PERT NETWORK-Summery Sheet
NIT - 164/PR/NBPDCL/2014 KATIHAR
CONTRACTOR: ENERGO ENGINEERING PROJECTS LTD Date : 30/09/2014
LOA Nos.: Supply: 2732/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 1st Revision
Erection: 2733/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 2nd Revision Date : 31/10/2014
2014 2015 2016
Sl.
No.Item Description Unit
LOA
Quantity
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
Kick off Activities
1 Signing of contract
2 Site Office establishment
3 Deployment of Manpower
4Detail scope of work -DPR by
NBPDCL
Part-
I(c)New PSS
1Handing over of suitable land by
NBPDCL for New SubstationNos 9
2 Engineering and Design
3 Submission of construction drawings
4 Approval of construction drawings
5 Development of Land
6 Civil construction
7Submission of Vendor / GTP of
equipments & other items
8Approval of Vendor / GTP of
equipments & other items
9 Manufacturing ,Inspection & Supply
10Erection /installation/testing &
commissioning 1 1 1 1 1 1 1 1 1
Part-
II33 KV Line KM 195
1Fixation of source point and
allocation of 33KV Bay by NBPDCL
2Submission of survey/construction
drawings
3Approval of survey/construction
drawings
4Submission of Vendor / GTP of
equipments & other items
5Approval of Vendor / GTP of
equipments & other items
6 Manufacturing ,Inspection & Supply
7Erection /installation/testing &
commissioning 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15
Part-
III11 KV Line KM 1100
1Submission of survey/construction
drawings
2Approval of survey/construction
drawings
3Submission of Vendor / GTP of
equipments & other items
Date : 16/10/2014
Page 1 of 38
![Page 3: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/3.jpg)
2014 2015 2016
Sl.
No.Item Description Unit
LOA
Quantity
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4Approval of Vendor / GTP of
equipments & other items
5 Manufacturing ,Inspection & Supply
6Erection /installation/testing &
commissioning 15 30 50 50 50 50 50 50 55 55 75 75 75 75 75 75 75 75 45.25
Part-
IV
New Distribution Transformer
SubstationSet 1738
1Submission of survey/construction
drawings
2Approval of survey/construction
drawings
3Submission of Vendor / GTP of
equipments & other items
4Approval of Vendor / GTP of
equipments & other items
5 Manufacturing ,Inspection & Supply
6Erection /installation/testing &
commissioning 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53
Part-
VLT Lines KM 1390.5
1Submission of survey/construction
drawings
2Approval of survey/construction
drawings
3Submission of Vendor / GTP of
equipments & other items
4Approval of Vendor / GTP of
equipments & other items
5 Manufacturing ,Inspection & Supply
6Erection /installation/testing &
commissioning 30 30 30 65 65 75 75 85 85 85 85 85 85 85 85 85 85 85 85.5
Part-
VIIPSS-Augmentation PSS 5
1Submission of SLD/LAYOUT &
proposal
2Approval of SLD/LAYOUT & proposal
3 Submission of construction drawings
4 Approval of construction drawings
5 Civil construction
6Submission & approval of Vendor /
GTP of equipments & other items
7 Manufacturing ,Inspection & Supply
8Erection /installation/testing &
commissioning 1 1 1 1 1
Part-
XBPL Connection Nos. 62068
1Handing over of BPL List of village by
NBPDCL
2Submission of Vendor / GTP of
equipments & other items
3Approval of Vendor / GTP of
equipments & other itemsPage 2 of 38
![Page 4: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/4.jpg)
2014 2015 2016
Sl.
No.Item Description Unit
LOA
Quantity
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 Manufacturing ,Inspection & Supply
5Erection /installation/testing &
commissioning 200 500 500 1500 1500 2000 2500 3500 3500 3500 3500 4500 4500 4500 4500 4500 4500 4500 4500 3368
Village ElectrificationHanding over of Villages
UE Nos 1271 20 25 45 67 65 60 60 60 85 85 85 85 80 75 75 125 125 49
PE Nos 269 5 8 10 15 15 15 15 15 15 15 20 25 25 25 25 21
Total Nos 1540 20 25 50 75 75 75 75 75 100 100 100 100 100 100 100 150 150 70
NOTE: The above pert chart is subject to timely approval of vendors/drawings, inspections, issuance of DI/road permit, releasing of payment, arranging statuary clearances, Right of Way and discharging of other contractual obligations by NBPDCL
Page 3 of 38
![Page 5: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/5.jpg)
SUPPLY PERT CHART KATIHAR
CONTRACTOR: ENERGO ENGINEERING PROJECTS LTDLOA Nos.: Supply: 2732/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 Erection: 2733/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
PART-I (a)33/11 KV Substation Works (2X10 MVA) - Partly
outdoor type substation No. 0
1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil, Buchholtz relay, breather,
OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on
bushing end), isolating link, isolation with insulators}, Vent explosion
plug, control wiring between sensing equipment and marshalling box,
cable supporting tray on the body of transformer, transformer wheels,
LV/HV bushing etc as required as per technical specifications, approved
drawings and scope of the work.
a 10 MVA with off load tap changer No 2 0
0
2 100 KVA, 11/0.433 kV, 3 ph, 50 Hz, ONAN,copper wound, CRGO core,
outdoor type Station Transformer along with transformer oil and all
accessories as required as per technical specifications, scope of works and
approved drawings.
No 1 0
0
3 DP structure comprising of MS galvanised 2 Nos,2x175x85mm double
welded 8 meter long RS joists, transformer base channels, 11KV HG Fuse
structure, 11 KV Isolators, 11 KV Station Type LAs structures etc including
hardware etc all complete for erection of 11/0.433 KV Station
Transformer.
Set 1 0
0
4 Galvanised Gantry structures made of Lattice structures of equal angles
sections, flat as per approved drawings. State practices are to be adopted
in the design. All structural steel members and bolts shall be galvanized
after fabrication as per IS:4759 and zinc coating shall not be less than
610gm/sq. meter for all structural steel members. All L45x45x5 will have
23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring
washers are to be used under each nut, structural steel shall conform to IS
2026. All weld shall be 6mm filled weld unless specified otherwise. All nuts
and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be
as per IS 2016 & spring washers shall be IS: 3063.
MT 16 0
0
5
36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1
Amps, 3 Nos outdoor type Current Transformers along with junction box
(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting
structures, permanent maintenance platform, marshalling box etc
required as per technical specifications, scope of works and approved
drawings
Set 4 0
0
6 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic
Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation
relays and other components etc as per approved drawings, specifications
and scope of works controlling:
0
a 33 kV feeder VCB with Static Tri-Vector Energy Meter No 2 0
b Power transformer 33 kV VCB with Static Tri-Vector Energy Meter with
differential relayNo 2 0
0
7 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings (without earth switch)
Set 7 0
0
8 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set= 3 nos.) Set 4 0
0
9 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set= 3
nos.)
Set 11 0
0
10 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos
indoor type Current Transformer,& PT indoor mounting type control panel
for Transformer breaker, control cabling between VCB and indoor control
panel and required accessories, A-meter, volt-meter, E/F & O/C , Relay &
accessories complete as per Technical specification( Volume-II) for
transformer breaker protection
Set 2 0
0
11 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor
type Current Transformer & PT, indoor mounting type control panel for
feeder protection, control cabling between VCB and indoor control panel
and required accessories, A-meter, volt-meter, 3-phase electronic energy
meter, E/F & O/C , Relay & accessories complete as per Technical
specification( Volume-II) for feeder breaker protection
Set 10 0
0
PERT NETWORK
NIT - 164/PR/NBPDCL/2014 KATIHAR
Date : 27/10/2014
Page 4 of 38
![Page 6: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/6.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
12 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor
type Current Transformer & PT, indoor mounting type control panel for
bus coupler, control cabling between VCB and indoor control panel and
required accessories, A-meter, volt-meter, 3-phase electronic energy
meter, E/F & O/C , Relay & accessories complete as per specification(
Volume-II) for bus coupler protection
Set 1 0
0
13
30V, 100 AH Pb Acid battery, battery stand made of teak wood duly
painted with anti rusting paint, battery insulators, inter-battery wiring
using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal
connectors, & all other accessories and connectors as per technical
specifications, approved drawings and scope of works.
Set 1 0
0
14 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave
rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB
as per technical specifications, approved drawings and scope of works. set 1 0
0
15 433V, ACDB along with three phase-neutral voltmeter, three phase
ammeter and Selector switches, 200 Amps TPN switch fuse unit as
incomer, 32 Amps TPN switches as outgoing feeders suited for number of
control panels, nos of VCB kiosk panel, having 20% spare outgoing
feeders, mounting arrangements etc as per technical specifications,
approved drawings and scope of works.
Set 1 0
0
16 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including
hardware fittings, hardware etc 0
a Wolf conductor (150 Sq. mm) km 0.3 0
b 50 mm dia Al. pipe Mtr. 50 0
0
17 Earthing & Grounding conductor as per Approved Electrical Layout for each
sub-station with 0
a 75 x 8 mm MS flat for ground mat MT 2.00 0.00
b 50 x 6 mm Galvanized GS flat (risers) MT 2.00 0.00
c 25mm dia MS rod 3 m long for earth mat MT 0.50 0.00
0
18 40 mm dia., 3000 mm long GI pipe earth electrode with test link, as per
technical specification. (for Power Transformer Neutral, Station
Transformer Neutral and Lightening Arresters direct earthing) Set 50 0
0
19 33 and 11 KV Insulator - Pin, Post and Disc insulators along with
Hardware & accessories suitable for Wolf conductors as per approved
drawings & specifications. (33 KV Disc Insulator of 70 KN, 1 set 33 KV Disc
Insulator=3 nos., for 33 KV Post Insulator 1 set = 2 nos.)
Set 1 0
0
20 Station Lighting System complete for switchyard, control room building,
main gate as per scope of work complete, 0
a Internal Electrification works of control room Set 1 0
b External Electrification including power receptacles, station yard lighting
with 4 Nos lightening mast (fitted with 2x250 watts SON fittings) made of
12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation
410 – SP - 60, complete as per technical specifications, approved drawings
and scope of the work.
Set 1 0
0
21 Fire Fighting Equipment comprises of Dry Chemical Powder Type (6 Kg) for
control room, CO2 Type of 4.5Kg Capacity for Control Room, two sets of
fire buckets set including their stand as per technical specifications, scope
of works and approved drawings (one sets= 3 nos. of fire Buckets)
Set 1 0
0
22 Power Cables including their termination materials like glands, lugs etc. 0
a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.07 0
b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.05 0
c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.75 0
0
23 Control cables including their termination materials like glands, lugs etc. 0
a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.2 0
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 1 0
c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.6 0
0
24 Outdoor type Distribution Box for station transformer comprising 200 A
incomer – switch fuse unit, 6 Nos Outgoing feeder – 63 A capacity switch
Fuse unit, 2 Nos 32 A Fuse switch fuse units, three phase, 63A, timer
control yard lighting contactor circuit, 3 phase, electronic Energy meter
for transformer power supply metering with suitable CT, 1 no., 20 A
Industrial socket and switch for local power supply requirements,
mounting channel clamps and hardware as per scope of work, technical
specifications and approved drawings,
Set 1 0
0
Page 5 of 38
![Page 7: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/7.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
25.a 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings
Set 10 0
25..b 12 kV, 200A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings
Set 1 0
0
26 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential
Transformer including accessories etc., complete as per technical
specifications, approved drawings and scope of the works. Set 2 0
0
27 Substation Tools and Plants like megger, earth tester, Multimeter, Tong
tester, D-spanners, screw drivers, earthing rods, earth mat etc as required
as per scope of work.
Set per
PSS1 0
0
28 11 KV, XLPE, 3 phase power cable, aluminium conductor, stranded 0
1Cx 300 sqmm ( Un-armored) km 0.72 0.00
3Cx 185sqmm (armored) km 1.10 0.00
0
29 Cable termination kit suitable for termination in transformer cable box/
breaker panel/ outdoor 11 KV terminals complete with all accessories etc. 0
1Cx 300 sqmm set 18 0
3Cx 185sqmm set 24 0
0
30 3 Phase 11 KV HG Fuse complete 200 A capacity as per technical
specificationsSet 1 0
Sub Total
0
PART-I (b)33/11 KV Substation Works (3X5 MVA) - Partly
outdoor type substation No. 0
1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil, Buchholtz relay, breather,
OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on
bushing end), isolating link, isolation with insulators}, Vent explosion
plug, control wiring between sensing equipment and marshalling box,
cable supporting tray on the body of transformer, transformer wheels,
LV/HV bushing etc as required as per technical specifications, approved
drawings and scope of the work.
a 5 MVA with off load tap changer No 3 0
0
2 100 KVA, 11/0.433 kV, 3 ph, 50 Hz, ONAN,copper wound, CRGO core,
outdoor type Station Transformer along with transformer oil and all
accessories as required as per technical specifications, scope of works and
approved drawings.
No 1 0
0
3 DP structure comprising of MS galvanised 2 Nos,2x175x85mm double
welded 8 meter long RS joists, transformer base channels, 11KV HG Fuse
structure, 11 KV Isolators, 11 KV Station Type LAs structures etc including
hardware etc all complete for erection of 11/0.433 KV Station
Transformer.
Set 1 0
0
4 Galvanised Gantry structures made of Lattice structures of equal angles
sections, flat as per approved drawings. State practices are to be adopted
in the design. All structural steel members and bolts shall be galvanized
after fabrication as per IS:4759 and zinc coating shall not be less than
610gm/sq. meter for all structural steel members. All L45x45x5 will have
23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring
washers are to be used under each nut, structural steel shall conform to IS
2026. All weld shall be 6mm filled weld unless specified otherwise. All nuts
and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be
as per IS 2016 & spring washers shall be IS: 3063.
MT 16 0
0
5
36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1
Amps, 3 Nos outdoor type Current Transformers along with junction box
(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting
structures, permanent maintenance platform, marshalling box etc
required as per technical specifications, scope of works and approved
drawings
No 5 0
0
6 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic
Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation
relays and other components etc as per approved drawings, specifications
and scope of works controlling:
0
a 33 kV feeder VCB with Static Tri-Vector Energy Meter No 2 0
b Power transformer 33 kV VCB with Static Tri-Vector Energy Meter No 3 0
0
7 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings (without earth switch)
Set 9 0
0
Page 6 of 38
![Page 8: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/8.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
8 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set= 3 nos.) Set 5 0
0
9 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set= 3
nos.)
Set 10 0
0
10 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos
indoor type Current Transformer,& PT indoor mounting type control panel
for Transformer breaker, control cabling between VCB and indoor control
panel and required accessories, A-meter, volt-meter, Relay & accessories
complete as per specifications for transformer breaker protection
Set 3 0
0
11 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos
indoor type Current Transformer,& PT indoor mounting type control panel
for Transformer breaker, control cabling between VCB and indoor control
panel and required accessories, A-meter, volt-meter, E/F & O/C , Relay &
accessories complete as per Technical specification( Volume-II) for
transformer breaker protection
Set 9 0
0
12 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor
type Current Transformer & PT, indoor mounting type control panel for
bus coupler, control cabling between VCB and indoor control panel and
required accessories, A-meter, volt-meter, 3-phase electronic energy
meter, E/F & O/C , Relay & accessories complete as per specification(
Volume-II) for bus coupler protection
Set 2 0
0
13
30V, 100 AH Pb Acid battery, battery stand made of teak wood duly
painted with anti rusting paint, battery insulators, inter-battery wiring
using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal
connectors, & all other accessories and connectors as per technical
specifications, approved drawings and scope of works.
Set 1 0
0
14 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave
rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB
as per technical specifications, approved drawings and scope of works. set 1 0
0
15 433V, ACDB along with three phase-neutral voltmeter, three phase
ammeter and Selector switches, 200 Amps TPN switch fuse unit as
incomer, 32 Amps TPN switches as outgoing feeders suited for number of
control panels, nos of VCB kiosk panel, having 20% spare outgoing
feeders, mounting arrangements etc as per technical specifications,
approved drawings and scope of works.
No 1 0
0
16 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including
hardware fittings, hardware etc 0
a Wolf conductor (150 Sq. mm) km 0.45 0
b 50 mm dia Al. pipe Mtr. 50 0
0
17 Earthing & Grounding conductor as per Approved Electrical Layout for each
sub-station with 0
a 75 x 8 mm MS flat for ground mat MT 2.5 0
b 50 x 6 mm Galvanized GS flat (risers) MT 2.5 0
c 25mm dia MS rod 3 m long for earth mat MT 0.5 0
0
18 40 mm dia., 3000 mm long GI pipe earth electrode with test linkas per
technical specification. (for Power Transformer Neutral, Station
Transformer Neutral and Lightening Arresters direct earthing) Set 50 0
0
19 33 and 11 KV Insulator - Pin, Post and Disc insulators along with
Hardware & accessories suitable for Wolf conductors as per approved
drawings & specifications. (33 KV Disc Insulator of 70 KN, 1 set 33 KV Disc
Insulator=3 nos., for 33 KV Post Insulator 1 set = 2 nos.)
Set 1 0
0
20 Station Lighting System complete for switchyard, control room building,
main gate as per scope of work complete, 0
a Internal Electrification works of control room Set 1 0
b External Electrification including power receptacles, station yard lighting
with 4 Nos lightening mast (fitted with 2x250 watts SON fittings) made of
12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation
410 – SP - 60, complete as per technical specifications, approved drawings
and scope of the work.
Set 1 0
0
21 Fire Fighting Equipment comprises of Dry Chemical Powder Type (6 Kg) for
control room, CO2 Type of 4.5Kg Capacity for Control Room, two sets of
fire buckets set including their stand as per technical specifications, scope
of works and approved drawings (one sets= 3 nos. of fire Buckets)
Set 1 0
0
22 Power Cables including their termination materials like glands, lugs etc. 0
a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.07 0
Page 7 of 38
![Page 9: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/9.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.05 0
c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.75 0
0
23 Control cables including their termination materials like glands, lugs etc. 0
a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.2 0
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 1 0
c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.7 0
0
24 Outdoor type Distribution Box for station transformer comprising 200 A
incomer – switch fuse unit, 6 Nos Outgoing feeder – 63 A capacity switch
Fuse unit, 2 Nos 32 A Fuse switch fuse units, three phase, 63A, timer
control yard lighting contactor circuit, 3 phase, electronic Energy meter
for transformer power supply metering with suitable CT, 1 no., 20 A
Industrial socket and switch for local power supply requirements,
mounting channel clamps and hardware as per scope of work, technical
specifications and approved drawings,
Set 1 0
0
25.a 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings
Set 9 0
25..b 12 kV, 200A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings
Set 1 0
0
26 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential
Transformer including accessories etc., complete as per technical
specifications, approved drawings and scope of the works. Set 2 0
0
27 Substation Tools and Plants like megger, earth tester, Multimeter, Tong
tester, D-spanners, screw drivers, earthing rods, earth mat etc as required
as per scope of work.
Set per
PSS1 0
0
28 11 KV, XLPE, 3 phase power cable, aluminium conductor, stranded 0
1Cx 300 sqmm ( Un-armored) km 0.72 0
3Cx 185sqmm (armored) km 1.1 0
0
29 Cable termination kit suitable for termination in transformer cable box/
breaker panel/ outdoor 11 KV terminals complete with all accessories etc. 0
1Cx 300 sqmm set 24 0
3Cx 185sqmm set 22 0
0
30 3 Phase 11 KV HG Fuse complete 200 A capacity as per technical
specificationsSet 1 0
0
Sub total
PART-I (c)33/11 KV Substation Works -2 x 5 MVA, Partly
outdoor type substation No. 9
1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil, Buchholtz relay, breather,
OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on
bushing end), isolating link, isolation with insulators}, Vent explosion
plug, control wiring between sensing equipment and marshalling box,
cable supporting tray on the body of transformer, transformer wheels,
LV/HV bushing etc as required as per technical specifications, approved
drawings and scope of the work.
a 5 MVA with off load tap changer No 2 18 2 2 2 1 2 1 2 2 2 2
0
2 100 KVA, 11/0.433 kV, 3 ph, 50 Hz, ONAN,copper wound, CRGO core,
outdoor type Station Transformer along with transformer oil and all
accessories as required as per technical specifications, scope of works and
approved drawings.
No 1 9
1 1 1 1 1 1 1 1 1
0
3 DP structure comprising of MS galvanised 2 Nos,2x175x85mm double
welded 8 meter long RS joists, transformer base channels, 11KV HG Fuse
structure, 11 KV Isolators, 11 KV Station Type LAs structures etc including
hardware etc all complete for erection of 11/0.433 KV Station
Transformer.
Set 1 9
1 1 1 1 1 1 1 1 1
0
Page 8 of 38
![Page 10: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/10.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 Galvanised Gantry structures made of Lattice structures of equal angles
sections, flat as per approved drawings. State practices are to be adopted
in the design. All structural steel members and bolts shall be galvanized
after fabrication as per IS:4759 and zinc coating shall not be less than
610gm/sq. meter for all structural steel members. All L45x45x5 will have
23 mm back mark. All L50x50x6 will have 28mm back mark. 3.5mm spring
washers are to be used under each nut, structural steel shall conform to IS
2026. All weld shall be 6mm filled weld unless specified otherwise. All nuts
and bolts shall be of property class 5.6 of IS 1367. Plain washers shall be
as per IS 2016 & spring washers shall be IS: 3063.
MT 14 126.00 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8 6
0
5
36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1
Amps, 3 Nos outdoor type Current Transformers along with junction box
(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting
structures, permanent maintenance platform, marshalling box etc
required as per technical specifications, scope of works and approved
drawings
Set 4 36 4 4 4 4 4 4 4 4 4
0
6 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic
Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation
relays and other components etc as per approved drawings, specifications
and scope of works controlling:
0
a 33 kV feeder VCB with Static Tri-Vector Energy Meter No 2 18 2 2 2 2 2 2 2 2 2
b Power transformer 33 kV VCB with Static Tri-Vector Energy Meter No 2 18 2 2 2 2 2 2 2 2 2
0
7 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings (without earth switch)
Set 7 63
7 7 7 7 7 7 7 7 7
0
8 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set= 3 nos.) Set 4 364 4 4 4 4 4 4 4 4
0
9 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set= 3
nos.)
Set 7 637 7 7 7 7 7 7 7 7
0
10 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos
indoor type Current Transformer,& PT indoor mounting type control panel
for Transformer breaker, control cabling between VCB and indoor control
panel and required accessories, A-meter, volt-meter, E/F & O/C , Relay &
accessories complete as per Technical specification( Volume-II) for
transformer breaker protection
Set 2 18 2 2 2 2 2 2 2 2 2
0
11 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor
type Current Transformer & PT, indoor mounting type control panel for
feeder protection, control cabling between VCB and indoor control panel
and required accessories, A-meter, volt-meter, 3-phase electronic energy
meter, E/F & O/C , Relay & accessories complete as per Technical
specification( Volume-II) for feeder breaker protection
Set 6 54 6 6 6 6 6 6 6 6 6
0
12 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, indoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos indoor
type Current Transformer & PT, indoor mounting type control panel for
bus coupler, control cabling between VCB and indoor control panel and
required accessories, A-meter, volt-meter, 3-phase electronic energy
meter, E/F & O/C , Relay & accessories complete as per specification(
Volume-II) for bus coupler protection
Set 1 9 1 1 1 1 1 1 1 1 1
0
13
30V, 100 AH Pb Acid battery, battery stand made of teak wood duly
painted with anti rusting paint, battery insulators, inter-battery wiring
using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal
connectors, & all other accessories and connectors as per technical
specifications, approved drawings and scope of works.
Set 1 9 1 1 1 1 1 1 1 1 1
0
14 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave
rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB
as per technical specifications, approved drawings and scope of works. set 1 9 1 1 1 1 1 1 1 1 1
0
15 433V, ACDB along with three phase-neutral voltmeter, three phase
ammeter and Selector switches, 200 Amps TPN switch fuse unit as
incomer, 32 Amps TPN switches as outgoing feeders suited for number of
control panels, nos of VCB kiosk panel, having 20% spare outgoing
feeders, mounting arrangements etc as per technical specifications,
approved drawings and scope of works.
Set 1 9 1 1 1 1 1 1 1 1 1
0
16 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including
hardware fittings, hardware etc 0
a Wolf conductor (150 Sq. mm) km 0.3 2.70 1.7 1
b 50 mm dia Al. pipe Mtr. 50 450.00 50 50 50 50 50 50 50 50 50
0
Page 9 of 38
![Page 11: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/11.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
17 Earthing & Grounding conductor as per Approved Electrical Layout for each
sub-station with 0
a 75 x 8 mm MS flat for ground mat MT 2 18.00 2 2 2 2 2 2 2 2 2
b 50 x 6 mm Galvanized GS flat (risers) MT 2 18.00 2 2 2 2 2 2 2 2 2
c 25mm dia MS rod 3 m long for earth mat MT 0.5 4.50 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
0
18 40 mm dia., 3000 mm long GI pipe earth electrode with test link,as per
technical specification. (for Power Transformer Neutral, Station
Transformer Neutral and Lightening Arresters direct earthing) Set 40 360 40 40 40 40 40 40 40 40 40
0
19 33 and 11 KV Insulator - Pin, Post and Disc insulators along with
Hardware & accessories suitable for Wolf conductors as per approved
drawings & specifications. (33 KV Disc Insulator of 70 KN, 1 set 33 KV Disc
Insulator=3 nos., for 33 KV Post Insulator 1 set = 2 nos.)
Set 1 9 1 1 1 1 1 1 1 1 1
0
20 Station Lighting System complete for switchyard, control room building,
main gate as per scope of work complete, 0
a Internal Electrification works of control room Set 1 9
1 1 1 1 1 1 1 1 1
b External Electrification including power receptacles, station yard lighting
with 4 Nos lightening mast (fitted with 2x250 watts SON fittings) made of
12 meters high Steel Tubular Poles (IS 2713 part I, II III) of designation
410 – SP - 60, complete as per technical specifications, approved drawings
and scope of the work.
Set 1 9
1 1 1 1 1 1 1 1 1
0
21 Fire Fighting Equipment comprises of Dry Chemical Powder Type (6 Kg) for
control room, CO2 Type of 4.5Kg Capacity for Control Room, two sets of
fire buckets set including their stand as per technical specifications, scope
of works and approved drawings (one sets= 3 nos. of fire Buckets)
Set 1 9
1 1 1 1 1 1 1 1 1
0
22 Power Cables including their termination materials like glands, lugs etc. 0
a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.07 0.63
0.63
b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.05 0.45
0.45
c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.5 4.50
4.5
0
23 Control cables including their termination materials like glands, lugs etc. 0
a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.2 1.80
1.8
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.7 6.30
6.3
c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.5 4.50
4.5
0
24 Outdoor type Distribution Box for station transformer comprising 200 A
incomer – switch fuse unit, 6 Nos Outgoing feeder – 63 A capacity switch
Fuse unit, 2 Nos 32 A Fuse switch fuse units, three phase, 63A, timer
control yard lighting contactor circuit, 3 phase, electronic Energy meter
for transformer power supply metering with suitable CT, 1 no., 20 A
Industrial socket and switch for local power supply requirements,
mounting channel clamps and hardware as per scope of work, technical
specifications and approved drawings,
Set 1 9 1 1 1 1 1 1 1 1 1
0
25.a 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings
Set 6 54 6 6 6 6 6 6 6 6 6
25..b 12 kV, 200 A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings
Set 1 9 1 1 1 1 1 1 1 1 1
26 36 kV, 3-pole, 1-Phase, 33kV/110 volt, Single core outdoor type Potential
Transformer including accessories etc., complete as per technical
specifications, approved drawings and scope of the works. Set 2 18
2 2 2 2 2 2 2 2 2
0
27
Substation Tools and Plants like megger, earth tester, Multimeter, Tong
tester, D-spanners, screw drivers, earthing rods, earth mat etc as required
as per scope of work.
Set per
PSS1 9
1 1 1 1 1 1 1 1 1
0
28 11 KV, XLPE, 3 phase power cable, aluminium conductor, stranded 0
1Cx 300 sqmm ( Un-armored)km 0.54 4.86
4.86
3Cx 185sqmm (armored)km 0.7 6.30
3 3.3
29 Cable termination kit suitable for termination in transformer cable box/
breaker panel/ outdoor 11 KV terminals complete with all accessories etc. 0
1Cx 300 sqmm set 18 162 18 18 18 18 18 18 18 18 18
Page 10 of 38
![Page 12: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/12.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3Cx 185sqmm set 14 126 14 14 14 14 14 14 14 14 14
0
30 3 Phase 11 KV HG Fuse complete 200 A capacity as per technical
specificationsSet 1 9
1 1 1 1 1 1 1 1 1
0
Sub total
PART II 33 KV Lines Dog 195
1 Support for 33 KV overhead line
a 9 meter/400 KG PSC Poles with RCC Base plate
No 16 3120100 100 100 100 200 200 200 200 250 250 250 250 200 200 200 200 120
b13 m long RS Joist 152x152 mm with RCC Base plate
No 1 19520 20 20 20 20 20 20 20 20 15
0
2
Galvanized pre-fabricated steel materials- Channels, angle, flats for over
head structures as per technical specification, approved drawings and
scope of work.
MT 0.67 130.65010 10 10 10 10 10 10 10 10 10 10 10.65 10
0
3
ACSR DOG Conductor of size 6/4.72 mm + 7/1.57 mm (100 mm² Al. Area)
including jointing sleeves and helicon formed fittings etc as required as
per technical specification, approved drawings and scope of work. km 3.09 602.55
50 50 50 50 50 50 50 50 50 50 50 52.55
0
4Galvanized Steel Nuts, bolts and washers as per technical specification,
approved drawings and scope of work. MT 0.024 4.680
2 2.68
0
5
33 KV porcelain Disc insulator 70 KN along with HW fittings as per
technical specification, approved drawings and scope of work.
(1set=3nos.)
Set 6 1170100 100 100 100 100 100 100 100 100 70 100 100
0
633 KV porcelain Pin Insulators with GI PIN as per technical specification,
approved drawings and scope of work. Set 48 9360
500 500 500 500 500 500 500 750 750 750 750 750 750 750 610
0
7
40 mm dia., 3000 mm long GI pipe earth electrode with test link as per
technical specification, approved drawings and scope of work, set 1 19520 20 20 20 20 20 20 20 20 15
0
8Coil earthing as per technical specification, approved drawings and scope
of work. Set 15 2925
195 100 100 100 100 200 200 200 200 200 200 200 200 200 200 200 200 125
0
98 SWG GI wire for earthing as per technical specification, approved
drawings and scope of work. MT 0.003 0.585
0.585
0
10
Galvanized Stay set with 50x8 mm stay clamp, HT stay guy insulator, nut
bolts, 2 Nos turn buckles, 1.8 m long, 20 mm diameter solid GS stay rod &
7/4.00 mm dia GI stranded wire complete as per technical specification,
approved drawings and scope of work.
Set 6 1170
100 100 100 100 100 100 100 100 100 70 100 100
0
11
36kV, 630A, 25kA, 3-ph, 3 Pin type, Vertical Mounting type, Gang
Operated, AB Switch along with Support Insulators, Base Channel down
Pipe, Arcing Horns etc. complete as per technical specifications, scope of
works and approved drawings
Set 0.1 20
100 100 100 100 100 100 100 100 100 70 100 100
Sub-Total (II)
Rabb
it405.00
Wea
sel695.25
1100.251 Support for 11 KV overhead line
a 8 m/200 kgs PSC Poles with RCC Base plate No 16.75 18429 400 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1029
b13 m long RS Joist 152x152 mm with RCC Base plate
No 0.25 27520 20 20 20 20 20 20 20 20 20 20 20 20 15
2
Galvanized pre-fabricated steel materials- channel, angle, flats for over
head structures as per technical specification, approved drawings and
scope of work.
MT 0.34 374.08510 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 20 24.08
0.000
3Galvanized Steel Nuts, Bolts with Washers as per technical specification,
approved drawings and scope of work. MT 0.0155 17.054
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
0
4
ACSR Conductors with Jointing sleeves, binding materials etc as required
as per technical specification, approved drawings and scope of work. 0
a 7/3.35 mm (50 mm² Al. Area) ( Rabbit) km 3.09 1251.45 50 100 100 100 150 150 150 150 150 151.45
b7/2.59 mm (30 mm² Al. Area) (weasel)
km 3.09 2148.32 100 200 200 300 300 300 300 300 148.32
0
5Porcelain Insulators with mounting hardware, fittings as per technical
specification, approved drawings and scope of work. 0
11 KV 45 KN Disc Insulator with hardware fittings (1set=1no.) set 6 6602 200 300 300 300 300 500 500 500 500 500 300 300 300 300 300 300 300 300 302
11 KV Pin insulators with GI Pin set 48 52812 1000 1500 1500 1500 3000 3000 3000 3000 3000 3000 4000 4000 3000 3000 3000 3000 3000 3000 3312
0
PART III
11 KV Lines
Page 11 of 38
![Page 13: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/13.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
6
Galvanized Stay set with 50x8 mm Stay clamp, HT stay guy insulator, nut
bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS stay rod &
7.3.15 mm dia GI stranded wire etc as required as per technical
specification, approved drawings and scope of work.
Set 6 6602
200 300 300 300 300 500 500 500 500 500 300 300 300 300 300 300 300 300 302
0
7 Earthing 0
a
40 mm dia., 3000 mm long GI pipe earth electrode with test link as per
technical specification, approved drawings and scope of work, Set 1 1100 50 50 100 100 100 100 100 100 100 100 100 100
bCoil earthing as per technical specification, approved drawings and scope
of work. Set 15 16504
500 500 500 500 500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1004
c8 SWG GI wire for earthing as per technical specification, approved
drawings and scope of work. MT 0.003 3.301
1 1 1.3
0
8
12kV, 200A, 25kA for 3sec, 3-ph, 3 Pin type, Vertical Mounting type, Gang
Operated, AB Switch along with Support Insulators, Base Channel down
Pipe, Arcing Horns etc. complete as per technical specifications, scope of
works and approved drawings
Set 0.1 110 5 5 10 10 10 10 10 10 10 10 10 10
Sub-Total (III)
63 KVA 1402
100
KVA336
Total 1738
1Distribution Transformer with all accessories as per as per technical
specification, approved drawings and scope of work. Nos
aThree Phase 63 KVA
No 1 1402 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 102
b Three Phase 100 KVA No 1 336 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 26
2Distribution Class 11KV Lightening Arrester for DT as per technical
specification, approved drawings and scope of work. Set 1 1738
70 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128
3 Substation Support Nos
a8 Mtr/200 KG PSC Poles with base plate
No 2 3476 140 140 140 140 240 240 240 240 240 240 240 240 240 250 250 256
4
Galvanized pre-fabricated steel materials- channel, angle, flats for over
head structures as per technical specification, approved drawings and
scope of work.
MT 0.255 443.1917.85 17.85 17.85 17.85 30.60 30.60 30.60 30.60 30.60 30.60 30.60 30.60 30.60 31.88 31.88 32.64
5Galvanized Steel Nuts, Bolts with Washers as per technical specification,
approved drawings and scope of work. MT 0.016 27.808
1.12 1.12 1.12 1.12 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 1.92 2.00 2.00 2.05
6
Porcelain Insulators with hardware fittings, hardware etc as required as
per technical specification, approved drawings and scope of work.
a11 KV, Disc Insulator with hardware fittings
Set 3 5214210 210 210 210 360 360 360 360 360 360 360 360 360 375 375 384
7
12 kV, 200A, 3-ph, 3 Pin type, Vertical Mounting type, Gang Operated, AB
Switch along with Support Insulators, Base Channel down Pipe, Arcing
Horns etc. complete as per technical specifications, scope of works and
approved drawings
Sets 1 1738 70 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128
811KV,200 AMP 3 pole, HG fuse set for 3-ph DTs as per technical
specification, approved drawings and scope of work. Sets 1 1738
70 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128
9
LT Distribution box with metering, One no. TPMCCB and LT control
mechanism as per scope of the work, technical specifications and
approved drawings suitable for following transformer:
a Three Phase 63 KVA No 1 1402 50 50 50 50 100 100 100 100 100 100 100 100 100 100 100 102
bThree Phase 100 KVA No 1 336 20 20 20 20 20 20 20 20 20 20 20 20 20 25 25 26
10
3 Nos pipe earthing using 40mm dia GI pipe 3000 mm long, as per IS 1161
and as per REC construction drawings as per approved drawings and
technical specifications,
Set 1 173870 70 70 70 120 120 120 120 120 120 120 120 120 125 125 128
11
ACSR Rabbit Conductor for jumpering including PG Clamps, bi-metallic
connectors, hardware etc as per technical specification, approved
drawings and scope of work.
km 0.009 15.64215.642
12
XLPE Aluminium Cable Conductor, Stranded, unarmoured cable for
connection of transformer LV bushing to Distribution Box as per Scope of
work, technical specification and approved drawings:
0
a1CX50 sqm aluminium conductor cable for Three Phase 63 KVA
km 0.015 21.0310 11.03
b1Cx95 sqm aluminium conductor cable for Three Phase 100KVA
km 0.015 5.040 2 3.04
13MRI/CMRI for DT meter as per technical specifications and scope of the
work, Nos. 0.02 35
Sub-Total (IV)
ONE
PHASE556.2
THREE
PHASE834.3
Total 1390.5
1 Support for LT overhead Line
PART IVDistribution Transformer Substations
PART VLT Line
Page 12 of 38
![Page 14: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/14.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
a8 m/200 Mg PSC Poles with RCC Base plate
No 21 29201500 500 1000 1000 1000 1000 1000 1000 1000 1500 1700 2000 2000 2000 2000 2000 2000 2000 2000 2001
0
2
Galvanized pre-fabricated steel materials - channel, angle, flats for over
head structures as per approved drawings, technical specifications and
scope of work
MT 0.02 27.811 1 1 1 1 1.25 1.25 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.75 1.75 1.81
3Nuts and Bolts with Washers as per approved drawings, technical
specifications and scope of workMT 0.001 1.3905
0.75 0.6405
4
Galvanised Stay Set with 50x8mm stay clamp, HT stay guy insulator, nut
bolts, 2 Nos turn buckles, 1.8 m long, 16 mm diameter solid GS Stay rod &
7/3.15 mm Dia GI stranded wire etc as requiredSet 7 9733.5
170 199 330 330 330 330 330 330 330 500 570 665 665 665 665 665 665 665 665 665
5 Earthing
Coil earthing as per technical specification, approved drawings and scope
of work. Set 5 6952.5
125 125 250 250 250 250 250 250 250 250 400 400 400 500 500 500 500 500 500 503
6
LT Line on AB Cables:(average span 40 m) including erection accessories
like Insulation Piercing Connectors, Anchoring Assembly, Suspension
Assembly, Service Clamp, Transformer Connection, Junction Sleeves and
Service Main Distribution boxes etc as required
a1-Phase ABC [1X16{Phase}+1x16 {Neutral}+{1x25 Messenger cum earth wire}] line
as per TS Km 1.03 572.886 10 10 20 20 20 20 20 20 20 30 30 40 40 40 40 40 40 40 40 32.886
b3-Phase ABC [3X50{Phase}+{1x35 Messenger cum earth wire}] line as per TS
Km 1.03 859.32915 15 35 35 35 35 35 35 35 35 55 55 55 55 55 55 55 55 55 54.329
Sub-Total (V)
PART VI Others
1 Line Crossing - Line to line / Road: Protective guarding as per REC construction standard drawing No A-1 to be provided
at locations where 11KV/33 KV line is crossing road, 11 KV line is crossing LT Lines/
P&T lines etc. Supplying 2 Nos guarding cross arm made of ISMC 75 channel, 2 Nos
Y- guy with 7/3.14 mm wire, 2 Nos 16 mm diameter Eye-bolts, 2 No earthing of
40mm dia GI pipe of 3 meter long, 8 SWG GI wires for earthing connection, 6 SWG
wire for guard wire, 8 SWG wire for cross lacing and 1 meter long extension piece of
ISMC 100 channel, MS clamps, hardware etc all complete including two coat red
oxide painting and two or more coats of aluminium oxide paint of reputed make.
SET 0.04 52 2 2 2 2 2 2 2 2 3 3 3 3 3 3 3 3 3 3 3 3
Sub-Total
233 KV FEEDER BAY at 33/11 KV Grid Substations
using RS Joist supportsNo. 9
i
Supplying materials for extension of 33 KV feeder bay using 4 support (2 Joist
welded together to form a support) of 9 m long, 175 x 85 mm RS Joists Bus Bar
structure, 2x2 support ( 2 Joist welded together to form a support) of 9 m long
175x85 mm RS Joist supports each for Isolator and Metering equipment support
structure including provision of base plate (0.2x0.5x0.5m size), supporting galvanised
steel sections of channel, angle and flat, danger notice plate, 1 No. GI Pipe earthing,
4Nos spike earthing, earth connection with 50X5mm GS Flat & 8 SWG GI wires, PG
Clamps, ACSR WOLF conductors, insulators, clamps, channels, including line isolator
switch of 800 A & 3 Nos Station Class LAs etc as per specifications and tender
drawing complete as required,
SET 1 9 1 1 1 1 1 1 1 1 1
0
ii
36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-1
Amps, 3 Nos outdoor type Current Transformers along with junction box
(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting
structures, permanent maintenance platform, marshalling box etc
required as per technical specifications, scope of works and approved
drawings
SET 1 9 1 1 1 1 1 1 1 1 1
iii 33kV, indoor, Control & Relay panel along with E/F & O/C relays, Mimic
Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation
relays and other components etc as per approved drawings, specifications
and scope of works controlling: a 33 kV feeder VCB with Static Tri-Vector Energy Meter
No 1 91 1 1 1 1 1 1 1 1
Sub Total
311 KV FEEDER BAY at 33/11 KV Grid Substations
using RS Joist Supports No. 6
i
Supplying materials for extension of 11 KV Feeder bay using 4 Nos. (2 Joist welded
together to form a support) 9 m long, 175 x 85 mm RS Joist structure including
provision of base plate (0.2x0.5x0.5m size), danger notice plate, 1 No GI Pipe
earthing, 4 Nos Spike Earthing, earth connection with 50X6 mm GS flat & 8 SWG GI
wire, PG Clamps,ACSR Wolf conductors, insulators, clamps, channels etc as per
specifications complete as required including isolator switch of 400 A & 3 Nos Station
Class LAs etc as per specifications and tender drawing complete as required
set 1 6 1 1 1 1 1 1
0
1
Page 13 of 38
![Page 15: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/15.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
ii 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit breaker
along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos outdoor type Current
Transformer along with junction box (1 no junction box for 3 no of 1-phase CTs),
Jumpers, earthing, supporting structures, permanent maintenance platform,
marshalling box, control cabling between VCB and indoor control panel and required
accessories complete as per technical specifications, approved drawings and scope of
the works.
SET 1 6 1 1 1 1 1 1
0
iii Indoor type control and relay panel: 0
Indoor type control and relay panel for 11kV, 3phase, 630 A VCB (feeder Breaker)
consisting of A-meter, volt-meter, E/F & O/C Relay & accessories complete as per
specifications for transformer breaker protection
No. 1 6 1 1 1 1 1 1
Sub Total
PART VII 33/11 KV Substation Augumentation Works - Fully
outdoor type substation
Addl. 5
MVA2
Addl.10
MVA0
5-10 MVA 0
3.15-10
MVA0
3.15/1.6-
5 MVA 4
Total 6
pss 5
a 10 MVA with off load tap changer No 0 0
b 5 MVA with off load tap changer No 6 6
1 1 1 1 1 1
2 Gantry structures made of Lattice structures of equal angles sections, flat
as per approved drawings. State practices are to be adopted in the design.
All structural steel members and bolts shall be galvanized after fabrication
as per IS:4759 and zinc coating shall not be less than 610gm/sq. meter for
all structural steel members. All L45x45x5 will have 23 mm back mark. All
L50x50x6 will have 28mm back mark. 3.5mm spring washers are to be
used under each nut, structural steel shall conform to IS 2026. All weld
shall be 6mm filled weld unless specified otherwise. All nuts and bolts
shall be of property class 5.6 of IS 1367. Plain washers shall be as per IS
2016 & spring washers shall be IS: 3063.
MT 7 7.00 1 1.5 1.5 1 1 1
3
36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 36kV, 1-Phase, 25kA/3 seconds, 800-400-200/1-1-
1Amps, 3 Nos outdoor type Current Transformers along with junction box
(1 no junction box for 3 no of 1-phase CTs), Jumpers, earthing, supporting
structures, permanent maintenance platform, marshalling box etc
required as per technical specifications, scope of works and approved
drawings
Set 4 4 1 1 1 1
4 33kV, Indoor, Control & Relay panel along with E/F & O/C relays, Mimic
Diagram, Voltmeter, Ammeter, Annunciation Windows with annunciation
relays and other components etc as per approved drawings, specifications
and scope of works controlling: a Power transformer 33 kV VCB with Static Tri-Vector Energy Meter
No. 6 61 1 1 1 1 1
b. Power transformer 33 kV VCB with Static Tri-Vector Energy Meter with differential
relayNo 0 0
5 36kV, 630A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings (without earth switch)
Set 8 8 1 1 1 1 1 1 1 1
6 30 kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set = 3
nos.)
Set 6 61 1 1 1 1 1
7 9kV, 10kA, 1-ph Station Class Lightening Arrester as per technical
specifications, approved drawings and scope of the works. ( 1 Set = 3
nos.)
Set 6 61 1 1 1 1 1
8.a 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-5, 3 Nos
outdoor type Current Transformer along with junction box (1 no junction
box for 3 no of 1-phase CTs), Jumpers, earthing, supporting structures,
permanent maintenance platform, marshalling box, control cabling
between VCB and indoor control panel and required accessories complete
as per technical specifications, approved drawings and scope of the works.
No 6 6 1 1 1 1 1 1
8.b 12 kV, 1250 A, 25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 1200-600-300/1-1-1, 3 Nos
outdoor type Current Transformer along with junction box (1 no junction
box for 3 no of 1-phase CTs), Jumpers, earthing, supporting structures,
permanent maintenance platform, marshalling box, control cabling
between VCB and indoor control panel and required accessories complete
as per technical specifications, approved drawings and scope of the works.
No 0 0
1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil, Buchholtz relay, breather,
OTI & WTI, Marshalling Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips {(with braided conductor on
bushing end), isolating link, isolation with insulators}, Vent explosion
plug, control wiring between sensing equipment and marshalling box,
cable supporting tray on the body of transformer, transformer wheels,
LV/HV bushing etc as required as per technical specifications, approved
drawings and scope of the work.
Page 14 of 38
![Page 16: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/16.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
9 Indoor type control and relay panel:
i Indoor type control and relay panel for 11kV, 3phase, 630 A VCB (feeder Breaker)
consisting of A-meter, volt-meter, E/F & O/C Relay & accessories complete as per
specifications for transformer breaker protection
No. 6 61 1 1 1 1 1
10
30V, 100 AH Pb Acid battery, battery stand made of teak wood duly
painted with anti rusting paint, battery insulators, inter-battery wiring
using 30 sqm, 1.1 kv, copper single core multi strand cable, terminal
connectors, & all other accessories and connectors as per technical
specifications, approved drawings and scope of works.
Set 3 3 1 1 1
11 30V, 40 Amp. Float-cum-Boost Battery Charger with full wave
rectification for 220 V, 1 phase, 50 Hz AC Input Supply with built in DCDB
as per technical specifications, approved drawings and scope of works. set 3 3 1 1 1
12 ACSR Conductor for Bus-Bars & Jumpers/Droppers/Terminations including
hardware fittings, hardware etc
a Wolf conductor (150 Sq. mm) km 0.4 0.4 0.4
13 Earthing & Grounding conductor as per Approved Electrical Layout for each
sub-station with
a 75 x 8 mm MS flat for ground mat MT 1.500 1.5
1.5
b 50 x 6 mm Galvanized GS flat (risers) MT 1.500 1.5
1.5
c 25mm dia MS rod 3 m long for earth mat MT 0.125 0.125
0.125
14 40 mm dia., 3000 mm long GI pipe earth electrode with test link as per
technical specification. (for Power Transformer Neutral, Station
Transformer Neutral and Lightening Arresters direct earthing) Set 40 40
20 20
0
15 33 and 11 KV Insulator - Pin, Post and Disc insulators along with
Hardware & accessories suitable for Wolf conductors as per approved
drawings & specifications.
Set 5 55
16 Power Cables including their termination materials like glands, lugs etc.
a 3.5 Core 70 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.125 0.125
0.125
b 3.5 Core 35 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.125 0.125
0.125
c 2 Core 16 Sq. mm armored, stranded aluminium conductor, PVC insulated and PVC
sheathed cable km 0.5 0.500
0.5
17 Control cables including their termination materials like glands, lugs etc.
a 2 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.1 0.100
0.1
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.5 0.500
0.5
c 10 Core 2.5 sqm armored, stranded copper conductor, PVC insulated and PVC
sheathed cable km 0.5 0.500
0.5
0
18 12 kV, 400A, 25kA for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support Insulators, Operating
Mechanism, Base Channel down Pipe and all required accessories
complete as per technical specifications, scope of works and approved
drawings
Set 12 12 2 2 2 2 2 2
0
19 3 Phase 33 KV HG Fuse complete 200 A capacity as per technical
specificationsset 5 5 1 1 1 1 1
Sub-Total
PART VIII 33 KV Railway Crossing NO. 11
1 33 kV grade XLPE, 3 core, 400 sqmm size power cable as per TS Mtr 230 2,530.00230 230 230 230 230 230 230 230 230 230 230
2 GI Pipe 150 mm dia (Light guage) for laying of cable over DP structure Mtr 12 132.0012 12 12 12 12 12 12 12 12 12 12
3Cast Iron spun pipe of 160mm dia in Pcs of 5.6 M and above long as per TS to be laid for
Under ground 33 kV Cable below Railway track at crossingMtr 120.0 1,320.00 120 120 120 120 120 120 120 120 120 120 120
4Outdoor type heat shrinkable termination kit complete with all accessories including lugs
suitable for 3 Core 400 Sqmm 33 kV grade Al conductor XLPE cable as per TSSet 4 44 4 4 4 4 4 4 4 4 4 4 4
Sub-Total
Part IX 11 KV Railway Crossing NO. 4
1 11 kV grade XLPE, 3 core, 300 sqmm size power cable as per TS Mtr 230 920.00230 230 230 230
2 GI Pipe 150 mm dia (Light guage) for Erection of cable over DP structure Mtr 12 48.00 12 12 12 12
3Cast Iron spun pipe of 160mm dia in Pcs of 5.6 M and above long as per TS to be laid for
Under ground 11 kV Cable below Railway track at crossingMtr 120.0 480.00
120 120 120 120
Page 15 of 38
![Page 17: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/17.jpg)
SUPPLY PERT CHART KATIHAR
Sr. No. DescriptionUnit
Unit Qty. Qty.2014 2015 2016
1 23 4.a 4
LOA date
21.08.14 Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4Outdoor type heat shrinkable termination kit complete with all accessories including lugs
suitable for 3 Core 185 Sqmm 11 kV grade Al conductor XLPE cable as per TSSet 4 16 4 4 4 4
Sub-Total
Part X LT Single Phase Service connection Set 62068
1 Single phase service connection using PVC insulated cable of size 2 Core 2.5 sqmm
aluminium conductor (up to 35m length of house hold from LT line), 10 SWG GI
tension wire, 20 mm GI Pipe medium class to accept service cable at consumer
residence, A meter board (200x350x40mm) for 1ø ( single phase) energy
meter,Service board (200x150x40mm),Single phase (5-30A) fully static class-1
energy meter, 2nos. single piano type ISI marked 250 V/5A switch 1no. 250V/5A
socket of ISI marked, 250V/5A ISI marked holder, 144-288V, upto 9 watts, 710
lumen LED lamp 250V,5A capacity ISI mark lamp holder, Internal wiring using 1.5
sqmm copper multistrands PVC insulated ISI marked cable, 250V/16A double pole
MCB of ISI marked and a cut-out a 10mm dia earth terminal point, internal wiring in
ISI marked 12mm dia PVC rigid pipes including its clamps, fittings and fixtures as
required as per REC drawing and Specifications. Earth point would be connected with
existing earth potential maintained by DISCOM through 10 SWG GI wireetc. as per
detail scope of work.
Set 1 62068 2000 2000 2000 2000 2000 2000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 4000 2068
Sub-Total
Grand Total Ex-works% DISCOUNT, IF ANY: _______
*̂
Note:
Page 16 of 38
![Page 18: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/18.jpg)
ERECTION PERT CHART KATIHAR
CONTRACTOR: ENERGO ENGINEERING PROJECTS LTDLOA Nos.: Supply: 2732/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14 Erection: 2733/ Patna, N-XIII/RE/NIT-164/14/Katihar-1422/2014 dtd. 21.08.14
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
PART I
(a)33/11 KV Grid Substation works:
Partly - outdoor (2x10 MVA) 2
Nos. 33 KV bay and 10 nos. of 11
KV bay
0
A Civil works: Design, supply of all material, T&P,
labour etc for the following civil works complete as
per TS1 Soil Investigation & Contour Survey of Substation
area as per Technical Specification PER S/S 1 0
2 Earth Filling & Site Levelling
i Earth work in PSS site with ordinary soil (vide
classification of soil item - A) obtained from borrow pits
free from logs, stumps, roots, rubbish or any other
ingredients likely to deteriorate or affect the stability of
the (1.0 meter filling considered size 60*40) site surface
including breaking the clods maximum to 60 mm. cube,
placing the earth in layers not exceeding 225 mm in loose
thickness, rough dressing including cost of cutting and
removing shrubs, roots falling in borrow area all complete
as per approved design, as per technical specification
CUM 2400 0
3 Gravel filling in switchyard area excluding road
and footpath.CUM 60 0
4 Construction of Boundary Wall including Barbed
Wire Fencing on MS angle over the Boundary Wall
and one Gate per Substation, including Supply,
Fabrication, Fixing, Painting all complete as per
approved Drawing & Technical Specification in all
33/11 kV new sub-stations
Mtr 200 0
5 Security fencing along with one switchyard gate
per Substation as per Technical specifications in all
33/11 kV new sub-stations - to isolate electrical
yard
Mtr 40 0
6 Design, engineering and construction of Control
Room Building including supply of T&P, Labour,
Cement, Reinforcement Steel, Form Work,
Excavation etc, all complete as per Technical
Specification and Tender Drawing in 33/11 kV new
sub-stations
Sqm 250 0
7 Design, engineering and construction of Cable
Trench of 0.5 Mtr wide, 1.0 Mtr. depth, precast
RCC Trench Cover, Water stops, Brick Work
wherever required including supply of T&P,
Labour, Cement, Reinforcement Steel, Steel
Angles, Flats, Form Work, Excavation etc, all
complete as per Technical Specification and
approved Drawing.
Mtr 120 0
8 Design, engineering and construction of Drainage
System in the Substation premises including
supply of T&P, Labour, Cement, brick, Form Work,
Excavation etc, all complete as per design,
Technical Specification and Tender Drawings in all
33/11 kV new sub-station
Mtr 100 0
9 Design, engineering and construction of approach
road, footpath including supply of T and P, labour,
brick, stone, earth, RCC and excavation,
compaction etc. all complete as per Technical
specifications.a width of approach road 3.00 m Mtr 100.00 0
b width of footpath 1.5 m Mtr 10.00 0.00
10 Stone pitching over sloping including supply of
stone and surface preparation as per drawingSq. Meter 25.00 0.00
PERT NETWORK
NIT - 164/PR/NBPDCL/2014 KATIHAR
Date : 27/10/2014
Page 17 of 38
![Page 19: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/19.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
11 Sinking of tube well and installation of motor
operated submersible pump of suitable capacity
along with water tank (1000 lit) and Medium grade
TATA make GI pipe and asseseries.
Set 1 0
B Substation works
12 Design, Engineering and construction of
transformer foundation, erection, filtration, testing
and commissioning of 33/11 kV, 3 ph, 50 Hz,
ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil,
Buchholtz relay, breather, OTI & WTI, Marshalling
Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips with
braided conductor on bushing end supported with
insulators, OTI & WTI Indicators, Vent explosion
plug, control wiring / cabling, cable supporting
tray on the body, transformer wheels, bushing etc
as required
a 10 MVA set 2 0
13 Design, Engineering, providing and construction of
transformer support/foundation, erection, testing
and commissioning of 100 KVA, 11/0.433 kV, 3 ph,
50 Hz, ONAN,copper wound, CRGO core, outdoor
type Station Transformer on double pole structure
(2x175x85 mm double welded) along with
transformer oil, Distribution Box, cabling,
substation earthing mat, equipment earthing,
substation equipment, 3 Nos. Station Class
Lighting Arresters, one set vertical mounting type
HG Fuse complete, one set horizontal operational
Isolator 12 KV (200A capacity) as required as per
specifications & drawings.
Set 1 0
14 Excavation, erection, cement concrete foundation,
erection, testing and commissioning of Galvanised
Gantry structures made of Lattice structures of
equal angles sections, flat as per approved
drawings. State practices are to be adopted in the
design. All structural steel members and bolts shall
be galvanized after fabrication as per IS:4759 and
zinc coating shall not be less than 610gm/sq.
meter for all structural steel members. All
L45x45x5 will have 23 mm back mark. All
L50x50x6 will have 28mm back mark. 3.5mm
spring washers are to be used under each nut,
structural steel shall conform to IS 2026. All weld
shall be 6mm filled weld unless specified
otherwise. All nuts and bolts shall be of property
class 5.6 of IS 1367. Plain washers shall be as per
IS 2016 & spring washers shall be IS: 3063 as per
approved drawings, technical specifications and
scope of the work.
MT 16.00 0.00
0
15 Design, Engineering and construction of foundation
(as per approved drawings), erection, testing and
commissioning of 36kV, 1250A, 25kA for 3 seconds,
3-ph, Outdoor type Vacuum Circuit breaker along
with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-
200/1-1-1 Amps outdoor type Current Transformer
along with junction box (1 no junction box for 3 no
of 1-phase CTs)], Jumpers, earthing, supporting
structures, maintenance platform, marshalling box,
control cabling between VCB and indoor control
panel and required accessories complete as per
approved drawings, technical specifications and
scope of the work.
Set 4 0
Page 18 of 38
![Page 20: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/20.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
16 Design, Engineering providing and installation of
ISMC 75 channel on top of indoor trench, erection
of panels on ISMC 75 channels, welding, testing
and commissioning of 33kV indoor Control & Relay
panel along with E/F & O/C relays, control and
power supply cabling in trench between field
equipment and panels, Mimic Diagram, Voltmeter,
Ammeter, Annunciation Windows with
annunciation relays and other components etc as
per approved drawings, technical specifications
and scope of the work for controlling:
a 33 kV feeder VCB with Static Tri-Vector Energy Meter etc No 2 0
b 33 kV Power transformer VCB with Static Tri-Vector
Energy Meter, with differential relayNo 2 0
17 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph
double break center rotating type (DBCR), Gang
Operated, isolator along with Support Insulators,
Operating Mechanism, Base Channel down Pipe
and all required accessories complete as per
approved drawings, technical specifications and
scope of the work,
Set 7 0
18 Design & Engineering (as per approved drawings),
Erection, testing and commissioning of 3 phase, 11
kV, 200A, HG Fuses with Support Insulators, , Base
Channel and all required accessories complete as
per approved drawings, technical specifications
and scope of the work,
Set 1 0
19 Design & Engineering (as per approved
drawings), Erection, testing and Commissioning of
36kV, 10kA, 1-ph Station Class Lightening
Arresters with mounting platform on Gantry and
Bus structure , jumpering from bus bar, earthing
connection using 50x6mm GS flat, hardware etc as
required, as per approved drawings, technical
specifications and scope of the work,
Set 4 0
20 Design & Engineering (as per approved drawings),
Erection, testing and Commissioning of 9kV, 10kA,
1-ph Station Class Lightening Arrester with
mounting platform on Gantry and Bus structure ,
jumpering from bus bar, earthing connection using
50x6mm GS flat, hardware, etc as required as per
approved drawings, technical specifications and
scope of the work.
Set 11 0
21 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
Commissioning of 36 kV, 1-Phase, 33kV/110 volt,
Single core outdoor type Potential transformer
along with junction box (1 no junction box for 3 no
of 1-phase PTs) including control and power supply
cabling, earthing connection using 50x6mm GS
flat and required accessories etc., complete as per
as per approved drawings, technical specifications
and scope of the work,
Set 2 0
22 Design, Engineering and construction of foundation
(as per approved drawings), Design, Engineering
and construction of foundation, erection, wiring,
testing and commissioning of 12 kV, 1250 A, 25kA,
3-ph, indoor type Vacuum Circuit breaker along
with 12 kV, 1-Phase, 25kA for 3 seconds, 1200-
600-300/1-1-1 A or 600-300-150/5-5, indoor type
Current Transformer along with control and relay
panel consisting of A-meter, volt-meter, E/F & O/C
Relay & accessories complete cabling between VCB
and indoor control panel and required accessories
complete as per approved drawings, technical
specifications and scope of the work,
a Transformer Protection Breaker Panel No 2 0
b Feeder Protection Breaker Panel No 10 0
c Bus Coupler Panel No 1 0
Page 19 of 38
![Page 21: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/21.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
23 Installation, initial charging, cabling,
interconnection cabling, testing and commissioning
of 30V, 100 AH Pb Acid battery on battery stand
made of teak wood duly painted with anti acid
rusting paint, battery insulators, inter-battery
wiring using 30 sqm copper single core multi
strand cable, terminal connectors, & all other
accessories and connectors as per as per approved
drawings, technical specifications and scope of the
work,
Set 1 0
24 Design, engineering, construction of foundation,
Installation, interconnection cabling, testing and
commissioning of 30V, 40 Amp. Float-Cum-Boost
Battery Charger with full wave rectification for
220 V, 1 phase, 50 Hz AC Input Supply with built
in DCDB as per approved drawings, technical
specifications and scope of the work,
No 1 0
25 Design, engineering, construction of foundation,
Installation, interconnection cabling, testing and
commissioning of 433V, ACDB as per approved
drawings, technical specifications and scope of the
work,
No 1 0
26 Excavation, laying, welding, refilling, earthing &
grounding conductor as per Approved Electrical
Layout for each sub-station and erection of riser up
to various equipment/gantry structures as per
scope of the work, specifications and approved
drawings,
a 75 x 8 mm MS flat for ground mat MT 2.0 0.0
b 50 x 6 mm Galvanized GS flat (risers) MT 2.0 0.0
c 25 mm dia MS Rod 3 m long for earth mat MT 0.5 0.0
27 Excavation, erection, testing and commissioning of
40 mm dia., 3000 mm long GI pipe earth electrode
by providing test link, RCC pit, RCC cover, placed
on GI frame, Charcoal, Salt and other accessories
complete as per approved drawings, technical
specifications and scope of the work for power
transformer neutral, station transformer neutral,
lightening arresters direct earthing.
Set 50.00 0.00
28 Erection, testing and commissioning of Bus
Conductor (wolf Conductor, Al pipe), bus jumpers
to various equipment using 11 KV and 33 KV
insulators, GI Pin, GI Hardware fittings, PG
Clamps, T-connectors etc as required as per
approved drawings, specifications and scope of the
work.
set 1.00 1.00
29 Erection, testing and commissioning through
erection of support, External Lighting work in the
substation yard with 4 No, 12m high steel tubular
lighting masts, 2x250 watts sodium vapour fittings
on each mast, Junction boxes of the fittings, area
lighting power distribution board, 2 nos. 3 Phase
63 Amp power receptacles, substation building
power supply, tube well power supply, etc as
required by laying power cables in
underground/above ground/trenches, construction
of foundations for receptacles, distribution boards
etc as required as per approved drawings,
specifications and scope of work.
Set 1 0
30 Erection, testing and commissioning of Fire
Fighting Equipment comprises of Dry Chemical
Powder Type (6 Kg) for control room; CO2 Type of
4.5Kg Capacity for Control Room and CO2 Type
Trolley Mounted of 22.5 Kg Capacity for Switch
Yard.
SET 1 0
31 Internal electrification work in Substation Control
room as per approved drawings, specifications and
scope of work by installing, erection, testing and
commissioning of fans, exhaust fans, fluorescent
lighting, LED lamps, L&F, power points, wiring
materials, Distribution Boards, Sub-distribution
boards etc. as per approved drawings
Set 1 0
0
Page 20 of 38
![Page 22: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/22.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
32 Power Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required
0
a 3.5 Core 70 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.070 0.000
b 3.5 Core 35 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.050 0.000
c 2 Core 16 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.750 0.000
33 Control Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required a 2 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable Km 0.20 0.00
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable Km 1.00 0.00
c 10 Core 2.5 sqm armored, stranded copper conductor,
PVC insulated and PVC sheathed cable Km 0.60 0.00
34 Laying, erection, termination using indoor & outdoor
termination kit, 11KV XLPE, Power armored cables of
following sizes: a 1Cx300 sqmm km 0.72 0.00
b 3Cx185 sqmm km 1.10 0.00
35 Erection, testing and commissioning of 12 kV, 400A, 25kA
for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support
Insulators, Operating Mechanism, Base Channel down
Pipe and all required accessories complete as per technical
specifications, scope of works and approved drawings
Set 10.00 0.00
Sub Total
PART I
(b)33/11 KV Grid Substation works:
Partly - outdoor (3x5 MVA) 2 Nos.
33 KV bay and 09 nos. of 11 KV bay0
A Civil works: Design, supply of all material, T&P,
labour etc for the following civil works complete as
per TS1 Soil Investigation & Contour Survey of Substation
area as per Technical Specification PER S/S 1 0
2 Earth Filling & Site Levelling
i Earth work in PSS site with ordinary soil (vide
classification of soil item - A) obtained from borrow pits
free from logs, stumps, roots, rubbish or any other
ingredients likely to deteriorate or affect the stability of
the (1.0 meter filling considered size 60*40) site surface
including breaking the clods maximum to 60 mm. cube,
placing the earth in layers not exceeding 225 mm in loose
thickness, rough dressing including cost of cutting and
removing shrubs, roots falling in borrow area all complete
as per approved design, as per technical specification
CUM 2400 0
3 Gravel filling in switchyard area excluding road
and footpath.CUM 60 0
4 Construction of Boundary Wall including Barbed
Wire Fencing on MS angle over the Boundary Wall
and one Gate per Substation, including Supply,
Fabrication, Fixing, Painting all complete as per
approved Drawing & Technical Specification in all
33/11 kV new sub-stations
Mtr 200 0
5 Security fencing along with one switchyard gate
per Substation as per Technical specifications in all
33/11 kV new sub-stations - to isolate electrical
yard
Mtr 40 0
6 Design, engineering and construction of Control
Room Building including supply of T&P, Labour,
Cement, Reinforcement Steel, Form Work,
Excavation etc, all complete as per Technical
Specification and Tender Drawing in 33/11 kV new
sub-stations
Sqm 250 0
0
Page 21 of 38
![Page 23: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/23.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
7 Design, engineering and construction of Cable
Trench of 0.5 Mtr wide, 1.0 Mtr. depth, precast
RCC Trench Cover, Water stops, Brick Work
wherever required including supply of T&P,
Labour, Cement, Reinforcement Steel, Steel
Angles, Flats, Form Work, Excavation etc, all
complete as per Technical Specification and
approved Drawing.
Mtr 120 0
8 Design, engineering and construction of Drainage
System in the Substation premises including
supply of T&P, Labour, Cement, brick, Form Work,
Excavation etc, all complete as per design,
Technical Specification and Tender Drawings in all
33/11 kV new sub-station
Mtr 100 0
9 Design, engineering and construction of approach
road, footpath including supply of T and P, labour,
brick, stone, earth, RCC and excavation,
compaction etc. all complete as per Technical
specifications.a width of approach road 3.00 m Mtr 100.00 0
b width of footpath 1.5 m Mtr 10.00 0
10 Stone pitching over sloping including supply of
stone and surface preparation as per drawingSq. Meter 25.00 0
11 Sinking of tube well and installation of motor
operated submersible pump of suitable capacity
along with water tank (1000 lit) and Medium grade
TATA make GI pipe and asseseries.
Set 1 0
B Substation works
12 Design, Engineering and construction of
transformer foundation, erection, filtration, testing
and commissioning of 33/11 kV, 3 ph, 50 Hz,
ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil,
Buchholtz relay, breather, OTI & WTI, Marshalling
Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips with
braided conductor on bushing end supported with
insulators, OTI & WTI Indicators, Vent explosion
plug, control wiring / cabling, cable supporting
tray on the body, transformer wheels, bushing etc
as required
a 5.0 MVA set 3 0
13 Design, Engineering, providing and construction of
transformer support/foundation, erection, testing
and commissioning of 100 KVA, 11/0.433 kV, 3 ph,
50 Hz, ONAN,copper wound, CRGO core, outdoor
type Station Transformer on double pole structure
(2x175x85 mm double welded) along with
transformer oil, Distribution Box, cabling,
substation earthing mat, equipment earthing,
substation equipment, 3 Nos. Station Class
Lighting Arresters, one set vertical mounting type
HG Fuse complete, one set horizontal operational
AB Switch (200A capacity) as required as per
specifications & drawings.
Set 1 0
0
Page 22 of 38
![Page 24: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/24.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
14 Excavation, erection, cement concrete foundation,
erection, testing and commissioning of Galvanised
Gantry structures made of Lattice structures of
equal angles sections, flat as per approved
drawings. State practices are to be adopted in the
design. All structural steel members and bolts shall
be galvanized after fabrication as per IS:4759 and
zinc coating shall not be less than 610gm/sq.
meter for all structural steel members. All
L45x45x5 will have 23 mm back mark. All
L50x50x6 will have 28mm back mark. 3.5mm
spring washers are to be used under each nut,
structural steel shall conform to IS 2026. All weld
shall be 6mm filled weld unless specified
otherwise. All nuts and bolts shall be of property
class 5.6 of IS 1367. Plain washers shall be as per
IS 2016 & spring washers shall be IS: 3063 as per
approved drawings, technical specifications and
scope of the work.
MT 16.00 0.00
15 Design, Engineering and construction of foundation
(as per approved drawings), erection, testing and
commissioning of 36kV, 1250A, 25kA for 3 seconds,
3-ph, Outdoor type Vacuum Circuit breaker along
with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-
200/1-1-1 Amps outdoor type Current Transformer
along with junction box (1 no junction box for 3 no
of 1-phase CTs)], Jumpers, earthing, supporting
structures, maintenance platform, marshalling box,
control cabling between VCB and indoor control
panel and required accessories complete as per
approved drawings, technical specifications and
scope of the work.
Set 5 0
16 Design, Engineering providing and installation of
ISMC 75 channel on top of indoor trench, erection
of panels on ISMC 75 channels, welding, testing
and commissioning of 33kV indoor Control & Relay
panel along with E/F & O/C relays, control and
power supply cabling in trench between field
equipment and panels, Mimic Diagram, Voltmeter,
Ammeter, Annunciation Windows with
annunciation relays and other components etc as
per approved drawings, technical specifications
and scope of the work for controlling:
a 33 kV feeder VCB with Static Tri-Vector Energy Meter etc No 2 0
b 33 kV Power transformer VCB with Static Tri-Vector
Energy Meter, No 3 0
17 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph
double break center rotating type (DBCR), Gang
Operated, isolator along with Support Insulators,
Operating Mechanism, Base Channel down Pipe
and all required accessories complete as per
approved drawings, technical specifications and
scope of the work,
Set 8 0
18 Design & Engineering (as per approved drawings),
Erection, testing and commissioning of 3 phase, 11
kV, 200A, HG Fuses with Support Insulators, , Base
Channel and all required accessories complete as
per approved drawings, technical specifications
and scope of the work,
Set 1 0
19 Design & Engineering (as per approved
drawings), Erection, testing and Commissioning of
36kV, 10kA, 1-ph Station Class Lightening
Arresters with mounting platform on Gantry and
Bus structure , jumpering from bus bar, earthing
connection using 50x6mm GS flat, hardware etc as
required, as per approved drawings, technical
specifications and scope of the work,
Set 5 0
Page 23 of 38
![Page 25: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/25.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
20 Design & Engineering (as per approved drawings),
Erection, testing and Commissioning of 9kV, 10kA,
1-ph Station Class Lightening Arrester with
mounting platform on Gantry and Bus structure ,
jumpering from bus bar, earthing connection using
50x6mm GS flat, hardware, etc as required as per
approved drawings, technical specifications and
scope of the work.
Set 10 0
21 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
Commissioning of 36 kV, 1-Phase, 33kV/110 volt,
Single core outdoor type Potential transformer
along with junction box (1 no junction box for 3 no
of 1-phase PTs) including control and power supply
cabling, earthing connection using 50x6mm GS
flat and required accessories etc., complete as per
as per approved drawings, technical specifications
and scope of the work,
Set 2 0
22 Design, Engineering and construction of foundation
(as per approved drawings), Design, Engineering
and construction of foundation, erection, wiring,
testing and commissioning of 12 kV, 1250 A, 25kA,
3-ph, indoor type Vacuum Circuit breaker along
with 12 kV, 1-Phase, 25kA for 3 seconds, 1200-
600-300/1-1-1 A or 600-300-150/5-5, indoor type
Current Transformer along with control and relay
panel consisting of A-meter, volt-meter, E/F & O/C
Relay & accessories complete cabling between VCB
and indoor control panel and required accessories
complete as per approved drawings, technical
specifications and scope of the work,
a Transformer Protection Breaker Panel No 3 0
b Feeder Protection Breaker Panel No 9 0
c Bus Coupler Panel No 2 0
23 Installation, initial charging, cabling,
interconnection cabling, testing and commissioning
of 30V, 100 AH Pb Acid battery on battery stand
made of teak wood duly painted with anti acid
rusting paint, battery insulators, inter-battery
wiring using 30 sqm copper single core multi
strand cable, terminal connectors, & all other
accessories and connectors as per as per approved
drawings, technical specifications and scope of the
work,
Set 1 0
24 Design, engineering, construction of foundation,
Installation, interconnection cabling, testing and
commissioning of 30V, 40 Amp. Float-Cum-Boost
Battery Charger with full wave rectification for
220 V, 1 phase, 50 Hz AC Input Supply with built
in DCDB as per approved drawings, technical
specifications and scope of the work,
No 1 0
25 Design, engineering, construction of foundation,
Installation, interconnection cabling, testing and
commissioning of 433V, ACDB as per approved
drawings, technical specifications and scope of the
work,
No 1 0
26 Excavation, laying, welding, refilling, earthing &
grounding conductor as per Approved Electrical
Layout for each sub-station and erection of riser up
to various equipment/gantry structures as per
scope of the work, specifications and approved
drawings,
a 75 x 8 mm MS flat for ground mat MT 2.5 0
b 50 x 6 mm Galvanized GS flat (risers) MT 2.5 0
c 25 mm dia MS Rod 3 m long for earth mat MT 0.5 0
27 Excavation, erection, testing and commissioning of
40 mm dia., 3000 mm long GI pipe earth electrode
by providing test link, RCC pit, RCC cover, placed
on GI frame, Charcoal, Salt and other accessories
complete as per approved drawings, technical
specifications and scope of the work for power
transformer neutral, station transformer neutral,
lightening arresters direct earthing.
Set 50.00 0
Page 24 of 38
![Page 26: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/26.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
28 Erection, testing and commissioning of Bus
Conductor (wolf Conductor, Al pipe), bus jumpers
to various equipment using 11 KV and 33 KV
insulators, GI Pin, GI Hardware fittings, PG
Clamps, T-connectors etc as required as per
approved drawings, specifications and scope of the
work.
set 1.00 0
29 Erection, testing and commissioning through
erection of support, External Lighting work in the
substation yard with 4 No, 12m high steel tubular
lighting masts, 2x250 watts sodium vapour fittings
on each mast, Junction boxes of the fittings, area
lighting power distribution board, 2 nos. 3 Phase
63 Amp power receptacles, substation building
power supply, tube well power supply, etc as
required by laying power cables in
underground/above ground/trenches, construction
of foundations for receptacles, distribution boards
etc as required as per approved drawings,
specifications and scope of work.
Set 1 0
30 Erection, testing and commissioning of Fire
Fighting Equipment comprises of Dry Chemical
Powder Type (6 Kg) for control room; CO2 Type of
4.5Kg Capacity for Control Room and CO2 Type
Trolley Mounted of 22.5 Kg Capacity for Switch
Yard.
SET 1 0
31 Internal electrification work in Substation Control
room as per approved drawings, specifications and
scope of work by installing, erection, testing and
commissioning of fans, exhaust fans, fluorescent
lighting, LED lamps, L&F, power points, wiring
materials, Distribution Boards, Sub-distribution
boards etc. as per approved drawings
Set 1 0
32 Power Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required a 3.5 Core 70 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.070 0
b 3.5 Core 35 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.050 0
c 2 Core 16 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.750 0
33 Control Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required a 2 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable Km 0.20 0
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable Km 1.00 0
c 10 Core 2.5 sqm armored, stranded copper conductor,
PVC insulated and PVC sheathed cable Km 0.60 0
34 Laying, erection, termination using indoor & outdoor
termination kit, 11KV XLPE, Power armored cables of
following sizes: a 1Cx300 sqmm km 0.72 0
b 3Cx185 sqmm km 1.00 0
35 Erection, testing and commissioning of 12 kV, 400A, 25kA
for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support
Insulators, Operating Mechanism, Base Channel down
Pipe and all required accessories complete as per technical
specifications, scope of works and approved drawings
Set 9.00 0
Sub Total
PART I
(c)33/11 KV Grid Substation works:
Partly - outdoor (2x5 MVA) 2 Nos.
33 KV bay and 06 nos. of 11 KV bay9
A Civil works: Design, supply of all material, T&P,
labour etc for the following civil works complete as
per TS1 Soil Investigation & Contour Survey of Substation
area as per Technical Specification PER S/S 1 9 1 1 1 1 1 1 1 1 1
Page 25 of 38
![Page 27: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/27.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
0
2 Earth Filling & Site Levelling
0
i Earth work in PSS site with ordinary soil (vide
classification of soil item - A) obtained from borrow pits
free from logs, stumps, roots, rubbish or any other
ingredients likely to deteriorate or affect the stability of
the (1.0 meter filling considered size 60*40) site surface
including breaking the clods maximum to 60 mm. cube,
placing the earth in layers not exceeding 225 mm in loose
thickness, rough dressing including cost of cutting and
removing shrubs, roots falling in borrow area all complete
as per approved design, as per technical specification
CUM 2400 21600 500 500 500 1000 1000 1000 1000 1000 1000 1000 1000 1500 1500 1500 1500 1500 1500 1500 1600
0
3 Gravel filling in switchyard area excluding road
and footpath.CUM 60 540 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30 30
0
4 Construction of Boundary Wall including Barbed
Wire Fencing on MS angle over the Boundary Wall
and one Gate per Substation, including Supply,
Fabrication, Fixing, Painting all complete as per
approved Drawing & Technical Specification in all
33/11 kV new sub-stations
Mtr 200 1800 50 50 100 100 100 100 100 100 100 100 100 100 100 100 125 125 125 125
0
5 Security fencing along with one switchyard gate
per Substation as per Technical specifications in all
33/11 kV new sub-stations - to isolate electrical
yard
Mtr 40 360 10 10 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25
0
6 Design, engineering and construction of Control
Room Building including supply of T&P, Labour,
Cement, Reinforcement Steel, Form Work,
Excavation etc, all complete as per Technical
Specification and Tender Drawing in 33/11 kV new
sub-stations
Sqm 250 2250 50 100 100 125 125 125 125 125 125 125 125 125 125 150 150 150 150 150
0
7 Design, engineering and construction of Cable
Trench of 0.5 Mtr wide, 1.0 Mtr. depth, precast
RCC Trench Cover, Water stops, Brick Work
wherever required including supply of T&P,
Labour, Cement, Reinforcement Steel, Steel
Angles, Flats, Form Work, Excavation etc, all
complete as per Technical Specification and
approved Drawing.
Mtr 120 1080 30 30 60 60 60 60 60 60 60 60 60 60 60 60 75 75 75 75
0
8 Design, engineering and construction of Drainage
System in the Substation premises including
supply of T&P, Labour, Cement, brick, Form Work,
Excavation etc, all complete as per design,
Technical Specification and Tender Drawings in all
33/11 kV new sub-station
Mtr 100 900 25 25 50 50 50 50 50 50 50 50 50 50 50 50 50 50 75 75
0
9 Design, engineering and construction of approach
road, footpath including supply of T and P, labour,
brick, stone, earth, RCC and excavation,
compaction etc. all complete as per Technical
specifications.
0
a width of approach road 3.00 m Mtr 100.00 900 50 50 50 50 50 50 50 50 50 50 50 50 50 50 50 75 75
b width of footpath 1.5 m Mtr 10.00 90 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 7.5 7.5
0
10 Stone pitching over sloping including supply of
stone and surface preparation as per drawingSq. Meter 25.00 225
12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 12.5 15 15 15 15 20 20
0
11 Sinking of tube well and installation of motor
operated submersible pump of suitable capacity
along with water tank (1000 lit) and Medium grade
TATA make GI pipe and asseseries.
Set 1 9 1 1 1 1 1 1 1 1 1
0
B Substation works 0
0
Page 26 of 38
![Page 28: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/28.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
12 Design, Engineering and construction of
transformer foundation, erection, filtration, testing
and commissioning of 33/11 kV, 3 ph, 50 Hz,
ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil,
Buchholtz relay, breather, OTI & WTI, Marshalling
Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips with
braided conductor on bushing end supported with
insulators, OTI & WTI Indicators, Vent explosion
plug, control wiring / cabling, cable supporting
tray on the body, transformer wheels, bushing etc
as required
0
a 5.0 MVA set 2 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2
0
13 Design, Engineering, providing and construction of
transformer support/foundation, erection, testing
and commissioning of 100 KVA, 11/0.433 kV, 3 ph,
50 Hz, ONAN,copper wound, CRGO core, outdoor
type Station Transformer on double pole structure
(2x175x85 mm double welded) along with
transformer oil, Distribution Box, cabling,
substation earthing mat, equipment earthing,
substation equipment, 3 Nos. Station Class
Lighting Arresters, one set vertical mounting type
HG Fuse complete, one set horizontal operational
AB Switch (200A capacity) as required as per
specifications & drawings.
Set 1 9 1 1 1 1 1 1 1 1 1
0
14 Excavation, erection, cement concrete foundation,
erection, testing and commissioning of Galvanised
Gantry structures made of Lattice structures of
equal angles sections, flat as per approved
drawings. State practices are to be adopted in the
design. All structural steel members and bolts shall
be galvanized after fabrication as per IS:4759 and
zinc coating shall not be less than 610gm/sq.
meter for all structural steel members. All
L45x45x5 will have 23 mm back mark. All
L50x50x6 will have 28mm back mark. 3.5mm
spring washers are to be used under each nut,
structural steel shall conform to IS 2026. All weld
shall be 6mm filled weld unless specified
otherwise. All nuts and bolts shall be of property
class 5.6 of IS 1367. Plain washers shall be as per
IS 2016 & spring washers shall be IS: 3063 as per
approved drawings, technical specifications and
scope of the work.
MT 14.00 126 2 5 7 7 7 7 7 7 7 7 7 7 14 14 14 7
0
15 Design, Engineering and construction of foundation
(as per approved drawings), erection, testing and
commissioning of 36kV, 1250A, 25kA for 3 seconds,
3-ph, Outdoor type Vacuum Circuit breaker along
with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-
200/1-1-1 Amps outdoor type Current Transformer
along with junction box (1 no junction box for 3 no
of 1-phase CTs)], Jumpers, earthing, supporting
structures, maintenance platform, marshalling box,
control cabling between VCB and indoor control
panel and required accessories complete as per
approved drawings, technical specifications and
scope of the work.
Set 4 36 2 2 2 2 2 2 2 2 2 3 3 3 3 3 3
0
16 Design, Engineering providing and installation of
ISMC 75 channel on top of indoor trench, erection
of panels on ISMC 75 channels, welding, testing
and commissioning of 33kV indoor Control & Relay
panel along with E/F & O/C relays, control and
power supply cabling in trench between field
equipment and panels, Mimic Diagram, Voltmeter,
Ammeter, Annunciation Windows with
annunciation relays and other components etc as
per approved drawings, technical specifications
and scope of the work for controlling:
0
a 33 kV feeder VCB with Static Tri-Vector Energy Meter etc No 2 18 2 2 2 2 2 2 2 2 2
b 33 kV Power transformer VCB with Static Tri-Vector
Energy Meter, No 2 18 2 2 2 2 2 2 2 2 2
0
Page 27 of 38
![Page 29: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/29.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
17 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph
double break center rotating type (DBCR), Gang
Operated, isolator along with Support Insulators,
Operating Mechanism, Base Channel down Pipe
and all required accessories complete as per
approved drawings, technical specifications and
scope of the work,
Set 7 63 4 4 4 4 4 4 4 5 5 5 5 5 5 5
0
18 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
commissioning of 3 phase, 33 kV, 100A, HG Fuses
with Support Insulators, , Base Channel and all
required accessories complete as per approved
drawings, technical specifications and scope of the
work,
Set 1 9 1 1 1 1 1 1 1 1 1
0
19 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
Commissioning of 36kV, 10kA, 1-ph Station Class
Lightening Arresters with mounting platform,
jumpering from bus bar, earthing connection using
50x6mm GS flat, hardware etc as required, as per
approved drawings, technical specifications and
scope of the work,
Set 4 36 2 2 2 2 2 2 2 2 2 2 4 4 4 4
0
20 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
Commissioning of 9kV, 10kA, 1-ph Station Class
Lightening Arrester with mounting platform,
jumpering from bus bar, earthing connection using
50x6mm GS flat, hardware, etc as required as per
approved drawings, technical specifications and
scope of the work.
Set 7 63 3 4 3 4 3 4 3 4 3 4 7 7 7 7
0
21 Design & Engineering (as per approved drawings),
Erection, testing and Commissioning of 9kV, 10kA,
1-ph Station Class Lightening Arrester with
mounting platform on Gantry and Bus structure ,
jumpering from bus bar, earthing connection using
50x6mm GS flat, hardware, etc as required as per
approved drawings, technical specifications and
scope of the work.
Set 2 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2
0
22 Design, Engineering and construction of foundation
(as per approved drawings), Design, Engineering
and construction of foundation, erection, wiring,
testing and commissioning of 12 kV, 1250 A, 25kA,
3-ph, indoor type Vacuum Circuit breaker along
with 12 kV, 1-Phase, 25kA for 3 seconds, 1200-
600-300/1-1-1 A or 600-300-150/5-5, indoor type
Current Transformer along with control and relay
panel consisting of A-meter, volt-meter, E/F & O/C
Relay & accessories complete cabling between VCB
and indoor control panel and required accessories
complete as per approved drawings, technical
specifications and scope of the work,
0
a Transformer Protection Breaker Panel No 2 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2
b Feeder Protection Breaker Panel No 6 54 3 3 3 3 3 3 3 3 3 3 6 6 6 6
c Bus Coupler Panel No 1 9 1 1 1 1 1 1 1 1 1
0
23 Installation, initial charging, cabling,
interconnection cabling, testing and commissioning
of 30V, 100 AH Pb Acid battery on battery stand
made of teak wood duly painted with anti acid
rusting paint, battery insulators, inter-battery
wiring using 30 sqm copper single core multi
strand cable, terminal connectors, & all other
accessories and connectors as per as per approved
drawings, technical specifications and scope of the
work,
Set 1 9 1 1 1 1 1 1 1 1 1
0
Page 28 of 38
![Page 30: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/30.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
24 Design, engineering, construction of foundation,
Installation, interconnection cabling, testing and
commissioning of 30V, 40 Amp. Float-Cum-Boost
Battery Charger with full wave rectification for
220 V, 1 phase, 50 Hz AC Input Supply with built
in DCDB as per approved drawings, technical
specifications and scope of the work,
No 1 9 1 1 1 1 1 1 1 1 1
0
25 Design, engineering, construction of foundation,
Installation, interconnection cabling, testing and
commissioning of 433V, ACDB as per approved
drawings, technical specifications and scope of the
work,
No 1 9 1 1 1 1 1 1 1 1 1
0
26 Excavation, laying, welding, refilling, earthing &
grounding conductor as per Approved Electrical
Layout for each sub-station and erection of riser up
to various equipment/gantry structures as per
scope of the work, specifications and approved
drawings,
0
a 75 x 8 mm MS flat for ground mat MT 2.0 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2
b 50 x 6 mm Galvanized GS flat (risers) MT 2.0 18 1 1 1 1 1 1 1 1 1 1 2 2 2 2
c 25 mm dia MS Rod 3 m long for earth mat MT 0.5 4.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
0
27 Excavation, erection, testing and commissioning of
40 mm dia., 3000 mm long GI pipe earth electrode
by providing test link, RCC pit, RCC cover, placed
on GI frame, Charcoal, Salt and other accessories
complete as per approved drawings, technical
specifications and scope of the work for power
transformer neutral, station transformer neutral,
lightening arresters direct earthing.
Set 40.00 360 20 20 20 20 20 20 20 20 40 40 40 40 40
0
28 Erection, testing and commissioning of Bus
Conductor (wolf Conductor, Al pipe), bus jumpers
to various equipment using 11 KV and 33 KV
insulators, GI Pin, GI Hardware fittings, PG
Clamps, T-connectors etc as required as per
approved drawings, specifications and scope of the
work.
set 1.00 1 1
0
29 Erection, testing and commissioning through
erection of support, External Lighting work in the
substation yard with 4 No, 12m high steel tubular
lighting masts, 2x250 watts sodium vapour fittings
on each mast, Junction boxes of the fittings, area
lighting power distribution board, 2 nos. 3 Phase
63 Amp power receptacles, substation building
power supply, tube well power supply, etc as
required by laying power cables in
underground/above ground/trenches, construction
of foundations for receptacles, distribution boards
etc as required as per approved drawings,
specifications and scope of work.
Set 1 9 1 1 1 1 1 1 1 1 1
0
30 Erection, testing and commissioning of Fire
Fighting Equipment comprises of Dry Chemical
Powder Type (6 Kg) for control room; CO2 Type of
4.5Kg Capacity for Control Room and CO2 Type
Trolley Mounted of 22.5 Kg Capacity for Switch
Yard.
SET 1 9 1 1 1 1 1 1 1 1 1
0
31 Internal electrification work in Substation Control
room as per approved drawings, specifications and
scope of work by installing, erection, testing and
commissioning of fans, exhaust fans, fluorescent
lighting, LED lamps, L&F, power points, wiring
materials, Distribution Boards, Sub-distribution
boards etc. as per approved drawings
Set 1 9 1 1 1 1 1 1 1 1 1
0
32 Power Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required
0
a 3.5 Core 70 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.070 0.63 0.07 0.07 0.07 0.07 0.07 0.07 0.07 0.07 0.07
b 3.5 Core 35 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.050 0.45 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
c 2 Core 16 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable Km 0.750 6.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75 0.75
0
Page 29 of 38
![Page 31: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/31.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
33 Control Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required
0
a 2 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable Km 0.20 1.80 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2 0.2
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable Km 0.70 6.30 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
c 10 Core 2.5 sqm armored, stranded copper conductor,
PVC insulated and PVC sheathed cable Km 0.50 4.50 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5 0.5
0
34 Laying, erection, termination using indoor & outdoor
termination kit, 11KV XLPE, Power armored cables of
following sizes:
0
a 1Cx300 sqmm km 0.54 4.86 0.54 0.54 0.54 0.54 0.54 0.54 0.54 0.54 0.54
b 3Cx185 sqmm km 0.70 6.3 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7 0.7
35 Erection, testing and commissioning of 12 kV, 400A, 25kA
for 3 seconds, 3-ph double break center rotating type
(DBCR), Gang Operated, isolator along with Support
Insulators, Operating Mechanism, Base Channel down
Pipe and all required accessories complete as per technical
specifications, scope of works and approved drawings
Set 6 54 3 3 3 3 3 3 3 3 6 6 6 6 6
Sub Total
PART II Erection, testing and Commissioning of New 33 KV
lines: Dog 195.00
1 Excavation of pit, cement concrete foundation,
erection of following Support for 33 KV overhead
line by providing and installing danger plate, anti-
climbing devices (barbed wire) and pole
numbering as per scope of work, approved
drawings and specifications: a 9 m/400 Kgs PSC Poles with RCC Base plate including
60% refilling by brick ballast/ stone bolder and 40 %
excavated soil as required
No 16 3120 100 100 200 200 200 200 200 200 200 200 200 200 200 200 200 200 120
b 13 m long RS Joist 152x152 mm with RCC Base plate with
cement concrete foundation ( 1:2:4) as required as per
scope of work, approved drawings and technical
specifications.
No 1 195 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15
2 Erection of galvanised pre-fabricated steel
materials- Channels, angle, flats for over head
structures
MT 0.67 130.65 5 5.65 8 8 8 8 8 8 8 8 8 8 8 8 8 8 8
3 Erection, testing and commissioning of ACSR DOG
Conductor of size 6/4.72 mm + 7/1.57 mm (100
mm² Al. Area) including jointing sleeves and
helicon formed fittings etc as required
ckm 1 195.00 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15
4 Erection of Galvanised Steel Nuts, bolts and
washers MT 0.024 4.68 0.12 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.24 0.36 0.36 0.36 0.36 0.36 0.36
5 Erection, testing and commissioning of 33 KV Disc
insulator 70 KN along with HW fittings (porcelain
disc insulator as the case may be with 70KN
fittings)
Set 6 1170 30 60 60 60 60 60 60 60 60 60 60 90 90 90 90 90 90
6 Erection, Testing and Commissioning of 33 KV Pin
Insulators with GI PIN (porcelain pin insulator as
the case may be with GI Pin)
Set 48 9360 240 480 480 480 480 480 480 480 480 480 480 720 720 720 720 720 720
7 Excavation, Erecting, Testing and Commissioning
of Pipe type Untreated Earthing as per approved
drawings, scope of work and technical
specifications as required.
Set 1 195 5 10 10 10 10 10 10 10 10 10 10 15 15 15 15 15 15
8 Excavation, Erecting, Testing and Commissioning
of Coil type Untreated Earthing as per approved
drawings, scope of work and technical
specifications as required.
Set 15 2925 75 75 175 150 150 150 200 200 200 200 200 200 200 200 200 200 150
9 Excavation and erection of galvanised Stay Set
with 50x8 mm stay clamp, HT stay guy insulator,
nut bolts, 2 Nos turn buckles, 1.8 m long, 20 mm
diameter solid GS stay rod & 7/4.00 mm dia GI
stranded wire by providing 0.3 cum cement
concrete foundations as per scope of work,
specifications and approved drawings.
Set 6 1170 30 60 60 60 60 60 60 60 60 60 60 90 90 90 90 90 90
10 Survey, route alignment & pole spotting,
preparation of survey report and uploading in the
web portal after approval of Engineer
Km 1 195 5 10 10 10 10 10 10 10 15 15 15 15 15 15 15 15
Page 30 of 38
![Page 32: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/32.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
11 Erection, Testing and Commissioning of 36kV AB
Switch along with Support Insulators, Base
Channel down Pipe, Arcing Horns etc. complete as
per technical specifications, scope of works and
approved drawings
Set 0.1 19.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 2 2
12 Erection, testing and commissioning of 8 SWG wire
for earthing, MT 0.003 0.585 0.015 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.03 0.045 0.045 0.045 0.045 0.045 0.045
Sub-Total (II)
Rabbit 405
Weasel 695.25
Total 1100.31 Excavation and erection of support for 11 KV
overhead line by providing and installing danger
plate, anti-climbing devices (barbed wire) and pole
numbering as per scope of work, approved
drawings and specifications: a 8 m/200 Kgs PSC Poles with RCC Base plate including
60% refilling by brick ballast/ stone bolder and 40 %
excavated soil as required
No 16.75 18429 250 500 500 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1250 1250 1250 1250 1179
b 13 m long RS Joist 152x152 mm with RCC Base plate with
cement concrete foundation ( 1:2:4) as required as per
scope of work, approved drawings and technical
specifications.
No 0.25 275 10 10 10 15 15 15 15 15 15 15 15 15 15 15 20 20 20 20
2 Erection of galvanised pre-fabricated steel
materials- channel, angle, flats for over head
structures
MT 0.34 374.09 10 20 20 20 20 20 20 20 20 20 20 20 20 25 25 25 25 24.09
3 Erection of galvanised Steel Nuts, Bolts with
WashersMT 0.0155 17.053875 0.5 0.5 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
4 Erection, Testing and Commissioning of ACSR
Conductors with Jointing sleeves, Helically formed
fittings etc as required a 7/3.35 mm (50 mm² Al. Area) (Rabbit) CKM 1 405.00 5 10 20 20 20 20 20 20 25 25 25 25 25 25 25 25 25 25 20
b 7/2.59 mm (30 mm² Al. Area) (Weasel) CKM 1 695.25 10 20 30 30 30 30 30 30 30 30 50 50 50 50 50 50 50 50 25.25
5 Erection, Testing and Commissioning of Porcelain
Insulators with mounting hardware, fittings
11 KV 45 KN Disc Insulator with hardware fittings Set 6 6601.5 90 180 300 300 300 300 300 300 330 330 450 450 450 450 450 450 450 450 272
11 KV Pin insulators with GI Pin Set 48.00 52812 720 1440 2400 2400 2400 2400 2400 2400 2640 2640 3600 3600 3600 3600 3600 3600 3600 3600 2172
6 Excavation and erection of galvanised Stay set
with 50x8 mm Stay clamp, HT stay guy insulator,
nut bolts, 2 Nos turn buckles, 1.8 m long, 16 mm
diameter solid GS stay rod & 7/3.15 mm dia GI
stranded wire etc as required by providing 0.2 cum
cement concreting as per scope of the work,
technical specifications and approved drawings.
Set 6.00 6601.5 90 180 300 300 300 300 300 300 330 330 450 450 450 450 450 450 450 450 272
7 Erection, Testing and Commissioning of 12kV AB
Switch along with Support Insulators, Base
Channel down Pipe, Arcing Horns etc. complete as
per technical specifications, scope of works and
approved drawings
Set 0.1 110.025 2 3 5 5 5 5 5 6 6 6 7 7 7 7 7 7 7 7 6
8 Excavation, Erecting, Testing and Commissioning
of Pipe type Untreated Earthing as per approved
drawings, scope of work and technical
specifications as required.
Set 1 1100.25 15 30 50 50 50 50 50 50 55 55 75 75 75 75 75 75 75 75 45
9 Excavation, Erecting, Testing and Commissioning
of Coil type Untreated Earthing as per approved
drawings, scope of work and technical
specifications as required.
Set 15.00 16503.75 200 450 450 900 900 900 900 900 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 904
10 Survey, route alignment & pole spotting,
preparation of survey report and uploading in the
web portal after approval of Engineer
Km 1 1100.25 15 35 50 50 50 50 50 50 50 50 50 100 100 100 100 100 100
11 Erection, testing and commissioning of 8 SWG GI
wire for earthing, MT 0.003 3.30075 0.045 0.09 0.15 0.15 0.15 0.15 0.15 0.15 0.165 0.165 0.225 0.225 0.225 0.225 0.225 0.225 0.225 0.225 0.135
Sub-Total (III)
63 KVA 1402
100 KVA 336
Total 1738
Part IVErection, Testing and Commissioning of new
Distribution Transformer Substations
Part III Erection, Testing and Commissioning of 11 KV Lines
Page 31 of 38
![Page 33: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/33.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 Erection, Testing and Commissioning of
Distribution Transformer with all accessories as
per TSa Three Phase 63 KVA No 1 1402 20 50 50 80 80 80 80 80 80 100 100 100 100 100 100 80 80 42
b Three Phase 100 KVA No 1 336 5 10 10 20 20 20 20 20 20 25 25 25 25 20 20 20 20 11
2 Erection, testing and Commissioning of 3-pole,
Distribution Class 11KV Lightening Arrester for
Distribution Transformer Substation by providing
and erecting Hot Deep galvanised stranded wire
7/3.15 mm as per scope of work, approved
drawings and technical specifications.
Set 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53
3 Excavation and erection of 11 KV Line Support by
providing and installing danger plate, anti-climbing
devices (barbed wire) and pole numbering as per
scope of work, approved drawings and
specifications:a 8 m/200 Kgs PSC Poles with RCC Base plate including
60% refilling by brick ballast/ stone bolder and 40 %
excavated soil as required
No 2 3476 50 120 120 200 200 200 200 200 200 250 250 250 250 240 240 200 200 106
4 Erection of Galvanised pre-fabricated steel
materials- channel, angle, flats for over head
structures
MT 0.255 443.19 6.375 15.3 15.3 25.5 25.5 25.5 25.5 25.5 25.5 31.875 31.875 31.875 31.875 30.6 30.6 25.5 25.5 13.515
5 Erection of Galvanised Steel Nuts, Bolts with
WashersMT 0.016 27.808 0.4 0.96 0.96 1.6 1.6 1.6 1.6 1.6 1.6 2 2 2 2 1.92 1.92 1.6 1.6 0.848
6 Erection, Testing and Commissioning of Insulators
a 11 KV, Disc Insulator ( porcelain) with hardware fittingsSet 3 5214 75 180 180 300 300 300 300 300 300 375 375 375 375 360 360 300 300 159
7 Erection, testing and Commissioning of 12 KV, 200
A, 3-pole AB Switch for Distribution Transformer
Substation.
Sets 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53
8 Erection, testing and commissioning of 3 pole,
11KV 200 AMP HG fuse set for 3-ph DTs Sets 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53
9 Erection, testing and Commissioning of LT
Distribution box with metering and LT control
mechanism as per scope of the work, by providing
50x8mm clamps, hardware, lugs, double
compression brass glands, 2.5sqmm copper multi
strands control cabling, earthing using 8 SWG GS
wire, technical specifications and approved
drawings suitable for following transformer:
a Three Phase 63 KVA No 1 1402 20 50 50 80 80 80 80 80 80 100 100 100 100 100 100 80 80 42
b Three Phase 100 KVA No 1 336 5 10 10 20 20 20 20 20 20 25 25 25 25 20 20 20 20 11
10 Excavation, erection, testing and commissioning of
set of 3 Nos pipe earthing using 40mm dia GI pipe
3000 mm long, as per IS 1161 and as per REC
construction drawings, making earth grid using
50x6mm GS Flat and riser and connecting risers to
various equipment using GS Stranded wires/GS 8
SWG wire as per scope of work, approved drawings
and technical specifications. Providing and erecting
charcoal, salt, lugs, hardware, etc as per approved
drawings, technical specifications and drawings.
Set 1 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53
11 Erection, testing and commissioning of ACSR
Rabbit Conductor for jumpering including PG
Clamps, bi-metallic connectors, hardware etc
Km 0.009 15.642 0.225 0.54 0.54 0.9 0.9 0.9 0.9 0.9 0.9 1.125 1.125 1.125 1.125 1.08 1.08 0.9 0.9 0.477
12 Erection, testing and commissioning of PVC
insulated, PVC sheathed, Aluminium Conductor,
Stranded, unarmoured cable for connection of
transformer LV bushing to Distribution Box as per
Scope of work, technical specification and
approved drawings:
a 1CX50 sqm aluminium conductor cable for Three Phase 63
KVAkm 0.015 21.030 0.3 0.75 0.75 1.2 1.2 1.2 1.2 1.2 1.2 1.5 1.5 1.5 1.5 1.5 1.5 1.2 1.2 0.63
b 1Cx95 sqm aluminium conductor cable for Three Phase
100KVAkm 0.015 5.040
0.075 0.15 0.15 0.3 0.3 0.3 0.3 0.3 0.3 0.375 0.375 0.375 0.375 0.3 0.3 0.3 0.3 0.165
Sub-Total (IV)
1-Phase 556.2
Part V LT Line Page 32 of 38
![Page 34: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/34.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
3-Phase 834.3
Total 1390.5
1 Excavation and erection of Support for LT overhead
Line by providing and installing danger plate, anti-
climbing devices (barbed wire) and pole
numbering as per scope of work, approved 8 m/200 Kgs PSC Poles with RCC Base plate including
60% refilling by brick ballast/ stone bolder and 40 %
excavated soil as required
No 21 29200.5 250 500 500 1000 1000 1500 1500 1500 1500 1500 2000 2000 2000 2000 2000 2000 2000 2000 1500 951
2 Excavation and erection of galvanised Stay Set
with 50x8mm stay clamp, stay guy insulator, nut
bolts, 2 Nos turn buckle's, 1.8 m long, 16 mm
diameter solid GS Stay rod & 7/3.15 mm Dia GI
stranded wire etc as required by providing 0.2 cum
cement concrete as per approved drawings,
technical specification and scope of work.
No 7 9733.5 200 200 350 350 400 500 500 500 500 650 650 650 650 700 700 700 700 500 333
3 Earthing of LT support by providing earthing at
every 6th pole through:
a Installation, testing and commissioning of untreated Coil
Earthing as per scope of work, technical specifications and
approved drawings
Set 5 6952.5 60 125 125 200 250 325 325 325 325 325 500 500 500 500 500 500 500 500 325 243
4 Erection, testing and Commissioning of LT Line on
AB Cables: (average span 40 m) including erection
accessories like Insulation Piercing Connectors,
Anchoring Assembly, Suspension Assembly, Service
Clamp, Transformer Connection, Junction Sleeves
and Service Main Distribution boxes etc as required
as per scope of work, approved drawings and
technical specifications.
a 1-Phase ABC [1X16{Phase}+1x16 {Neutral}+{1x25
Messenger cum earth wire}] line as per TS km 1.03 572.886 10 10 25 25 25 25 35 35 35 35 35 35 35 35 35 35 35 35 32.8
b 3-Phase ABC [3X50{Phase}+{1x35 Messenger cum earth
wire}] line as per TS km 1.03 859.33 20 20 40 40 50 50 50 50 50 50 50 50 50 50 50 50 50 50 39.33
5 Survey, route alignment & pole spotting,
preparation of survey report and uploading in the
web portal after approval of Engineer
Km 1 1390.50 15 50 50 50 50 65 65 65 65 65 100 100 100 100 100 100 125 125.5
Sub-Total (V)
Part-VI Others
1 Line Crossing - Line to line / Road:
Excavation, Erection, testing and commissioning of
Protective guarding as per REC construction standard
drawing No A-1 to be provided at locations where 11KV/33
KV line is crossing road, 11 KV line is crossing LT Lines/
P&T lines etc. Supplying 2 Nos guarding cross arm made
of ISMC 75 channel, 2 Nos Y- guy with 7/3.14 mm wire, 2
Nos 16 mm diameter Eye-bolts, 2 Nos earthing of 40mm
dia GI pipe of 3 meter long, 8 SWG GI wires for earthing
connection, 6 SWG wire for guard wire, 8 SWG wire for
cross lacing and 1 meter long extension piece of ISMC 100
channel, MS clamps, hardware etc all complete including
two coat red oxide painting and two or more coats of
aluminium oxide paint of reputed make. Providing and
installing cement concreting as per scope of work,
approved drawings and technical specifications.
SET 0.04 52 2 2 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Sub Total
2 33 KV FEEDER BAY at 33/11 KV Grid Substations
using RS Joist supportsNo. 9
Part V LT Line
Page 33 of 38
![Page 35: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/35.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
i Excavation, Erection, testing and commissioning of
extension of 33 KV feeder bay using 2X4 support (2 Joist
welded together to form a support) of 9 m long, 175 x 85
mm RS Joists Bus Bar structure, 2x2 support ( 2 Joist
welded together to form a support) of 9 m long 175x85
mm RS Joist supports each for Isolator and Metering
equipment support structure including provision of base
plate (0.2x0.5x0.5m size), supporting galvanised steel
sections of channel, angle and flat, danger notice plate, 1
No GI Pipe earthing, 4 Nos Spike Earthing, earth
connection with 50X6 mm GS flat & 8 SWG GI wire, PG
Clamps, ACSR WOLF conductors, insulators, clamps,
channels, including line isolator switch of 800 A & 3 Nos
Station Class LAs etc as per specifications and tender
drawing complete as required. Providing and installing
cement concreting, charcoal, salt etc as per scope of
work, approved drawings and technical specifications.
Set 1 9 1 1 1 1 1 1 1 1 1
ii Design, Engineering and construction of
foundation, erection, testing and commissioning of
36kV, 1250A, 25kA for 3 seconds, 3-ph, Outdoor
type Vacuum Circuit breaker along with 36kV, 1-
Phase, 25kA/3 seconds, 800-400-200/1-1-1 Amps,
3 Nos outdoor type Current Transformers along
with junction box (1 no junction box for 3 no of 1-
phase CTs), Jumpers, earthing, supporting
structures, permanent maintenance platform,
marshalling box etc required as per technical
specifications, scope of works and approved
drawings
Set 1 9 1 1 1 1 1 1 1 1 1
iii Erection, testing and commissioning of Indoor type control
and relay panel for 33kV, indoor, Control & Relay panel
along with E/F & O/C relays, Mimic Diagram, Voltmeter,
Ammeter, Annunciation Windows with annunciation relays
and other components etc as per approved drawings,
specifications and scope of works controlling:
33 kV feeder VCB with Static Tri-Vector Energy Meter
Set 1 9 1 1 1 1 1 1 1 1 1
Sub Total
3 11 KV FEEDER BAY at 33/11 KV Grid Substations
using RS Joist Supports No. 6
i Excavation, Erection, testing and commissioning of
extension of 11 KV Feeder bay using 2x4 Nos. (2 Joist
welded together to form a support) 9 m long, 175 x 85
mm RS Joist structure including provision of base plate
(0.2x0.5x0.5m size), danger notice plate, 1 No GI Pipe
earthing, 4 Nos Spike Earthing, earth connection with
50X6 mm GS flat & 8 SWG GI wire, PG Clamps, DOG
conductors, insulators, clamps, channels etc as per
specifications complete as required including isolator
switch of 400 A & 3 Nos Station Class LAs etc as per
specifications and tender drawing complete as required.
Providing and installing cement concreting, charcoal, salt
etc as per scope of work, approved drawings and technical
specifications.
Set 1 6 1 1 1 1 1 1
ii Design, Engineering and construction of foundation,
erection, testing and commissioning of 12 kV, 1250 A,
25kA for 3 seconds, 3-ph, Outdoor type Vacuum Circuit
breaker along with 12 kV, 1-Phase, 25kA, 600-300-150/5-
5, 3 Nos outdoor type Current Transformer along with
junction box (1 no junction box for 3 no of 1-phase CTs),
Jumpers, earthing, supporting structures, permanent
maintenance platform, marshalling box, control cabling
between VCB and indoor control panel and required
accessories complete as per technical specifications,
approved drawings and scope of the works.
Set 1 6 1 1 1 1 1 1
iii Indoor type control and relay panel:
Erection, testing and commissioning of Indoor type control
and relay panel for 11kV, 3phase, 630 A VCB (feeder
Breaker) consisting of A-meter, volt-meter, E/F & O/C
Relay & accessories complete as per specifications for
transformer breaker protection
set 1 6 1 1 1 1 1 1
Sub Total
4 Supply and installation of RGGVY sign Board as per
scope of work, approved drawings and technical
specification,
UEV25
a Village Electrification Board and mounting angles with
excavation for foundations and concreting No 25 25 1 1 1 1 1 1 1 1 1 1 2 2 2 2 2 2 2 1
Page 34 of 38
![Page 36: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/36.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
b Distribution Transformer Electrification Board with clamp -
mounting on substation structure No 1738 1738 25 60 60 100 100 100 100 100 100 125 125 125 125 120 120 100 100 53
Sub Total
Addl. 5
MVA
2
Addl.10
MVA0
5-10 MVA 0
3.15-10
MVA0
3.15/1.6-5
MVA 4
Total 6pss 5
1 Design, Engineering and construction of
transformer foundation, erection, filtration, testing
and commissioning of 33/11 kV, 3 ph, 50 Hz,
ONAN, Cu Wound, Outdoor Conventional type
Power Transformer along with transformer oil,
Buchholtz relay, breather, OTI & WTI, Marshalling
Box, Conservator tank, oil level indicator, valves, 2
sets of 50x8 mm GS Neutral Earthing strips with
braided conductor on bushing end supported with
insulators, OTI & WTI Indicators, Vent explosion
plug, control wiring / cabling, cable supporting
tray on the body, transformer wheels, bushing etc
as required
set
a 10 MVA with off load tap changer No 1 0
b 5 MVA with off load tap changer No 1 6 1 1 1 1 1 1
2 Excavation, erection, cement concrete foundation,
erection, testing and commissioning of Galvanised
Gantry structures made of Lattice structures of
equal angles sections, flat as per approved
drawings. State practices are to be adopted in the
design. All structural steel members and bolts shall
be galvanized after fabrication as per IS:4759 and
zinc coating shall not be less than 610gm/sq.
meter for all structural steel members. All
L45x45x5 will have 23 mm back mark. All
L50x50x6 will have 28mm back mark. 3.5mm
spring washers are to be used under each nut,
structural steel shall conform to IS 2026. All weld
shall be 6mm filled weld unless specified
otherwise. All nuts and bolts shall be of property
class 5.6 of IS 1367. Plain washers shall be as per
IS 2016 & spring washers shall be IS: 3063 as per
approved drawings, technical specifications and
scope of the work.
MT 7 0.5 0.5 1 1 1 1 1 1
3 Design, Engineering and construction of foundation
(as per approved drawings), erection, testing and
commissioning of 36kV, 1250A, 25kA for 3 seconds,
3-ph, Outdoor type Vacuum Circuit breaker along
with 36kV, 1-Phase, 25kA for 3 seconds, 800-400-
200/1-1-1 Amps outdoor type Current Transformer
along with junction box (1 no junction box for 3 no
of 1-phase CTs)], Jumpers, earthing, supporting
structures, maintenance platform, marshalling box,
control cabling between VCB and indoor control
panel and required accessories complete as per
approved drawings, technical specifications and
scope of the work.
Set 4 1 1 1 1
PART VII33/11 KV Augmentation of Existing Substation
works: Fully outdoor
Page 35 of 38
![Page 37: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/37.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
4 Design, Engineering providing and installation of
ISMC 75 channel on top of indoor trench, erection
of panels on ISMC 75 channels, welding, testing
and commissioning of 33kV indoor Control & Relay
panel along with E/F & O/C relays, control and
power supply cabling in trench between field
equipment and panels, Mimic Diagram, Voltmeter,
Ammeter, Annunciation Windows with
annunciation relays and other components etc as
per approved drawings, technical specifications
and scope of the work for controlling:
a 33 kV Power transformer VCB with Static Tri-Vector
Energy Meter, No. 6
1 1 1 1 1 1
b 33 kV Power transformer VCB with Static Tri-Vector
Energy Meter, with differential relayNo. 0
5 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
commissioning of 36kV, 630A, 25kA for 3 sec, 3-ph
double break center rotating type (DBCR), Gang
Operated, isolator along with Support Insulators,
Operating Mechanism, Base Channel down Pipe
and all required accessories complete as per
approved drawings, technical specifications and
scope of the work,
Set 8 1 1 1 1 1 1 1 1
6 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
Commissioning of 36kV, 10kA, 1-ph Station Class
Lightening Arresters with mounting platform,
jumpering from bus bar, earthing connection using
50x6mm GS flat, hardware etc as required, as per
approved drawings, technical specifications and
scope of the work,
Set 6 1 1 1 1 1 1
7 Design, Engineering and construction of foundation
(as per approved drawings), Erection, testing and
Commissioning of 9kV, 10kA, 1-ph Station Class
Lightening Arrester with mounting platform,
jumpering from bus bar, earthing connection using
50x6mm GS flat, hardware, etc as required as per
approved drawings, technical specifications and
scope of the work.
Set 6 1 1 1 1 1 1
8.a Design, Engineering and construction of foundation (as
per approved drawings), Design, Engineering and
construction of foundation, erection, wiring, testing and
commissioning of 12 kV, 1250 A, 25kA, 3-ph, Outdoor
type Vacuum Circuit breaker along with 12 kV, 1-Phase,
25kA for 3 seconds, 600-300-150/5-5 A , outdoor type
Current Transformer along with junction box (1 no
junction box for 3 no of 1-phase CTs), Jumpers, earthing,
supporting structures, permanent maintenance platform,
marshalling box, control cabling between VCB and indoor
control panel and required accessories complete as per
approved drawings, technical specifications and scope of
the work for Transformer Protection Breaker Panel
Set 6 1 1 1 1 1 1
8.b Design, Engineering and construction of foundation (as
per approved drawings), Design, Engineering and
construction of foundation, erection, wiring, testing and
commissioning of 12 kV, 1250 A, 25kA, 3-ph, Outdoor
type Vacuum Circuit breaker along with 12 kV, 1-Phase,
25kA for 3 seconds, 1200-600-300/1-1-1 A , outdoor type
Current Transformer along with junction box (1 no
junction box for 3 no of 1-phase CTs), Jumpers, earthing,
supporting structures, permanent maintenance platform,
marshalling box, control cabling between VCB and indoor
Set 0
9 Installation, initial charging, cabling,
interconnection cabling, testing and commissioning
of 30V, 100 AH Pb Acid battery on battery stand
made of teak wood duly painted with anti rusting
paint, battery insulators, inter-battery wiring using
30 sqm copper single core multi strand cable,
terminal connectors, & all other accessories and
connectors as per as per approved drawings,
technical specifications and scope of the work,
Set 2.5 1 1 1
Page 36 of 38
![Page 38: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/38.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
10 Design, engineering, construction of foundation,
Installation, interconnection cabling, testing and
commissioning of 30V, 40 Amp. Float-Cum-Boost
Battery Charger with full wave rectification for
220 V, 1 phase, 50 Hz AC Input Supply with built
in DCDB as per approved drawings, technical
specifications and scope of the work,
set 2.5 1 1 1
11 Excavation, laying, welding, refilling, earthing &
grounding conductor as per Approved Electrical
Layout for each sub-station and erection of riser up
to various equipment/gantry structures as per
scope of the work, specifications and approved
drawings,
a 75 x 8 mm MS flat for ground mat MT 1.5 0.5 0.5 0.5
b 50 x 6 mm Galvanized GS flat (risers) MT 1.5 0.5 0.5 0.5
c 25 mm dia MS Rod 3 m long for earth mat MT 0.125 0.04 0.04 0.045
12 Excavation, erection, testing and commissioning of
40 mm dia., 3000 mm long GI pipe earth electrode
by providing test link, RCC pit, RCC cover, placed
on GI frame, Charcoal, Salt and other accessories
complete as per approved drawings, technical
specifications and scope of the work for power
transformer neutral, station transformer neutral,
lightening arresters direct earthing.
Set 40 5 5 5 5 5 5 5 5
13 Erection, testing and commissioning of Bus
Conductor (wolf Conductor), bus jumpers to
various equipment using 11 KV and 33 KV
insulators, GI Pin, GI Hardware fittings, PG
Clamps, T-connectors etc as required as per
approved drawings, specifications and scope of the
work.
km 0.4 0.05 0.05 0.05 0.05 0.05 0.05 0.05 0.05
14 Power Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required a 3.5 Core 70 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable meter 0.125 0.05 0.05 0.025
b 3.5 Core 35 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable meter 0.125 0.05 0.05 0.025
c 2 Core 16 Sq. mm armored, stranded aluminium
conductor, PVC insulated and PVC sheathed cable meter 0.5 0.05 0.05 0.05 0.05 0.05 0.05 0.1 0.1
15 Control Cables including their termination at
indoor/outdoor terminals including supply of
glands, lugs, cable ties, etc as required a 2 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable meter 0.1 0.025 0.025 0.05
b 5 Core 2.5 sqm armored, stranded copper conductor, PVC
insulated and PVC sheathed cable meter 0.5 0.05 0.05 0.05 0.05 0.05 0.05 0.1 0.1
c 10 Core 2.5 sqm armored, stranded copper conductor,
PVC insulated and PVC sheathed cable meter 0.5 0.05 0.05 0.05 0.05 0.05 0.05 0.1 0.1
Sub Total
PART
VIII33 KV Railway Crossing NO. 11
1
Laying,termination, Erection, Testing & commissioning of 2
nos. 33 KV grade 3-core 400 Sqmm XLPE power cable for
underground Railway Crossing including using
jointing/Termination Kit, GI pipe, CI pipe, clamps, conectors
bolts, nuts, fixing and fitting of barbed wire with all
accessories etc. complete in all respect as per TS, approved
drawing
Set 1 11 1 1 1 1 1 1 1 1 1 1 1
Sub Total
Part IX 11 KV Railway Crossing NO. 4Laying,termination, Erection, Testing & commissioning of 2
nos.11 KV grade 3-core 300 Sqmm XLPE power cable for
underground Railway Crossing including using
jointing/Termination Kit, GI pipe, CI pipe, clamps, conectors
bolts, nuts, fixing and fitting of anti-climbing device with all
accessories etc. complete in all respect as per TS, approved
drawing
Set 1 4 1 1 1 1
Sub Total
Part X LT Single Phase Service connection 62068
Page 37 of 38
![Page 39: PERT NETWORK-Summery Sheet - NBPDCL | Portal …app.nbpdcl.in/portal/Notices/15-Nov-2014-17-46_PERT.pdfNo. 0 1 33/11 kV, 3 ph, 50 Hz, ONAN, Cu Wound, Outdoor Conventional type Power](https://reader033.vdocuments.us/reader033/viewer/2022051307/5ac8eb707f8b9a7d548cc39e/html5/thumbnails/39.jpg)
ERECTION PERT CHART KATIHAR
Sl. No. Description Unit Unit
Quantity
Total
Quantity 2014 2015 2016
1 2 3 4 5 LOA date
21.08.14Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug Sept Oct Nov Dec Jan Feb Mar Apr May June July Aug
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
1 Erection testing and commissioning of Single phase
service connection using PVC insulated cable of
size 2 Core 2.5 sqmm aluminium conductor (up to
35m length of house hold from LT line), 10 SWG GI
tension wire, 20 mm GI Pipe medium class to
accept service cable at consumer residence, A
meter board (200x350x40mm) for 1ø ( single
phase) energy meter,Service board
(200x150x40mm),Single phase (5-30A) fully static
class-1 energy meter, 2nos. single piano type ISI
marked 250 V/5A switch 1no. 250V/5A socket of
ISI marked, 250V/5A ISI marked holder, 144-
288V, upto 9 watts, 710 lumen LED lamp 250V,5A
capacity ISI mark lamp holder, Internal wiring
using 1.5 sqmm copper multistrands PVC insulated
ISI marked cable, 250V/16A double pole MCB of
ISI marked and a cut-out a 10mm dia earth
terminal point, internal wiring in ISI marked 12mm
dia PVC rigid pipes including its clamps, fittings
and fixtures as required as per REC drawing and
Specifications. Earth point would be connected
with existing earth potential maintained by
DISCOM through 10 SWG GI wireetc. as per detail
scope of work.
No 1 62068 200 500 500 1500 1500 2000 2500 3500 3500 3500 3500 4500 4500 4500 4500 4500 4500 4500 4500 3368
Sub Total
Grand Total
Page 38 of 38