paper vibration

Upload: cesar-diaz

Post on 01-Jun-2018

212 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/9/2019 paper vibration

    1/7

     

    Journal of Chongqing University (English Edition) [ISSN 1671-8224]

    Vol. 8 No.1

    March 2009 

    50

     Article ID:  1671-8224(2009)01-0050-07 

    To cite this article: YE Zhi-xiong, LI Li, LONG Xiao-hong. Aeolian vibration control measures for ground wires of Han River long span transmission lines [J]. J Chongqing

    Univ: Eng Ed [ISSN 1671-8224], 2009, 8(1): 50-56.

    Aeolian vibration control measures for ground wires of Han Riverlong span transmission lines 

    YE Zhi-xiong1,2,†

    , LI Li1,2

    , LONG Xiao-hong1,2

     1 School of Civil Engineering and Mechanics, HuaZhong University of Science and Technology, Wuhan 430074, P. R. China

    2 Hubei Key Laboratory of Control Structure, HuaZhong University of Science and Technology, Wuhan 430074, P. R. China

    Received 17 June 2008; received in revised form 5 September 2008

    Abstract: Long span ultra-high voltage (UHV) transmission lines have serious aeolian vibration problems. To control these

    vibrations, we improved the energy balance method in the following aspects: the wind power input, the conductor self-damping,

    and the damper dissipated power. Meanwhile, we built a theoretical mechanical model of β  wire dampers and derived energy

    dissipation calculation formulae. This permits the vibration energy dissipated by β wire dampers can be considered in the energy

     balance method. Then, we developed a computer program based on the improved energy balance method using Matlab, and

    analyzed UHV long span ground wires of the Han River long span project in P. R. China. The results show that the combination

    of β  wire dampers and Stockbridge dampers can reduce vibration of UHV long span transmission lines, which provides a

    reference for research and construction of UHV engineering projects.

    Keywords:  ultra-high voltage transmission lines; aeolian vibration; energy balance method; Stockbridge dampers; β  wire

    dampers

    CLC number: TM752 Document code: A

    1 Introduction a 

    Researchers have investigated aeolian vibrations of

    electrical transmission lines (also called conductors) for

    many years. Many researchers have demonstrated that

    suitable damping devices can reduce the induced

    dynamic bending strain values of the conductors,

    thereby protecting conductors from fatigue failure.

    Zheng [1] and Ervik et al. [2] used the energy balancemethod to analyze aeolian vibrations of an overhead

    line. They evaluated the vibration level by finding the

     balance between the ambient wind energy input and the

    energy dissipated by both the conductor itself (namely

    self-damping) and the added dampers. However, the

    †YE Zhi-xiong (叶志雄): [email protected].

    ∗ Funded by the Natural Science Foundation of China (No.

    50878093).

    result of this method has some errors because the windenergy input and conductor self-damping are uncertain

    and the accuracy mostly depends on experimental

     precision.

    Recently, Diana et al. [3], Lu and Chan [4]

    developed a novel approach based on impedance

    transfer plus forced vibration to analyze aeolian

    vibration of a single conductor with multiple dampers.

    However, there is no method for calculating the powerdissipated by wire dampers even though the calculation

    theory for Stockbridge dampers is comparatively

    mature [5-6]. The installation of wire dampers usually

    is based on qualitative analysis and simulation testing.

    The electrical demands increased dramatically in P.

    R. China as its economy developed rapidly. Therefore,

    the State Grid Corporation of China planned and

    constructed an ultra-high voltage (UHV) grid. Due to

    their cross sections, the height of suspension and span

    distance of long span UHV transmission lines increase,

    and their vibration conditions become more serious. In

  • 8/9/2019 paper vibration

    2/7

    Z. X. Ye, et al.

     Aeolian vibration control measures

    J. Chongqing Univ. Eng. Ed. [ISSN 1671-8224], 2009, 8(1): 50-56 51

    this paper, we improved the energy balance method,

     built a theoretical mechanical model of β damper, and derived energy dissipation calculation formulae. Basedon the improved energy balance method, we then

    developed a computer program using Matlab software.

    We also analyzed UHV ground wires crossing the Han

    River. The results show that the algorithm is very

    efficient and it meets the analytical requirement of

    UHV transmission lines. Therefore, the combination of

    β wire dampers and Stockbridge dampers can provide

    anti-vibration for UHV long span transmission lines.

    Our work serves as a reference for research and

    construction of UHV engineering projects.

    2 Improvement of the energy balance method

    When conductor self-damping alone cannot ensure

    the safety of transmission lines, special dampers need

    to be mounted. The following energy balance holds for

    a given frequency (or mode) over the span:

    W C DP P P= + , (1)

    whereW

    P   is the  ambient wind power input over the

    free span;C

    P  is the power dissipated by the conductor

    itself over the free span; andD

    P  is the power dissipated

     by the dampers. The Stockbridge damper, the wiredamper and the spacer damper are commonly used

    damping devices. DP  is the sum of their consumed

    energy.

    D d b sP P P P= + + , (2)

    whered

    P  is the power dissipated by Stockbridge

    dampers, P  by wire dampers, ands

    P  by spacer

    dampers. Obtaining each power is the key step of the

    energy balance method. Therefore, we improved this

    method in three aspects: the wind power input, the

    conductor self-damping and the damper dissipated power.

    2.1 Improvement of the wind power input

    The wind power inputW

    P  normally is computed

    from aerodynamic forces obtained by wind tunnel

    experiments which are carried out by measuring the

    drag and lift forces on the oscillating cylinders and

    flexible rods or cables under uniform laminar cross-

    flow in the wind tunnel (as shown in Ref. [7]). The

     power (per unit length) imparted to a conductor by

    wind can be expressed by the following empiricalequation [4]:

    3 40

    W ( ) ( ) A

    P F V F f D D

    ′= , (3)

    where V    is the velocity of wind;  D   is the conductor

    diameter; A0 is the steady state displacement amplitude;

     f  is the vibration frequency of conductor; and F  and F ′  represent the functions, respectively.

    Terrain and ground objects show significant effects

    on reducing the wind power input values as compared

    to that in laminar winds. Kraus and Hagedorn [8]

    carried out field tests on an actual transmission line,and compared the results with that of the wind tunnel

    data. Then they pointed out that the wind power input

    strongly depends on the turbulence level and the

    component of the wind velocity parallel to the cable.

    Therefore, the wind power input obtained from wind

    tunnel experiments should be verified for an actual line

    according to terrain categories at the site. Considering

    the terrain category, we applied a reduction factor

    suggested by the CIGRE (conseil international des

    grands réseaux électriques ) to reduce the wind energy

    due to turbulence for the appropriate terrain. This

    reduction factor can be expressed as

    w2

    L

    1

    1 ( / )V  I I  β    =

    +, (4)

    wherew

     β    is the wind energy reduction factor due to

    turbulence;L

     I   is the lock-in index and is used to

    reflect the lock-in effect in aeolian vibration, which

    may take the value of 0.09;V  I   is the turbulence

    intensity of the wind and

    m/V V  I V σ = , (5)

    in which V σ    is the standard deviation of wind speed;and

    mV   is the mean wind speed.

    The turbulence intensity can be determined by the

    statistics of local wind. However, this information is

    lacking. Then an empirical equation in Ref. [2] may be

    used to estimate the value.

    2.2 Improvement of conductor self-damping

    When a conductor flexes, its strands slip against

    each other. This relative motion generates frictional

  • 8/9/2019 paper vibration

    3/7

    Z. X. Ye, et al.

     Aeolian vibration control measures

    J. Chongqing Univ. Eng. Ed. [ISSN 1671-8224], 2009, 8(1): 50-56 52

    forces which provide damping. In addition, internal

    losses are incurred within the core and individualstrands of the conductor at the microscopic level,

    which is known as the material damping. The

    combination of these dissipative effects is referred to as

    conductor self-damping, which depends on material

    composition, manufacturing technology, actual

    tensions, ambient temperature, vibration frequency and

    amplitude, and other factors. Conductor self-damping

    thus is determined mainly by experimental

    measurement. It is usually approximated in the

    following form:

    0

    C

    ( ) y

    P Kf  D

     β α = , (6)

    where0

     y  is the amplitude of vibration; K , α  and  β  are

    coefficients determined experimentally.

    At the preliminary design stage, if no cable sample is

    available and the cable type has not yet been measured,

    some hypotheses are required. It would be convenient

    to have available rules that predict internal losses of

    cables. Noiseux [9] derived the earliest calculation laws

    of internal damping of stranded cables based on the

     basic cable differential equation.  Lu [4] suggested asemi-empirical equation for calculating conductors

    self-damping as:

    4.5 6 2.56

    C eq S 0 5

    c

    1.07 10 D

     D f AP E k k K L

     β +

    = × , (7)

    where  A is the displacement amplitude;  L is the length

    of a conductor;S

    k   is the reduction factor on the

    maximum conductor bending stiffness andS

    0.5k   = ;

    Dk   is an empirical factor, and

    D0.54k   =  for an

    aluminum conductor steel reinforced (ACSR)

    conductor, whileD

    0.65k   =  for a stranded steel

    conductor;c

    V    is conductor’s wave velocity, which is

    related to the conductor’s catenary constant C , and

    cgV C = , in which g is the gravity constant; eq E   is

    the equivalent Young’s modulus of the conductor; 0K   

    is a constant for conductors, which can be determined

     by test.

    By curve fitting the Kinectrics’ data, the following

    results were obtained [10].

    1) For an all-aluminum conductor (AAC) Arbutus

    conductor:

    K 0 = 0.003 5 and  β  = −0.433 2;

    2) For an ACSR Drake conductor:

    K 0 = 0.004 2 and  β  = −0.425 6.

    We modified the semi-empirical equation theoretical

    calculations referring to the test results of Xu and

    Wang [11] and realized the improvement of conductor

    self-damping. Certainly, experiment tests might be

    necessary to obtain the exact self-damping values of

    some types of wire.

    2.3 Improvement of power dissipated by dampers

    We applied an improved calculation method [12] to

    optimize the damper location. First, the probable

    distribution of transmission line vibration frequencies

    were obtained according to the frequency distribution

    of the wind speed. Then the weighted amplitude ratio

    was calculated to determine the optimal installation

     position of dampers on aerial conductors. This method

    can take into consideration the dangerous vibration

    frequency range and the occurrence probability of each

    vibration frequency. Finally, an advanced formula [13]

    was used to calculate the power characteristics of

    damper, which can take into account the damper

    installation position and the conductor bending

    stiffness and tension.

    When dampers are fixed on overhead transmissionlines, the characteristics of the coupled vibration of

    dampers and transmission lines create a complicated

     problem involving a structure-flow interaction. There is

    a significant error if we do not consider the distortion

    due to the dampers when we study the response of

    transmission lines. Therefore, finding the ratio of the

    amplitude at the damper’s clamp to that at the free span

    is necessary.

    We found different approaches in the literature

    solving for the amplitude ratios. For example, Li et al.

    [14] indicated that the finite element method can

    analyze the dynamic characteristics of conductor-damper coupling systems and account for damper

     position, a conductor’s bending stiffness, the rotational

    effect of dampers, and the possible support flexibility

    at the end of a conductor span. We used this approach

    to carry out modal analysis of the coupling system and

    find the amplitude ratios for each vibration mode.

    3 Calculation of power dissipated by wire

    dampers

    Wire dampers are very complex vibration

  • 8/9/2019 paper vibration

    4/7

    Z. X. Ye, et al.

     Aeolian vibration control measures

    J. Chongqing Univ. Eng. Ed. [ISSN 1671-8224], 2009, 8(1): 50-56 53

    elimination systems. There is no complete systematic

    method for designing and calculating the power theydissipated. Therefore, their installation is usually based

    on qualitative analysis and simulation testing. Wire

    dampers (Bretelles) consist of a length of conductor

    which is similar to the main conductor in the span.

    They are mounted under the main conductor and

    attached by a type of parallel groove clamp. Three- and

    four-loop dampers of one piece construction (festoons)

    mount around the attachment clamps reaching out into

    the span. The energy dissipation mechanism of wire

    dampers is similar to the combinations of many

    Stockbridge dampers. Festoons of varying lengths have

    a damping action for different vibration frequencies.

    They take many forms, such as the modified Bate

    damper, the cross wire damper, the Christmas tree

    formed damper, and so on.

    Wang [5] pointed that β  wire dampers combined

    with Stockbridge dampers are reasonable and suitable

    for the vibration damping of long span transmission

    lines. This anti-vibration measure has been applied in

    more than 20 long span projects in P. R. China.

    Laboratory testing, the field vibration measurement,

    and running state detection all have shown that it is

    effective and practical. Therefore, we mainly studied

    this measure in the paper.

    3.1 Mechanical model of wire damper

    We assumed that two ends of a wire damper are

    rigidly fixed on an overhead conductor. The average

    wire pressure is T ; the mass per unit length of wire is m;

    the wire bending stiffness is EI ; and the wire damping

    ratio is η . Suppose the vertical displacement of wire

    dampers is  y, the governing equation for the free

    motion of a wire damper then can be deduced as

    4 2 2

    4 2 20

     y y y y EI T m

    t  x x t 

    η ∂ ∂ ∂ ∂

    − + + =

    ∂∂ ∂ ∂

    , (8)

    where  x is the abscissa and represents the length from

    the damper location to the supporting clamp; and t   is

    the time. Solving Eq. (8), the natural vibration

    frequencies of wire damperscω   can be obtained:

    22 2 2 2

    c 2 2

    π π1

    2

    n T n EI  

    m L m L T 

    η ω 

      ⎛ ⎞   ⎛ ⎞= + −⎜ ⎟   ⎜ ⎟

    ⎝ ⎠⎝ ⎠, (9)

    where n is a natural number. Each main vibration shape

    is

    ( )2 c cπ

    ( , ) e cos sin sint 

    mn

     y x t A t B t x L

    η 

    ω ω −

    = + , (10)

    where A and B are constants.

    Suppose the connection points of a wire damper are

     x1 and x2 respectively. According to the conditions for

    matching displacement, velocity and acceleration of the

    two points, the ratio of the amplitude of wire damper

    ( A ) to that of free span conductor ( c A ) is obtained.

    ( )

    ( )

    2

    2 12 12

     b c b c

    2 1c

     b

    ππ πsin cos sin

    πsin

    n x xn x n x

     A L L L

    n x x A

     L

    −⎛ ⎞−⎜ ⎟

    ⎛ ⎞ ⎜ ⎟= +⎜ ⎟ ⎜ ⎟−⎝ ⎠ ⎜ ⎟

    ⎝ ⎠2

    1

    c

    πsin

    n x

     L

    ⎛ ⎞⎜ ⎟⎝ ⎠

    ,  (11)

    where  Lc  is the length of conductor;  L b  is the full arc

    length of wire damper.

    3.2 Power dissipation calculation formulae for wire

    dampers

    When a wire damper vibrates due to external forces(such as aeolian excitation), the vibration equation may

     be approximated as:

    4 2 2

    ω4 2 2( , )

     y y y y EI T m F x t 

    t  x x t η 

    ∂ ∂ ∂ ∂− + + =

    ∂∂ ∂ ∂, (12)

    whereωF    represents the dynamic force acting on the

    wire damper due to vortex shedding. Multiplying Eq.

    (12) by y

    ∂ and integrating it over one cycle and over

    one span length leads to

    0

    0

    4 2 2

    4 2 20d d

     L t 

     y y y y y EI T m t x

    t t  x x t 

    τ 

    η +   ⎡ ⎤∂ ∂ ∂ ∂ ∂− + + =⎢ ⎥∂ ∂∂ ∂ ∂⎣ ⎦

    ∫ ∫

    [ ]0

    0  ( , ) d d

     L t 

     yF x t t x

    τ +   ∂

    ∂∫ ∫.  (13)

    The left side of Eq. (13) corresponds to the energy

    dissipated by the wire damper over one cycle and over

    the span length. The right side of Eq. (13) refers to the

    energy imparted to the wire damper span by external

    forces over one cycle. Thus the power dissipated by the

    wire damper can be found by the left-hand side of Eq.

  • 8/9/2019 paper vibration

    5/7

    Z. X. Ye, et al.

     Aeolian vibration control measures

    J. Chongqing Univ. Eng. Ed. [ISSN 1671-8224], 2009, 8(1): 50-56 54

    (13) after incorporating Eq. (10) into Eq. (13).

    5 4 2 3 2

     b c b c c16π

     EI P EI A fL A m

    T δ λ δ ω  −= + , (14)

    where λ   is the vibration wavelength; andc

    δ  is the

    material damping ratio of wire damper.

    Generally, after a suspended wire damper is

    subjected to its own weight, its assumes a catenary

    configuration. The curve equation can be written as

    cosh( / ) y C x C = . Assuming the span length of wire

    damper is  Ld and the sag of wire damper is S , the full

    arc length of wire damper can be approximated by

    2

     b d

    d

    83S  L L L

    = + .

    The material damping ratio of conductor can be

    empirically expressed as follows.

    Free span:

    0.52

    2 6D

    c 0 2

    c

    (2π) 102

    k D f AK f 

     β δ ⎡ ⎤

    = ×⎢ ⎥⎣ ⎦

    ,

    and span terminal

    0.56D

    c 02π 10

    2

    k DmK f fA

     EI 

     β δ ⎡ ⎤= ×⎢ ⎥⎣ ⎦

    .

    The energy dissipation calculation formula for wire

    damper then can be expressed as:

    4.5 6 2.56

     b eq D S 0 b 5

    c

    1.07 10 D f A

    P E k k K LV 

     β +

    = × +

    1.5 3.5 2.54 0.25 0.75

    eq D 0

    c

      8.7 10 D f A

     E k K mV 

     β +

    × ,  (15)

    in which c gV T = .

    4 Anti-vibration design of ground wires

    We mainly introduced the anti-vibration measure

    design for ground wires because the aeolian vibration

    of ground wires generally is more severe. We took the

    Han River long span project as an example. The Han

    River long span transmission lines of the 1 000 kV

    Jindongnan-Nanyang-Jingmen UHV AC transmission

     project are 1 650 meters long. The type of ground wire

    is JLB20B-240 and its diameter is 0.020 m. The mass

     per unit length is 1.595 5 kg m−1, and the average

    running tension is 48 945.8 N.In the project, we chose the wind power curve of

    Diana and Falco to compute the wind energy. Taking

    into consideration the effect of wind turbulence

    intensity, we theoretically calculated the value of

    ground wire self-damping and advanced it by referring

    to test results of other types. Based on the improved

    energy balance method, we developed a computer

     program using Matlab software. Then we computed the

    deflection and bending strain in a conductor without a

    damper. According to the standard of danger vibration

    [15], when the bending strain (ε ) exceeds 200 × 10−6, itis dangerous for aluminum steel-covered strands

    JLB20B-240. Therefore, the dangerous vibration

    frequency range is from 7.4 Hz to 62.9 Hz. According

    to the calculation method in Ref. [12], we can

    determine the maximum vibration proof efficiency ( M )

    at the location of the corresponding x (Fig. 1).

    It can be seen from the Fig. 1 that the best location

    of FR4 dampers (one type of Stockbridge dampers) are

    1.01 m, 2.34 m and 3.70 m away from the supporting

    clamp when the key protection frequency range is from

    6 Hz to 65 Hz. The results of analysis after dampers

    were mounted in these positions are shown in Fig. 2.

    Fig. 1 Maximum vibration proof efficiency ( M ) with its

    corresponding length from the location of damper to the

    supporting clamp ( x) after installing FR4 type dampers

    The aeolian vibration of the Han River UHV long

    span project ground wires is severe (Fig. 2). The

    dangerous frequency range is 8 Hz to 64 Hz, which is

    wide. Three Stockbridge dampers are needed at each

    end. Fig. 2 shows that Stockbridge dampers of two FR3

  • 8/9/2019 paper vibration

    6/7

    Z. X. Ye, et al.

     Aeolian vibration control measures

    J. Chongqing Univ. Eng. Ed. [ISSN 1671-8224], 2009, 8(1): 50-56 55

    type plus four FR4 type in the span achieve better

    vibration reduction than 6 FR4 ones. Therefore,combined use of Stockbridge dampers with different

     power characteristics better suppresses aeolian

    vibrations. However, ε   exceeds 200 × 10−6 whenvibration frequencies are between 45 Hz and 52 Hz.

    Test calculations indicate that additional Stockbridge

    dampers have no obvious effect. Therefore, we chose

    to use Stockbridge dampers combined with β  wire

    dampers.

    Fig. 2 Bending strain (ε ) of the ground wires with and

    without dampers

    Suppose β wire dampers using the same material as

    the ground wire, the cable sag is 1/10 to 1/5 times its

    full length. Referring to Eq. (9), the expression for

    natural frequencies of a wire damper (n

    ω  ) can be

    simplified as:

    2 2

    n 2

    π π1

    n T n EI  

     L m  L T ω 

      ⎛ ⎞= +⎜ ⎟

    ⎝ ⎠. (16)

    Inserting each parameter into (16) gives:

    22 2

    n 2

    π π π1 26.92

    n T n EI n

     L m L L T ω 

      ⎛ ⎞   ⎛ ⎞= + =⎜ ⎟   ⎜ ⎟

    ⎝ ⎠⎝ ⎠. (17)

    The minimum resonant frequency for a 4.0 m single

    festoon wire damper is approximately 3 Hz, about

    42 Hz for a 1.0 m one, and roughly 66 Hz for a 0.8 m

    one.

    Considering the deficiency of energy consumption in

    high frequency of Stockbridge dampers, we arranged 2

    to 3 0.8 meter-long festoons wire dampers. After

    computing and optimizing structural forms of wire

    dampers, β  wire dampers are eventually designed ascombinations of a 4.0 m single festoon wire damper, a

    3.0 m one, a 2.0 m one, and two 0.8 m ones in the span

    (5 festoons in total). The nearest mounting point is

    0.3 m away from the supporting clamps of the

    conductor. Fig. 3 shows the mounting configuration

    and Fig. 4 shows the analysis results.

    Fig. 3 Installation scheme of β dampers and FR dampers

    Fig. 4 Bending strain (ε ) with combination anti-vibration

    measures

    It can be seen from Fig. 4 that β  wire dampers

    combined with Stockbridge dampers can respond to

    most of the frequencies experienced over the range of

    wind speeds causing vibration, and can keep the bending strain under the required standard. Short

    festoon wire dampers have very good energy

    dissipation capacity at high frequencies. If they are

    decreased in weight by layer-stripping, a broader range

    of frequencies possibly could be suppressed. The

    results show that this damping device can satisfy the

    vibration prevention requirements of UHV long span

    transmission lines. Nevertheless, the accuracy of

    numerical calculation results mainly depends on

     parameters of wind input power and conductor self-

    damping, which need the confirmation of field testing.

  • 8/9/2019 paper vibration

    7/7

    Z. X. Ye, et al.

     Aeolian vibration control measures

    J. Chongqing Univ. Eng. Ed. [ISSN 1671-8224], 2009, 8(1): 50-56 56

    5 Conclusions

    1) An improved energy balance method can account

    for the effect of terrain and ground objects, support

     boundary conditions at the span end of conductors,

    average running tension of the conductor, and the

    damper position. Therefore, the method is applicable in

    aeolian vibration suppression design and calculation.

    2) The derived energy dissipation calculation

    formulae of β wire dampers are effective theoretically

    and practically.

    3) The results of numerical calculation show that β 

    wire dampers combined with Stockbridge dampers are

    effective at suppressing aeolian vibrations. This

    damping device can satisfy the vibration preventionrequirements of UHV long span transmission lines,

    which can be used for the vibration damping of long

    span transmission lines.

    4) Theoretical results must be checked and verified

     by field testing because of the particularity and

    importance of UHV. Vibration model testing and field

    vibration measurement absolutely are necessary for

    construction. It is possible to design transmission lines

    with more operational safety using these methods.

    References

    [1] Zheng YQ. Aeolian vibration of the transmission

    conductor [M]. Beijing: China Water Conservancy and

    Electric Power Press, 1987. (In Chinese).

    郑玉琪.架空输电线微风振动[M].北京 :水利电力出

    版社,1987.

    [2] Ervik M, Berg A, Boelle A, et al. Report on aeolian

    vibration of power overhead lines [J]. Electra,

    1989(124): 41-77.

    [3] Diana G, Claren FR, Cloutier L. Modeling of aeolian

    vibration of single conductors: assessment of the

    technology [J]. Electra, 1998(181): 53-69.

    [4] Lu ML, Chan JK. An efficient algorithm for aeolian

    vibration of single conductor with multiple dampers [J].

    IEEE Transactions on Power Delivery, 2007, 22(3):

    1822-1829.

    [5] Wang JC. Discussion on the anti-vibration measures of

    long span conductors [C]. In: Chinese Society for

    Electrical Engineering editors. The second session of

    the 4th annual meeting symposium of Chinese Society

    for Electrical Engineering on transmission and electric.

    Beijing: 2004: 411-416. (In Chinese).

    王景朝.大跨越导线防振方案探讨[C].中国电机工程

    学会输电电气四届二次学术年会论文集.北京 :

    2004:411-416.

    [6] Kamiyama H, Hiratsuka S, Fukuda N, et al.Development of a high-strength conductor, accessories

    and stringing method for an over-water crossing of the

    Osaki Thermal Power Line [J]. Furukawa Review,

    1999(18): 37-43.

    [7] Diana G, Falco M. On the forces transmitted to a

    vibrating cylinder by a blowing fluid [J]. Meccanica,

    1971, 6(1): 9-22.

    [8] Kraus M, Hagedorn P. Aeolian vibrations: wind energy

    input evaluated from measurements on an energized

    transmission line [J]. IEEE Transactions on Power

    Delivery, 1991, 6(3): 1264-1270.

    [9] Noiseux DU. Similarity laws of the internal damping of

    stranded cables in transverse vibrations [J]. IEEE

    Transactions on Power Delivery, 1992, 7(3): 1574-

    1581.

    [10] Lu ML, Orth M. Predicting the failure of line post

    insulator mounting studs due to aeolian vibrations,

    PD1013245 [R]. Palo Alto (CA): Electric Power

    Research Institute, 2006 June.

    [11] Xu NG, Wang JC. Conductor self-damping

    measurement and a practical calculating method [J].

    Electric Power, 1995, 28(2): 17-20. (In Chinese).

    徐乃管,王景朝.导线自阻尼的测量及实用归算方法

    [J].中国电力,1995,28(2):17-20.

    [12] Ye ZX, Li L, Jiang YC, et al. Calculation of installing positions of damper based on probability distribution of

    wind speed [J]. Journal of Vibration and Shock, 2007,

    26(10): 60-63. (In Chinese).

    叶志雄,李黎,江宜城,等.基于风速概率分布的防振锤

    安装位置计算[J].振动与冲击,2007,26(10):60-63.

    [13] Ye ZX, Li L, Long XH, et al. Calculation and

    application for power characteristics of damper with

    considering its location [J]. Electric Power

    Construction, 2008, 29(5): 5-8. (In Chinese).

    叶志雄,李黎,龙晓鸿,等.考虑安装位置的防振锤功率

    特性计算及其应用[J].电力建设,2008,29(5):5-8.

    [14] Li L, Kong DY, Long XH, et al. Analysis of aeoliantransmission conductor with dampers by the finite

    element method [J]. High Voltage Engineering, 2008,

    34(2): 324-328. (In Chinese)

    李黎,孔德怡,龙晓鸿,等.安装防振锤的输电线微风振

    动有限元分析[J].高电压技术,2008,34(2):324-328.

    [15] Shao TX. Mechanical computation of power

    transmission conductor [M]. 2nd ed. Beijing: China

    Electric Power Press, 2003: 312-354. (In Chinese).

    邵天晓.架空送电线路的电线力学计算[M].第二版.北

    京:中国电力出版社,2003:312-354.

    Edited by XUE Jing-yuan