Duct- and wall fansCK | CV | KV | LPK | RS

w w w. o s t b e r g . c o m

Page 2: osberg

Quality and innovation are the two basic words for CA Östberg. In accordance with our pursuit to deliver the bestproducts possible as well as caring for environmental issues weare certified according to both ISO 9001 and ISO 14001.

Östberg fans have a good reputation amongst contractors andinstallers all over the world. Listening to our customers manyideas of product improvement helps us in the continuous deve-lopment of our product range. This communication has lead toefficient, maintenance free fans easy to install. Before release,new products are carefully tested in our modern laboratory toensure quality and performance.

All CA Östberg fans are manufactured from the best qualitycomponents. Prior to despatch the fans are being tested and theresults are being computer stored for future reference.

Östberg is a company you can rely on today and in the future.

Östberg is one of the leading manufacturers of in-line ductfans with its head office and manufacturing facility based inAvesta Sweden. Östberg products are available in mostcountries around the world.

Page 3: osberg

CK 4-7

CK 220V / 60 Hz 8-9

LPK 10-13

RS 14-16

CAU 17

CV/KV 18-19

ACCESSORIES 20-21

Installation, operation, maintenance and wiring diagrams 22

Sound data explanation 23

3

Table of Contentspage

AB C.A. Östberg preserve the right to changes without further notice.

© 2004, AB C.A. Östberg, Avesta, Sweden.All rights reserved. No part of this folder may be reproduced or transmitted in any formor by any means, without the written permission by C.A. Östberg, Sweden.

For more information about our product range, visit our web site.

www.ostberg.com

Page 4: osberg

We know in reality where our fans are working. This is why we design our CK range for a long trouble free life. The housing (1) must resist rough handling. The European builtexternal rotor motor (2) is of high quality. The terminal box (3) is IP 44.

4

1 2

3

Page 5: osberg

A CHAIN IS NEVER STRONGER THAN ITS WEAKEST LINK.The CK is one of the most reliable fans you can get and an excellent choice even in complexduct systems. Quality, efficiency, reliability and low sound levels makes the CK a favouriteamongst contractors and installers. Every single CK is individually tested before it´s despatched.

5

High Capacity And ReliabilityIn-line centrifugal duct fan, type CK, is a straight-through radialfan. It is compact, with a high capacity and very easy to install.The CK fan can cope with high pressure and long duct runs,whilst still operating at an acceptable sound level. The fan speed can be controlled by voltage or frequency variationregulators. Several fans can be connected to the same controllerproviding the total nominal current of the fans does not exceed therating of the controller.The CK range of fans are moisture resistant and are approved forinstalling in humid or damp environments. The fans are ratedIP44 when installed in a duct system. They must not be used fortransporting grinding dust, soot or similar. The casing is manufac-tured from pre-galvanized steel. Automatic thermo-contacts openif the temperature within the motor windings becomes excessive.

AccessoriesDuct clamps, mounting brackets, back-draught shutters, louvreshutters, safety grills and speedcontrollers. (See page 20-21).

CK circular duct fanCKCK

Östberg The Fan Companywas founded in 1981 byHans Östberg.

The major break-through forthe company was his inven-tion of the circular duct fan,CK. The product has been agreat success ever since.

Hans Östberg still has a key-position within the organiza-tion and the company hastoday 180 employees.

Östberg is one of the worldsleading manufacturers of in-line duct fans and the com-pany has, over the years,gained a reputation for beinginnovative and reliable.

Page 6: osberg

6

CK 100 A/C CK 125 A/C CK 160 B/C

CK 200 A/B CK 250 A/C CK 315 B/C

More than 80% of allthe fans we produce areexported.Östberg is certified accor-ding to ISO 9001 aswell as ISO 14001.

Circular duct fan, CK 100 A 100 C 125 A 125 C 160 B 160 C 200 A 200 B 250 A 250 C 315 B 315 CVoltage V/Hz 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50Current A 0,18 0,32 0,19 0,33 0,31 0,44 0,50 0,69 0,50 0,81 0,84 1,24Input W 41 70 42 72 71 100 115 158 115 185 190 284Speed Rpm 1900 2460 1700 2360 2410 2480 2580 2500 2580 2420 2465 2370Enclosure class, motor IP 44 44 44 44 44 44 44 44 44 44 44 44Insulation class, motor F F F F F F F F F F F FMax temp Cº 85 70 85 70 70 65 60 60 60 55 50 50Weight Kg 2,9 2,9 2,9 2,9 3,2 4,3 4,6 5,1 4,6 5,3 6,1 6,5Wiring diagram, pg 22 No: 4040002 4040001 4040002 4040001 4040001 4040001 4040001 4040001 4040001 4040001 4040001 4040001

TECHNICAL DATA, CK

Flow m3/hFlow m3/hFlow m3/h

Flow m3/h Flow m3/hFlow m3/h

Tota

l pre

ssure

Pa

Tota

l pre

ssure

Pa

Tota

l pre

ssure

Pa

Tota

l pre

ssure

Pa

Tota

l pre

ssure

Pa

Tota

l pre

ssure

Pa

Flow m3/s Flow m3/s Flow m3/s

Flow m3/sFlow m3/sFlow m3/s

AB C.A. Östberg preserve the right to changes without further notice.

Page 7: osberg

7

Type of fan dB(A) tot 63 125 250 500 1k 2k 4k 8k40 l/s Inlet 66 45 56 64 60 58 52 45 38

CK, CV, KV 100 A 125 Pa To environment 36 43 35 21 33 35 39 37 37 3160 l/s Inlet 70 50 61 66 65 65 59 52 46

CK, CV, KV 100 C 170 Pa To environment 42 49 34 23 40 40 44 42 44 3840 l/s Inlet 67 44 51 66 60 56 52 47 39

CK, CV, KV 125 A 130 Pa To environment 36 43 35 20 35 34 38 38 36 3080 l/s Inlet 70 49 55 64 67 64 60 55 48

CK, CV, KV 125 C 145 Pa To environment 42 49 36 25 39 39 44 43 45 3670 l/s Inlet 69 48 54 64 65 63 58 53 48

CK, CV, KV 160 B 195 Pa To environment 42 49 35 24 39 40 45 44 44 32160 l/s Inlet 73 52 60 64 68 69 64 64 54

CK, CV, KV 160 C 190 Pa To environment 49 56 35 34 42 49 54 47 48 35190 l/s Inlet 72 52 60 64 67 66 64 65 55

CK, CV, KV 200 A 190 Pa To environment 47 54 34 31 42 46 50 47 48 34160 l/s Inlet 73 52 62 66 67 66 65 64 58

CK, CV, KV 200 B 300 Pa To environment 48 55 35 30 40 48 52 48 49 41135 l/s Inlet 74 51 60 67 67 69 68 64 55

CK, CV, KV 250 A 250 Pa To environment 47 54 26 30 34 47 52 47 44 38160 l/s Inlet 74 52 59 66 67 69 69 66 60

CK, CV, KV 250 C 320 Pa To environment 49 56 26 38 40 50 53 49 46 40220 l/s Inlet 74 54 56 61 65 65 70 67 65

CK, CV, KV 315 B 300 Pa To environment 47 54 28 35 43 48 49 50 45 41180 l/s Inlet 75 58 60 67 66 66 72 68 66

CK, CV, KV 315 C 425 Pa To environment 50 57 30 35 44 51 51 53 50 43

Type of fan Ød ØD a bCK 100 A 100 242 20 146CK 100 C 100 242 20 146CK 125 A 125 242 20 150CK 125 C 125 242 20 150CK 160 B 160 272 26 145CK 160 C 160 344 28 177CK 200 A 200 344 28 172CK 200 B 200 344 28 172CK 250 A 250 344 28 172CK 250 C 250 344 28 172CK 315 B 315 402 28 199CK 315 C 315 402 28 199

LpA LWA

SOUND DATA, CK, CV, KV

DIMENSIONS, CK

You find ourfans in all EUcountries.

AB C.A. Östberg preserve the right to changes without further notice.

Explanations to sound data, pg 23

Page 8: osberg

Fans from Östberg are used inseveral countries in South America.

8

Type of fan dB(A) tot 63 125 250 500 1k 2k 4k 8kInlet 58 35 51 52 51 50 45 43 23

CK 100 A To environment 33 40 23 28 29 31 37 33 27 25Inlet 72 47 64 65 66 65 63 57 48

CK 100 C To environment 45 52 25 31 40 40 48 46 41 40Inlet 56 39 46 50 52 48 44 39 23

CK 125 A To environment 31 38 22 28 30 30 32 30 26 24Inlet 71 50 60 63 67 64 63 58 51

CK 125 C To environment 45 52 25 34 40 40 47 43 47 37Inlet 70 44 56 63 66 63 60 53 47

150 B / 160 B To environment 46 53 23 36 38 42 49 48 39 29Inlet 75 51 68 70 69 67 64 61 50

150 C / 160 C To environment 49 56 24 41 43 48 53 46 47 32Inlet 76 54 62 70 72 69 65 63 56

CK 200 A To environment 48 55 22 32 37 47 51 47 48 33Inlet 78 56 67 73 71 69 66 70 61

CK 200 B To environment 50 57 26 39 44 51 53 48 44 38Inlet 77 53 59 67 69 73 68 67 59

CK 250 A To environment 50 57 22 30 40 51 51 53 49 34Inlet 75 54 56 63 67 69 69 67 65

CK 250 C To environment 49 56 32 36 37 49 53 47 44 35Inlet 73 55 59 61 64 66 68 67 61

CK 315 B To environment 49 56 26 47 42 47 50 52 44 32Inlet 73 56 61 63 64 65 67 66 60

CK 315 C To environment 50 57 28 37 40 50 52 53 45 34

LpA LWA

SOUND DATA, CK 60 Hz

High Capacity And ReliabilityIn-line centrifugal duct fan, type CK, is a straight-through radialfan. It is compact, with a high capacity and very easy to install.The CK fan can cope with high pressure and long duct runs, whilst still operating at an acceptable sound level. The fan speed can be controlled by voltage or frequency variation regulators. Several fans can be connected to the same controller providing the total nominal current of the fans does not exceed the rating of the controller.The CK range of fans are moisture resistant and are approved for installing in humid or damp environments. The fans are rated IP44 when installed in a duct system. They must not be used for transporting grinding dust, soot or similar. The casing is manufactured from pre-galvanized steel. Automatic thermo-contacts open if the temperature within the motor windings becomes excessive.

AccessoriesDuct clamps, mounting brackets, back-draught shutters, louvreshutters, safety grills and speedcontrollers. (See page 20-21).

CK 220V/60 Hz cirkular duct fanCK 220V/60 HzCK 220V/60 Hz

Explanations to sound data, pg 23

Page 9: osberg

CK 100, 60 Hz CK 125, 60 Hz CK 150/160, 60 Hz

CK 200, 60 Hz CK 250, 60 Hz CK 315, 60 Hz

9

CK 220V/60 HzCK 220V/60 HzCK 220V/60 Hz

CK 220 V / 60 Hz 100 A 100 C 125 A 125 C 160 B 160 C 200 A 200 B 250 A 250 C 315 B 315 CVoltage V/Hz 220/60 220/60 220/60 220/60 220/60 220/60 220/60 220/60 220/60 220/60 220/60 220/60Current A 0,21 0,42 0,21 0,44 0,43 0,60 0,71 0,97 0,71 1,00 1,13 1,40Input W 45 91 45 95 93 131 154 211 154 217 247 304Speed Rpm 1530 2700 1435 2510 2585 2555 2750 2730 2760 2645 2500 2655Enclosure class, motor IP 44 44 44 44 44 44 44 44 44 44 44 44Insulation class, motor F F F F F F F F F F F FMax temp Cº 80 70 80 70 70 70 60 50 60 60 50 50Weight Kg 2,9 2,9 2,9 2,9 3,2 4,3 4,6 5,1 4,6 5,3 6,1 6,5Wiring diagram, pg 22 No: 4040002 4040001 4040002 4040001 4040001 4040001 4040001 4040001 4040001 4040001 4040001 4040001

TECHNICAL DATA, CK 60 Hz150 B / 150 C /

AB C.A. Östberg preserve the right to changes without further notice.

Page 10: osberg

10

Type of fan Flow/Tot pressure dB(A) tot 63 125 250 500 1k 2k 4k 8kInlet 54 45 48 45 47 47 42 37 29

22 l/s Outlet 58 43 47 49 51 55 49 42 33LPK 100 A 145 Pa To environment 37 44 28 33 38 35 37 34 32 32

Inlet 62 50 57 56 54 54 51 50 4146 l/s Outlet 67 53 57 60 59 62 60 55 49

LPK 100 B 245 Pa To environment 44 51 28 34 46 43 44 42 40 38Inlet 60 46 50 52 54 55 50 44 31

41 l/s Outlet 63 47 51 56 57 60 53 48 38LPK 125 A 142 Pa To environment 42 49 29 35 41 41 44 42 36 33

Inlet 66 53 57 58 61 60 57 51 4170 l/s Outlet 70 53 57 61 63 66 62 57 49

LPK 125 B 217 Pa To environment 48 55 30 37 47 47 51 49 44 39Inlet 70 54 60 63 65 64 56 53 45

94 l/s Outlet 71 55 60 65 65 66 62 60 51LPK 160 B 210 Pa To environment 49 56 33 41 49 51 50 47 41 38

Inlet 72 54 63 66 68 65 58 57 49107 l/s Outlet 74 57 62 67 67 67 66 63 55

LPK 160 D 260 Pa To environment 49 56 33 39 46 51 51 48 44 41

LpA LWASOUND DATA, LPK

You find fans from Östberg inalmost every country in Asia.

LPK 100 A 100 B 125 A 125 B 125 D 160 B 160 D 200 A 200 BVoltage V 230 230 230 230 230 230 230 230 230Current A 0,16 0,34 0,21 0,44 0,24 0,55 0,72 0,48 0,77Input W 36 77 47 100 53 122 162 110 175Speed Rpm 870 1800 1050 1450 1175 1750 2150 925 1100Enclosure class, motor IP 44 44 44 44 44 44 44 44 44Insulation class, motor F F F F F F F F FMax temp °C 80 50 80 55 80 55 45 50 60Weight kg 3,5 3,5 3,8 3,8 3,8 4,4 4,6 5,2 5,2Wiring diagram, pg 22 No: 4040002 4040001 4040002 4040001 4040001 4040001 4040001 4040001 4040001

TECHNICAL DATA, LPK

LPK are small, very use-ful in-line duct fans.They have an extre-mely low profile,which is only 20 mm more thanthe duct diameter.They complementwell the CK range.LPK is the perfect choice where a lowinstalled height is required.An added benefit is theswing-out motor andimpeller for ease of cleaning and maintenan-ce. All fans are fitted with anexternal rotor motor with forward curved impellar whichensures a high performance. Themotor bearings are sealed for life.

LPK low profile fanLPKLPK

Swing-out!

continue on page 12Explanations to sound data, pg 23

Page 11: osberg

An exciting exampleof where you canfind Östberg fans isChek Lap Kok - aninternational airportin Hong Kong.

11

LPK 100 A/B LPK 125 A/B

LPK 160 B/D

DIMENSIONS, LPK

Type of fan C DLPK 100 122 100LPK 125 152 125LPK 160 186 160LPK 200 see next page

AB C.A. Östberg preserve the right to changes without further notice.

Page 12: osberg

Type of fan Flow/Tot pressure dB(A) tot 63 125 250 500 1k 2k 4k 8kInlet 60 43 52 56 56 49 44 34 29

55 l/s Outlet 65 47 59 57 58 59 54 52 48LPK 125 D 120 Pa To environment 40 47 31 36 40 41 41 39 37 39

Inlet 64 47 58 54 58 55 56 54 47105 l/s Outlet 67 55 50 59 61 61 57 56 50

LPK 200 A 145 Pa To environment 46 53 29 40 40 47 47 47 43 41Inlet 68 51 63 61 62 58 57 56 50

170 l/s Outlet 72 60 65 63 66 64 63 63 57LPK 200 B 175 Pa To environment 50 57 36 43 44 50 53 49 47 44

SOUND DATA, LPK

DIMENSIONS, LPK 200 A/B

LPK 200 A/BLPK 125 D

12LPK 200

AB C.A. Östberg preserve the right to changes without further notice.

LpA LWA

Explanations to sound data, pg 23

Flow m3/h

Tota

l pre

ssure

Pa

Flow m3/s

Flow m3/h

Tota

l pre

ssure

Pa

Flow m3/s

Page 13: osberg

TECHNICAL DATA, LPKI

LPKI 125 BVoltage V 230/50Current A 0,46Input W 104Speed Rpm 1450Enclosure class, motor IP 44Insulation class, motor FMax temp °C 55Weight kg 3,9Wiring diagram, pg 22 No: 4040001

SOUND DATA, LPK

Type of fan Flow/Tot pressure dB(A) tot 63 125 250 500 1k 2k 4k 8kInlet 66 58 59 62 59 55 52 43 38

70 l/s Outlet 71 61 59 64 65 65 62 61 59LPKI 125 B 240 Pa To environment 45 52 28 42 44 45 46 44 39 40

Silencing coverTo environment 43 50 27 41 44 42 44 41 38 39

LPKI 125 B

13

LPLPKK IIAn insulated version

LPK I

AB C.A. Östberg preserve the right to changes without further notice.

LpA LWA

Flow m3/h

Tota

l pre

ssure

Pa

Flow m3/s

Explanations to sound data, pg 23

Page 14: osberg

The RS fan is an exhaust fan suitable for installation onan outside wall. It is equipped with an external rotorinduction motor with forward curved impellar and is surrounded by a box of painted pre-galvanized steel. The fan speed can be controlled by voltage or frequencyvariation regulators.

Exhaust fan RS 125 A 125 C 160 A 160 CVoltage V 230 230 230 230Current A 0,20 0,32 0,29 0,46Input W 45 73 64 104Speed Rpm 1400 2460 1200 2480Enclosure class, motor IP 44 44 44 44Insulation class, motor F F F FMax temp Cº 85 70 65 65Weight kg 3,4 3,4 5,0 5,0Wiring diagram, pg 22 No: 4040002 4040001 4040002 4040001

Type of fan Flow/Tot pressure dB(A) tot 63 125 250 500 1k 2k 4k 8kInlet 63 47 54 58 58 56 51 42 28

RS 125 A 39 l/s, 90 Pa To environment 55 62 41 40 50 56 58 55 44 35Inlet 70 55 59 63 65 63 59 51 40

RS 125 C 50 l/s, 145 Pa To environment 62 69 48 41 56 63 66 63 54 46Inlet 61 45 53 55 56 54 45 37 19

RS 160 A 68 l/s, 95 Pa To environment 51 58 48 38 49 53 52 50 40 32Inlet 73 52 60 66 70 68 59 55 41

RS 160 C 138 l/s, 210 Pa To environment 64 71 48 44 60 66 66 64 58 46

LpA LWA

SOUND DATA, RS

TECHNICAL DATA, RS

RS outside wall-mounted exhaust fan

14

Russia is an enormous country,with a big demand for high quali-ty ventilation products. Östberg is one of the leading sup-pliers of inline duct fans in Russia.

RSRS

Explanations to sound data, pg 23

Page 15: osberg

Type of fan A B C D ERS 80 A/C 230 252 122 80 170RS 100 A/C 230 252 122 100 170RS 125 A/C 230 252 122 125 170RS 160 A/C 332 310 147 160 195

DIMENSIONS, RS

15

RS 125 A/C RS 160 A/C

AB C.A. Östberg preserve the right to changes without further notice.

Page 16: osberg

RSSmall sizes

TECHNICAL DATA, RS

SOUND DATA, RS

RS

Type of fan Flow/Tot pressure dB(A) tot 63 125 250 500 1k 2k 4k 8k30 l/s Inlet 66 57 58 60 61 59 55 50 42

RS 80 A 125 Pa To environment 57 64 31 39 52 59 62 58 51 4335 l/s Inlet 72 61 63 66 67 66 61 56 50

RS 80 C 195 Pa To environment 63 70 36 43 56 64 67 63 58 4935 l/s Inlet 67 58 59 61 61 60 55 50 42

RS100 A 105 Pa To environment 56 63 30 37 49 56 61 56 50 4135 l/s Inlet 73 60 61 66 68 67 62 57 53

RS 100 C 195 Pa To environment 62 69 35 43 54 63 67 62 57 48

RS 80 A 80 C 100 A 100 CVoltage V 230 230 230 230Current A 0,20 0,32 0,21 0,34Input W 45 74 48 76Speed Rpm 1850 2520 1830 2490Enclosure class, motor IP 44 44 44 44Insulation class, motor F F F FMax temp °C 80 75 80 75Weight kg 3,4 3,4 3,4 3,4Wiring diagram, pg 22 No: 4040002 4040001 4040002 4040001

RS 80 A/C RS 100 A/C

16

AB C.A. Östberg preserve the right to changes without further notice.

LpA LWA

Explanations to sound data, pg 23

Flow m3/h

Tota

l pre

ssure

Pa

Flow m3/s

Flow m3/h

Tota

l pre

ssure

Pa

Flow m3/s

Page 17: osberg

CAU 125 A / B / CCAU 125 A / B / CMultiple inlet exhaust fan

17

CAU 125 A B CCurve no A B CVoltage, V/Hz 230/50 230/50 230/50Current , A 0,21 0,45 0,53Power, W 48 104 120Speed, Rpm 1050 1500 1750Wiring diagram nr: 4040002 4040001 4040001Weight , kg: 4,7 4,7 4,7

Type of fan Flow/Tot pressure tot dB(A) 63 125 250 500 1k 2k 4k 8kEnvironment 39 46 32 34 37 36 43 36 32 30

35l/s Outlet 55 44 45 50 50 40 37 33 21CAU 125 A 125 Pa Inlet 64 48 56 57 57 59 55 48 40

Environment 43 50 34 37 41 41 45 41 39 3460l/s Outlet 58 45 47 54 53 44 42 39 29

CAU 125 B 280 Pa Inlet 68 49 58 60 61 63 62 54 47Environment 41 48 34 36 41 40 42 40 37 32

85l/s Inlet 60 47 48 56 55 45 42 38 32CAU 125 C 260 Pa Outlet 72 55 62 64 64 66 65 57 51

Tota

l pre

ssure

Pa

Flow m3/h

Flow m3/s

MEASUREMENTS, CAU

TECHNICAL DATA, CAU

SOUND DATA, CAU

CAU 125 A/B/C

CAU with its 3 inlets and one outlet provides amultifunction. The fan is equipped with an externalrotor introduction motor and it has forward curvedimpeller and insulation on the inlet side. Casingfrom pre-galvanized steel.

AB C.A. Östberg preserve the right to changes without further notice.

Explanations to sound data, pg 23

Page 18: osberg

CV/KVWall mounted fans CV and KV can be supplied with 12 different capacities, each size in five different configurations. The fans have a stable housing of pre-galvanized steel and are entirely maintenance free. They can be positioned quite freely and can therefore be used in a wide variety of applications. All the fans have ball bearing mounted external rotor type induction motors with radial backward curved impellers. The fans can be speed controlled by voltage variation and operate at an acceptable sound level. The wall fans are moisture resistant and are approved for installation in humid and damp environments.

18

K=SquareC=Circular

Wall mounted fan

Capacity(see diagram)

F=Exhaust airT=Intake air

U=Direct to wallI=Flush fitted or recessed

Connection dimensionDIMENSIONS, CV/KV

K

V

F

U

160

B

CV/KV wall mounted fansCV/KVCV/KV

Type of fan ∅d1 ∅D1 ∅D2 a b c ∅d2 e f gCV/KV 100 A 100 240 262 6 24 80 7 6 140 310 295CV/KV 100 C 100 240 262 6 24 80 7 6 140 310 295CV/KV 125 A 125 240 262 6 24 80 7 6 140 310 295CV/KV 125 C 125 240 262 6 24 80 7 6 140 310 295CV/KV 160 B 160 268 290 6 30 70 7 6 155 335 320CV/KV 160 C 160 342 364 6 26 92 10 6 195 400 385CV/KV 200 A 200 342 364 6 34 83 10 6 195 400 385CV/KV 200 B 200 342 364 6 34 83 10 6 195 400 385CV/KV 250 A 250 342 364 6 33 83 10 6 195 400 385CV/KV 250 C 250 342 364 6 33 83 10 6 195 400 385CV/KV 315 B 315 400 432 4 34 112 12 6 225 460 445CV/KV 315 C 315 400 432 4 34 112 12 6 225 460 445

+–

+–

+–

+–

+–

+–

+–

+–

+–

+–

+–

+–

Page 19: osberg

19

CV/KV 100 A/C CV/KV 125 A/C CV/KV 160 B/C

CV/KV 200 A/B CV/KV 250 A/C CV/KV 315 B/C

Wall fan KV/CV 100 A 100 C 125 A 125 C 160 B 160 C 200 A 200 B 250 A 250 C 315 B 315 CVoltage V/Hz 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50 230/50Current A 0,18 0,32 0,19 0,33 0,31 0,44 0,50 0,69 0,44 0,84 0,84 1,24Input W 41 70 42 72 71 100 115 158 101 192 190 284Speed Rpm 1860 2390 1700 2320 2410 2480 2580 2500 2580 2420 2465 2370Enclosure class, motor IP 44 44 44 44 44 44 44 44 44 44 44 44Insulation class, motor F F F F F F F F F F F FMax temp Cº 85 70 85 70 70 65 60 60 60 50 50 50Weight Kg 2,5 2,5 2,5 2,5 2,8 4,0 4,1 4,8 4,1 4,9 5,6 6,0Wiring diagram, pg 22 No: 4040002 4040001 4040002 4040001 4040001 4040001 4040001 4040001 4040001 4040001 4040001 4040001

TECHNICAL DATA, CV/KV

SOUND DATA, CV/KV

See page 7.

1=Curve measured with duct connection to the induction side.2=Curve measured without duct connection.

AB C.A. Östberg preserve the right to changes without further notice.

Page 20: osberg

accessories

20

DUCT CLAMPThe fan is connected to the duct using duct clamp MK. The clamp is made of pre-gal-vanized steel and is rubber-lined to seal the connection and absorb vibrations. Theclamp allows the fan to be easily removed for inspection and cleaning,Available in sizes Ø 100, 125, 160, 200, 250 and 315 mm.

BACK DRAUGHT SHUTTERFor fitting in circular ducts. Made of pre-galvanized steel with spring-loaded vanes ofaluminium, the RSK back draught shutter can be fitted in any position and is availablein the following diametres: Ø 100, 125, 160, 200, 250 and 315 mm.

MOUNTING BRACKETFor easy fitting of CK fans on walls orin ceilings, the MPM bracket is suitablefor all circular duct fans. The bracketmay be screwed or riveted to the fan.

LOUVRE SHUTTERSOur self-closing louvre shutters havea very low air flow resistance. Forexample; Resistance is 10 Pa at 4m/s air speed, 30 Pa at 6,5 m/s and50 Pa at 8,5 m/s.

ELECTRONIC THERMOSTAT For fitting to controller or direct to wall. On / off control of rising or falling tempera-ture. Sensitivity + 0,5ºC. Maximum loading 16 A/250 V or 10 A/380 V.Safety approved.

SAFETY GRILLEType BSV with angled lugs for fitting pipes. Made of pre-galvanized steel mesh. Available in sizes Ø 80, 100, 125, 160, 200, 250, 315, 355, 400, 450, 500, 560, 630, 710 and800 mm.

Type Ød A B B1 B2 CVK 10 100 140 140 110 110 15VK 12 125 160 160 110 110 20VK 16 - 190 190 130 130 26VK 20 - 240 240 167 193 28VK 25 - 290 290 217 243 28VK 30 - 340 340 267 293 28VK 35 - 390 390 317 343 28VK 40 - 440 440 367 393 28VK 45 - 490 490 417 443 28VK 50 - 540 540 467 493 28VK 63 - 685 685 671 585 40VK 71 - 685 685 771 685 40VK 80 - 876 885 862 785 40VK 90 - 1026 985 1012 885 40

accessoriesaccessories

Page 21: osberg

VRTE, TRANSFORMER CONTROLLERFor manual five-step control of single phase motors. The con-troller is enclosed in a durable PVC housing.

Output voltages: VRTE C: 75V, 110V, 145V, 180V and 230V.VRTE 1 / 3 / 5: 60V, 105V, 130V, 160V and 230V.

VRDE, TRANSFORMER CONTROLLERFor high and low speed control of single phase motors. A timeror a thermostat may be fitted. Five user-selected voltages can beset for high or low speeds. Enclosed in durable PVC housing.

VRS, THYRISTOR CONTROLLER For manual variable speed control of single phase motors.Minimum speed is adjusted by means of a screw under theknob. The controller is certified and approved as conforming toelectrical safety and interference regulations on all markets.

Type Current Encl. rating VoltageVRS 0,5 I / U* 0,5 A IP 44 / 54 230VVRS 1,0 I / U* 1,0 A IP 44 / 54 230VVRS 2,0 I / U* 2,0 A IP 44 / 54 230VVRS 4,0 U* 4,0 A IP 54 230V

*I=Flush fitted. U=Direct to wall.

Type Current Voltage Encl. rating a b cVRTE C 1,0 A 230V IP 44 135 70 65VRTE 1 1,4 A 230V IP 54 170 135 85VRTE 3 3,0 A 230V IP 54 170 135 105VRTE 5 5,0 A 230V IP 54 220 170 105

Type Current Voltage Encl. rating a b cVRDE 1,5 1,5 A 230V IP 54 254 200 167VRDE 3 3,0 A 230V IP 54 254 200 167

Ø50

80 2332

80 Ø45

21

Page 22: osberg

Single phase.Single phase.

22

instruction and maintenanceinstruction and maintenanceinstruction and maintenance

wiring diagramswiring diagramswiring diagrams

Fans CK, CV, KV, LPK och RS from C.A. Östberg are all equipped with an asynchronous motorof external rotor type with sealed for lifetime ball bearings.Single phase motors are equipped with an approved thermo-contact protector with automaticreset. These must be connected over a motorprotector, or if speed control is used, over a thermo-contact relay, fitted as standard in our 3-phase transformers.The thermo-contact breaks the cur-rent if the temperature in the motor windings becomes excessive.In single-phase motors the thermo-contact is reset as follows: Turn off the mains power. Waituntil the motor has cooled. Reconnect the mains power.The fans are intended for continuous operation and can be controlled by voltage or frequencyvariation regulators. They are NOT designed for transporting explosive gases, grinding dust, sootor similar.

Electrical installationThe fan may only be installed by a qualified electrician. All fans are supplied fully wired and readyto fit in a sealed installation unit.1. Check that the voltage, frequency, cycles etc of the mains correspond to the specifications on

the fan’s ID plate.2. All electrical wiring and connections must be carried out in compliance with your national

safety regulations.3. The fan must be earthed!

Installation and fittingMaximum temperature of transported air, see diagrams.

Care and maintenanceThe only maintenance required is cleaning. We recommend inspection of the impeller every sixmonths if the fan is operated continuously. Before cleaning: Disconnect the mains and block themains switch. Wait until the motor and impeller has stopped rotating.Care must be taken during dismantling and cleaning so as not to disturb the fan’s balance. Strongdetergents or cleaning agents must not be used for cleaning the fan. Internal insulation may bewiped clean with a damp cloth. Sharp or rotating tools must not be used as these may damageouter surfaces.

In case of breakdown1. Check that mains power is reaching the fan.2. Disconnect from the mains and make sure the impeller is not blocked.3. Check the thermo-contact according to the description above. If the thermo-contact has acti-

vated, the cause of overheating should be determined to prevent the same fault reocurring.4. If the fault persists, change the capacitor.5. If these steps do not help, contact your supplier.

Page 23: osberg

explanations to sound dataexplanations to sound dataexplanations to sound data

23

The sound data have been compiled by means of sound measurement methods as follows:Pressure and flow: ISO 5801Determination of acoustic sound level in duct: ISO 5136Determination of acoustic sound level in reverberation room: ISO 3741

DesignationsLWA tot: Total A-weighted sound power level dB(A) (ref 10-12 W)=the sum of the sound power level in the octave ranges. LWA: A-weighted sound power level in octave range dB(A) (ref 10-12 W).LpA: A-weighted sound pressure level in dB(A) according to normed A-weightening correction and relating to an effective absorption area of 20 m2 with half spherical translation at a distance of 3 meters.

Page 24: osberg

AB C.A. ÖSTBERGINDUSTRIGATAN 2SE-774 35 AVESTASWEDEN

TEL +46 226 86 000FAX +46 226 86 005

e-mail: [email protected]

OLA

GLU

ND

GRA

FISK

FO

RM/C

.A.Ö

STBE

RG

PH

OTO

GRA

PHY:

PAT

RIK

LIN

DST

RÖM

.

PR

INTI

NG

: PR

INFO

AVE

STA

OFF

SET.

W

040

7