pcs-9830b x instruction manual en domestic general x r1.05

Upload: arief-sandy-anggoro

Post on 28-Feb-2018

382 views

Category:

Documents


44 download

TRANSCRIPT

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    1/164

    PCS-9830B

    Switching ControllerInstruction Manual

    NR Electric Co., Ltd.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    2/164

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    3/164

    Preface

    PCS-9830B Switching Control l er I

    Date: 2015-02-15

    Preface

    Introduction

    This guide and the relevant operating or service manual documentation for the equipment provide

    full information on safe handling, commissioning and testing of this equipment.

    Documentation for equipment ordered from NR Electric Co., Ltd. is dispatched separately from

    manufactured goods and may not be received at the same time. Therefore this guide is provided

    to ensure that printed information normally present on equipment is fully understood by the

    recipient.

    Before carrying out any work on the equipment, the user should be familiar with the contents of

    this manual and read relevant chapters carefully.

    This chapter describes the safety precautions recommended when using the equipment. Before

    installing and using the equipment, this chapter must be thoroughly read and understood.

    Health and Safety

    The information in this chapter of the equipment documentation is intended to ensure that

    equipment is properly installed and handled in order to maintain it in a safe condition.

    When electrical equipment is in operation, dangerous voltages will be present in certain parts of

    the equipment. Failure to observe warning notices, incorrect use, or improper use may endanger

    personnel and equipment and cause personal injury or physical damage.

    Before working in the terminal strip area, the equipment must be isolated.

    Proper and safe operation of the equipment depends on appropriate shipping and handling,

    proper storage, installation and commissioning, and on careful operation, maintenance and

    servicing. For this reason only qualified personnel may work on or operate the equipment.

    Qualified personnel are individuals who:

    Are familiar with the installation, commissioning, and operation of the equipment and of the

    system to which it is being connected;

    Are able to safely perform switching operations in accordance with accepted safety

    engineering practices and are authorized to energize and de-energize equipment and to

    isolate, ground, and label it;

    Are trained in the care and use of safety apparatus in accordance with safety engineering

    practices;

    Are trained in emergency procedures (first aid).

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    4/164

    Preface

    PCS-9830B Sw itching Control lerII

    Date: 2015-02-15

    Instructions and Warnings

    The following indicators and standard definitions are used:

    DANGER means that death, severe personal injury, or considerable equipment damage willoccur if safety precautions are disregarded.

    WARNING means that death, severe personal injury, or considerable equipment damage could

    occur if safety precautions are disregarded.

    CAUTION means that light personal injury or equipment damage may occur if safety

    precautions are disregarded. This particularly applies to damage to the device and to

    resulting damage of the protected equipment.

    WARNING!

    The firmware may be upgraded to add new features or enhance/modify existing features, please

    make sure that the version of this manual is compatible with the product in your hand.

    WARNING!

    During operation of electrical equipment, certain parts of these devices are under high voltage.

    Severe personal injury or significant equipment damage could result from improper behavior.

    Only qualified personnel should work on this equipment or in the vicinity of this equipment. These

    personnel must be familiar with all warnings and service procedures described in this manual, as

    well as safety regulations.

    In particular, the general facility and safety regulations for work with high -voltage equipment must

    be observed. Noncompliance may result in death, injury, or significant equipment damage.

    DANGER!

    Never allow the current transformer (CT) secondary circuit connected to this equipment to be

    opened while the primary system is live. Opening the CT circuit will produce a dangerously high

    voltage.

    WARNING!

    Exposed terminals

    Do not touch the exposed terminals of this equipment while the power is on, as the high

    voltage generated is dangerous.

    Residual voltage

    Hazardous voltage can be present in the DC circuit just after switching off the power supply. It

    takes a few seconds for the voltage to discharge.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    5/164

    Preface

    PCS-9830B Switching Control l er III

    Date: 2015-02-15

    CAUTION!

    Earthing

    The earthing terminal of the equipment must be securely earthed.

    Operating environment

    The equipment must only be used within the range of ambient environment detailed in the

    specification and in an environment free of abnormal vibration.

    Ratings

    Before applying AC voltage and current or the power supply to the equipment, check that they

    conform to the equipment ratings.

    Printed circuit board

    Do not attach and remove printed circuit boards when the power supply to the equipment is

    on, as this may cause the equipment to malfunction.

    External circuit

    When connecting the output contacts of the equipment to an external circuit, carefully check

    the supply voltage used in order to prevent the connected circuit from overheating.

    Connection cable

    Carefully handle the connection cable without applying excessive force.

    Typographic and Graphical Conventions

    The following symbols are used in drawings:

    Input signal of a function block, such as a logic setting, a blocking

    signal or a analog comparator signal etc.

    Input inversion signal of a function block, such as a logic setting,

    a blocking signal or a analog comparator signal etc.

    &

    AND gate: all the input signals are 1, then the output is 1

    OR gate: anyone the input signals is 1, then the output is 1

    S Q

    R Q

    RS flipflop (static memory): setting input (S), resetting input (R),

    output (Q) and inverted output (Q)

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    6/164

    Preface

    PCS-9830B Sw itching Control lerIV

    Date: 2015-02-15

    t 0

    Timer: pickup with delay t, dropout without delay

    0 t

    Timer: pickup without delay, dropout with delay t

    t1 t2

    Timer: pickup with delay t1, dropout with delay t2

    Junction (connection point)

    Copyright 2015 NR. All rights reserved.

    We reserve all rights to this document and to the information contained herein. Improper use in particular reproduction and di ssemina tion

    to third parties is strictl y fo rbidden except where expressly authorized.

    The info rmation in this manual is carefully checked periodically, and necessary corrections will be included in future editions. If

    nevertheless any errors are detected, suggestions for correction or improvement are greatly appreciated.

    We reserve the rights to make technical improvements without notice.

    NR ELECTRIC CO., LTD.

    Headquarters: 69, Suyuan Avenue, Jiangning, Nanjing 211102, China

    Manufactory: 18, Xinfeng Road, Jiangning, Nanjing 211111, China

    Tel: +86-25-87178888

    Fax: +86-25-87178999

    Website: www.nrelect.com, www.nrec.com

    P/N: ZL_PCS-9830B_X_Instruction Manual_EN_Domestic General_X Version: R1.05

    http://www.nrelect.com/http://www.nrelect.com/http://www.nrec.com/http://www.nrec.com/http://www.nrec.com/http://www.nrec.com/http://www.nrelect.com/
  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    7/164

    Preface

    PCS-9830B Switching Control l er V

    Date: 2015-02-15

    Documentation Structure

    The manual provides a functional and technical description of this device and a comprehensive

    set of instructions for the devices use and application.

    The chapter contents are summarized as below:

    1 Introduction

    Briefly introduce the application, functions and features about this device.

    2 Technical Data

    Introduce the technical data about this device, such as electrical specifications, mechanical

    specifications, ambient temperature and humidity range, communication port parameters, type

    tests, setting ranges and accuracy limits and the certifications that our products have passed.

    3 Operation Theory

    Introduce a comprehensive and detailed functional description of this device.

    4 Supervision

    Introduce the automatic self-supervision function of this device.

    5 Hardware

    Introduce the main function carried out by each module of this device and providing the definition

    of pins of each module.

    6 Settings

    List of all the settings and their ranges and step sizes, together with a brief explanation of each

    setting and some notes about the setting application.

    7 Human Machine Interface

    Introduce the hardware of the human machine interface (HMI) module and a detailed guide for the

    user how to use this device through the HMI. It also lists all the information which can be view

    through the HMI, such as settings, all kinds of reports etc.

    8 Installation

    Introduce the recommendations on unpacking, handling, inspection and storage of this device. A

    guide to the mechanical and electrical installation of this device is also provided, incorporating

    earthing recommendations.

    9 Commissioning

    Introduce how to commission this device, comprising checks on the calibration and functionality of

    this device.

    10 Maintenance

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    8/164

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    9/164

    1 Introduct ion

    PCS-9830B Switching Control ler 1-aDate: 2015-02-15

    1 Introduction

    Table of Contents

    1.1 Application.....................................................................................................................1-1

    1.2 Functions .......................................................................................................................1-2

    1.2.1 Controlled Switching Function .......................................................................................... 1-2

    1.2.2 Auxiliary and Management Functions............................................................................... 1-2

    1.3 Features..........................................................................................................................1-2

    List of Figures

    Figure 1.1-1 Typical application of PCS-9830B ..................................................................... 1-1

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    10/164

    1 Introduct i on

    PCS-969830B Swi tchin g Control l er1-bDate: 2015-02-15

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    11/164

    1 Introduct ion

    PCS-9830B Switching Control ler 1-1Date: 2015-02-15

    1.1 Application

    In power system, the traditional random switching mode of circuit breakers will generate inevitably

    over-voltage, inrush current, electromagnetic transient effect and so on, affect insulation and life of

    equipment, and even induce protection malfunction. The CS (Controlled Switching, abbreviated

    CS), as the ideal solution to solve the above problems, is a method of making circuit breaker close

    or open at the optimum time instant. When switching no-load line, no-load transformers,

    capacitors, reactors and other equipments, the CS can greatly reduce overvoltage as well as

    inrush current during energizing and de-energizing operations, thus eliminating harmful electrical

    transients to the electrical equipment and the power system, extending the life of electrical

    equipment and improving the stability of the power system.

    The typical application of this device is show in following figures.

    Controlled close

    Open command

    Analog quantity detection

    (current or voltage)

    Sensor signalControl system

    Close command

    The reference voltage

    Controlled open

    The

    controlled

    device

    Busbar at

    source side

    PCS-9830

    VT

    VT

    CT

    CT

    CT

    A B C

    Figure 1.1-1 Typical application of PCS-9830B

    The PCS-9830B switching controller needs the input of the reference voltage used to determine

    the controlled phase, and it usually selects the VT of circuit breaker busbar at source side as the

    reference voltage. The input analog quantity detection of the controlled side is used as the criteria

    whether the switching is finished. The binary inputs that the device needs are mainly close

    commands and open commands of control system. The output contacts of controlled close and

    controlled open are connected to the closing and opening circuits of breaker respectively, and it

    can configure two sets of output module when matching circuit breaker with double jump rings.

    Moreover, the device supports the sensor signal inputs, which are used to achieve real-time

    monitoring of ambient temperature, control voltage, phase oil pressure, phase SF6gas pressure

    and other external parameters, compensating for the influence of the parameters on the circuit

    breaker operating time.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    12/164

    1 Introduct i on

    PCS-969830B Swi tchin g Control l er1-2Date: 2015-02-15

    1.2 Functions

    1.2.1 Controlled Switching Function

    Controlled closing function

    Controlled opening function

    Compensation based on system frequency

    Real-time compensation based on ambient temperature

    Real-time compensation based on control voltage

    Real-time compensation based on oil pressure of each phase hydraulic mechanism of circuit

    breaker

    Real-time compensation based on gas pressure of each phase SF6circuit breaker

    Real-time compensation based on circuit breaker idle time

    Real-time compensation based on cumulative operation number of circuit breaker

    Self-adaptive function based on analog quantity detection

    One set of device is able to realize controlled switching of circuit breaker of loads with

    different characteristics and realize two sets of target phase angle control functions in one unit

    Automatically determine the reference side, controlled side and the current target phase

    1.2.2 Auxiliary and Management Functions

    Reference voltage abnormality monitoring

    Sensors abnormality monitoring

    Operating characteristics monitor of circuit breaker

    Hardware failure alarm

    Event SOE records, etc.

    PC debugging and disturbance recording

    1.3 Features

    Real-time compensation and self-adaptive function

    This device is equipped with complete real-time compensation function, such as ambient

    temperature, control voltage, each phase oil pressure, each phase SF 6 gas pressure and

    other external parameters, and in the self-adaptive mode the compensation function also can

    be put into. In addition, the device can automatically record the parameter values of the latest

    operation and compare it with the real-time values of the current operation, so gets the

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    13/164

    1 Introduct ion

    PCS-9830B Switching Control ler 1-3Date: 2015-02-15

    compensation values of this time and compensates it. Moreover, the device has the

    compensation based on circuit breaker idle time and cumulative operation number of circuit

    breaker, reducing the affect of the above factors on the mechanical properties of the circuit

    breaker.

    Automatically select the reference voltage and the charge direction

    In double-busbar connection, it can automatically select the reference voltage according to

    the auxiliary binary inputs, and in 3/2 busbar connection, it can automatically select the

    reference voltage and the charge direction according to the auxiliary bina ry inputs and voltage

    criteria to make it more intelligent.

    Controlled switching of circuit breaker of loads with different characteristics using a single

    device

    The device is equipped two sets of setting for different closing and opening targets and the

    settings can be set independently. As an example, for the two-direction control of the middle

    circuit breaker in the 3/2 busbar connection, one PCS-9830B can finish the two-direction

    control of controlled closing and controlled opening, more flexibly and adaptively.

    Cooperates with synchronism closing operation

    If the control system sends a synchronism closing command, this device can automatically

    detect whether the VT voltage of the controlled side is alive; if any phase voltage of the

    controlled side is alive, this device will output closing pulse after it receives closing command.

    Supports control circuit breaker with phase-segregated mechanism or three-phase

    combination mechanism

    This device can support different types of circuit breaker mechanism through a relevant

    setting. To the circuit breaker with phase-segregated mechanism, the control logic for each

    phase is independent; and to the circuit breaker with three-phase combination mechanism,

    the control logic for phase A is used to control the circuit breaker, and the relevant settings

    about phase B and phase C will be inactive and hidden.

    Output circuit design of combination of IGBT and relay

    IGBT can achieve rapid control and discreteness of operation time is almost negligible.

    High-performance general-purpose hardware and real-time calculations

    Hardware structure of 32-bit DSP+ARM microprocessors is adopted. DSP is responsible of

    logic calculation and logic output, and ARM is in charge of event and disturbance recording,

    HMI, communication, and printing etc. High performance hardware ensures real-time

    calculation for all functions in each sampling interval of this device. This device adopts 32-bit

    high performance CPUs and DSPs, internal high-speed bus, and intelligent I/O. Both

    hardware and software adopt modular design, which can be flexibly configured. Features

    include versatility, easy expansion, and easy maintenance.

    Modular programs

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    14/164

    1 Introduct i on

    PCS-969830B Swi tchin g Control l er1-4Date: 2015-02-15

    Modular programs allow flexible protection configuration and easy functional adjustment.

    Strong EM compatibility

    Integral panel and fully enclosed chassis are adopted. Strong electricity and weak electricity

    are strictly separated. Traditional rear board wiring mode is not used. At the same time,

    measures against interference are taken in software design, greatly improving the immunity to

    disturbances. Outwards EM radiation satisfies relevant standards.

    Easy commissioning and maintenance

    Friendly HMI and convenience testing capabilities is provided.

    Powerful communication function

    Flexible communication mode is provided. Up to 4 independent Ethernet interfaces, up to 2

    independent RS-485 communication interfaces and 1 RS-232 print interface are provided.

    Multiple time synchronization methods are optional

    Complete event recording function

    At least 128 faults and operation sequence, 128 fault waveforms, results of 1024

    self-supervision reports, and 1024 binary signal change reports can be recorded.

    Auxiliary PC software

    PC auxiliary software is supported in Windows 9X/Me/2000/NT/XP, Vista, and Win7 operating

    system, being user-friendly and easy to device setup and commissioning on site. Waveform

    analysis software can provide detailed analog quantity and binary signal change information

    during controlled switching, facilitating the analysis of the controlled opening and closing

    process.

    Support both AC and DC power supply

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    15/164

    2 Technical Data

    PCS-9830B Switching Control ler 2-aDate: 2015-02-15

    2 Technical Data

    Table of Contents

    2.1 General Specification .................................................................................................2-1

    2.1.1 Electrical Specifications ................................................................................................... 2-1

    2.1.2 Mechanical Specifications ................................................................................................ 2-2

    2.1.3 Ambient Temperature and Humidity ................................................................................. 2-3

    2.1.4 Communication Interfaces ............................................................................................... 2-3

    2.1.5 Type Test ......................................................................................................................... 2-4

    2.2 Management Functions..............................................................................................2-6

    2.2.1 Clock Performance .......................................................................................................... 2-6

    2.2.2 Wave Recording .............................................................................................................. 2-6

    2.2.3 Binary Input Signal........................................................................................................... 2-6

    2.3 Certification ...................................................................................................................2-6

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    16/164

    2 Technical Data

    PCS-9830B Switching Control ler2-bDate: 2015-02-15

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    17/164

    2 Technical Data

    PCS-9830B Switching Control ler 2-1Date: 2015-02-15

    2.1 General Specification

    2.1.1 Electrical Specifications

    2.1.1.1 Power Supply

    Standard IEC60255-11: 2008

    Rated voltage 24Vdc, 48Vdc, 110Vdc, 220Vdc, 24Vac, 48Vac, 110Vac, 220Vac

    Variation 80% ~ 120%

    Permissible ripple voltage Max 15% of the rated voltage (DC power supply)

    Burden< 15W @ Quiescent condition

    < 20W @ Operating condition

    2.1.1.2 Analog Current Input Ratings

    Phase rotation ABC

    Rated frequency (fn) 50Hz

    Rated current (In) 1A 5A

    Linear to 30In 30In

    Thermal

    withstand

    capability

    continuously 3In 3In

    for 10s 30In 30In

    for 1s 100In 100In

    for half a cycle 250In 250In

    Burden (@ In) < 0.15VA/phase < 0.25VA/phase

    2.1.1.3 Analog Voltage Input Ratings

    Phase rotation ABC

    Rated frequency (fn) 50Hz

    Rated voltage (Un) 100V ~ 130V (phas e-to-phase voltage)

    Linear to 130V

    Thermal

    withstand

    capability

    continuously 130V

    10s 200V

    1s 250V

    Burden < 0.10VA / phase

    2.1.1.4 Binary Input

    Rated voltage 24V 48V 110V 220V

    Rated current 1.20mA 2.40mA 1.10mA 2.20mA

    Pickup voltage 55% ~ 70% rated voltage

    ONvalue voltage 70% ~ 120% rated voltage

    OFFvalue voltage < 50% rated voltage

    Maximum permitted voltage 120% rated voltage

    High voltage withstand 2000Vac, 2800VdcResolving time for logic input < 1ms

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    18/164

    2 Technical Data

    PCS-9830B Switching Control ler2-2Date: 2015-02-15

    2.1.1.5 Binary Output

    Relay contact output

    Output model Potential-free contact

    Max system voltage 380Vac, 250Vdc

    Voltage across open contact 1000V RMS for 1min

    Continuous carry 5.0A @ 380Vac, 5.0A @ 250Vdc

    Short duration current 6A for 3000ms, 15A for 500ms , 30A for 200ms

    Breaking capacity

    0.65A @ 48Vdc, L/R=40ms

    0.30A @ 110Vdc, L/R=40ms

    0.15A @ 220Vdc, L/R=40ms

    Pickup time < 8ms

    Dropout time < 5ms

    Bounce time 1ms

    Durability loaded contact 10,000 operations minimum

    unloaded contact 20,000 operations minimum

    IGBT output

    Output purpose For tripping or closing

    Output model Potential-free contact

    Max system voltage 600Vdc

    Continuous carry 10A

    The reverse polarity of the IGBT is not permitted.

    2.1.1.6 Transducer Input

    Standard IEC 60255-1:2009

    Input range 4~20mA 0~5V

    Input resistance 235 4.4k

    Accuracy class 0.5 class 0.5

    2.1.2 Mechanical Specifications

    Enclosure dimensions See Figure 8.6-1

    Trepanning dimensions See Figure 8.6-1, M6 screw

    Mounting way Flush mounted

    Weight per device Approx. 9.0kg (fully equipped)

    Local control panel Small control module: a 240128-dot LCD, a 9-key keypad and 20 LEDs

    Display language Optional: Chinese, English

    Housing material Aluminum

    Housing color Silver grey

    Location of terminals Rear panel of the device

    Protection class IEC60225-1: 2009

    Front side: IP40

    Rear side, connection terminals: IP30

    Other Sides: IP50

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    19/164

    2 Technical Data

    PCS-9830B Switching Control ler 2-3Date: 2015-02-15

    2.1.3 Ambient Temperature and Humidity

    Standard IEC60225-1: 2009

    Operating temperature range -40C ~ +70C (for the LCD -20C ~ +70C)

    Transport and storage temperature range -40C ~ +70C

    Permissible humidity 5% ~ 95%, condensation not permissible

    Altitude < 3000m

    2.1.4 Communication Interfaces

    2.1.4.1 Ethernet Port for RTU/SCADA

    Medium Parameters

    Ethernet

    Electrical

    Port number 2 or 4

    Connector type RJ-45

    Transmission rate 100Mbits/s

    Transmission standard 100Base-TX

    Transmission distance < 100m

    Protocol IEC60870-5-103:1997 or IEC61850

    Safety level Isolation to ELV level

    Optical

    Port number 0 or 2

    Optical fiber and connector Glass fiber, Multi-mode, ST

    Transmission rate 100Mbits/s

    Transmission standard 100Base-FX

    Wave length 1300nm

    Transmission distance < 2000m

    Minim um transmission power -20dBm

    Reception sensitivity -30dBm

    Protocol IEC60870-5-103:1997 or IEC61850

    2.1.4.2 Serial Port for RTU/SCADA

    Medium Parameters

    RS-485 (EIA)

    Port number 0 or 2

    Baud rate 4800 ~ 115200bps

    Transmission distance < 1000m @ 4800bps

    Maximal capacity 32

    Protocol IEC60870-5-103:1997

    Safety level Isolation to ELV level

    2.1.4.3 Serial Port for Printer

    Medium Parameters

    RS-232 (EIA)

    Port number 1

    Baud rate 4800 ~ 115200bps

    Printer type EPSON

    LQ-300K

    Safety level Isolation to ELV level

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    20/164

    2 Technical Data

    PCS-9830B Switching Control ler2-4Date: 2015-02-15

    2.1.4.4 Serial Port for Time Synchronization

    Medium Parameters

    RS-485 (EIA)

    Port number 1

    Transmission distance < 500m

    Maximal capacity 32

    Timing standard PPS, IRIG-B

    Safety level Isolation to ELV level

    2.1.4.5 Ethernet Port for Debugging

    Medium Parameters

    Electrical Ethernet

    (in front panel)

    Port number 1

    Connector type RJ-45

    Transmission rate 100Mbits/s

    Transmission standard 100Base-TX

    Transmission distance < 100m

    Safety level Isolation to ELV level

    2.1.5 Type Test

    2.1.5.1 Environmental Tests

    Dry cold test IEC60068-2-1: 2007, 16h at -25C

    Dry heat test IEC60068-2-2: 2007, 16h at +55C

    Damp heat test IEC60068-2-78: 2001, 10 days, 93%RH, +55C

    Cyclic temperature with

    humidity test

    IEC60068-2-30: 2005, six (12+12hours) cycles , 95%RH,

    low temperature +25C, high temperature +55C

    2.1.5.2 Electrical Tests

    Dielectric test IEC60255-27: 2005, test voltage: 2kV, 50Hz, 1min

    Impulse voltage testIEC60255-5: 2000, test voltage: 5kV, unipolar impulses, waveform 1.2/50s,

    source energy 0.5J

    Overvoltage category IEC60255-5: 2000, Class III

    Insulation measurement IEC60255-5: 2000, insulation resistance >100M@ 500Vdc

    Pollution degree IEC60225-1: 2009, Class II

    2.1.5.3 Electromagnetic Compatibility

    1MHz burst disturbance tests

    - Common mode

    - Differential mode

    IEC60255-22-1: 2007, Class III

    2.5kV

    1.0kV

    Electrostatic discharge tests

    - For contact discharge

    - For air discharge

    IEC60255-22-2: 2008, Class IV

    8.0kV

    15.0kV

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    21/164

    2 Technical Data

    PCS-9830B Switching Control ler 2-5Date: 2015-02-15

    Radio frequency interference tests

    - Frequency sweep

    - Radiated amplitude-modulated

    - Spot frequency

    - Radiated amplitude-modulated

    - Radiated pulse-modulated

    IEC60255-22-3: 2007, Class III

    10V/m(RMS), f=801000MHz

    10Vm(RMS), f=80/160/450/900MHz

    10Vm(RMS), f=900MHz

    Fast transient disturbance tests

    - Power supply, I/O & Earth terminals

    - Communication terminals

    IEC60255-22-4: 2008, Class IV

    4kV, 2.5kHz, 5/50ns

    2kV, 5.0kHz, 5/50ns

    Surge immunity tests

    - Power supply, AC inputs, I/O terminals

    IEC60255-22-5: 2008, Class IV

    1.2/50us,

    4kV, line-to-ground

    2kV, line-to-line

    Conducted RF electromagnetic disturbance

    - Power supply, AC, I/O, Comm. terminals

    IEC60255-22-6: 2001, Class III

    10V(RMS), 150kHz~80MHz

    Power frequency field immunity IEC60255-22-7: 2003, Class A

    10s

    300V, line-to-ground

    150V, line-to-l ine

    Conducted emission limits IEC60255-25: 2000, Class A

    Radiated emission limits IEC60255-25: 2000, Class A

    Auxiliary power supply performance

    - Voltage dips

    - Voltage short interruptions

    IEC60255-11: 2008

    Up to 200ms for dips to 40% of rated voltage

    without reset30ms for interruption without rebooting

    Power frequency magnetic field immunity IEC61000-4-8: 2001, Class V

    100A/m for 1min

    1000A/m for 3s

    Pulse magnetic field immunity IEC61000-4-9: 2001, Class V

    6.4/16us, 1000A/m for 3s

    Damped oscillatory magnetic field immunity IEC61000-4-10: 2001, Class V

    100kHz & 1MHz100A/m

    Ring wave immunity

    - Power supply, I/O terminals

    IEC61000-4-12: 2006, Class III

    1MHz

    2kV, line-to-ground

    1kV, line-to-line

    2.1.5.4 Mechanical Tests

    Vibration test IEC60255-21-1:1988, Class I

    Shock test IEC60255-21-2:1988, Class I

    Bump test IEC60255-21-2:1988, Class I

    Seismic test IEC60255-21-3:1988, Class I

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    22/164

    2 Technical Data

    PCS-9830B Switching Control ler2-6Date: 2015-02-15

    2.2 Management Functions

    2.2.1 Clock Performance

    Real time clock accuracy 3s/day

    Accuracy of GPS synchronization 1ms

    External time synchronization IRIG-B (200-98), PPS, SNTP protocol

    2.2.2 Wave Recording

    Maximum duration 15 cycles , cover all the operation process

    Recording position 1 cycles before pickup of trigger element

    2.2.3 Binary Input Signal

    Resolution of binary input signal 1ms

    Binary input mode Potential-free contact

    Resolution of SOE 2ms

    2.3 Certification

    ISO9001: 2008

    ISO14001: 2004

    OHSAS18001: 2007

    ISO10012: 2003

    CMMI L5

    EMC: 2004/108/EC, EN50263: 1999

    Products safety(PS): 2006/95/EC, EN61010-1: 2001

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    23/164

    3 Operat ion Theory

    PCS9830B Switch ing Control ler 3-aDate: 2015-02-15

    3 Operation Theory

    Table of Contents

    3.1 Overview ........................................................................................................................3-1

    3.2 Controlled Switching Control Strategy ..................................................................3-1

    3.3 Controlled Switching Control Theory ....................................................................3-2

    3.3.1 Controlled Closing Process .............................................................................................. 3-2

    3.3.2 Controlled Opening Process ............................................................................................ 3-3

    3.4 Reference Voltage Selection Logic .........................................................................3-4

    3.4.1 Logic for Single-busbar Mode .......................................................................................... 3-4

    3.4.2 Logic for Double-busbar Mode ......................................................................................... 3-4

    3.4.3 Logic for 3/2 Circuit Breaker Mode ................................................................................... 3-5

    3.4.4 Logic for Quadrilateral Wiring Mode ................................................................................. 3-6

    3.4.5 Logic for Line with Shunt Reactor Wiring Mode ................................................................ 3-7

    3.5 Controlled Switching Function ................................................................................3-8

    3.5.1 Real-time Compensation Function ................................................................................... 3-9

    3.5.2 Self-adaptive Compensation Function.............................................................................. 3-9

    3.6 Auxiliary Functions .................................................................................................. 3-10

    3.6.1 Frequency Compensation Function................................................................................ 3-10

    3.6.2 Circuit Breaker Mechanical Characteristic Supervision................................................... 3-10

    3.7 Measurement Functions ..........................................................................................3-11

    List of Figures

    Figure 3.2-1 Example of closing a grounded star wiring capacitor ..................................... 3-2

    Figure 3.3-1 Controlled closing process ............................................................................... 3-2

    Figure 3.3-2 Controlled opening process.............................................................................. 3-3

    Figure 3.4-1 Single-busbar mode........................................................................................... 3-4

    Figure 3.4-2 Double-busbar mode ......................................................................................... 3-5

    Figure 3.4-3 3/2 circuit breaker wiring mode......................................................................... 3-6

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    24/164

    3 Operat ion Theory

    PCS-9830B Switching Control ler3-bDate: 2015-02-15

    Figure 3.4-4 Quadrilateral wiring mode ................................................................................. 3-7

    Figure 3.4-5 Line with shunt reactor wiring mode ................................................................ 3-8

    Figure 3.5-1 Deviation correction self-adaptive control ..................................................... 3-10

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    25/164

    3 Operat ion Theory

    PCS9830B Switch ing Control ler 3-1Date: 2015-02-15

    3.1 Overview

    The PCS-9830B controls the circuit breaker close or open at the optimum time instant related to

    the phase angle via time controlled switching operations, at the same time considering pre -strike

    and arcing characteristics during the closing and opening operation as well as the influence of

    external operating conditions. Taking the measurements, it can greatly reduce transient

    overvoltage and overcurrent during energizing and de-energizing operations, thus extending the

    life of electr ical equipment and improving the stability of the entire power system.

    The PCS-9830B provides controlled closing/opening function, real-time compensation and

    self-adaptive function etc.

    3.2 Controlled Switching Control Strategy

    The reasons why the inductive load and capacitive load generate overvoltage or inrush current

    are different, which cause the closing or opening phase position of the circuit breaker are different.

    So it is necessary to adopt different control strategies for different types of loads.

    The closing or opening phase position of the circuit breaker also has relationship with the

    grounded mode of the controlled target object.

    The following table shows the ideal phase angle. Theoretically, if the system phase sequence is

    three-phase positive sequence (A, B, C or B, C, A or C, A, B), the control effect is equivalent. The

    phase angle ofUA

    is taken as reference value.

    Controlled

    equipment

    Grounded

    mode

    Control

    type

    Phase

    A B C

    Transformer

    GroundedClose 90 180 180

    Open 90 30 150

    UngroundedClose 90 0 0

    Open 90 180 180

    Reactor

    GroundedClose 90 30 150

    Open 90 30 150

    Ungrounded Close 90 0 0

    Open 90 180 180

    Capacitor

    (Transmission line)

    GroundedClose 0 120 60

    Open 90 30 150

    UngroundedClose 180 90 90

    Open 90 180 180

    OthersClose User defined User defined User defined

    Open User defined User defined User defined

    In practical application, the closing angle or opening angle can be selected from 0~359

    independently.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    26/164

    3 Operat ion Theory

    PCS-9830B Switching Control ler3-2Date: 2015-02-15

    Takes closing a grounded star wiring (Y) capacitor as an example, the UAis reference value, so

    the settings of the closing angles of the three phases are set as following figure.

    UA zero-cross point

    UA

    0

    T1 UCUB

    36060 120

    System voltage

    UB closing phase angle: 120

    UC closing phase angle: 60UA closing phase angle: 0

    Figure 3.2-1 Example of closing a grounded star wiring capacitor

    3.3 Controlled Switching Control Theory

    3.3.1 Controlled Closing Process

    It is assumed that the closing phase angle of the controlled target is 0, and the closing control

    process is shown in following figure.

    Opened Closing

    Closed

    tReference

    voltage

    TclswaitTclslag

    Tcls

    NT+Tclstarg

    Target closing point

    T0 T1 T2

    T3 T4

    Tpre

    Contact

    touching

    moment

    Closing

    command

    Output closing

    command

    Voltage

    zero-cross

    Sample analog values of controlled side

    Contact

    state

    Closing

    command Pre-breakdown time

    Figure 3.3-1 Controlled closing process

    Where:

    Tclswait= N T + Tclstarg- Tcls- Tclslag+ Tpre

    N is an integer;

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    27/164

    3 Operat ion Theory

    PCS9830B Switch ing Control ler 3-3Date: 2015-02-15

    Tclswait is the waiting time of the controlled closing operation which considers the

    pre-breakdown time;

    T is the period time of the reference voltage;

    Tclstarg

    is the time which is calculated from the target closing phase angle;

    Tclsis the inherent closing time of the circuit breaker;

    Tclslagis the lag time of the closing circuit;

    Tpreis the pre-breakdown time.

    3.3.2 Controlled Opening Process

    It is assumed that the opening phase angle of the controlled target is 90, and the opening control

    process is shown in following figure.

    Closed

    t

    Topnwait

    Topnlag

    Topn

    T0 T1 T2

    T3 T4

    Tarcing

    NT+Topntarg

    Reference

    voltage

    Sample analog values of controlled side

    Closing

    command

    Output opening

    command

    Contact

    separating

    moment

    Arc

    extinction

    moment

    Target opening point

    Arcing

    Opening

    Opened

    Contact

    state

    Opening

    command

    Figure 3.3-2 Controlled opening process

    Where:

    Topnwait= N T + Topntarg- Topn- Topnlag+ Tarcing

    N is an integer;

    Topnwaitis the waiting time of the controlled closing operation which considers the arcing time;

    T is the period time of the reference voltage;

    Topntargis the time which is calculated from the target opening phase angle;

    Topnis the inherent opening time of the circuit breaker;

    Topnlagis the lag time of the opening circuit;

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    28/164

    3 Operat ion Theory

    PCS-9830B Switching Control ler3-4Date: 2015-02-15

    Tarcingis the arcing time.

    3.4 Reference Voltage Selection Logic

    This device can automatically select the reference voltage according to the related criterion. This

    device supports two sets of configurations for predefined target phase angle control operation. If

    the controlled circuit breaker is closed or opened with different load, this device can realize

    automatic selection of two different control strategies.

    If only one phase voltage is inputted, this device can calculate the other two phase voltages

    according to the phase position relationship. This device can input three different reference

    voltages, and this device can automatically select the reference side, the controlled side and the

    target phase angle according to the reference voltage real-time value and the auxiliary contact

    binary input values in different application field.

    This device can support several kinds of reference voltage selection methods.

    3.4.1 Logic for Single-busbar Mode

    In single-busbar mode, the busbar is the No.1 reference side, and any one of three busbar phase

    voltages can be used as reference voltage. The controlled circuit breaker is used to open or close

    the controlled device. Only the target phase angle of the No.1 controlled side needs be set.

    Controlled

    side 1

    Controlled

    device

    PCS-9830B

    Busbar Reference side 1

    Voltage: Ua/Ub/Uc

    Or current: Ia/Ib/Ic

    Controlled CBPhase selection

    control

    Voltage

    Figure 3.4-1 Single-busbar mode

    The setting [Opt_RefVoltMode] should be set as0: SingleBB

    .

    The output mode of this device can be select according to the busbar voltage. If the busbar

    voltage is alive, the controlled switching logic will be in service after this device receives control

    command; otherwise, this device will output control command directly. The side circuit breaker in

    3/2 circuit breaker wiring mode has the same control logic as the single busbar mode.

    3.4.2 Logic for Double-busbar Mode

    In double-busbar mode, the No.1 busbar is the No.1 reference side, and the No.2 busbar is the

    No.2 reference side. And any one of three busbar phase voltages of the two busbars can be used

    as reference voltage respectively. The positions of the two busbar disconnectors are inputted tothis device. Only the target phase angle of the No.1 controlled side needs be set.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    29/164

    3 Operat ion Theory

    PCS9830B Switch ing Control ler 3-5Date: 2015-02-15

    Phase selectioncontrol

    Controlled

    device

    PCS-9830B

    Busbar 2

    Controlled CB

    Busbar 1

    Controlled

    side 1

    DS of BB1 DS of BB2

    Reference side 1 Reference side 2

    Voltage: Ua/Ub/Uc

    Or current: Ia/Ib/Ic

    Figure 3.4-2 Double-busbar mode

    The setting [Opt_RefVoltMode] should be set as 1: DoubleBB.

    The auxiliary contacts of the busbar disconnectors are used to detect the positions of the two

    busbar disconnectors. This device supports single-position (89a or 89b) and double-position (89a

    and 89b) contact inputs.

    The reference voltage is selected according to the positions of the two busbar disconnector s. If

    the No.1 disconnector is closed, the voltage of the No.1 busbar is used as the reference voltage

    preferentially. If the No.1 disconnector is opened but the No.2 disconnector is closed, the voltage

    of the No.2 busbar is used as the reference voltage. If the positions of the two disconnectors are

    abnormal at the same time, the selected reference voltage is kept.

    When the reference voltage has been selected already, if the reference voltage is alive, the

    controlled switching logic will be in service after this device receives control command; otherwise,

    this device will output control command directly.

    If the reference voltage has not been selected, this device will output control command directly if it

    receives control command.

    If the positions of the two disconnectors are opened at the same time, the alarm signal

    [Alm_89b_BB1&BB2] will be issued; and if the positions of the two d isconnectors are closed at the

    same time, the alarm signal [Alm_89a_BB1&BB2] will be issued. If the double-position of the

    busbar disconnector is abnormal, the alarm signal [Alm_89_BB1&BB2] will be issued. These

    signals will be reverted if the abnormal position situation is disappeared.

    Only if the setting [Opt_Mechanism] is set as 0: Single-phase, this mode can be in service.

    3.4.3 Logic for 3/2 Circuit Breaker Mode

    In 3/2 circuit breaker wiring mode, the control of the center circuit breaker has two typical

    operations.

    1. The voltage of the No.1 busbar is alive and the No.1 circuit breaker (CB1) is closed, the No.1

    controlled device is energized or de-energized by controlling the controlled circuit breaker

    (center circuit breaker).

    2. The voltage of the No.2 busbar is alive and the No.2 circuit breaker (CB2) is closed, the No.2

    controlled device is energized or de-energized by controlling the controlled circuit breaker

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    30/164

    3 Operat ion Theory

    PCS-9830B Switching Control ler3-6Date: 2015-02-15

    (center circuit breaker).

    Controlled

    device 1

    PCS-9830B

    Busbar 2

    Controlled CB

    Busbar 1

    Controlleddevice 2Controlledside 2

    CB1

    CB2

    Phase selection

    control

    Reference side 1

    Reference side 2

    Voltage: Ua/Ub/Uc

    Or current: Ia/Ib/Ic

    Voltage: Ua/Ub/Uc

    Or current: Ia/Ib/Ic

    Controlled

    side 1

    Figure 3.4-3 3/2 circuit breaker wiring mode

    And any one of three busbar phase voltages of the two busbars can be used as reference voltage

    respectively. In this mode, this device can control the two controlled device to be energized or

    de-energized respectively. So the target phase angles should be set respectively according to

    load characteristic.

    The setting [Opt_RefVoltMode] should be set as 2: CenterCB.

    The auxiliary contacts of the side circuit breakers are used to detect the positions of the two side

    circuit breakers. This device supports single-position (52a or 52b) and double-position (52a and

    52b) contact inputs.

    The reference voltage is selected according to the positions of the two side circuit breakers. If the

    CB1 is closed and the CB2 is opened or the voltage of the No.2 busbar is dead, the voltage of the

    No.1 busbar is used as the reference voltage. If the CB2 is closed and the CB1 is opened or the

    voltage of the No.1 busbar is dead, the voltage of the No.2 busbar is used as the reference

    voltage. If the positions of the two side circuit breakers are abnormal at the same time, the

    selected reference voltage is kept.

    When the reference voltage has been selected already, if the reference voltage is alive, the

    controlled switching logic will be in service after this device receives control command; otherwise,

    this device will output control command directly.

    If the reference voltage has not been selected, this device will output control command directly if it

    receives control command.

    The double-position of the busbar disconnector is abnormal, the alarm signal [Alm_52_SideCB]

    will be issued. This signal will be reverted if the abnormal position situation is disappeared.

    If a fixed control operation is adopted, the reference voltage selection logic is same as the single

    busbar mode. For example, if only the No.1 controlled device needs to be controlled through the

    center circuit breaker, the voltage of the No.2 busbar can be used as reference voltage.

    3.4.4 Logic for Quadrilateral Wiring Mode

    In quadrilateral wiring mode, to the controlled device of the No.1 controlled side, it needs that the

    No.1 controlled circuit breaker (CB1) and the No.2 controlled circuit breaker (CB2) should be

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    31/164

    3 Operat ion Theory

    PCS9830B Switch ing Control ler 3-7Date: 2015-02-15

    configured with a PCS-9830B respectively.

    Take the PCS-9830B which is configured for the CB1 as an example, the voltages (phase

    voltages) of the No.1 reference side, the No.2 reference side and the No.3 reference side need to

    be inputted to this device. The controlled device is energized or de-energized by controlling the

    CB1. Only the target phase angle of the No.1 controlled side needs to be set.

    Controlled

    device

    PCS-9830B

    PCS-9830B

    Line 3

    Line 1

    Line 2

    Phase

    selection

    control

    Controlled CB 1

    Controlled

    side 1

    Reference side 2

    Reference side 1

    Reference side 3

    Controlled

    CB 2

    Voltage: Ua/Ub/Uc

    Or current: Ia/Ib/Ic

    Figure 3.4-4 Quadrilateral wiring mode

    The setting [Opt_RefVoltMode] should be set as 3: Quad.

    The reference voltage is selected from the three reference sides. The selection sequence is from

    the No.1 reference side to the No.3 reference side.

    When the reference voltage has been selected already, if the reference voltage is alive, the

    controlled switching logic will be in service after this device receives control command; otherwise,

    this device will output control command directly.

    Only if the setting [Opt_Mechanism] is set as 0: Single-phase, this mode can be in service.

    3.4.5 Logic for Line with Shunt Reactor Wiring Mode

    In the line with shunt reactor wiring mode, if an independent circuit breaker is configured for the

    shunt reactor, the PCS-9830B needs to select the reference voltage according to the position of

    the shunt reactor circuit breaker, the positions of the line switches and the operation state of the

    busbars.

    The reference voltages (phase voltages) of the No.1 reference side, the No.2 reference side and

    the No.3 reference side need to be inputted to this device. The No.1 controlled side is controlled

    by closing or opening the circuit breaker (Controlled CB). Only the target phase angle of the No.1

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    32/164

    3 Operat ion Theory

    PCS-9830B Switching Control ler3-8Date: 2015-02-15

    controlled side needs to be set. The voltage or current signal of the No.1 controlled side is used to

    decide the closing or opening point.

    PCS-9830B

    Busbar 1

    CB3

    Busbar 2

    Controlled

    side 2

    CB2

    CB1

    Phase selection

    control

    Reference side 2

    Reference side 1

    Voltage: Ua/Ub/Uc

    Or current: Ia/Ib/Ic

    Controlled

    CB

    Shunt

    Reactor

    Controlled side 1

    Line

    Switch

    Reference side 3

    Figure 3.4-5 Line with shunt reactor wiring mode

    The setting [Opt_RefVoltMode] should be set as 4: LineReactor.

    The states of the circuit breakers (CB1, CB2 and CB3) and the states of the line switches are also

    inputted to this device. This device can support normal open contact, normal close contact and

    double-position contact.

    If the switch of the line is closed and the line voltage is alive, the voltage of the No.3 reference side

    is selected as reference voltage preferentially. When the switch of the line is opened, if the circuit

    breaker CB1 is closed and the voltage of the No.1 busbar is alive, the voltage of the No.1

    reference side is selected as reference voltage preferentially. When the switch of the line is

    opened, if the circuit breakers CB2and CB3are closed and the voltage of the No.2 busbar is

    alive, the voltage of the No.2 reference side also can be selected as reference voltage.

    When the reference voltage has been selected already, if the reference voltage is alive, the

    controlled switching logic will be in service after this device receives control command; otherwise,

    this device will output control command directly.

    Only if the setting [Opt_Mechanism] is set as 0: Single-phase, this mode can be in service.

    3.5 Controlled Switching Function

    This device provides complete controlled switching function: real-time compensation function and

    self-adaptive compensation function. If the real-time compensation function is enabled, this device

    can execute the controlled switching logic control according to predefined closing or opening time

    settings. If the self-adaptive compensation function is enabled, this device can continually correct

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    33/164

    3 Operat ion Theory

    PCS9830B Switch ing Control ler 3-9Date: 2015-02-15

    the deviation of target point according to the recent operation deviation, and the correction

    amplitude can be configured by setting related parameters. The compensation function related

    the parameters of temperature, control voltage, SF6 gas pressure, oil pressure, idle time and

    operation number etc. can be enabled or disabled flexibly.

    To achieve precise control and desired results, the dispersion and stability of the inherent

    operation time of the circuit breaker mechanism is an important factor, and the dispersions of the

    pre-breakdown time and arcing time have effect to the final control results. Therefore, it is

    important to obtain the true and accurate time parameters and configure them reasonably.

    3.5.1 Real-time Compensation Function

    Real-time compensation function without deviation correction of external parameters

    In this mode, the impacts of temperature, control voltage, energy storage level and SF 6gas

    pressure etc. to the operation time of the circuit breaker are

    ignored by disabling the related

    settings in this device. See Section3.3for the details about the control process.

    Real-time compensation function with deviation correction of external parameters

    The operation time of the circuit breaker mechanism with the tiny changes of the parameters

    of temperature, control voltage, oil pressure, SF6 gas pressure, idle time and operation

    number etc. This device can sample these analog values to calculate the deviation of the

    operation time. Then the operation time can be corrected on the basis of the deviation.

    This device provides 8 analog sensors for sampling temperature, control voltage, three phase

    oil pressures of circuit breaker and there phase SF6gas pressures. The statistics of idle time

    and operation number can be automatically countered in this device.

    3.5.2 Self-adaptive Compensation Function

    Self-adaptive compensation function without deviation correction of external parameters

    This device can automatically detect the operation finished instant of circuit breaker

    according to the sudden change of the feedback signals, and record the operation time of

    each phase. If the self-adaptive compensation function is enabled, this device can

    automatically correct the deviation in next operation according to the finished operation

    records to improve the precision of next operation.

    The deviation correction mode of the self-adaptive compensation function can be set freely

    through the settings [K_Calbr_Cls] and [K_Calbr_Opn].

    Take the voltage zero-cross closing operation as an example, on the assumption that the

    latest closing moment t2is after the target phase angle and the closing time is not changed,

    if the setting [K_Calbr_Cls] is set as 0.5, the expected closing moment is t1(the current

    deviation is half of last one); if the setting [K_Calbr_Cls] is set as 0.0, the expected closing

    moment is t0; and if the setting [K_Calbr_Cls] is set as 1.0, the expected closing moment

    is still t2.

    Because this device has no history operation record when it is in service at first time, the

    controlled switching logic will be executed according to predefined settings.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    34/164

    3 Operat ion Theory

    PCS-9830B Switching Control ler3-10Date: 2015-02-15

    System voltage

    Predefined target

    closing point

    Last practical

    closing point

    Expected next closing point

    (K_Calbr_Cls = 0.5)

    Expected next closing point

    (K_Calbr_Cls = 1.0)

    Expected next closing point

    (K_Calbr_Cls = 0.0)

    Feedback signals

    t0 t1 t2

    Figure 3.5-1 Deviation correction self-adaptive control

    Self-adaptive compensation function with deviation correction of external parameters

    The deviation correction function is supported in self-adaptive compensation mode. This

    device can record previous operation deviation and external parameter values. It can correct

    the deviation according to the related deviation correction setting in current operation. To

    expectantly correct the operation time of the circuit breaker as expectation, this device

    calculates the compensation value due to the changes of the external parameters in two

    adjacent closing or opening operations by comparing the real-time values and history values

    of the external parameters.

    3.6 Auxiliary Functions

    3.6.1 Frequency Compensation Function

    If the frequency compensation function is enabled, this device will correct each phase waiting time

    value according to the time period of the reference voltage and the target phase angle by

    monitoring the frequency of the reference voltage. By this way, this device can compensate

    control error due to the frequency fluctuation of system voltage.

    3.6.2 Circuit Breaker Mechanical Characteristic Supervision

    This device gets the operation information of the controlled circuit breaker according to the

    feedback signals of the controlled side, and automatically records the operation characteristic of

    the controlled circuit breaker or supervises the necessary circuit breaker characteristic in each

    control operation to present the abnormal situation in the operation period of circuit breaker.

    In normal situation, the operation time difference of a certain phase of the circuit breaker is within

    a definite time period. This device can monitor the operation time difference, and if it detects that

    the operation time difference (between the current operation time and the predefined reference

    value) is greater than the predefined setting, a related alarm signal will be issued

    ([Alm_ClsTimeDiffx] or [Alm_OpnTimeDiffx], x: A, B or C).

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    35/164

    3 Operat ion Theory

    PCS9830B Switch ing Control ler 3-11Date: 2015-02-15

    The three-phase operation time difference of the circuit breaker should be within a definite time

    period. If this device detects the three-phase operation time difference is greater than the

    predefined setting, a related alarm signal will be issued ([Alm_ClsTimeDiff3P] or

    [Alm_OpnTimeDiff3P]).

    If the compensation function of the external parameters is enabled, this device will calculate the

    compensation value of the operation time of the circuit breaker due to these external parameters.

    If the calculated compensation value is greater than the predefined setting, a related alarm signal

    will be issued ([Alm_ExtVarCompTime_Cls] or [Alm_ExtVarCompTime_Opn]).

    3.7 Measurement Functions

    This device can sample the single-phase voltages of the No.1, No.2 and reference sides, and the

    three-phase voltages and currents of the No.1 and No.2 controlled sides. It also can measure the

    real-time frequency.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    36/164

    3 Operat ion Theory

    PCS-9830B Switching Control ler3-12Date: 2015-02-15

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    37/164

    4 Su pervis ion

    PCS-9830B Switching Control ler 4-aDate: 2015-02-15

    4 Supervision

    Table of Contents

    4.1 Overview ........................................................................................................................4-1

    4.2 Supervision Functions ...............................................................................................4-1

    4.2.1 Device Hardware Supervision .......................................................................................... 4-1

    4.2.2 Board Configuration Error Supervision ............................................................................. 4-1

    4.2.3 Setting Supervision .......................................................................................................... 4-1

    4.2.4 Time Synchronization Supervision ................................................................................... 4-2

    4.2.5 Auxiliary Communication Testing Supervision................................................................... 4-2

    4.2.6 Binary Output Testing Supervision ................................................................................... 4-2

    4.2.7 Device Maintenance Supervision ..................................................................................... 4-2

    4.2.8 Reference Voltage Supervision ........................................................................................ 4-2

    4.2.9 External Parameter Sensor Supervision........................................................................... 4-2

    4.2.10 CB and DS Position Supervision .................................................................................... 4-2

    4.2.11 CB Mechanical Characteristic Supervision ..................................................................... 4-2

    4.2.12 Frequency Supervision .................................................................................................. 4-2

    4.3 Alarm Signals................................................................................................................4-3

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    38/164

    4 Supervis ion

    PCS-9830B Switching Control ler4-bDate: 2015-02-15

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    39/164

    4 Su pervis ion

    PCS-9830B Switching Control ler 4-1Date: 2015-02-15

    4.1 Overview

    When this device is in energizing process before the LED HEALTHY is on, this device needs to

    be checked to ensure there are no errors. Therefore, the automatic supervision function, which

    checks the health of this device during startup and normal operation procedure, is very important.

    This device based on the microprocessor operations has the capability for implementing this

    automatic supervision function.

    In case a fatal fault is detected during automatic supervision, this device will be blocked out. It

    means that this device is out of service. Therefore you must re-energize this device or even

    replace a module to make this device back into service.

    4.2 Supervision Functions

    4.2.1 Device Hardware Supervision

    The MCU, RAM, ROM, FPGA chips in this device are monitored continuously to ensure whether

    they are damaged or have some errors.

    If any one of them is detected damaged or having error, this device will be blocked, the alarm

    signal [Fail_Device] will be issued, and the LED indicator HEALTHY will be off at the same time.

    4.2.2 Board Configuration Error Supervision

    If the board configuration of this device does not comply with the program software of this device,

    the alarm signals [Fail_Device] and [Fail_BoardConfig] will be issued, and the LED indicator

    HEALTHY will be off at the same time.

    4.2.3 Setting Supervision

    This device has 10 setting groups, but only one is active at any time. The settings of active setting

    group are checked continuously.

    If anyone of the active settings is confirmed to be modified, this device will be blocked, the alarm

    signals [Fail_Device] and [Fail_Setting] will be issued; meanwhile, if the modified setting is out of

    the appointed range, the alarm signal [Fail_Setting_OvRange] will be issued at the same time.

    The LED indicator HEALTHY will be off at the same time.

    If anyone of the items of the setting file is changed (the program of this device is updated), the

    alarm signal [Fail_SettingItem_Chgd] will be issued, The LED indicator HEALTHY will be off at

    the same time. The items of the setting include the setting number, the setting name, the setting

    range, the setting step etc.

    If anyone of the items of the setting file is changed (the program of this device is updated), the

    alarm signal [Fail_SettingItem_Chgd] will be issued. The LED indicator HEALTHY will be off at

    the same time. The items of the setting include the setting number, the setting name, the settingrange, the setting step etc.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    40/164

    4 Supervis ion

    PCS-9830B Switching Control ler4-2Date: 2015-02-15

    If the settings which are from the HMI module to the main CPU module are not in accordance with

    the current settings of the main CPU module, the alarm signal [Alm_Setting_MON] will be issued.

    The LED indicator ALARM will be on at the same time.

    4.2.4 Time Synchronization Supervision

    If the time synchronization function is enabled in this device, but this device detects the time

    synchronization is not correct, the alarm signals [Alm_Device] and [Alm_TimeSync] will be issued

    and the LED indicator ALARM will be on at the same time.

    4.2.5 Auxiliary Communication Testing Supervision

    If this device is in the auxiliary communication testing of binary signal or metering, the alarm

    signals [Alm_Device] and [Alm_CommTest] will be issued and the LED indicator ALARM will be

    on at the same time.

    4.2.6 Binary Output Testing Supervision

    If this device is in the binary output testing, the alarm signals [Alm_Device] and [Alm_BOTest] will

    be issued and the LED indicator ALARM will be on at the same time.

    4.2.7 Device Maintenance Supervision

    If this device is in the maintenance situation, the alarm signals [Alm_Device] and

    [Alm_Maintenance] will be issued and the LED indicator ALARM will be on at the same time.

    4.2.8 Reference Voltage Supervision

    If this device detects that any one of the reference voltages is less than 30V for longer than 3s, a

    related alarm signal [Alm_U_Refx] (x: 1, 2 or 3) will be issued and the LED indicator ALARM will

    be on at the same time.

    4.2.9 External Parameter Sensor Supervision

    If this device detects that any one of the sampled values of the external parameter sensors is out

    of the predefined range for longer than 10s, a related alarm signal will be issued and the LED

    indicator ALARM will be on at the same time.

    4.2.10 CB and DS Position Supervision

    If this device detects that any one of the CB and DS positions is abnormal for longer than 60s, a

    related alarm signal will be issued and the LED indicator ALARM will be on at the same time.

    See Section 3.4for more details.

    4.2.11 CB Mechanical Characteristic Supervision

    See Section 3.6.2for more details.

    4.2.12 Frequency Supervision

    If the frequency of each reference side is out of the range fn-0.5Hzto fn+0.5Hz(fn: systemfrequency) for longer than 3s, a related alarm signal [Alm_f_Refx] (x: 1, 2 or 3) will be issued and

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    41/164

    4 Su pervis ion

    PCS-9830B Switching Control ler 4-3Date: 2015-02-15

    the LED indicator ALARM will be on at the same time.

    4.3 Alarm Signals

    All the alarm signals listed below which may be issued.

    No. Alarm Element Description HEALTHY ALARM

    1 Fail_Device A serious fault is detected to block this device. Off

    2 Fail_BoardConfig The module configuration of this device is wrong. Off

    3 Fail_Setting_OvRange Anyone of the settings is out of range. Off

    4 Fail_SettingItem_Chgd Anyone of the setting items is changed. Off

    5 Fail_Setting The setting verification is not correct. Off

    6 Fail_FPGA The hardware FPGA is abnormal. Off

    7 Alm_Device Anyone of the software supervision alarm occurs. On

    8 Alm_Version The current program version is not correct. On

    9 Alm_Setting_MON The settings from the HMI module are not correct. On

    10 Alm_CommTest The communication test operation is executed. On

    11 Alm_BOTest The binary output test operation is executed. On

    12 Alm_Maintenance The device is in maintenance situation. On

    13 Alm_TimeSync The time synchronization is not correct. On

    14 Alm_U_Ref1 The No.1 reference voltage is abnormal. On

    15 Alm_U_Ref2 The No.2 reference voltage is abnormal. On

    16 Alm_U_Ref3 The No.3 reference voltage is abnormal. On

    17 Alm_f_Ref1The frequency of the No.1 reference side is out of the

    range. On

    18 Alm_f_Ref2The frequency of the No.2 reference side is out of the

    range. On

    19 Alm_f_Ref3The frequency of the No.3 reference side is out of the

    range. On

    20 Alm_Err_AmbientTemp The temperature sensor is abnormal. On

    21 Alm_L_AmbientTemp The temperature is less than the lower limit. On

    22 Alm_H_AmbientTemp The temperature is greater than the upper limit. On

    23 Alm_Err_CtrlVolt The control voltage sensor is abnormal. On24 Alm_L_CtrlVolt The control voltage is less than the lower limit. On

    25 Alm_H_CtrlVolt The control voltage is greater than the upper limit. On

    26 Alm_Err_OilPrA The oil pressure sensor of phase A is abnormal. On

    27 Alm_L_OilPrAThe oil pressure of phase A is less than the lower

    limit. On

    28 Alm_H_OilPrAThe oil pressure of phase A is greater than the

    upper limit. On

    29 Alm_Err_OilPrB The oil pressure sensor of phase B is abnormal. On

    30 Alm_L_OilPrBThe oil pressure of phase B is less than the lower

    limit. On

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    42/164

    4 Supervis ion

    PCS-9830B Switching Control ler4-4Date: 2015-02-15

    31 Alm_H_OilPrBThe oil pressure of phase B is greater than the

    upper limit. On

    32 Alm_Err_OilPrC The oil pressure sensor of phase C is abnormal. On

    33 Alm_L_OilPrCThe oil pressure of phase C is less than the lower

    limit.

    On

    34 Alm_H_OilPrCThe oil pressure of phase C is greater than the

    upper limit. On

    35 Alm_Err_GasPrA The SF6pressure sensor of phase A is abnormal. On

    36 Alm_L_GasPrAThe SF6pressure of phase A is less than the lower

    limit. On

    37 Alm_H_GasPrAThe SF6 pressure of phase A is greater than the

    upper limit. On

    38 Alm_Err_GasPrB The SF6pressure sensor of phase B is abnormal. On

    39 Alm_L_GasPrB

    The SF6pressure of phase B is less than the lower

    limit. On

    40 Alm_H_GasPrBThe SF6 pressure of phase B is greater than the

    upper limit. On

    41 Alm_Err_GasPrC The SF6pressure sensor of phase C is abnormal. On

    42 Alm_L_GasPrCThe SF6pressure of phase C is less than the lower

    limit. On

    43 Alm_H_GasPrCThe SF6 pressure of phase C is greater than the

    upper limit. On

    44 Alm_ClsTimeDiffAThe closing time difference of phase A is greater

    than the setting [t_Diff_1P_Cls].

    On

    45 Alm_ClsTimeDiffBThe closing time difference of phase B is greater

    than the setting [t_Diff_1P_Cls]. On

    46 Alm_ClsTimeDiffCThe closing time difference of phase C is greater

    than the setting [t_Diff_1P_Cls]. On

    47 Alm_OpnTimeDiffAThe opening time difference of phase A is greater

    than the setting [t_Diff_1P_Opn]. On

    48 Alm_OpnTimeDiffBThe opening time difference of phase B is greater

    than the setting [t_Diff_1P_Opn]. On

    49 Alm_OpnTimeDiffCThe opening time difference of phase C is greater

    than the setting [t_Diff_1P_Opn]. On

    50 Alm_ClsTimeDiff3PThe three-phase closing time difference is greater

    than the setting [t_Diff_3P_Cls]. On

    51 Alm_OpnTimeDiff3PThe three-phase opening time difference is greater

    than the setting [t_Diff_3P_Opn]. On

    52 Alm_ExtVarCompTime_Cls

    The closing time with the external variable

    compensation is greater than the setting

    [t_ExtVarComp_Cls].

    On

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    43/164

    4 Su pervis ion

    PCS-9830B Switching Control ler 4-5Date: 2015-02-15

    53 Alm_ExtVarCompTime_Opn

    The opening time with the external variable

    compensation is greater than the setting

    [t_ExtVarComp_Opn].

    On

    54 Alm_CompCurveSettings The setting of the compensation curve is wrong. On

    55 Alm_52_SideCB The position of the side circuit breaker is abnormal. On56 Alm_89_BB1&BB2 The position of the busbar disconnector is abnormal. On

    57 Alm_89a_BB1&BB2The positions of the two busbar disconnectors are

    closed at the same time. On

    58 Alm_89b_BB1&BB2The positions of the two busbar disconnectors are

    opened at the same time. On

    59 Alm_52_MainCBThe position of the controlled circuit breaker is

    abnormal. On

    60 Alm_52_CenterCB The position of the center circuit breaker is abnormal. On

    61 Alm_89_Line The position of the line switch is abnormal. On

    62 Alm_BO_Direct The operation signal outputs directly. On

    Here, Onmeans the LED is on, Offmeans the LED is off, and means having no influence.

    The handling suggestions of the alarm events are listed as below.

    No. Alarm Element Handing Suggestion

    1 Fail_Device Please check whether there has a serious error in this device.

    2 Fail_BoardConfig Please check whether the board configuration complies with the software.

    3 Fail_Setting_OvRangePlease ensure whether anyone of the settings is out of range, and make the

    related settings be in the setting range.

    4 Fail_SettingItem_ChgdPlease enter the relevant setting menu of this device and use the submenu

    Confirm Settings(under submenu Settings) to confirm it.

    5 Fail_Setting Please ensure whether anyone of the settings is modified.

    6 Fail_FPGA Please inform the manufacturer to deal with it.

    7 Alm_Device Please ensure whether anyone of the software supervision alarm occurs.

    8 Alm_Version Please inform the manufacturer to deal with it.

    9 Alm_Setting_MON Please inform the manufacturer to deal with it.

    10 Alm_CommTest Please check whether this device is in communication test situation.

    11 Alm_BOTest Please check whether this device is in binary output test si tuation.

    12 Alm_Maintenance Please check whether the binary input for denoting maintenance is energized.

    13 Alm_TimeSync Please check whether the time synchronization signal is correct.

    14 Alm_U_Ref1 Please check the input circuit of the No.1 reference voltage.

    15 Alm_U_Ref2 Please check the input circuit of the No.2 reference voltage.

    16 Alm_U_Ref3 Please check the input circuit of the No.3 reference voltage.

    17 Alm_f_Ref1 Please check the voltage input of the No.1 reference side.

    18 Alm_f_Ref2 Please check the voltage input of the No.2 reference side.

    19 Alm_f_Ref3 Please check the voltage input of the No.3 reference side.

    20 Alm_Err_AmbientTemp

    Please check the temperature sensor input and the related settings.21 Alm_L_AmbientTemp

    22 Alm_H_AmbientTemp

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    44/164

    4 Supervis ion

    PCS-9830B Switching Control ler4-6Date: 2015-02-15

    23 Alm_Err_CtrlVolt

    Please check the control voltage sensor of phase A and the related settings.24 Alm_L_CtrlVolt

    25 Alm_H_CtrlVolt

    26 Alm_Err_OilPrA

    Please check the oil pressure sensor of phase A and the related settings.27 Alm_L_OilPrA28 Alm_H_OilPrA

    29 Alm_Err_OilPrB

    Please check the oil pressure sensor of phase B and the related settings.30 Alm_L_OilPrB

    31 Alm_H_OilPrB

    32 Alm_Err_OilPrC

    Please check the oil pressure sensor of phase C and the related settings.33 Alm_L_OilPrC

    34 Alm_H_OilPrC

    35 Alm_Err_GasPrA

    Please check the gas pressure sensor of phase A and the related settings.36 Alm_L_GasPrA

    37 Alm_H_GasPrA

    38 Alm_Err_GasPrB

    Please check the gas pressure sensor of phase B and the related settings.39 Alm_L_GasPrB

    40 Alm_H_GasPrB

    41 Alm_Err_GasPrC

    Please check the gas pressure sensor of phase C and the related settings.42 Alm_L_GasPrC

    43 Alm_H_GasPrC

    44 Alm_ClsTimeDiffA

    Please check whether the feedback signals are abnormal and whether the

    related settings are set reasonably.

    45 Alm_ClsTimeDiffB

    46 Alm_ClsTimeDiffC

    47 Alm_OpnTimeDiffA

    48 Alm_OpnTimeDiffB

    49 Alm_OpnTimeDiffC

    50 Alm_ClsTimeDiff3P

    51 Alm_OpnTimeDiff3P

    52 Alm_ExtVarCompTime_Cls Please check whether the sensors are abnormal, whether the related settings

    are set reasonably.53 Alm_ExtVarCompTime_Opn

    54 Alm_CompCurveSettings Please check whether the compensation curve settings are set reasonably.

    55 Alm_52_SideCB Please check the side circuit breaker and its auxiliary contact circuit.

    56 Alm_89_BB1&BB2

    Please check the disconnectors and their auxiliary contact circuits.57 Alm_89a_BB1&BB2

    58 Alm_89b_BB1&BB2

    59 Alm_52_MainCB Please check the controlled circuit breaker and its auxiliary contact circuit.

    60 Alm_52_CenterCB Please check the center circuit breaker and its auxiliary contact circuit.

    61 Alm_89_Line Please check the line switch and its auxiliary contact circuit.

    62 Alm_BO_Direct Please check whether the operation conditions are satisfied.

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    45/164

    5 Hardware

    PCS-9830B Switching Control ler 5-aDate: 2015-02-15

    5 Hardware

    Table of Contents

    5.1 Overview ........................................................................................................................5-1

    5.2 Basic Enclosure ...........................................................................................................5-2

    5.3 Human Machine Interface Module (NR4856) ........................................................5-3

    5.4 Power Supply Module (NR4304/NR4305) ..............................................................5-3

    5.5 Main CPU Module (NR4106MA/B/C) ........................................................................5-4

    5.6 Network DSP Module (NR4138A).............................................................................5-6

    5.7 Analog Input Module (NR4412) ................................................................................5-7

    5.8 Binary Output Module (NR4524A) ...........................................................................5-8

    5.9 Binary Input Module (NR4501A/D) ....................................................................... 5-10

    5.10 DC Analog Input Module (NR4410C) ..................................................................5-11

    List of Figures

    Figure 5.1-1 Front panel of this device .................................................................................. 5-1

    Figure 5.1-2 Rear panel of this device (fully equipped) ........................................................ 5-2

    Figure 5.2-1 Rack, back plane and slot allocation of this device ......................................... 5-2

    Figure 5.4-1 View of the power supply module ..................................................................... 5-3

    Figure 5.5-1 View of the main CPU module ........................................................................... 5-5

    Figure 5.6-1 View of the network DSP module ...................................................................... 5-6

    Figure 5.7-1 View of the analog input module....................................................................... 5-7

    Figure 5.8-1 View of the binary output module ..................................................................... 5-9

    Figure 5.9-1 View of the binary input module ..................................................................... 5-10

    Figure 5.10-1 View of the DC analog input module..............................................................5-11

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    46/164

    5 Hardware

    PCS-9830B Switching Control ler5-bDate: 2015-02-15

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    47/164

    5 Hardware

    PCS-9830B Switching Control ler 5-1Date: 2015-02-15

    5.1 Overview

    The modular design of this device allows it to be easily upgraded or repaired by a qualified service

    person. The faceplate is hinged to allow easy access to the configurable modules, and

    back-plugging structure design makes it easy to repair or replace any modules.

    There are several types of hardware modules in this device; each module takes a different part.

    The relevant modules can be selected according to the practical engineering demands.

    These modules which are supported in this device and their module codes are listed as below.

    Slot No. Module Description Module Code Configuration

    1 Main CPU module NR4106 Mandatory

    2 Network DSP module NR4138 Mandatory

    3~4 Analog input module NR4412 Mandatory5 Binary output module NR4524 Mandatory

    6 Binary output module NR4524 Optional

    7 Binary input module NR4501 Mandatory

    8 DC analog input module NR4410 Optional

    9 Power supply module NR4304 Mandatory

    x Human machine interface module NR4856 Mandatory

    The following two figures show the front panel and the rear panel of this device.

    Switching Controller

    PCS-9830

    ENT

    ESC

    GRP

    HEALTHY

    ALARM

    1

    20

    19

    18

    17

    16

    15

    14

    13

    12

    11

    10

    9

    8

    7

    6

    5

    4

    3

    2

    Figure 5.1-1 Front panel of this device

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    48/164

    5 Hardware

    PCS-9830B Switching Control ler5-2Date: 2015-02-15

    NR4524A NR4501ANR4106MA NR4138A

    RX

    RX

    01

    07

    21

    20

    17

    19

    16

    06

    0504

    12

    11

    15

    03

    10

    14

    02

    13

    09

    08

    18

    22

    PWR+

    NR4304

    PWR-GND

    NR4412

    01 02

    03 04

    05 06

    07

    09 10

    11 12

    13 14

    15 16

    2423

    2221

    2019

    1817

    08

    2625

    NR4524A NR4410C

    Figure 5.1-2 Rear panel of this device (fully equipped)

    NOTE! The hardware module configuration in above figure is only a demonstration for

    explaining how the hardware module is configured. The hardware module configuration

    can be different according to the different engineering demands, and the hardware

    module configuration of a practical engineering should be taken as final and binding.

    5.2 Basic Enclosure

    The basic enclosure of this device is an electronic equipment rack (seeFigure 5.2-1) with an

    adequate number of slots for all these modules. The basic rack is equipped with a back plane

    (mother board), and the back plane provides some back plane lines for distributing signals within

    the enclosure. The rack, back plane and the slot allocation of this device is shown as below.

    NR4106MA/B/C

    NR4138A

    Slot: 1 2 3 4 5 6

    NR4524A

    NR4501A/D

    NR4524A

    (Optional)

    NR4412

    NR4304/NR4305

    NR4410C

    (Optional)

    7 8 9

    Figure 5.2-1 Rack, back plane and slot allocation of this device

  • 7/25/2019 PCS-9830B X Instruction Manual en Domestic General X R1.05

    49/164

    5 Hardware

    PCS-9830B Switching Control ler 5-3Date: 2015-02-15

    5.3 Human Machine Interface Module (NR4856)

    The human machine interface (HMI) module is installed on the front panel of this device. It is used

    to observe the running status and event information on the LCD, and configure the protection

    settings and device operation mode. It can help the user to know the status of this device and

    detailed event information easily, and provide convenient and friendly access interface for the user.

    Please see Chapter 7for further details about how to access the human machine interface.

    5.4 Power Supply Module (NR4304/NR4305)

    The power supply module is a power supply converter with electr ical insulation between input and

    output, and a maximum output power of 30W. The power supply module has an input voltage

    range as described in Section 2.1.1.1. The power supply module can provide two groups of +5Vdc

    power supply outputs for other modules in this device. The tolerances of the output voltages are

    continuously monitored.

    The use of an external miniature circui