options - power-genexpower-genex.com/_uploadfiles2/data/001017/481496025029... · 2017. 5. 29. ·...

4
Flameproof IECEx / ATEX / KC Ex d IIB+H 2 T6 - IP67 Rugged aluminum die-cast housing Compact single unit with built-in solenoid valve Auto / Manual button easy to convert NAMUR mounting shaft or fork lever shaft adjustable for a non-NAMUR pneumatic actuator Options 4 x SPDT mechanical limit switch 4 x P&F proximity sensor 2 x Hermetically sealed magnetic sensor 4 - 20mA output position transmitter More economical in costs and simple wiring to a single unit comparison with separate installations of explosion proof limit switches and explosion proof solenoid valve

Upload: others

Post on 09-Sep-2020

0 views

Category:

Documents


0 download

TRANSCRIPT

Page 1: Options - POWER-GENEXpower-genex.com/_uploadfiles2/data/001017/481496025029... · 2017. 5. 29. · 0.01 ~ 0.1 mm > 3 mA < 1 mA cable PCV, 130 mm 0.14 mm PBT PBT IP67-25 ~ +100℃

Flameproof IECEx / ATEX / KC Ex d IIB+H2 T6 - IP67

Rugged aluminum die-cast housing

Compact single unit with built-in solenoid valve

Auto / Manual button easy to convert

NAMUR mounting shaft or fork lever shaft adjustable for a non-NAMUR pneumatic actuator

Options

4 x SPDT mechanical limit switch4 x P&F proximity sensor2 x Hermetically sealed magnetic sensor4 - 20mA output position transmitter

More economical in costs and simple wiring to a single unit comparison with separate installations of explosion proof limit switches and explosion proof solenoid valve

Page 2: Options - POWER-GENEXpower-genex.com/_uploadfiles2/data/001017/481496025029... · 2017. 5. 29. · 0.01 ~ 0.1 mm > 3 mA < 1 mA cable PCV, 130 mm 0.14 mm PBT PBT IP67-25 ~ +100℃

Valve Monitoring Controller

Mechanical Switches

Proximity Sensors

BN

BU

L +

L -

Switching element functionRated operating distanceInstallationOutput polarityAssured operating distance

Nominal voltageSwitching frequencyHysteresisCurrent consumption Measuring plate not detected Measuring plate detected

Connection typeCore cross-sectionHousing materialSensing faceProtection degree

NJ2-V3-N / P&F

NAMUR NC2mmembeddableNAMUR0 ~ 1.62mm

8.2 VDC0 ~ 1000 Hz0.01 ~ 0.1 mm

> 3 mA< 1 mA

cable PCV, 130 mm0.14 mmPBTPBTIP67-25 ~ +100℃

General Specifiactions

Nominal Ratings

Mechanical Specifications

Operating Temperature

Switching element functionRated operating distanceInstallationOutput polarityAssured operating distance

Nominal voltageSwitching frequencyHysteresisCurrent consumption Measuring plate not detected Measuring plate detected

Connection typeCore cross-sectionHousing materialSensing faceProtection degree

NJ4-12GK-SN / P&F

NAMUR NC4 mmnot embeddableNAMUR0 ~ 3.24 mm

8.2 VDC0 ~ 1500 Hz3 %

> 3 mA< 1 mA

cable PCV, 2 m0.34 mmPBTPBTIP66-50 ~ +100℃

General Specifiactions

Nominal Ratings

Mechanical Specifications

Operating Temperature< Wiring >

< NJ4-12GK-N / P&F >

< NJ2-V3-N / P&F >

Operating Temperature -20 ~ +105℃

SPDT, SZM-V16-2FA-61 / STARION

Type

Rating

Non-inductive load

250 VAC8 VDC30 VDC125 VDC250 VDC

Resistive load16A16A10A0.6A0.3A

Lamp load2A4A4A

0.1A0.05A

Inductive loadInductive load

10A10A10A0.6A0.3A

Motor load3A6A4A

0.1A0.05A

Operating Temperature -20 ~ +80℃

DPDT, DZ-10G / OMRON

Type

Rating

Non-inductive load

125 VAC250 VAC8 VDC14 VDC30 VDC125 VDC250 VDC

Inductive load

NC2A

1.5A3A3A3A

0.5A0.25A

NO1A

0.7A1.5A1.5A1.5A0.5A

0.25A

Lamp loadResistive loadNC NO NC

3A2A5A5A3A

0.05A0.03A

NO1.5A1A

2.5A2.5A1.5A

0.05A0.03A

Motor loadInductive load

10A10A10A10A10A0.5A

0.25A

6A4A6A6A4A

0.05A0.03A

NC NO< DPDT Mechanical Switch >

< SPDT Mechanical Switch >

SPDT Switch 1 SPDT Switch 2

1NC C NO NC C NO

2 3 4 5 6

DPDT Switch 1

1NO1 NC1 COM1 NO2 NC2 COM2

2 3 4 5 6

DPDT Switch 2

7 8 9 10 11 12NO1 NC1 COM1 NO2 NC2 COM2

M2

Page 3: Options - POWER-GENEXpower-genex.com/_uploadfiles2/data/001017/481496025029... · 2017. 5. 29. · 0.01 ~ 0.1 mm > 3 mA < 1 mA cable PCV, 130 mm 0.14 mm PBT PBT IP67-25 ~ +100℃
Page 4: Options - POWER-GENEXpower-genex.com/_uploadfiles2/data/001017/481496025029... · 2017. 5. 29. · 0.01 ~ 0.1 mm > 3 mA < 1 mA cable PCV, 130 mm 0.14 mm PBT PBT IP67-25 ~ +100℃

133.4

Solenoid Valve

164.3

30.2

4Auto / ManualBotton92

55.1

5510

55.1

133.4

146.4

83.750

57

57

28.5

28.5

23

4-M64-M8

196.6

7

< Dual Coil Type >189.6

Pad

< Single Coil Type >

01

N024

6789

NO

NSD

ABC

::

::::

::::

::

:::

:::

Mechanical switchesProximity sensors

None2 x SPDT4 x SPDT2 x DPDT

2 x NJ2-V3-N / P&F4 x NJ2-V3-N / P&F2 x NJ2-12GM-N / P&F4 x NJ2-12GM-N / P&F

None4 ~ 20mA output signal

NoneSingle coil typeDual coil type

220VAC110VAC24VDC

Switch Type :

Switch / Sensor : - Mechanical Switches

- Proximity Sensors

Position Transmitter : (only for 2 x switch / sonsor)

Coil Type :

Pilot Power Supply