  • AIR CONDITIONING SYSTEMCOOLING ONLY [50Hz]

    PCS0911A

  • CEILING MOUNTED CASSETTE TYPE

    FHC18NUV1 FHC21NUV1 FHC26NUV1R18NUV1 R21NUV1 R26NUV1 / Y1Outdoor unit

    Indoor unit

    18,0005.3

    4,560

    21,0006.2

    5,290

    26,0007.6

    6,550

    2 2.5 3

    kW

    Btu/h

    kcal/h

    CEILING SUSPENDED TYPE

    OUTDOOR UNIT

    R18NUV1 R21NUV1 R26NUV1 / Y1

    DUCT CONNECTION

    LOW STATIC PRESSURE TYPE

    FDBG18PUV1 FDBG21PUV1 FDBG26PUV1

    FH21NUV1 FH26NUV1R21NUV1 R26NUV1 / Y1

    R18NUV1 R21NUV1 R26NUV1 / Y1

    HP

    Cooling only

    Outdoor unit

    Indoor unit

    Outdoor unit

    Indoor unit

    Outdoor unit

    Indoor unit

    Outdoor unit

    Indoor unit

    FDMG26PUV1R26NUV1 / Y1

    MIDDLE STATIC PRESSURE TYPE

    Capacity *1The values given for2 HP6 HP is for FHC type,6.5 HP7 HP is for FDMG type.

    *1. Note : Rated cooling capacities are based on the following conditions: Return air temp., 27CDB, 19.0CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal)

    FHC30NUV1R30NUV1 / Y1

    30,0008.8

    7,570

    3.5

    R30NUV1 / Y1

    FH30NUV1R30NUV1 / Y1

    FDMG30PUV1R30NUV1 / Y1

    FDMG26NUV1R26NUV1 / Y1

    FDMG30NUV1R30NUV1 / Y1

    The match for tastefully designed offices and stores.

    People are drawn to beaut i fu l ly designed stores that express the latest . People work best in off ices

    imbued with funct ional beauty.

    Daik in s SkyAir is the choice to br ing high qual i ty air condi t ioning to stores and off ices l ike th is.

    Thanks to i ts many advantages such as quiet operat ion, ease of use and f lexible instal lat ion, the SkyAir

    enjoys an excel lent reputat ion throughout the wor ld wherever i t is used.

    1

  • FHC42NUV1R42NUY1

    FHC48NUV1R48NUY1

    42,00012.3

    10,600

    48,00014.1

    12,100

    5 6

    CEILING MOUNTED CASSETTE TYPE

    FH42NUV1R42NUY1

    FH48NUV1R48NUY1

    51,00015.0

    12,900

    6.5

    56,00016.4

    14,100

    7

    R51NUY1R48NUY1R42NUY1 R56NUY1

    FDMG42PUV1 FDMG48PUV1R42NUY1 R48NUY1

    FDMG51PUV1R51NUY1

    FDMG56PUV1R56NUY1

    FHC36NUV1R36NUV1 / Y1

    36,00010.6

    9,100

    4

    R36NUV1 / Y1

    FH36NUV1R36NUV1 / Y1

    FDMG36PUV1R36NUV1 / Y1

    FDMG42NUV1 FDMG48NUV1R42NUY1 R48NUY1

    FDMG51NUV1R51NUY1

    FDMG56NUV1R56NUY1

    FDMG36NUV1R36NUV1 / Y1

    CEILING SUSPENDED TYPE

    DUCT CONNECTION TYPE

    The indoor uni t is instal led inside the cei l ing and ducts discharge air in any direct ion. Comfort is provided without even knowing that an air condi t ioner is instal led.

    Simple design and quiet operat ion auto-swing air f low br ings comfort to each and every corner of the room. Instal lat ion and maintenance are easy.

    Simple design and quiet operat ion auto-swing air f low br ings comfort to each and every corner of the room. Instal lat ion and maintenance are easy.

    The indoor uni t is instal led inside the cei l ing and ducts discharge air in any direct ion. Comfort is provided without even knowing that an air condi t ioner is instal led.

    This uni t is instal led at center cei l ing. Air is b lown in four direct ions to br ing comfort . Operat ion is quiet .

    This uni t is instal led at center cei l ing. Air is b lown in four direct ions to br ing comfort . Operat ion is quiet .

    2

  • Quiet, decor-blending form and easy installation

    3

    CEILING MOUNTED

    CASSETTE TYPE

    BRC7C613W

    A signal receiver must be added to the indoor unit.

    Note: Remote controller cable not included. Cables must be procured locally.

    Wireless remote controller and signal receiver unit are sold as a set.

    Wired LCD remote controller

    Wireless LCD remote controller

    BRC1C61

    FHC18NU48NUCooling only

    Signal receiver unit (Installed type)

    FHC-NU

    Accessory required for indoor unit

    Option

    *1 *2

    Sw

    ing

    pat

    tern

    sel

    ectio

    n

    Sw

    itcha

    ble

    fan

    spee

    d

    Aut

    o sw

    ing

    Pro

    gra

    mm

    e "D

    ry"

    Hig

    h ce

    iling

    ap

    plic

    atio

    n

    Tim

    er s

    elec

    tor

    Dra

    in p

    ump

    mec

    hani

    sm

    Pre

    cha

    rged

    for

    up to

    15

    m

    Long

    -life

    filte

    r

    Mou

    ld r

    esis

    tant

    trea

    tmen

    t fo

    r fil

    ter

    Filte

    r si

    gn

    Cei

    ling

    soi

    ling

    pre

    vent

    ion

    Ultr

    a lo

    ng-li

    fe fi

    lter

    Hig

    h-ef

    ficie

    ncy

    filte

    r

    Fres

    h ai

    r in

    take

    kit

    Aut

    o-re

    star

    t

    Two

    sele

    ctab

    le

    tem

    per

    atur

    e-se

    nsor

    s

    Cooling only

    MouldpreventionComfort Work & Servicing

    Control features Options OthersFeature

    Features

    *1Applicable when wired remote controller is used*2Applicable to R36NUR48NU outdoor units

    Model

    42/36dB(A)FHC36NU

    (220V)

    High Low

    Sound level

    PE

    fin

  • 4Optimal comfort and convenience assured by 3 air discharge modes

    Compact body and quiet operation

    Air discharge opening increases flow without increasing wind speed, hence discharged air reaches farther than before.

    Indoor units use anaerodynamically designedDiffuser Turbo Fan

    Wide air distribution

    Suitable for high ceilings

    Programme "Dry"

    Switchable fan speed: High/Low

    Multi-Flow System

    Two selectable temperature-sensors

    Unified square panelsAll models from the 18NU to 48NU use the same size panel. Multiple unit installations maintain a physical uniformity that is aesthetically pleasing and make it easier to plan ceiling lighting systems and to design interiors.

    Quick and easy to install

    Both indoor unit and wired remote controller (option) contain temperature- sensors. Temperature sensing can be set at the unit or, to further improve comfort level, closer to the target area at the wired remote control.This feature require initial setting by the installer.

    Draft resistance has been reduced by incorporating, into a single unit, an impeller and a diffuser to control air flow inside the unit. The Diffuser Turbo Fan is both quiet during operation and compact.

    All models suspended without lift

    Installable in any direction

    Provided with drain pump mechanism

    The high-performance filter and other options are easily clipped into place. There is no need for a screwdriver.

    Easy installation of options

    Just 240 mm high. Installable in tight ceiling spaces (18NU26NU)

    Easy height adjustment

    Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

    1 pattern4-way flow

    4 pattern3-way flow

    3 pattern2-way flow

    " " denotes piping direction. " " denotes sealing member for air discharge outlet (option) .

    Number of air discharge outlets used

    18NU26NU4-wayflow

    3-wayflow

    2-wayflow

    4-wayflow

    3-wayflow

    2-wayflow

    30NU48NU

    2.7 m3.0 m3.5 m

    3.0 m3.3 m3.5 m

    3.5 m3.8 m-

    3.2 m3.6 m4.2 m

    3.6 m4.0 m4.2 m

    4.2 m4.2 m-

    Note: Operation sound increases when using 2-way or 3-way flow.

    Air direction can be selected according to installation.

    StandardCeiling height

    High ceiling High ceiling

    Criteria for ceiling height and number ofair discharge outlets

    Note: For 3-way or 2-way flow installation, the sealing member for air discharge outlet (option) must be used to close off the unused outlet(s).

    26NU 35 30

    18NU 33 29

    950 mm

    950

    mm

    Same for all models

    Indoor unit High Low

    36NU 42 36

    21NU 35 30

    42NU 42 3648NU 42 36

    Diffuser

    Blade

    *Temperature-sensor on indoor unit must be used when the air conditioner is controlled from another room.

    **Wireless remote controller does not have a temperature-sensor.

    *When the thermostat turns off.

    Note: Initial settings are for standard ceiling height and 4-way flow. High ceiling settings 1 and 2 are set from the remote controller.

    Note: If the wireless remote control option is installed, a light receptor unit is housed in one of the adjuster pockets.

    240 mm *1 245 mm *2

    750 mm

    *1 298 mm high with 30NU48NU*2 303 mm high with 30NU48NU

    Each corner of the unit has an Adjuster Pocket that lets you easily adjust the unit's suspended height.

    Note: Air direction is set to the standard position when the unit is shipped from the factory. The position can be changed from the remote controller.

    Air directionDesired situation

    Auto-swing

    5-levelsair directionsetting

    Draft prevention(In heating mode)

    Auto air direction control

    Settable to 5 different levels between 10 and 40

    Settable to 5 different levels between 10 and 65

    Settable to 5 different levels between 30 and 65

    Auto-swing between10 and 40

    Auto-swing between10 and 65

    Auto-swing between30 and 65

    When drafts are unwanted For gentle drafts(Ceiling is soiled.) When ceilings must be kept spotlessDraft prevention setting Standard setting Setting to prevent soiling of ceiling

    At heating startup and thermo OFF*, air discharge is automatically set to a near horizontal 10 to prevent direct exposure to cool air drafts.

    The air direction is set automatically to the memorised position of the previous air direction. (Initial setting is 65 for heating and 30 for cooling.)

    At heating startup and thermo OFF*, air discharge is

    automatically set to 30 to prevent both direct exposure to cool air drafts and contact with ceilings.

    Super Cassette

    1

    2

    1

    2

    (m)2.7

    3

    (m)3.2

    4 (m)32101234 (m)

    Conventional model

    2.5 m/sec2.5 m/sec

    2.0 m/sec2.0 m/sec

    1.5 m/sec1.5 m/sec

    1.0 m/sec1.0 m/sec

    0.5 m/sec0.5 m/sec

    Air discharge distribution comparison42NU

    dB(A)(220V)

    30NU 39 34

  • Upgrade to a quiet and compact system.

    5

    CEILING SUSPENDED TYPE

    46/40dB(A)FH36NU

    (220V)

    High Low

    Sound level

    BRC7NU66

    A signal receiver must be added to the indoor unit.

    Note: Remote controller cable not included. Cables must be procured locally.

    Wireless remote controller and signal receiver unit are sold as a set.

    Wired LCD remote controller

    Wireless LCD remote controller

    BRC1NU61

    FH21NU48NUCooling only

    Signal receiver unit (Installed type)

    *1 Cooling only

    MouldpreventionComfort

    Work & Servicing Options

    Control featuresFeature

    Features

    *1Applicable to R36NUR48NU outdoor units

    Pre

    cha

    rged

    for

    up to

    15

    m

    Long

    -life

    filte

    r

    Mou

    ld r

    esis

    tant

    trea

    tmen

    t fo

    r fil

    ter

    Aut

    o-re

    star

    t

    Others

    PE

    fin

    Model Switc

    hab

    le fa

    n sp

    eed

    Aut

    o sw

    ing

    Pro

    gra

    mm

    e "D

    ry"

    Tim

    er s

    elec

    tor

    Mou

    ld p

    roof

    ing

    d

    rain

    pan

    Accessory required for indoor unit

    Option

    FH-NU

  • 64421NU26NU 44

    Quiet operationSpreads comfortable air throughout the room

    Installation flexibility for freedom of design

    Wide air discharge openings produce a spreading 100 airflow

    Air is blown up to 50 in the downward direction.

    Reduced edge space, flexible installation

    Uniform height and depth. Compact design for small-capacity models to meet tighter dimensional constraints.

    All wiring and internal servicing done from below the unit

    Installable on ceilings 3.5 m high

    Switchable fan speed: High/Middle/Low

    Programme "Dry"

    Indoor unit High Low

    36NU 46 4030NU 45 40

    42NU 48 4248NU 49 43

    *Water used in the test-run can now be drained from the air discharge opening rather than from the side as was formerly the case.

    Weight of all models reduced (down 10% compared with previous models). Transfer and installation work is less arduous.

    Improved-oil resistant grilleOil-resistant plastic is used for the air discharge grille. This improves durability in restaurants and other similar environments.

    Absence of bristles minimises clinging dirt and simplifies cleaning.

    It is easy to wipe dirt off the flat side and lower surfaces of the unit.

    The unit fits more snugly into tight spaces.

    Pipes more easily rigged, tooPlastic panels are used to conceal piping holes. Holes can be easily punched out without requiring special tools.

    For all maintenance tasks, access is from bottom surface

    Easier to maintainLong-life filter lasts about half year * maintenance not required

    Note: Intended for use in salons, dining rooms, and ordinary sales floors, this specification is not suitable for kitchens or other harsh environments.

    1,590 mm30 mm or more

    30 mm or more

    * For dust concentration of 0.15 mg/m3

    For 48NU indoor unit

    Non-dew flap without bristles

    Easy-clean, flat surfaces

    100

    50

    195

    1,590

    42NU 48NU

    680

    1,160 1,400

    (mm)

    Sound operation has been reduced on the exposed ceiling suspended type unit.

    Height

    Indoor unit

    WidthDepth

    Uses quiet stream fanand other quiet technologies.

    Turbulent flow is produced

    Non-dew flap

    Straightening vane

    Quiet stream fan

    26NU 36NU30NU21NU

    Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature.

    Auto-swing (up&down) brings comfort to the room.

    4040

    (220V) dB(A)

    Note : Anechoic chamber conversion value, measured according to JIS parameters and criteria.

  • DUCT CONNECTION

    MIDDLE STATIC PRESSURE TYPE

    Accessory required for indoor unitOption

    45/37dB(A)FDMG36PU

    (220V)

    High Low

    Sound level

    FDMG26PU56PUFDMG26NU56NU

    Cooling only

    FDMG-NUFDMG-PU

    Quiet operation

    Switchable fan speed: High/Middle/Low

    Drain pipe connection can be done inside the unit. Coolant and drain pipe outlets are at the same opening.

    FDMG26PU

    Indoor unit

    FDMG42PU

    FDMG36PU

    FDMG48PU

    FDMG56PU

    FDMG51PU

    High

    4645

    42

    46

    4747

    38FDMG30PU 44 36

    LOW

    3737

    37

    3737

    Air conditioner295 mm

    Ordinary duct(procured locally)

    Ordinary duct(procured locally)

    Air discharge Air intake305 mm or more

    (FDMG26NU56NU)

    Superior freedom of layout

    Unit can be mounted in the ceiling and air can be delivered freely by duct.

    The duct system allows the efficient location of discharge outlets in accordance with the room layoutMiddle static pressure type, usable in a larger than standard spaceDuct connection is simpler with standard rear intake chambers

    Work & Servicing

    Pre

    cha

    rged

    for

    up to

    15

    m

    Cooling only

    Comfort Control features OthersFeature

    Features

    Aut

    o-re

    star

    t

    *2

    Two

    sele

    ctab

    le

    tem

    per

    atur

    e-se

    nsor

    s

    *1

    PE

    fin

    Model Switc

    hab

    le fa

    n sp

    eed

    *1Applicable when wired remote controller is used (FDMG-PU)*2Applicable to R36NUR51NU outdoor units

    (220V) dB(A)

    Digital remote controller

    KRC47-2A KRC47-1A

    Remote controller

    FDMG36PU

    Wired LCD remote controller

    Wireless remote controller and signal receiver unit are sold as a set.

    Signal receiver unit

    (Separate type)BRC4C64

    A signal receiver must be added to the indoor unit.

    Note: Remote controller cable not included. Cables must be procured locally.

    Wireless LCD remote controller

    BRC1C61

    For FDMG-NU

    For FDMG-PU

    7

    (FDMG26PU56PU is switchable fan speed: High/Low)

  • 8Accessory required for indoor unitOption

    Simultaneous air conditioning of two rooms and ventilation grille (ventilation opening)

    Ventilation grille

    Door-installedventilation grille

    Ventilation grille

    Wall-installedventilation grille

    Under-door cutout

    Under-door cutoutWhen air conditioning two rooms simultaneously, the air discharged into each room must be circulated back to the air conditioner. To achieve this, a ventilation duct should be installed for each room or one of the indicated ventilation grilles should be installed on the partitioning wall or under the door between the rooms.

    Ventilates air through the partitioning wall. (See right)

    Partitioning wall

    Note: The under-door cutout method should be used only when there is a small volume of airflow.

    (This feature also applies to duct connection middle static pressure type.)

    Ideal for quiet, beautiful living spacesSuitable for condominiums and apartments, houses and hotels

    DUCT CONNECTION

    LOW STATIC PRESSURE TYPE

    FDBG18PU26PUCooling only

    FDBG-PU

    CompactSmall, lightweight, and easy-to-install indoor unit.

    Quiet operation

    FDBG18PU 41 38FDBG21PU 43 40FDBG26PU 43 40

    Indoor unit High Low

    43/40dB(A)FDBG26PU

    (220V)

    High Low

    Sound level

    Work & Servicing

    Pre

    cha

    rged

    for

    up to

    10

    m

    Cooling only

    Comfort Control features OthersFeature

    Features A

    uto-

    rest

    art

    Two

    sele

    ctab

    le

    tem

    per

    atur

    e-se

    nsor

    s

    *1

    PE

    fin

    Model Switc

    hab

    le fa

    n sp

    eed

    *1Applicable when wired remote controller is used

    (220V) dB(A)

    Suction chamberAir filter[Duct connection]

    To prevent increased operation sound, avoid installing the air suction grille directly below the suction chamber.

    or moreor moreor more

    Wired LCD remote controller

    Wireless remote controller and signal receiver unit are sold as a set.

    Signal receiver unit

    (Separate type)BRC4C64

    A signal receiver must be added to the indoor unit.

    Note: Remote controller cable not included. Cables must be procured locally.

    Wireless LCD remote controller

    BRC1C61

  • Fitted with wide inlet fan (Applies to R26NU51NU)

    Curved Super Aero Grille restricts the spread of exhaust gas and fits in the same space as conventional outdoor units.

    Fitted with Super Aero Grille (Applies to R26NU51NU)

    Equipped with scroll compressor for quiet operation

    Even less operation sound

    Wide inlet fan

    Allowed refrigerant pipe length and level difference

    Max. length Max. leveldifference

    Pre charged*1

    R26NU

    R36NU 30 m(Equivalent length 50 m)

    30 m(Equivalent length 50 m)

    30 m(Equivalent length 50 m)

    30 m(Equivalent length 50 m)R18NU

    R21NU

    30 m(Equivalent length 50 m)

    30 m(Equivalent length 50 m)

    R42NU

    R48NU

    R51NU

    Note: 1Additional refrigerant charging is required if the refrigerant pipe is longer than the length.

    (Applies to R36NU56NU)

    Construction

    Non-treated fin

    PE fin

    Aluminium

    AluminiumCorrosion resistantacrylic resin

    Hydrophilic film

    500

    50

    (mm)

    50 m(Equivalent length 70 m)R56NU

    30 m(Equivalent length 50 m)

    9

    OUTDOOR UNIT

    Quiet Operation

    Fully shaped aerodynamic propellers are designed to push air with a large wing surface. This provides both high blow volume and quiet operation with minimal turbulence.

    Slim-design and low-profile compact outdoor units (Applies to R26NU51NU)

    Compact

    Compactly designed outdoor unit with interior layout optimised for the smooth airflow.

    Smooth running, minimal vibration, low operating sound.

    To suppress turbulence and achieve quiet operation, the curved ribs of the grille are optimised to meet the outflow of air.

    Pre charged for up to 15 metres (Applies to R36NU51NU)

    Installation and maintenance

    If refrigerant piping length does not exceed 5m (R56NU), 10m (R18NU,R21NU, R26NU), 15m (R36NU, R42NU, R48NU, R51NU), there is no need for on-site gas charging.

    Heat exchange fins provided with anti-corrosion treatment

    Takes installation environment into consideration

    Durability

    To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit.

    4-direction piping offers greater layout freedom (Applies to R26NU56NU)

    (Applies to R26NU36NU)

    Piping can be run from the front, bottom, right or rear surface according to how the unit is installed.

    10 m

    15 m

    10 m

    10 m

    15 m

    15 m

    5 m

    15 m

    20m

    R30NU 30 m(Equivalent length 50 m)10 m 20m

    20 m

    15 m

    15 m

    20 m

    20 m

    30 m

    20 m

    Outdoor unit Sound level

    R36NUV1R36NUY1

    R30NUY1

    5557R30NUV1

    R42NUY1 57R48NUY1

    R18NUV1

    R21NUV1

    59

    4954

    R51NUY1 59

    R36NU R42NU R48/51NUR26/30NU

    (In case of V1: 220V, Y1: 380V) dB(A)

    R18NU R21NU

  • 10

    Air discharge direction angle can be set (fixed setting)

    Dehumidification is microprocessor controlled to prevent abrupt and uncomfortable changes in air temperature. Useful for reducing uncomfortable humidity without uncomfortable cooling of the room.

    Operation starts when the preset time of the ON timer elapses and stops when the preset time of the OFF timer elapses.

    Sanitary filter has mould resistant treatment.

    Mould proofing maintains hygiene by preventing growth in highly humid conditions.

    Steeper gradient realises more efficient condensate drainage. High-lift is especially useful for long lengths of drain piping.

    If refrigerant piping length does not exceed 15 m, there is no need for on-site gas charging. (Applies to R36NU51NU)

    If there is a power outage while the equipment is operating, operations will restart in the same mode as before the power cut when electricity is restored.

    Delivers comfortable air-conditioning to all areas, near to and far from the air-conditioner.

    High setting provides maximum reach while low setting minimises drafts.

    To achieve increased durability by improved resistance to salt corrosion and atmospheric pollution, coated PE fins (with special acryl pretreatment) are used for the heat exchanger of the outdoor unit. In high corrosive areas, regular maintenance needs to be carried out.

    Abundance of functions that provide comfortable air-conditioning in stores and offices. See the list of main functions given on the page introducing each indoor unit.

    Auto-swing

    Programme "Dry"

    Timer selector

    Mould resistant treatment for filter

    Mould proofing drain pan

    Drain pump mechanism

    Pre charged for up to 15 metres

    Auto-restartSwitchable fan speed

    PE fin

    Maintenance is not required for one year (two years when a ceiling mounted cassette type is used).

    Long-life filter

    (1) Air direction range in standard position

    (2) Air direction range in draft prevention position

    (3) Air direction range in ceiling soiling prevention position

    (draft prevention, standard, ceiling soiling prevention)

    Note:When units are installed on high ceilings, depending on the model, various restrictions concerning maximum height, air discharge direction, and choice of options may apply.

    You can freely set 3 air discharge positions by remote controller.

    Swing pattern selection

    Delivers air-conditioning comfort all the way down to the floor in air-conditioning zones with high ceilings.

    High-ceiling application

    The filter sign warns you when it is time to clean the filter.

    *When using a wired remote controller the sign is displayed in the LCD. When using a wireless remote controller the filter sign lamp illuminates on the signal receiver unit.

    Filter sign

    Daikin's innovative air discharge mechanism keeps airflow away from the ceiling. Ceiling cleaning is less frequently required.

    Ceiling soiling prevention function

    Two types are available: 65% and 90% colorimetry.

    High-efficiency filter unit

    Requires no maintenance for about 4 years* (10,000 h) in stores and offices. * For dust concentration of 0.15 mg/m3

    Ultra long-life filter

    You can provide air-conditioning with fresh air from outside. Convenient for places where a ventilation fan cannot be installed.

    Fresh-air intake kit

    C o m f o r t

    Mould prevention

    O t h e r s

    Work and Servicing

    Control features

    Options

    *Connecting ducts, insect nets, fire dampers, air filters, and other parts should, as required, be procured locally.

    **Outside Air fan interlocked with air conditioning unit is necessary. Optional PCB(KRP1C63)is required for interlocking.

    ***It is recommended that the volume of outdoor air introduced through the kit is limited to 10% of the maximum airflow rate of the indoor unit. Introducing higher quantities will increase the operating noise and may also influence temperature sending.

    Note:

  • Hermetically sealed scroll type

    2030 (equivalent length 50 m)

    21 to 46

    Cooling capacity 1a/1b

    kWBtu/h

    kcal/hkWPower consumption 1a/1b

    CDB

    CWBOperation range

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Dimensions(HXWXD)

    Colour

    mmmm

    Sound level (H/L) (220V) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2, 3 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Unit

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Decoration panel

    UnitDecoration panel

    Machine weightkgkgUnit

    Decoration panel

    Airflow rate (H/L) m3/mincfm

    Outdoorunit

    Colour

    mm

    Operation range

    Max. interunit piping length mmMax. installation level difference

    kWMotor outputCompressor Type

    CEILING MOUNTED CASSETTE TYPE

    White

    Ivory

    Both liquid and gas piping

    ----------

    14 to 28

    Power supply V1: 1 Phase, 220240 V, 50 Hz Y1: 3 Phase, 380415 V, 50 Hz

    Note : 1Rated cooling capacities are based on the following conditions: 1aIndoor temp., 27CDB, 19.5CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal). 1bIndoor temp., 27CDB, 19.0CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal).2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3In case of V1: 220V, Y1: 380V.

    Ivory Hermetically sealed scroll type

    CEILING SUSPENDED TYPE

    20

    Cooling capacity 1a/1b

    kWBtu/h

    kcal/hkWPower consumption 1a/1b

    ModelName

    Indoorunit

    Indoor unit

    Outdoor unit

    Sound level (H/L) (220V) 2 dB(A)

    Refrigerant charge (R-22) kg

    Sound level 2, 3 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Machine weight kg

    Operation range CDB

    Operation range CWB

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    Airflow rate (H/L) m3/mincfm

    Outdoorunit

    Colour

    mm

    Dimensions (HXWXD)

    Colour

    mm

    Max. interunit piping length mmMax. installation level difference

    kWMotor outputCompressor Type

    Note : 1Rated cooling capacities are based on the following conditions: 1aIndoor temp., 27CDB, 19.5CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal). 1bIndoor temp., 27CDB, 19.0CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal).2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3In case of V1: 220V, Y1: 380V.

    Power supply V1: 1 Phase, 220240 V, 50 Hz Y1: 3 Phase, 380415 V, 50 Hz

    White

    14 to 28

    21 to 46

    Both liquid and gas piping

    30 (equivalent length 50 m)

    36,500/36,00010.7/10.6

    9,200/9,100

    46/40195X1,590X680

    35

    3.002.0

    1,170X900X32081 (V1), 79 (Y1)

    (Charged for 15 m)

    I.Do/ 20XO.Do/ 26

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    4.06/4.06

    32-34/22-241,129-1,200/776-847

    55

    36FH36NUV1R36NUV1R36NUY1

    30,400/30,0008.9/8.8

    7,670/7,570

    45/40195X1,400X680

    32

    2.52.3

    770X900X32070 (V1), 69 (Y1)

    (Charged for 10 m)

    I.Do/ 20XO.Do/ 26

    o/ 9.5o/ 15.9

    o/ 26.0 (Hole)

    3.48/3.48

    26-27/22-23917-953/776-811

    30FH30NUV1R30NUV1R30NUY1

    42,700/42,00012.5/12.3

    10,800/10,600

    48/42195X1,590X680

    35

    3.752.4

    1,170X900X32087

    (Charged for 15 m)

    I.Do/ 20XO.Do/ 26

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    4.83/4.83

    38-40/23-251,341-1,412/811-882

    57

    R42NUY1

    42FH42NUV1

    49,100/48,00014.4/14.1

    12,400/12,100

    49/43195X1,590X680

    35

    4.502.6

    1,345X900X32092

    (Charged for 15 m)

    I.Do/ 20XO.Do/ 26

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    5.50/5.50

    42-44/24-261,482-1,553/847-917

    59

    R48NUY1

    48FH48NUV1

    15

    Hermetically sealed rotary type

    3.002.0

    1,170X900X32081 (V1), 79 (Y1)

    (Charged for 15 m)

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    55

    36FHC36NUV1

    R36NUV1R36NUY1

    33/241,164/847

    288X840X840

    28

    42/36

    40X950X950

    5

    I.Do/ 25XO.Do/ 32

    36,500/36,00010.7/10.6

    9,200/9,1004.04/4.04

    2.52.3

    770X900X32070 (V1), 69 (Y1)

    (Charged for 10 m)

    o/ 9.5o/ 15.9

    o/ 26.0 (Hole)

    30FHC30NUV1

    R30NUV1R30NUY1

    28/21988/741

    288X840X840

    28

    39/34

    40X950X950

    5

    I.Do/ 25XO.Do/ 32

    30,400/30,0008.9/8.8

    7,670/7,5703.45/3.45

    3.752.4

    1,170X900X32087

    (Charged for 15 m)

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    57

    R42NUY1

    42FHC42NUV1

    33/241,164/847

    42/36288X840X84040X950X950

    285

    I.Do/ 25XO.Do/ 32

    42,700/42,00012.5/12.3

    10,800/10,6004.79/4.79

    4.502.6

    1,345X900X32092

    (Charged for 15 m)

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    59

    R48NUY1

    48FHC48NUV1

    33/241,164/847

    42/36288X840X84040X950X950

    285

    I.Do/ 25XO.Do/ 32

    49,100/48,00014.4/14.1

    12,400/12,1005.49/5.49

    Ivory white

    18FHC18NUV1

    R18NUV1

    1.71.20

    49540X750X270

    42

    (Charged for 10 m)

    o/ 6.4o/ 15.9

    o/ 18.0 (Hole)I.Do/ 25XO.Do/ 32

    15/11529/388

    230X840X840

    24

    33/29

    40X950X950

    5

    18,100/18,0005.3/5.3

    4,580/4,5602.03/2.02

    Hermetically sealed rotary type

    21FHC21NUV1

    R21NUV1

    2.21.50

    54685X800X300

    61

    (Charged for 10 m)

    o/ 6.4o/ 15.9

    o/ 18.0 (Hole)I.Do/ 25XO.Do/ 32

    19/14670/494

    230X840X840

    24

    35/30

    40X950X950

    5

    21,200/21,0006.2/6.2

    5,340/5,2902.46/2.45

    26FHC26NUV1

    R26NUV1R26NUY1

    57 57

    2.52.3

    770X900X32070 (V1), 69 (Y1)

    (Charged for 10 m)

    o/ 9.5o/ 15.9

    o/ 26.0 (Hole)I.Do/ 25XO.Do/ 32

    19/14670/494

    230X840X840

    24

    35/30

    40X950X950

    5

    26,300/26,0007.7/7.6

    6,630/6,5503.07/3.07

    26FH26NUV1R26NUV1R26NUY1

    57 57

    2.52.3

    770X900X32070 (V1), 69 (Y1)

    (Charged for 10 m)

    I.Do/ 20XO.Do/ 26

    o/ 9.5o/ 15.9

    o/ 26.0 (Hole)

    44/40

    26,300/26,0007.7/7.6

    6,630/6,5503.10/3.10

    22-23/9-20776-811/317-706

    195X1,160X68026

    15

    21FH21NUV1

    R21NUV1

    2.21.50

    54685X800X300

    61

    (Charged for 10 m)

    I.Do/ 20XO.Do/ 26

    o/ 6.4o/ 15.9

    o/ 18.0 (Hole)

    21,200/21,0006.2/6.2

    5,340/5,290

    22-23/9-20776-811/317-706

    44/40195X1,160X680

    26

    2.72/2.71

    Ivory white

    11

  • CDB

    CWB

    kWHermetically sealed rotary type

    1.71.13

    49540X750X270

    42

    2.21.55

    54685X800X300

    61

    1530 (equivalent length 50 m)

    (Charged for 10 m) (Charged for 10 m)

    o/ 6.4o/ 15.9

    o/ 6.4o/ 15.9

    o/ 18.0 (Hole) o/ 18.0 (Hole)

    Both liquid and gas piping

    2.52.3

    770X900X32070 (V1), 69 (Y1)

    (Charged for 10 m)

    o/ 9.5o/ 15.9

    o/ 26.0 (Hole)

    20

    57

    21 to 46

    2.12/2.11 2.73/2.72 3.33/3.33

    3/4B (I.Do/ 21.6XO.Do/ 27.2)

    ----------13/11

    458/388

    41/38260X900X580

    25

    18/15635/529

    43/40260X1,300X580

    32

    18/15635/529

    43/40260X1,300X580

    3214 to 28

    Ivory white Ivory

    Cooling capacity 1a/1b

    kWBtu/h

    kcal/hkWPower consumption 1a/1b

    Operation range

    ModelName

    Indoor unit

    Outdoor unit

    Dimensions (HXWXD) mmSound level (H/L) (220V) 2 dB(A)

    2.0 2.0 2.0Rated external static pressure mmH2O

    Refrigerant charge (R-22) kg

    Sound level 2, 3 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H/L) m3/mincfm

    Outdoorunit

    mm

    Operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    R18NUV1 R21NUV1R26NUV1R26NUY1

    Colour

    Power supply

    Motor outputCompressor Type

    DUCT CONNECTION LOW STATIC PRESSURE TYPE

    Note : 1Rated cooling capacities are based on the following conditions: 1aSuction temp., 27CDB, 19.5CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal). 1bSuction temp., 27CDB, 19.0CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal). 2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3In case of V1: 220V, Y1: 380V.

    18FDBG18PUV1

    21 26FDBG21PUV1 FDBG26PUV1

    V1: 1 Phase, 220240 V, 50 Hz Y1: 3 Phase, 380415 V, 50 Hz18,100/18,000

    5.3/5.34,580/4,560

    21,200/21,0006.2/6.2

    5,340/5,290

    26,300/26,0007.7/7.6

    6,630/6,550

    Hermetically sealed rotary type

    3/4B (I.Do/ 21.6XO.Do/ 27.2)

    DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

    Note : 1Rated cooling capacities are based on the following conditions: 1aSuction temp., 27CDB, 19.5CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal). 1bSuction temp., 27CDB, 19.0CWB; outdoor temp. 35CDB. Equiv. refrigeration piping, 7.5 m (horizontal). 2Anechoic chamber conversion value, measured according to JIS parameters and criteria. During operation these values are somewhat higher owing to ambient conditions.

    3In case of V1: 220V, Y1: 380V.

    ----------

    Hermetically sealed scroll type

    Both liquid and gas piping

    Cooling capacity 1a/1b

    kWBtu/h

    kcal/hkWPower consumption 1a/1b

    CDB

    CWBOperation range

    ModelName

    Indoor unit

    Outdoor unit

    Dimensions (HXWXD) mmSound level (H/L) (220V) 2 dB(A)

    Refrigerant charge (R-22) kgSound level 2, 3 dB(A)Dimensions (HXWXD) mmMachine weight kg

    Piping connections

    mmLiquid (Flare)

    Heat insulation

    mmGas (Flare)mmDrain Indoor unit

    Outdoor unit

    kg

    Airflow rate (H)Fan m3/mincfm

    Outdoorunit

    mm

    Operation range

    Max. interunit piping length mm

    Machine weight

    Indoorunit

    Colour

    Max. installation level difference

    30 (equivalent length 50 m)

    Ivory

    Colour

    Power supply V1: 1 Phase, 220240 V, 50 Hz Y1: 3 Phase, 380415 V, 50 Hz

    kWMotor outputCompressor Type

    14 to 28

    21 to 46

    36,500/36,00010.7/10.6

    9,200/9,100

    305X1,550X68052

    2.0(Charged for 15 m)

    1,170X900X32081 (V1), 79(Y1)

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    371,306

    45/37

    3.00

    55

    36

    FDMG36NUV1R36NUV1R36NUY1

    30,400/30,0008.9/8.8

    7,670/7,570

    305X1,550X68051

    2.3(Charged for 10 m)

    770X900X32070 (V1), 69 (Y1)

    o/ 9.5o/ 15.9

    o/ 26.0 (Hole)

    3.46/3.46

    341,200

    44/36

    2.5

    30

    FDMG30NUV1R30NUV1R30NUY1

    20

    42,700/42,00012.5/12.3

    10,800/10,600

    305X1,550X68052

    2.4(Charged for 15 m)

    1,170X900X32087

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    421,482

    46/37

    3.75

    57

    42

    FDMG42NUV1

    R42NUY1

    49,100/48,00014.4/14.1

    12,400/12,100

    305X1,550X68052

    2.6(Charged for 15 m)

    1,345X900X32092

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    421,482

    46/37

    4.50

    59

    48

    FDMG48NUV1

    R48NUY1

    52,200/51,00015.3/15.0

    13,200/12,900

    305X1,900X68058

    2.7 (Charged for 15 m)

    1,345X900X32093

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    421,482

    47/37

    4.50

    59

    51

    FDMG51NUV1

    R51NUY1

    50 (equivalent length 70 m)30

    57,000/56,00016.7/16.4

    14,400/14,1004.16/4.16 4.84/4.84 5.55/5.55 5.90/5.90 6.45/6.45

    305X1,900X68058

    2.8 (Charged for 5 m)

    1,345X880X370114

    o/ 9.5o/ 19.1

    o/ 26.0 (Hole)

    421,482

    47/37

    4.50

    56

    56

    FDMG56NUV1

    R56NUY1

    26

    FDMG26NUV1FDMG36PUV1FDMG30PUV1 FDMG42PUV1 FDMG48PUV1 FDMG51PUV1 FDMG56PUV1FDMG26PUV1

    R26NUV1R26NUY1

    2.52.3(Charged for 10 m)

    770X900X32070 (V1), 69 (Y1)

    o/ 9.5o/ 15.9

    o/ 26.0 (Hole)

    57 57

    26,300/26,0007.7/7.6

    6,630/6,5503.15/3.15

    23811

    42/38Rated external static pressure mmH2O 9.810.1 8.0 8.0 9.8 9.88.5

    305X1,350X68043

    12

  • 13

    DUCT CONNECTION LOW STATIC PRESSURE TYPE

    Outdoor unit

    KIS95-------Drain piping kit -------

    Indoor unit

    Note: 1Wiring for wired remote controller to be procured locally.

    CEILING SUSPENDED TYPE

    Replacement long-life filterL-type piping kit (for upward direction)Remote controller

    Resin net

    Wireless typeWired type1

    Note: 1Wiring for wired remote controller to be procured locally.

    Remote controllerWireless typeWired type1

    FDBG18PU FDBG21PU FDBG26PU

    FH21NU FH26NU FH30NU FH36NU FH42NU

    KHFJ5F160

    FH48NU

    FHC18NU FHC21NU FHC26NU FHC30NU FHC36NU FHC42NU FHC48NU

    KAF501DA160KAF501DA80 KAF501DA112KHFJ5F80

    -------Central drain plug KKPJ5F180

    BRC1NU61BRC7NU66

    CEILING MOUNTED CASSETTE TYPE

    ItemType

    Decoration panel

    Fresh air intake kit Without the T-joint pipe and fanWith the T-joint pipe,without fan

    Direct installation type

    Chamber type

    Sealing member for air discharge outletPanel spacer

    Note:1Required for installing high-efficiency filter or ultra long-life filter. 2Wiring for wired remote controller to be procured locally.3This optional accessory requires DTA102A52.4Installation box for adaptor PCB (KRP1B98) is necessary.

    High-efficiency filter

    High-efficiency filter chamber Replacement long-life filter

    (Colorimetric method 65%)(Colorimetric method 90%)

    Replacement high-efficiency filter

    (Colorimetric method 65%)(Colorimetric method 90%)

    Remote controller Wired type2

    Wireless type

    Ultra long-life filterReplacement ultra long-life filterBranch duct chamber

    BYC125K-W1, BYC125K-W2

    KDDF55D160

    KDBH55D160W

    KDD55DA160KDD55DA160KKDDJ55X160

    KAF551K160KAFP55D160KAF55K160H

    KAF556DA80KAF557DA80

    KAF556DA160KAF557DA160

    KDJ55K80 KDJ55K160BRC1C61

    BRC7C613W

    KDBP55H160WA

    KAFP552B80 KAFP552B160KAFP553B80 KAFP553B160

    R18NU R21NU R26NU R30NU R36NU R42NU R48NU R51NU R56NU

    Central remote controller3

    Unified ON/OFF controller3

    Schedule timer3

    DCS302CA61DCS301BA61DST301BA61

    DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

    BRC4C64

    FDMG26PU FDMG30PU FDMG36PU FDMG42PU FDMG48PU FDMG51PU FDMG56PU

    BRC1C61

    Note: 1Wiring for wired remote controller to be procured locally.

    Remote controllerWireless typeWired type1

    BRC4C64BRC1C61

    Adaptor for wiring4

    Wiring adaptor for electrical appendices3

    Interface adaptor for SkyAir seriesInstallation box for adaptor PCB

    KRP1BA57KRP4AA53DTA102A52KRP1B98

    ItemType

    ItemType

    KRC47-2ARemote controllerDigital remote controller

    FDMG26NU FDMG30NU FDMG36NU FDMG42NU FDMG48NU FDMG51NU FDMG56NU

    KRC47-1A

    ItemType

    ItemType

    ItemType

  • DIMENSIONS (Unit: mm)

    1234567

    89101112131415161718

    Air discharge grilleAir suction grilleAir filterGas pipe connectionLiquid pipe connection Drain pipe connecitonEarth terminal (inside the electric components box) (M4)Suspension bracketBackward piping and wiring connection opening lidUpward piping and wiring connection opening lidRight side pipe connection Left back drain pipe connection Left side drain pipe connection Right side drain pipe connection Hole of wall for taking out in piping back Upward drain pipe connection Upward gas pipe connection Upward liquid pipe connection

    Notes:1

    2

    3

    A B

    1120 1160

    1120 1160

    FH21NUV1

    FH26NUV1

    1550 1590

    1550 1590

    1550 1590

    FH36NUV1

    FH42NUV1

    FH48NUV1

    CEILING SUSPENDED TYPE

    14

    Location of unit's Name Plate: Bottom of fan housing inside the suction grille.In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.The remote control code is the standard attached.(0.5 mm2 2 wicks O.D. 5.4)(It is attached to VRV.)

    CEILING MOUNTED CASSETTE TYPE

    Notes:1Location of unit's Name Plate For Main body: Switch Box Cover inside surface of suction grille. For decoration panel: Panel frame inside surface of suction grille.2When installing an optional accessory, refer to the installation drawings. For fresh air intake kit Inspection port is necessary. For high efficiency filter unit Inspection port is not necessary.3In case of using wireless remote controller, this position will be a signal receiver. Refer to the drawing of wireless remote controller in detail.

    Liquid pipe connectionGas pipe connectionDrain pipe connectionPower supply connectionRemote control code and control wiring connectionAir discharge grilleAir suction grillePort for water supplyCorner decoration coverDrain hose

    1

    2

    3

    4

    5

    6

    7

    8

    9

    10

    C

    165

    195

    A

    230

    288

    B

    240

    298

    D

    ----

    165

    E

    ----

    195

    FHC18NUV1-26NUV1

    FHC30NUV1-48NUV1

    FHC18NUV1 / 21NUV1 / 26NUV1 / 30NUV1 / 36NUV1 / 42NUV1 / 48NUV1

    FH21NUV1 / 26NUV1 / 30NUV1 / 36NUV1 / 42NUV1 / 48NUV1

    1360 1400FH30NUV1

    ! "

    #

    $$

    %

    #

    $$

    %

    ! "

    #

    &$

    %

    ' ( ) )

    ** *

    + , , - . $

    ** */

    ** *

    **

    *

    **

    *

    0. $

    0.$

    1$

    2

    3/

    1$$

    1$ $

    *

    4

    52

    #

    6

    %

    ! !

    6 , $,

    6

    ,$,

    ! "

    #

    $$

    %

    0.$

    *

    [FHC30NUV1-48NUV1]

    [FHC18NUV1-26NUV1]

    !"

    #$

    % & ' ( '

    &

    ) *%"

    ""+

    ",+

    ,

    +

    ,

    ",

    " +

    -

    +

    -

    ."

    "

    +

    +

    .

    ""-

    .+

    ",+

    +

    +

    +

    /0(

    $

    &

    $"+

    1

    $

    ++

    -

    +

    ++

    + -

    -+

    +-

    -+

    +

    + -

    .

    "

    ++

    .

    +

    , -

    +

    "

    -

    +

    ,

    -

    % 2 & 3 & ' ( '

    *3 & &

    *3 & &

    4

    +

    ++

    5

    #

    /0(

    $

    /0(

    $

  • DIMENSIONS (Unit: mm)DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

    Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

    1234

    Note: 1Location of unit's Name Plate: Chamber cap

    Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

    5678

    15

    FDMG26PUV1

    1550

    A B C E F G

    1353 1403 1314 7XP150=1050 18-M4HolesFDMG30NUV1/36NUV1/42NUV1/48NUV1

    FDMG51NUV1/56NUV1 1900 1703 1753 1664

    D

    1334

    1684 9XP150=1350 22-M4Holes

    1550

    H J K M N O

    1353 1337 7XP150=1050 20-M4Holes1900 1703 1687

    L

    1321

    1671 9XP150=1350 24-M4Holes

    263

    269

    FDMG30PUV1 / 36PUV1 / 42PUV1 / 48PUV1 / 51PUV1 / 56PUV1

    !

    "

    #

    $

    %

    &

    '

    (

    )

    *

    +

    , -

    Note: 1Location of unit's Name Plate: Chamber cap

    Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

    1234

    Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

    5678

    !

    "#

    !"#

    $

    %

    &

  • 16

    DUCT CONNECTION MIDDLE STATIC PRESSURE TYPE

    Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

    1234

    Note: 1Location of unit's Name Plate: Chamber cap

    Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

    5678

    FDMG26NUV1

    1550

    A B C E F G

    1353 1403 1314 7XP150=1050 18-M4HolesFDMG30NUV1/36NUV1/42NUV1/48NUV1

    FDMG51NUV1/56NUV1 1900 1703 1753 1664

    D

    1334

    1684 9XP150=1350 22-M4Holes

    1550

    H J K M N

    1353 1337 7XP150=1050 20-M4Holes1900 1703 1687

    L

    1321

    1671 9XP150=1350 24-M4Holes

    FDMG30NUV1 / 36NUV1 / 42NUV1 / 48NUV1 / 51NUV1 / 56NUV1

    ! "#$

    ! "#$

    # %#

    #& "

    !

    "

    #

    $

    %

    &

    '

    (

    )

    ' '*

    +

    ,

    ' '*

    Note: 1Location of unit's Name Plate: Chamber cap

    Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

    1234

    Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

    5678

  • (Unit: mm)DIMENSIONS (Unit: mm)DIMENSIONS

    17

    DUCT CONNECTION LOW STATIC PRESSURE TYPE

    Liquid pipe connection Gas pipe connectionDrain pipe connectionGround terminal

    1234 Note: 1Location of unit's Name Plate: Chamber cap

    Switch boxControl wiring intake (for remote controller)Control wiring intake (for outdoor unit)Suspension bracket

    5678

    A B C F G I

    900

    FDBG21PUV1/26PUV1 1300

    704

    1104

    755

    1155

    D

    684

    1084

    E

    664

    1064

    3XP150=450 500 3XP150=450 674 688 704 900 10-M4Holes 12-M4Holes6XP150=900 700

    H

    127

    102 6XP150=900 1074 1088 1104 1300 16-M4Holes 18-M4Holes

    FDBG18PUV1

    J K L M N O

    FDBG18PUV1 / 21PUV1 / 26PUV1

    !

    "#

    $

    %

    &

    '

    (

    )

    *

    +

    ,

    -

    .

    /

  • OUTDOOR UNIT

    R18NUV1

    R21NUV1

    18

    !

    "# $

    %

    &'(

    )*

    +

    +

    ,

    )-

    .

    )

    !

    -+

    *

    *+

    )*

    +!

    + +

    +)

    -

    *

    )*

    .

    +

    !

    *)

    ! )*

    +

    +

    ,

    +

    &

    ,

    .

    /

    !"

    !"

    #

    $% &

    '(

    )

    *

    +"

    (

    ,

    ,-.

    ( /

    )

    *

  • DIMENSIONS (Unit: mm)

    19

    OUTDOOR UNIT

    R36NUV1/Y1

    Gas pipe connection Liquid pipe connection Service port(in the unit) Grounding terminal Refrigerant piping intake Power supply wiring intake Control wiring intake Drain pipe connection

    12345678

    R26NUV1/Y1R30NUV1/Y1

    Note: In some circumstances, with certain machine types, it may not be possible to attach the supplied piping.

    Gas pipe connectionLiquid pipe connectionGrounding terminal M5(in switch box)

    Refrigerant piping intakePower supply wiring intakeControl wiring intakeDrain connection

    1

    2

    3

    4

    5

    6

    7

  • 20

    OUTDOOR UNIT

    R42NUY1, R48NUY1, R51NUY1

    Gas pipe connectionLiquid pipe connectionService port (in the unit)

    Grounding terminal M5 (in switch box)

    Refrigerant piping intakePower supply wiring intakeControl wiring intakeDrain pipe connection

    1

    2

    3

    4

    5

    6

    7

    8

    A

    R42NUY1

    R48NUY1/51NUY1

    1170

    1345

    B

    54

    55

    C

    113

    D

    579

    Gas pipe connectionLiquid pipe connectionService port(in the unit)

    Grounding terminal M5(in switch box)

    Refrigerant piping intakePower supply wiring intakeControl wiring intakeDrain outlet

    1

    2

    3

    4

    5

    6

    7

    8

    R56NUY1

  • 21

    REMOTE CONTROLLER

    DIMENSIONS (Unit: mm)

    !

    "# $#

    ! #

    # #

    %

    !

    #&

    '()*'+ %'

    ),&-, ,

    .

    /# /

    00 !!

    ) #-, !

    )

    1# $, ,,

    2#& ,3#4 !! !

    ( 0 *! # #

    # ,0 ,

    / & 0

    (

    ), !## / ,0

    5 6- 7 4 , $

    #& ,3#4 !! !

    8

    9

    89

    :8

    &

    ,

    8:

    9

    )#!#-

    0

    +6&

    ! #

    *! #

    ,

    :8

    9

    :

    *

    %

    990

    %

    90

    %

    ;

    9

    #

    8

    9

    :

    ;

    8

    ;

    9

    8

    :

    8

    :

    *! # ,

    ## &

    ?2## $ &/@

    *! # ,

    ## &

    ?2## $ &/@

    )#!#-

    0

    9 80

    *! #

    *! #

    ,

    *= ## &

    = / #-

    ##

    *=

    ( 4

    7,#;

    =

    8:0

    #-##-

    8

    0

    :

    9;

    #- ##-

    A

    ;

    $,

    / &

    " # # ! ,# :

    = # , =# / #

    #,0

    , 9 ! ,

    $ , /

    !/#

    *! # !##

    *! # ## &

    *=

    *! # !##

    *= ## &

    *=

    "# #

    "# #-

    */-#

    #-

    *=

  • 22

    H

    L

    500 or m

    ore

    50(100

    )

    or mor

    e

    1000 or

    more

    200(30

    0)

    or mor

    e

    L H

    L H

    L H

    [Space required for outdoor unit installation] (Unit: mm)Dimensions inside brackets [ ] indicate case where air direction adjustment guide is adjusted downward.

    For R26NU-56NU

    200(30

    0) or m

    ore

    1000 or more

    200 or more

    100 or

    more

    100 or more100 or more

    50(100

    ) or mo

    re

    1000 or

    more

    100 or

    more

    500 or le

    ss

    1000

    or m

    ore

    500 or

    more

    150 or

    more

    150 or more 150 or more

    500 or le

    ss

    1000

    or m

    ore

    200(30

    0) or m

    ore

    1000 or more

    200 or more

    500 or le

    ss

    1000

    or m

    ore

    500 or

    less

    500 or

    more

    1000

    or m

    ore

    500 or l

    ess

    1000 or

    more

    1000

    or m

    ore

    When there is an obstruction on the inlet side

    When the obstruction on the outlet side is higher than the unit itself (There is no limit to the height of the obstruction on the outlet side.)

    When there are obstructions on both the inlet and outlet sides

    When there is an obstruction on the outlet side

    When there are obstructions on the inlet side and both lateral sides

    2. For series installation (more than two units)

    When there are obstructions on both sides

    Pattern 1

    When the overhead space is open

    1. For single unit installation

    When there is an obstruction only on the inlet side

    When there is an obstruction in the overhead space

    When the overhead space is open

    When there are obstructions on both sides

    When there is an obstruction in the overhead space

    When there is an obstruction on the inlet side

    When there are obstructions on the inlet side and both lateral sides

    2. For series installation (more than two units)

    1. For single unit installation

    1. For single unit installation

    When the overhead space is open

    2. For series installation (more than two units)

    1. For single unit installation

    2. For series installation (more than two units)

    1. For single unit installation

    2. For series installation (more than two units)

    An obstruction in the overhead space

    An obstruction in the overhead space

    An obstruction in the overhead space

    An obstruction in the overhead space

    For other patterns, please referto engineering databook.

    An obstruction in the overhead space

    The values represent the case for the R26 type through R56 type. The dimensions in ( ) are for the R36 and R56 type (The unit values is mm. )In case of R56 model, the values in < > are those when the air discharge direction of the grille is downward.

  • DealerHead Office:Umeda Center Bldg., 2-4-12, Nakazaki-Nishi,Kita-ku, Osaka, 530-8323 Japan

    Tokyo Office:JR Shinagawa East Bldg., 2-18-1, Konan,Minato-ku, Tokyo, 108-0075 Japan

    http://www.daikin.com/global_ac/

    1. Air conditioners should not be installed in areas where corrosive gases, such as acid gas or alkaline gas, are produced.2. If the outdoor unit is to be installed close to the sea shore, direct exposure to the sea breeze should be avoided. If you need to install the outdoor unit close to the sea shore, contact your local distributor.

    Cautions on product corrosion

    Warning Daikin products are manufactured for export to numerous countries throughout the world. Prior to purchase, please confirm with your local authorised importer, distributor and/or retailer whether this product conforms to the applicable standards, and is suitable for use, in the region where the product will be used. This statement does not purport to exclude, restrict or modify the application of any local legislation.

    Ask a qualified installer or contractor to install this product. Do not try to install the product yourself. Improper installation can result in water or refrigerant leakage, electrical shock, fire or explosion.

    Use only those parts and accessories supplied or specified by Daikin. Ask a qualified installer or contractor to install those parts and accessories. Use of unauthorised parts and accessories or improper installation of parts and accessories can result in water or refrigerant leakage, electrical shock, fire or explosion.

    Read the User's Manual carefully before using this product. The User's Manual provides important safety instructions and warnings. Be sure to follow these instructions and warnings.

    If you have any enquiries, please contact your local importer, distributor and/or retailer.

    Specifications, designs and other content appearing in this brochure are current as of April 2011 but subject to change without notice.

    JMI-0107 JQA-1452

    Organization:DAIKIN INDUSTRIES, LTD.AIR CONDITIONING MANUFACTURING DIVISION

    Scope of Registration:THE DESIGN/DEVELOPMENT AND MANUFACTURE OF COMMERCIAL AIR CONDITIONING, HEATING, COOLING, REFRIGERATING EQUIPMENT, COMMERCIAL HEATING EQUIPMENT, RESIDENTIAL AIR CONDITIONING EQUIPMENT, HEAT RECLAIM VENTILATION, AIR CLEANING EQUIPMENT, MARINE TYPE CONTAINER REFRIGERATION UNITS, COMPRESSORS AND VALVES.