On LoadTap Changers
OLTC type RS 5 / RS 5.3 RSV 5.3
Mechanical endurance 500,000 s.o. 500,000 s.o.
Electrical endurance 150,000 s.o. 300,000 s.o.
Maximum rated currents 200, 400, 630, 1250 A up to 1250 A
Highest voltage for equipment up to 72,5 kV up to 36 kV
Step voltage up to 3000 V up to 1000 V
Maximum number of tap operating positions 14 / 27 14 / 27
Tap selector insulation level K, L K
elliptic / round round
Three phase design for transformers with delta connected windings
02www.seielectric.com
On Load Tap Changers
03
OLTC type RS 6 / RS 6.3 RSV 6.3
Mechanical endurance 500,000 s.o. 500,000 s.o.
Electrical endurance 150,000 s.o. 300,000 s.o.
Maximum Rated Currents up to 1250 A up to 1200 A
Highest voltage for equipment up to 300 kV up to 300 kV
Step voltage up to 2500 V up to 2500 V
Maximum number of tap operating positions 14 / 27 14 / 27
Tap selector insulation level K, L, M K, L, M
elliptic / round round
Three phase design for regulation at neutral point
www.seielectric.com
On Load Tap Changers
04
OLTC type RS 7 RSV 7.3
Mechanical endurance 500,000 s.o. 500,000 s.o.
Electrical endurance 500,000 s.o. 500,000 s.o.
Maximum Rated Currents 200, 400, 630, 800 A 400, 550, 700, 1200 A
Highest voltage for equipment up to 300 kV up to 300 kV
Step voltage up to 3000 V up to 3000 V
Maximum number of tap operating positions 107 107
Tap selector insulation level M, N M, N
round round
Single phase design with increased number of operating positions
On Load Tap Changers
www.seielectric.com
OLTC type RS 9 / RS 9.3 RSV 9.3
Mechanical endurance 1 000,000 s.o. 1 200,000 s.o.
Electrical endurance 500,000 s.o. 500,000 s.o.
Maximum Rated CurrentsI ph: 200, 400, 630, 800, 1200, 1600 AIII ph: 200, 400, 630 A
I ph: 400, 550, 700, 1200, 1500 AIII ph: 400, 550, 700
Highest voltage for equipment up to 300 kV up to 300 kV
Step voltage up to 4000 V up to 3500 V
Maximum number of tap operating positions 18 / 35 18 / 35
Tap selector insulation level K, L, M, N, P K, L, M, N, P
elliptic / round elliptic / round
Single phase design for regulation at any point on the winding
Three phase design for regulation at neutral point
05
On Load Tap Changers
www.seielectric.com
OLTC type RS 12 RSV 12
Mechanical endurance 500,000 s.o. 1 200,000 s.o.
Electrical endurance 200,000 s.o. 800,000 s.o.
Maximum Rated Currents 200, 400 A 250, 400, 600 A
Highest voltage for equipment up to 145 kV up to 145kV
Step voltage up to 2500 V up to 2500 V
Maximum number of tap operating positions 14 / 27 12 / 23
round round
Single phase design for regulation at any point on the winding
Compact three phase designfor transformers with star and delta connected windings
06
On Load Tap Changers
www.seielectric.com
OLTC type RS 21
Mechanical endurance 800,000 s.o.
Electrical endurance 200,000 s.o.
Maximum Rated Currents 310 A
Highest voltage for equipment 72,5 kV
Step voltage 1200 V
Maximun number of tap operating positions up to 23
Tap selector insulation level L
Carrying flange shape elliptic
Single phase design used in SF6 Gas Insulated Transformers
07
On Load Tap Changers
www.seielectric.com