawings

Set 1 9 1 1 1 1 1 1 1 1 1

0

32 Power Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required

0

a 3.5 Core 70 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.070 0.63 0.07 0.07 0.07 0.07 0.07 0.07 0.07 0.07 0.07

b 3.5 Core 35 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.050 0.45 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05

c 2 Core 16 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable Km 0.750 6.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75

0

Page 29 of 38

Page 31: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

33 Control Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required

0

a 2 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable Km 0.20 1.80 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable Km 0.70 6.30 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7

c 10 Core 2.5 sqm armored, stranded copper conductor,

PVC insulated and PVC sheathed cable Km 0.50 4.50 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5

0

34 Laying, erection, termination using indoor & outdoor

termination kit, 11KV XLPE, Power armored cables of

following sizes:

0

a 1Cx300 sqmm km 0.54 4.86 0.54 0.54 0.54 0.54 0.54 0.54 0.54 0.54 0.54

b 3Cx185 sqmm km 0.70 6.3 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7

35 Erection, testing and commissioning of 12 kV, 400A, 25kA

for 3 seconds, 3-ph double break center rotating type

(DBCR), Gang Operated, isolator along with Support

Insulators, Operating Mechanism, Base Channel down

Pipe and all required accessories complete as per technical

specifications, scope of works and approved drawings

Set 6 54 3 3 3 3 3 3 3 3 6 6 6 6 6

Sub Total

PART II Erection, testing and Commissioning of New 33 KV

lines: Dog 195.00

1 Excavation of pit, cement concrete foundation,

erection of following Support for 33 KV overhead

line by providing and installing danger plate, anti-

climbing devices (barbed wire) and pole

numbering as per scope of work, approved

drawings and specifications: a 9 m/400 Kgs PSC Poles with RCC Base plate including

60% refilling by brick ballast/ stone bolder and 40 %

excavated soil as required

No 16 3120 100 100 200 200 200 200 200 200 200 200 200 200 200 200 200 200 120

b 13 m long RS Joist 152x152 mm with RCC Base plate with

cement concrete foundation ( 1:2:4) as required as per

scope of work, approved drawings and technical

specifications.

No 1 195 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15

2 Erection of galvanised pre-fabricated steel

materials- Channels, angle, flats for over head

structures

MT 0.67 130.65 5 5.65 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8

3 Erection, testing and commissioning of ACSR DOG

Conductor of size 6/4.72 mm + 7/1.57 mm (100

mm² Al. Area) including jointing sleeves and

helicon formed fittings etc as required

ckm 1 195.00 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15

4 Erection of Galvanised Steel Nuts, bolts and

washers MT 0.024 4.68 0.12 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.36 0.36 0.36 0.36 0.36 0.36

5 Erection, testing and commissioning of 33 KV Disc

insulator 70 KN along with HW fittings (porcelain

disc insulator as the case may be with 70KN

fittings)

Set 6 1170 30 60 60 60 60 60 60 60 60 60 60 90 90 90 90 90 90

6 Erection, Testing and Commissioning of 33 KV Pin

Insulators with GI PIN (porcelain pin insulator as

the case may be with GI Pin)

Set 48 9360 240 480 480 480 480 480 480 480 480 480 480 720 720 720 720 720 720

7 Excavation, Erecting, Testing and Commissioning

of Pipe type Untreated Earthing as per approved

drawings, scope of work and technical

specifications as required.

Set 1 195 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15

8 Excavation, Erecting, Testing and Commissioning

of Coil type Untreated Earthing as per approved

drawings, scope of work and technical

specifications as required.

Set 15 2925 75 75 175 150 150 150 200 200 200 200 200 200 200 200 200 200 150

9 Excavation and erection of galvanised Stay Set

with 50x8 mm stay clamp, HT stay guy insulator,

nut bolts, 2 Nos turn buckles, 1.8 m long, 20 mm

diameter solid GS stay rod & 7/4.00 mm dia GI

stranded wire by providing 0.3 cum cement

concrete foundations as per scope of work,

specifications and approved drawings.

Set 6 1170 30 60 60 60 60 60 60 60 60 60 60 90 90 90 90 90 90

10 Survey, route alignment & pole spotting,

preparation of survey report and uploading in the

web portal after approval of Engineer

Km 1 195 5 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15

Page 30 of 38

Page 32: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

11 Erection, Testing and Commissioning of 36kV AB

Switch along with Support Insulators, Base

Channel down Pipe, Arcing Horns etc. complete as

per technical specifications, scope of works and

approved drawings

Set 0.1 19.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2

12 Erection, testing and commissioning of 8 SWG wire

for earthing, MT 0.003 0.585 0.015 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.045 0.045 0.045 0.045 0.045 0.045

Sub-Total (II)

Rabbit 405

Weasel 695.25

Total 1100.31 Excavation and erection of support for 11 KV

overhead line by providing and installing danger

plate, anti-climbing devices (barbed wire) and pole

numbering as per scope of work, approved

drawings and specifications: a 8 m/200 Kgs PSC Poles with RCC Base plate including

60% refilling by brick ballast/ stone bolder and 40 %

excavated soil as required

No 16.75 18429 250 500 500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1250 1250 1250 1250 1179

b 13 m long RS Joist 152x152 mm with RCC Base plate with

cement concrete foundation ( 1:2:4) as required as per

scope of work, approved drawings and technical

specifications.

No 0.25 275 10 10 10 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20

2 Erection of galvanised pre-fabricated steel

materials- channel, angle, flats for over head

structures

MT 0.34 374.09 10 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25 24.09

3 Erection of galvanised Steel Nuts, Bolts with

WashersMT 0.0155 17.053875 0.5 0.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1

4 Erection, Testing and Commissioning of ACSR

Conductors with Jointing sleeves, Helically formed

fittings etc as required a 7/3.35 mm (50 mm² Al. Area) (Rabbit) CKM 1 405.00 5 10 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 20

b 7/2.59 mm (30 mm² Al. Area) (Weasel) CKM 1 695.25 10 20 30 30 30 30 30 30 30 30 50 50 50 50 50 50 50 50 25.25

5 Erection, Testing and Commissioning of Porcelain

Insulators with mounting hardware, fittings

11 KV 45 KN Disc Insulator with hardware fittings Set 6 6601.5 90 180 300 300 300 300 300 300 330 330 450 450 450 450 450 450 450 450 272

11 KV Pin insulators with GI Pin Set 48.00 52812 720 1440 2400 2400 2400 2400 2400 2400 2640 2640 3600 3600 3600 3600 3600 3600 3600 3600 2172

6 Excavation and erection of galvanised Stay set

with 50x8 mm Stay clamp, HT stay guy insulator,

nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm

diameter solid GS stay rod & 7/3.15 mm dia GI

stranded wire etc as required by providing 0.2 cum

cement concreting as per scope of the work,

technical specifications and approved drawings.

Set 6.00 6601.5 90 180 300 300 300 300 300 300 330 330 450 450 450 450 450 450 450 450 272

7 Erection, Testing and Commissioning of 12kV AB

Switch along with Support Insulators, Base

Channel down Pipe, Arcing Horns etc. complete as

per technical specifications, scope of works and

approved drawings

Set 0.1 110.025 2 3 5 5 5 5 5 6 6 6 7 7 7 7 7 7 7 7 6

8 Excavation, Erecting, Testing and Commissioning

of Pipe type Untreated Earthing as per approved

drawings, scope of work and technical

specifications as required.

Set 1 1100.25 15 30 50 50 50 50 50 50 55 55 75 75 75 75 75 75 75 75 45

9 Excavation, Erecting, Testing and Commissioning

of Coil type Untreated Earthing as per approved

drawings, scope of work and technical

specifications as required.

Set 15.00 16503.75 200 450 450 900 900 900 900 900 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 904

10 Survey, route alignment & pole spotting,

preparation of survey report and uploading in the

web portal after approval of Engineer

Km 1 1100.25 15 35 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100

11 Erection, testing and commissioning of 8 SWG GI

wire for earthing, MT 0.003 3.30075 0.045 0.09 0.15 0.15 0.15 0.15 0.15 0.15 0.165 0.165 0.225 0.225 0.225 0.225 0.225 0.225 0.225 0.225 0.135

Sub-Total (III)

63 KVA 1402

100 KVA 336

Total 1738

Part IVErection, Testing and Commissioning of new

Distribution Transformer Substations

Part III Erection, Testing and Commissioning of 11 KV Lines

Page 31 of 38

Page 33: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 Erection, Testing and Commissioning of

Distribution Transformer with all accessories as

per TSa Three Phase 63 KVA No 1 1402 20 50 50 80 80 80 80 80 80 100 100 100 100 100 100 80 80 42

b Three Phase 100 KVA No 1 336 5 10 10 20 20 20 20 20 20 25 25 25 25 20 20 20 20 11

2 Erection, testing and Commissioning of 3-pole,

Distribution Class 11KV Lightening Arrester for

Distribution Transformer Substation by providing

and erecting Hot Deep galvanised stranded wire

7/3.15 mm as per scope of work, approved

drawings and technical specifications.

Set 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53

3 Excavation and erection of 11 KV Line Support by

providing and installing danger plate, anti-climbing

devices (barbed wire) and pole numbering as per

scope of work, approved drawings and

specifications:a 8 m/200 Kgs PSC Poles with RCC Base plate including

60% refilling by brick ballast/ stone bolder and 40 %

excavated soil as required

No 2 3476 50 120 120 200 200 200 200 200 200 250 250 250 250 240 240 200 200 106

4 Erection of Galvanised pre-fabricated steel

materials- channel, angle, flats for over head

structures

MT 0.255 443.19 6.375 15.3 15.3 25.5 25.5 25.5 25.5 25.5 25.5 31.875 31.875 31.875 31.875 30.6 30.6 25.5 25.5 13.515

5 Erection of Galvanised Steel Nuts, Bolts with

WashersMT 0.016 27.808 0.4 0.96 0.96 1.6 1.6 1.6 1.6 1.6 1.6 2 2 2 2 1.92 1.92 1.6 1.6 0.848

6 Erection, Testing and Commissioning of Insulators

a 11 KV, Disc Insulator ( porcelain) with hardware fittingsSet 3 5214 75 180 180 300 300 300 300 300 300 375 375 375 375 360 360 300 300 159

7 Erection, testing and Commissioning of 12 KV, 200

A, 3-pole AB Switch for Distribution Transformer

Substation.

Sets 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53

8 Erection, testing and commissioning of 3 pole,

11KV 200 AMP HG fuse set for 3-ph DTs Sets 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53

9 Erection, testing and Commissioning of LT

Distribution box with metering and LT control

mechanism as per scope of the work, by providing

50x8mm clamps, hardware, lugs, double

compression brass glands, 2.5sqmm copper multi

strands control cabling, earthing using 8 SWG GS

wire, technical specifications and approved

drawings suitable for following transformer:

a Three Phase 63 KVA No 1 1402 20 50 50 80 80 80 80 80 80 100 100 100 100 100 100 80 80 42

b Three Phase 100 KVA No 1 336 5 10 10 20 20 20 20 20 20 25 25 25 25 20 20 20 20 11

10 Excavation, erection, testing and commissioning of

set of 3 Nos pipe earthing using 40mm dia GI pipe

3000 mm long, as per IS 1161 and as per REC

construction drawings, making earth grid using

50x6mm GS Flat and riser and connecting risers to

various equipment using GS Stranded wires/GS 8

SWG wire as per scope of work, approved drawings

and technical specifications. Providing and erecting

charcoal, salt, lugs, hardware, etc as per approved

drawings, technical specifications and drawings.

Set 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53

11 Erection, testing and commissioning of ACSR

Rabbit Conductor for jumpering including PG

Clamps, bi-metallic connectors, hardware etc

Km 0.009 15.642 0.225 0.54 0.54 0.9 0.9 0.9 0.9 0.9 0.9 1.125 1.125 1.125 1.125 1.08 1.08 0.9 0.9 0.477

12 Erection, testing and commissioning of PVC

insulated, PVC sheathed, Aluminium Conductor,

Stranded, unarmoured cable for connection of

transformer LV bushing to Distribution Box as per

Scope of work, technical specification and

approved drawings:

a 1CX50 sqm aluminium conductor cable for Three Phase 63

KVAkm 0.015 21.030 0.3 0.75 0.75 1.2 1.2 1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 1.5 1.5 1.2 1.2 0.63

b 1Cx95 sqm aluminium conductor cable for Three Phase

100KVAkm 0.015 5.040

0.075 0.15 0.15 0.3 0.3 0.3 0.3 0.3 0.3 0.375 0.375 0.375 0.375 0.3 0.3 0.3 0.3 0.165

Sub-Total (IV)

1-Phase 556.2

Part V LT Line Page 32 of 38

Page 34: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

3-Phase 834.3

Total 1390.5

1 Excavation and erection of Support for LT overhead

Line by providing and installing danger plate, anti-

climbing devices (barbed wire) and pole

numbering as per scope of work, approved 8 m/200 Kgs PSC Poles with RCC Base plate including

60% refilling by brick ballast/ stone bolder and 40 %

excavated soil as required

No 21 29200.5 250 500 500 1000 1000 1500 1500 1500 1500 1500 2000 2000 2000 2000 2000 2000 2000 2000 1500 951

2 Excavation and erection of galvanised Stay Set

with 50x8mm stay clamp, stay guy insulator, nut

bolts, 2 Nos turn buckle's, 1.8 m long, 16 mm

diameter solid GS Stay rod & 7/3.15 mm Dia GI

stranded wire etc as required by providing 0.2 cum

cement concrete as per approved drawings,

technical specification and scope of work.

No 7 9733.5 200 200 350 350 400 500 500 500 500 650 650 650 650 700 700 700 700 500 333

3 Earthing of LT support by providing earthing at

every 6th pole through:

a Installation, testing and commissioning of untreated Coil

Earthing as per scope of work, technical specifications and

approved drawings

Set 5 6952.5 60 125 125 200 250 325 325 325 325 325 500 500 500 500 500 500 500 500 325 243

4 Erection, testing and Commissioning of LT Line on

AB Cables: (average span 40 m) including erection

accessories like Insulation Piercing Connectors,

Anchoring Assembly, Suspension Assembly, Service

Clamp, Transformer Connection, Junction Sleeves

and Service Main Distribution boxes etc as required

as per scope of work, approved drawings and

technical specifications.

a 1-Phase ABC [1X16{Phase}+1x16 {Neutral}+{1x25

Messenger cum earth wire}] line as per TS km 1.03 572.886 10 10 25 25 25 25 35 35 35 35 35 35 35 35 35 35 35 35 32.8

b 3-Phase ABC [3X50{Phase}+{1x35 Messenger cum earth

wire}] line as per TS km 1.03 859.33 20 20 40 40 50 50 50 50 50 50 50 50 50 50 50 50 50 50 39.33

5 Survey, route alignment & pole spotting,

preparation of survey report and uploading in the

web portal after approval of Engineer

Km 1 1390.50 15 50 50 50 50 65 65 65 65 65 100 100 100 100 100 100 125 125.5

Sub-Total (V)

Part-VI Others

1 Line Crossing - Line to line / Road:

Excavation, Erection, testing and commissioning of

Protective guarding as per REC construction standard

drawing No A-1 to be provided at locations where 11KV/33

KV line is crossing road, 11 KV line is crossing LT Lines/

P&T lines etc. Supplying 2 Nos guarding cross arm made

of ISMC 75 channel, 2 Nos Y- guy with 7/3.14 mm wire, 2

Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 40mm

dia GI pipe of 3 meter long, 8 SWG GI wires for earthing

connection, 6 SWG wire for guard wire, 8 SWG wire for

cross lacing and 1 meter long extension piece of ISMC 100

channel, MS clamps, hardware etc all complete including

two coat red oxide painting and two or more coats of

aluminium oxide paint of reputed make. Providing and

installing cement concreting as per scope of work,

approved drawings and technical specifications.

SET 0.04 52 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3

Sub Total

2 33 KV FEEDER BAY at 33/11 KV Grid Substations

using RS Joist supportsNo. 9

Part V LT Line

Page 33 of 38

Page 35: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

i Excavation, Erection, testing and commissioning of

extension of 33 KV feeder bay using 2X4 support (2 Joist

welded together to form a support) of 9 m long, 175 x 85

mm RS Joists Bus Bar structure, 2x2 support ( 2 Joist

welded together to form a support) of 9 m long 175x85

mm RS Joist supports each for Isolator and Metering

equipment support structure including provision of base

plate (0.2x0.5x0.5m size), supporting galvanised steel

sections of channel, angle and flat, danger notice plate, 1

No GI Pipe earthing, 4 Nos Spike Earthing, earth

connection with 50X6 mm GS flat & 8 SWG GI wire, PG

Clamps, ACSR WOLF conductors, insulators, clamps,

channels, including line isolator switch of 800 A & 3 Nos

Station Class LAs etc as per specifications and tender

drawing complete as required. Providing and installing

cement concreting, charcoal, salt etc as per scope of

work, approved drawings and technical specifications.

Set 1 9 1 1 1 1 1 1 1 1 1

ii Design, Engineering and construction of

foundation, erection, testing and commissioning of

36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor

type Vacuum Circuit breaker along with 36kV, 1-

Phase, 25kA/3 seconds, 800-400-200/1-1-1 Amps,

3 Nos outdoor type Current Transformers along

with junction box (1 no junction box for 3 no of 1-

phase CTs), Jumpers, earthing, supporting

structures, permanent maintenance platform,

marshalling box etc required as per technical

specifications, scope of works and approved

drawings

Set 1 9 1 1 1 1 1 1 1 1 1

iii Erection, testing and commissioning of Indoor type control

and relay panel for 33kV, indoor, Control & Relay panel

along with E/F & O/C relays, Mimic Diagram, Voltmeter,

Ammeter, Annunciation Windows with annunciation relays

and other components etc as per approved drawings,

specifications and scope of works controlling:

33 kV feeder VCB with Static Tri-Vector Energy Meter

Set 1 9 1 1 1 1 1 1 1 1 1

Sub Total

3 11 KV FEEDER BAY at 33/11 KV Grid Substations

using RS Joist Supports No. 6

i Excavation, Erection, testing and commissioning of

extension of 11 KV Feeder bay using 2x4 Nos. (2 Joist

welded together to form a support) 9 m long, 175 x 85

mm RS Joist structure including provision of base plate

(0.2x0.5x0.5m size), danger notice plate, 1 No GI Pipe

earthing, 4 Nos Spike Earthing, earth connection with

50X6 mm GS flat & 8 SWG GI wire, PG Clamps, DOG

conductors, insulators, clamps, channels etc as per

specifications complete as required including isolator

switch of 400 A & 3 Nos Station Class LAs etc as per

specifications and tender drawing complete as required.

Providing and installing cement concreting, charcoal, salt

etc as per scope of work, approved drawings and technical

specifications.

Set 1 6 1 1 1 1 1 1

ii Design, Engineering and construction of foundation,

erection, testing and commissioning of 12 kV, 1250 A,

25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit

breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-

5, 3 Nos outdoor type Current Transformer along with

junction box (1 no junction box for 3 no of 1-phase CTs),

Jumpers, earthing, supporting structures, permanent

maintenance platform, marshalling box, control cabling

between VCB and indoor control panel and required

accessories complete as per technical specifications,

approved drawings and scope of the works.

Set 1 6 1 1 1 1 1 1

iii Indoor type control and relay panel:

Erection, testing and commissioning of Indoor type control

and relay panel for 11kV, 3phase, 630 A VCB (feeder

Breaker) consisting of A-meter, volt-meter, E/F & O/C

Relay & accessories complete as per specifications for

transformer breaker protection

set 1 6 1 1 1 1 1 1

Sub Total

4 Supply and installation of RGGVY sign Board as per

scope of work, approved drawings and technical

specification,

UEV25

a Village Electrification Board and mounting angles with

excavation for foundations and concreting No 25 25 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 1

Page 34 of 38

Page 36: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

b Distribution Transformer Electrification Board with clamp -

mounting on substation structure No 1738 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53

Sub Total

Addl. 5

MVA

2

Addl.10

MVA0

5-10 MVA 0

3.15-10

MVA0

3.15/1.6-5

MVA 4

Total 6pss 5

1 Design, Engineering and construction of

transformer foundation, erection, filtration, testing

and commissioning of 33/11 kV, 3 ph, 50 Hz,

ONAN, Cu Wound, Outdoor Conventional type

Power Transformer along with transformer oil,

Buchholtz relay, breather, OTI & WTI, Marshalling

Box, Conservator tank, oil level indicator, valves, 2

sets of 50x8 mm GS Neutral Earthing strips with

braided conductor on bushing end supported with

insulators, OTI & WTI Indicators, Vent explosion

plug, control wiring / cabling, cable supporting

tray on the body, transformer wheels, bushing etc

as required

set

a 10 MVA with off load tap changer No 1 0

b 5 MVA with off load tap changer No 1 6 1 1 1 1 1 1

2 Excavation, erection, cement concrete foundation,

erection, testing and commissioning of Galvanised

Gantry structures made of Lattice structures of

equal angles sections, flat as per approved

drawings. State practices are to be adopted in the

design. All structural steel members and bolts shall

be galvanized after fabrication as per IS:4759 and

zinc coating shall not be less than 610gm/sq.

meter for all structural steel members. All

L45x45x5 will have 23 mm back mark. All

L50x50x6 will have 28mm back mark. 3.5mm

spring washers are to be used under each nut,

structural steel shall conform to IS 2026. All weld

shall be 6mm filled weld unless specified

otherwise. All nuts and bolts shall be of property

class 5.6 of IS 1367. Plain washers shall be as per

IS 2016 & spring washers shall be IS: 3063 as per

approved drawings, technical specifications and

scope of the work.

MT 7 0.5 0.5 1 1 1 1 1 1

3 Design, Engineering and construction of foundation

(as per approved drawings), erection, testing and

commissioning of 36kV, 1250A, 25kA for 3 seconds,

3-ph, Outdoor type Vacuum Circuit breaker along

with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-

200/1-1-1 Amps outdoor type Current Transformer

along with junction box (1 no junction box for 3 no

of 1-phase CTs)], Jumpers, earthing, supporting

structures, maintenance platform, marshalling box,

control cabling between VCB and indoor control

panel and required accessories complete as per

approved drawings, technical specifications and

scope of the work.

Set 4 1 1 1 1

PART VII33/11 KV Augmentation of Existing Substation

works: Fully outdoor

Page 35 of 38

Page 37: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

4 Design, Engineering providing and installation of

ISMC 75 channel on top of indoor trench, erection

of panels on ISMC 75 channels, welding, testing

and commissioning of 33kV indoor Control & Relay

panel along with E/F & O/C relays, control and

power supply cabling in trench between field

equipment and panels, Mimic Diagram, Voltmeter,

Ammeter, Annunciation Windows with

annunciation relays and other components etc as

per approved drawings, technical specifications

and scope of the work for controlling:

a 33 kV Power transformer VCB with Static Tri-Vector

Energy Meter, No. 6

1 1 1 1 1 1

b 33 kV Power transformer VCB with Static Tri-Vector

Energy Meter, with differential relayNo. 0

5 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph

double break center rotating type (DBCR), Gang

Operated, isolator along with Support Insulators,

Operating Mechanism, Base Channel down Pipe

and all required accessories complete as per

approved drawings, technical specifications and

scope of the work,

Set 8 1 1 1 1 1 1 1 1

6 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

Commissioning of 36kV, 10kA, 1-ph Station Class

Lightening Arresters with mounting platform,

jumpering from bus bar, earthing connection using

50x6mm GS flat, hardware etc as required, as per

approved drawings, technical specifications and

scope of the work,

Set 6 1 1 1 1 1 1

7 Design, Engineering and construction of foundation

(as per approved drawings), Erection, testing and

Commissioning of 9kV, 10kA, 1-ph Station Class

Lightening Arrester with mounting platform,

jumpering from bus bar, earthing connection using

50x6mm GS flat, hardware, etc as required as per

approved drawings, technical specifications and

scope of the work.

Set 6 1 1 1 1 1 1

8.a Design, Engineering and construction of foundation (as

per approved drawings), Design, Engineering and

construction of foundation, erection, wiring, testing and

commissioning of 12 kV, 1250 A, 25kA, 3-ph, Outdoor

type Vacuum Circuit breaker along with 12 kV, 1-Phase,

25kA for 3 seconds, 600-300-150/5-5 A , outdoor type

Current Transformer along with junction box (1 no

junction box for 3 no of 1-phase CTs), Jumpers, earthing,

supporting structures, permanent maintenance platform,

marshalling box, control cabling between VCB and indoor

control panel and required accessories complete as per

approved drawings, technical specifications and scope of

the work for Transformer Protection Breaker Panel

Set 6 1 1 1 1 1 1

8.b Design, Engineering and construction of foundation (as

per approved drawings), Design, Engineering and

construction of foundation, erection, wiring, testing and

commissioning of 12 kV, 1250 A, 25kA, 3-ph, Outdoor

type Vacuum Circuit breaker along with 12 kV, 1-Phase,

25kA for 3 seconds, 1200-600-300/1-1-1 A , outdoor type

Current Transformer along with junction box (1 no

junction box for 3 no of 1-phase CTs), Jumpers, earthing,

supporting structures, permanent maintenance platform,

marshalling box, control cabling between VCB and indoor

Set 0

9 Installation, initial charging, cabling,

interconnection cabling, testing and commissioning

of 30V, 100 AH Pb Acid battery on battery stand

made of teak wood duly painted with anti rusting

paint, battery insulators, inter-battery wiring using

30 sqm copper single core multi strand cable,

terminal connectors, & all other accessories and

connectors as per as per approved drawings,

technical specifications and scope of the work,

Set 2.5 1 1 1

Page 36 of 38

Page 38: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

10 Design, engineering, construction of foundation,

Installation, interconnection cabling, testing and

commissioning of 30V, 40 Amp. Float-Cum-Boost

Battery Charger with full wave rectification for

220 V, 1 phase, 50 Hz AC Input Supply with built

in DCDB as per approved drawings, technical

specifications and scope of the work,

set 2.5 1 1 1

11 Excavation, laying, welding, refilling, earthing &

grounding conductor as per Approved Electrical

Layout for each sub-station and erection of riser up

to various equipment/gantry structures as per

scope of the work, specifications and approved

drawings,

a 75 x 8 mm MS flat for ground mat MT 1.5 0.5 0.5 0.5

b 50 x 6 mm Galvanized GS flat (risers) MT 1.5 0.5 0.5 0.5

c 25 mm dia MS Rod 3 m long for earth mat MT 0.125 0.04 0.04 0.045

12 Excavation, erection, testing and commissioning of

40 mm dia., 3000 mm long GI pipe earth electrode

by providing test link, RCC pit, RCC cover, placed

on GI frame, Charcoal, Salt and other accessories

complete as per approved drawings, technical

specifications and scope of the work for power

transformer neutral, station transformer neutral,

lightening arresters direct earthing.

Set 40 5 5 5 5 5 5 5 5

13 Erection, testing and commissioning of Bus

Conductor (wolf Conductor), bus jumpers to

various equipment using 11 KV and 33 KV

insulators, GI Pin, GI Hardware fittings, PG

Clamps, T-connectors etc as required as per

approved drawings, specifications and scope of the

work.

km 0.4 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05

14 Power Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required a 3.5 Core 70 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable meter 0.125 0.05 0.05 0.025

b 3.5 Core 35 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable meter 0.125 0.05 0.05 0.025

c 2 Core 16 Sq. mm armored, stranded aluminium

conductor, PVC insulated and PVC sheathed cable meter 0.5 0.05 0.05 0.05 0.05 0.05 0.05 0.1 0.1

15 Control Cables including their termination at

indoor/outdoor terminals including supply of

glands, lugs, cable ties, etc as required a 2 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable meter 0.1 0.025 0.025 0.05

b 5 Core 2.5 sqm armored, stranded copper conductor, PVC

insulated and PVC sheathed cable meter 0.5 0.05 0.05 0.05 0.05 0.05 0.05 0.1 0.1

c 10 Core 2.5 sqm armored, stranded copper conductor,

PVC insulated and PVC sheathed cable meter 0.5 0.05 0.05 0.05 0.05 0.05 0.05 0.1 0.1

Sub Total

PART

VIII33 KV Railway Crossing NO. 11

1

Laying,termination, Erection, Testing & commissioning of 2

nos. 33 KV grade 3-core 400 Sqmm XLPE power cable for

underground Railway Crossing including using

jointing/Termination Kit, GI pipe, CI pipe, clamps, conectors

bolts, nuts, fixing and fitting of barbed wire with all

accessories etc. complete in all respect as per TS, approved

drawing

Set 1 11 1 1 1 1 1 1 1 1 1 1 1

Sub Total

Part IX 11 KV Railway Crossing NO. 4Laying,termination, Erection, Testing & commissioning of 2

nos.11 KV grade 3-core 300 Sqmm XLPE power cable for

underground Railway Crossing including using

jointing/Termination Kit, GI pipe, CI pipe, clamps, conectors

bolts, nuts, fixing and fitting of anti-climbing device with all

accessories etc. complete in all respect as per TS, approved

drawing

Set 1 4 1 1 1 1

Sub Total

Part X LT Single Phase Service connection 62068

Page 37 of 38

Page 39: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power

ERECTION PERT CHART KATIHAR

Sl. No. Description Unit Unit

Quantity

Total

Quantity 2014 2015 2016

1 2 3 4 5 LOA date

21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24

1 Erection testing and commissioning of Single phase

service connection using PVC insulated cable of

size 2 Core 2.5 sqmm aluminium conductor (up to

35m length of house hold from LT line), 10 SWG GI

tension wire, 20 mm GI Pipe medium class to

accept service cable at consumer residence, A

meter board (200x350x40mm) for 1ø ( single

phase) energy meter,Service board

(200x150x40mm),Single phase (5-30A) fully static

class-1 energy meter, 2nos. single piano type ISI

marked 250 V/5A switch 1no. 250V/5A socket of

ISI marked, 250V/5A ISI marked holder, 144-

288V, upto 9 watts, 710 lumen LED lamp 250V,5A

capacity ISI mark lamp holder, Internal wiring

using 1.5 sqmm copper multistrands PVC insulated

ISI marked cable, 250V/16A double pole MCB of

ISI marked and a cut-out a 10mm dia earth

terminal point, internal wiring in ISI marked 12mm

dia PVC rigid pipes including its clamps, fittings

and fixtures as required as per REC drawing and

Specifications. Earth point would be connected

with existing earth potential maintained by

DISCOM through 10 SWG GI wireetc. as per detail

scope of work.

No 1 62068 200 500 500 1500 1500 2000 2500 3500 3500 3500 3500 4500 4500 4500 4500 4500 4500 4500 4500 3368

Sub Total

Grand Total