on line pd monitoting of power system components

Upload: jjcanoolivares

Post on 03-Jun-2018

311 views

Category:

Documents


20 download

TRANSCRIPT

  • 8/11/2019 On Line PD Monitoting of Power System Components

    1/148

    Sung In Cho

    On-Line PD (Partial Discharge)

    Monitoring of Power System Components

    School of Electrical Engineering

    Thesis submitted for examination for the degree of Master of

    Science in Technology.

    Espoo 09.09. 2011

  • 8/11/2019 On Line PD Monitoting of Power System Components

    2/148

    Abstract

    AALTO UNIVERSITY ABSTRACT OF THE

    SCHOOL OF ELECTRICAL ENGINEERING MASTERS THESIS

    Author: Sung In Cho

    Title: On-Line PD (Partial Discharge) Monitoring of Power system Components

    Date: 09.09.2011 Language: English Number of pages: 13+135

    Department of Electrical Engineering

    Professorship: Power systems and High voltage Engineering Code: S-18

    Supervisor: Prof. Matti Lehtonen

    Instructor: D.Sc. (Tech.) Petri Hyvnen

    Condition based maintenance has emerged as a priority issue in modern power

    systems, and has reminded so for last several decades. Appropriate monitoring

    and diagnosis before severe faults occur make it possible to control and operate

    power systems in a more reliable, effective, and sustainable way. Compared other

    monitoring techniques, Partial Discharge (PD) monitoring seems the most

    promising methodology for detecting possible dielectric breakdown, aging and

    ultimately faults in power system components. In order to maximize the benefits

  • 8/11/2019 On Line PD Monitoting of Power System Components

    3/148

    Acknowledgements

    This thesis was done in the department of Electrical Engineering in Aalto University

    School of Electrical Engineering in Espoo, Finland in collaboration with Doble

    Lemke in Dresden, Germany. To begin with, I truly appreciate to my supervisor, Prof.

    Matti Lehtonen, with his guide and supports during this thesis work. In addition, I

    also would like to express my gratitude to D.Sc. (Tech.) Petri Hyvnen, instructor, for

    his guide, advice and encourage. Thanks to Dr. Stefan Kornhuber, engineering

    manager in Doble Lemke, I can finalize my thesis work in a more fruitful, valuable,

    and reliable way with his precise comments and critical advice. Moreover it is very

    important to express my appreciation to the Service team in Doble Lemke and other

    kind staffs especially for the one who took me to the city centre when I lost my last

    bus at the first day in the Kesselsdorf.

    I certainly appreciate my friends so-called Otaniemi Familyin Finland who has the

    same family name, ByungJin, KyungHyun, and EunAh. I am deeply thankful to all

    b h i d KOSAFI b h ll h i d I l

  • 8/11/2019 On Line PD Monitoting of Power System Components

    4/148

    List of Abbreviations

    PD Partial Discharge

    IEC International Electrotechnical Commission

    CBM Condition Based Maintenance

    HF High Frequency

    VHF Very High Frequency

    UHF Ultra High Frequency

    AE Acoustic Emission

    UPS Uninterruptible Power Supply

    HVE High Voltage Equipment

    GIS Gas Insulated System

    TEAM Th l El i l A bi d M h i l

  • 8/11/2019 On Line PD Monitoting of Power System Components

    5/148

    AM/FM Amplitude Modulation/ Frequency Modulation

    k-NN K Nearest Neighbour

    NN Neural Network

    BNN Back propagation Neural Network

    PNN Probabilistic Neural Network

    PSA Pulse Sequence Analysis

    DP Degree of Polymerization

    FDS Frequency Domain Spectrum

    PDC Polarization/Depolarization Current analysis

    FRA Frequency Response Analysis

    C&PF Capacitance and Power Factor

    C&DF Capacitance and Dissipation Factor

    IRA Impulse Response Analysis

  • 8/11/2019 On Line PD Monitoting of Power System Components

    6/148

    XLPE Cross-linked Polyethylene

    PVC Poly Vinyl Chloride

    EPR Ethylene Propylene Rubber

    TDR Time Domain Reflectometry

    FTRC Frequency Turned Resonant Circuit

    ITRC Inductively Turned Resonant Circuit

    HVDC High Voltage Direct Current

    PDIV Partial Discharge Inception Voltage

    GPS Global Positioning System

    TCP/IP Transmission Control Protocol/Internet Protocol

    RTU Ring Main Unit

    PILC Paper Insulated Lead Cable

    MIND Mass-Impregnated Non-Draining paper insulated cable

  • 8/11/2019 On Line PD Monitoting of Power System Components

    7/148

    TE Transverse Electric Wave

    TM Transverse Magnetic Wave

    UI User Interface

    PC Personal Computer

    RF Radio Frequency

    TF map Time/Frequency map

  • 8/11/2019 On Line PD Monitoting of Power System Components

    8/148

    List of symbol

    aC Capacitance of the test object

    bC Stray capacitance of the PD source

    cC Internal capacitance of PD source

    kC Measuring Capacitor

    1U Applied test voltage

    2U Voltage drop across the PD source

    3U Voltage drop across the mR

    mC Measuring capacitor

    mR Measuring resistor

    sG Grounding switch

  • 8/11/2019 On Line PD Monitoting of Power System Components

    9/148

    0R Reading of the PD instrument

    0q Known calibrating charge

    iP The probability of appearance for that value ix in the i-th phase

    u The mean value

    2 The variance

    1

    1

    i

    i

    dy

    dx The differential coefficient before and after the peak of the distribution

    ix The average discharge magnitude of the positive half cycle

    iy The average discharge magnitude of the negative half cycle

    sQ The sum value of discharges of the mean pulse height distribution in

    the negative cycle

    sQ The sum value of discharges of the mean pulse height distribution in

  • 8/11/2019 On Line PD Monitoting of Power System Components

    10/148

    initialDP Initial DP

    e Eulers number

    1C The HV capacitance of the bushing

    2C The LV capacitance of the bushing

    L The test inductance (or external inductor)

    C The cable capacitance

    c The cut-off wave length

    a The outer radius of the conductor

    b The inner radius of the conductor

    0c The propagation velocity of the signal (30cm/ns)

  • 8/11/2019 On Line PD Monitoting of Power System Components

    11/148

    Table of Contents

    Abstract........................................................................................................................... i

    Acknowledgements ....................................................................................................... ii

    List of Abbreviations................................................................................................... iii

    List of symbol ............................................................................................................... vii

    Table of Contents .......................................................................................................... x

    CHAPTER 1 ................................................................................................................. 1

    1 Introduction .......................................................................................................... 1

    1.1

    Motivation................................................................................................. 1

    1.2

    Condition Based Maintenance on Power System ..................................... 3

    1.3

    PD monitoring in power system ............................................................... 5

    1.4

    Thesis Overview ....................................................................................... 6

    1.5

    The aim of the Thesis ............................................................................... 7

    CHAPTER 2 ................................................................................................................. 8

    2 PD measurement System ..................................................................................... 8

    2.1

    PD monitoring system configuration ........................................................ 8

  • 8/11/2019 On Line PD Monitoting of Power System Components

    12/148

    3.3.2 Time resolved method ............................................................................ 37

    3.3.3 3-Phase Amplitude Relation Diagram (3 PARD) ................................... 38

    3.4 PD feature extraction and de-noising ..................................................... 38

    3.4.1 Noises in PD ........................................................................................... 39

    3.4.2 Gating and Windowing ........................................................................... 39

    3.4.3 Pulse arrival time difference ................................................................... 40

    3.4.4 Digital filter method ............................................................................... 41

    3.4.5 Signal processing method ....................................................................... 41

    3.4.6 Statistical method.................................................................................... 42

    3.4.7

    PD pulse shape method ........................................................................... 44

    3.5

    PD pattern classification ......................................................................... 44

    3.5.1

    Distance classifier ................................................................................... 44

    3.5.2 Neural Network (NN) ............................................................................. 453.5.3

    Support Vector Machine (SVM) ............................................................ 46

    3.5.4

    Pulse Sequence Analysis (PSA) ............................................................. 47

    3.6

    Signal processing of PD signal ............................................................... 48

    CHAPTER 4 ............................................................................................................... 49

    4 PD M it i P S t C t 49

  • 8/11/2019 On Line PD Monitoting of Power System Components

    13/148

    4.3.3 Different diagnosis and monitoring techniques on rotating machines ... 75

    4.3.4 On-line PD monitoring on rotating machines ......................................... 77

    4.3.5 Available products for on-line PD monitoring of RM ........................... 79

    4.3.6 Summary and Conclusion ....................................................................... 80

    4.4 GIS (Gas Insulated System).................................................................... 81

    4.4.1 GIS in power system ............................................................................... 81

    4.4.2 PD types in GIS ...................................................................................... 83

    4.4.3 Different diagnosis and monitoring techniques on GIS ......................... 84

    4.4.4 On-line PD monitoring on GIS ............................................................... 85

    4.4.5

    Available products on-line PD monitoring of GIS ................................. 87

    4.4.6

    Summary and Conclusion ....................................................................... 89

    4.5

    On-line PD monitoring on power system components ........................... 90

    CHAPTER 5 ............................................................................................................... 91

    5

    Conclusion and Future work ............................................................................ 91

    References ................................................................................................................... 93

    Appendix 1: CASE STUDY 1....................................................................................... 116

    Appendix 2: CASE STUDY 2....................................................................................... 120

    A di 3 CASE STUDY 3 125

  • 8/11/2019 On Line PD Monitoting of Power System Components

    14/148

    CHAPTER1

  • 8/11/2019 On Line PD Monitoting of Power System Components

    15/148

    monitoring power systems which are the most intricate system humans have ever

    made in history.

    Compared to many protection methods in power system, Partial Discharge (PD) is

    considered as one of the most promising solutions for monitoring and detecting

    possible faults in the system before they occur. Thanks to the development of other

    engineering areas such as radio communication, computer science and signal

    processing, protection systems are becoming cheaper and more robust, also highsensitivity. PD is able to find possible symptoms of faults in the system in the most

    fundamental and simplest way.

    With IEC 60270 and other standards regarding PD monitoring, PD measurement

    techniques and calibration had been established with detailed explanations for

    monitoring purposes. Since direct detection of PD is not possible, conventionally

    technicians have been using so-called apparent change detection. Whilst traditional

    methods are detected after failure or discrete periodic interval monitoring, modem

    techniques are largely dependent on the relative changes of important parameters in

    time or frequency domain. As a result, Condition Based Maintenance (CBM) has been

  • 8/11/2019 On Line PD Monitoting of Power System Components

    16/148

    1.2 Condition Based Maintenance on Power System

    The most significant issue for industrial utilities is the protection of possible faults

    which usually incur tremendous repair cost and inconvenience to the customer. Even

    though Uninterruptible Power Supply (UPS) makes it possible to operate electrical

    equipment in hospital or factories that require a stable and continuous power supply,

    unexpected power interruption increases the possibility of large scale disaster and

    cascade blackout. Therefore utilities have been developing proper monitoring system

    for power system in order to predict and prevent electrical faults before they occur.

    Largely, there are two considerable reasons for CBM.

    1. Maintenance of good operating condition has become a priority for preventing

    penalty cost and protecting expensive electric High Voltage Equipment (HVE).

    2. With technological progress in computer science, signal processing, and radio

    communication, CBM operating with reasonable price and reliable accuracy has

    arisen [2].

  • 8/11/2019 On Line PD Monitoting of Power System Components

    17/148

    Figure. 1.1TEAM stress on Power System Components [7, 8]

    Regarding the monitoring insulation system of power system components, there are

    four main influencing factors affecting the lifetime of the insulation system, known as

  • 8/11/2019 On Line PD Monitoting of Power System Components

    18/148

    2. Appropriate signal processing makes it possible for on-line PD monitoring

    without noises around the monitored equipment.

    3. Sensors and tools for on-line PD monitoring are widely available at a relatively

    reasonable price.

    4. Continuous PD information with analysis facilitates possible life prediction

    modelling of HVE [5].

    5. On-line PD monitoring is possible while the system components are in operation

    otherwise they need to be disconnected and tested in the laboratory, entailing

    expensive costs for conducting off-line tests [6].

    Since measuring electromagnetic field change is effective even in a noisyenvironmental and while power components are in operation, on-line PD monitoring

    on power system components will provide enough information for CBM, operating

    the power system in a safe, reliable and, predictable way.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    19/148

    placement internal or external of HVE. During sensing, back ground noise signal from

    different system components can be mixed with PD signals from the examined

    component. Therefore, noise deduction obtained from the sensors signal generates

    important PD features in order for a more precise diagnosis. These features have its

    distinct characteristics so that it is possible to classify them by comparing with prior

    data from the laboratory or on-site. This process is known as pattern recognition or

    pattern classification. By doing so, the PD monitoring system finally estimates the

    possible fault type. Finally, all of this process can be used for life prediction

    modelling of the HVE. Based on all of the information from PD sensing to life

    prediction, a more precise PD monitoring system is possible. Moreover on-line PD

    monitoring based on the above diagram makes it possible for real-time monitoring

    data analysis, resulting in a robust CBM operation.

    1.4 Thesis Overview

    The thesis consists of 5 chapters. The first chapter will explain motivations and a

  • 8/11/2019 On Line PD Monitoting of Power System Components

    20/148

    1.5 The aim of the Thesis

    The objective of the thesis is be a holistic review of existent PD measurement,interpretation algorithms and applications for on-line monitoring of high voltage

    power system components from a theoretical and practical perspective. The aim is to

    not only collect the data related to PD monitoring system, but also categorization and

    discuss of each application and PD monitoring system is presented. In addition, the

    thesis clarifies the following questions regarding PD monitoring systems:

    1. What kinds of methods are currently used to monitor a PD signal in power system

    components?

    2. What kinds of sensors are currently used on different power system components to

    detect PD and its location?

    3. How can the PD signal extracted from a noisy environment for on-line PD

    monitoring?

    4. Based on different sensors, how can fault situation be defined according to the PD

    signal pattern?

  • 8/11/2019 On Line PD Monitoting of Power System Components

    21/148

    CHAPTER2

  • 8/11/2019 On Line PD Monitoting of Power System Components

    22/148

  • 8/11/2019 On Line PD Monitoting of Power System Components

    23/148

    impossible owing to inaccessibility to the PD spot inside of the test object. The simple

    equivalent capacitor arrangement of system layout so-called a-b-c model and

    measuring system is shown in Figure2.1.

    Figure. 2.1 Simple capacitive a-b-c model and measuring mechanism [9]

    aC = Capacitance of the test object which is not affected by any PD

    bC = Stray capacitance of the PD source

    cC = Internal capacitance of PD source

    As we can see, three capacitance values represent capacitance of the insulation

  • 8/11/2019 On Line PD Monitoting of Power System Components

    24/148

    Apparent charge [9, 10]

    Figure. 2.2 Apparent charge measurement equivalent circuit [9]

    1U = Applied test voltage

    2U =Voltage drop across the PD source

    3U =Voltage drop across the mR

  • 8/11/2019 On Line PD Monitoting of Power System Components

    25/148

    3 1( )

    a

    a m

    CU U

    C C (2.1)

    Simplification of the equation with the consideration thatmC is much higher than aC

    3 1m a aU C U C q (2.2)

    Taking into account thatbC aC , the equation can also be expressed as

    1 2a a bq U C U C (2.3)

    By multiply aC / aC , the final equation will be

    2 a b ba c

    a a

    U C C C q q

    C C (2.4)

    In other words, above equation describes that the discharge occurred at cC will causes

    a voltage drop as 1U which will be transmitted through bC to the capacitance aCby the

    ratio as bC / aC .Therefore the measureable charge ( aq ) is a certain portion of actual

    charge ( cq ) at the PD site due to the fact that bC / aC 1. We should note that the

  • 8/11/2019 On Line PD Monitoting of Power System Components

    26/148

    According to the IEC 60270, the relationship of frequency spectrum of PD and

    measuring frequency band was covered. Firstly, the integrated part of PD should be

    assumed as constant within measured frequency band width. Secondly, the upper and

    lower frequency band cut-off ( 1fand 2f ) should be lower than measured constant

    part of PD value. Lastly the recommended gain gap between frequency spectrum of

    PD and measuring frequency band should be less than 6dB. Recommended frequency

    band widths in IEC 60270 standard can be categorized wide and narrow bandmeasurement shown below.

    Wide band measurement

    Lower limit frequency: 30 kHz< 1f

  • 8/11/2019 On Line PD Monitoting of Power System Components

    27/148

    Figure. 2.4 Basic coupling mode in series with the coupling capacitor [11]

    Figure. 2.5 Basic coupling mode in series with the test object capacitor [11]

  • 8/11/2019 On Line PD Monitoting of Power System Components

    28/148

    Figure. 2.6 Polarity discrimination coupling mode [11]

    Figure. 2.7 Balanced coupling mode [10]

    Additionally, this coupling requires interrupting the grounding connection of the test

  • 8/11/2019 On Line PD Monitoting of Power System Components

    29/148

    Figure. 2.8 Coupling device described by IEC 60270 [9]

    k

    C = Coupling Capacitance

    aC = Test object virtual capacitance

    mR = Measuring resistor

    mL = Shunt inductor

    mC = Measuring capacitor

  • 8/11/2019 On Line PD Monitoting of Power System Components

    30/148

    of the PD instrument0

    ( )R . The relationship of the series capacitance of the calibrator

    ( 0C ), test object ( aC ), and coupling capacitor ( kC ) can be expressed according to theIEC 60270 as shown in below.

    0 0.1 ( )a kC C C (2.5)

    Commercially available calibrators inject a known pulse (0 0 0q C U ) with certain

    time intervals connected near the coupling device shown in Figure 2.10. This can alsoensure the connection of the whole measurement system. The following equation can

    simply explain how to calculate the calibration factor.

    0

    0

    a

    kq q

    R (2.6)

  • 8/11/2019 On Line PD Monitoting of Power System Components

    31/148

    power system components. The third version of IEC 60270 presents detailed

    information from a coupling device to the calibration method as seen above. Even

    though this method is vulnerable to noise and other interferences, the biggest

    advantage over unconventional PD measurement system is the availability of the

    estimated magnitude of PD.

    A recent paper [16] pointed out some fundamental limitations of the conventional

    method with three points; integration error in case of non-linear, possiblesuperposition error, calibration limits, and unknown attenuation of PD signal from PD

    spots to sensors. Those challenges tackle the advantages of the conventional method

    in terms of accuracy of the measurement system. Nevertheless, IEC 60270 has been

    widely used as an application for new power system components testing and

    commissioning, on-site measurement, and laboratory tests for periodic examination.For on-line application, calibration procedure and high signal to noise ratio makes it

    difficult to apply the IEC 60270 method. However transformer application such as

    multi-terminal measurements and GIS application for sensitivity verification have

    sometimes been combined with the unconventional method which will be covered in

  • 8/11/2019 On Line PD Monitoting of Power System Components

    32/148

    Unconventional PD detection methods [20]

    Electrical detection [21]:Electromagnetic measurement of PD consists of couplingdevices and data acquisition unit. The most suitable frequency band for application

    regarding each power system components are shown in Table 2.1.

    Cable Transformer GISRotating

    Machine

    HF (3 - 30MHz) O - - OVHF (30300MHz) O O O

    UHF (300M3GHz) O O -

    Table 2.1 Suitable frequency band according to system components (O=Good, =OK, -=NO)

    Appropriate sensors and its placement on test object detect electromagnetic signal.

    Detection of electromagnetic transient signal from PD occurrence is usually

    performed by capacitive or inductive sensors. More detailed information regarding

    system configuration, sensor type, and placement according to each system

    components is covered in chapter 4. The main advantage of this method is its

  • 8/11/2019 On Line PD Monitoting of Power System Components

    33/148

    Optical detection [25, 26]: Optical emission from PD can be detected by optical

    sensors. Unlike electrical signals from PD, optical signals largely depend on different

    factors such as insulation material, temperature, PD intensity and pressure. The

    spectrum of hydrogen or nitrogen depending on the surrounding material is the most

    dominant concerning the spectrum of PD. There are roughly two kind of optical PD

    detection techniques as a result of different kind of ionization, excitation and

    recombination processes during the discharge; direct detection of optical PD signal

    and detect of change of an optical beam. Detection of optical signal includes surface

    detection and the detection inside of the test object such as GIS and transformer. For

    cable application, corona emits the spectrum range around 280nm to 410nm at high

    voltage transmission line which can be detected by a UV-visible camera during the

    daytime. The rationale behind this is the ultra violet radiation ranging from 240nm to

    280nm tends to be absorbed by the ozone layer. The optical sensors transferring signal

    to the outside at photomultiplier, also can be placed inside the test object which is

    efficient for a light-tight GIS impulse voltage test. This impulse voltage test is not

    suitable for an electrical PD detection system. Another method called opto-acoustic

    measurement catches sonic or ultrasonic range acoustic emission caused by PD which

  • 8/11/2019 On Line PD Monitoting of Power System Components

    34/148

    Electrical Acoustical Optical Chemical

    Advantage

    Applicative forall kinds ofHVE

    Intensity,source, type,location of PDis assessable

    The mostsuitable forcontinuous on-line PDmonitoring

    High sensitivity

    Immunityagainstelectrical noise

    Very efficientfor localizationof PD

    Relatively lowcost

    Immunityagainstelectrical noise

    High sensitivityLocation of PD

    is assessable(insome case)

    Test is possiblefor impulsevoltagecondition

    Immunityagainstelectrical noise

    Easy tomeasure

    Provide criticalinformation forGo/No Godecision

    Disadvantage

    Highelectromagneticinterference

    Relativeexpensive cost

    Low signalintensity

    Not good forcontinuous PDmeasurement

    No informationaboutmagnitude ofPD

    No informationabout location,source,intensity, andtype of PD

    Possible

    Sensors

    CapacitiveInductive

    Piezo-electrictransducersCondensermicrophones

    Optical fibreUV detector

    photomultipliertube

    DGA SensorsSF6 Sensors

    Main

    applicative All HVETransformer Cable, GIS

    TransformerGIS

  • 8/11/2019 On Line PD Monitoting of Power System Components

    35/148

    Unconventional PD measurement system

    Unconventional PD measurement is much more suitable for on-site and on-line PDmeasurement in which the external interferences largely influence the measured

    signal. Especially electromagnetic wave and acoustic detection has been widely used

    in the field since these two methods simply provide sufficient information concerning

    the existence of PD and its possible location covering almost all kinds of power

    systems components. As seen below in the Table 2.3, possible on-line application ofdifferent system components can be realized by nonconventional PD measurement

    systems.

    Cable Transformer GISRotating

    Machine

    Acoustic O O O

    Electromagnetic O O O O

    Optical - - - -

    Chemical - O - -

    Table 2.3 Possible on-line PD detection techniques on power system components [37]

  • 8/11/2019 On Line PD Monitoting of Power System Components

    36/148

    object, test engineer and so on. In particular the nonconventional methods have not

    been supported by standard, resulting many different test set ups regarding higher

    frequency and other energy detection from PD occurrence. Standardization will

    bolster the analysis of the correlation of the measured quantities from both methods.

    On the other hand efforts have been made to combine the two techniques in order to

    overcome each drawback. In particular a combined solution is effectively applicative

    on transformer and GIS. This kind of integrated approach can detect PD occurrencewith accuracy and scalable quantity in a low noise environment. In this section,

    correlation of the two measuring systems and its combining approach will be covered.

    Conventional versus nonconventional PD monitoring

    Fundamentally, PD measurement systems according to IEC 60270 and

    nonconventional methods are measuring different quantities, apparent charge and

    electromagnetic waves or others, even if it comes from the same source. Some

    questions have arisen regarding the correlation between the two different methods and

    interpretation of results [21]. The general comparison is shown below in Table2. 4.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    37/148

    Measuring quantity Apparent charge

    Transient earth voltage or currentpulse ( Electromagnetic wave)Acoustic, Chemical by products,Optical spectrum

    Measuring systemCoupling device, transmissionsystem, measuring instrument

    Sensing components, transmissionpath, data acquisition unit

    Noise Level Relatively high Relatively low

    Application type

    Mostly Off-line (Laboratory, On-site)On-line (Transformer)

    Off-line and on-lineOn-line (Electrical, Chemical)

    Table 2.4 Comparison of conventional and nonconventional method

    *typical narrow band width for HF/VHF is 2MHz

    **Typical wide band range is 50MHz or higher

    ***Zero span mode for individual frequencies or for specific frequency range

    between 4 and 6MHz or higher

  • 8/11/2019 On Line PD Monitoting of Power System Components

    38/148

    Figure. 2.11 Example of combining PD measurement methods on Transformer [29]

    2.3 On-line VS Off-line PD measurement system

    In this thesis, on-line PD monitoringmeans the system with following requirements

    PD measurement while the test object is in normal operation

    Continuous PD monitoring (Trendable)

    Permanent installation of PD coupling device

  • 8/11/2019 On Line PD Monitoting of Power System Components

    39/148

    sometimes cannot be detected using the off-line method because it is carried out in

    different circumstance to that of real cases such as load condition, vibration,

    temperature, humidity and so on. That means the test object which passes for off-line

    PD test can have potential failure in the power grid. This method, moreover, is

    expensive due to outage during PD measurement.

    However off-line PD measurement usually has high sensitivity and accuracy because

    of relatively low back ground noise and is very suitable for new equipment qualitycontrol. For on-line PD measurement, on the contrary, the measurement is very

    realistic because it performed under the real circumstances. The cost is relatively less

    expensive and it is possible to have trendable data for the test object, meaning that the

    life cycle management can be possible with on-line PD monitoring. The main

    research ongoing in the on-line PD monitoring field concerns signal processing due tohigh noise combined with a true PD signal. However recent papers and commercially

    available on-line PD measurement systems ensures effective on-line PD measurement

    with appropriate signal processing techniques.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    40/148

    UHF/AE technique can determine the concrete status of the test object. However

    different measuring configurations of UHF/AE make it difficult to have strict linearity

    and correlation. In this sense, draft IEC 62478 can assist to clarify the promising

    UHF/AE detection configuration and make it more robust in the near future.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    41/148

    CHAPTER3

  • 8/11/2019 On Line PD Monitoting of Power System Components

    42/148

    3.1 Detectable PD signals

    Partial discharge is detectable in a different way due to the fact that it generatescertain reactions according to the insulation materials in the system components.

    Generated signals from PD are usually detectable in an electric, acoustic, chemical,

    and optical way [44]. Electrical and chemical signals are referred to for finding out

    PD occurrence in high voltage equipment, and acoustic signals are used to localize the

    spot where PD takes place. Depending on the characteristic of the power systemcomponents, appropriate signal detecting can differ. Nowadays, combining of the

    methods guarantees more accurate PD detection. In [45], a more physical approach to

    the PD mechanism is presented.

    3.1.1 Electrical signal

    PD occurrence in the power system equipment makes the electrical signal. That is

    because partial discharge brings about electron transfer in a short current impulse

    within nanoseconds [1]. As described in the Chapter 2, in order to detect electrical

  • 8/11/2019 On Line PD Monitoting of Power System Components

    43/148

    3.1.2 Acoustic signal

    Even though electrical signals are the obvious evidence of PD occurrence, acoustic

    signal generated from the mechanical wave of a small explosion around the spot

    where the PD takes place is widely used for PD monitoring [46]. The biggest benefit

    of acoustic signal is the immunity from electromagnetic interferences [47, 18].

    Moreover acoustic detection is not an intrusive method compared to other

    measurement types [46]. In addition, the acoustic signal detection method is favoured

    for localizing PD in the test object. By using several acoustic sensors on the object

    which have PD occurrences inside, the computation of travelling time difference from

    each sensor provide geometric information of PD location [48]. However even though

    acoustic signals represent is against electrical interferences, acoustic noise or

    mechanical vibration from other high voltage equipment can affect acoustic signal

    strength.

    3.1.3 Chemical signal

    Partial discharge also creates a chemical reaction with the insulation material. One

  • 8/11/2019 On Line PD Monitoting of Power System Components

    44/148

    Coupled Device (CCD) Cameras can detect optical signals with relatively higher

    sensitivity in air tight test objects such as GIS.

    3.2 Sensors

    In this section, the sensors used regarding PD detection are covered. Currently there

    are many sensors which have been used depending upon the measuring method andtest object. Since the sensor plays an essential role in PD measuring configuration,

    appropriate selection and its location can affect the measurement result significantly.

    The basic requirements of PD sensors are below [52]

    Be able to sense and record measuring quantities from PD source for a set of

    defined frequency bands

    Can differentiate between PD signal and background noises

    Small enough in order to be attached to the test object

    The sensors traditionally detect PD below 500kHz due to technical limits and lack of

  • 8/11/2019 On Line PD Monitoting of Power System Components

    45/148

    version of HFCT is commercially available as shown in Figure 3.1. The HFCT detect

    PD up to several hundred MHz.

    Figure. 3.1 Commercially available core closed and split type of HFCTs

    Rogowski coil [56, 57]:The Rogowski coil is a proper sensor for PD working on the

    inductive principle with frequency bandwidth between 1 to 4 MHz. The Rogowski

    coil has a structure of a circular plastic mold with a winding mounted for a uniformly

    distributed density of turn with frequency dependant characteristic. By mounting

  • 8/11/2019 On Line PD Monitoting of Power System Components

    46/148

    capacitors has to be designed in order to withstand 60 Hz high-voltages, and it should

    be manufactured to have low inductance in order to have good high-frequency

    response. These two considerations are the reason for the relatively high price

    compared to for example radio frequency current transformer (RFCT) type detector.

    On the other hand, the advantage is that the pulse signals are usually much larger

    because they can be placed closer to PD spots. The PD activity in each phase,

    moreover, can be determined.

    Figure. 3.2 Commercially available Epoxy-mica encapsulated couplers

  • 8/11/2019 On Line PD Monitoting of Power System Components

    47/148

    Currently Doble lemke (DN 50/80), and Omicron (UVS 610) uses this kind of sensors

    on their UHF PD measurement for power transformer. Externally mounted UHF

    sensors first developed as a GIS application and it has been widely used as

    transformer UHF detection as well [63]. Detailed information about various UHF

    antennas such as horn, loop, and, dipole type for GIS applications is described in [54].

    Directional coupler [21, 60, 64-65]:The directional coupler is a combination of a

    capacitive with an inductive sensor. It is possible to use two directional in a cablejoint. By doing so, it is possible to distinguish PD impulses coming from outside (left

    or right side) or inside the joint. In other cases, depending upon the direction of pulse,

    energy can be coupled to a different output port in case of special sensors with two

    outputs. The main application of this type of sensor is using a cable joint. For cable

    joint application, a directional coupler can achieve high sensitivity. Typical operating

    frequencies are usually from several MHz up to GHz.

    3.2.2 Non-electric sensors

    Fibre optic sensor:Detection of acoustic signal from a PD source can also be done

  • 8/11/2019 On Line PD Monitoting of Power System Components

    48/148

    by increasing positive hole density in a p-type semiconductor. This sensor is currently

    only used in an academic field but its use has been shown in some papers. However

    based on this sensor, off-line PD detection in GIS is possible.

    Piezoelectric transducers [72]: The sensor is typically operating in the frequency

    band in the 120160 kHz range. In order to minimize the varying response according

    to the electromagnetic fields, the transducer can be either a differential type utilizing

    two crystals or a shielded single crystal transducer with an integral pre-amplifiercircuit. Usually an integral pre-amplifier circuit type is the more common

    configuration due to high amplitude and low impedance output. Since the acoustic

    impedance of a sensing crystal differs from as that of the steel transformer wall, an

    efficient hard-epoxy resin material is used with thermal and electrical isolation

    characteristic. Commercially available acoustic detection for PD localization which is

    applicative for transformer has been successfully used.

    3.3 PD monitoring visualization

  • 8/11/2019 On Line PD Monitoting of Power System Components

    49/148

    .

    Figure. 3.3 PRPD patterns as pulses and pattern (PD-Smart)

  • 8/11/2019 On Line PD Monitoting of Power System Components

    50/148

    However, this PRPD pattern of each measurement cannot entail complete

    identification of fault type because it depends on the PD measurement unit, sensor,

    frequency band, test object and multiple causes of overlapping faults. Because of that,

    there are some cases the typical patterns of PRPD do not match the true cause of PD

    [76]. In order to increase accuracy of PRPD match with true fault causes, the same

    measuring configuration and reference of each test object are required. A more

    sophisticated display of PRPD in 3D in terms of PD amplitude, cycle number, and

    phase position is shown in [77]. Pattern analysis and recognition based on PRPD will

    be introduced in the on feature extraction and classification section.

    3.3.2 Time resolved method

    PD display based on measuring time can be called time resolved PD data shown in

    Figure 3.5. Since this visualization focuses on more on the timing of PD occurrence,

    time resolved data can provide information on the location of PD with several sensors

    placed at different spots rather than PD magnitude. In [78], time of flight calculation

    based on time resolved PD pattern at GIS is presented in detail in chapter 4. Other

  • 8/11/2019 On Line PD Monitoting of Power System Components

    51/148

    3.3.3 3-Phase Amplitude Relation Diagram (3 PARD)

    3-PARD, or a star diagram, is cross talk between more than one phase on each

    measurement [43, 81-83]. So called multi-terminal measurement, measuring 3 phases

    with three couplers, can acquire synchronous PD data for all three phases of the test

    object such as three phase transformer or GIS. This method make it possible to

    compare the magnitude of PD occurrence on each phases, helping locate PD source

    occurring in perhaps one of the three phases and eliminating external noise shown in

    the display. The 3-PARD is a plot with a 120 phase shift of the three phase axis

    shown in Figure 3.6. This method has been developed by the Technical University of

    Berlin.

    Figure. 3.5 3-PARD comparing PD magnitude on each phase [29]

  • 8/11/2019 On Line PD Monitoting of Power System Components

    52/148

    3.4.1 Noises in PD

    Detecting of a true PD signal from measured results is a matter of in-depth knowledge

    and incremented experience on measured signal and noise characteristic in different

    situations and test objects. Since PD activities in power equipment occur within less

    than a few hundred nanoseconds as fast rising time which is low level pulse

    depending on faults type of the test objects, the de-noising process can be achieved by

    understanding the noise characteristic and eliminating them from the true PD signal.

    Typical noise during PD measurement can be categorized [85, 86].

    Sinusoidal noise: This type of noise is the narrow band noise signal such as

    communication carrier signal from AM/FM modulation which can be removed by

    applying, for instance, a digital filter.

    Pulse type (repetitive or random) noise:This type of noise possibly comes frompower electronics, other switching operations or, Radio Frequency (RF) emissions

    from power equipment. Even though repetitive noise can be rejected by a gating

    circuit and other method which can detect periodic noise against PD signal, random

    pulse type noise is hardly eliminated.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    53/148

    Figure. 3.6 Principal of gating method for noise reduction

  • 8/11/2019 On Line PD Monitoting of Power System Components

    54/148

    Those two couplers detect signals at different spots with time difference for the same

    PD signal which can be from the test object side not from a grid. Thus, by comparison

    of pulse arrival time on two couplers, one can distinguish noise from the grid side.

    The basic scheme is shown in Figure 3.9 [1, 88].

    3.4.4 Digital filter method

    When PD is corrupted by noise caused by radio communication, a matched filter is a

    very well-suited as a solution. First of all, a matched filter can make it possible to

    maximize SNR of PD by suppressing noise. In addition, it can make accurate

    estimation on the time of arrival and magnitude of maximum PD pulse. The time of

    arrival of PD pulse and SNR are deeply related as those two variables are inversely

    proportional. Simply a matched filter uses a template which is a prediction of the

    shape and amplitude of a PD pulse. The coefficients should be determined in order to

    construct a specific matched filter for a specific measurement. One solution for this,

    for example for the cable case, is the injection of a known pulse and measuring its

    pulse propagation characteristic as impedance. By calculating time-of-arrival, the PD

  • 8/11/2019 On Line PD Monitoting of Power System Components

    55/148

    PD measurement, reducing noises and extracting a very small amount of data from

    actual measurement [96]. The basic steps of wavelet transform applied for noise

    reduction are described below.

    Decomposition: set a mother wavelet and a maximum decomposition level,

    computing the wavelet decomposition coefficients at each level from 1 to N.

    Thresholding: Compute threshold coefficient for each and apply threshold to the

    coefficients at each level

    Reconstruction:Reconstruct the signal with the modified coefficients from 1 to N

    3.4.6 Statistical method

    Statistical methods for extracting PD features are based on PRPD pattern [73, 97-98].By applying statistical computation on PRPD patterns, different distributions can be

    characterized as statistical parameters. The following distribution functions are used.

    Skewness: shows the asymmetry or degree of tilt of the data of the distribution

    compared to a normal distribution.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    56/148

    Number of peaks: represents the distribution with single peak or more. The peak of

    the distribution can be defined as:

    1 1

    1 1

    0, 0i i

    i i

    dy dy

    dx dx (3.3)

    Where 1

    1

    i

    i

    dy

    dxis the differential coefficient before and after the peak of the distribution.

    Cross-correlation factor: shows correlation of the distribution shape between

    positive and negative cycles of the distribution.

    2 2 2 2

    /

    [ ( ) / ] [ ( ) / ]

    i i i i

    i i i i

    x y x y ncc

    x x n y y n (3.4)

    where ix is the average discharge magnitude of positive half cycle and iy is the that

    of negative cycle. When cc is close to zero, it means the shape of positive and

    negative cycles are the same, otherwise it will be asymmetrical.

    Asymmetry: shows the comparison of the mean level of the positive and negative

    half of the voltage cycle.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    57/148

    3.4.7 PD pulse shape method

    This method is based on time resolved PD data for instance, apparent charge and

    voltage magnitude within a certain time interval due to the fact that different PD

    source can generate different PD pulse shape [73, 99]. The features extracted on an

    one to one basis using single discharge source. The Following parameters can be used

    Pulse rise time:time required to rise from 10% to 90% levels of the peak value.

    Pulse decay time:time required to decay from 90% to 10% levels of the peak value.

    Pulse width:time interval between 50% levels on both sides of the peak value.

    Area under pulse:area enclosed by the q-t curve in the time interval for 10% levels

    in the rising and falling segments.

    3.5PD pattern classification

    Many researchers and theses have studied the pattern classification of PD. Therefore

    many different methods have been introduced in order to understand and trace of

    certain PD pattern such as artificial neural network, fuzzy logic, genetic algorism, and

  • 8/11/2019 On Line PD Monitoting of Power System Components

    58/148

    The optimal number of neighbours depends on the data. Thus if there is new data

    coming to the feature space, it is classified by major voting of k-number closest

    neighbours of the new data spot. This also can be a drawback because certain types of

    classes with the more frequent examples tend to dominate and are highly possible to

    be selected. In order to overcome this problem, the class should be weighted by

    experts or based on experience. The mathematical explanation is in [103]. The

    advantage of this classification is easy to update new data to reference and, it is

    simple to implement because it do not require training. However if redundant features

    concerning the classification are included, possible errors can occur [104]. Therefore

    careful selection of the feature is of importance.

    3.5.2 Neural Network (NN)

    Artificial neural network has been applied for PD classification [73, 97, 105-108].

    The basic idea of NN is based on biological neural functions taken from brain-like

    problem solving. The basic structure of NN consists of three mutually connected

    different types of layer, an input layer, hidden layers, and output layer shown in

  • 8/11/2019 On Line PD Monitoting of Power System Components

    59/148

    classification. Details of both methods are presented in the above references.

    Although NN is a very efficient tool for PD pattern classification especially due to the

    fact that it does not requires any assumption the PD data structure, it has several

    drawbacks including; dependence of convergence criteria upon learning coefficient

    such as the number of layers, learning time; and it is also difficult to include new

    features which requires retraining.

    3.5.3 Support Vector Machine (SVM)

    Support vector machine is one of the most promising techniques works by using

    outstanding learning algorithms especially in power systems such as load forecasting,

    power stability, and fault location detection [100, 109-110]. The main idea of SVM is

    to calculate the optimal hyperplane separating two classes. SVM uses the so-called

    non-linear kernel trick. SVM can find the solution of non-linearly separable condition

    using an implicit mapping technique into a high dimensional dot-product space called

    the feature space through the use of the kernel trick. A detailed explanation of the

    kernel method is shown in the above references. Despite the sophisticated procedure

  • 8/11/2019 On Line PD Monitoting of Power System Components

    60/148

    3.5.4 Pulse Sequence Analysis (PSA)

    Pulse Sequence Analysis (PSA) proposed by Martin Hoof and Rainer Patsch in 1990sis one of the most popular techniques for visualization of PD pattern classification

    [111-113]. The idea of this method is that two consecutive pulses caused by PD

    activities have a strong relationship. This means that the previous PD pulse has an

    impact on the condition of next pulse. Therefore analysis of the relationship of

    continuous pulses of voltage change due to the corresponding change of the localelectric field at the PD spot is an important factor which can investigate correlations

    between consecutive pulses as shown in Figure 3.12.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    61/148

    Figure. 3.123 Example of PSA in GIS; surface and corona discharge [113]

    The advantage of PSA is its clear differences between certain PD patterns due to the

    physical characteristics of PD activities according to the source of PD. However if the

    voltage differences of continuous PD activities cannot be defined from measurement,

    PSA is hard to apply

    3.6Signal processing of PD signal

    Since measured PD signal has a very low magnitude happening with nano-second

  • 8/11/2019 On Line PD Monitoting of Power System Components

    62/148

    CHAPTER4

  • 8/11/2019 On Line PD Monitoting of Power System Components

    63/148

    4.1.1 Transformer in power system

    The transformer is one of the most complicated structured components in the powersystem. Normally most transformers operate efficiently for between 20-35 years,

    which can be extended with proper maintenance [114]. Moreover, even though the

    failure rate is quite low about 0.2-2% a year [115], it usually causes cascading faults

    on different system components. Therefore, appropriate maintenance based

    monitoring while in operation is the key point for preventing transformer failure.

    Transformer insulations and its characteristics are also a bit complicated compared to

    that of other components. The most common insulation material in transformer is

    mineral oil which is being replaced by environmentally friendly oil and cellulose

    [116]. In [33], failure rates according to the transformer parts are tap changer (41%),

    windings (19%), tank and oil (13%), terminal (12%) and so forth. Another statistical

    survey for transformer rate is shown in [117]

    Transformer structure and failure rate

  • 8/11/2019 On Line PD Monitoting of Power System Components

    64/148

    Continuous PD monitoring on a transformer

    According to the CIGRE data [117, 118], the tap changer has the highest possibility of

    failure and then leakage, winding etc. That means appropriate healthy monitoring of

    transformer can prevent possible failure beforehand. One recent paper demonstrates

    on load tap changer monitoring using a continuous DGA method [119]. When it

    comes to PD monitoring on transformer, it can be categorized as electrical, acoustical,

    and chemical detection [44]. Regarding the electrical signal detection method, both

    IEC 60270 and UHF detection is widely used. Due to the complexity in transformer

    and its bulky volume, electrical sensors can be mounted outside on a bushing (IEC

    60270) or in side of the transformer using the oil drain valve (UHF). For locating PD

    course inside of the transformer, the acoustic emission method is used to calculate the

    time difference between different sensor placements [120, 121]. Chemical detection

    has been widely used in a periodical way with techniques such as DGA or Furan

    analysis.

    4.1.2 PD types in Transformer

    In some papers [4, 23, 122], there are different types of PD in the transformer which

  • 8/11/2019 On Line PD Monitoting of Power System Components

    65/148

    coupling. The main reason behind this discharge is a bad earth connection in a

    transformer

    4.1.3 Different diagnosis and monitoring techniques on transformer

    Among many monitoring techniques, this section only includes the on-line applicative

    monitoring method and compatible with continuous PD monitoring on powertransformer. In this section, monitoring techniques are categorized as oil testing,

    electrical, mechanical, and thermal monitoring of transformer. In [123-125], more

    detailed transformer diagnosis and monitoring techniques are covered

    Oil testing

    Oil is one of the widely used insulation materials for transformer. An Oil test is

    carried out by analyzing gases produced by local thermal stress or partial discharge

    taking place in the insulation liquid during abnormal operation. Therefore, gas

  • 8/11/2019 On Line PD Monitoting of Power System Components

    66/148

    MVA rating transformers and a portable detector is not so precise compared to that of

    one in a laboratory. However there have been many studies on this method including

    combining artificial neural network and expert knowledge [126].

    Furan Analysis and Degree of Polymerization (DP)

    When the paper insulation in transformer lose the insulation strength, furanic

    compounds that are by-products from paper insulation material appear in the oil,

    which can be analyzed and used for paper aging prediction and DP. 2-furaldehyde is

    considered the main product of aging, initiated by 5- furaldehyde in the early stages

    [128]. Furan analysis is applied in the case of high level of thermal stress,

    overloading, detection of high levels Carboxide, or sudden changes in oil color and

    moisture content rates in the oil [114]. Life estimation of transformer according to the

    DP is shown in [129]. The Constant K is defined as

    ( 237)

    E

    R Tk Ae (4.1)

  • 8/11/2019 On Line PD Monitoting of Power System Components

    67/148

    13600

    ( 237 )0.004

    =Estimated life of the transformer Te

    A

    (4.3)

    Thermal monitoring

    Thermal monitoring is a widely used method and has possible on-line applications.

    High temperature means abnormal condition in any parts of a transformer losing

    electrical dielectric strength if the thermal continues without any maintenance or

    appropriate remedy actions. Usually thermal spots indicate possible faults and

    insulation failures caused by overloading or local overheating which can accelerate

    insulation aging rapidly. Because the transformer is complex equipment which has

    non-linear characteristics with different components such as winding, load tap

    changer, and core, thermal monitoring are not so precise to pinpoint the exact failure

    spots which may be inaccessible to an external probe [116]. Infrared scanning check

    of the external temperature on the transformer is now available [114]. One of the

    disadvantages is that this method costs a lot in order to sense temperature directly

    using fibre optic [116, 2]

  • 8/11/2019 On Line PD Monitoting of Power System Components

    68/148

  • 8/11/2019 On Line PD Monitoting of Power System Components

    69/148

    noise, appropriate signal processing techniques will be required for continuous on-site

    PD monitoring.

    Figure. 4.1 IEC 60270 recommendation for PD monitoring system on bushing

    aC =The test object capacitance

    1C =The HV capacitance of the bushing

    2C = The LV capacitance of the bushing

  • 8/11/2019 On Line PD Monitoting of Power System Components

    70/148

    Figure. 4.2 Drain valve type UHF sensor [43, 136]

    Figure. 4.3 UHF dielectric window type [137]

  • 8/11/2019 On Line PD Monitoting of Power System Components

    71/148

    In Figure 4.4, possible sensor place using Cartesian coordinates is shown. The biggest

    problem of the AE detection method for localizing the PD source in the transformer is

    its signal sensitivity. This method should measure acoustic signal at the same time

    with at least 3 or 4 different sensors in different positions. In [121], detailed

    mathematical explanations and possible signal processing techniques are covered.

    4.1.5 Available products for on-line PD monitoring of transformer

    Doble Lemke

    Doble Lemke GmbH uses a conventional and unconventional method for on-line PD

    monitoring of the transformer. In conventional PD monitoring, tap bushing coupling

    with a low voltage capacitor is used as a sensor. This method is also applicative for

    multi terminal measurement analyzed by a 3-PARD diagram eliminating noises and

    comparing each phase. For the noise reduction, gating from a gate sensor and the

    winding technique for phase-locked noise is used. In unconventional PD monitoring,

    oil drain valve type sensor in the UHF (300 MHz-1 GHz) band or a UHF tap hatch

  • 8/11/2019 On Line PD Monitoting of Power System Components

    72/148

  • 8/11/2019 On Line PD Monitoting of Power System Components

    73/148

    4.1.6 Summary and Conclusion

    Since transformer is the most intricate power system component, there are many

    different ways or monitoring techniques for preventing possible faults. As some

    companies have already provided on-line PD monitoring system on power

    transformer for a couple of years, one can infer the fact that on-line PD monitoring of

    transformer will be widely used in the very near future. Especially transformer

    application PD monitoring techniques can be combined with other chemical,

    mechanical or thermal monitoring with the other methods mentioned in this section.

    On-line PD monitoring on the transformer focuses preliminary on PD magnitude

    (peak value) and source location. Regardless of the apparent charge or UHF

    measurement, changing or increasing of PD magnitude inside the transformer means

    the fact that the transformer needs a more specific inspection or to be repaired.However, for the purpose of on-line monitoring, the UHF method is more reliable due

    to the strong resistance to back ground noise. For the localizing of the PD source,

    acoustic emission detection technique has the key solution of locating PD source

    inside the transformer as highlighted in many papers.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    74/148

    been widely used in the laboratory, on-site as the form of on-line or off-line

    monitoring. Especially after installation of the cable system in the power system,

    detecting faulty connection by different PD monitoring methods such as Damped AC

    (DAC), Very Low Frequency (VLF) for example have been gaining its reputation.

    Therefore, in this section, all kinds of PD monitoring techniques in cable will be

    covered with detailed information regarding on-line PD monitoring in the cable

    system as well as its available products in the market

    4.2.1 Cable system in power system

    Cable network systems in the power system are one of the most important part but

    also the part most vulnerable to failure. Cable network can be categorized as Extra

    High Voltage (EHV), High voltage (HV), Medium Voltage (MV) and Low Voltage

    (LV) networks. The failure rate of the cable system is more frequent for lower voltage

    networks, meaning LV networks have the greatest outage time of all network. More

    than half of cable failure stems from electrical reason and the rest of them are due to

    external non-electrical inference [132] In particular in MV networks the causes of

  • 8/11/2019 On Line PD Monitoting of Power System Components

    75/148

    Figure. 4.5 XLPE cable structure [142]

    Components Description

  • 8/11/2019 On Line PD Monitoting of Power System Components

    76/148

    Continuous PD monitoring on cable network

    Traditionally, PD monitoring on cables has been widely used due to its effectiveness

    in CBM based monitoring and in localizing of the faults area. Especially for PD

    monitoring of cables, standard procedures such as Very Low Frequency (VLF),

    Damped AC (DAC), Alternative Current (AC) or Direct Current (DC) testing are

    popular due to the fact that they can verify possible faults areas of joint and

    termination after assembling by detecting and localizing PD in the cable. However,

    for the purpose of on-line monitoring, high attenuation of the PD signal along the long

    cable line makes it difficult to pick the exact PD and its location. Nowadays on-line

    PD monitoring of the cable has been used by sensing the PD signal with HFCT,

    capacitive coupling sensors, and so on. More detail will be covered up in the coming

    section.

    4.2.2 PD types in cable system

    PD occurrence in the cable system can be divided into an internal, surface, and

  • 8/11/2019 On Line PD Monitoting of Power System Components

    77/148

    Corona:PD occurs in open air around the cable.

    4.2.3 Different diagnosis and monitoring techniques on cables

    There are many ways to monitor cables in a laboratory, on-site, or with on/off-line

    methods. After a brief explanation of different monitoring techniques used on cable

    networks, this section focuses on electrical, especially partial discharge method. Aswell as methods presented here, there are also destructive methods such as Cable

    sampling, lead sheath analysis, and paper analysis [147].

    Tangent Delta (Loss angle, or Dissipation Factor testing) Measurement

    This method provides information regarding the aging of a cable by determining the

    loss factor due to the tangent delta value which is related to the composition of the

    connection, the trajectory, and the actual cable temperature. In perfect conditions, a

    cable has capacitive characteristics maintaining the phase difference between voltage

    and current at 90 degree. However, if there are defects in cable, the angle between

  • 8/11/2019 On Line PD Monitoting of Power System Components

    78/148

    appropriate temperature sensors. Semiconductor type sensor or optical fibre is popular

    for continuous temperature monitoring of cables. The advantage of this monitoring is

    to have real-time thermal behaviour of the cable that it is possible to use for thermal

    rating re-assessment. However almost all cable systems are in operation practically at

    low load condition for most of their service time, making it impossible to calculate

    effective thermal resistivity of the cable. Therefore, temperature monitoring on a

    cable should focus on a particular time and section of the cable.

    Partial discharge monitoring

    Even though thermal stress has a significant impact on the aging mechanism of the

    cable, electrical stress is prominent cause of aging. PD monitoring of the cable is the

    most effective method that is able to monitor electrical aging [153]. For localization

    of PD, Time Domain Reflectometry (TDR) which uses the reflection of pulse signal at

    the cable termination [154, 155] has been used. PD monitoring of the cable system

    can be clearly categorized into the off-line and on-line method. Regarding the off-line

    method, it has been widely used with an extensive voltage withstand test in order to

  • 8/11/2019 On Line PD Monitoting of Power System Components

    79/148

    On-line monitoring Off-line monitoring

    Advantage

    Can be performed while cable is inoperation

    EconomicalReal operation condition can be taken

    into account.

    Proven technology for on-site,laboratory test, and commissioning

    High sensitivityCalibration possible

    Disadvantage

    Low sensitivityComplicated data analysis is requiredInsulated earthing ground is required

    Out of connection is requiredRelatively bulky equipment requiredOutage costPD occurrence can be differ compared

    to its operation at service voltageOverall condition during testing

    (Temperature, humidity, vibration)can differ from operation condition

    Table 4.3 On-line versus Off-line PD monitoring on Cable [157, 158]

    b. On-line PD monitoring

    An on-line cable PD monitoring technique has proven its efficiency recently. As

    mentioned above, on-line PD monitoring on the cable network has many advantages

  • 8/11/2019 On Line PD Monitoting of Power System Components

    80/148

    (FTRC) and, Inductively Turned Resonant Circuit (ITRC) with the following resonant

    equation (4.4) in cable.

    1

    (2 )F

    LC (4.4)

    L= test inductance (or external inductor)

    C= cable capacitance

    The FTRC method uses power electronics converter generating harmonics and noises

    in the test system. Therefore appropriate signal processing techniques are required.

    However, there is no moving part included in this method. On the other hand, because

    ITRC usually use auto transformer, there are no such electronic pulse noises.

    Moreover voltage can increase smoothly which makes it easier to reach the PD

    inception voltage. The drawback of ITRC is its moving components which should be

    maintained periodically.

    Damped AC (DAC) voltage method:This method consists of a direct voltage source,

  • 8/11/2019 On Line PD Monitoting of Power System Components

    81/148

    Advantages of this method are its simplicity, lightweight and cost effectiveness with

    low power required

    Impulse voltage method:Impulse voltage with a very fast rate of rise and decay rate

    similar to power frequency can be applied for on-site tests. This method has its

    strength owing to lightweight equipment. Disadvantages of this method are hard to

    determine the inception voltage of PD, high attenuation along the long cable length,

    distance dependent test results, and difficulty to find correlation between routinefactory and on-site test regarding partial discharge values.

    4.2.4 On-line PD monitoring on cable

    IEC 60270 method is not appropriately applicative for on-line PD monitoring on

    cables. Usually HF or UHF detection for gaining high signal to noise ratio (SNR) is

    an attractive method for this purpose [163-169]. Since cable terminal and joint is the

    part of cable most vulnerable to failure, on-line PD monitoring on cable accessories is

    important for cable monitoring.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    82/148

    Figure. 4.7 HFCT coupling application at the cable termination [168]

    In Figure 4.7 HFCT in a slightly different location at the cable terminal is shown.According to the availability, the coupling spot can be adjustable. In order to localize

    the PD source in the cable system, dual sensor techniques (installing two sensors at

    each end of cable or cable joint) are required. Because of strong attenuation along the

    cable, PD localization requires more engineering techniques such as the pulse

  • 8/11/2019 On Line PD Monitoting of Power System Components

    83/148

    Emerson

    Their approach for online cable PD monitoring combines Tangent Delta testing, off-

    line method with VLF PD monitoring, and the ultrasonic method. RF embedded noise

    reduction can eliminate noise from PD with RFCT as a sensor. Regarding localization

    of the PD source, they can make it possible to have about 1 % accuracy in up to 3

    miles of cable length, which is an application for XLPE, EPR, PILC and CLX

    Armored cable types

    HVPD

    HVPD uses HFCT attached around the earth connections and TEV attached

    magnetically to the outside of metal-clad switchgear sensor which is applicable for

    Polymeric (XLPE, PVC), Paper (PILC, MIND), Rubber (EPR), both 3-Core and

    Single-Core Cables, and 'Mixed' cables with transition joints. Two cable ends attached

    sensors are monitored for PD localization using a pulse injection method which is

    successfully performed for up to 5 km on MV cable

  • 8/11/2019 On Line PD Monitoting of Power System Components

    84/148

    EPR). 3D visualization of PD in the cable moreover makes it possible to check PD

    occurrence according to the cable length, time and intensity.

    Power PD

    Power PD uses HFCT as a sensor on shield ground cables which can be shown as a

    PRPD or 3D graph.

    Techimp

    Techimp uses HFCT sensors, and FMC (Flexible Magnetic Coupler) sensors directly

    at the two terminations of the cable. In long cables, the installations can be performed

    at the middle of cable. For localization of a PD source, they analyze Amplitude/

    Frequency characteristics of PD, TDM method, and Arrival Time Analysis with GPS

    (Global Positioning System). Moreover this can be connected to a Ethernet network,

    and controlled from a remote location.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    85/148

    thus the higher frequency pulses related to PD activity is only detected near the PD

    source.

    The most appropriate sensor selection for cable case is capacitive coupling and HFCT

    according to the application. Since cable accessories, joint and terminal, are the

    biggest cause of possible faults, on-line PD monitoring near joint or terminal of cable

    has been widely used. However, using two HFCT at each end of cable with PD

    localizing techniques by TDR or pulse injection method has been proven its efficiencyon on-line PD monitoring for long length cable.

    4.3 Rotating Machine

    Rotating machine such as synchronous generator, induction motors and DC or AC

    machines is one of the most important parts of the power system. The main reasons of

    faults in rotating machines are thermal, electrical and, mechanical stress. Continuous

    PD monitoring of rotating machine has been considered as efficient diagnostic tool for

    several decades [170 171] In this section on line PD monitoring of rotating machine

  • 8/11/2019 On Line PD Monitoting of Power System Components

    86/148

  • 8/11/2019 On Line PD Monitoting of Power System Components

    87/148

    rate comes from persistent overloading (4.2%), and normal deterioration (26.4%). The

    main failed components on RM are stator ground insulation (23%), turn insulation

    (4%), and others (8%) [175,176]. More detailed information regarding RM failure is

    in [177]. Therefore PD monitoring stator windings has normally been performed in

    many industries and utilities. Continuous PD monitoring provide several advantages

    for rotating machines; (i) provides warning for personnel, and (ii) solves the problem

    of difficulty for RM testing under the same condition by supplying continuous

    trendable data [174]. Moreover, other stress such as thermal or mechanical vibration

    on RM can create a void or cracks which are detectable in the form of PD, expressed

    as a symptom of stator winding failure [178].

    4.3.2 PD types in rotating machines

    The most popular sensing place for PD monitoring on RM is at the machine terminal.

    However PD can occur inside of RM usually from stator winding which can be

    attenuated or distorted during propagation from the PD source to the measuring place.

    Therefore analysis of the magnitude and wave form of PD sometime provides

  • 8/11/2019 On Line PD Monitoting of Power System Components

    88/148

    delaminated at the copper conductor due to the thermal overstressing [181]. This

    depends on the thermal condition of RM [182]

    Endwinding Discharge: This usually occurs in the overhang region when a

    contamination of the conductor takes place owing to mechanical corrosion or for

    particular RM, where bar coils belonging to different phases locate in the same slot

    [183]. Therefore the reason of this discharge results from phase to phase voltage with

    not enough room between coils of different phases or partly conductive contamination[76]. According to [182], this type of PD usually has a high magnitude in negative

    cycle and it is temperature dependant.

    4.3.3 Different diagnosis and monitoring techniques on rotating machines

    In [184], an intensive review of almost all possible monitoring techniques with regard

    to RM is covered in detail. Largely, there are thermal, chemical, mechanical and,

    electrical monitoring techniques have been widely used.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    89/148

    Use thermal imaging, to find a hot spot in the RM, which has been used on a

    lot of other HVE.

    Evaluate distributed temperatures of RM or bulk temperatures of the coolant

    fluid.

    Chemical monitoringHigh thermal stresses in RM generate chemical reactions in the insulation material,

    usually starting from 120 Celsius by emitting hydrocarbons and ethylene. However,

    this method tends to be expensive to perform and is limited by its accuracy.

    Electrical monitoring [185]

    With regard to electrical monitoring on RM, methods include the insulation resistance

    and polarization index, partial discharge, Capacitance and Dissipation Factor, Motor

    Current Spectral Analysis (MCSA), High Voltage DC Ramp and Power Monitoring

  • 8/11/2019 On Line PD Monitoting of Power System Components

    90/148

    DC due to the cancellation of AC components from different phases if the flux and

    torque is in a normal condition [186].

    Motor Current Spectrum Analysis (MCSA) monitors stator current and its

    spectrum. This can be easily implemented with Current Transformer (CT) around

    supply cables. Because its accurate analysis and easy installation, this method has

    been widely used.

    Partial Dischargecan be applied in two different ways, on-line and off-line. In the

    case of off-line, just like off-line PD monitoring after laying the cable case, high AC

    test voltage is fed into the cable and PD occurrences are recorded. Off- line PD

    monitoring on RM which are not in operation are analysed without any operating

    stress such as thermal or mechanical vibration, and other possible stresses while the

    machine is in the grid. This information can mislead or failure to notice possible faults

    in RM during operational condition. However, on-line PD monitoring on RM can

    provide realistic data under the same circumstances of real conditions and situations

    of load variation. In particular, on-line PD monitoring on RM largely depends on

    operation temperature and load condition. One limitation of PD monitoring on RM is

  • 8/11/2019 On Line PD Monitoting of Power System Components

    91/148

    measurement sometimes accompanies its temperature and load record, for example, a

    full load at a moderate temperature.

    Figure. 4.8 Capacitive coupling method on RM [110]

    For noise reduction, two sensors installed at different spots in one phase terminal canbe used. The basis of this method is the arrival time difference between two sensors.

    By doing so, sensors can recognize the PD signal source from an external or internal

    spot.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    92/148

  • 8/11/2019 On Line PD Monitoting of Power System Components

    93/148

    Power Diagnostix GmbH

    Power Diagnostix GmbH installs a capacitive coupler close to windings such as a bus

    bar at each phase if necessary especially for large machines. Global intranet access

    and visualization of the monitoring data can be connected to this installation.

    PDtech (Qualitrol Company LLC)

    PDtech uses capacitive couplings near the generator terminal and HFCT around the

    cable which is available for all HV-machines rated current and voltage. This

    application provides an alarm and is compatible with SCADA systems.

    PowerPD

    They capture PD signals from generators and motors by coupling in each phase using

    a Capacitor Coupler. This application has an early warning system and scans between

    200 KHz-300 MHz.

    T hi

  • 8/11/2019 On Line PD Monitoting of Power System Components

    94/148

    vulnerability to faults, the PD signal from stator winding can be distorted or

    attenuated at the sensing spot.

    For online PD applications, capacitive sensors at the generator terminal, Rogowski

    coils and HFCT at the end cable connection spot, or directional electromagnetic

    coupler at stator winding slot wedge has proven efficient in research and available

    products in the market. VHF is the most appropriate monitoring frequency range. In

    order to reduce noise and locate the PD source, two sensors at one phase different

    spots, pulse shape analysis with 3 PARD diagram can be used.

    4.4 GIS (Gas Insulated System)

    GIS has been widely used for HV insulation since 1960. Due to its high insulationcharacteristic and break down voltage with injected gas- usually SF_6 compared to air,

    GIS makes it possible to construct the substation in a more compact and reliable way

    [192]. PD detection techniques in GIS are conventional, unconventional or combined

    both covered in a recent paper [193]. Usually the sensor should be located within an

    i t di t th t th d t t PD i l f th GIS UHF

  • 8/11/2019 On Line PD Monitoting of Power System Components

    95/148

    Gas

    Usually Use as gas insulation material or Mixture with [195]High pressure (4 bar) and low pressure (1.2bar)

    High pressure has better dielectric characteristics

    Conductor system

    Aluminum tubes according to the rated voltage and current, its thickness anddiameter can be specified

    Silver plated contact surface

    Solid Spacer

    Physical support of high-voltage conductors and mechanical operation ofswitchgear

    Cause electrical field distortion within GIS

    Table 4.5 GIS's insulation and enclosure components and material [141]

    The inside components of the GIS usually vary between types, such as the circuit

    breaker, disconnection switch, current transformer, voltage transformer, bus bar and

    so forth [141]. Therefore, different components can cause different failures inside the

    GIS. In [196], different analysis of GIS failures was conducted based on thirty years

    failure history from five German utilities and 7 companies. Depending on the location

    of GIS, the most common failures occurred in the switching compartment (40.4%),

    Voltage Transformer (VT), Surge Arrestors (SA) and bushing compartment (17.3%)

  • 8/11/2019 On Line PD Monitoting of Power System Components

    96/148

    Electromagnetic Wave (TEM). This wave cannot pass through the opened contact

    switching compartment. At higher power frequencies, however, electric and magnetic

    fields of the transmitting waves are not entirely transverse to the direction of wave

    propagation, known as Transverse Electric (TE), Transverse Magnetic (TM). The

    waves have short wave lengths compared to TEM, and either electric or magnetic

    fields can have the components transmitting at the same direction toward wave

    propagation direction, which can pass though the opened contact in GIS. The cut-off

    frequency between TEM and TE, TM can be defined by the following equation

    ( )c a b (4.5)

    Where c = cut-off wave length, a, b= outer and inner radius of the conductor and

    chamber respectively. For example in the case of 420kV,cis about 1.2m so that the

    cut-off frequency can be approximately 250MHz. This TEM and TE, TM can affect

    the detectable frequency range for on-line PD monitoring on GIS. Appendix A in

    [200], detail mathematical frame work of TEM, TE, and TM is covered.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    97/148

    Free moving particle: This is a particle freely moving inside the GIS. Poor

    manufacture processes and contact between different electrodes inside GIS can cause

    free moving particles. Even though free moving particles have been found to be

    harmless compared, for example, to floating electrodes, continuous PD occurrence

    from free moving particle can result in SF_6 decomposition, and eventually

    breakdown in the GIS [203]. This was pointed out as the main cause of failure in a

    GIS [204]

    Particles fixed on the spacer or insulation surface:This case indicates that certain

    free moving particles can be fixed on the resin spacer or other insulation surface

    inside the GIS. Fixed particles can generate corona type PD or breakdown in the gas-

    solid interface by accelerating electric field distribution strength at that location [205].

    4.4.3 Different diagnosis and monitoring techniques on GIS

    According to [206], indicative methods to find possible faults are PD diagnostic

    (22.4%), Visual Inspection of switchgear enclosure and surrounding area (18.1%),

    and Thermo-graphic Inspection (12%). Therefore PD monitoring and visual

  • 8/11/2019 On Line PD Monitoting of Power System Components

    98/148

    operation of GIS. The UHF/AE PD detection method has been regarded as the most

    promising PD monitoring technique for GIS. Detailed techniques in terms of on-line

    monitoring are covered in this chapter.

    High frequency current detection [209]:Current pulses caused by discharge in GIS

    can be detected using by capacitor or charged conductor and intermediary insulator

    equipped with a receiver electrode immersed in resin. This method has been used and

    is a possible application for permanent monitoring.

    SF6 quality assessment [209]: Impurities of GIS cause a significant impact on

    insulation failure. Therefore, appropriate monitoring for SF6 quality has been used

    periodically in order to decide dielectric strength. Gas analysis performed by sampling

    for gas-chromatography or infer-red spectrograph is a proven method. Air contents

    measurement with a portable oxygen detector can give an immediate indication of air

    contents in the GIS. Lastly continuous or periodic moisture measurement is efficient

    as well. Because this method is relatively expensive and redundant, periodic detection

    for the first month of operation is sufficient in order to ensure SF6 filling condition in

    the GIS.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    99/148

    Unconventional method [196, 210]

    Unconventional on-line PD monitoring on GIS uses VHF/UHF detection and the AE

    detection method. As mentioned above, since TEM is highly attenuated at higher

    frequencies, TEM mode in GIS is strong in VHF (40 to 300 MHz). Even though the

    VHF method has many similarities with UHF in the sense that they can provide the

    location of PD, the most significant disadvantage of VHF is interference similar to

    IEC method. However, VHF method sometimes makes it possible to be calibrated by

    injecting a known pulse. On the other hand, the UHF (300 to 3 GHz) method can

    detect TE and TM which are generated by a very fast rising time PD current within

    ten picoseconds. In addition UHF has a similar sensitivity to the IEC method due to

    its good immunity to noise. The rule of thumb regarding distance between UHF

    sensors should be within 20m. The most widely used sensor types are in Figure 4.10.

  • 8/11/2019 On Line PD Monitoting of Power System Components

    100/148

    PD localization [135]

    PD source localization inside the GIS simply uses time-of-flight measurement with

    two different sensors. Electric PD signal inside the GIS can propagate two UHF PDsensors at different time intervals according to the sensor placement.

    Figure. 4.11 Time of flight method for PD localization in GIS [135]

    In Figure 4.11, the simple scheme of PD localization is shown. If there are two

    different UHF sensors and the PD occurs between them, the time domain PD location

    can be calculated as below in a situation when the time of flight at two different UHF

    sensors is known.

  • 8/11/2019 On Line PD Monitoting of Power System Compon