oxiperm® 164 d for 30 to 2000 g/h - sialco · oxiperm® 164 d for 30 to 2000 g/h ... , dosing...

8
GRUNDFOS ALLDOS PRODUCT INFORMATION Oxiperm® 164 D for 30 to 2000 g/h Preparation of chlorine dioxide from diluted solutions

Upload: truongthuy

Post on 04-Jun-2018

216 views

Category:

Documents


1 download

TRANSCRIPT

Page 1: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

GRUNDFOS allDOS product information

oxiperm® 164 d for 30 to 2000 g/hPreparation of chlorine dioxide from diluted solutions

Page 2: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

2

Oxiperm® 164 D / 30 to 2000 g/h

3

Oxiperm® 164 D / 30 to 2000 g/h

Measurements in mm

types / technical datameasurements

technical data

adjustment of the preparation capacity Manual by menu-controlled operator prompting, automatic by input signals

protection level • IP65 Electronics,dosingpumps,solenoidvalve(option),flowmeter• IP44 Bypasspump(option)• P67 Dosingcontroller

admissible concentration of chemicals • HCl 9percentbyweight

• NaClO2 7.5percentbyweight

admissible• ambienttemperature• operationwatertemperature• chemicalstemperature

5to40°C 2to30°C 2to30°C

admissible relative air humidity Max.80%at40°C,notcondensing

Connectiondilutionwaterinlet PVCpipeDN20/option:3/4”NPTmalethread

connection clo2 solution PVCpipeDN20/option:3/4”NPTmalethread

Safety equipment • ParallelmonitoringofcapacityviadosingcontrollerandinternalHallsensorsignalforalldosingpumps

material Supportingrack PPFastening Stainless steelReactor PVCgrey,lacqueredstainlesssteelPostmixer PVCgreyPipes PVCgreyGaskets FPM/PTFE

types

clo2

preparation capacity

pmax

[bar]

consumption of components

[l/h]

Consumptionofbypasswater[l/h] (input pressure < p

max)

Weight type

continuous operation

batch operation *)

0.5 - 2 g/l 2 - 3.3 g/l [kg][g/h] 50 Hz 60 Hz Hcl naclo2

30 10 10 0.7 420 14 14-7.7 33 164-030d (dfi)

120 9 6 2.9 420 55 55-31 34 164-120d (dfi)

220 7 7 5.2 420 100 100-56 34 164-220d (dfi)

350 9 9 8.3 420 160 160-89 57 164-350d

700 9 9 16.5 900 320 320-179 62 164-700d

1000 9 9 24 900 450 450-258 66 164-1000d

1500 9 9 35 900 680 680-383 76 164-1500d

2000 9 6 48 900 900 900-517 82 164-2000d

*) Inbatchoperationtheconcentrationisfreelyadjustablebetween0.5and3.3g/l Between2and3.3g/lthesystemoperatesatfullcapacity.From2downto0.5g/lthesystemreducesthecapacitycontinuously,because thedosingquantityofthechemicalcomponentsisregulatedifthebypasswaterquantityissettoconstant.

Thesesystemsarealsoavailableasfrontinstallationvariants.Theirdesignationis164-xxxDFI.

measurementsFrontinstallationsystem164-xxxDFIStandard system

K

L

HClNaClO2

A

B

FE

C2

D

C1

C

M

HClNaClO2

K

L

G

H

AB

FE

CC1

CC2

M

a B c E f G H K L mconnections

c1 and c2option: npt ¾”

type

700 650 40 800 760 230 148 148 410 ø 11 DN20 164-030d

700 650 40 800 760 230 148 148 410 ø 11 DN20 164-120d

700 650 40 800 760 230 148 148 410 ø 11 DN20 164-220d

950 790 45 900 710 – – 102 213 ø 10 DN20 164-030dfi

950 790 45 900 710 – – 102 213 ø 10 DN20 164-120dfi

950 790 45 900 710 – – 102 213 ø 10 DN20 164-220dfi

760 700 70 1010 970 268 135 181 470 ø 11 DN20 164-350d

760 700 70 1010 970 268 135 181 470 ø 11 DN20 164-700d

760 700 70 1010 970 268 135 181 470 ø 11 DN20 164-1000d

760 700 70 1300 1260 268 135 181 470 ø 11 DN20 164-1500d

760 700 70 1300 1260 268 135 181 470 ø 11 DN20 164-2000d

Page 3: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

2

Oxiperm® 164 D / 30 to 2000 g/h

3

Oxiperm® 164 D / 30 to 2000 g/h

Measurements in mm

types / technical datameasurements

technical data

adjustment of the preparation capacity Manual by menu-controlled operator prompting, automatic by input signals

protection level • IP65 Electronics,dosingpumps,solenoidvalve(option),flowmeter• IP44 Bypasspump(option)• P67 Dosingcontroller

admissible concentration of chemicals • HCl 9percentbyweight

• NaClO2 7.5percentbyweight

admissible• ambienttemperature• operationwatertemperature• chemicalstemperature

5to40°C 2to30°C 2to30°C

admissible relative air humidity Max.80%at40°C,notcondensing

Connectiondilutionwaterinlet PVCpipeDN20/option:3/4”NPTmalethread

connection clo2 solution PVCpipeDN20/option:3/4”NPTmalethread

Safety equipment • ParallelmonitoringofcapacityviadosingcontrollerandinternalHallsensorsignalforalldosingpumps

material Supportingrack PPFastening Stainless steelReactor PVCgrey,lacqueredstainlesssteelPostmixer PVCgreyPipes PVCgreyGaskets FPM/PTFE

types

clo2

preparation capacity

pmax

[bar]

consumption of components

[l/h]

Consumptionofbypasswater[l/h] (input pressure < p

max)

Weight type

continuous operation

batch operation *)

0.5 - 2 g/l 2 - 3.3 g/l [kg][g/h] 50 Hz 60 Hz Hcl naclo2

30 10 10 0.7 420 14 14-7.7 33 164-030d (dfi)

120 9 6 2.9 420 55 55-31 34 164-120d (dfi)

220 7 7 5.2 420 100 100-56 34 164-220d (dfi)

350 9 9 8.3 420 160 160-89 57 164-350d

700 9 9 16.5 900 320 320-179 62 164-700d

1000 9 9 24 900 450 450-258 66 164-1000d

1500 9 9 35 900 680 680-383 76 164-1500d

2000 9 6 48 900 900 900-517 82 164-2000d

*) Inbatchoperationtheconcentrationisfreelyadjustablebetween0.5and3.3g/l Between2and3.3g/lthesystemoperatesatfullcapacity.From2downto0.5g/lthesystemreducesthecapacitycontinuously,because thedosingquantityofthechemicalcomponentsisregulatedifthebypasswaterquantityissettoconstant.

Thesesystemsarealsoavailableasfrontinstallationvariants.Theirdesignationis164-xxxDFI.

measurementsFrontinstallationsystem164-xxxDFIStandard system

K

L

HClNaClO2

A

B

FE

C2

D

C1

C

M

HClNaClO2

K

L

G

H

AB

FE

CC1

CC2

M

a B c E f G H K L mconnections

c1 and c2option: npt ¾”

type

700 650 40 800 760 230 148 148 410 ø 11 DN20 164-030d

700 650 40 800 760 230 148 148 410 ø 11 DN20 164-120d

700 650 40 800 760 230 148 148 410 ø 11 DN20 164-220d

950 790 45 900 710 – – 102 213 ø 10 DN20 164-030dfi

950 790 45 900 710 – – 102 213 ø 10 DN20 164-120dfi

950 790 45 900 710 – – 102 213 ø 10 DN20 164-220dfi

760 700 70 1010 970 268 135 181 470 ø 11 DN20 164-350d

760 700 70 1010 970 268 135 181 470 ø 11 DN20 164-700d

760 700 70 1010 970 268 135 181 470 ø 11 DN20 164-1000d

760 700 70 1300 1260 268 135 181 470 ø 11 DN20 164-1500d

760 700 70 1300 1260 268 135 181 470 ø 11 DN20 164-2000d

Page 4: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

4

Oxiperm® 164 D / 30 to 2000 g/h

5

Oxiperm® 164 D / 30 to 2000 g/h

Suction line systems• 2suctionlineswith2tankcovers• Withemptysignalandpre-alert

tank size ø tank opening Suction line

30 l 45-46mm 1.3m,2.5m,5m

60 l 45-46/57-58.5mm 1.3m,2.5m,5m

200 l 56mm 2.5m,5m

Water extractionmaterial connection

systemconnection watersupply

order number

PVC DN20 G1“ 521-164.2

injection unitmaterial connection

systemconnection

injection unitorder number

PVC DN20 R1“ 522-232

Spare parts setsfor oxiperm® System pressure

less than 3 bar more than 3 bar

164-030D/120D 553-720 553-720.1

164-220D 553-745 553-745.1

164-350D 553-722 553-722.1

164-700D 553-723 553-723.1

164-1000D 553-724 553-724.1

164-1500D 553-725 553-725.1

164-2000D 553-726 553-726.1

accessories

Electrical and electronic data• Mainsvoltage230V/50Hzor115V/60Hz

• Control:PLC

• 4-lineplaintextdisplay

• Menu-controlledoperatorprompting

• Flow-schemewithLEDdisplayshowingmodeanderrorsignal

Powerconsumption • upto220g/h approx.300VA

• from350g/h approx.650VA

analog inputs 0(4)-20mAinputorfreeconfiguration,charge50Ohm

digital inputs • Contactwatermeter,1to45pulses/sec. forcontrol*)

• MINcontactformainwater• RemoteOn/Off• Errorgaswarningunit• PreparationtankClO

2:overflow,MAX,MIN,dryrun

analog outputs 0(4)-20mAinputorfreeconfiguration, max.charge500Ohm

potential-free outputs

• Errormessages• Pre-alert:chemicalsempty• DryrunClO

2solutiontank(batchsystems)

• Automatic/manualoperation max.charge250V,6A,max.550VA

*) note: Thewatermeterhastobedesignedinawaythatthenumberofinputpulsesforthecontrolisbetween1-45pulses/sec.

Versionscheck valve (reactor)

• Systembackpressurelessthan3bars• Systembackpressuremorethan3bars

Systemcompletelyforwallmounting

options• Withsolenoidvalve,with/withoutexhaustsystem

• Forbatchoperation,with/withoutexhaustsystem

• Withinternalbypasspump,with/withoutexhaustsystem

• Withexternalcentrifugalpump(providedbythecustomer), with/withoutexhaustsystem

Bus system

• Modbus(RS232/RS485)

• ProfibusDPmodule(onrequest)

• EthernetTCP/IPmodule(onrequest)

operating languages

Standard:German

Otherlanguagescanbeselectedwiththesoftware:

• English,French,Spanish,Italian

data

Page 5: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

4

Oxiperm® 164 D / 30 to 2000 g/h

5

Oxiperm® 164 D / 30 to 2000 g/h

Suction line systems• 2suctionlineswith2tankcovers• Withemptysignalandpre-alert

tank size ø tank opening Suction line

30 l 45-46mm 1.3m,2.5m,5m

60 l 45-46/57-58.5mm 1.3m,2.5m,5m

200 l 56mm 2.5m,5m

Water extractionmaterial connection

systemconnection watersupply

order number

PVC DN20 G1“ 521-164.2

injection unitmaterial connection

systemconnection

injection unitorder number

PVC DN20 R1“ 522-232

Spare parts setsfor oxiperm® System pressure

less than 3 bar more than 3 bar

164-030D/120D 553-720 553-720.1

164-220D 553-745 553-745.1

164-350D 553-722 553-722.1

164-700D 553-723 553-723.1

164-1000D 553-724 553-724.1

164-1500D 553-725 553-725.1

164-2000D 553-726 553-726.1

accessories

Electrical and electronic data• Mainsvoltage230V/50Hzor115V/60Hz

• Control:PLC

• 4-lineplaintextdisplay

• Menu-controlledoperatorprompting

• Flow-schemewithLEDdisplayshowingmodeanderrorsignal

Powerconsumption • upto220g/h approx.300VA

• from350g/h approx.650VA

analog inputs 0(4)-20mAinputorfreeconfiguration,charge50Ohm

digital inputs • Contactwatermeter,1to45pulses/sec. forcontrol*)

• MINcontactformainwater• RemoteOn/Off• Errorgaswarningunit• PreparationtankClO

2:overflow,MAX,MIN,dryrun

analog outputs 0(4)-20mAinputorfreeconfiguration, max.charge500Ohm

potential-free outputs

• Errormessages• Pre-alert:chemicalsempty• DryrunClO

2solutiontank(batchsystems)

• Automatic/manualoperation max.charge250V,6A,max.550VA

*) note: Thewatermeterhastobedesignedinawaythatthenumberofinputpulsesforthecontrolisbetween1-45pulses/sec.

Versionscheck valve (reactor)

• Systembackpressurelessthan3bars• Systembackpressuremorethan3bars

Systemcompletelyforwallmounting

options• Withsolenoidvalve,with/withoutexhaustsystem

• Forbatchoperation,with/withoutexhaustsystem

• Withinternalbypasspump,with/withoutexhaustsystem

• Withexternalcentrifugalpump(providedbythecustomer), with/withoutexhaustsystem

Bus system

• Modbus(RS232/RS485)

• ProfibusDPmodule(onrequest)

• EthernetTCP/IPmodule(onrequest)

operating languages

Standard:German

Otherlanguagescanbeselectedwiththesoftware:

• English,French,Spanish,Italian

data

Page 6: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

6

Oxiperm® 164 D / 30 to 2000 g/h

7

Oxiperm® 164 D / 30 to 2000 g/h

oxiperm® 164 c withsolenoidvalve

oxiperm® 164 c Batch operation

oxiperm® 164 c withinternalbypasspump

1 oxiperm® 164 d electronics 2 Connectionforbypasswaterinput 3 ConnectionfortheClO

2 solution line output to the

injectionunit 4 SuctionlinefortheHCldosingpump 5 SuctionlineforNaClO

2 dosing pump

6 Shutt-offvalve(bycustomer) 7 Sampleextraction(bycustomer) 8 Checkvalve(bycustomer),

foroperationwithaninternalbypasspump 9 Shut-offvalveforbypasswaterextraction(by

customer)10 Exhaustsystemforsupportingrack(option)11 Dilutiontankwithlevelmonitoring(option)

for batch operation12 Pressureloadingvalves(bycustomer)forsystem

backpressures < 1 bar13 Inductiveflowmeter4-20mAorcontactwater

meterforproportionalcontrolofthesystem

note: Forprotectionofthedrinkingwatersupply,thecustom-erhastoprovideapipedisconnector(toDVGW,W624).

Installationdrawings

HClNaClO2ClO2

11

36

1

10

54

9

2

67

3

1

10

54

2

9

13

12

HClNaClO2

8 139

1

67

10

54

2

3

HClNaClO2

Page 7: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

6

Oxiperm® 164 D / 30 to 2000 g/h

7

Oxiperm® 164 D / 30 to 2000 g/h

oxiperm® 164 c withsolenoidvalve

oxiperm® 164 c Batch operation

oxiperm® 164 c withinternalbypasspump

1 oxiperm® 164 d electronics 2 Connectionforbypasswaterinput 3 ConnectionfortheClO

2 solution line output to the

injectionunit 4 SuctionlinefortheHCldosingpump 5 SuctionlineforNaClO

2 dosing pump

6 Shutt-offvalve(bycustomer) 7 Sampleextraction(bycustomer) 8 Checkvalve(bycustomer),

foroperationwithaninternalbypasspump 9 Shut-offvalveforbypasswaterextraction(by

customer)10 Exhaustsystemforsupportingrack(option)11 Dilutiontankwithlevelmonitoring(option)

for batch operation12 Pressureloadingvalves(bycustomer)forsystem

backpressures < 1 bar13 Inductiveflowmeter4-20mAorcontactwater

meterforproportionalcontrolofthesystem

note: Forprotectionofthedrinkingwatersupply,thecustom-erhastoprovideapipedisconnector(toDVGW,W624).

Installationdrawings

HClNaClO2ClO2

11

36

1

10

54

9

2

67

3

1

10

54

2

9

13

12

HClNaClO2

8 139

1

67

10

54

2

3

HClNaClO2

Page 8: oxiperm® 164 d for 30 to 2000 g/h - SIALCO · oxiperm® 164 d for 30 to 2000 g/h ... , dosing pumps,2 solenoid valve (option), flowmeter ... 5 to 40 °C 2 to 30 °C

BeingresponsibleisourfoundationThinkingaheadmakesitpossible

Innovationistheessence

Subjecttochange91834789 0108En

15.810017 V7.0

© Grundfos alldos dosing & disinfection

ALLDOSEichlerGmbH

www.grundfosalldos.com