or-10-045 (rp-1477) impact of typical weather year ... huang, krarti... · transactions, volume...
TRANSCRIPT
Impact of Typical Weather Year Selection Approaches on Energy Analysis of Buildings
Donghyun Seo Yu Joe Huang Moncef Krarti, PhD, PEStudent Member ASHRAE Member ASHRAE Member ASHRAE
OR-10-045 (RP-1477)
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
This paper is based on findings resulting from ASHRAE Research Project RP-1477.
ABSTRACT
The paper summarizes the results of a series of analyses toassess the impact of the selection procedure used to generate oftypical year weather on annual building energy use. The build-ing energy analysis is carried out using detailed whole buildingsimulation tool that utilizes hourly typical year weather files.Annual energy use for prototypical office buildings are obtainedfor 10 sites representing a wide range of climatic conditions inthe U.S. In particular, the analyses presented in this paper eval-uate the impacts of weighting factors for various weather vari-ables and of the length of historical data used on predicting theenergy use of building systems.
The results of the analysis indicated that a maximum of 5%difference in annual office building energy use can result fromthe selection procedure used to generate typical weather yearfor the 10 US climates considered in this study.
INTRODUCTION
Detailed building energy simulation tools such as DOE-2 (LBL 1981) and EnergyPlus (Crawley et al. 2000) arecommonly used to design sustainable buildings. These toolsrequire hourly typical year weather files in order to estimatebuilding energy use and building indoor comfort. Severalprocedures do exist to develop typical weather data using asingle year of hourly data that are selected to represent therange of weather patterns that can be found in a multi-year dataset (Keeble 1990).
Several approaches have been utilized to develop andformat a typical weather year for building energy analysisincluding the ASHRAE Test Reference Year or TRY (ASH-
RAE 1976), Typical Meteorological Year or TMY (Hall et al.1978), the Weather Year for Energy Calculations (Crow 1981),TMY2 (Marion and Urban 1995), ASHRAE InternationalWeather for Energy Calculations or IWEC (Thevenard andBrunger 2002), and more recently TMY3 (Wilcox and Marion2008). Other selection approaches have been proposed (Hui1996).
Limited analyses have been reported to assess the impactof the selection criteria for generating the typical weather yearon predicting the performance of building energy systems(Arigirou et al. 1999 and Massie and Kreider 2001). In partic-ular, Argiriou et al. (1999) tested several different TMYweather files generation procedures for Athens with 20 years(1977 to 1996) measured weather data. They consideredseveral configurations of weighting factors and four methodsto generate typical weather year including: the TMY method(Hall et al. 1978), a Danish method (Lund and Eidorff 1980),Festa-Ratto method (Festa and Ratto 1993), and 20-year aver-age meteorological year. They developed weather data evalu-ation system based on building and solar systems.Specifically, they utilized a simple solar water heating system,a building, a photovoltaic system, and a large scale solar heat-ing system with inter-seasonal storage, and PV system.TRNSYS is used in the evaluation analysis (Anon 2000). Amodified Festa-Ratto method was found to provide the bestdata set for Athens. Massie and Kreider (2001) estimated thediscrepancies between TMY and TMY2s in predicting theperformance of a photovoltaic system and a wind turbine.
In this paper, a series of sensitivity analyses is presentedto assess the impact of the typical weather selection criteria on
©2010 ASHRAE. THIS PREPRINT MAY NOT BE DISTRIBUTED IN PAPER OR DIGITAL FORM IN WHOLE OR IN PART. IT IS FOR DISCUSSION PURPOSES ONLYAT THE 2010 ASHRAE WINTER CONFERENCE. The archival version of this paper along with comments and author responses will be published in ASHRAETransactions, Volume 116, Part 1. ASHRAE must receive written questions or comments regarding this paper by February 12, 2010, if they are to be included inTransactions.
Donghyun Seo is a graduate student and Moncef Krarti, PhD, PE is a Professor and Associate Chair in the Civil, Environmental, and Archi-tectural Engineering Department at the University of Colorado, Boulder, CO. Joe Huang is president of White Box Technologies, Inc., Moraga,CA, and formerly a staff scientist at Lawrence Berkeley National Laboratory, Berkeley, CA.
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
building energy analysis results. In particular, the impacts onannual energy use predictions of weighting factors associatedwith various weather variables and of the length of historicaldata used in the selection procedure are evaluated throughoutthe paper. The analysis is carried out for 10 U.S. sites for whichmeasured weather data for at least 30 years are reported. First,a brief description of the prototypical office building used inthe simulation analysis is provided. Then, the results of thesimulation analyses are presented and discussed.
BUILDING MODEL DESCRIPTION
For this analysis, a prototypical office building wasmodeled using a whole-building hourly simulation tool (LBL1981). The prototypical building model consists of 3-storyoffice building with a gross floor area of 48,000 ft2 (4461 m2)as illustrated in Figure 1. A power density of 0.8 W/ft2 (8.7 W/m2) is assumed for lighting systems equipped with electronicballasts and daylight control sensors. Daylight control cover-age area is 54% covering all the perimeter offices. Officeequipment power density is assumed to be 1.0 W/ft2 (10.8 W/m2) for computers, laser printers, photocopiers, and facsimilemachines. The building envelope is assumed to include 40%fenestration-to-wall ratio with glazing varying by climate to
meet ASHRAE Standard 90.1 (ASHRAE 2004). The outsideair ventilation rate is set to be 20 CFM/person (9.5 L/s perperson). The HVAC system for the building consists of a vari-able air volume (VAV) system with hot water reheat coils anddry-bulb outside air economizer. The central plant includes0.55 kW per ton centrifugal chillers and a 90% efficiency gas-fired boiler. Table 1 provides a summary of the basic featuresof the prototypical office building. Table 2 lists the 10 U.S.sites used to carry out the analysis presented in this paper.
Figure 1 Office building model.
Table 1. Summary of the Basic Features of the Prototypical Office Building Model
Architectural Mechanical
Floor Area 16,000 sf (1487 m2) Design Temp. 75°F/72°F [Cooling/Heating] (24°C/22°C)
Gross Area 48000 sf (4461 m2) Thermo. Set 76°F/82°F (24.5°C/28°C) [Cooling]
60°F/64°F (15.5°C/18°C) [Heating]
Peri. Depth 20 ft (6.1 m) [57% of floor area] HVAC VAV+Reheat
Wall Wood, metal frame, R-19 batt. Overall R-10.5 Fans Variable Speed Drives (VSDs)
Roof Built-up roof, metal frame, R-18 insulation, Overall R-22
OA 20 cfm/person (9.5 L/s per person)
Economizer control
WWR 40% (floor to ceiling) Chiller 0.55 kW/ton
Glazing Variable with climate Boiler 90%
Daylight Control Perimeter zones
Shading 3 ft (0.9 m) overhang on S, E, and W 50fc design level
LPD/ EPD 0.8 /1.0 W/sf(8.7/10.8 W/m2)
Dimming control
Table 2. Selected 10 U.S. Sites
USAF Stations STATE LAT LON ELEV (m) Climate Zone (ASHRAE Std 90.1)
725180 ALBANY COUNTY ARPT NY 42.45N 073.48W 89 5A
722190 ATLANTA INTL ARPT GA 33.39N 084.25W 315 3A
911820 HONOLULU INTL ARPT HI 21.21N 157.56W 5 1A
723860 LAS VEGAS/MCCARRAN NV 36.05N 115.10W 664 5B
726410 MADISON/DANE RGNL WI 43.08N 089.20W 264 6A
722020 MIAMI INTL AIRPORT FL 25.49N 080.17W 4 2A
725500 OMAHA/EPPLEY FIELD NE 41.18N 095.54W 299 5A
722780 PHOENIX/SKY HARBOR AZ 33.26N 112.01W 337 3B
727930 SEATTLE-TACOMA INTL WA 47.27N 122.18W 137 5B
722740 TUCSON INTL AIR PORT AZ 32.07N 110.56W 779 3B
2 OR-10-045 (RP-1477)
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
IMPACT OF TYPICAL WEATHER YEAR
Using the simulation building model, annual total energyconsumption and peak electrical demand are estimated forvarious annual typical weather data sets and are compared tothose mean values obtained from 30 years of simulation data.The typical weather year data sets considered in this analysisinclude:
• IWEC, generated data sets for the 10 U.S. sites using thebasic IWEC selection procedure (Thevenard and Brun-ger 2002),
• TMY, generated data sets for the 10 U.S. sites using theTMY selection procedure outlined by Hall et al. (1978),
• TMY2n, generated data sets for the 10 U.S. sites usingthe TMY2 selection procedure outlined by Marion andUrban (1995),
• TMY2r, existing data sets for the 10 U.S. sites publishedby NREL (Marion and Urban 1995), and
• EqWt, generated data sets for the 10 U.S. sites using aselection procedure based on equal weighting factors asdescribed in Donghyun et al. (2008).
To be consistent with the published TMY2r weather files,meteorological data sets of 30 years spanning from 1961 to1990 were used in generating IWEC, TMY, TMY2n, andEqWt weather files (Donghyun et al. 2008).
Table 3 summarizes the results of the simulation analysisand provides the annual energy use differences in terms ofheating, cooling, and total using the simulation resultsobtained using the 30-year average data set as a reference.Generally, the largest differences (over 5%) are found for heat-ing energy use and for warm climates such as Phoenix and LasVegas. For all sites and weather data sets, cooling energydifferences are generally small ranging from –3 to 1%. Interms of total building energy use, IWEC and TMY2n datasets provide the least differences and EqWt and TMY2r datasets exhibit the largest differences. However, these differencesare not significant and are generally below 2%.
Table 4 presents the differences in electrical annual peakdemand values obtained for various typical weather data usingthe 30-year averages as references. For all sites and weatherdata sets, peak demand differences are below 5%. The aver-ages of the differences for all 10 cities range from 1.6%
Table 3. Annual Total Building Energy Use Differences Between Typical Weather Data and 30-Year Average
IWEC EqWt TMY TMY2n TMY2r
Albany Elec (kWh) 296369 –0.5% 297680 0.2% 296918 0.0% 297164 0.1% 297259 –0.3%Gas (Mbtu/GJ) 736.4 –0.2% 735.7 1.3% 735.9 1.3% 735.4 1.2% 730.6 0.1%
Total (MBtu/GJ) 1747.9 1.4% 1751.7 –0.7% 1749.3 –0.5% 1749.6 –0.6% 1745.1 0.6%Atlanta Elec (kWh) 314559 –0.5% 315552 –0.2% 310582 –1.7% 314401 –0.5% 315018 –0.3%
Gas (Mbtu/GJ) 243.4 6.4% 222 –2.9% 253.5 10.9% 232.2 1.5% 228.6 0.0%Total (MBtu/GJ) 1317.0 0.7% 1299.0 –0.6% 1313.5 0.5% 1305.3 –0.2% 1303.8 –0.3%
Honolulu Elec (kWh) 379932 0.0% 378877 –0.3% 368211 –3.1% 380320 0.1% 377504 –0.7%Gas (Mbtu/GJ) 46.9 1.9% 46.9 1.9% 46.5 1.0% 46.9 1.9% 46.2 0.4%
Total (MBtu/GJ) 1343.6 0.0% 1340.0 –0.2% 1303.2 –3.0% 1344.9 0.1% 1334.6 –0.6%Las Vegas Elec (kWh) 333272 –0.1% 332231 –0.4% 333191 –0.1% 331743 –0.6% 333071 –0.2%
Gas (Mbtu/GJ) 123.4 –3.3% 124.5 –2.5% 128.7 0.8% 123.5 –3.3% 114.4 –10.4%Total (MBtu/GJ) 1260.9 –0.4% 1258.4 –0.6% 1265.9 0.0% 1255.7 –0.8% 1251.2 –1.2%
Madison Elec (kWh) 302346 0.0% 301992 –0.1% 302267 0.0% 301990 –0.1% 300074 –0.7%Gas (Mbtu/GJ) 793.2 –2.3% 790.1 –2.7% 817.9 0.7% 794.8 –2.1% 779.3 –4.0%
Total (MBtu/GJ) 1825.1 –1.0% 1820.8 –1.2% 1849.5 0.3% 1825.5 –1.0% 1803.5 –2.2%Miami Elec (kWh) 377545 –0.5% 377545 –0.5% 378260 –0.3% 377428 –0.5% 379842 0.1%
Gas (Mbtu/GJ) 49 1.4% 49 1.4% 49 1.4% 49 1.4% 47.8 –1.1%Total (MBtu/GJ) 1337.6 –0.4% 1337.6 –0.4% 1340.0 –0.2% 1337.2 –0.4% 1344.2 0.1%
Omaha Elec (kWh) 311337 0.2% 309205 –0.5% 310159 –0.2% 309008 –0.6% 310159 –0.2%Gas (Mbtu/GJ) 655.8 1.9% 631.9 –1.9% 627.8 –2.5% 634.9 –1.4% 627.8 –2.5%
Total (MBtu/GJ) 1718.4 0.8% 1687.2 –1.0% 1686.4 –1.1% 1689.5 –0.9% 1686.4 –1.1%Phoenix Elec (kWh) 358285 0.7% 357580 0.5% 355185 –0.2% 358034 0.6% 355185 –0.2%
Gas (Mbtu/GJ) 70.4 –11.5% 75.7 –4.8% 79.2 –0.4% 72.1 –9.3% 79.2 –0.4%Total (MBtu/GJ) 1293.2 0.0% 1296.1 0.2% 1291.4 –0.2% 1294.1 0.0% 1291.4 –0.2%
Seattle Elec (kWh) 268311 –0.7% 269452 –0.3% 270812 0.2% 269322 –0.3% 270812 0.2%Gas (Mbtu/GJ) 400.5 –0.2% 381.9 –4.8% 400.6 –0.2% 385.6 –3.9% 400.6 –0.2%
Total (MBtu/GJ) 1316.2 –0.5% 1301.5 –1.7% 1324.9 0.1% 1304.8 –1.4% 1324.9 0.1%Tucson Elec (kWh) 333749 –0.2% 333126 –0.4% 335585 0.3% 332106 –0.7% 335585 0.3%
Gas (Mbtu/GJ) 87.5 –6.4% 91.7 –2.0% 89.1 –4.7% 94.1 0.6% 89.1 –4.7%Total (MBtu/GJ) 1226.6 –0.7% 1228.7 –0.5% 1234.5 –0.1% 1227.6 –0.6% 1234.5 –0.1%
OR-10-045 (RP-1477) 3
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
(IWEC) to 2.4% (TMY). The use of TMY2n and TMY2r leadsto respectively 1.84% and 2.17% average differences for theannual electrical peak demand for the prototypical officebuilding considered in this analysis. Figures 2 and 3 providescatter diagrams for respectively the monthly electrical peakdemand and total building energy use obtained from theenergy analysis of the prototypical office building usingTMY2n and TMYr against the same results generated using30-year average data.
Figure 4 illustrates the scatter diagrams of monthly cool-ing and heating energy end-uses obtained using TMY2n andTMY2r weather data plotted against monthly means calcu-lated for the simulation results generated for the 30-yearperiod (1961 to 1990) for all the 10 sites. Table 5 summarizesthe statistical results of the comparative analysis betweenTMY2n and TMY2r and the mean values obtained for the 30-year for both heating and cooling energy end-uses.
Both TMY2n and TMY2r annual weather data setsprovide energy use predictions that are in good agreement withthe mean values of the simulation results compiled for 30years. Generally, the results obtained using TMY2n weatherare statistically slightly closer to the 30-year mean predictionsfor both natural gas and electricity annual energy use thanthose generated with TMY2r. The mean of the differencesassociated with TMY2n and TMY2r are only 0.15% and0.25%, respectively, while the standard deviation of the differ-ences is only 0% and 1.3%, respectively.
IMPACT OF WEIGHTING FACTORS
Using the simulation building model, annual total energyconsumption are estimated for various TMY2 weather datasets obtained using different configurations weighting factors
and are compared to those mean values obtained from 30 yearsweather data. Table 6 lists the weighting factors associatedwith all weather parameters (Donghyun et al. 2008). Dewpoint temperature (DPT) and wind speed (WSP) weightingfactors are set to be constant (10%) due to their relatively smalleffect on building energy use. A 6-digit code is assigned toeach weighting factor configuration. The first 2-digit set is theweight factor (in fraction multiplied by 10) associated withdry-bulb temperature (DBT), the second 2-digit set is theweighting factor associated with the global horizontal solarirradiation (GHI), and the third 2-digit set is the weightingfactor associated with the direct normal solar irradiation(DNI). For example, the code 040400 refers to the case wherea weight factor of 0.4 is assigned for DBT, 0.4 for GHI, and 0.0for DNI.
Table 7 summarizes the results of the simulation analysiswith various weighting factors and provides the annual energyuse differences in terms of heating, cooling, and total using thesimulation results obtained using the 30-year average data setas references. Generally, the largest differences (over 5%) arefound for heating energy use and for warm climates such asAtlanta, Phoenix and Las Vegas. For all sites and weather datasets, cooling energy differences are generally small rangingfrom 3.1% to –1.5%.
For the annual total building energy use, the differences inthe simulation results obtained from the TMY2 data sets andmean value for the 30-year period are below 3% regardless ofweighting configuration. However, these differences canreach 8% for the annual heating energy use when the weight-ing factor on dry bulb temperature is 0.2 or zero.
Figure 5 illustrates the R2 variation of the correlationbetween monthly total building energy use values predictedusing TMY2 and those obtained from averaging 30 years of
Table 4. Annual Electrical Peak Demand Differences Between Typical Weather Data and 30-Year Average
IWEC EqWt TMY TMY2n TMY2r
Albany Peak (kW) 135.9 136.9 135.9 135.9 135.4Diff. % 0.3% 1.0% 0.3% 0.3% –0.1%
Atlanta Peak (kW) 154.5 154.9 151.8 154.5 147.8Diff. % 3.5% 3.7% 1.7% 3.5% –1.0%
Honolulu Peak (kW) 150.5 150.5 146.7 151.8 147.2Diff. % 0.5% 0.5% –2.0% 1.4% –1.7%
Las Vegas Peak (kW) 165.5 165.4 162.3 165.5 168.1Diff. % 1.6% 1.5% –0.4% 1.6% 3.2%
Madison Peak (kW) 144.5 144.3 147.1 139.4 145.3Diff. % 2.8% 2.7% 4.6% –0.8% 3.4%
Miami Peak (kW) 164.7 164.7 156.0 164.7 159.3Diff. % 3.1% 3.1% –2.4% 3.1% –0.3%
Omaha Peak (kW) 149.8 150.5 161.4 150.4 161.4Diff. % –1.6% –1.1% 6.1% –1.2% 6.1%
Phoenix Peak (kW) 171.1 171.1 169.8 171.1 169.8Diff. % –0.6% –0.6% –1.3% –0.6% –1.3%
Seattle Peak (kW) 117.2 115.0 121.3 121.7 121.3Diff. % 1.1% –0.8% 4.6% 4.9% 4.6%
Tucson Peak (kW) 158.3 154.9 156.4 154.9 156.4Diff. % 1.2% –1.0% 0.0% –1.0% 0.0%
4 OR-10-045 (RP-1477)
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
Figure 2 Scatter diagrams of monthly peak demand: TMY2n and TMY2r vs. 30-year weather data.
OR-10-045 (RP-1477) 5
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
Figure 3 Scatter diagrams of monthly energy use: TMY2n and TMY2r vs. 30-year weather data.
6 OR-10-045 (RP-1477)
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
simulation data as a function of the weighting factors associ-ated with 5 U.S. sites. The R2 values are almost equal to 1.0 forall weighting factor configurations except in Atlanta. Thelower R2 values (i.e., R2 > 0.95) are obtained when the weight-ing factor of DBT is set to zero implying that DBT is a crucialparameter to the TMY weather data selection process.
IMPACT OF THE NUMBER OF WEATHER YEARS
Using the simulation building model, annual total energyconsumption are estimated for various TMY2 weather datasets generated from several periods with varying number ofyears and are compared to those mean values obtained from 30years weather data. Table 8 summarizes the results of thesimulation analysis and provides the annual energy use differ-ences in terms of electricity, natural gas, and total energy use
using the simulation results obtained using the 30-year aver-age data set as references. Generally, the largest differencesare found as expected for TMY2 generated from small numberof years.
Figure 6 illustrates the R2 variation of the correlationbetween monthly total building energy use values predictedusing TMY2 and those obtained from averaging 30 years ofsimulation data as a function of the number of years utilized togenerate the typical weather year for 10 U.S. sites. For all sitesexcept Atlanta, the correlation R2 is above 0.95 when morethan 5 years are used to generate TMY weather data. ForAtlanta, there are large differences between monthly heatingenergy use values predicted by TMY2 and mean values for 30years. At lest 12 years are needed to generate TMY2 in orderfor the value of R2 to exceed 0.90 in Atlanta.
An analysis of the historical data show that there is anincrease in average winter temperatures for Atlanta as well asPhoenix and thus a decrease in annual heating degree overbetween 1961 and 1990 as shown in Figure 7. Thus, whenTMY2 is selected based on only few years (starting from1961), the heating degree days will be higher than thatobtained from either 30-year average, or TMY2 based on 25or 30 years. Moreover, the results of Figure 7 indicates that theyears selected for TMY2 during winter months can affectsignificantly the heating energy use predicted for an officebuilding in a warm climate with relatively non negligible heat-ing needs such as Atlanta.
SUMMARY AND CONCLUSIONS
The impact of the selection of typical weather year data onpredicting annual building energy use is investigated andcompared against 30-year average data using statistical anal-
Table 5. Mean and Standard Deviation of the Monthly Values for Monthly Cooling and Heating
Energy End-Uses Obtained for the 30-Year Average, TMY2n, and TMY2r
Cooling Energy (kWh) Heating Energy [MBtu (GJ)]
30 Avg.
Mean 27329.7 Mean 26.7
Standard Deviation
4986.3 Standard Deviation
42.1
Confidence Level (95.0%)
901.3 Confidence Level (95.0%)
7.6
Mean 27262.6 Mean 26.4
TMY2n
Standard Deviation
4986.1 Standard Deviation
42.2
Confidence Level (95.0%)
901.3 Confidence Level (95.0%)
7.6
Mean 27287.6 Mean 26.2
TMY2r
Standard Deviation
4922.9 Standard Deviation
42.2
Confidence Level (95.0%)
889.9 Confidence Level (95.0%)
7.5
Figure 4 Scatter diagrams of monthly cooling and heatingenergy obtained using TMY2n and TMY2r againstmonthly means for 30 years (1961-1990).
Table 6. Weighting Factors Used for the Sensitivity Analysis
Weights DBT DPT WSP GHI DNI
080000 0.8 0.1 0.1 0 0
060200 0.6 0.1 0.1 0.2 0
040400 0.4 0.1 0.1 0.4 0
020600 0.2 0.1 0.1 0.6 0
000800 0 0.1 0.1 0.8 0
060002 0.6 0.1 0.1 0 0.2
040202 0.4 0.1 0.1 0.2 0.2
020402 0.2 0.1 0.1 0.4 0.2
000602 0 0.1 0.1 0.6 0.2
040004 0.4 0.1 0.1 0 0.4
020204 0.2 0.1 0.1 0.2 0.4
000404 0 0.1 0.1 0.4 0.4
020006 0.2 0.1 0.1 0 0.6
000206 0 0.1 0.1 0.2 0.6
000008 0 0.1 0.1 0 0.8
OR-10-045 (RP-1477) 7
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
Table 7. Annual Energy Use Predictions Using TMY2 with Different Weighting Factors Compared Against Mean Annual Energy Use Obtained with Multi-Year Simulations
Numberof yr Energy
Albany Atlanta Honolulu Las Vegas Madison
Energy Use
Diff%
Energy Use
Diff%
Energy Use
Diff%
Energy Use
Diff%
Energy Use
Diff%
30 yr Avg of Multi Year Simulation
Elec (MWh) 141 — 160 — 224 — 334 — 302 —
Gas (MBtu) 726 — 229 — 46 — 128 — 812 —
Total (MBtu) 1207 — 775 — 811 — 1266 — 1844 —
Total (MWh) 354 — 227 — 237 — 371 — 540 —
080000 Elec (MWh) 142 0.6 158 –1.0 222 –0.7 334 0.2 302 –0.1
Gas (MBtu) 734 1.1 239 4.3 46 0.2 128 0.3 813 0.1
Total (MBtu) 1218 0.9 779 0.6 805 –0.6 1269 0.2 1844 0.0
Total (MWh) 357 228 236 372 540
060200 Elec (MWh) 142 0.8 158 –1.3 222 –0.7 334 0.1 302 0.0
Gas (MBtu) 730 0.5 237 3.8 47 1.9 123 –3.3 798 –1.7
Total (MBtu) 1215 0.6 776 0.2 806 –0.5 1263 –0.2 1830 –0.7
Total (MWh) 356 227 236 370 536
060002 Elec (MWh) 142 0.7 159 –0.7 223 –0.4 334 0.0 302 0.0
Gas (MBtu) 734 1.0 241 5.4 46 –0.3 123 –3.7 793 –2.4
Total (MBtu) 1218 0.9 783 1.1 808 –0.4 1261 –0.4 1824 –1.1
Total (MWh) 357 229 237 369 534
040400 Elec (MWh) 140 –0.7 158 –1.3 224 –0.1 333 –0.1 302 0.1
Gas (MBtu) 737 1.4 232 1.5 47 1.9 123 –3.3 804 –1.0
Total (MBtu) 1214 0.6 771 –0.4 811 0.0 1261 –0.4 1837 –0.4
Total (MWh) 356 226 238 369 538
040202 Elec (MWh) 142 0.7 157 –1.8 224 0.0 333 –0.2 303 0.1
Gas (MBtu) 735 1.2 232 1.5 46 –0.3 123 –3.8 804 –1.0
Total (MBtu) 1219 1.0 769 –0.8 810 –0.1 1259 –0.6 1837 –0.4
Total (MWh) 357 225 237 369 538
040004 Elec (MWh) 141 0.0 157 –1.8 224 –0.1 332 –0.6 304 0.4
Gas (MBtu) 726 –0.1 232 1.5 46 –0.3 124 –3.0 804 –1.0
Total (MBtu) 1207 –0.1 769 –0.8 810 –0.1 1256 –0.8 1841 –0.2
Total (MWh) 353 225 237 368 539
020600 Elec (MWh) 141 0.0 157 –2.2 222 –0.7 331 –0.7 301 –0.3
Gas (MBtu) 736 1.3 235 2.9 47 1.9 138 7.7 791 –2.6
Total (MBtu) 1217 0.8 769 –0.7 806 –0.6 1269 0.2 1819 –1.3
Total (MWh) 356 225 236 372 533
020402 Elec (MWh) 141 0.0 158 –1.3 223 –0.5 331 –0.9 302 –0.1
Gas (MBtu) 736 1.3 233 1.8 47 1.9 124 –3.1 789 –2.9
Total (MBtu) 1217 0.8 772 –0.4 808 –0.3 1252 –1.1 1819 –1.3
Total (MWh) 356 226 237 367 533
020204 Elec (MWh) 141 0.1 159 –0.8 224 0.0 332 –0.6 303 0.2
Gas (MBtu) 721 –0.7 225 –1.5 46 –0.3 124 –3.2 795 –2.1
Total (MBtu) 1203 –0.4 767 –1.0 811 0.0 1255 –0.9 1828 –0.9
Total (MWh) 352 225 237 368 535
020006 Elec (MWh) 141 0.2 158 –1.1 223 –0.2 332 –0.6 303 0.3
Gas (MBtu) 726 –0.1 226 –1.4 46 –0.3 126 –1.3 791 –2.6
Total (MBtu) 1207 0.0 766 –1.2 809 –0.2 1257 –0.7 1826 –1.0
Total (MWh) 354 224 237 368 535
8 OR-10-045 (RP-1477)
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
ysis. A comparative analysis based on the average simulationpredictions obtained for 30-year period is carried out. Impactsof weighting factors and the numbers of years used to generatetypical weather data are investigated for 10 U.S. sites.
The results of the simulation analyses presented in thispaper for prototypical office buildings show a maximum 5%difference between the simulation results obtained using anytypical weather data sets (TMY, IWEC, and TMY2) and thoseobtained by averaging the results for 30 years for the 10 U.S.climates considered in this paper. In terms of total building
energy use, IWEC and TMY2n data sets provide the leastdifferences against long-term energy use predictions. More-over, the results indicate that, for the 10 U.S. climates consid-ered in the study, 15 years of recorded data would be sufficientto generate a typical weather year suitable for energy analysisof prototypical office buildings. Additional work is needed togeneralize the results for other climates and building types.
REFERENCES
Argiriou A., S. Lykoudis, S. Kontoyiannidis, C.A. Balaras,A. Asimakopoulos, M. Petrakis, and P. Kassomenos.1999. Comparison of methodologies for TMY genera-tion using 20 years data for Athens, Greece. SolarEnergy 66(1):33-45.
Anon. 2000. TRNSYS: Transient system simulation program.Solar Energy Laboratory, University of Wisconsin,Madison, WI.
ASHRAE. 1976. ASHRAE handbook of fundamentals.American Society of Heating Refrigeration and Air-Conditioning Engineers, Inc., Atlanta.
Crawley, D.B., L.K. Lawrie, C.O. Pedersen, and F.C. Win-kelmann. 2000. Energy plus: Energy simulation pro-gram. ASHRAE Journal 42(4):49-56.
Crow, L.W., 1981, Development of hourly data for weatheryear for energy calculations (WYEC), including solar
000800 Elec (MWh) 140 –0.7 158 –1.4 224 –0.2 331 –0.8 301 –0.3
Gas (MBtu) 739 1.8 234 2.4 47 1.9 131 2.5 775 –4.5
Total (MBtu) 1217 0.8 773 –0.3 810 –0.1 1260 –0.5 1804 –2.2
Total (MWh) 356 226 237 369 528
000602 Elec (MWh) 140 –0.7 158 –0.9 223 –0.2 329 –1.5 302 –0.1
Gas (MBtu) 739 1.8 211 –7.5 47 1.9 133 4.2 784 –3.5
Total (MBtu) 1217 0.8 752 –2.9 810 –0.1 1254 –0.9 1814 –1.6
Total (MWh) 356 220 237 367 531
000404 Elec (MWh) 140 –0.5 158 –0.9 225 0.2 332 –0.3 303 0.2
Gas (MBtu) 739 1.8 240 4.7 45 –1.4 129 0.7 772 –5.0
Total (MBtu) 1218 0.8 780 0.7 812 0.1 1263 –0.2 1805 –2.1
Total (MWh) 357 229 238 370 529
000206 Elec (MWh) 141 0.3 157 –1.7 224 –0.1 333 –0.2 303 0.2
Gas (MBtu) 725 –0.2 244 6.8 45 –1.4 122 –4.4 772 –5.0
Total (MBtu) 1207 0.0 781 0.8 809 –0.2 1259 –0.6 1805 –2.1
Total (MWh) 354 229 237 369 529
000008 Elec (MWh) 140 –0.5 158 –1.1 225 0.4 330 –1.0 303 0.2
Gas (MBtu) 736 1.3 244 6.8 46 –0.3 126 –1.1 768 –5.4
Total (MBtu) 1214 0.6 784 1.2 813 0.3 1254 –1.0 1802 –2.3
Total (MWh) 356 230 238 367 528
Table 7. Annual Energy Use Predictions Using TMY2 with Different Weighting Factors Compared Against Mean Annual Energy Use Obtained with Multi-Year Simulations (continued)
Numberof yr Energy
Albany Atlanta Honolulu Las Vegas Madison
Energy Use
Diff%
Energy Use
Diff%
Energy Use
Diff%
Energy Use
Diff%
Energy Use
Diff%
Figure 5 Impact of TMY2 weighting factors on totalbuilding use predictions for 5 U.S. sites.
OR-10-045 (RP-1477) 9
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
Tabl
e 8.
An
nual
Ene
rgy
Use
Pre
dic
tions
Usi
ng T
MY
2 G
ener
ated
with
Diff
eren
t Nu
mb
er o
f Yea
rs C
om
pare
d A
gai
nst
Mea
n A
nnu
al
Ene
rgy
Use
Obt
aine
d w
ith M
ulti-
Year
Sim
ulat
ion
Num
ber
of y
rE
nerg
y
Alb
any
Atl
anta
Hon
olul
uL
as V
egas
Mad
ison
Mia
mi
Om
aha
Pho
enix
Seat
tle
Tuc
son
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
30 y
r Avg
. of
Mul
ti Y
ear
Sim
ulat
ion
Ele
c (M
Wh)
297
—16
0—
224
—33
4—
302
—37
9—
311
—35
6—
270
—33
5—
Gas
(M
Btu
)72
6—
229
—46
—12
8—
812
—48
—64
4—
80—
401
—94
—
Tota
l (M
Btu
)17
40—
775
—81
1—
1266
—18
44—
1343
—17
04—
1294
—13
23—
1235
—
28 y
r(6
3-90
)E
lec
(MW
h)29
6–0
.431
596
.938
069
.833
2–0
.530
1–0
.337
7–0
.630
9–0
.635
90.
826
9–0
.333
3–0
.3
Gas
(M
Btu
)74
82.
922
0–3
.747
1.9
130
1.7
793
–2.3
48–0
.563
5–1
.477
–3.0
386
–3.9
90–4
.2
Tota
l (M
Btu
)17
571.
012
9567
.213
4566
.012
62–0
.318
21–1
.213
35–0
.616
90–0
.913
010.
613
05–1
.412
28–0
.6
26 y
r(6
5-90
)E
lec
(MW
h)29
70.
031
596
.837
969
.433
2–0
.330
20.
037
8–0
.431
0–0
.335
70.
426
9–0
.433
3–0
.3
Gas
(M
Btu
)72
3–0
.521
1–7
.747
1.9
128
0.4
818
0.7
48–1
.563
2–1
.984
6.2
382
–4.8
90–4
.2
Tota
l (M
Btu
)17
36–0
.212
8565
.913
4265
.612
63–0
.318
490.
313
37–0
.416
89–0
.913
040.
813
01–1
.712
28–0
.6
24 y
r(6
7-90
)E
lec
(MW
h)29
70.
131
496
.438
170
.333
50.
330
30.
237
9–0
.230
8–0
.836
01.
126
9–0
.433
4–0
.3
Gas
(M
Btu
)72
5–0
.221
8–4
.845
–1.4
125
–2.2
811
–0.2
48–1
.564
3–0
.277
–3.0
388
–3.3
90–4
.2
Tota
l (M
Btu
)17
390.
012
9066
.513
4766
.212
670.
118
440.
013
40–0
.216
95–0
.613
050.
913
07–1
.312
28–0
.6
22 y
r(6
9-90
)E
lec
(MW
h)29
70.
031
697
.438
069
.533
40.
030
30.
237
8–0
.430
9–0
.736
01.
126
9–0
.333
4–0
.3
Gas
(M
Btu
)72
70.
020
6–9
.745
–1.4
128
0.4
831
2.4
48–1
.563
2–1
.977
–3.0
386
–3.8
92–2
.1
Tota
l (M
Btu
)17
400.
012
8465
.713
4165
.512
670.
018
651.
113
37–0
.416
85–1
.113
050.
913
05–1
.412
30–0
.4
20 y
r(7
1-90
)E
lec
(MW
h)29
70.
131
596
.837
969
.133
3–0
.130
30.
338
10.
431
0–0
.436
01.
227
0–0
.233
40.
0
Gas
(M
Btu
)72
0–0
.921
0–8
.047
1.9
130
1.5
840
3.5
46–4
.064
3–0
.177
–3.0
390
–2.9
89–4
.7
Tota
l (M
Btu
)17
35–0
.312
8565
.913
3965
.212
670.
118
751.
713
460.
316
99–0
.313
061.
013
10–1
.112
31–0
.4
18 y
r(7
3-90
)E
lec
(MW
h)29
70.
031
797
.938
170
.133
50.
630
30.
338
00.
231
0–0
.336
11.
526
9–0
.533
40.
0
Gas
(M
Btu
)72
0–0
.919
1–1
6.5
471.
912
1–5
.683
32.
646
–4.0
647
0.5
77–3
.338
6–3
.889
–4.7
Tota
l (M
Btu
)17
34–0
.312
7164
.113
4766
.212
65–0
.118
681.
313
440.
117
050.
013
091.
213
03–1
.512
31–0
.4
16 y
r(7
5-90
)E
lec
(MW
h)29
7–0
.131
899
.038
170
.233
60.
830
40.
537
7–0
.631
0–0
.236
01.
126
9–0
.433
60.
5
Gas
(M
Btu
)70
3–3
.221
6–5
.447
1.9
121
–5.6
868
6.9
490.
665
61.
978
–2.0
382
–4.9
89–4
.7
Tota
l (M
Btu
)17
15–1
.413
0368
.213
4866
.412
680.
219
053.
313
35–0
.617
140.
613
060.
913
00–1
.812
370.
1
14 y
r(7
7-90
)E
lec
(MW
h)29
70.
131
999
.438
571
.833
81.
430
40.
637
7–0
.731
0–0
.336
11.
527
0–0
.133
80.
9
Gas
(M
Btu
)71
0–2
.321
5–6
.145
–1.8
121
–5.6
875
7.7
48–0
.367
34.
675
–6.2
381
–5.0
951.
8
Tota
l (M
Btu
)17
24–0
.913
0368
.213
5967
.612
750.
719
123.
713
34–0
.617
311.
613
071.
013
03–1
.612
471.
0
10 OR-10-045 (RP-1477)
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
12 y
r(7
9-90
)E
lec
(MW
h)29
80.
331
899
.138
471
.633
60.
730
30.
338
10.
630
8–0
.936
32.
226
9–0
.333
91.
2
Gas
(M
Btu
)72
2–0
.520
2–1
1.5
46–0
.312
0–5
.882
92.
147
–3.0
677
5.2
73–8
.639
6–1
.294
0.1
Tota
l (M
Btu
)17
39–0
.112
8966
.413
5867
.512
670.
118
641.
113
490.
417
281.
413
131.
513
15–0
.612
501.
2
10 y
r(8
1-90
)E
lec
(MW
h)29
80.
231
898
.538
471
.233
3–0
.330
40.
638
10.
630
7–1
.136
62.
926
9–0
.333
70.
9
Gas
(M
Btu
)71
2–2
.020
9–8
.445
–1.8
127
–0.8
793
–2.4
47–3
.065
21.
273
–8.6
390
–2.8
952.
0
Tota
l (M
Btu
)17
28–0
.712
9367
.013
5467
.112
62–0
.418
30–0
.713
490.
417
01–0
.213
222.
213
10–1
.012
470.
9
08 y
r(8
3-90
)E
lec
(MW
h)29
90.
632
110
0.4
384
71.3
334
0.0
304
0.7
378
–0.2
311
0.1
363
2.2
272
0.5
339
1.3
Gas
(M
Btu
)70
2–3
.418
8–1
7.6
460.
612
5–2
.177
4–4
.847
–3.0
650
1.0
73–8
.640
40.
695
1.9
Tota
l (M
Btu
)17
22–1
.012
8265
.513
5667
.312
63–0
.218
12–1
.713
39–0
.317
120.
413
131.
513
300.
512
511.
3
06 y
r(8
5-90
)E
lec
(MW
h)29
70.
132
099
.938
572
.033
91.
530
40.
438
10.
531
10.
036
32.
127
31.
134
22.
3
Gas
(M
Btu
)69
1–4
.820
1–1
2.3
460.
612
90.
775
5–7
.147
–3.6
640
–0.5
69–1
3.7
392
–2.2
962.
2
Tota
l (M
Btu
)17
06–1
.912
9266
.813
6167
.912
841.
417
91–2
.913
480.
417
01–0
.213
091.
213
250.
112
642.
3
05 y
r(8
6-90
)E
lec
(MW
h)29
80.
332
110
0.6
387
72.8
335
0.5
302
0.1
384
1.2
311
0.0
365
2.6
273
0.9
342
2.3
Gas
(M
Btu
)68
2–6
.119
7–1
4.0
46–0
.512
3–3
.570
4–1
3.4
47–2
.557
3–1
1.0
73–8
.736
4–9
.493
–0.4
Tota
l (M
Btu
)16
98–2
.412
9266
.813
6768
.612
680.
117
36–5
.913
581.
116
34–4
.113
181.
912
94–2
.312
622.
1
04 y
r(8
7-90
)E
lec
(MW
h)29
90.
731
999
.638
371
.234
12.
130
40.
538
31.
031
40.
936
73.
127
20.
834
22.
1
Gas
(M
Btu
)65
3–1
0.0
194
–15.
245
–1.8
127
–0.3
715
–11.
947
–3.6
593
–7.9
73–8
.636
3–9
.493
–0.2
Tota
l (M
Btu
)16
74–3
.812
8465
.713
5467
.012
901.
917
52–5
.013
550.
916
63–2
.413
242.
412
93–2
.312
591.
9
03 y
r(8
8-90
)E
lec
(MW
h)29
80.
432
210
1.5
384
71.4
339
1.7
303
0.2
387
2.0
309
–0.4
366
2.9
271
0.2
344
2.7
Gas
(M
Btu
)68
0–6
.418
8–1
7.8
45–1
.813
98.
774
6–8
.246
–4.4
579
–10.
072
–9.7
406
1.1
86–7
.7
Tota
l (M
Btu
)16
97–2
.412
8866
.313
5667
.312
972.
417
80–3
.513
671.
816
35–4
.113
222.
113
300.
512
591.
9
02 y
r(8
9-90
)E
lec
(MW
h)29
7–0
.132
610
3.7
378
69.0
339
1.7
303
0.3
391
3.2
311
0.0
367
3.2
274
1.5
344
2.7
Gas
(M
Btu
)66
1–9
.018
2–2
0.4
46–0
.314
09.
680
4–1
.046
–4.2
646
0.4
74–6
.842
56.
089
–5.3
Tota
l (M
Btu
)16
73–3
.812
9467
.113
3865
.012
982.
518
38–0
.313
822.
917
070.
113
282.
613
612.
912
622.
1
Tabl
e 8.
An
nual
Ene
rgy
Use
Pre
dic
tions
Usi
ng T
MY
2 G
ener
ated
with
Diff
eren
t Nu
mb
er o
f Yea
rs C
om
pare
d A
gai
nst
Mea
n A
nnu
al
Ene
rgy
Use
Obt
aine
d w
ith M
ulti-
Year
Sim
ula
tion
(con
tinue
d)
Num
ber
of y
rE
nerg
y
Alb
any
Atl
anta
Hon
olul
uL
as V
egas
Mad
ison
Mia
mi
Om
aha
Pho
enix
Seat
tle
Tuc
son
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
Ene
rgy
Use
Dif
f.%
OR-10-045 (RP-1477) 11
Authors may request permission to reprint or post on their personal or company Web site once the final version of the article has been published. A reprint permission form may be found at www.ashrae.org.
data, at 21 stations throughout the US. ASHRAE Trans-actions 87(1):896-905.
Donghyun, S., M. Krarti, and J. Huang. 2008. Evaluation oftypical weather year selection approaches. Submitted toASHRAE Transactions, Atlanta.
Festa, R. and C.F. Ratto. 1993. Proposal of a numerical pro-cedure to select reference years. Solar Energy 50:9-17.
Hall, I.J., R.R. Prairie, H.E. Anderson, and E.C. Boes. 1978.Generation of a typical meteorological year. In: Pro-ceedings of the 1978 annual meeting of the AmericanSection of ISES, pp. 669-671.
Hui, C.M. 1996. Energy performance of air-conditionedbuildings in Hong Kong, PhD Thesis. City University ofHong Kong.
Keeble, E. 1990. Availability of UK climatic data for use insimulation, BEPAC Technical Note 90/1, Building Re-search Establishment, U.K., October.
LBL. 1981. DOE reference manual version 2.1A. Preparedfor the U.S. Department of Energy by Lawrence Berke-ley Laboratory, Report LBL-8706 Rev. 2.
Lund, H. and S. Eidorff. 1980. Selection methods for pro-duction of test reference years. Appendix D, contract284-77 ES DK. Final report EUR 7306 EN. Copenha-gen: Technical University of Denmark, Thermal Insula-tion Laboratory.
Marion, W. and K. Urban. 1995. Users manual for TMY2stypical meteorological years. National RenewableEnergy Laboratory, Golden, CO.
Massie, D.D. and J.F. Kreider. 2001. Comparison of and dis-crepancies between TMY and TMY2s predictions forsimple photovoltaic and wind energy simulation, ASMETrans, vol. 123.
Thevenard, D.J. and A.P. Brunger. 2002. The development oftypical weather years for international locations, Part II,Production, ASHRAE Transaction 108(2):480-486.
Wilcox, S. and W. Marion. 2008. Users manual for TMY3data sets, NREL Technical Report NREL/TP-581-43156,April, Golden, CO.
Figure 6 Impact of number of years used to generate TMY2data sets on R2 of the correlation total buildinguse predictions from TMY2 and mean of 30 yearsresults for 10 U.S. sites.
Figure 6 Historical annual heating degree days (HDD)variation from 1961 to 1990.
12 OR-10-045 (RP-1477)