OWNER:
SET NUMBER
COVER SHEETINDEX OF DRAWINGS
LB0
SITE-WIND ZONE PLAN / LB1
THE BOARD OF REGENTSTHE UNIVERSITY OF TEXAS SYSTEM
PARTIAL ROOF PLANLB2
PARTIAL ROOF PLAN / ROOFING DETAILSLB3
ROOFING DETAILSLB4
ROOFING DETAILSLB5
ROOFING DETAILSLB6
FALL PROTECTION PLAN / DETAILSS1
AUSTIN, TEXAS
OWNER'S REPRESENTATIVE:
REUBEN PINKSON, ARCHITECT - FACILITIES MANAGEMENTU. T. HEALTH SCIENCE CENTER - SAN ANTONIO7703 FLOYD CURL DRIVESAN ANTONIO, TEXAS 78284-7957
ROOFING CONSULTANTS:
HOLLON+CANNON GROUP, LLC12885 RESEARCH BLVD, SUITE 210BAUSTIN, TEXAS 78750(512) 300-0452
ROOFING SCHEDULES
LIBRARYBUILDING
EXISTING ROOF ASSEMBLY SCHEDULE
SECTION:
2.0" EPS INSULATIONSTRUCTURAL CONCRETE DECK
L1aROOF
SINGLE-PLY MEMBRANE
METAL DECKING
L1b, L1c, L1d, L2 and L3SECTIONS:ROOF
STONE BALLAST
2.5" EPS INSULATION
L4 thru L13SECTIONS:ROOF
STRUCTURAL CONCRETE
SINGLE-PLY MEMBRANESTONE BALLAST
NEW ROOF ASSEMBLY SCHEDULE
SECTION: L1aROOF
REMOVE EXISTING ROOFING TO STRUCTURAL CONCRETE DECK
2-PLY MODIFIED BITUMEN ROOF MEMBRANE TORCH APPLIED1/2" GYPSUM COVER BOARD SET IN ADHESIVE
REMOVE EXISTING COATING TO CONCRETE DECK
L4 thru L13SECTION:ROOF
1-PLY MODIFIED BITUMEN MEMBRANE
PREPARE EXISTING CONCRETE PER MANUFACTURER'SRECOMMENDATIONS
1/8" / FT. TAPERED POLYISOCYANURATE INSULATION W/ 3.5" STARTING THICKNESS SET IN ADHESIVE
L1b, L1c, L1d, L2 and L3SECTIONS:ROOF
2-PLY MODIFIED BITUMEN ROOF MEMBRANE TORCH APPLIED1/2" GYPSUM COVER BOARD SET IN ADHESIVE
1/8" / FT. TAPERED POLYISOCYANURATE INSULATION W/ 3.5"STARTING THICKNESS SET IN ADHESIVE
REMOVE EXISTING ROOFING TO METAL DECKPOLYISOCYANURATE FILL INSULATION AS REQ'D TO MATCHTOP SURFACE OF ADJACENT CONCRETE DECK MECHANICALLYFASTENED
SYMBOLS LEGEND
SYMBOL LABEL DESCRIPTION DETAIL
PS PENETRATION FL'G 1/LB4
RD PRIMARY ROOF DRAIN 9/LB4
EF EXHAUST FAN 3/LB4
OSC OVERFLOW SCUPPER 6/LB3, 8/LB5
C CONDENSATE LINE 8/LB4
E ELECTRICAL LINE SECTIONG GAS LINE 07 7200 00
NOT IN CONTRACT
TRAFFIC PAD
slope DRAINAGE SLOPE
TAPERED CRICKET
VTR PLUMBING VENT 2/LB4
FP FALL PROTECTION 4/LB5
HS HOT STACK 6/LB4
WIND UP-LIFT PRESSURES AND PERIMETER DIAGRAM
MEAN ROOF HEIGHT< 60 ft.
ZONE 1 FIELD=ZONE 2 PERIMETER=ZONE 3 CORNER=
a = 10% OF LEAST HORIZONTAL DIMENSIONOF BUILDING, OR 0.4 h, WHICHEVER IS
OF LEAST HORIZONTAL DIMENSION OR 3 ft.SMALLER, BUT NOT LESS THAN EITHER 4%
ZONE 1
MEAN ROOF HEIGHT> 60 ft.
FIELD=ZONE 2ZONE 3
PERIMETER=CORNER=
a = 10% OF LEAST HORIZONTAL DIMENSIONOF BUILDING, BUT NOT LESS THAN 3 ft.
(CONTRACTOR SHALL VERIFY ASSUMPTIONS W/ MANUFACTURER)DESIGN ASSUMPTIONS
BEXPOSURE CATEGORY
3
90 MPHBASIC WIND SPEED =
PARTIALLY ENCLOSEDCLASSIFICATION OF ENCLOSURE =
=
1.15OCCUPANCY IMPORTANCE FACTOR =
1TOPOGRAPHIC FACTOR =
BLD'G HEIGHT
WIND UPLIFT PRESSURES (PSF)(CONTRACTOR SHALL VERIFY PRESSURES W/ MANUFACTURER)
FIELD PERIMETER CORNER
0 to 30'-0" 27 39 56
30'-0" to 40'-0'' 28 43 61
40'-0" to 50'-0'' 30 46 64
DESIGN UPLIFT PRESSURE (PSF)INSTALLED WIND UPLIFT RESISTANCE VALUES SHALL BE TWO (2.0) TIMES THE SPECIFIED
WIND UPLIFT PRESSURES
3
aa
2
3
3
2
2
1
SAMPLE PLAN VIEW OF ROOF
3
2a
2a2
2
3
2
3
1
2
SAMPLE PLAN VIEW OF ROOF
2
3
GENERAL NOTES TO CONTRACTOR
GENERAL NOTES:
1. CONTRACTOR SHALL VERIFY OPERATIONAL STATUS OF ROOF TOP EQUIPMENT W/ OWNER.ABANDONED EQUIPMENT AND CURBS SHALL BE REMOVED FROM THE BUILDING. AND DISPOSED OF. REPAIR DECKING AT ABANDONED PENETRATIONS (NOT SCHEDULED ON
2. EXISTING GAS, CONDENSATE, ELECTRICAL, HYDRONIC PIPING, ETC. SHALL BEDISCONNECTED, RAISED AND RECONNECTED AS REQ'D TO ACCOMMODATE NEW ROOFSYSTEM THICKNESS AND MEMBRANE FLASHING HEIGHT REQUIREMENTS.
1. PROVIDE PIPE SUPPORTS PER DETAIL 8/LB4 AT "SMALL" CONDUIT / PIPING, UNLESS OTHERWISE INDICATED ON ROOF PLAN. SEE SPECIFICATION SECTION 07 7200 00 FOR
3. EXISTING ROOF TOP EQUIPMENT SHALL BE DISCONNECTED RAISED AND RECONNECTEDAS REQ'D TO PROVIDE MEMBRANE BASE FLASHING HEIGHTS SPECIFIED.
EQUIPMENT / PIPING SUPPORTS:
1. PROVIDE TRAFFIC PROTECTION PADS AT ROOF ACCESS POINTS AND ON ALL SIDES OFROOF TOP UNITS.
TRAFFIC PROTECTION:
THE DRAWINGS FOR REMOVAL) PER UNIT PRICING, DETAILS AND SPECIFICATIONS.
DRAINAGE:
1. CRICKETS / SADDLES SHALL BE TWICE THE ADJACENT ROOF SLOPE
ROOF TOP EQUIPMENT / PENETRATIONS:
1. CONTRACTOR SHALL VERIFY FIELD DIMENSIONS.
2. PROVIDE TAPERED CRICKETS ON HIGH SIDE OF CURBED PENETRATIONS AS REQ'D TODIRECT DRAINAGE AROUND PENETRATION.
2. FIELD MEASUREMENTS ARE REQUIRED FOR BIDDING PURPOSES.
4. EXISTING DUCT WORK SHALL BE DISCONNECTED, RAISED AND RECONNECTED AS REQ'D TO ACCOMMODATE NEW ROOF SYSTEM THICKNESS AND MEMBRANE FLASHING HEIGHT REQUIREMENTS.
DEFINITION OF "SMALL" CONDUIT / PIPING.
3. CONTRACTOR IS RESPONSIBLE FOR VERIFICATION OF EXISTING ROOFING SYSTEM.
L1a
L2
L3
L1b L1c
L1d
SITE PLAN / KEY PLAN / WIND ZONE PLAN - LIBRARY BUILDINGNOT TO SCALE
PLAN NORTH
CORNER(ZONE 3)
PERIMETER(ZONE 2)
FIELD(ZONE 1)
1/2" GYPSUM BOARD
KEYED NOTES TO CONTRACTOR
1 PROVIDE NEW BACKER ROD AND SEALANT AT INTERIOR / EXTERIOR CONTROL JOINTS PER DETAIL 3/LB5.
2 FIELD VERIFY SCUPPER LOCATIONS WITH ARCHITECT
3 LOWER FLASHING / EXPANSION JOINT CURB BELOW STEELSUPPORT ANCHOR PER DETAIL 2/LB6
4 REMOVE CABLE PENETRATION THROUGH BASE FLASHING.REMOVE CABLE RUN FROM ROOF SURFACE.OWNER TO RETAIN CABLING AND ACCESSORIES.
MONOLITHIC RESIN MEMBRANE
COATING
1. PROVIDE ISOLATION TAPE BETWEEN TREATED WOOD BLOCKING AND METALCOMPONENTS, WHETHER SHOWN IN DRAWINGS OR NOT.
TREATED WOOD BLOCKING
12/21/2012DATE:
SHEET:
LB1OF
6
PCCCHECKED BY:
CANNON J.DRAWN BY:
1.
REVISION SCHEDULE:
ISSUE FOR BID 12/21/122.3.4.5.6.7.
hollongroup, llc
+hg c
+cannon
KEY PLAN / SITE PLANROOFING SCHEDULES
UT
HE
ALT
H S
CIE
NC
E C
EN
TER
at S
AN
AN
TON
IOR
EP
LAC
EM
EN
T of
Roo
f at
DO
LPH
BR
ISC
OE
JR
. LIB
RA
RY
RO
OF
San
Ant
onio
, Tex
as 7
8229
HYD
HS HS HS
HYD
LIBRARY - SECTIONS L1, L2, L31/8" = 1'-0''SCALE:
PLAN NORTH
1
LB2
ROOF PLAN
L1a
L2
L3
L1b
L1c
L1d
RD RD
RD
RD RD RD RD
RDRDRDRD
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
slopeslope
ODOD
OD OD OD
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
1/8'
'/ft
. TA
PERE
DIN
SUL
ATI
ON
1/8''/ft. TAPEREDINSULATION
slopeslope
DS
DS
PS
ABAND.
RH
EF
EF
VTR
VTR
EF
PSPSPS
FP
FP
PS
PS
PS
PS
FP
FP
FP
FP
FP
FP
FPEF
EF
VTR
VTR
VTR
VTR
VTR
VTR
FPFP
PS
PS
FP
FP
VTR
EF
VTR
LB410
ROOF HATCH PERDETAIL 5/LB4
LINE OF METALDECKING
LB57 SIM.
LB57SIM.LB5
7SIM.
LB57
SIM.
LB34
LB57
LB57
LB57
LB57
LB57
LB57
LB57
LB57
LB46TYP.
LB61TYP.
OD
LB54TYP.
EF
SPLASH PAN PERDETAIL 7/LB4
LB43TYP.
LB42TYP.
LB49TYP.
LB57
EXIST. HYDRANT TO BE EXTENDED BY OWNER.PROVIDE ROOF FLASHING PER DETAIL 1/LB4 - SIM.
LB410
LINE OF METALDECKING
(SHOWN DASHED)(SHOWN DASHED)LB57
LB54 TYP.
RD
LB49TYP.
LB42TYP.
LB41 TYP.
LB61TYP.
OD
ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3
ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3
ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3
ROOF LINE BELOWSEE ENLARGED PLAN SHEET LB3
LINE OF METALDECKING(SHOWN DASHED)
SPLASHPAN PERDETAIL 7/LB4
LB55
(HIGH ROOF)TYP. @ "L2"
LB56
(LOW ROOF)TYP. @ "L1"
LB56
(LOW ROOF)TYP. @ "L1"
LB55
(HIGH ROOF)TYP. @ "L3"
LB34
LB34
EXP.
JT.
EXP. JT.
LB34
EXP.
JT.
OSC
NEW OVERFLOW SCUPPERPER DETAIL 6/LB3
NEW OVERFLOW SCUPPERPER DETAIL 6/LB3
OSCNEWNEW
OSCNEW
OSCNEW
NEW OVERFLOW SCUPPERPER DETAIL 6/LB3
NEW OVERFLOW SCUPPERPER DETAIL 6/LB3
EXIST. HYDRANT TO BE EXTENDED BY OWNER. PROVIDE ROOF FLASHINGPER DETAIL 1/LB4 - SIM.
OSC
NEW OVERFLOW SCUPPERPER DETAIL 6/LB3NEW
NEW OVERFLOW SCUPPERPER DETAIL 6/LB3
OSCNEW
OSCNEW
SIM.
NEW OVERFLOW SCUPPERPER DETAIL 8/LB5
NEWFP
NEWFP
NEW FALL PROTECTION ANCHORSRE: STRUCTURAL. PROVIDE ROOF FLASHINGPER DETAIL 1/LB4
1
1
1
22
22
22
SKYLIGHTABAND.SKYLIGHT
3 TYP.
3TYP.
3TYP.
4
444
CRICKET SLOPE @ TWICE ROOF SLOPETYPICAL
12/21/2012DATE:
SHEET:
LB2OF
6
PCCCHECKED BY:
CANNON J.DRAWN BY:
1.
REVISION SCHEDULE:
ISSUE FOR BID 12/21/122.3.4.5.6.7.
hollongroup, llc
+hg c
+cannon
ROOF PLAN
UT
HE
ALT
H S
CIE
NC
E C
EN
TER
at S
AN
AN
TON
IOR
EP
LAC
EM
EN
T of
Roo
f at
DO
LPH
BR
ISC
OE
JR
. LIB
RA
RY
RO
OF
San
Ant
onio
, Tex
as 7
8229
LIBRARY - SECTIONS 1/8" = 1'-0''SCALE:
PLAN NORTH
1
LB3
PARTIAL ROOF PLAN (4TH FLOOR)
LIBRARY - SECTIONS 1/8" = 1'-0''SCALE:
PLAN NORTH
2
LB3
PARTIAL ROOF PLAN (3RD FLOOR)
(INTERIOR SPACE)
(INTERIOR SPACE)
LIBRARY - SECTIONS 1/8" = 1'-0''SCALE:
PLAN NORTH
3
LB3
PARTIAL ROOF PLAN (2ND FLOOR)
(INTERIOR SPACE)
L4 L5 L6 L7
L8 L9 L10
L11 L12 L13
FLASHING AT ROOF EDGEPER DETAIL 4/LB6 TYP.
SHELF ROOF BELOW PERPLAN 2/LB3
SHELF ROOF BELOW PERPLAN 2/LB3
DRAIN DRAIN DRAIN DRAIN
DRAIN DRAIN DRAIN
DRAIN DRAIN DRAIN
FLASHING AT WINDOWPER DETAIL 3/LB6 - TYP.
FLASHING AT WINDOWPER DETAIL 3/LB6 - TYP.
FLASHING AT ROOF EDGEPER DETAIL 4/LB6 TYP.
FLASHING AT ROOF EDGEPER DETAIL 4/LB6 TYP.
FLASHING AT WINDOWPER DETAIL 3/LB6 - TYP.
1/2'' COVER BOARD
ROOF SYSTEM
BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.
CANT STRIP
3" = 1'-0"PARAPET4
LB3
TAPERED POLYISO. (THICKNESS VARIES)
POLYISOCYANURATE
3/4" PLYWOOD
EXIST. STRUC. CONC. DECK
SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.
24 GA. PRE-FINISHED CONT. CLEAT
1" 2" 1"3"8"
-MIN
.
24 GA. PRE-FINISHED EXP. JT. COVERSELF-ADHERING UNDERLAYMENT24 GA. PRE-FINISHED COUNTERFLASHINGSCREWS @ 16'' O.C.24 GA. PRE-FINISHED RECEIVER
DRIVE-PINS W/ NEOPRENE WASHERS@ 16'' O.C.
CONT. SEALANTEXIST. PARAPET
1'' STANDING SEAM PER DETAIL 1/LB5
DRIVE-PINS W/ NEOPRENE WASHERS @ 16'' O.C.
22 GA. GALV. CONT. CLEATSELF-ADHERING UNDERLAYMENT
EXIST. TILE EXTERIOREXIST. CONC. PARAPET
24 GA. PRE-FINISHED COPING
3" = 1'-0"PARAPET COPING5
LB3
NOTE: SEE DETAIL 4/LB3 FOR PARAPET
3"
4"
FLASHING BELOW
NOTE: SEE DETAIL 5/LB3 FOR COPING ABOVE
3" = 1'-0"SCUPPER6
LB3
EXIST. STRUC. CONC. DECK
NOT TO SCALEELEVATION - CLOSUREA
2'' SEE SCHEDULE 2"
2"4"
2"
NOT TO SCALEISOMETRICB
24 GA. PRE-FINISHED CLOSURE PLATE SET
PROVIDE NEW SCUPPER OPENING THRU EXIST PARAPET AS REQ'D
4" 1/2''-MIN.
2''
4"-M
IN.
EXIST. CONCRETE PANEL
DRIVE-PINS W/ NEOPRENE WASHERS
DRIVE-PINS W/ NEOPRENE WASHERS@ EA CORNER
24 GA. GALV. SCUPPER SLEEVESOLDER ALL JOINTS WATERTIGHT
1/2'' COVER BOARDROOF SYSTEM
1/4'' COVER BOARD2X TRT'D WD. CANT (@ SCUPPER ONLY)
NOTE:1. PARAPET / WALL EXPANSION JOINT NOTES PER DETAIL 4/LB32. SCUPPER FLOW LINE SHALL BE 2" ABOVE
EDGE OF PRIMARY DRAINAGE DEVISE
2"
4"3"
1/4'' COVER BOARDMEMBRANE STRIP-IN PLYMEMBRANE BASE FLASHING
1" 2" 1"
EXIST. TILE
IN SEALANT
@ EA CORNER
TRT'D WD. BLK'G TO MATCH HT. OF INSULATION ANCHOR TO DECK
POLYISOCYANURATE
TAPERED POLYISO
@ 6'' O.C.
FLEXIBLE VAPOR RETARDER W/ COMPRESSIBLE INSULATION
4"X6" CONT. STL. ANGLE ANCHORED TOCURB AND DECK @ 24'' O.C. - STAGGERED
2X TRT'D WD. CURB AS REQ'D TO PROVIDE FLASHING HT.
1"1"
FIEL
DV
ERIF
Y
EXIST.
SCUPPER SIZES
SCUPPER DIMENSIONS
4" x 24"
12/21/2012DATE:
SHEET:
LB3OF
6
PCCCHECKED BY:
CANNON J.DRAWN BY:
1.
REVISION SCHEDULE:
ISSUE FOR BID 12/21/122.3.4.5.6.7.
hollongroup, llc
+hg c
+cannon
PARTIAL ROOF PLANSROOFING DETAILS
UT
HE
ALT
H S
CIE
NC
E C
EN
TER
at S
AN
AN
TON
IOR
EP
LAC
EM
EN
T of
Roo
f at
DO
LPH
BR
ISC
OE
JR
. LIB
RA
RY
RO
OF
San
Ant
onio
, Tex
as 7
8229
3" = 1'-0"PENETRATION FLASHING1
LB4 3" = 1'-0"VENT THRU ROOF2
LB4 3" = 1'-0"FLANGED VENT4
LB43" = 1'-0"MECHANICAL CURB3
LB4
EXISTING OR NEW RIGID PENETRATION
NOTE:1. CONDUIT PENETRATING ROOFING ASSEMBLY SHALL BE RIGID CONDUIT. CONTRACTOR
2. CONDUIT SHALL BE ONE CONTINUOUS PIECE FROM UNDERSIDE OF DECK EXTENDINGMIN. 6" ABOVE PENETRATION SEAL. ANCHOR TO DECK OR NEAREST STRUC. FRAMING ASREQ'D TO ELIMINATE MOVEMENT.
SHALL REPLACE ALL FLEXIBLE OR DAMAGED PENETRATIONS W/ RIGID CONDUIT
REMOVE ASPHALTIC CONTAMINATES FROM PENETRATION PRIOR TO INSTALLATION OF PENETRATION SEAL
1/2" COVER BOARD
EXISTING DECKING
POLYISOCYANURATE
OR SEALANT
3. MINIMUM 1'' SPACE IS REQUIRED BETWEEN PENETRATIONS AND INTERIOR WALL OFPENETRATION CURB AND BETWEEN MULTIPLE PENETRATIONS. REROUTE PENETRATIONSAS REQUIRED TO PROVIDE MINIMUM 1" SPACING REQUIRED
BIRD SCREEN
8"
4"1/2"MIN.
EXISTING FLUE EXTEND AS NECESSARY
24 GA. GALV. VENT FLASHINGFULLY SOLDER JOINTS WATERTIGHT
EXISTING DECKING
POLYISOCYANURATE
24 GA. GALV. VENT CAPPROVIDE CAP TO MATCH EXIST.
1/2'' COVER BOARDROOF SYSTEMSTRIP-IN PLY
COVER BD. ANCHOR TO DECK W/TRT'D WD. BLK'G TO MATCH HT. OF
2" MIN
.
APPROPRIATE FASTENERS @ 6'' O.C.
VENT STACK EXTENSION AS REQ'D
CONT. SEALANT
NOTE:1. PRIME VENT FLANGE, SET IN MASTIC AND NAIL AT 3" O.C. - STAGGERED
EXIST. CURB
24 GA. GALV. SLIP FLASHING
EXISTING MECHANICAL HOOD
PROVIDE MIN. 8'' FLASHING HEIGHTTRT'D 2X CURB EXTENSION
DO NOT MODIFY - DAMAGEDCOMPONENTS SHALL BE REPLACED
3"
8"-M
IN.
EXISTING DECKING
POLYISOCYANURATE
1/2'' COVER BOARDROOF SYSTEM
BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY
1/4'' COVER BD.
1/4'' COVER
CANT STRIP
@ 12'' O.C. (MIN. 2 PER SIDE)SCREWS W/ NEOPRENE WASHERS
NOTE:1. EXTEND EXISTING CURB W/ TRT'D 2X BLK'G AND SIMPSON "A24" ANGLES, OR APPROVED EQUAL,
SPACED AT 12" O.C.
BOARD
EXISTING STACKEXTEND AS NECESSARY TO PROVIDE 8" HEIGHT
1"
8''-M
IN.
4''-MIN.
2. REMOVE VENT EXTENSION / GOOSE NECK, WERE EXISTING, AS REQ'D TO INSTALL NEWLEAD FLASHING. REINSTALL IN CONT. BEAD OF SEALANT
4# LEAD FLASHING - FOLD INTOTOP OF STACK MIN. 1"
CONT. SEALANT
PVC VENT EXTENSION(IF NECESSARY)
CONT. SEALANT
ROOF SYSTEM
STRIP-IN PLY
1/2'' COVER BOARD
NOTE:1. PRIME LEAD FLANGE AND SET IN MASTIC
3"
24 GA. STAINLESSSTEELSLEEVE
EXISTING DECKING
POLYISOCYANURATE
MONOLITHIC RESIN FLASHINGAS PRODUCED BY THE MEMBRANEMANUFACTURERROOF SYSTEM
GRANULAR SURFACEDTRAFFIC PAD 2" LARGERTHAN SUPPORTSET PAD IN FULL BED OF FLASHING CEMENT
ADJUSTABLE HEIGHT PIPE SUPPORTADHERE TO TRAFFIC PAD W/ SEALANT
3" = 1'-0"PIPE SUPPORT8
LB4
NOTE:1. DISCONNECT, RAISE AND RECONNECT EXISTING GAS LINES, ELECTRICAL LINES, ETC.
2. SPACE PIPE SUPPORTS @ 8'-0" O.C.
AS REQ'D TO ACCOMMODATE HEIGHT OF PIPE SUPPORT.
3. PROVIDE PIPE SUPPORTS WITHIN 12"-18" OF CORNERS AND/OR TEE INTERSECTIONS
4. PROVIDE PIPE RETAINER BRACKETS (NOT SHOWN)
EXISTING STRUC. CONC. DECK
TRT'D WD. BETWEEN DRAINBOWL AND DECK
EXIST. UNDERDECK CLAMP
1/2'' COVER BOARD
MEMBRANE BASE PLYMEMBRANE CAP SHEET
MEMBRANE STRIP-IN PLY
1/2"/FT. TAPERED POLYISOCYANURATE SUMP W/ 2'' STARTING THICKNESS(SEE PLAN VIEW FOR OVERALL SIZE)
36"X 36" LEAD SHEET FLASHINGDRAIN CLAMPING RINGNEW DRAIN STRAINERPOLYISOCYANURATE1/2" COVER BOARD
3'-0"
3.5"
3" = 1'-0"PRIMARY ROOF DRAIN9
LB4
NOT TO SCALEROOF DRAIN - PLAN VIEWA
slsl
slsl
6'-0"TYP. ALL SIDES
1/2"/FT. TAPEREDSUMP
CRICKET
NOTE:1. REPLACE MISSING OR DAMAGED COMPONENTS W/ NEW CAST IRON COMPONENTS
2. REPLACE ALL PLASTIC / NONMETAL COMPONENTS W/ NEW CAST IRON COMPONENTS
3. RAISE OR LOWER DRAIN BOWL AS REQ'D TO MATCH HEIGHT SHOWN BELOW
4. LEAD SHEET FLASHING - PRIME ALL SURFACES AND SET IN FULL BED OF MASTIC
EXIST. DRAIN LINE - MODIFY AS REQ'D TO ACCOMMODATE CHANGE IN DRAIN BOWL ELEVATION
DOWNSPOUT
24 GA. GALV. SPLASH PANADHERE TO TRAFFIC PAD W/ SEALANT
GRANULAR SURFACEDTRAFFIC PAD 2" LARGERTHAN SPLASH PAN
24 GA. X 1" GALV.STRAP POP-RIVETTO DS AND SPLASH PAN
SET PAD IN FULL BED OF FLASHING CEMENT
3" = 1'-0"SPLASH PAN7
LB4
24 GA. GALV. 1'' TALLRIBS SOLDERED TOSPLASH PAN
NOT TO SCALEPLAN VIEWA
24 GA. GALV. SPLASH PANADHERE TO TRAFFIC PAD W/ SEALANT
30"
12"
18"
TRAFFIC PAD
NOT TO SCALEISOMETRICA NOT TO SCALE
PLAN VIEWC
24 GA. GALV. SPLASH PANADHERE TO TRAFFIC PAD W/ SEALANT
TRAFFIC PADGRANULAR SURFACED
ROOF LINE
PROVIDE 45° BREAK @ BACKOF SPLASH PAN AS REQ'D TOFIT TIGHT AGAINST CANT STRIP
LINE OF CANT / BASE FLASHING
3" = 1'-0"HOT STACK6
LB43" = 1'-0"ROOF HATCH5
LB4
EXISTING FLUE EXTEND AS
24 GA. GALV. VENT BASEFULLY SOLDER JOINTS WATERTIGHT
EXISTING
1/2'' COVER BOARDROOF SYSTEMSTRIP-IN PLYCONT. SEALANT
4"1/2"MIN.
24 GA. GALV. UMBRELLAFULLY SOLDER JOINTS WATERTIGHT
STAINLESS STEEL CLAMPINGDRAW BAND
CONT. SEALANT
NECESSARY
8''-M
IN.
2"-M
IN.
NOTE:1. PRIME VENT BASE
FIELD VERIFY 1" MIN. ALL SIDES
FLANGE, SET IN MASTIC AND NAIL AT 3" O.C. - STAGGERED
POLYISOCYANURATE
1/2'' COVER BOARDROOF SYSTEM
BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.
CANT STRIP
POLYISOCYANURATE
POLYISOCYANURATE
ANCHOR TOP OF BASE FLASHING
EXIST. ROOF HATCHANCHOR TO BLK'G @ 12'' O.C.
8''-M
IN.
DECKING
EXISTING DECKING
COVER BD. ANCHOR TO DECK W/TRT'D WD. BLK'G TO MATCH HT. OF
APPROPRIATE FASTENERS @ 12'' O.C. COVER BD. ANCHOR TO DECK W/TRT'D WD. BLK'G TO MATCH HT. OF
APPROPRIATE FASTENERS @ 6'' O.C.
3" = 1'-0"SKYLIGHT10
LB4
EXTENSION PROVIDE TRT'D 2X CURB
1/2'' COVER BOARDROOF SYSTEM
BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.
CANT STRIP
MIN. 8'' FLASHINGHEIGHT TAPERED POLYISO
(THICKNESS VARIES)
POLYISOCYANURATE
EXIST. METAL DECK
EXIST. CURB
EXIST. SHEATHING
8"-M
IN.
3'' POLYISOCYANURATE INSULATION ADHERED
2X4'S W/ JOIST HANGERS @ 24'' O.C.
SELF-ADHERING UNDERLAYMENT
3/4'' PLYWOOD NAILED @ 8'' O.C.
3"
SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.
24 GA. GALV. CURB COVERPROVIDE POSITIVE DRAINAGE
TO BOTTOM OF PLYWOOD.
NOTE:1. EXTEND EXISTING CURB W/ TRT'D 2X BLK'G AND SIMPSON "A24" ANGLES, OR APPROVED EQUAL,
SPACED AT 12" O.C.
12/21/2012DATE:
SHEET:
LB4OF
6
PCCCHECKED BY:
CANNON J.DRAWN BY:
1.
REVISION SCHEDULE:
ISSUE FOR BID 12/21/122.3.4.5.6.7.
hollongroup, llc
+hg c
+cannon
ROOFING DETAILS
UT
HE
ALT
H S
CIE
NC
E C
EN
TER
at S
AN
AN
TON
IOR
EP
LAC
EM
EN
T of
Roo
f at
DO
LPH
BR
ISC
OE
JR
. LIB
RA
RY
RO
OF
San
Ant
onio
, Tex
as 7
8229
NOTE:1. SEE 1/LB5 FOR COPING JOINT INFORMATION2 SEE 2/LB5 FOR COPING CORNER JOINT INFORMATION
1/2'' COVER BOARD
ROOF SYSTEM
BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BOARD
CANT STRIP
SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.
TAPERED POLYISO.(THICKNESS VARIES)
CONTINUOUS
COPING
1'' STANDING SEAM
1'' SELF-ADHERING
COPING
NOT TO SCALECOPING JOINT1
LB5
(FILL SEAM W/ SEALANT)
NOT TO SCALECOPING CORNER JOINT2
LB5
CLEAT
COPING
CONTINUOUS CLEAT
1'' STANDING SEAM
NOT TO SCALEEXPLODED VIEWA NOT TO SCALE
SECTIONB
UNDERLAYMENT
1" STANDING SEAMPER DETAIL 1B/LB5
EQ.
EQ.
EQ.
4"
24 GA. PRE-FINISHED COPING
1'' STANDING SEAM PER DETAIL 1/LB5
POLYISOCYANURATE
EXIST. CONC. PARAPET
2X TRT'D WD. STUDS @ 16'' O.C.FILL BETWEEN STUDS W/ BATT INSUL.
22 GA. GALV. CONT. CLEAT
1/4" COVER BOARD OVER TOP OF PARAPET
24 GA. PRE-FINIHSED FASCIA
22 GA. GALV. CONT. CLEAT
24 GA. PRE-FINIHSED FASCIA
22 GA. GALV. CONT. CLEAT 2"
3/4"
3/4"
3/4" PLYWOOD
EXIST. STRUC. CONC. DECK
3/4" PLYWOOD
3" = 1'-0"PARAPET7
LB5
8"-M
IN.
3/4" PLYWOODPROVIDE 1/2"/FT. SLOPE
SELF-ADHERING UNDERLAYMENT
2x''a'' - TYP
SEALANT
TYP''a''
CLOSED CELLBACKER ROD
MASONRY
NOT TO SCALECONTROL JOINT3
LB5
3'' = 1'-0''SECTIONA 3'' = 1'-0''
ELEVATION @ COPINGB
4"
SECTION "A"
CONTROL JOINT
EXTEND CJ 4'' MIN.BELOW COPING
24 GA. PRE-FINISHEDCOPING
EXIST. PARAPETPANEL
3" = 1'-0"EXIST. FALL PROTECTION ANCHOR4
LB5
EXISTING STEEL ANCHORSCRAPE, PRIME AND PAINTEXPOSED PORTION OF STEEL
1/2" COVER BOARD
EXISTING DECKING
POLYISOCYANURATE
MONOLITHIC RESIN FLASHINGAS PRODUCED BY THE MEMBRANEMANUFACTURERROOF SYSTEM
NOTE:1. REMOVE ASPHALTIC CONTAMINATES FROM
PENETRATION PRIOR TO INSTALLATION OF RESIN FLASHING
3" = 1'-0"GUTTER5
LB5
6" 3/4"
4''1/2"MIN.
3"1/
2"
1/2'' COVER BOARDMEMBRANE BASE PLY
MEMBRANE CAP PLYMEMBRANE STRIP-IN PLY
POLYISOCYANURATE
1"5"
24 GA. PRE-FINISHED EDGE METAL
12 GA. x 1" GALV. GUTTER STRAP
24 GA. PRE-FINISHED GUTTER
5-1/2'' WIDE TRT'D WD. BLK'GANCHORED TO EXISTING BLK'G@ 12'' O.C. - STAGGERED TOP OF BLK'G SHALL MATCH TOPOF COVER BOARD1/
2"
5"x5" 24 GA. PRE-FINISHED DOWNSPOUT
@ 30'' O.C.
EXIST. METAL DECK
3" = 1'-0"WALL FLASHING6
LB5
8"-M
IN.
EXISTING STRUC. CONC. DECK
POLYISOCYANURATE
1/2'' COVER BOARD
ROOF SYSTEMCANT STRIP
24 GA. PRE-FINISHED COUNTERFLASHING
SCREWS @ 16'' O.C.24 GA. PRE-FINISHED RECEIVER
DRIVE-PINS W/ NEOPRENE WASHERS@ 16'' O.C.
CONT. SEALANTEXIST. CONC. WALL
BASE FLASHING BACKER PLYBASE FLASHING FINISH PLY1/4'' COVER BD.
12 GA. x 1'' GALVANIZED TERM BARANCHOR @ 12'' O.C.
1"1"
3"
TAPERED POLYISO.
POLYISOCYANURATE
EXIST. CONC. PARAPET
3" = 1'-0"PARAPET8
LB5
4" 1/2''-MIN.
24 GA. GALV. SCUPPER SLEEVESOLDER ALL JOINTS WATERTIGHT
1/2'' COVER BOARDROOF SYSTEM
1/4'' COVER BOARD2X TRT'D WD. CANT (@ SCUPPER ONLY)
4"3"
IN CONT. BED OF SEALANT24 GA. PRE-FINISHED CLOSURE PLATE SET
MODIFY EXISTING PARAPET AS REQ'DTO ACCOMMODATE NEW SCUPPER ELEVATION
2''
4"-M
IN.
EXIST. CONC. PARAPET
FASTENER W/ NEOPRENE WASHERS@ EA CORNER
DRIVE-PINS W/ NEOPRENE WASHERS
AND DIMENSIONS(MATERIAL TO BE REMOVED SHOWN DASHED)
1-1/2"
2"
NOTE:1. PARAPET PER DETAIL 7/LB52. SCUPPER FLOW LINE SHALL BE 2" ABOVE
EDGE OF PRIMARY DRAINAGE DEVISE
NOT TO SCALEELEVATION - CLOSUREA
2'' SEE SCHEDULE 2"
2"4"
2"
NOT TO SCALEISOMETRICB
EXIST. STRUC. CONC. DECK
TRT'D WD. BLK'G TO MATCH HT. OF INSULATION ANCHOR TO DECK@ 6'' O.C.
FIEL
DV
ERIF
Y
NEW
SCUPPER SIZES
SCUPPER DIMENSIONS
4" x 18"
EXIST. CONC.PANEL
12/21/2012DATE:
SHEET:
LB5OF
6
PCCCHECKED BY:
CANNON J.DRAWN BY:
1.
REVISION SCHEDULE:
ISSUE FOR BID 12/21/122.3.4.5.6.7.
hollongroup, llc
+hg c
+cannon
ROOFING DETAILS
UT
HE
ALT
H S
CIE
NC
E C
EN
TER
at S
AN
AN
TON
IOR
EP
LAC
EM
EN
T of
Roo
f at
DO
LPH
BR
ISC
OE
JR
. LIB
RA
RY
RO
OF
San
Ant
onio
, Tex
as 7
8229
3" = 1'-0"SMALL DECK REPAIR1
LB6
EXIST. STRUC. CONC. DECK
POLYISOCYANURATE
10 GA. GALV. STEEL PLATEANCHOR TO DECK AT EA. CORNER
1/2'' COVER BOARDROOF SYSTEM
12''-MAX.
4" - TYP.
3" - TYP. DRIVE-PINS W/ NEOPRENE WASHERS @ EA. CORNERFILL VOID W/ BATT INSULATOIN24 GA. PRE-FINISHED CLOSURE
1/2'' COVER BOARD
ROOF SYSTEMMONOLITHIC RESIN FLASHING
3" = 1'-0"PARAPET2
LB6
TAPERED POLYISO. (THICKNESS VARIES)
POLYISOCYANURATE
EXIST. STRUC. CONC. DECK
SCREWS W/ NEOPRENE WASHERS@ 16'' O.C.
24 GA. PRE-FINISHED CONT. CLEAT
24 GA. PRE-FINISHED EXP. JT. COVER
SELF-ADHERING UNDERLAYMENT
SCREWS @ 16'' O.C.
24 GA. PRE-FINISHED RECEIVER
DRIVE-PINS W/ NEOPRENE WASHERS@ 16'' O.C.
CONT. SEALANT
EXIST. STEEL SUPPORT / ANCHORPLATE - SCRAPE, PRIME AND PAINT
EXIST. PARAPET
1" 2" 1"
3/4" PLYWOOD
FLEXIBLE VAPOR RETARDERW/ COMPRESSIBLE INSUL.
4"X6" CONT. STL. ANGLE ANCHORED TO CURB AND
2X TRT'D WD. CURB AS REQ'D TO PROVIDE
DECK @ 24'' O.C. STAGGERED
FLASHING HT.
4"
3"
3'' = 1'-0''ELEVATION @ SUPPORT ANCHOR TO WALLA
EXPANSION JOINT COVER / CLEAT
FIELDCONT. SEALANT BEADSURFACE MOUNTED RECEIVER
COUNTERFLASHING
MOD. BIT. BASE FLASHING
ROOF LINE
SURFACE MOUNTED RECEIVER
1/2"TYP.
EXPANSION JOINT COVER / CLEAT
STEEL PLATE / ANCHOREXIST. PARAPET
2/LB
6
4/LB
3
NOTE:1. LOWER FLASHING AT POST CONNECTION AS SHOWN.2. PROVIDE RESIN MEMBRANE FLASHING AT BASE FLASHING
LESS THAN 8" IN HEIGHT
RESIN MEMBRANE FLASHING
2"
1/2"TYP.
2" 44 3"
MONOLITHIC RESIN FLASHING
EXIST. CONC. DECK
MEMBRANE BASE PLYBACKER ROD AND SEALANT
1/4"-MAX
EXIST. WINDOW
3" = 1'-0"FLASHING @ WINDOW3
LB6
NOTE:1. FLASHING SHALL NOT BLOCK WINDOW WEEP SYSTEM
2"
3" = 1'-0"FLASHING @ ROOF EDGE4
LB6
MONOLITHIC RESIN FLASHINGMEMBRANE BASE PLY
EXIST. CONC. DECK
2. EXTEND MEMBRANE BASE PLY BELOW EDGE OF WINDOW
12/21/2012DATE:
SHEET:
LB6OF
6
PCCCHECKED BY:
CANNON J.DRAWN BY:
1.
REVISION SCHEDULE:
ISSUE FOR BID 12/21/122.3.4.5.6.7.
hollongroup, llc
+hg c
+cannon
ROOFING DETAILS
UT
HE
ALT
H S
CIE
NC
E C
EN
TER
at S
AN
AN
TON
IOR
EP
LAC
EM
EN
T of
Roo
f at
DO
LPH
BR
ISC
OE
JR
. LIB
RA
RY
RO
OF
San
Ant
onio
, Tex
as 7
8229
L3
12/21/2012DATE:
SHEET:
S11
DRWCHECKED BY:
MMDRAWN BY:
1.
REVISION SCHEDULE:
ISSUE FOR BID 12/21/122.3.4.5.6.7.
hollongroup, llc
+hg c
+cannon
STRUCTURAL PLAN
UT
HE
ALT
H S
CIE
NC
E C
EN
TER
at S
AN
AN
TON
IOR
EP
LAC
EM
EN
T of
Roo
f at
DO
LPH
BR
ISC
OE
JR
. LIB
RA
RY
RO
OF
San
Ant
onio
, Tex
as 7
8229
C:\Users\marc\Desktop\0Jobsnew\6852 UTHSC Library Fall Arrestors\6852 S-1.dwg, 12/21/2012 9:47:47 AM, marc,DWG To PDF.pc3
Project Manual
for the
UNIVERSITY OF TEXAS
HEALTH SCIENCE CENTER AT SAN ANTONIO
Replacement of the Dolph Briscoe Jr. Library Roof
December 21, 2012
WORK REQUEST NO. 00275239‐002
SERVICE ORDER NO. SO13‐022
12885 Research Blvd., Suite 210B Austin, Texas 78750 Ph (512) 300‐0452
Replacement of the Dolph Briscoe Jr. Library Roof The U.T. Health Science Center at San Antonio
TABLE OF CONTENTS - 1
TABLE OF CONTENTS - DIVISION 01 THRU 26 SECTION TITLE PAGE NO. DIVISION 01 - GENERAL REQUIREMENTS SECTION 01 1100 00 - SUMMARY OF THE WORK 01 1100 00-1 THRU 4 SECTION 01 2200 00 - UNIT PRICES 01 2200 00-1 THRU 2 SECTION 01 3100 00 - PROJECT MANAGEMENT AND COORDINATION 01 3100 00-1 THRU 6 SECTION 01 3300 00 - SUBMITTAL PROCEDURES 01 3300 00-1 THRU 5 SECTION 01 4000 00 - QUALITY REQUIREMENTS 01 4000 00-1 THRU 2 SECTION 01 4200 00 - REFERENCE STANDARDS 01 4200 00-1 THRU 3 SECTION 01 5000 00 - TEMPORARY FACILITIES AND CONTROLS 01 5000 00-1 THRU 4 SECTION 01 6100 00 - PRODUCT REQUIREMENTS 01 6100 00-1 THRU 2 SECTION 01 7329 00 - CUTTING AND PATCHING 01 7329 00-1 THRU 3 SECTION 01 7800 00 - CLOSEOUT PROCEDURES 01 7800 00-1 THRU 5 DIVISION 02 THRU 05 - NOT USED DIVISION 06 - WOODS AND PLASTICS SECTION 06 1050 00 - ROOF CARPENTRY 06 1050 00-1 THRU 5 DIVISION 07 - THERMAL AND MOISTURE PROTECTION SECTION 07 0151 00 - PREPARATION FOR RE-ROOFING 07 0151 00-1 THRU 6 SECTION 07 5216 00 - MODIFIED BITUMEN ROOF SYSTEM 07 5216 00-1 THRU 12 SECTION 07 5220 00 - ROOFING INSTALLER’S WARRANTY 07 5220 00-1 THRU 2 SECTION 07 5600 00 - FLUID APPLIED FLASHING AND MEMBRANE 07 5600 00-1 THRU 7 SECTION 07 6200 00 - FLASHING AND SHEET METAL 07 6200 00-1 THRU 9 SECTION 07 7200 00 - ROOF ACCESSORIES 07 7200 00-1 THRU 3 SECTION 07 7900 00 - JOINT SEALERS 07 7900 00-1 THRU 4 DIVISION 09 THRU 22 - NOT USED DIVISION 23 - MECHANICAL SECTION 23 0530 00 - MECHANICAL PROVISIONS 23 0530 00-1 THRU 9 DIVISION 24 THRU 25 - NOT USED DIVISION 26 - ELECTRICAL SECTION 26 0530 00 - ELECTRICAL PROVISIONS 26 0530 00-1 THRU 3 END OF TABLE OF CONTENTS