p12x_envcc55 hard-soft ware

Upload: rindarayna

Post on 04-Jun-2018

226 views

Category:

Documents


0 download

TRANSCRIPT

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    1/12

    Technical Guide P12x/EN VC/C55

    MiCOM P120/P121/P122/P123

    HARDWARE/SOFTWARE VERSION

    P120 P121 P122 P123

    HISTORY AND COMPATIBILITY

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    2/12

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    3/12

    Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 1/10

    P120 - Serial number Hardware Correlation

    Serial Number Hardware installed

    From 2299001 to 4799797 HARDWARE VERSION 2

    From 4799798 to 1001999 HARDWARE VERSION 3

    From 1101001 HARDWARE VERSION 4

    Relay Type P120

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V1.F 11/06/99 Resolution of KITZ201problem

    Modification of the outputrelay latching

    HARD V 2

    HARD V 3HARD V 4

    V3.B 19/11/99 Suppression of password inorder to acknowledge thealarms

    Auto acknowledgement ofthe instantaneous

    Modbus time out of 200 ms

    Display of the letter P in the

    menu N and N-1 whenpassword is active

    !V2.0

    V3.C 22/08/00 VDEW improvements !V2.0

    HARD V 3

    HARD V 4

    V4.A 15/03/01 Integration of DNP3protocol

    Management of alternativelogic input

    Latching of the auxiliaryoutput relay by relay and

    not by functionThe digital input can workwith AC signals (100 to 250

    V AC)

    !V2.0 HARD V 4

    V4.D 27/08/02 Courier improvment :adding of the cell 0010 (CBcontrol)

    IEC103 : correction of thechecksum calculation forshort message.

    !V2.0 HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    4/12

    P12x/EN VC/C55 Technical GuideHardware/Software Version

    Page 2/10 MiCOM P120/P121/P122/P123

    P121 - Serial number Hardware Correlation

    Serial Number Hardware installed

    From 2599001 to 4799797 HARDWARE VERSION 2

    From 4799798 to 0801999 HARDWARE VERSION 3

    From 0901001 HARDWARE VERSION 4

    Relay Type P121

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V2.J 30/08/99 MODBUS improvement :

    Correction of alencountered problem(answer to asynchronisation telegram,creation of a 2 secondstime out )

    HARD V 2

    HARD V 3HARD V 4

    V3.B 19/11/99 Suppression of password inorder to acknowledge thealarms

    Auto acknowledgement ofthe instantaneous

    Modbus time out of 200 ms

    Display of the letter P in themenu N and N-1 whenpassword is active

    !V2.0 HARD V 3

    HARD V 4

    V3.C 25/01/00 Evolution of Modbus writing16 bits

    !V2.0

    V3.E 16/03/00 Czech and Hungarianversion delivery

    !V2.0

    V3.G 22/08/00 VDEW improvements !V2.0

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    5/12

    Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 3/10

    Relay Type P121

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V4.E 31/01/01 Latch of the output relaysLatch of the auxiliary relays,relay by relay and not byfunction (like previously upto V3 version). On the otherhand the latch of the TRIPoutput relay remains byfunction.

    If the auxiliary relays arelatched, no alarm isdisplayed. For anaknowledgment of the latchthe user has to go in theOP-PARAMETERS/Relaystatus Menu and push onthe clear push button.

    DNP3 level 2 and 3

    Addition of the tripping andclosing order for IEC103

    The digital input can work

    with AC signals (100 to 250V AC)

    !V2.0

    V5.D 31/01/01 Improvement of the englishlabels.

    !V2.0

    HARD V 4

    V5.F 08/08/02 Courier improvment :adding of the cell 0010 (CBcontrol)

    IEC103 : correction of thechecksum calculation forshort message.

    !V2.0 HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    6/12

    P12x/EN VC/C55 Technical GuideHardware/Software Version

    Page 4/10 MiCOM P120/P121/P122/P123

    P122 - Serial number Hardware Correlation

    Serial Number Hardware installed

    From 2599001 to 4799797 HARDWARE VERSION 2

    From 4799798 to 0801999 HARDWARE VERSION 3

    From 0901001 HARDWARE VERSION 4

    Relay Type P122

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V2.J 30/08/99 MODBUS improvement :

    Correction of alencountered problem(answer to asynchronisation telegram,creation of a 2 secondstime out )

    HARD V 2

    HARD V 3HARD V 4

    V3.B 29/11/99 Suppression of password inorder to acknowledge thealarms

    Auto acknowledgement ofthe instantaneous

    Modbus time out of 200 ms

    Display of the letter P in themenu N and N-1 whenpassword is active

    !V2.0

    V3.C 06/01/00 Label correction !V2.0

    V3.D 06/04/00 Evolution of Modbus writing16 bits

    !V2.0

    V3.E 16/03/00 Czech and Hungarianversion delivery

    !V2.0

    V3.G 22/08/00 VDEW improvements !V2.0

    HARD V 3

    HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    7/12

    Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 5/10

    Relay Type P122

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V4.E 31/01/01 Latch of the output relaysLatch of the auxiliary relays,relay by relay and not byfunction (like previously upto V3 version). On the otherhand the latch of the TRIPoutput relay remains byfunction.If the auxiliary relays arelatched,an alarm will be displayed.

    If the user acknowledgesthis alarm, the auxiliaryrelays will be delatched.DNP3 level 2 and 3

    Addition of the tripping andclosing order for IEC103Phase rotation (ABC or

    ACB)Third threshold algorithmfor improvment of thebehaviour on saturatedcurrent transformersTimer for the undercurrentfeature (0 to 150 sec)Tripping curves (rectifiercurve + LABORELLECcurves)Selection of the Settinggroup by level or by edge.CB fail detection (possibilityto inhibit the startingsignals)Instanteneous record

    Rolling demandPeak value demandInstantaneous alarmsettable : self or not selfresetMatrix for the autorecloserThe digital input can workwith AC signals signals (24

    V to 250 V AC)Necessity to set in HMIConfiguration menu, the

    type of voltage used, eitherACor DC

    !V2.0 HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    8/12

    P12x/EN VC/C55 Technical GuideHardware/Software Version

    Page 6/10 MiCOM P120/P121/P122/P123

    Relay Type P122

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V5.A 27/09/01 Maintenance mode formanual command of theoutput relays

    Reset of leds by logic inputor control command orfront panel or on new faultappearance

    Addition of negativesequence protection feature(ANSI code 46) with twothresholds

    Addition of the CBsupervision feature.

    !V2.0

    V5.C 04/10/01 VDEW improvements

    (Updating of theinformation SCN into the

    ASDU END OF GENERALINTERROGATION)

    !V2.0

    V5.D 30/01/02 Addition of orderCOM1/COM2/COM3/CO

    M4 assignalble on theauxiliary relays.

    Addition of the logic inputsAUX3 and AUX 4 do notgenrating alarm message.

    Improvement of englishlabel

    !V2.0

    HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    9/12

    Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 7/10

    Relay Type P122

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V5.F 08/08/02 EA approval option : logicalinput filtering on 24samples instead of 12either 15 ms at 50 Hz)

    Improvment of theRecording of rollingdemand in ram saved. Theprevious version could leadto an untimely ram savederror message due to themanagement of this

    recording

    Courier improvment :adding of the cell 0010 (CBcontrol) protected bypassword

    Correction of theconfiguration of taux3 andtaux4 for MODBUS

    IEC103 : correction of thechecksum calculation for

    short message. Correctionof the I0 channel data intothe disturbance record

    !V2.0 HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    10/12

    P12x/EN VC/C55 Technical GuideHardware/Software Version

    Page 8/10 MiCOM P120/P121/P122/P123

    P123 - Serial number Hardware Correlation

    Serial Number Hardware installed

    From 2599001 to 4799797 HARDWARE VERSION 2

    From 4799798 to 0801999 HARDWARE VERSION 3

    From 0901001 HARDWARE VERSION 4

    Relay Type P123

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V2.J 30/08/99 MODBUS improvement :

    Correction of al

    encountered problem(answer to asynchronisation telegram,creation of a 2 secondstime out )

    HARD V 2

    HARD V 3

    HARD V 4

    V3.B 29/11/99 Suppression of password inorder to acknowledge thealarms

    Auto acknowledgement ofthe instantaneous

    Modbus time out of 200 msDisplay of the letter P in themenu N and N-1 whenpassword is active

    !V2.0

    V3.C 06/01/00 Label correction !V2.0

    V3.D 06/04/00 Evolution of Modbus writing16 bits

    !V2.0

    V3.E 13/04/00 Czech and Hungarianversion delivery

    !V2.0

    V3.G 22/08/00 VDEW improvements !V2.0

    HARD V 3

    HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    11/12

    Technical Guide P12x/EN VC/C55Hardware/Software VersionMiCOM P120/P121/P122/P123 Page 9/10

    Relay Type P123

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V4.E 31/01/01 Latch of the output relaysLatch of the auxiliary relays,relay by relay and not byfunction (like previously upto V3 version). On the otherhand the latch of the TRIPoutput relay remains byfunction. If the auxiliaryrelays are latched, an alarmwill be displayed. If the useracknowledges this alarm,

    the auxiliary relays will bedelatched.DNP3 level 2 and 3

    Addition of the tripping andclosing order for IEC103Phase rotation (ABC or

    ACB)Third threshold algorithmfor improvement of thebehaviour on saturatedcurrent transformersTimer for the undercurrentfeature (0 to 150 sec)Tripping curves (rectifiercurve + LABORELLECcurves)Selection of the Settinggroup by level or by edge.CB fail detection (possibilityto inhibit the startingsignals)Instantaneous recordRolling demand

    Peak value demandInstantaneous alarmsettable : self or not selfresetMatrix for the auto-recloser

    Addition of a secondthreshold with definite timefor the I2 featureThe digital input can workwith AC signals (24 V to250 V AC)

    Necessity to set in HMIConfiguration menu, thetype of voltage used, eitherACor DC .

    !V2.0 HARD V 4

  • 8/13/2019 p12x_envcc55 Hard-Soft Ware

    12/12

    P12x/EN VC/C55 Technical GuideHardware/Software Version

    Page 10/10 MiCOM P120/P121/P122/P123

    Relay Type P123

    SoftwareVersion

    Date ofIssue

    Full Description of ChangesS1Compatibility

    BackwardCompatibility withprevious hardware

    V5.A 27/09/01 Maintenance mode formanual command of theoutput relays

    Reset of leds by logic inputor control command orfront panel or on new faultappearance

    !V2.0

    V5.C 04/10/01 VDEW improvements

    (Updating of theinformation SCN into the

    END OF GENERALINTERROGATION ASDU)

    !V2.0

    V5.D 30/01/02 Addition of orderCOM1/COM2/COM3/COM4 assignalble on theauxiliary relays.

    Addition of the logic inputsAUX3 and AUX 4 do notgenerating alarm message.

    Improvement of english

    label

    !V2.0

    HARD V4

    V5.F 08/08/02 EA approval option : logicalinput filtering on 24samples instead of 12either 15 ms at 50 Hz)Improvment of theRecording of rollingdemand in ram saved. Theprevious version could leadto an untimely ram savederror message due to themanagement of thisrecordingCourier improvment :adding of the cell 0010 (CBcontrol) protected bypasswordCorrection of theconfiguration of taux3 andtaux4 for MODBUSIEC103 : correction of thechecksum calculation for

    short message. Correctionof the I0 channel data intothe disturbance record

    !V2.0 HARD V4